7348749 DrawingsAsOne.pdf

PDF 4 MB Posted

Attached to
MCAS-Cherry Point New Fire Alarm System B4415
Solicitation number
N400857348749
Issued by

About this file

These are architectural and engineering drawings for a new fire alarm system installation at Marine Corps Air Station (MCAS) Cherry Point, North Carolina, specifically for Building 4415. The comprehensive set of drawings includes floor plans, demolition plans, electrical details, fire alarm system specifications, and installation requirements. Key components include:

The project involves replacing the existing fire alarm and mass notification system with a new Fire Alarm/Mass Notification Control Panel (FMCP), adding new smoke detectors, manual pull stations, speaker strobes, and associated wiring. The drawings specify detailed installation requirements for devices, conduit routing, mounting heights, and system integration. The work is to be performed in a fully occupied building, with strict requirements for maintaining emergency egress, system functionality, and minimizing disruption to ongoing operations. The project number is 7348749, and the drawings are dated July 3, 2025, prepared by Summer Consultants for the Naval Facilities Engineering Command.

View the file

Other files

File Type Posted
RFP 7348749.pdf PDF
7348749 SpecsAsOne.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAIN GATE PASS AND

ID OFFICE PROJECT LOCATION

SLOCUM GATE

4TH AVE.

F STREET

E STREET

ROOSEVELT BLVD

PROJECT LOCATION

LAY DOWN AREA

2ND AVE.

FI

LE

N

AM

E:

OU

R

RE

F:

PL

OT

D

AT

E:

7/8

/20

1:

:03 P

M

1.1

G-

1.D W

G

A

B

C

D

1 2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

7900 Westpark Dr. | Suite A405 | McLean, VA 22102

(703) 556-8820 | www.summerconsultants.com

SUMMER

CONSULTANTS

I N C O R P O R A T E D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M

AR

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N , C

H

ER

R Y

PO

IN

T, N

C

FA

C

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

A

C Q

U

IS

IT

IO

N S

D

IV

IS

IO

N M

C

AS

C H

ER

R

Y

PO

IN

T

- C H

ER

R

Y

PO

IN

T, N C

N

EW

F

IR

E

AL

AR

M

S

YS

TE

M

IN

B

U

IL

D

IN

G

7348749

4 5

RAP RAP RAP

C O

VE

R

S H

EE

T

G-001

NEW FIRE ALARM SYSTEM

WORK ORDER NO.

LOCATION MAPVICINITY MAP DRAWING INDEX

SHEET

NUMBER SHEET TITLE NAVFAC

DWG NO.

G-001 COVER SHEET 12925872

A-001 SYMBOLS AND ABBREVIATIONS 12925873

A-101 FIRST FLOOR PLAN 12925874

A-501 DOOR DETAILS 12925875

A-502 DOOR DETAILS 12925876

A-503 DOOR DETAILS 12925877

FA001 FIRE ALARM NOTES AND LEGEND 12925878

FD101 FIRE ALARM EXISTING FLOOR PLAN 12925879

FA101 FIRE ALARM FINAL REFLECTED CEILING PLAN 12925880

FA401 FIRE ALARM ENLARGED PLANS 12925881

FA501 FIRE ALARM DETAILS 12925882

E-001 SYMBOLS AND ABBREVIATIONS 12925883

ED101 RENOVATION FLOOR PLAN - DEMOLITION 12925884

E-101 RENOVATION FLOOR PLAN - POWER AND TELECOM 12925885

CHERRY POINT, NC

MARINE CORPS AIR STATION

ASBESTOS & LEAD-BASED PAINT

7348749

NO ASBESTOS CONTAINING MATERIALS WERE FOUND IN THE BUILDING.

LBP'S AND PAINT CONTAINING LEAD WITH LEAD CONCENTRATIONS

GREATER THAN OR EQUAL TO 1.0 mg/cm² FOUND IN THE FOLLOWING

SURFACES:

PC-1: WHITE METAL CONDUIT PIPES LOCATED IN THE MECHANICAL ROOM

PAINT WITH LEAD CONCENTRATION LESS THAN 1.0 mg/cm² COVERS ALL

OTHER SURFACES.

IN BUILDING 4415

N

N

LAYDOWN AREA

THE PRIMARY LAYDOWN AREA IS SHOWN IN THE LOCATION MAP.

THIS AREA SHALL BE USED AS THE LOCATION FOR THE JOB

TRAILER, IF ONE IS NECESSARY. THIS AREA MAY ALSO PROVIDE

LIMITED SPACE FOR MATERIAL STORAGE AND STAGING VIA A

CON-EX BOX. ALL PEDESTRIAN AND VEHICULAR ACCESS TO

ADJACENT AREAS OF THIS LAYDOWN AREA SHALL BE

MAINTAINED TO THE GREATEST EXTENT POSSIBLE. THIS

INFORMATION IS FOR BIDDING PURPOSES ONLY. ALL FINAL

LAYDOWN AND STAGING AREAS SHALL BE SUBJECT TO

GOVERNMENT APPROVAL AND MAY CHANGE. 01

12925872

07/03/2025

FI

LE

N

RE

F:

PL

OT

D

AT

E:

7/7

/20

1:

:56 P

M

1.0

A-

1.D W

G

A

B

C

D

1 2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

7900 Westpark Dr. | Suite A405 | McLean, VA 22102

(703) 556-8820 | www.summerconsultants.com

SUMMER

CONSULTANTS

I N C O R P O R A T E D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M

AR

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N , C

H

ER

R Y

PO

IN

T, N

C

FA

C

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

A

C Q

U

IS

IT

IO

N S

D

IV

IS

IO

N M

C

AS

C H

ER

R

Y

PO

IN

T

- C H

ER

R

Y

PO

IN

T, N C

N

EW

F

IR

E

AL

AR

M

S

YS

TE

M

IN

B

U

IL

D

IN

G

7348749

4 5

ABV ABOVE

ACT ACOUSTIC CEILING TILE

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

AHU AIR HANDLING UNIT

ALT ALTERNATIVE

ALUM ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECTURAL

AVG AVERAGE

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BOD BASIS OF DESIGN

BOT BOTTOM

BRD BOARD

BSMT BASEMENT

CAB CABINET

CL CLOSET

CLG CEILING

COL COLUMN

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUOUS

CPT CARPET

CTR CENTER

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DH DOUBLE HUNG

DIA DIAMETER

DIM DIMENSION

DIV DIVISION

DN DOWN

DRW DRAWER

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWGS DRAWINGS

E EAST

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

ENCL ENCLOSURE

EQ EQUAL

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EX EXISTING

EXP EXPANSION

EXT EXTERIOR

FA FIRE ALARM

FD FLOOR DRAIN

FE(C) FIRE EXTINGUISHER (CABINET)

FF FINISH FLOOR

FLR FLOOR(ING)

FLUOR FLUORESCENT

FR FRAME

FRT FIRE RETARDANT TREATED

FT FEET

FT FOOT

GL GLASS

GWB GYPSUM WALL BOARD

HDWR HARDWARE

HM HOLLOW METAL

HR HOUR

HT HEIGHT

HVAC HEATING, VENTILATION, AND AIR

CONDITIONING

INSUL INSULATION

INT INTERIOR

JAN JANITOR

JT JOINT

KD KNOCK DOWN

KIT KITCHEN

LAM LAMINATE

LAV LAVATORY

LIN LINEAR

LT LIGHT

MAINT MAINTENANCE

MATL MATERIAL

MAX MAXIMUM

MDF MEDIUM DENSITY FIBER BOARD

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MIN MINUTES

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MTL METAL

N NORTH

N/A NOT APPLICABLE

NIC NOT IN CONTRACT

NRC NOISE REDUCTION

COEFFICIENT

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OFCI CONTRACTING OFFICER

FURNISHED/ CONTRACTOR

INSTALLED

OFF OFFICE

OH OVERHEAD

OPG OPENING

OPHD OPPOSITE HAND

OPP OPPOSITE

PH PENTHOUSE

PLAM PLASTIC LAMINATE

PLN PLAN

POL POLISH(ED)

PR PAIR

PTD PAINTED

PTN PARTITION

QT QUARRY TILE

QTY QUANTITY

RCP REFLECTED CEILING PLAN

REF REFRIGERATOR

REF REFERENCE

REQD REQUIRED

REV REVISION

REV REVISE

RF ROOF

RM ROOM

RO ROUGH OPENING

RTU ROOF TOP UNIT

SCHED SCHEDULE

SCWD SOLID CORE WOOD DOOR

SECT SECTION

SF SQUARE FEET

SF SQUARE FOOT

SHT SHEET

SIM SIMILAR

SPEC SPECIFICATION

SQ SQUARE

SS SOLID SURFACE

SST STAINLESS STEEL

STC SOUND TRANSMISSION

COEFFICIENT

STL STEEL

STN STAIN

STOR STORAGE

STR STAIR

STRUC STRUCTURE

SYM SYMMETRICAL

SYM SYMBOL

SYS SYSTEM

T&G TONGUE AND GROOVE

TC TERRA COTTA

TEL TELEPHONE

TEMP TEMPORARY

THK THICK

TLT TOILET

TO TOP OF

TV TELEVISION

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

W WEST

W/ WITH

W/O WITHOUT

WD WOOD

WH WATER HEATER

WT WEIGHT

ABBREVIATIONS:

DRAWING TITLE

8'0 16' 1/8"=1'-0"

TITLE MARK1

PLAN DETAIL

STRUCTURAL COLUMN DESIGNATION

NORTH ARROW INDICATES PLAN NORTH

REVISION CLOUD WITH REVISION NUMBER

DESIGNATION

BREAK LINE

XX-# FINISH TAG

LEGEND - DRAWING SYMBOLS

N

BUILDING MATCHLINE

REFER TO SHEET A-101

A. REFER TO THE PROJECT SPECIFICATIONS UNDER SEPARATE COVER

B. ALL DIMENSION UNITS ARE IMPERIAL UNITS UNLESS OTHERWISE NOTED

C. DO NOT SCALE THE DRAWINGS

D. WORK IS TO BE PERFORMED IN A FULLY OCCUPIED BUILDING; PERIODS OF

SYSTEM INTERRUPTIONS MUST BE APPROVED BY GOVERNMENT; REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION

E. CONTRACTOR MUST MAINTAIN EMERGENCY EGRESS ACCESS AT ALL TIMES

F. IF ANY DISCREPANCIES EXIST BETWEEN DRAWINGS AND FIELD CONDITIONS,

THEN NOTIFY THE GOVERNMENT PRIOR TO THE START OF WORK

G. NOT ALL EXISTING FIRE RATED PARTITIONS ARE LABELED ON DRAWINGS;

GENERAL CONTRACTOR TO MAINTAIN ALL EXISTING FIRE RATINGS AND

SMOKE PARTITIONS

H. THE WORD "PROVIDE" SHALL MEAN "FURNISH AND INSTALL"

GENERAL NOTES - ARCHITECTURAL:

