7328941 DWG as One SIGNED.pdf
PDF 6 MB Posted
- Solicitation number
- 7328491
About this file
This file contains construction drawings and technical specifications for a fuel dispensing system repair project at Marine Corps Air Station Cherry Point, North Carolina. The project involves repairing and upgrading the fuel dispensing system at Building 4049, with work order number 7328491, under the Naval Facilities Engineering Command Mid-Atlantic.
The scope includes demolition of existing underground double-wall fuel piping and electrical systems, installation of new flexible double-wall fuel piping (UL971 compliant) from existing above-ground storage tanks to fuel dispensers, replacement of fuel control systems including a new Veeder Root TLS-450 fuel tank controller, installation of emergency shutoff systems, and associated electrical work including new conduit routing and panel modifications. The project requires soil sampling and testing per EPA Method 8015C for petroleum contamination where existing fuel piping is removed, with proper disposal of contaminated materials per North Carolina Department of Environmental Quality regulations. All work must comply with NFPA codes for hazardous locations, UFC standards, and environmental regulations, with a minimum one-year warranty required upon beneficial occupancy. The drawings were finalized on October 12, 2023, and include civil, mechanical, and electrical plans with detailed specifications for materials and installation methods.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 7328491 RFP Final.pdf | ||
| 7328491 SPEC as One SIGNED.pdf | ||
| 7328491 RFP.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T4820D
T4820L
T4820B
T4820F
3976P
T4820I
1791 4601
R
IF
LE
R
AN
G
E R
O
AD
D U
FF
Y
R O
AD
ACCESS ROAD
MARINE CORPS AIR STATION
CHERRY POINT, NORTH CAROLINA
REPAIR FUEL DISPENSING SYSTEM (B4049)
WO# 7328491
RIVER
New Bern
Dover
Tuscarora KinstonUS 70
NEUSE
Pollocksville
Trenton Seven Springs
Otway
Beaufort
US 70
Morehead City
N
E O
C A
MaysvilleComfort
US 17
Verona
Folkstone
Dixon
Holly Ridge
NEW RIVER
Pink
Beulaville
Hill
US 117
US 421
Wallace
Jacksonville
Richlands
I
T C
A N
US
Hampstead
T L
Scott Hill
A
Burgaw
Leland Wilmington
Havelock
Swansboro
VICINITY MAP - MCAS CHERRY POINT, N.C.
Words Corner
C O
V E
R S
H E
E T
A N
D
IN
D E
X
12882694
G-001
US 74 & 76
INDEX OF DRAWINGS
GENERAL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
G-001 12882694 1 COVER SHEET AND INDEX
G-002 12882695 2 GENERAL NOTES
EXISTING CONDITIONS
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
VF100 12882696 3 CIVIL EXISTING CONDITIONS PLAN
CIVIL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
C-001 12882697 4 CIVIL GENERAL NOTES, LEGENDS, AND ABBREVIATIONS
CD100 12882698 5 CIVIL DEMOLITION PLAN
CS100 12882699 6 CIVIL SITE PLAN
C-500 12882700 7 CIVIL DETAILS
MECHANICAL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
M-001 12882701 8 MECHANICAL NOTES, ABBREVIATIONS AND LEGENDS
MD101 12882702 9 MECHANICAL DEMOLITION PLAN
MP101 12882703 10 MECHANICAL FUEL PLAN
M-501 12882704 11 MECHANICAL DETAILS
ELECTRICAL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
E-001 12882705 12 ELECTRICAL DETAILS, ABBREVIATIONS AND LEGENDS
E-002 12882706 13 ELECTRICAL DEMOLITION AND GENERAL NOTES
E-003 12882707 14 ELECTRICAL PANEL SCHEDULES AND DETAILS
ED101 12882708 15 ELECTRICAL DEMOLITION PLAN
ED102 12882709 16 ELECTRICAL DEMOLITION PLAN
EP101 12882710 17 ELECTRICAL POWER AND CONTROL PLAN
EP102 12882711 18 ELECTRICAL POWER AND CONTROL PLAN
B4049 FUEL
DISPENSING
SYSTEM
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
M
ID
AT
LA
NT
IC
RE
PA
IR
F
UE
L D
IS
PE
NS
IN
G
SY
ST
EM
(B
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
FINAL SUBMISSION - 10-12-2023
7328491
SUPPORT TRA INING
MCAS CHERRY POINT, NC
FINAL
11/21/2023
G E
N E
R A
L N
O
TE
S
12882695
G-002
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
M
ID
AT
LA
NT
IC
RE
PA
IR
F
UE
L D
IS
PE
NS
IN
G
SY
ST
EM
(B
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
FINAL SUBMISSION - 10-12-2023
7328491
SUPPORT TRA INING
MCAS CHERRY POINT, NC
GENERAL DESIGN AND CONSTRUCTION NOTES:
1. ANY REFERENCES TO STATE GOVERNMENT, FEDERAL GOVERNMENT, OR INDUSTRY
STANDARDS OR SPECIFICATION MADE HEREIN SHALL FORM A PART OF THE WORK TO THE
EXTENT REFERENCED THERETO AND ALL MATERIALS AND WORKMANSHIP UNDER THIS
CONTRACT SHALL COMPLY WITH OR EXCEED THESE STANDARDS AND REFERENCE. ALL
REFERENCED STANDARDS SHALL BE THE LATEST EDITION.
2. ALL MANUFACTURED EQUIPMENT AND PRODUCTS SHALL BE NEW MATERIALS IN UNDAMAGED
CONDITION AND INSTALLED AS PER MANUFACTURER'S LATEST PRINTED INSTRUCTIONS,
UNLESS SPECIFIED OTHERWISE HEREIN.
3. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTION OF EXISTING FACILITIES & EQUIPMENT
FROM DAMAGE DURING INSTALLATION OF THE WORK AND DURING TESTING OPERATIONS.
4. CONTRACTOR SHALL TAKE INTO ACCOUNT THE SPECIAL TREATMENT OF ANY HAZARDOUS
WASTE, AS WELL AS THE RELATED ENVIRONMENTAL IMPLICATIONS. COORDINATE WITH
CONTRACTING OFFICER REGARDING AVAILABLE TEST REPORTS ON ANY EXISTING
CONDITIONS. REFER ALSO TO GEOTECHNICAL REPORT WHICH IS AVAILABLE UPON REQUEST,
IF APPLICABLE TO THE PROJECT SCOPE. EVERY EFFORT SHALL BE MADE TO RECYCLE
ELIGIBLE MATERIALS, AND THOSE NOT SUITABLE, SHALL BE DISPOSED OF OFF BASE IN
ACCORDANCE WITH THE REQUIREMENTS OF THE (NCDEQ) NORTH CAROLINA DEPARTMENT OF
ENVIRONMENTAL QUALITY.
5. ENSURE THAT ANY DEMOLITION, UTILITY CUT AND CAPPING, AND DEBRIS REMOVAL SERVICE
PERFORMED AT THE BASE IS COMPLETED IN SUCH A MANNER THAT WILL RESTORE A NEAT
AND PROFESSIONAL APPEARANCE OF BASE AREAS.
6. THE FACILITY/AREA SHALL BE CLEANED IN ITS ENTIRETY, INCLUDING EXTERIOR AREAS,
BEFORE BEING RETURNED TO THE GOVERNMENT.
