7434099 DrawingAsOne SIGNED.pdf
PDF 209 KB Posted
- Attached to
- Repairs to Room 107B, B4066 for KC130 OTA #7
- Solicitation number
- N400857434099
About this file
This document is an electrical plan and details drawing for repairs to Building 4305A, Room 107B at Marine Corps Air Station Cherry Point, North Carolina. The drawing, numbered E-101, provides a detailed electrical schematic for modifications to a KC-130 Operational Training Area (OTA) #7, including specific installation instructions such as:
- Installing a 2'H x 18"L ground bar with a #2/0 green insulated conductor
- Installing a 3P4W, 208Y/120V, 60A surface-mount electrical panel
- Adding an Emergency Power Off (EPO) switch connected to a breaker
- Constructing a new wall section with double doors
- Installing a "Simulator in Use" light and sign
- Reconfiguring light switches in rooms 107A and 107E
- Blacking out and sealing existing doors to prevent light leakage
The drawing is part of a Navy contract (Solicitation Number N400857434099) specifically for repairs to Room 107B in Building 4066, restricted to M&R MACC (Maintenance and Repair Multiple Award Construction Contract) contractors.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0001 7434099.pdf | ||
| RFP 7434099.pdf | ||
| 7434099 Streamlined MACC.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
0' 1/4"=1'
15'
A
B
2 3
C
D
1 2 3
AS SHOWN
BUILDING 4305A
1 1 12912785
7434099
EL
EC
TR
IC
AL
P
LA
N
A N
D D
ET
AI
LS
RCM
RCM
RCM
N/A
NAH
LPF
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
M
AR
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N , C
H
ER
R Y
PO
IN
T, N
.C
DRAWFORM REVISION JULY 2003
NAVFAC DRAWING NO.
SHEET OF
CONSTR. CONTR. NO.
CODE ID. NO. 80091 SIZE D
STA. PROJ. NO.
SCALE:
FED NO.
SPEC. NO.
A
DESIGN DIRECTOR
B
CHIEF ARCH./ ENGR.
PROJECT MANAGER
FIRE PROTECTION
BRANCH MANAGER
QC
DATE
A/E
DRAWN
REVIEW
DESIGN
EFD
FOR EFD FOR COMMANDER NAVFAC
ACTIVITY - SATISFACTORY TO
DATE
APPROVED
APPROVED
SEAL
C
A/E'S USE THIS SPACE FOR YOUR ADDRESS INFO.
FACILITIES ENGINEERING
DESIGNED & ENGINEERED BY:
SY
M
D
ES
C
R
IP
TI
O
N
D
D
AT
E
AP
PR
5' 10'
0" 1/8"=1"
30"6" 12" 18" 24"
KEYED NOTES #
1 INSTALL 2'H X 18"L X 1/4"T GROUND BAR 40"AFF IN ROOM
107A AS SHOWN. USE #2/0 GREEN INSULATED CONDUCTOR
IN 1" EMT TO CONNECT TO EXISTING GROUND BAR IN ROOM
110 USING CRIMPED LUGS ON EACH END.
2 INSTALL 3P4W, 208Y/120V, 60A, 20 SPACE, SURFACE MOUNT,
MLO PANEL, FED FROM NEW 3P60A CB IN PANEL HAU USING
4#6 AND 1#8G IN 1.25" EMT. INSTALL 3 PHASE CABLE FROM
3P60A SHUNT TRIP BREAKER IN PANEL OTA-7, 20 FOOT
LONG, #6-5 FLEXIBLE CABLE WITH CROUSE HINES 560-C9W
FEMALE CONNECTOR.
3 INSTALL EMERGENCY POWER OFF (EPO) SWITCH TO
3P60ST BREAKER IN PANEL OTA-7, FEED FROM 1P20A CB IN
PANEL OTA-7.
4 INSTALL WALL SECTION APPROX 12'H X 10'W WITH DOUBLE
DOOR. USE 6" METAL STUDS, 5/8" GYPSUM BOARD, 72"W X
85"H DOOR OPENING WITH SOLID CORE WOODEN LEAFS.
5 INSTALL "SIMULATOR IN USE" LIGHT ABOVE DOOR WITH
"SIMULATOR IN USE" SIGN ABOVE LIGHT.
6 INSTALL 3 WAY LIGHT SWITCHES IN 107A AND 107E AND
RECONFIGURE LIGHTS IN EACH ROOM TO BE CONTROLLED
BY THE NEW SWITCHES.
7 BLACK OUT GLASS IN EXISTING DOORS AND SEAL AROUND
DOORS TO PREVENT LIGHT LEAKAGE AROUND DOORS.
ELECTRICAL PANEL
ELECTRICAL FEEDER
GROUND BAR, WALL MOUNTED
LIGHT SWITCH
"SIMULATOR IN USE" LIGHT
EMERGENCY POWER OFF SWITCH
LEGEND
B4066 PLAN
S
L
B4066 KEY PLAN
E
"EPO" DETAIL
AutoCAD SHX Text 108A
AutoCAD SHX Text 108B
AutoCAD SHX Text 107A
AutoCAD SHX Text 107B
AutoCAD SHX Text 107C
AutoCAD SHX Text
HAU 208Y/120V 200A
AutoCAD SHX Text
OTA-7 208Y/120V 60A
AutoCAD SHX Text
EMER POWER OFF (EPO)
AutoCAD SHX Text
GROUND BAR
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
EXISTING GROUND BAR
AutoCAD SHX Text
OTA-7
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text 107D
AutoCAD SHX Text 107E
AutoCAD SHX Text
HAU 28,30,32
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
OTA-7
AutoCAD SHX Text
OTA-7 2
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text E-101
AutoCAD SHX Text
B4066 RM107B REPAIRS FOR OTA #7
AutoCAD SHX Text
GRAPHIC SCALES:
AutoCAD SHX Text 1/4"=1'
AutoCAD SHX Text
AREA OF WORK
AutoCAD SHX Text 1/32"=1'
AutoCAD SHX Text
NO SCALE
| Sheets and Views |
| 12912785 B4066 OTA#7 |
File details come from the government source that posted it. Updated .