SHEET KEYNOTE#

HC DAS HC

SY

M

BO

LS

A N

D A

BB

R

EV

IA

TI

O

N S

12925873

A-001

N

RE

F:

PL

OT

D

AT

E:

7/7

/20

1:

:57 P

M

1.0

A-

1.D W

G

A

B

C

D

1 2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

7900 Westpark Dr. | Suite A405 | McLean, VA 22102

(703) 556-8820 | www.summerconsultants.com

SUMMER

CONSULTANTS

I N C O R P O R A T E D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M

AR

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N , C

H

ER

R Y

PO

IN

T, N

C

FA

C

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

A

C Q

U

IS

IT

IO

N S

D

IV

IS

IO

N M

C

AS

C H

ER

R

Y

PO

IN

T

- C H

ER

R

Y

PO

IN

T, N C

N

EW

F

IR

E

AL

AR

M

S

YS

TE

M

IN

B

U

IL

D

IN

G

7348749

4 5

F

111113114

N

8'0 16' 1/8"=1'-0"

FIRST FLOOR PLAN 1

GENERAL NOTES - FLOOR PLAN

SHEET KEYNOTES

G1. REFER TO ENTIRE SET OF DRAWINGS FOR ADDITIONAL SCOPE OF WORK

NOT SHOWN ON ARCHITECTURAL DRAWINGS

G2. PROTECT ALL EXISTING TO REMAIN BUILDING COMPONENTS, EQUIPMENT,

AND FINISHES

LEGEND - FLOOR PLAN

NOT ALL SHEET KEYNOTES WILL BE USED.

1 REFER TO SHEETS A-501, A-502, AND A-503 FOR DOOR SCOPE OF WORK

EXISTING PARTITION TO REMAIN

EXISTING DOOR, DOOR FRAME, AND DOOR

HARDWARE TO REMAIN

XX-#

XX-#

FINISH DESIGNATION FOR ROOM; REFER TO

INTERIOR FINISH AND MATERIAL SCHEDULE

EXTENT OF FINISH AT DESIGNATED LOCATIONS;

REFER TO INTERIOR FINISH AND MATERIAL.

SCHEDULE

XXX DOOR TAG

CLASSROOM

CLASSROOM

STORAGE

HC DAS HC

FI

R

ST

F

LO

O

R P

LA

N

12925874

A-101

ACTIVITY

MUSIC

STORAGE

JANITOR &

GIRLS

BOYS

LOBBY

ENTRY

OFFICE

WORKROOM

STAFF

LOCKERS

TLT

STORAGE

STORAGE

CHECKOUT

EQUIPMENT

MEETING

MECHANICAL

GYMANSIUM

1 1 1

EXISTING PAINTED CMU WALL TO

REMAIN; CONFIRM CONCEALED

CONDITIONS WHEN DOOR FRAME

IS REMOVED; CONFIRM THAT

DOOR JAMB ANCHORS CAN BE

INSTALLED AND ANCHORED TO

CMU; PROVIDE NEW HOT DIP

GALVANIZED DOOR ANCHORS AT

EACH DOOR FRAME HOLE

PROVIDE NEW IN-KIND DOOR, GLAZING,

FRAME, HARDWARE, SENSORS/CONTROLS;

ANCHOR TO JAMBS ONLY; INSTALL FRAMES

AND INSTALL AND ADJUST HARDWARE TO

ENSURE THAT DOORS SWING FREELY

CLOSED TO LATCHING AND FULL WEATHER

SEAL AT ALL EDGES OF DOORS; PAINT

EXTERIOR AND INTERIOR TO MATCH

EXISTING FINISHES; GROUT SOLID AT JAMBS

WITHOUT FILLING MASONRY EXPANSION

JOINT BETWEEN BRICK AND DOOR FRAME1" INSET INDICATED FOR DOOR #114; REINSTALL

AT DEEPER INSET, WHERE EXISTING CONDITIONS

DICTATE AT DOOR #111 AND #113

EXISTING AIR BARRIER, INSULATION,

AND BRICK TIES TO REMAIN

AIR CAVITY - ENSURE BRICK IS NOT

IN CONTACT WITH CMU

REINSTALL EXISTING BRICK AND

TIES; MATCH MORTAR TYPE,

APPEARANCE, AND TOOLING TO

ORIGINAL

PROVIDE COLORED SILICONE

SEALANT ON BACKER ROD - COLOR

TO MATCH EXISTING; CONFIRM

WIDTH

WHERE INDICATED ON THE

ELEVATION, PROVIDE MASONRY

EXPANSION JOINT BETWEEN BRICK

AND DOOR FRAME; LEAVE GROUT

OUT OF THIS CONDITION AND FILL

WITH CLOSED CELL NEOPRENE

FOAM

1" VIF 8" VIF8" VIF

MATCH EXISTING

PROVIDE SOLID 1/8" THICK PTFE 3.5"

X 3.5" BEARING PAD WITH TWO

STAINLESS STEEL FLAT HEAD 1/4"

DIA. SCREWS SET INTO MORTAR

FILLED BRICK CORES; INSET SO

BACKER ROD AND SEALANT CAN BE

INSTALLED AT ALL EXPOSED SIDES

PROVIDE CLOSED CELL NEOPRENE

FOAM COMPRESSIBLE FILLER

PROVIDE 26 GAGE HEMMED STAINLESS

STEEL DRIP EDGE AND NEW FLASHING TO

MATH HENRY TWF CONFIGURED TO SUIT

FLASHING CONDITIONS

REINSTALL EXISTING STEEL LOOSE LINTEL AFTER CLEANING

AND TREATING WITH ZINC RICH PRIMER. APPLY SPRAY APPLIED

PTFE COATING TO BEARING END AT MASONRY EXPANSION

JOINT; ENSURE AT LEAST 4" OF BEARING EACH END; PAINT

EXPOSED SURFACES TO MATCH EXISTING CONDITIONS

REINSTALL EXISTING BRICK AND TIES;

MATCH MORTAR TYPE, APPEARANCE, AND

TOOLING TO ORIGINAL

PROVIDE 3/16" STAINLESS STEEL

HORIZONTAL JOINT REINFORCING

24" LONG - TO MATCH H&B H&B 220;

REFER TO PARTIAL ELEVATION

FI

LE

N

RE

F:

PL

OT

D

AT

E:

7/7

/20

1:

:58 P

M

1.0

A-

1.D W

G

A

B

C

D

1 2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

7900 Westpark Dr. | Suite A405 | McLean, VA 22102

(703) 556-8820 | www.summerconsultants.com

SUMMER

CONSULTANTS

I N C O R P O R A T E D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M

AR

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N , C

H

ER

R Y

PO

IN

T, N

C

FA

C

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

A

C Q

U

IS

IT

IO

N S

D

IV

IS

IO

N M

C

AS

C H

ER

R

Y

PO

IN

T

- C H

ER

R

Y

PO

IN

T, N C

N

EW

F

IR

E

AL

AR

M

S

YS

TE

M

IN

B

U

IL

D

IN

G

7348749

4 5

DOOR JAMB DETAIL AT 1" INSET1

HC DAS HC

D O

O R

D

ET

AI

LS

12925875

A-501

MASONRY EXPANSION JOINT LINTEL BEARING DETAIL

0 9"6"3"

3"=1'-0"2

GENERAL NOTES - DOOR DETAILS

G1. SALVAGE MATERIALS AS REQUIRED TO PERFORM THE REPAIRS AND

INSTALL ANY NEW WORK. PROVIDE ALL TEMPORARY NECESSARY

ENGINEERED SHORING AND SUPPORTS TO PREVENT SAFETY HAZARDS

AND TO PROTECT THE BUILDING AND MATERIALS.

G2. FOR DOOR, GLAZING, FRAME, HARDWARE, SENSORS/CONTROLS;

PROVIDE NEW TO MATCH EXISTING. VERIFY ALL WORK BEFORE OR

DURING SUBMITTALS ASSURING THAT NEW WORK WILL FIT INTO

EXISTING MASONRY OPENINGS, MATCH EXISTING APPEARANCE, AND

MEET IN-KIND OR CURRENT CONTRACTING OFFICER REQUIREMENTS.

FOR INSTANCE GLAZING IS ASSUMED TO BE CLEAR IONOMER

LAMINATED LAZING MATCHING SENTRY GLASS IN LIEU OF WIRED GLASS

WHICH IS NO LONGER FAVORED FOR SECURITY GLASS.

G3. AS APPROVED BY THE CONTRACTING OFFICER, PROVIDE ALL

NECESSARY MEASURES TO MAINTAIN UNFETTERED EGRESS, SECURITY

AND CONTROL, WATER AND AIR INTRUSION PREVENTION, AND VERMIN

CONTROL.

G4. CONFIRM ALL CONDITIONS IN THE FIELD. REPORT ALL DISCREPANCIES

TO THE CONTRACTING OFFICER AND ENGINEER.

G5. SALVAGE BRICK, STEEL LOOSE LINTEL, AND RELATED WORK FOR

REINSTALLATION. CLEAN ITEMS TO ME REINSTALLED. PROVIDE NEW

STEEL LINTEL ANGLES IF EXISTING ARE DETERMINED TO BE DAMAGED

OR OF LESSER CAPACITY THAN INDICATED ON HEAD DETAIL.

G6. REPLACE ANY DAMAGED ITEMS TO BE REINSTALLED WITH MATCHING

ITEMS. PATCH, REFINISH, AND REPAINT SURFACES DISTURBED BY THE

WORK. MATCH ALL COLORS AND GLOSS LEVELS TO SUIT THE

CONTRACTING OFFICER. PAINT DOORS AND FRAMES, INSIDE AND OUT

TO MATCH EXISTING.

G7. VERTICAL MASONRY EXPANSION JOINTS MUST BE FREE TO COMPRESS

AND EXPAND. REPORT ANY OBSTRUCTION IN JOINTS TO THE

CONTRACTING OFFICER AND ENGINEER. BEHIND THE SEALANT AND

BACKER, JOINTS SHOULD BE FILLED WITH COMPRESSIBLE NEOPRENE

FILLER FULL DEPTH OF BRICK.

G8. HORIZONTAL MASONRY EXPANSION JOINT IS A SLIDE BEARING

CONDITION AS DETAILED. PROTECT CONDITION WITH BACKER AND

SEALANT. CONFIRM THAT MATERIALS CAN SLIDE.

G9. MATCH MORTAR TYPE, APPEARANCE, AND TOOLING TO EXISTING

ORIGINAL MORTAR. REPOINT MORTAR JOINTS THAT DO NOT MATCH

ORIGINAL MORTAR JOINTS.