WARRANTY:
1. CONTRACTOR SHALL FURNISH A MINIMUM ONE YEAR WARRANTY AGAINST DEFECTS IN
MATERIAL AND WORKMANSHIP STARTING ON THE BENEFICIAL OCCUPANCY DATE.
GENERAL INFORMATION:
1. THE CONTRACTOR SHALL PROVIDE ALL MANAGEMENT, TOOLS, SUPPLIES, EQUIPMENT, LABOR, AND APPLICABLE LICENSES AND PERMITS NECESSARY TO COMPLETE THE PROJECT. ALL
WORK SHALL BE DONE IN STRICT ACCORDANCE WITH THE CONTRACTING DOCUMENTS, THE
STATEMENT OF WORK (SOW) AND SUBJECT TO THE TERMS AND CONDITIONS OF THE
CONTRACT AND IN ACCORDANCE WITH (UFC) UNITED FACILITIES CRITERIA, UNIFIED FACILITIES GUIDE SPECIFICATIONS (UFGS), THE INTERNATIONAL BUILDING CODE (IBC), INTERNATIONAL
PLUMBING CODE (IPC), NATIONAL ELECTRICAL CODE (NEC), NATIONAL ELECTRICAL SAFETY
CODE (NESC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), EPA 402-K-01-001 (2008), NORTH CAROLINA DEPARTMENT OF TRANSPORTATION (NCDOT), NORTH CAROLINA
DEPARTMENT OF ENVIRONMENTAL QUALITY (NCDEQ), BASE DESIGN AND CONSTRUCTION
STANDARDS INCLUDING BASE EXTERIOR ARCHITECTURAL PLAN (BEAP), AND ALL OTHER
APPLICABLE CODES.
WORKING CONDITIONS:
1. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONS TO INSURE THAT OPERATIONS ARE
CONDUCTED IN A MANNER AS TO MINIMALLY INTERFERE WITH THE NORMAL OPERATIONS OF
THE BASE AND THE SAFETY AND CONVENIENCE OF BASE PERSONNEL. THE CONTRACTOR
SHALL COORDINATE UTILITY OUTAGES WITH THE APPROPRIATE BASE UTILITY SERVICE OFFICE
AND THE USER.
GENERAL PROJECT NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL DIMENSIONS, QUANTITIES AND SQUARE
FOOTAGES. ALL DIMENSIONS, QUANTITIES AND SQUARE FOOTAGES INCLUDED ARE
APPROXIMATIONS. CONSTRUCTION AND DEMOLITION SHALL BE IN STRICT ACCORDANCE WITH
THE BASE DESIGN AND CONSTRUCTION STANDARDS. THE INFORMATION PROVIDED IN THE
STATEMENT OF WORK (SOW), THE PROVIDED DRAWINGS, AND THE REQUIREMENTS OF THE
BASE. DESIGN AND CONSTRUCTION STANDARDS SHALL BE DETERMINED TO BE THE MINIMUM
STANDARDS REQUIRED IN THIS PROJECT.
2. THE CONTRACTOR SHALL VIDEO ALL AREAS IN WHICH WORK SHALL OCCUR PRIOR TO
STARTING WORK TO INCLUDE INTERIOR AND EXTERIOR JOB SITE AND SURROUNDING AREA.
UFC'S TAKE PRECEDENCE OVER ALL STANDARDS, CODES AND BASE DESIGN STANDARDS AND
REQUIREMENTS THAT PERTAIN TO THE WORK WITHIN THIS SOW.
3. DURING CONSTRUCTION, THE CONTRACTOR SHALL TAKE CARE NOT TO DAMAGE EXISTING
STRUCTURES, ETC. THAT WILL NOT BE REPLACED AS PART OF THIS CONTRACT. CONTRACTOR
SHALL BE RESPONSIBLE FOR THE TEMPORARY SUPPORT OF ALL DEVICES AS REQUIRED TO
PERFORM WORK. ANY DEMOLITION WORK THAT NEEDS TO BE ACCOMPLISHED TO COMPLETE
THE CONTRACT IS THE RESPONSIBILITY OF THE CONTRACTOR. ALL MATERIAL SHALL BE
INSTALLED PER MANUFACTURERS' RECOMMENDATIONS. ALL ITEMS LISTED IN THE SOW ARE
TO BE SUPPLIED AND INSTALLED BY THE CONTRACTOR UNLESS OTHERWISE NOTED.
4. A PRE-CONSTRUCTION MEETING WILL BE HELD AT THE BASE TO INCLUDE THE CONTRACTOR
AND GOVERNMENT REPRESENTATIVES. THE GOVERNMENT SHALL SET UP THIS MEETING WITH
THE CONTRACTOR AND GOVERNMENT REPRESENTATIVES, TO DISCUSS ALL PERTINENT
PROJECT REQUIREMENTS, AS WELL AS ANY OTHER CONSTRUCTION ISSUES THE
CONTRACTOR MAY HAVE. WHERE FINISHES ARE PART OF THE PROJECT SCOPE, ALL FINISHES
SHALL BE PRESENTED TO THE CONTRACTING OFFICER AS ONE SUBMITTAL FOR SELECTION
AND APPROVAL PRIOR TO INSTALLATION. ALL MATERIAL THAT COULD BE DISCONTINUED
SHALL BE ON-SITE, PRIOR TO STARTING PROJECT SO THERE WILL BE NO DIFFERENCE IN
COLOR OR PATTERN.
5. WHERE SPECIFIC PART NUMBERS OR MANUFACTURERS ARE REFERENCED, IT SHALL BE
UNDERSTOOD THAT THE CONTRACTOR MAY SUBMIT A PROPOSED EQUAL FOR
CONSIDERATION.
6. THE TERM "SHALL" WHERE USED IS EQUIVALENT TO "MUST". ALL WORK AND MATERIALS
NOTED ARE NEW UNLESS NOTED OTHERWISE.
7. THE TERM "INSTALL" WHERE USED IS EQUIVALENT TO "PROVIDE", (FURNISH AND INSTALL
COMPLETE).
MW
PT 800
NORTHING: 431449.3300'
EASTING: 2636324.3620'
ELEVATION: 23.41'
DI
RIM 20.84'
CB
DI
RIM 21.33'
CB
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
XXXXXXXXXXXXXXXXXX
GAS PUMP
GAS PUMP
LP
FUEL
TANK FUEL
TANK
S
SS
SS
SS
SS
SS
W
WW
W
WWWW
UP
UP
UP
UP
U P
U P
METAL LID
RIM 22.36'
METAL LID
RIM 22.46'
METAL LID
RIM 22.38'
RAISED CONCRETE
FUEL ISLAND
CONTROL POINT: 801
299.69'
S84° 26' 45.41"W
MW
LIGHT POLE
FUEL PUMP/
DISPENSE
(TYP)
BOLLARD
(TYP)
MONITORING
WELL
UNDERGROUND
JUNCTION
BOXES
FUEL SPILL
CONTAINMENT
UNIT
ELEC. BOX WITH
RAISED LIGHT
PROJECT LIMITS
22.5
22.0
21.5
22.0
23.0
RI
FL
E
RA
NG
E
RD
B4049
X X
X X
X X
X
XXXXXX
X X
X X
X
X
X X
PROJECT LIMITS
1"=20'-0"SCALE:
10' 20' 40' 60'0
CIVIL EXISTING CONDITIONS
PLAN
NORTH
1" = 20'
C
IV
IL
E
X
IS
TI
N
G C
O N
D
IT
IO
N
S P
LA
N
12882696
VF100
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
M
ID
AT
LA
N
TI
C
R
EP
AI
R
F U
EL
D
IS
PE
N
SI
N G
S
YS
TE
M
(B
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
GENERAL SHEET NOTES
FINAL SUBMISSION - 10-12-2023
7328491
SUPPORT TRA INING
MCAS CHERRY POINT, NC
SURVEY NOTES
1. SEE SHEET C-001 FOR CIVIL GENERAL NOTES, LEGENDS, AND
ABBREVIATIONS.