G10. PROTECT ELECTRICAL CONDUITS AND BACK BOXES DURING THE WORK,

BUILD BACK INTO MASONRY. SALVAGE, CLEAN, RELAMP, AND

REINSTALL EXISTING LIGHT FIXTURES OVER DOORS. CONFIRM

INSTALLATION AND WEATHERPROOFING MEETS NEMA/NEC.

REFER TO DOOR, FRAME, AND HARDWARE GENERAL NOTES AS FOLLOWS:

G11. DOOR, GLAZING, FRAME, DOOR HARDWARE,

SENSORS/CONTROLS:

PROVIDE COMPLETE AND FULLY COORDINATED DOOR,

GLAZING, FRAME, HARDWARE, SENSORS/CONTROLS

SUBMITTALS PREPARED AND QUALITY ASSURED BY A DHI

CERTIFIED AHC.

G12. DOORS, FRAMES, AND ANCHORS MUST MEET ANSI/SDI A250.8-2023 FULL

FLUSH FACTORY WELDED AND GALVANIZED/GALVANNEALED TO MEET

SDI 112. GRADE OF DOORS, FRAMES, AND ANCHORS MUST MEET LEVEL

4 AND PHYSICAL PERFORMANCE LEVEL A, UNLESS OTHERWISE

APPROVED BY THE CONTRACTING OFFICER. ANCHORS MUST MEET

ASTM A591, WITH COATING WEIGHT OF 0.075 OZ/SF OR GREATER.

DOORS AND FRAMES MUST MEET THE EXISTING EGRESS

REQUIREMENTS AND FUNCTIONALITY AND FIT INTO THE EXISTING

ROUGH OPENING AT EACH DOORWAY AS VERIFIED IN THE FIELD BY THE

CONTRACTOR.

G12. DOOR HARDWARE MUST MATCH THE FUNCTION, SECURITY LEVEL, AND

FINISH OF THE EXISTING HARDWARE. GRADE FOR ALL HARDWARE

MUST MEET ANSI/BHMA GRADE 1.

G13. PROVIDE ALL CONCEALED CONDUITS, BACK BOXES, WIRE AND

HARNESSES, CONTACT SWITCHES, AND OTHER CONTROL OR SECURITY

SYSTEMS REQUIRED TO TIE IN TO EXISTING CENTRAL SYSTEMS AND TO

MATCH EXISTING FUNCTIONS AND QUALITY STANDARDS.

G14. HINGES: PROVIDE BRUSHED STAINLESS STEEL BARREL HINGES WITH

NON-REMOVABLE PINS TO MATCH EXISTING IN SIZE AND GAUGE.

PROVIDE FOUR HINGES PER DOOR.

G15. EXIT DEVICES: PROVIDE BRUSHED STAINLESS STEEL RIM TYPE. IF

APPROVED BY THE CONTRACTING OFFICER, PROVIDE MORTISE KEYED

DOGGING. IF APPROVED BY THE CONTRACTING OFFICER, PROVIDE

MORTISE KEYED EXTERIOR ACCESS TO THE INTERIOR. KEY BLANKS TO

BE NICKEL SILVER AND STAMPED AS DIRECTED BY THE CONTRACTING

OFFICER. PROVIDE ELECTRO/MECHANICAL LOCK/UNLOCK, LATCH BOLT

POSITION SENSOR, BOLT MINDER IN STRIKE, AND POWER TRANSFER

DEVICE AT JAMB AS REQUIRED TO MATCH EXISTING FUNCTIONALITY.

G16. KEY CYLINDERS AND KEYS: IF REQUIRED TO PROVIDE CYLINDERS AND

KEYS, MATCH CONTRACTING OFFICER'S BUILDING STANDARD AND KEY

PER THE CONTRACTING OFFICER'S WRITTEN DIRECTIONS.

G17. ALARM DEVICES: PROVIDE BRUSHED STAINLESS STEEL OR POWDER

COAT SILVER DOOR MOUNTED ALARM.

G18. DOOR CLOSERS: PROVIDE SILVER POWDER COAT CAST IRON BODY,

COVER, AND FORGED ARM WITH CUSHIONED STOP. PROVIDE

POWDER-COATED BRACKETS AS REQUIRED TO ALLOW FULL

AUTOMATIC CLOSURE TO LATCHING AND ALLOW DOOR GASKETING TO

SEAL.

G19. THRESHOLDS: PROVIDE CLEAR ANODIZED ALUMINUM, THERMALLY

BROKEN, SILICONE BULB SEAL, ADA/ABA COMPLIANT COPED TO DOOR

FRAME PROFILE.

G20. DOOR GASKETING: PROVIDE CLEAR ANODIZED ADJUSTABLE JAMB AND

HEAD SILICONE COMPRESSION GASKETS.

G21. DOOR DRIPS: PROVIDE CLEAR ANODIZED 3/4 INCH PROJECTION OR

GREATER DOOR BOTTOM DRIP AND VINYL BLADE SWEEP.

G22. FRAME DRIPS: PROVIDE CLEAR ANODIZED 3 1/2 INCH PROJECTION HEAD

OF FRAME DRIP, FULL WIDTH OF FRAME.

G23. KICK PLATES: IF APPROVED BY THE CONTRACTING OFFICER, PROVIDE

BRUSHED STAINLESS 10 INCH X DOOR WIDTH LESS 1 INCH

ADHERED IN PLACE AND ANCHORED WITH COUNTERSUNK SCREWS

ALONG PERIMETER. INSTALLED ON THE PUSH SIDE.

G24. PROVIDE FULL BED SILICONE SEALANT UNDERSIDE OF THRESHOLDS TO

FORM A COMPLETE WATER BARRIER. SEAL TRANSITION BETWEEN

DOOR FRAMES AND CONCRETE AND DOOR FRAMES AND THRESHOLDS.

G25. PROVIDE STAINLESS STEEL FASTENERS FOR ALL DOOR HARDWARE

FASTENERS.

G26. PROVIDE LAMINATED TEMPERED CLEAR ANTI-INTRUSION GLAZING AT

DOOR LITES LAMINATED WITH A CLEAR SOLID IONOMER INTERLAYER TO

MATCH SENTRY-GLASS.

G27. CONFIRM THAT DOORWAYS ARE NOT REQUIRED TO BE FIRE RATED OR

REQUIRED TO MEET OTHER STANDARDS NOT ADDRESSED HEREIN.

0 9"6"3" 3"=1'-0"

MASONRY

EXPANSION JOINT AT

DOOR #111 AND

DOOR #114; REPLACE

SEALANT AND

BACKER FULL

HEIGHT; COLOR TO

MATCH BRICK

AT DOOR #111 AND

DOOR #114 PROVIDE

3/16" STAINLESS

STEEL HORIZONTAL

JOINT REINFORCING

24" LONG - TO MATCH

H&B H&B 220

MASONRY EXPANSION JOINT

AT DOOR #111 AND DOOR

#114; REPLACE SEALANT

AND BACKER FULL LENGTH;

COLOR TO MATCH MORTAR.

SEE BEARING DETAIL

MASONRY EXPANSION

JOINT AT DOOR #111 AND

DOOR #114 BETWEEN

OUTER FRAME AND

BRICK; PROVIDE

SEALANT AND BACKER

FULL HEIGHT; COLOR TO

MATCH EXISTING

MASONRY EXPANSION JOINT AT

DOOR #113 AND DOOR #114;

REPLACE SEALANT AND

BACKER FULL HEIGHT; COLOR

TO MATCH BRICK

AT DOOR #113 PROVIDE

3/16" STAINLESS STEEL

HORIZONTAL JOINT

REINFORCING 24" LONG -

TO MATCH H&B H&B 220

MASONRY

EXPANSION JOINT

AT DOOR #113;

REPLACE SEALANT

AND BACKER FULL

HEIGHT; COLOR TO

MATCH BRICK

MASONRY EXPANSION

JOINT AT DOOR #113;

REPLACE SEALANT

AND BACKER FULL

LENGTH; COLOR TO

MATCH MORTAR; SEE

BEARING DETAIL

OPPOSITE HAND

MASONRY

EXPANSION JOINT AT

DOOR #113 BETWEEN

OUTER FRAME AND

BRICK; PROVIDE

SEALANT AND

BACKER FULL

HEIGHT; COLOR TO

MATCH EXISTING

REMOVE EXISTING DOOR, GLAZING, FRAME, HARDWARE,

SENSORS/CONTROLS; VERIFY ALL FUNCTIONALITY, GRADE,

MATERIALS, AND CONCEALED ASSEMBLIES; PROVIDE ENTIRELY

NEW IN-KIND REPLACEMENT OF DOOR, GLAZING, FRAME,

HARDWARE, SENSORS/CONTROLS; INCLUDE NEW IONOMER

LAMINATED SECURITY GLAZING; PROVIDE COMPLETE PRODUCT

DATA, HARDWARE SCHEDULE, AND SHOP DRAWINGS

CONFORMING TO IN-KIND REPLACEMENT AND IONOMER

LAMINATED GLAZING; IDENTIFY ANY CONFLICT BETWEEN

IN-KIND REPLACEMENT AND ALL CURRENT OWNER FACILITY

REQUIREMENTS IN SUBMITTALS WITH REQUEST FOR

CONFIRMATION ON DIRECTION AS PART OF REVIEW, OR

PROVIDE RFI IF DIRECTED

PROVIDE TEMPORARY EXIT DOOR ASSEMBLY AS APPROVED BY

THE OWNER TO SECURE OPENING, ALLOW UNFETTERED

EGRESS, AND PREVENT WATER AND VERMIN INGRESS

FI

LE

N

RE

F:

PL

OT

D

AT

E:

7/7

/20

1:

:58 P

M

1.0

A-

2.D W

G

A

B

C

D

1 2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

7900 Westpark Dr. | Suite A405 | McLean, VA 22102

(703) 556-8820 | www.summerconsultants.com

SUMMER

CONSULTANTS

I N C O R P O R A T E D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M

AR

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N , C

H

ER

R Y

PO

IN

T, N

C

FA

C

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

A

C Q

U

IS

IT

IO

N S

D

IV

IS

IO

N M

C

AS

C H

ER

R

Y

PO

IN

T

- C H

ER

R

Y

PO

IN

T, N C

N

EW

F

IR

E

AL

AR

M

S

YS

TE

M

IN

B

U

IL

D

IN

G

7348749

4 5

0 18"12"6" 1-1/2"=1'-0"

PARTIAL DOOR HEAD ELEVATION - TYPICAL AT THREE DOORS1

HC DAS HC

D O

O R

D

ET

AI

LS

12925876

A-502

GENERAL NOTES - DOOR DETAILS

G1. SALVAGE MATERIALS AS REQUIRED TO PERFORM THE REPAIRS AND

INSTALL ANY NEW WORK. PROVIDE ALL TEMPORARY NECESSARY

ENGINEERED SHORING AND SUPPORTS TO PREVENT SAFETY HAZARDS

AND TO PROTECT THE BUILDING AND MATERIALS.

G2. FOR DOOR, GLAZING, FRAME, HARDWARE, SENSORS/CONTROLS;

PROVIDE NEW TO MATCH EXISTING. VERIFY ALL WORK BEFORE OR

DURING SUBMITTALS ASSURING THAT NEW WORK WILL FIT INTO

EXISTING MASONRY OPENINGS, MATCH EXISTING APPEARANCE, AND

MEET IN-KIND OR CURRENT CONTRACTING OFFICER REQUIREMENTS.

FOR INSTANCE GLAZING IS ASSUMED TO BE CLEAR IONOMER

LAMINATED LAZING MATCHING SENTRY GLASS IN LIEU OF WIRED GLASS

WHICH IS NO LONGER FAVORED FOR SECURITY GLASS.

G3. AS APPROVED BY THE CONTRACTING OFFICER, PROVIDE ALL

NECESSARY MEASURES TO MAINTAIN UNFETTERED EGRESS, SECURITY

AND CONTROL, WATER AND AIR INTRUSION PREVENTION, AND VERMIN

CONTROL.

G4. CONFIRM ALL CONDITIONS IN THE FIELD. REPORT ALL DISCREPANCIES

TO THE CONTRACTING OFFICER AND ENGINEER.

G5. SALVAGE BRICK, STEEL LOOSE LINTEL, AND RELATED WORK FOR

REINSTALLATION. CLEAN ITEMS TO ME REINSTALLED. PROVIDE NEW

STEEL LINTEL ANGLES IF EXISTING ARE DETERMINED TO BE DAMAGED

OR OF LESSER CAPACITY THAN INDICATED ON HEAD DETAIL.

G6. REPLACE ANY DAMAGED ITEMS TO BE REINSTALLED WITH MATCHING

ITEMS. PATCH, REFINISH, AND REPAINT SURFACES DISTURBED BY THE

WORK. MATCH ALL COLORS AND GLOSS LEVELS TO SUIT THE

CONTRACTING OFFICER. PAINT DOORS AND FRAMES, INSIDE AND OUT

TO MATCH EXISTING.

G7. VERTICAL MASONRY EXPANSION JOINTS MUST BE FREE TO COMPRESS

AND EXPAND. REPORT ANY OBSTRUCTION IN JOINTS TO THE

CONTRACTING OFFICER AND ENGINEER. BEHIND THE SEALANT AND

BACKER, JOINTS SHOULD BE FILLED WITH COMPRESSIBLE NEOPRENE

FILLER FULL DEPTH OF BRICK.

G8. HORIZONTAL MASONRY EXPANSION JOINT IS A SLIDE BEARING

CONDITION AS DETAILED. PROTECT CONDITION WITH BACKER AND

SEALANT. CONFIRM THAT MATERIALS CAN SLIDE.

G9. MATCH MORTAR TYPE, APPEARANCE, AND TOOLING TO EXISTING

ORIGINAL MORTAR. REPOINT MORTAR JOINTS THAT DO NOT MATCH

ORIGINAL MORTAR JOINTS.

G10. PROTECT ELECTRICAL CONDUITS AND BACK BOXES DURING THE WORK,

BUILD BACK INTO MASONRY. SALVAGE, CLEAN, RELAMP, AND

REINSTALL EXISTING LIGHT FIXTURES OVER DOORS. CONFIRM

INSTALLATION AND WEATHERPROOFING MEETS NEMA/NEC.

REFER TO DOOR, FRAME, AND HARDWARE GENERAL NOTES AS FOLLOWS:

G11. DOOR, GLAZING, FRAME, DOOR HARDWARE,

SENSORS/CONTROLS:

PROVIDE COMPLETE AND FULLY COORDINATED DOOR,

GLAZING, FRAME, HARDWARE, SENSORS/CONTROLS

SUBMITTALS PREPARED AND QUALITY ASSURED BY A DHI

CERTIFIED AHC.

G12. DOORS, FRAMES, AND ANCHORS MUST MEET ANSI/SDI A250.8-2023 FULL

FLUSH FACTORY WELDED AND GALVANIZED/GALVANNEALED TO MEET

SDI 112. GRADE OF DOORS, FRAMES, AND ANCHORS MUST MEET LEVEL

4 AND PHYSICAL PERFORMANCE LEVEL A, UNLESS OTHERWISE

APPROVED BY THE CONTRACTING OFFICER. ANCHORS MUST MEET

ASTM A591, WITH COATING WEIGHT OF 0.075 OZ/SF OR GREATER.

DOORS AND FRAMES MUST MEET THE EXISTING EGRESS

REQUIREMENTS AND FUNCTIONALITY AND FIT INTO THE EXISTING

ROUGH OPENING AT EACH DOORWAY AS VERIFIED IN THE FIELD BY THE

CONTRACTOR.

G12. DOOR HARDWARE MUST MATCH THE FUNCTION, SECURITY LEVEL, AND

FINISH OF THE EXISTING HARDWARE. GRADE FOR ALL HARDWARE

MUST MEET ANSI/BHMA GRADE 1.

G13. PROVIDE ALL CONCEALED CONDUITS, BACK BOXES, WIRE AND

HARNESSES, CONTACT SWITCHES, AND OTHER CONTROL OR SECURITY

SYSTEMS REQUIRED TO TIE IN TO EXISTING CENTRAL SYSTEMS AND TO

MATCH EXISTING FUNCTIONS AND QUALITY STANDARDS.

G14. HINGES: PROVIDE BRUSHED STAINLESS STEEL BARREL HINGES WITH

NON-REMOVABLE PINS TO MATCH EXISTING IN SIZE AND GAUGE.

PROVIDE FOUR HINGES PER DOOR.

G15. EXIT DEVICES: PROVIDE BRUSHED STAINLESS STEEL RIM TYPE. IF

APPROVED BY THE CONTRACTING OFFICER, PROVIDE MORTISE KEYED

DOGGING. IF APPROVED BY THE CONTRACTING OFFICER, PROVIDE

MORTISE KEYED EXTERIOR ACCESS TO THE INTERIOR. KEY BLANKS TO

BE NICKEL SILVER AND STAMPED AS DIRECTED BY THE CONTRACTING

OFFICER. PROVIDE ELECTRO/MECHANICAL LOCK/UNLOCK, LATCH BOLT

POSITION SENSOR, BOLT MINDER IN STRIKE, AND POWER TRANSFER

DEVICE AT JAMB AS REQUIRED TO MATCH EXISTING FUNCTIONALITY.

G16. KEY CYLINDERS AND KEYS: IF REQUIRED TO PROVIDE CYLINDERS AND

KEYS, MATCH CONTRACTING OFFICER'S BUILDING STANDARD AND KEY

PER THE CONTRACTING OFFICER'S WRITTEN DIRECTIONS.

G17. ALARM DEVICES: PROVIDE BRUSHED STAINLESS STEEL OR POWDER

COAT SILVER DOOR MOUNTED ALARM.

G18. DOOR CLOSERS: PROVIDE SILVER POWDER COAT CAST IRON BODY,

COVER, AND FORGED ARM WITH CUSHIONED STOP. PROVIDE

POWDER-COATED BRACKETS AS REQUIRED TO ALLOW FULL

AUTOMATIC CLOSURE TO LATCHING AND ALLOW DOOR GASKETING TO

SEAL.

G19. THRESHOLDS: PROVIDE CLEAR ANODIZED ALUMINUM, THERMALLY

BROKEN, SILICONE BULB SEAL, ADA/ABA COMPLIANT COPED TO DOOR

FRAME PROFILE.

G20. DOOR GASKETING: PROVIDE CLEAR ANODIZED ADJUSTABLE JAMB AND

HEAD SILICONE COMPRESSION GASKETS.

G21. DOOR DRIPS: PROVIDE CLEAR ANODIZED 3/4 INCH PROJECTION OR

GREATER DOOR BOTTOM DRIP AND VINYL BLADE SWEEP.

G22. FRAME DRIPS: PROVIDE CLEAR ANODIZED 3 1/2 INCH PROJECTION HEAD

OF FRAME DRIP, FULL WIDTH OF FRAME.

G23. KICK PLATES: IF APPROVED BY THE CONTRACTING OFFICER, PROVIDE

BRUSHED STAINLESS 10 INCH X DOOR WIDTH LESS 1 INCH

ADHERED IN PLACE AND ANCHORED WITH COUNTERSUNK SCREWS

ALONG PERIMETER. INSTALLED ON THE PUSH SIDE.

G24. PROVIDE FULL BED SILICONE SEALANT UNDERSIDE OF THRESHOLDS TO

FORM A COMPLETE WATER BARRIER. SEAL TRANSITION BETWEEN

DOOR FRAMES AND CONCRETE AND DOOR FRAMES AND THRESHOLDS.

G25. PROVIDE STAINLESS STEEL FASTENERS FOR ALL DOOR HARDWARE

FASTENERS.

G26. PROVIDE LAMINATED TEMPERED CLEAR ANTI-INTRUSION GLAZING AT

DOOR LITES LAMINATED WITH A CLEAR SOLID IONOMER INTERLAYER TO

MATCH SENTRY-GLASS.

G27. CONFIRM THAT DOORWAYS ARE NOT REQUIRED TO BE FIRE RATED OR

REQUIRED TO MEET OTHER STANDARDS NOT ADDRESSED HEREIN.