1. EXISTING CONDITIONS SURVEY PERFORMED BY CAPE FEAR
ENGINEERING IN MAY 2023.
2. SURVEY CONTROL DATA ESTABLISHED, UTILIZING NORTH
CAROLINA VIRTUAL REFERENCE STATION (VRS) SYSTEM.
3. HORIZONTAL DATUM IS NAD '83 AND ELEVATIONS ARE BASED ON
NAVD '88 (2011) VERTICAL DATUM.
4. CONTROL POINTS:
N: 431449.33' E: 2636324.362'
ELEV: 23.41'
N: 431420.3242' E: 2636026.0751'
ELEV: 23.26'
5. UNDERGROUND UTILITIES, LOCATED BY CAPE FEAR
ENGINEERING USING A COMBINATION OF GPR, LOCATING
EQUIPMENT, AND VISIBLE PHYSICAL EVIDENCE.
6. AT TIME OF SURVEY THERE WERE NUMEROUS VEHICLES,
DUMPSTERS, CONNEX BOXES, AND OTHER ITEMS LOCATED
THROUGHOUT THE SITE. THESE ITEMS WERE NOT SURVEYED.
KEY PLAN
PLAN
NORTH
1" = 100'
1"=100'-0"SCALE:
50' 100' 200' 300'
C
IV
IL
G
E N
E R
A L
N O
TE
S
, L E
G E
N D
S , A
N D
A B
B R
E V
IA
TI
O N
S
12882697
C-001
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
M
ID
AT
LA
N
TI
C
R
EP
AI
R
F U
EL
D
IS
PE
N
SI
N G
S
YS
TE
M
(B
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
FINAL SUBMISSION - 10-12-2023
7328491
SUPPORT TRA INING
MCAS CHERRY POINT, NC
CIVIL GENERAL NOTES:
1. REFER TO THE PROJECT SPECIFICATIONS IN ALL SITUATIONS. BRING CONFLICTS BETWEEN PROJECT SPECIFICATIONS AND PLANS TO THE ATTENTION OF THE CONTRACTING OFFICER AND/OR ENGINEER FOR RESOLUTION. ALL MATERIALS
AND WORKMANSHIP MUST CONFORM TO THE PROJECT SPECIFICATIONS.
2. EXISTING UTILITY INFORMATION IS NOT TO BE RELIED ON AS BEING EXACT OR COMPLETE. LOCATION, VERIFICATION, SUPPORT AND PROTECTION OF ALL ABOVE GROUND AND UNDERGROUND UTILITIES TO REMAIN IN PLACE, INCLUDING ANY UTILITIES NOT INDICATED ON CONTRACT DRAWINGS IS REQUIRED. ANY CONFLICTS OR DISCREPANCIES MUST BE BROUGHT TO THE CONTRACTING OFFICER'S AND/OR ENGINEER'S ATTENTION IMMEDIATELY. CAPE FEAR ENGINEERING
HAS NOT PHYSICALLY LOCATED ANY UNDERGROUND UTILITIES.
3. PRIOR TO ANY EXCAVATION, CONTRACTOR MUST HAVE THE EXISTING UNDERGROUND LINES MARKED ON THE GROUND SURFACE IN THE AREAS OF CONSTRUCTION. POTHOLE AND PHYSICALLY VERIFY DEPTH AND LOCATION OF ALL UTILITY LINES IN THE WORK AREA THAT REQUIRE COORDINATION WITH WORK ITEMS. POTHOLE VERIFICATION MUST BE DONE WELL IN ADVANCE OF ACTUAL WORK SO THAT POTENTIAL UTILITY CONFLICTS CAN BE VERIFIED AND RESOLVED
WITHOUT CAUSING SCHEDULE DELAYS.
4. PROTECT ALL EXISTING STRUCTURES, TREES, PAVEMENT, UTILITIES, AND OTHER PROPERTY UNLESS THEY ARE TO BE DEMOLISHED. ANY PROPERTY NOT AUTHORIZED FOR REMOVAL, BUT DAMAGED BY THE CONTRACTOR MUST BE RESTORED BY THE CONTRACTOR TO THEIR PRE-CONSTRUCTION CONDITION OR BETTER AT NO ADDITIONAL EXPENSE TO
THE OWNER.
5. MAKE EVERY EFFORT TO SAVE PROPERTY IRONS, MONUMENTS, OTHER PERMANENT POINTS AND LINES OF REFERENCE AND CONSTRUCTION STAKES. PROPERTY IRONS, MONUMENTS, AND OTHER PERMANENT POINTS OF REFERENCE
DESTROYED BY THE CONTRACTOR MUST BE REPLACED AT THE CONTRACTOR'S EXPENSE.
6. WORK PERFORMED UNDER THIS CONTRACT MUST NOT IMPACT THE OPERATION OF ANY ADJACENT PROPERTIES UNLESS
A UTILITY OUTAGE HAS BEEN APPROVED IN ADVANCE.
7. SEQUENCE WORK AS NECESSARY TO ENSURE THAT ALL UTILITY SERVICES, INCLUDING FIRE HYDRANTS, REMAIN
OPERATIONAL DURING CONSTRUCTION.
8. RESTORE ANY ACCESS ROADS AND STAGING AREAS USED BACK TO THEIR PRE-CONSTRUCTION CONDITION OR BETTER.
VEGETATE ALL DISTURBED AREAS IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
9. TAKE ADEQUATE PROTECTIVE MEASURES TO ENSURE THAT EXISTING PAVEMENT SURFACES ARE NOT DAMAGED FROM TRACKED CONSTRUCTION EQUIPMENT OR ANY OTHER POSSIBLE SOURCE WHEN EQUIPMENT IS BEING MOVED. REPAIR ANY PAVED AREAS DAMAGED DURING CONSTRUCTION TO THEIR PRE-CONSTRUCTION CONDITION OR BETTER.
10. EXISTING PAVEMENTS AND ALL OTHER AREAS ADJACENT TO THE SITE MUST BE KEPT CLEAN AT ALL TIMES. DO NOT
ALLOW BUILD UP OF SOIL, MUD, DUST OR OTHER DEBRIS.
11. CONTRACTOR IS RESPONSIBLE FOR ALL SURVEYING AND STAKING TO COMPLETE THE WORK.
12. ANY AND ALL MATERIAL QUANTITIES INDICATED ON THIS PLAN SET ARE FOR REFERENCE ONLY. CONTRACTOR MUST
VERIFY ALL MATERIAL QUANTITIES SHOWN.
13. KEEP REDLINE MARK-UPS OF ANY CHANGES MADE FROM THE APPROVED PLAN AND PROVIDE COPY OF REDLINES TO
ENGINEER UPON PROJECT COMPLETION.