EXISTING PAINTED CMU WALL TO

REMAIN. CONFIRM CONCEALED

CONDITIONS WHEN DOOR FRAME IS

REMOVED

REINSTALL EXISTING STEEL LOOSE LINTEL AFTER

CLEANING AND TREATING WITH ZINC RICH

PRIMER. APPLY SPRAY APPLIED PTFE COATING

TO BEARING END AT MASONRY EXPANSION JOINT;

ENSURE AT LEAST 4" OF BEARING EACH END;

PAINT EXPOSED SURFACES TO MATCH EXISTING

CONDITIONS

PROVIDE PAINTABLE SEALANT ON

BACKER ROD; CONFIRM WIDTH

PROVIDE CLOSED CELL NEOPRENE

FOAM COMPRESSIBLE FILLER

PROVIDE NEW IN-KIND DOOR, GLAZING, FRAME,

HARDWARE, SENSORS/CONTROLS; ANCHOR TO

JAMBS ONLY; INSTALL FRAMES AND INSTALL AND

ADJUST HARDWARE TO ENSURE THAT DOORS

SWING FREELY CLOSED TO LATCHING AND FULL

WEATHER SEAL AT ALL EDGES OF DOORS; PAINT

EXTERIOR AND INTERIOR TO MATCH EXISTING

FINISHES; GROUT SOLID AT JAMBS WITHOUT

FILLING MASONRY EXPANSION JOINT BETWEEN

BRICK AND DOOR FRAME

1" INSET INDICATED FOR DOORS #114; REINSTALL

AT DEEPER INSET, WHERE EXISTING CONDITIONS

DICTATE AT DOOR #111 AND #113

EXISTING AIR BARRIER, INSULATION, AND

BRICK TIES TO REMAIN

PROVIDE AIR BARRIER COMPATIBLE SEALANT

AT BRICK TIES AND TERMINATION BAR FOR

HIGH END OF THROUGH WALL FLASHING

REINSTALL EXISTING BRICK AND TIES. MATCH

MORTAR TYPE, APPEARANCE, AND TOOLING TO

ORIGINAL. PROVIDE NEW PLASTIC FIBROUS

MESH WEEPS AT 16" O.C

PROVIDE PLASTIC FIBROUS MESH MORTAR

SCREEN FULL LENGTH

PROVIDE 26 GAGE HEMMED STAINLESS STEEL

DRIP EDGE AND NEW FLASHING TO MATH

HENRY TWF CONFIGURED TO SUIT FLASHING

CONDITIONS

PROVIDE COLORED SILICONE SEALANT ON

BACKER ROD - COLOR TO MATCH EXISTING;

CONFIRM WIDTH

DO NOT REINSTALL METAL DRIP CURRENTLY

FASTENED TO BREAK HEADER AT ONE DOOR

UNLESS REQUIRED BY THE OWNER

PROVIDE NEW 3 1/2" EXTRUDED ALUMINUM

DOOR HEAD DRIP FULL WITH OF FRAME OVER

EACH DOOR. PROVIDE WITH STAINLESS STEEL

SCREWS. SET FLANGE ON SILICONE SEALANT

BEFORE FASTENING SO WHOLE FLANGE IS

SEALED. EXISTING 3 1/2" CAN BE REUSED, IF IN

GOOD CONDITION 1" VIF 8" VIF8" VIF

MATCH EXISTING

FI

LE

N

RE

F:

PL

OT

D

AT

E:

7/7

/20

1:

:59 P

M

XX

X.

XX

A-

3.D W

G

A

B

C

D

1 2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

7900 Westpark Dr. | Suite A405 | McLean, VA 22102

(703) 556-8820 | www.summerconsultants.com

SUMMER

CONSULTANTS

I N C O R P O R A T E D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M

AR

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N , C

H

ER

R Y

PO

IN

T, N

C

FA

C

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

A

C Q

U

IS

IT

IO

N S

D

IV

IS

IO

N M

C

AS

C H

ER

R

Y

PO

IN

T

- C H

ER

R

Y

PO

IN

T, N C

N

EW

F

IR

E

AL

AR

M

S

YS

TE

M

IN

B

U

IL

D

IN

G

7348749

4 5

DOOR HEAD DETAIL

0 9"6"3"

3"=1'-0"1

GENERAL NOTES - DOOR DETAILS

G1. SALVAGE MATERIALS AS REQUIRED TO PERFORM THE REPAIRS AND

INSTALL ANY NEW WORK. PROVIDE ALL TEMPORARY NECESSARY

ENGINEERED SHORING AND SUPPORTS TO PREVENT SAFETY HAZARDS

AND TO PROTECT THE BUILDING AND MATERIALS.

G2. FOR DOOR, GLAZING, FRAME, HARDWARE, SENSORS/CONTROLS;

PROVIDE NEW TO MATCH EXISTING. VERIFY ALL WORK BEFORE OR

DURING SUBMITTALS ASSURING THAT NEW WORK WILL FIT INTO

EXISTING MASONRY OPENINGS, MATCH EXISTING APPEARANCE, AND

MEET IN-KIND OR CURRENT CONTRACTING OFFICER REQUIREMENTS.

FOR INSTANCE GLAZING IS ASSUMED TO BE CLEAR IONOMER

LAMINATED LAZING MATCHING SENTRY GLASS IN LIEU OF WIRED GLASS

WHICH IS NO LONGER FAVORED FOR SECURITY GLASS.

G3. AS APPROVED BY THE CONTRACTING OFFICER, PROVIDE ALL

NECESSARY MEASURES TO MAINTAIN UNFETTERED EGRESS, SECURITY

AND CONTROL, WATER AND AIR INTRUSION PREVENTION, AND VERMIN

CONTROL.

G4. CONFIRM ALL CONDITIONS IN THE FIELD. REPORT ALL DISCREPANCIES

TO THE CONTRACTING OFFICER AND ENGINEER.

G5. SALVAGE BRICK, STEEL LOOSE LINTEL, AND RELATED WORK FOR

REINSTALLATION. CLEAN ITEMS TO ME REINSTALLED. PROVIDE NEW

STEEL LINTEL ANGLES IF EXISTING ARE DETERMINED TO BE DAMAGED

OR OF LESSER CAPACITY THAN INDICATED ON HEAD DETAIL.

G6. REPLACE ANY DAMAGED ITEMS TO BE REINSTALLED WITH MATCHING

ITEMS. PATCH, REFINISH, AND REPAINT SURFACES DISTURBED BY THE

WORK. MATCH ALL COLORS AND GLOSS LEVELS TO SUIT THE

CONTRACTING OFFICER. PAINT DOORS AND FRAMES, INSIDE AND OUT

TO MATCH EXISTING.

G7. VERTICAL MASONRY EXPANSION JOINTS MUST BE FREE TO COMPRESS

AND EXPAND. REPORT ANY OBSTRUCTION IN JOINTS TO THE

CONTRACTING OFFICER AND ENGINEER. BEHIND THE SEALANT AND

BACKER, JOINTS SHOULD BE FILLED WITH COMPRESSIBLE NEOPRENE

FILLER FULL DEPTH OF BRICK.

G8. HORIZONTAL MASONRY EXPANSION JOINT IS A SLIDE BEARING

CONDITION AS DETAILED. PROTECT CONDITION WITH BACKER AND

SEALANT. CONFIRM THAT MATERIALS CAN SLIDE.

G9. MATCH MORTAR TYPE, APPEARANCE, AND TOOLING TO EXISTING

ORIGINAL MORTAR. REPOINT MORTAR JOINTS THAT DO NOT MATCH

ORIGINAL MORTAR JOINTS.

G10. PROTECT ELECTRICAL CONDUITS AND BACK BOXES DURING THE WORK,

BUILD BACK INTO MASONRY. SALVAGE, CLEAN, RELAMP, AND

REINSTALL EXISTING LIGHT FIXTURES OVER DOORS. CONFIRM

INSTALLATION AND WEATHERPROOFING MEETS NEMA/NEC.

REFER TO DOOR, FRAME, AND HARDWARE GENERAL NOTES AS FOLLOWS:

G11. DOOR, GLAZING, FRAME, DOOR HARDWARE,

SENSORS/CONTROLS:

PROVIDE COMPLETE AND FULLY COORDINATED DOOR,

GLAZING, FRAME, HARDWARE, SENSORS/CONTROLS

SUBMITTALS PREPARED AND QUALITY ASSURED BY A DHI

CERTIFIED AHC.

G12. DOORS, FRAMES, AND ANCHORS MUST MEET ANSI/SDI A250.8-2023 FULL

FLUSH FACTORY WELDED AND GALVANIZED/GALVANNEALED TO MEET

SDI 112. GRADE OF DOORS, FRAMES, AND ANCHORS MUST MEET LEVEL

4 AND PHYSICAL PERFORMANCE LEVEL A, UNLESS OTHERWISE

APPROVED BY THE CONTRACTING OFFICER. ANCHORS MUST MEET

ASTM A591, WITH COATING WEIGHT OF 0.075 OZ/SF OR GREATER.

DOORS AND FRAMES MUST MEET THE EXISTING EGRESS

REQUIREMENTS AND FUNCTIONALITY AND FIT INTO THE EXISTING

ROUGH OPENING AT EACH DOORWAY AS VERIFIED IN THE FIELD BY THE

CONTRACTOR.

G12. DOOR HARDWARE MUST MATCH THE FUNCTION, SECURITY LEVEL, AND

FINISH OF THE EXISTING HARDWARE. GRADE FOR ALL HARDWARE

MUST MEET ANSI/BHMA GRADE 1.

G13. PROVIDE ALL CONCEALED CONDUITS, BACK BOXES, WIRE AND

HARNESSES, CONTACT SWITCHES, AND OTHER CONTROL OR SECURITY

SYSTEMS REQUIRED TO TIE IN TO EXISTING CENTRAL SYSTEMS AND TO

MATCH EXISTING FUNCTIONS AND QUALITY STANDARDS.

G14. HINGES: PROVIDE BRUSHED STAINLESS STEEL BARREL HINGES WITH

NON-REMOVABLE PINS TO MATCH EXISTING IN SIZE AND GAUGE.

PROVIDE FOUR HINGES PER DOOR.

G15. EXIT DEVICES: PROVIDE BRUSHED STAINLESS STEEL RIM TYPE. IF

APPROVED BY THE CONTRACTING OFFICER, PROVIDE MORTISE KEYED

DOGGING. IF APPROVED BY THE CONTRACTING OFFICER, PROVIDE

MORTISE KEYED EXTERIOR ACCESS TO THE INTERIOR. KEY BLANKS TO

BE NICKEL SILVER AND STAMPED AS DIRECTED BY THE CONTRACTING

OFFICER. PROVIDE ELECTRO/MECHANICAL LOCK/UNLOCK, LATCH BOLT

POSITION SENSOR, BOLT MINDER IN STRIKE, AND POWER TRANSFER

DEVICE AT JAMB AS REQUIRED TO MATCH EXISTING FUNCTIONALITY.

G16. KEY CYLINDERS AND KEYS: IF REQUIRED TO PROVIDE CYLINDERS AND

KEYS, MATCH CONTRACTING OFFICER'S BUILDING STANDARD AND KEY

PER THE CONTRACTING OFFICER'S WRITTEN DIRECTIONS.

G17. ALARM DEVICES: PROVIDE BRUSHED STAINLESS STEEL OR POWDER

COAT SILVER DOOR MOUNTED ALARM.

G18. DOOR CLOSERS: PROVIDE SILVER POWDER COAT CAST IRON BODY,

COVER, AND FORGED ARM WITH CUSHIONED STOP. PROVIDE

POWDER-COATED BRACKETS AS REQUIRED TO ALLOW FULL

AUTOMATIC CLOSURE TO LATCHING AND ALLOW DOOR GASKETING TO

SEAL.

G19. THRESHOLDS: PROVIDE CLEAR ANODIZED ALUMINUM, THERMALLY

BROKEN, SILICONE BULB SEAL, ADA/ABA COMPLIANT COPED TO DOOR

FRAME PROFILE.