EXISTING CONDITION NOTES:
1. SEE SHEET VF100 FOR EXISTING CONDITIONS AND SURVEY INFORMATION.
OFFSITE BORROW AREA NOTES
1. CONTRACTOR IS RESPONSIBLE FOR ENSURING OFFSITE BORROW AREA HAS AN APPROVED EROSION CONTROL PERMIT
AND APPROPRIATE MEASURES IN PLACE PRIOR TO LAND DISTURBING ACTIVITY.
2. NO BORROW MATERIALS ARE AVAILABLE ON GOVERNMENT PROPERTY.
DEMOLITION PLAN NOTES:
1. LOCATE UNDERGROUND UTILITIES AND COORDINATE DEMOLITION AND / OR RELOCATION WORK. SPECIFICALLY TAKE EXTRA CAUTIONARY MEASURES TO PREVENT DISRUPTION OF ANY TELECOM FIBER IN THE PROJECT AREA. ONCE LOCATED IN THE FIELD, POSITIVE VERIFICATION BY POTHOLING IS REQUIRED. REPORT ANY CONFLICTS OR
DISCREPANCIES TO ENGINEER.
2. LIMITS OF DEMOLITION AND DIMENSIONS ARE SHOWN FOR GENERAL REFERENCE. CONTRACTOR MUST BE RESPONSIBLE FOR REMOVAL OF ALL ITEMS, INCLUDING ALL EXCAVATED MATERIALS NECESSARY TO COMPLETE WORK WITHIN THIS
CONTRACT.
3. WHERE ASPHALT/CONCRETE DEMOLITION IS REQUIRED, USE A SAW CUT AT THE LIMITS OF DEMOLITION OR NEAREST
JOINT TO OBTAIN A CLEAN VERTICAL EDGE.
4. DEDICATED DEMOLITION AND OTHER WASTE AREAS/EARTHEN MATERIAL STOCKPILES MUST BE LOCATED AT LEAST 50'
FROM STORMDRAINS OR STREAMS.
5. REPORT ANY UNSUITABLE SOILS, CONTAMINATED SOILS, AND BURIED CONCRETE AND DEBRIS TO THE CONTRACTING
OFFICER.
6. UNDERGROUND UTILITIES SHOWN ON THE DEMOLITION PLANS MAY EXTEND FURTHER THAN SHOWN. CONTRACTOR IS RESPONSIBLE FOR COMPLETE REMOVAL OF UTILITIES WITHIN THE ENTIRE PROJECT SITE UNLESS OTHERWISE NOTED.
STORMWATER AND GRADING NOTES:
1. DURING CONSTRUCTION, PERFORM GRADING IN A MANNER AND SEQUENCE THAT WILL PROVIDE PROPER DRAINAGE AT
ALL TIMES.
2. ADJUST AND/OR CUT EXISTING PAVEMENT AS NECESSARY TO ASSURE A SMOOTH FIT AND CONTINUOUS GRADE.
3. UPON THE COMPLETION OF CONSTRUCTION AND SITE STABILIZATION, ALL NEW PIPES AND EXISTING PIPES IMPACTED BY CONSTRUCTION MUST BE CLEANED TO REMOVE ALL ACCUMULATED SILT, SEDIMENT AND DEBRIS.
EROSION CONTROL NOTES:
1. TOTAL DISTURBED AREA IS LESS THAN 1.0 ACRE. A LAND DISTURBANCE PERMIT IS NOT REQUIRED.
2. ALL EROSION AND SEDIMENT CONTROL MEASURES MUST BE IN ACCORDANCE WITH THE NORTH CAROLINA
SEDIMENTATION AND EROSION CONTROL DESIGN MANUAL (LATEST EDITION).
3. PROVIDE POSITIVE DRAINAGE AWAY FROM THE SITE AT ALL TIMES.
4. IF UNFORESEEN EROSIVE CONDITIONS DEVELOP DURING CONSTRUCTION AS THE RESULT OF INCREASED RUNOFF OR SEDIMENT DISPLACEMENT, THE CONTRACTOR SHALL TAKE ACTION TO REMEDY SUCH CONDITIONS AND PREVENT
DAMAGE TO ADJACENT PROPERTIES.
5. EROSION AND SEDIMENT CONTROL MEASURES SHALL BE MAINTAINED CONTINUOUSLY, RELOCATED WHEN NECESSARY, AND SHALL BE CHECKED FOR STABILITY AND PROPER FUNCTIONING AFTER EVERY RAINFALL EVENT.
SIGNAGE, STRIPING, AND MARKING NOTES:
1. THE CONTRACTOR IS RESPONSIBLE FOR ALL PEDESTRIAN AND VEHICULAR TRAFFIC DETOURS AND MUST USE APPROPRIATE SIGNAGE AND BARRICADES IN ACCORDANCE WITH ALL BASE, STATE, AND FEDERAL REQUIREMENTS.
2. ALL ROAD AND LANE CLOSURES MUST BE REQUESTED AND APPROVED BY THE CONTRACTING OFFICER PRIOR TO
CLOSING OF ANY ROADWAYS.
3. ALL ROAD CLOSURES MUST BE SUBMITTED TO THE CONTRACTING OFFICER A MINIMUM OF 15 DAYS PRIOR TO THE REQUIRED DATE OF CLOSURE AND MUST INCLUDE A TRAFFIC CONTROL PLAN IN ACCORDANCE WITH MUTCD AND EM 385-1-1.
4. ALL TRAFFIC CONTROL METHODS AND DEVICES, BOTH TEMPORARY AND PERMANENT, MUST BE IN ACCORDANCE WITH THE U.S. DEPARTMENT OF TRANSPORTATION FEDERAL HIGHWAY ADMINISTRATION'S "MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES" (MUTCD), MOST RECENT EDITION AND THE NORTH CAROLINA DEPARTMENT OF TRANSPORTATION
(NCDOT).
5. ANY EXISTING PAVEMENT MARKINGS IN THE VICINITY OF THE PROJECT LIMITS THAT ARE DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED TO THE CONTRACTING OFFICER'S SATISFACTION.