G20. DOOR GASKETING: PROVIDE CLEAR ANODIZED ADJUSTABLE JAMB AND

HEAD SILICONE COMPRESSION GASKETS.

G21. DOOR DRIPS: PROVIDE CLEAR ANODIZED 3/4 INCH PROJECTION OR

GREATER DOOR BOTTOM DRIP AND VINYL BLADE SWEEP.

G22. FRAME DRIPS: PROVIDE CLEAR ANODIZED 3 1/2 INCH PROJECTION HEAD

OF FRAME DRIP, FULL WIDTH OF FRAME.

G23. KICK PLATES: IF APPROVED BY THE CONTRACTING OFFICER, PROVIDE

BRUSHED STAINLESS 10 INCH X DOOR WIDTH LESS 1 INCH

ADHERED IN PLACE AND ANCHORED WITH COUNTERSUNK SCREWS

ALONG PERIMETER. INSTALLED ON THE PUSH SIDE.

G24. PROVIDE FULL BED SILICONE SEALANT UNDERSIDE OF THRESHOLDS TO

FORM A COMPLETE WATER BARRIER. SEAL TRANSITION BETWEEN

DOOR FRAMES AND CONCRETE AND DOOR FRAMES AND THRESHOLDS.

G25. PROVIDE STAINLESS STEEL FASTENERS FOR ALL DOOR HARDWARE

FASTENERS.

G26. PROVIDE LAMINATED TEMPERED CLEAR ANTI-INTRUSION GLAZING AT

DOOR LITES LAMINATED WITH A CLEAR SOLID IONOMER INTERLAYER TO

MATCH SENTRY-GLASS.

G27. CONFIRM THAT DOORWAYS ARE NOT REQUIRED TO BE FIRE RATED OR

REQUIRED TO MEET OTHER STANDARDS NOT ADDRESSED HEREIN.

HC DAS HC

D O

O R

D

ET

AI

LS

12925877

A-503

GENERAL SHEET NOTES

A

B

C

D

1 2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M

AR

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N , C

H

ER

R Y

PO

IN

T, N

C

FA

C

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

A

C Q

U

IS

IT

IO

N S

D

IV

IS

IO

N M

C

AS

C H

ER

R

Y

PO

IN

T

- C H

ER

R

Y

PO

IN

T, N C

N

EW

F

IR

E

AL

AR

M

S

YS

TE

M

IN

B

U

IL

D

IN

G

7348749

4 5

Suite 203 4520 Mint Hill Village Lane

Mint Hill, NC 28227

Fire Protection & Building Code Specialists

Lovett Consultants

Ph. 704.545.8383 NC Firm License No: F-0296

IN

RT

N

JE

NO

L.

TE

NA

040804

ENG

F

NI EER

OL

V

SEAL

S

A

SFORP

E H C

I

AL

OI N

OR L

T

ER

1. REFER TO FD101 FOR THE FIRE ALARM EXISTING FLOOR PLAN.

2. REFER TO FA101 FOR THE FIRE ALARM FINAL FLOOR PLAN.

3. REFER TO FA401 FOR THE FIRE ALARM ENLARGED PLANS.

4. REFER TO FA501 FOR THE FIRE ALARM DETAILS.

SUBSCRIPTS

WEATHERPROOF

PROTECTIVE CAGE

(WP)

(CG)

LEGEND

K

FACP

FMCP

FAA

TRNS

LOC

MIC

RTS

BATT

DACT

F

S S

MM

CM

TS

FS

S

SP

EOL

FAD

MANUAL PULL STATION

SMOKE DETECTOR

IN DUCT SMOKE DETECTOR

FIRE ALARM ANNUNCIATOR

MASS NOTIFICATION TRANSCEIVER

LOCAL OPERATING CONSOLE

MICROPHONE

REMOTE TEST STATION

BATTERY CABINET

DIGITAL ALARM COMMUNICATOR TRANSMITTER

MONITORING MODULE

CONTROL MODULE

TAMPER SWITCH MONITORING MODULE

FLOW SWITCH MONITORING MODULE

END OF LINE RESISTOR

SURGE PROTECTOR

DRAWING STORAGE BOX

FIRE DEPARTMENT KNOX BOX

WALL MOUNTED SPEAKER STROBE: � INDICATES CANDELA RATING

CEILING MOUNTED SPEAKER STROBE: � INDICATES CANDELA RATING

WALL MOUNTED SPEAKER

WALL MOUNTED HORN STROBE

WALL MOUNT STROBE; � INDICATES CANDELA RATING

WALL MOUNT HORN STROBE; � INDICATES CANDELA RATING

FIRE ALARM CONTROL PANEL

FIRE ALARM / MASS NOTIFICATION CONTROL PANEL

DISTRIBUTION PANELBOARD

PUBLIC ADDRESS SYSTEM

PUBLIC ADDRESS SYSTEM MICROPHONE - EXISTING TO REMAIN

PA

LENGTH:

mm - MILLIMETER m - METER in - " - INCH ft - ' - FOOT

AREA:

mm² - SQUARE MILLIMETER m² - SQUARE METER sq.in - SQUARE INCH sq.ft - SQUARE FOOT

GENERAL:

AFF - ABOVE FINISHED FLOOR

AHU - AIR HANDLING UNIT

CD - CANDELA

COE - CORPS OF ENGINEERS

EG - EXAMPLE GIVEN

ETC - ETCETERA

FD - FIRE DEPARTMENT

HR - HOUR

IDC - INITIATING DEVICE CIRCUIT

LED - LIGHT EMITTING DIODE

MAX - MAXIMUM

MIN - MINIMUM, MINUTE

NAC - NOTIFICATION APPLIANCE

CIRCUIT

NEC - NATIONAL ELECTRIC CODE

NFPA - NATIONAL FIRE PROTECTION

ASSOCIATION

NTS - NOT TO SCALE

RMC - RIGID METALLIC CONDUIT

SLC - SIGNALING LINE CIRCUIT

SPD - SURGE PROTECTION DEVICE

UFC - UNIFIED FACILITIES CRITERIA

W/ - WITH

W/O - WITHOUT

ABBREVIATION LIST

THE SYSTEM MUST COMPLY WITH THE FOLLOWING CODES AND STANDARDS.

1. NFPA 70 NATIONAL ELECTRICAL CODE - 2023 ED.

2. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE - 2025 ED.

3. NFPA 90A INSTALLATION OF AIR-CONDITIONING AND VENTING - 2024 ED.

4. NFPA 101 LIFE SAFETY CODE - 2024 ED.

5. UFC 1-200-01 GENERAL BUILDING REQUIREMENTS: CHANGE 4, DEC 17, 2024.

6. UFC 3-600-01 DESIGN: FIRE PROTECTION ENGINEERING FOR FACILITIES; CHANGE 6, MAY 6, 2021.

7. UFC 3-520-01 INTERIOR ELECTRICAL SYSTEM: JAN 16, 2025.

8. UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS: CHANGE 1, JAN 1, 2010.

1. MONITORING MODULES AND CONTROL MODULES/RELAYS MUST BE ADDRESSABLE AND LOCATED WITHIN 36" OF THE SPECIFIC DEVICE OR EQUIPMENT IT CONTROLS OR MONITORS AS REQUIRED DURING PHASED

MIGRATION.

2. PROVIDE EACH TAMPER SWITCH WITH A SEPARATE ADDRESS. CLEARLY LABEL ALL ADDRESSABLE DEVICES

AND CIRCUITS WITH A TYPED PRINTABLE LABEL AFFIXED TO EACH DEVICE.

3. EXISTING FIRE ALARM DEVICES MUST BE MIGRATED TO THE NEW FMCP TO ENSURE UNINTERRUPTED

OPERATION.

4. THE PA SYSTEM MUST AUTOMATICALLY MUTE UPON ACTIVATION OF THE FIRE ALARM SYSTEM TO ENSURE

CLEAR AUDIBILITY OF EMERGENCY ALERTS.

INTERFACE/CONTROLS:

1. THE CIRCUIT BREAKERS MUST BE DEDICATED RED CIRCUIT BREAKERS WITH A LOCK-OPEN DEVICE TO COMPLY

WITH NFPA 72 REQUIREMENTS.

2. PROVIDE CIRCUIT IDENTIFICATION AT THE BREAKER PANEL FOR FIRE ALARM AND MASS NOTIFICATION

CIRCUITS.

3. SECONDARY POWER MUST BE BY RECHARGEABLE BATTERIES SIZED TO OPERATE THE SYSTEM FOR EITHER 48 HRS IN STANDBY/SUPERVISORY MODE WITH AN ADDITIONAL 15 MIN IN ALARM OR 60 MIN FULL ALARM

IMMEDIATELY AFTER LOSS OF PRIMARY POWER, WHICHEVER IS GREATER.

4. THE SYSTEM MUST INCLUDE FULLY AUTOMATIC, SOLID STATE BATTERY CHARGER(S) UTILIZING A TRICKLE-CHARGE OR A FLOAT-CHARGE. THE CHARGER(S) MUST HAVE THE CAPACITY TO RECHARGE

BATTERIES TO 95% OF FULL CHARGE WITHIN 48 HOURS.

5. THE BATTERIES WITH CHARGER(S) MUST BE HOUSED IN THE FMCP CABINET OR AN ADJACENT BATTERY

CABINET. POWER BOOSTERS WITH CHARGER(S), MUST BE LOCATED ON THE ZONE IT SERVES.

6. BATTERY CABINET MUST BE INSTALLED A MINIMUM OF 12" AFF.

POWER/BATTERIES:

1. REFER TO FA501 FOR DETAIL DIAGRAMS AND SEQUENCE OF OPERATIONS MATRIX.

2. THE LAYOUT SHOWN IS TO CONVEY THE DESIGN INTENT. THE FINAL SYSTEM LAYOUT MUST BE COMPLETED BY THE

CONTRACTOR IN ACCORDANCE WITH THE LISTED DESIGN CRITERIA.

3. KEYED PANELS AND PULL STATIONS TO ALL BE KEYED ALIKE.

4. THE EXISTING FACP IN THE MECHANICAL ROOM MUST REMAIN OPERATIONAL UNTIL THE NEW FMCP IS FULLY

FUNCTIONAL AND TESTED.

5. EXISTING FIRE ALARM CIRCUITS MUST BE MIGRATED TO THE NEW FMCP VIA TEMPORARY MONITOR AND CONTROL

MODULES TO ENSURE UNINTERRUPTED OPERATION.

6. ALL NAC DEVICES MUST BE COMBINED FIRE ALARM/MASS NOTIFICATION DEVICES.

7. CONTRACTOR MUST COORDINATE FIRE ALARM INSTALL WITH FACILITY AND BASE PERSONNEL, ENSURING LIMITED

OUTAGES WITH NO WORK WHILE YOUTH ARE IN THE BUILDING. POTENTIAL FOR AFTER HOURS AND WEEKEND WORK.