ABBREVIATIONS
SYMBOL LEGEND:
DETAIL
REFERENCE
SECTION
DETAIL TITLE
NOT TO SCALE
VIEW TITLE
DETAIL TITLE
IDENTIFICATION
NUMBER
SHEET # FOR
SECTION/DETAIL
SCALE
IDENTIFICATION
NUMBER
IDENTIFICATION
NUMBER
SHEET # FOR
SECTION/DETAIL
C-500
A1
C-500
SCALE
A/C AIR CONDITIONER
ATFP ANTI TERRORISM FORCE PROTECTION
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMP BEST MANAGEMENT PRACTICE
BW BARBED WIRE
C&G CURB AND GUTTER
CB CATCH BASIN
CC CONCRETE CURB
CI CURB DROP INLET
CJ CONTRACTION JOINT
CLF CHAIN LINK FENCE
CMH COMMUNICATION MANHOLE
CONC CONCRETE
D/B DESIGN/BUILD
DCJ DOWELED CONSTRUCTION JOINT
DI DROP INLET
DPW DEPARTMENT OF PUBLIC WORKS
DUMP DUMPSTER
E EAST
EHH ELECTRICAL HANDHOLE
EG EXISTING GAS
EJ EXPANSION JOINT
ELEC ELECTRIC
EMH ELECTRICAL MANHOLE
EL ELEVATION
FDC FIRE DEPARTMENT CONNECTION
FES FLARED END SECTION
FFE FINISH FLOOR ELEVATION
FL FLOW LINE
GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
HW HEAD WALL
IE INVERT ELEVATION
LP LIGHT POLE
LSA LANDSCAPE STONE
MAT MATERIAL
MH MANHOLE
MOF METAL ORNAMENTAL FENCE
MUTCD MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES
N NORTH
NCDEQ NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY
NCDOT NORTH CAROLINA DIVISION OF TRANSPORTATION
NE NORTHEAST
NIC NOT IN CONTRACT
NOAA NATIONAL OCEANIC AND ATMOSPHERIC ADMINISTRATION
NW NORTHWEST
PNG PIEDMONT NATURAL GAS
PP POWER POLE
PT PHYSICAL TRAINING
PVC POLYVINYL CHLORIDE
RCP REINFORCED CONCRETE PIPE
S SOUTH
SCM STORMWATER CONTROL MEASURE
SDMH STORM DRAIN MANHOLE
SE SOUTHEAST
SEP SEPARATION
SMH SANITARY SEWER MANHOLE
STA STATION
STY STORY
SW SOUTHWEST
TC TOP OF CURB
TD TRENCH DRAIN
TE THICKENED EDGE
TEJ THICKENED EDGE EXPANSION JOINT
THH TELECOMMUNICATION HANDHOLE
TMH TELECOMMUNICATION MANHOLE
TRANS TRANSFORMER
TSB TEMPORARY SEDIMENT BASIN
TYP TYPICAL
UG UNDERGROUND
UNK UNKNOWN
VIF VERIFY IN FIELD
W WEST
W/BW WITH BARBED WIRE
WV WATER VALVE
WW WING WALL
VIEW TITLE
1" = 20'
PLAN
NORTH
ASPHALT PAVEMENT
CONCRETE PAVEMENT
CONCRETE PAD
PROTECTIVE BOLLARD
LIGHT POLE
SYMBOL LEGEND
DESCRIPTION
SITE
DEMO PROPOSEDEXISTING
ELECTRICAL
UNDERGROUND
DESCRIPTION DEMO PROPOSEDEXISTING
LINETYPE LEGEND
UP UP UPUP UP\ \ \ \ \ \ \ \ \ \
X X X X XCHAINLINK FENCE X X X X XX X X X X\ \ \ \ \ \ \ \ \ \
SITE
FUEL LINE G G \ \ \ \ \ \ \ \ \ \G G G
DI
RIM 20.84'
CB
DI
RIM 21.33'
CB
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
XXXXXXXXXXXXXXXXXX
GAS PUMP
GAS PUMP
LP
G G
G
G
G
G
G
G
G
G
G G
G
G G
G G
G G
G
G
G
G
G
G
G
G
G G
G G
FUEL
TANK FUEL
TANK
S
SS
SS
SS
SS
SS
W
WW
W
WWWW
UP
UP
UP
UP
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
UP
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
UP
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
U P
METAL LID
RIM 22.36'
METAL LID
RIM 22.46'
METAL LID
RIM 22.38'
RAISED CONCRETE
FUEL ISLAND
MW
LIGHT POLE
FUEL PUMP/
DISPENSE
(TYP)
BOLLARD
(TYP)
MONITORING
WELL
UNDERGROUND
JUNCTION
BOXES
FUEL SPILL
CONTAINMENT
UNIT
ELEC. BOX WITH
RAISED LIGHT
PROJECT LIMITS
22.5
22.0
21.5
22.0
23.0
TYP.
TYP.
TYP.
RI
FL
E
RA
NG
E
RD
B4049
X X
X X
X X
X
XXXXXX
X X
X X
X
X
X X
PROJECT LIMITS
C
IV
IL
D
E M
O
LI
TI
O
N P
LA
N
12882698
CD100
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
M
ID
AT
LA
N
TI
C
R
EP
AI
R
F U
EL
D
IS
PE
N
SI
N G
S
YS
TE
M
(B
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
FINAL SUBMISSION - 10-12-2023
7328491
SUPPORT TRA INING
MCAS CHERRY POINT, NC
1"=20'-0"SCALE:
10' 20' 40' 60'0
CIVIL DEMOLITION PLAN
PLAN
NORTH
1" = 20'
SHEET KEYNOTES
1. SEE SHEET C-001 FOR CIVIL GENERAL NOTES, LEGENDS, AND
ABBREVIATIONS.
2. SOIL SAMPLING AND TESTING ARE REQUIRED FOR ALL
SUBGRADE BELOW AREAS WHERE EXISTING FUEL PIPING IS
REMOVED AS SHOWN FOR THIS PROJECT. SOIL SAMPLING MUST
FOLLOW EPA METHOD 8015C WITH TESTING REQUIRED FOR TPH
DRO AND TPH GRO. REQUIRED FREQUENCY OF SAMPLES:
- ONE SAMPLE EVERY 20 LINEAR FEET OF SUBGRADE BENEATH
ALL FUEL PIPING AFTER PIPING DEMOLITION/ REMOVAL.
- ONE SAMPLE UNDER EACH DISTRIBUTION POINT (FILLER).
- SAMPLES TO BE STORED IN A STOCKPILE AWAY FROM
PROJECT AREA. COORDINATE LOCATION WITH ROICC AND
USER(S).
3. CONTRACTOR MUST REMOVE AND LEGALLY DISPOSE OF ALL
CONSTRUCTION AND DEMOLITION WASTE OFF OF GOVERNMENT
PROPERTY IN ACCORDANCE WITH FEDERAL, STATE, MCAS
CHERRY POINT, AND LOCAL REQUIREMENTS.
4. IF FREE PRODUCT IS ENCOUNTERED IN THE TRENCH, ALL WORK
IS TO STOP AND EAD NEEDS TO BE CONTACTED IMMEDIATELY.
5. PROTECT EXISTING MONITORING WELLS ON THIS SITE. REPORT
ANY DAMAGE TO ROICC AND REPAIR DAMAGE.
6. PERFORM DEMOLITION OF PAVING TO ACCESS EXISTING FUEL
PIPING FOR DEMOLITION AND TO MAKE ACCESS FOR
INSTALLATION OF NEW FUEL PIPING. PERFORM DEMOLITION
WITHOUT DISTURBING EXISTING BOLLARDS OR OTHER
INFRASTRUCTURE. IF BOLLARDS OR OTHER ITEMS ARE
DEMOLISHED OR DAMAGED, REPLACE WITH MATERIALS AND
CONSTRUCTION TO MATCH EXISTING.
1. SAW CUT AND REMOVE PAVEMENT AS REQUIRED TO REMOVE
UNDERGROUND FUEL PIPING AND ELECTRICAL ROUTING.
(SEE SHEETS ED101 AND EP101)
2. REMOVE BURIED DOUBLE WALL FUEL PIPING AND APPURTENANCES,
HANDLE, TRANSPORT AND DISPOSE OF OFFSITE PER ALL STATE AND
FEDERAL REGULATIONS. SAMPLE EXCAVATED SOILS AS PER NCDEQ SOIL
SAMPLING METHODS.
(SEE GENERAL SHEET NOTE 2 ABOVE AND DETAIL 8 ON C-500).
3. REMOVE AND DISPOSE BURIED ELECTRICAL (SEE ED101).
4. DISCONNECT AND REMOVE GAS BOY FUEL PUMPS AND OTHER
EQUIPMENT AND APPURTENANCES. STORE AND PROTECT FOR
REINSTALLATION. SAMPLE EXCAVATED SOILS AS PER NCDEQ SOIL
SAMPLING METHODS.
(SEE GENERAL SHEET NOTE 2 ABOVE AND DETAIL 8 ON C-500)
5. EXISTING LIGHT POLE TO REMAIN.
6. EXISTING CONCRETE BOLLARDS TO REMAIN.
7. REMOVE AND DISPOSE CONCRETE PAVEMENT TO EXISTING JOINTS.
EXISTING MONITORING WELLS TO BE PROTECTED.
8. SAW CUT, REMOVE, AND DISPOSE CONCRETE PAD AS REQUIRED TO
INSTALL AND CONNECT NEW FUEL PIPING AND ELECTRICAL.
9. EXISTING SIGNS AND FIRE EXTINGUISHER TO REMAIN.
KEY PLAN
PLAN
NORTH
1" = 100'
1"=100'-0"SCALE:
50' 100' 200' 300'
DI
RIM 20.84'
CB
DI
RIM 21.33'
CB
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
XXXXXXXXXXXXXXXXXX
GAS PUMP
GAS PUMP
LP
FUEL
TANK FUEL
TANK
S
SS
SS
SS
SS
SS
W
WW
W
WWWW
UP
UP
UP
UP
U P
U P
METAL LID
RIM 22.36'
METAL LID
RIM 22.46'
METAL LID
RIM 22.38'
RAISED CONCRETE
FUEL ISLAND
MW
LIGHT POLE
FUEL PUMP/
DISPENSE
(TYP)
MONITORING
WELL
22.5'
22.0
21.5
.0
.5
22.0
23.0 23.0
FUEL SPILL
CONTAINMENT
UNIT
ELEC. BOX WITH
RAISED LIGHT
PROJECT LIMITS
C-500
TYP.
1 1 C-500
TYP.
7 7 C-500
TYP.
7 7 C-500
TYP.
±21.89EX
±21.84EX
±21.82EX
±22.03EX
±21.97EX
±21.71EX
±21.67EX
±22.04EX
±22.32EX
±22.53EX
±21.94EX
±21.96EX
±22.05EX
±22.06EX
C-500
C-500
TYP.
RI
FL
E
RA
NG
E
RD
B4049
X X
X X
X X
X
XXXXXX
X X
X X
X
X
X X
PROJECT LIMITS
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
M
ID
AT
LA
N
TI
C
R
EP
AI
R
F U
EL
D
IS
PE
N
SI
N G
S
YS
TE
M
(B
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
FINAL SUBMISSION - 10-12-2023
7328491
SUPPORT TRA INING
MCAS CHERRY POINT, NC
C
IV
IL
S
IT
E
P
LA
N
12882699
CS100
1"=20'-0"SCALE:
10' 20' 40' 60'0
CIVIL SITE PLAN
PLAN
NORTH
1" = 20'
1. SEE SHEET C-001 FOR CIVIL GENERAL NOTES, LEGENDS, AND
ABBREVIATIONS.
2. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE
SYSTEM TO INCLUDE BUT NOT LIMITED TO NECESSARY
CONTROLS FOR THE PUMPS, EMERGENCY SHUT OFFS, AND ANY
OTHER FUEL/ GAS CODE REQUIRED SAFETY FEATURES.
1. ASPHALT PAVEMENT.
2. RAISED CONCRETE FUEL ISLAND WITH EXISTING GAS-BOY FUEL
PUMPS, LIGHT-POLE, SIGNAGE, AND FIRE EXTINGUISHER.
3. CONCRETE PAVEMENT WITH CONTROL JOINTS.
4. LOCATION OF FLEXIBLE UNDERGROUND FUEL SUPPLY PIPING
SYSTEM ROUTE. PIPING SYSTEM SHALL PROVIDE A DEDICATED
LINE FROM SINGLE EXISTING TANK TO EACH PUMP (SEE MP101).
5. LOCATION OF UNDERGROUND CONDUIT ROUTE FROM BUILDING
TO DISPENSERS AND TANKS/ TANK CONTROLS
(SEE ELECTRICAL PLANS).
6. PATCH CONCRETE PAD.
7. TEMPORARY INLET PROTECTION SEDIMENT TRAP
8. TRANSITION SUMP FOR FUEL LINE
SHEET KEYNOTES
1"=100'-0"SCALE:
50' 100' 200' 300'
KEY PLAN
PLAN
NORTH
1" = 100'
NOTE:
- ELECTRICAL CONDUIT AND FUEL PIPING
NOT SHOWN FOR CLARITY, REFER TO
MECHANICAL AND ELECTRICAL SHEETS
FOR ROUTING AND CONNECTIONS.
TYP. DROP INLET STRUCTURE
TEMPORARY INLET
PROTECTION SEDIMENT TRAP
(SILTSACK OR EQUAL)
TYP. DROP INLET METAL GRATE
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
C O
M M
AN
D
M
ID
AT
LA
N
TI
C
R
EP
AI
R
F U
EL
D
IS
PE
N
SI
N G
S
YS
TE
M
(B
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
FINAL SUBMISSION - 10-12-2023
7328491
SUPPORT TRA INING
MCAS CHERRY POINT, NC
C
IV
IL
D
E
TA
IL
S
12882700
C-500
NOT TO SCALE
12" 12"
WIDTH VARIES
MIN. MIN.
TACK COAT (TYP.)
NEW UTILITY
(PROVIDE TRACER WIRE/
MARKING TAPE PER SPECS)
ASPHALT
PAVEMENT
CUT TO NEAT
EDGE & PRIME
PRIOR TO PAVING
PIPE TRENCH (VARIES BASED
ON TYPE OF UTILITY)
NOTE:
TRENCH WIDTH VARIES BASED ON TYPE, SIZE AND DEPTH OF UTILITY. CONTRACTOR MUST
PROVIDE A TRENCH WIDTH REQUIRED FOR COMPLETE INSTALLATION AND/OR REMOVAL PER
SPECIFICATIONS. THE MINIMUM TRENCH WIDTH FOR ANY OPEN CUT IS 5 FEET.
TRENCH WIDTH VARIES
(SEE NOTE BELOW)
12"
MIN.
EDGE MILL (TYP.)
PROVIDE BEDDING PER
SPECIFICATIONS
ASPHALT PATCH
2" S9.5C
8" CRUSHED STONE
BASE COURSE (ABC)
COMPACTED SUBGRADE
3" I-19.0C (INTERMEDIATE
COURSE)
ASPHALT PAVEMENT
NOT TO SCALE
6" AGGREGATE BASE COURSE (ABC)
6" CONCRETE (650 PSI FLEXURAL STRENGTH)
TOP 12" OF SUBGRADE TO BE
COMPACTED TO 95% DRY DENSITY,
STANDARD PROCTOR
NOTES:
1.H = PAVEMENT THICKNESS
2.JOINT SPACING MUST BE INSTALLED PER PROJECT SPECIFICATIONS
SAWED CONTRACTION JOINT (CJ )
NOT TO SCALE
3/8"
5/16" ±1/16"
1/4"
3/4"
H /4
+1 /4
1/8"
SECOND
SAWCUT
FIRST
SAWCUT
1/2" DIA.