GENERAL:

DESIGN CRITERIA - FIRE ALARM/MASS NOTIFICATION SYS.

1. THE INITIATING CIRCUITS MUST BE CLASS "B".

2. ALL SMOKE DETECTORS CONNECTED TO THE FMCP MUST HAVE AN ADJUSTABLE ALARM VERIFICATION

FEATURE, INITIALLY SET AT 20 SECONDS.

3. ALL SMOKE DETECTORS MUST BE PHOTO-ELECTRIC UNLESS NOTED OTHERWISE.

4. MULTI-CRITERIA DETECTORS ARE PROHIBITED.

5. MANUAL PULL STATIONS MUST BE ADDRESSABLE DOUBLE ACTION TYPE WITH MECHANICAL RESET FEATURES.

IF RESET BY KEY, IT MUST BE THE SAME AS REQUIRED FOR THE CONTROL PANEL.

6. EACH SPRINKLER WATERFLOW SWITCH MUST HAVE A SEPARATE ADDRESS.

INITIATING CIRCUITS (SLC):

1. THE FMCP NOTIFICATION CIRCUITS MUST BE A CLASS "B".

2. THE AUDIBLE ALARM NOTIFICATION MUST BE BY VOICE EVACUATION SYSTEM. SPEAKERS MUST HAVE MANUALLY

SELECTABLE MULTI/VARIABLE WATTAGE, 0.25 TO 1.0 WATTS IN 0.25 WATT INCREMENTS. INITIAL SETTING TO BE AT 0.50

WATTS AND ADJUSTED AS NECESSARY TO MEET INTELLIGIBILITY REQUIREMENTS .

3. VOICE MESSAGES MUST BE FEMALE, AND UTILIZE THE INSTALLATIONS STANDARD SIGNALS AND MESSAGES. MESSAGES

MUST BE APPROVED BY THE SERVING FIRE DEPARTMENT OR AHJ.

4. THE NUMBER AND PLACEMENT OF SPEAKER(S) TO BE SUFFICIENT TO PROVIDE 0.70 (CSI SCORE) INTELLIGIBILITY RATING WITHIN THE AREA OF ALL DOORS, FIRE SHUTTERS, MOVABLE PARTITIONS, AND SIMILAR DEVICES CLOSED.

5. VISUAL NOTIFICATION MUST BE PROVIDED IN ALL NORMALLY OCCUPIED, PUBLIC, AND COMMON USE AREAS. OFFICES

DESIGNED FOR FOUR OR MORE PERSONS MUST HAVE VISUAL NOTIFICATION.

6. VISUAL NOTIFICATION MUST BE PROVIDED IN ALL NORMALLY UNOCCUPIED AREAS GREATER THAN 900 SQ. FT. SUCH AS

MECH., ELECTRICAL, STORAGE, COMMUNICATIONS, JANITORS ROOMS, AND SIMILAR SPACES.

7. STROBES MUST HAVE MANUALLY SELECTABLE CANDELA RATINGS, 15 TO 110 CANDELA. CANDELA RATING MUST BE

BASED ON LOCATION AND QUANTITY IN A ROOM IN ACCORDANCE WITH NFPA 72.

8. VISIBLE NOTIFICATION APPLIANCES MUST HAVE CLEAR LENS IN A WHITE HOUSING MARKED "ALERT" IN RED.

NOTIFICATION CIRCUITS (NAC):

1. ALL CONDUCTORS TO BE RUN IN 3/4" MINIMUM RIGID METAL CONDUIT (EMT). PROVIDE CONDUIT SIZES, QUANTITIES, AND CONFIGURATION IN ACCORDANCE WITH LISTED DESIGN CRITERIA AND MANUFACTURER'S

APPROVED SHOP DRAWINGS.

2. ALL CONDUCTORS MUST BE EITHER STRANDED OR SOLID COPPER. 18 AWG MIN FOR SLC AND 16 AWG MIN. FOR

NAC CIRCUITS.

3. ALL CONDUIT, WIRES, AND CABLES IN FINISHED SPACES MUST BE CONCEALED IN WALLS, CEILING, AND SIMILAR

SPACES. REUSE EXISTING CONDUIT WHEN CONCEALED IN CMU WALLS.

4. ALL CONDUCTORS TO RUN SPLICE FREE FROM DEVICE TO DEVICE. WIRE NUTS, CRIMPED CONNECTORS, OR

TWISTING OF CONDUCTORS IS PROHIBITED.

5. RUN ALL WIRING TO AND WITHIN THE CONTROL PANEL IN THE VERTICAL OR HORIZONTAL PLANE, MAKE ALL TURNS AT 90 DEGREES ANGLES, AND TIGHTLY BUNDLED AND WRAPPED. IDENTIFY ALL CONDUCTORS INDIVIDUALLY WITH

PERMANENT PRINTED LABELS AFFIXED WITH SHRINK WRAP.

6. DEVICE CONNECTIONS MUST BE THE DEVICE SCREW TERMINALS OR TERMINAL STRIPS MOUNTED WITHIN THE

JUNCTION BOX.

7. ALL CONDUIT, JUNCTION/BACK BOXES, COVERS, AND COUPLINGS ARE TO BE FACTORY PAINTED RED IN

UNFINISHED AREAS (E.G. ABOVE CEILINGS, IN MECHANICAL ROOMS, ETC).

8. ALL CONDUIT, JUNCTION/BACK BOXES, COVERS AND COUPLINGS ARE PERMITTED TO BE PAINTED TO MATCH ROOM FINISH. THE INSIDE COVER OF JUNCTION BOXES TO BE IDENTIFIED AS "FIRE ALARM". CONDUIT TO HAVE 3/4" RED

BANDS EVERY 20 FT AND BOTH SIDES OF ALL FLOORS, WALLS, AND CEILING PENETRATIONS.

9. 120 VAC CIRCUITS TO CONTROL PANELS, SUBPANELS, TRANSMITTERS, AMPLIFIER PANELS, AND BOOSTER PANELS MUST BE EQUIPPED WITH SPD. THE SPD MUST BE LOCATED IN AN ADJACENT HINGED TERMINAL BOX.

WIRING, CONDUIT:

1. PROVIDE A LOC NEAR THE BUILDING'S ENTRANCE, NOT TO BE INSTALLED IN A LOCKED ROOM OR CLOSET.

2. LOC MUST BE INSTALLED IN A SMALL, WALL MOUNTED, NON-LOCKABLE ENCLOSURE IN A YEAR-ROUND

ENVIRONMENTALLY CONDITIONED SPACE.

3. PROVIDE EQUIPMENT IDENTIFICATION SIGNAGE ON THE OUTSIDE OF THE LOC ENCLOSURE.

LOCAL OPERATING CONSOLE (LOC):

1. THE EXISTING FACP IN THE MECHANICAL ROOM MUST REMAIN OPERATIONAL UNTIL THE NEW FMCP IN THE

STORAGE ROOM IS FULLY FUNCTIONAL.

2. INSTALL AND ENERGIZE THE NEW FMCP PRIOR TO ANY DEVICE MIGRATION.

3. INSTALL TEMPORARY CONTROL AND MONITORING MODULES FOR THE EXISTING CIRCUITS.

4. REROUTE EXISTING NAC AND IDC CIRCUITS TO THE TEMPORARY MODULES.

5. PERFORM FUNCTIONAL TESTING AND INSPECTION TO ENSURE EXISTING DEVICES AND CIRCUITS ARE FUNCTIONAL

AND SIGNALS ARE SENT TO MONITORING STATION. EXISTING FACP CAN BE DEMOLISHED ONCE EXISTING CIRCUITS

AND DEVICES ARE FUNCTIONAL.

6. REMOVE EXISTING DEVICES AND CABLING ON A DEVICE BY DEVICE BASIS. REPLACE WITH NEW DEVICES AND CABLING. REUSE CONDUIT AND BACK BOXES WHERE EMBEDDED IN CMU WALLS. MAINTAIN EXISTING CIRCUITS FOR

FUNCTIONALITY OF SYSTEM.

7. AT THE END OF EACH WORK SESSION, CONDUCT A FUNCTIONAL TEST TO ENSURE THE SYSTEM IS FULLY

OPERATIONAL FOR OCCUPANCY THE FOLLOWING DAY.

8. COORDINATE INSTALLATION ACTIVITIES TO ENSURE THE BUILDING HAS COMPLETE AND CONTINUOUS COVERAGE AFTER EACH WORK PERIOD. PROVIDE FIRE WATCH DURING PERIODS OF DOWNTIME (ONLY PREAPPROVED OVER NIGHT AND/OR ON THE WEEKENDS). SYSTEM MUST BE COMPLETELY OPERATIONAL PRIOR TO THE BUILDINGS

HOURS OF OPERATION.

9. REMOVE ABANDONED CONDUIT WHERE NOT EMBEDDED IN MASONRY WALLS OR CONCRETE SLABS/WALLS.

10. FIELD VERIFY EXISTING CONDITIONS THAT MAY IMPACT SYSTEM INSTALLATION OR COMPLIANCE WITH NFPA 70, NFPA 72, UFC 3-600-01, AND NOTIFY THE CONTRACTING OFFICER PRIOR TO BEGINNING WORK.

11. ANY DAMAGE CAUSED BY DEMOLITION MUST BE REPAIRED (E.G., CEILING TILES, WALL FINISHES, SCREW HOLES, CONDUIT/DEVICE/EQUIPMENT REMOVAL).

PHASE AND DEMOLITION:

CONTROL PANEL:

1. THE FIRE ALARM MASS NOTIFICATION CONTROL PANEL (FMCP) MUST BE A SITE PROGRAMMABLE ADDRESSABLE

SYSTEM WITH VOICE EVACUATION.

2. THE FMCP MUST BE LOCATED IN A YEAR-ROUND ENVIRONMENTALLY CONDITIONED SPACE.

3. THE FMCP MUST HAVE AN 80 CHARACTER (MIN.) LCD ALPHANUMERIC DISPLAY AND A 400 EVENTS NON-VOLATILE

HISTORY LOG MEMORY.

4. CONTROL FUNCTIONS MUST BE ACCESSIBLE ONLY BY USER CODE OR SECURED BEHIND A LOCKED CABINET.

FI

R

E A

LA

R

M N

O

TE

S A

N D

L

EG

EN

D

FA001

12925878

PA/MIC

FAA

F

F

FF

F

S

FACP

F

FE

FE

FE

R T S

CG

C G

CG

C G

FS

P A /M

IC

0 8' 16'4'

FIRE ALARM - EXISTING FLOOR PLAN

PLAN

NORTH

EXISTING FACP TO REMAIN OPERATIONAL UNTIL THE NEW FMCP IS FULLY

FUNCTIONAL. ALL FIRE ALARM DEVICES H BE MIGRATED TO THE NEW FMCP

TO ENSURE CONTINUOUS PROTECTION. AFTER COMPLETION OF DEVICE

MIGRATION AND SYSTEM TESTED FOR FUNCTIONALITY, EXISTING FACP CAN

BE REMOVED.