BACKER ROD
SILICONE SEALANT
DETAIL
NOTES:
1.H = PAVEMENT THICKNESS
2.JOINT SPACING MUST BE INSTALLED PER PROJECT SPECIFICATIONS.
EXPANSION JOINT (EJ )
NOT TO SCALE
3/4" 3/8"±1/16"
3/8"
H 3" TO 6"
PREFORMED
EXPANSION JOINT
MATERIAL
PER SPECIFICATIONS
H/2
SILICONE SEALANT
1/8" R
PREFORMED
EXPANSION JOINT
MATERIAL
CONTRACTION
JOINT
SEE DETAIL ABOVE
CONTRACTION
JOINT
REINFORCING
(WHERE
INDICATED)
C-500
THICKENED EDGE(TE)(TEJ)
NOT TO SCALE
C-500
5' MIN
H
H+3'' VARIES
STRUCTURE OR PAVEMENT INTERFACE. SEE
SIDEWALK AND PAVING
NOTES ON SHEET C-001
EXPANSION JOINT
WHERE INDICATED PAVEMENT OR SIDEWALK. SEE
PLAN SHEETS FOR SPECIFIC
MATERIAL TYPE
6" COMPACTED BASE
COURSE (ABC OR GCA)
APPROVED SUBGRADE
3" MIN FROM
EACH FACE
6X6 W2.1XW2.1
WELDED WIRE FABRIC (WWF)
C-500
12" 12"
WIDTH VARIES
MIN. MIN.
TACK COAT (TYP.)
EXISTING UTILITY
TO BE REMOVED
ASPHALT
PAVEMENT
CUT TO NEAT
EDGE & PRIME
PRIOR TO PAVING
EXCAVATED MATERIAL FOR
UTILITY REMOVAL TO REMAIN
ONSITE. AFTER REMOVAL OF
UTILITY, REPLACE EXCAVATED
MATERIAL IN TRENCH. INSTALL
IN LIFTS AND COMPACT PER
PROJECT SPECIFICATIONS.
TRENCH WIDTH VARIES
(SEE NOTE BELOW)
12"
MIN.
EDGE MILL (TYP.)
PROVIDE BEDDING PER
SPECIFICATIONS
PROVIDE COMPACTED
STRUCTURAL FILL OR ABC
STONE AS REQUIRED
BASED ON ANY VOID
CREATED BY REMOVED
UTILITY.
CONCRETE PAVEMENT
NOT TO SCALE
NEW UTILITY INSTALLATION
EXISTING UTILITY REMOVAL
TYP. CONCRETE PAVEMENT SECTION
NOT TO SCALE
TEMPORARY INLET PROTECTION SEDIMENT TRAP7
NOT TO SCALE
NCDEQ GUIDELINES FOR SAMPLING - SECTION 4.0 FIGURES 2 AND 38
Figure 2 - Volumes of Stockpiles
Note: These equations have been simplified for ease of calculation.
H = Height
W = Width L = Length Conical Stockpiles:
Volume = (H x L x W)/3
Rectangular Stockpiles - pointed crest:
Volume = (H x L x W)/2
Rectangular Stockpiles - flat topped:
Volume = H x [(L x W) - (2 x H x W)]
H = Height
W = Width L = Length
H = Height
W = Width L = Length
L > W > H
Figure 3 - Soil Stockpile Sampling Map (Example)
Stockpile Type: Rectangle, Flat-topped
Volume = 4 x [(21 x 11) - (2 x 4 x 11)] = 572 cubic yards where: Height (maximum) = 12 feet = 4 yards Length (maximum) = 63 feet = 21 yards Width (maximum) = 33 feet = 11 yards
Composite Samples 3 Primary Samples per core Sample Depths 1 core 1a 1’, 4’, 7’ core 1b 1’, 5’, 8’
2 core 2a 2’, 6’, 10’ core 2b 1’, 4’, 7’
3 core 3a 1’, 3’, 5’ core 3b 2’, 5’, 8’
NOTE: Each composite sample contains six primary samples, three from core “a” and three from core “b.”
3 b a b a b a
043801
TROY O . GRADY
SEAL
R
EENI GN
P R
OF E S S I ON
A
E
L
NO
RT H CAROL I NA
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
M
ID
AT
LA
NT
IC
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
2246 Yaupon Dr.
Wilmington, NC
28401
Tel: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2023 CBHF Engineers, PLLC NC# P-0506
Engineers, PLLC
FINAL SUBMISSION - 10-12-2023
RE
PA
IR
F
UE
L D
IS
PE
NS
IN
G
SY
ST
EM
(B
7328491
1. ALL MECHANICAL PIPING WORK SHALL BE IN STRICT COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE AND LOCAL
CODES AND STANDARDS.
2. ALL DIMENSIONS AND ELEVATIONS FOR NEW EQUIPMENT, PIPING AND APPARATUS ARE APPROXIMATE AND ARE ONLY FOR CONTRACTOR'S GUIDANCE. CONTRACTOR SHALL SUBMIT DIMENSIONS AND ELEVATIONS VERIFIED IN THE FIELD.
PIPING INDICATED ON THE DRAWINGS, SECTIONS AND PROSPECTIVE VIEWS ARE SHOWN DIAGRAMMATICALLY. PIPE ELEVATIONS IN EXACT LOCATIONS SHALL BE DETERMINED BY THE INSTALLING CONTRACTOR AND DETAILED ON THE
SHOP DRAWINGS.
3. ALL DUCT DIMENSIONS INDICATED ON PLAN ARE CLEAR INSIDE DIMENSIONS. CONTRACTOR MUST ACCOUNT FOR THE
THICKNESS OF EXTERIOR INSULATION WHEN DETERMINING INSTALLATION CLEARANCES.
4. THE CONTRACTOR SHALL TEMPORARILY COVER ALL OPENINGS WITH A NON-COMBUSTIBLE MATERIAL, AND SEAL THEM AIR TIGHT TO PREVENT CONTAMINATION OF THE RESPECTIVE SYSTEMS DURING CONSTRUCTION.
5. CONTRACTOR SHALL REMOVE AND DISPOSE OF OFFSITE ALL DEMOLISHED WORK IN ACCEPTABLE AND SAFE MANNER
AND SHALL KEEP ALL NON-WORK AREAS CLEAN AND SAFE.
6. ALL EXISTING EQUIPMENT AND CONNECTIONS THAT NEED TO BE TEMPORARILY DEMOLISHED FOR RIGGING AND / OR INSTALLATION SHALL BE REINSTALLED AND BROUGHT BACK TO ORIGINAL CONDITIONS PRIOR TO TEMPORARY
REMOVAL.
7. INSTALL WORK SO AS TO BE READILY ACCESSIBLE FOR OPERATION, MAINTENANCE AND REPAIR. MINOR DEVIATIONS FROM DRAWINGS MAY BE MADE TO ACCOMPLISH THIS, BUT CHANGES WHICH INVOLVE EXTRA COST SHALL NOT BE
MADE WITHOUT APPROVAL.