A

B

C

D

2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

D E

P A

R T

M E

N T

O

T

H E

V

Y N

A V

A L

F

A C

I L I T

I E

S

E

N G

I N

E E

R I N

G

C

O M

M A

N D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M A

R I N

E

C

O R

P S

I

A

T I O

N

C

H E

R R

Y

P

O I N

T

N

C

F A

C I L I T

I E

S

E

N G

I N

E E

R I N

G

C Q

U I S

I T

I O

D

V

I S

I O

N M

C A

S

C

H E

R R

Y

P

O I N

T

C

H E

R R

Y

P

O I N

T

N

C

N E

W

F

I R

E

A

L A

M

Y S

T E

M

B

U I L D

I N

G

7348749

4 5

Suite 203 4520 Mint Hill Village Lane

Mint Hill, NC 28227

Fire Protection & Building Code Specialists

Lovett Consultants

Ph. 704.545.8383 NC Firm License No: F-0296

IN

RT

N

JE

NO

L.

T E

NA

040804

E NG

F

NI EER

OL

V

SEAL

S

A

SFORP

E H C

I

AL

OI N

OR L

T

E R

F I R

E

A

L A

R M

E X

I S

T I N

G

F

L O

L A

N

KEY NOTES

GENERAL SHEET NOTES

FD101

1. REFER TO FA001 FOR THE FIRE ALARM NOTES AND LEGEND.

2. REFER TO FA101 FOR THE FIRE ALARM FINAL FLOOR PLAN.

3. REFER TO FA401 FOR THE FIRE ALARM ENLARGED PLANS.

4. REFER TO FA501 FOR THE FIRE ALARM DETAILS.

12925879

FMCP F

CM

T S

F S

R T S

LOCS WP

TRNS

FAD

S

F

F

FFF

F

SS

S

CG CG CG

C

G

C G

CG CGCG

S S

S

W P

S

WP

W P

S

WP

S

WP

S

BATT

FAA

30 30 30 30

K P A /M

IC

0 8' 16'4'1 FIRE ALARM - FINAL REFLECTED CEILING PLAN

PLAN

NORTH

KEY NOTES

LISTED POLYCARBONATE PROTECTIVE COVER OVER FIRE ALARM PULL

STATION TO PREVENT PHYSICAL DAMAGE. ENSURE PROTECTION

DEVICE DOES NOT INTERFERE WITH OPERATION PER NFPA 72

REQUIREMENTS.

PROVIDE DEDICATED RED CIRCUIT BREAKERS FOR FIRE ALARM

SYSTEM AND MNS TRANSCEIVER. CLEARLY IDENTIFY CIRCUITS AT THE

PANEL AND EQUIP WITH A LOCK-OPEN DEVICE.

PA SYSTEM AUTOMATICALLY SILENCES UPON SYSTEM ACTIVATION TO

ENSURE CLEAR AUDIBILITY OF EMERGENCY MESSAGES.

RUN CONDUIT DOWN MULLION TO DEVICE AND SECURE IN PLACE.

SEAL ALL PENETRATIONS OF INTERIOR WALLS SMOKE-TIGHT USING

APPROVED FIRESTOP OR SMOKE SEALANT MATERIALS.

GENERAL SHEET NOTES

A

B

C

D

1 2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M

AR

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N , C

H

ER

R Y

PO

IN

T, N

C

FA

C

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

A

C Q

U

IS

IT

IO

N S

D

IV

IS

IO

N M

C

AS

C H

ER

R

Y

PO

IN

T

- C H

ER

R

Y

PO

IN

T, N C

N

EW

F

IR

E

AL

AR

M

S

YS

TE

M

BU

IL

D

IN

G

7348749

4 5

Suite 203 4520 Mint Hill Village Lane

Mint Hill, NC 28227

Fire Protection & Building Code Specialists

Lovett Consultants

Ph. 704.545.8383 NC Firm License No: F-0296

IN

RT

N

JE

NO

L.

TE

NA

040804

ENG

F

NI EER

OL

V

SEAL

S

A

SFORP

E H C

I

AL

OI N

OR L

T

ER

FI

R

E A

LA

R

M

FI

N A

L R

EF

LE

C

TE

D C

EI

LI

N G

P

LA

N

FA101

1. REFER TO FA001 FOR THE FIRE ALARM NOTES AND LEGEND.

2. REFER TO FD101 FOR THE FIRE ALARM EXISTING FLOOR PLAN.

3. REFER TO FA401 FOR THE FIRE ALARM ENLARGED PLANS.

4. REFER TO FA501 FOR THE FIRE ALARM DETAILS.

12925880

FMCP

TRNS

FAD

S

BATT

KEY NOTES

GENERAL SHEET NOTES

A

B

C

D

2 3 4 5

1 2 3

A

B

C

D

SCALE:

FED. WORK ORDER

SHEET

NAVFAC DRAWING NO.

DES DRW

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

DRAWFORM REVISION: 10 MARCH 2009

CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

OF

PROJECT NO.:

AS NOTED

N/A

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

D E

P A

R T

M E

T

V

Y N

A V

A L

F

A C

I L I T

I E

S

E

N G

I N

E E

R I N

G

C

O M

M A

N D

MC

AS

C

HE

RR

Y

PO

IN

T, N

C

CH

ER

RY

P

OI

NT

, N

C

M A

R I N

E

C

O R

A

T I O

N

C

H E

R R

Y

P

O I N

T

N

C

F A

C I L I T

I E

S

E

N G

I N

E E

R I N

Q

U I S

I T

I O

V

I S

I O

N M

C A

S

C

H E

R R

Y

P

O I N

T

C

H E

R R

Y

P

O I N

T

N

C

N E

W

F

I R

E

A

L A

S

T E

M

I L D

I N

G

7348749

4 5

Suite 203 4520 Mint Hill Village Lane

Mint Hill, NC 28227

Fire Protection & Building Code Specialists

Lovett Consultants

Ph. 704.545.8383 NC Firm License No: F-0296

IN

RT

N

JE

NO

L.

T E

NA

040804

E NG

F

NI EER

OL

V

SEAL

S

A

SFORP

E H C

I

AL

OI N

OR L

T

E R

F I R

E

A

L A

R M

E N

L A

R G

A

N S

1. REFER TO FA001 FOR THE FIRE ALARM NOTES AND LEGEND.

2. REFER TO FD101 FOR THE FIRE ALARM EXISTING FLOOR PLAN.

3. REFER TO FA101 FOR THE FIRE ALARM FINAL FLOOR PLAN.

4. REFER TO FA501 FOR THE FIRE ALARM DETAILS.

FA401

0 2' 4'1'

FIRE ALARM ENLARGED PLAN - 105

PLAN

NORTH

SECTION - 105

0 2' 4'1'

CABINET PLACEMENT SUGGESTIVE, CONTRACTOR TO FINALIZE

PLACEMENT VIA SHOP DRAWINGS.

PROVIDE THE ENCLOSURES WITH PROTECTION AGAINST DAMAGE FROM

THE DOOR SWING. DOOR LEAF MUST REMAIN OPERATIONAL.

12925881

BATTERIES

S/P

MIC

S/PDACT

S/P

F TS FS

EOL

CM

S

RTS

S

EOL

EOL

LOC

PA

MM CM

S

EOL

B E

T W

E E

N

O P

E R

A B

R

T

SPEAKER/STROBE

STROBE OR

M

I N

FMCP

FLOOR

12" MAX.

4" MIN.

4"

MIN.

5'-0"

MIN.

SMOKE

DETECTOR

CONDUIT

CEILING

C

O N

T R

O L S

WALL MOUNTED

SUPPLY OR

RETURN GRILL

S T

R O

SMOKE DETECTOR

LOC

FAA

CEILING BRIDGE

A

C

T

U

A

D

I

B

O

U

B

G

N

N

E

L

A

C

T

U

A

D

I

B

P

E

R

V

I

S

O

G

N

N

E

L

A

C

T

U

A

M

M

O

U

B

G

N

D

I

C

A

T

O

R

A

C

T

U

A

D

I

B

A

G

N

N

E

L

A

C

T

U

A

M

M

A

G

N

D

I

C

A

T

O

R

S

Y

S

T

T

P

U

T

S

A

C

T

U

A

M

M

P

E

R

V

I

S

O

G

N

D

I

C

A

T

O

R

A B C D E F G H I J K L M N O P Q R

A

C

T

I

V

A

D

I

B

V

I

C

E

T

R

A

N

S

M

O

U

B

G

N

P

A

R

T

M

E

N

T

CEILING MOUNTED SMOKE DETECTOR ACTIVATION

MANUAL PULL STATION - FIRE

A

C

T

U

A

S

U

T

I

F

I

C

A

T

I

O

N

A

C

T

U

A

D

I

B

T

I

F

I

C

A

T

I

O

N

A

C

T

I

V

A

D

I

B

R

R

E

S

P

O

N

D

I

S

S

A

G

E

BASE MNS

OPEN CIRCUIT

FMCP - AC POWER FAILURE

FMCP - LOW OR MISSING BATTERY

LOCAL MNS MICROPHONE ACTIVATION

LOCAL MNS ACTIVATION (LOC, ACU)

GROUND FAULT

NOTIFICATION CIRCUIT (NAC) - SHORT

T

R

A

N

S

M

P

G

N

P

A

R

T

M

E

N

T

I

N

T

E

R

R

U

A

D

I

B

G

N

T

P

U

T

S

S T

S

I

L

E

N

E

A

K

E

R

HVAC DUCT SMOKE DETECTOR ACTIVATION

T

R

A

N

S

M

A

P

A

R

T

M

E

N

T

I

N

I

T

I

A

U

T

D

O

W

S

O

C

I

A

T

W

O

K

T

E

C

T

A

N

S

F

W

T

T

E

R

I

E

S

A B C D E F G H I J K L M N O P Q R S T

SPRINKLER FLOW SWITCH

TAMPER SWITCH

ANNUNCIATION AT

LOCAL PANEL

NOTIFICATION

AU

XI

LIA

RY

FU

NC

TI

ON

S

SYSTEM INPUTS

SEE FLOOR PLAN FOR EXACT NUMBER AND LOCATION OF INITIATION

DEVICES.

4 FEET ABOVE THE APEX OF THE ROOFLINE WITH A UL LISTED

WEATHERHEAD.

CIRCUIT PROVIDED W/ RED BREAKERS, LOCK OPEN DEVICE FED FROM THE

SAME ELECTRIC PANEL.

MIGRATE EXISTING SLC AND NAC CIRCUITS TO THE NEW…