TERMABBREVIATION
AIR MOVEMENT AND CONTROL ASSOCIATIONAMCA
AMPERE (AMP, AMPS)AMP
COEFFICIENT OF PERFORMANCECOP
DEGREEDEG OR º
DRY BULBDB
EXHAUST GRILLEEG
ELECTRONICALLY COMMUTATED MOTORECM
ENERGY EFFICIENCY RATIOEER
FANF
FAHRENHEITºF
HEIGHTHGT OR H
HORSEPOWERHP
HOUR(S)HR
INCHES WATER GAUGEIN.-WG
KILOWATTKW
LOUVERL
MAXIMUMMAX
1000 BTUHMBH
MINIMUMMIN.
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNEMA
OUNCEOZ
OUTSIDE AIROA
PERCENT%
POUNDSLBS
ROOF TOP UNITRTU
REVOLUTIONS PER MINUTERPM
SUPPLY AIRSA
SQUARESQ
UNIT HEATERUH
VOLT/PHASE/HERTZV/PH/HZ
WIDTHW
WET BULBWB
ADJUSTABLEADJ
EXTERNAL STATIC PRESSUREESP
FEETFT
INCHIN.
MINIMUM CIRCUIT AMPACITYMCA
MAXIMUM OVER CURRENT PROTECTIONMOCP
TRANSFER GRILLETG
ENTERING AIR TEMPERATUREEAT
LEAVING AIR TEMPERATURELAT
SQUARE-FEETSF
CUBIC FEET PER MINUTECFM
AMERICAN SOCIETY OF TESTING AND MATERIALSASTM
FULL LOAD AMPSFLA
TYPICALTYP
CONCRETE MASONRY UNITCMU
CAST IN PLACECIP
MEAN COINCIDENT WET BULBMCWB
1. THE CONTRACTOR SHALL REVIEW THE DRAWINGS AND SPECIFICATIONS FOR DEMOLITION REQUIREMENTS AND LAYOUT HIS WORK IN A COMPATIBLE AND COMPLEMENTARY MANNER. REMOVE ALL EQUIPMENT, PIPING, SUPPORTS, CONTROLS, ACCESSORIES, ETC..., AND MECHANICAL ITEMS MADE OBSOLETE BY THESE ALTERATIONS AS SHOWN IN THE MECHANICAL DRAWINGS. ALL ITEMS TO BE REMOVED OR MODIFIED MAY NOT BE SHOWN, HOWEVER, THIS CONTRACTOR SHALL REMOVE ANY MECHANICAL WORK AS REQUIRED BY THE CONSTRUCTION OR AS DIRECTED BY THE GOVERNMENT
CONTRACTING OFFICER. SURVEY THE AFFECTED AREAS BEFORE SUBMITTING A BID.
2. SCHEDULING OF DEMOLITION - COORDINATE SCHEDULING OF MECHANICAL DEMOLITION WORK WITH THE CONTRACTING OFFICER SO AS TO MINIMIZE DISRUPTION OF THE GOVERNMENT'S USE OF THE FACILITIES AND MAINTAIN THE CONSTRUCTION SEQUENCE. SEE DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INSTRUCTIONS CONCERNING
PHASING AND SEQUENCE OF WORK.
3. DEMOLISHED MATERIALS - UNLESS SPECIFICALLY REQUESTED BY THE GOVERNMENT, ALL DEMOLISHED MECHANICAL MATERIALS SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE SITE AND
DISPOSED OF PROPERLY.
4. THESE DRAWINGS ARE COMPILED BY THE ENGINEER FROM THE GOVERNMENT'S AS-BUILT RECORD DRAWINGS AND LIMITED FIELD VERIFICATION OF EXISTING CONDITIONS FOR THE PURPOSE OF INDICATING THE WORK REQUIRED AND ARE BELIEVED TO BE CORRECT. NOTWITHSTANDING, THE CONTRACTOR SHALL VERIFY ALL PIPING, EQUIPMENT
LOCATIONS, DIMENSIONS AND ALL FIELD CONDITIONS AFFECTING HIS WORK.
5. WHERE MECHANICAL PIPING SYSTEMS PASS THROUGH THE DEMOLITION AREAS TO SERVE OTHER PORTIONS OF THE PREMISES, THEY SHALL REMAIN OR BE SUITABLY RELOCATED AND THE SYSTEM RESTORED TO NORMAL OPERATION.
ADVISE THE CONTRACTING OFFICER IMMEDIATELY IF SUCH CONDITIONS ARE UNCOVERED BEFORE PROCEEDING WITH
ADDITIONAL WORK.
6. PROTECT ALL EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND PUBLIC ADDRESS SYSTEMS AND MAINTAIN THEM IN OPERATION THROUGHOUT THE PROGRESS OF THE WORK. NOTIFY THE CONTRACTING OFFICER IN WRITING IF SHUTDOWNS ARE REQUIRED PRIOR TO ANY OUTAGE OF SERVICE. WHERE THE DURATION OF A PROPOSED OUTAGE CANNOT BE TOLERATED BY THE GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS REQUIRED MAINTAINING
SERVICE.
7. SURVEY THE AFFECTED AREAS BEFORE STARTING DEMOLITION AS ALL EXISTING CONDITIONS CANNOT BE
COMPLETELY DEPICTED ON THE DRAWINGS AND SOME UNUSUAL CONDITIONS EXIST.
8. IF ANY UNUSUAL CONDITIONS ARE ENCOUNTERED DURING DEMOLITION, CONTACT THE CONTRACTING OFFICER FOR
ASSISTANCE.
NOTE: ALL ABBREVIATIONS MAY NOT BE USED IN PROJECT.
HOT WATER COILHC
EXHAUST AIREA
RETURN AIRRA
SUPPLY GRILLESG
RETURN GRILLERG
VENT THROUGH ROOFVTR
MECHANICAL GENERAL NOTES:
MECHANICAL DEMOLITION NOTES:
MECHANICAL ABBREVIATIONS
MECHANICAL PIPE LEGEND
FUEL PIPINGG
FUEL PIPING - EXISTING(X)G
VENT PIPINGV
MECHANICAL PIPE SYMBOLS
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
45 DEGREE ELBOW DOWNor
45 DEGREE ELBOW SIDEor
45 DEGREE ELBOW UPor
ANGLE VALVE
BACKFLOW PREVENTERBFP
BALL VALVE SIDEor
BLOCK VALVE / SHUTOFF VALVE
BOILER BLOWDOWN VALVE (SUPPLIED WITH BOILER)
BOILER STOP CHECK VALVE
BUTTERFLY VALVE SIDEor oror
CHECK VALVE SIDEor
CIRCUIT SETTER
DOMESTIC WATER METERWM
DRAIN
ELBOW DOWNor
ELBOW SIDEor
ELBOW UPor
FLANGE
FLANGED STARTUP STRAINER
FLOW MEASURING ORIFICE
FLOW TRANSMITTERFT
GATE VALVE SIDE
GAUGE
GLOBE VALVE
PUMP END
PUMP SIDEor
PUMPor
SLIP ON FLANGE END
SLIP ON FLANGE SIDE
STEAM TRAPT
TEE BRANCH DOWNor
TEE END UPor
TEE SIDEor
TRIPLE DUTY VALVEor
WELD NECK FLANGE END
WELD NECK FLANGE SIDE
NOTE: ALL ITEMS LISTED MAY NOT BE USED IN THIS PROJECT.
RPZRPZ
10/05/2023
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
XXXXXXXXXXXXXXXXX
GAS PUMP
GAS PUMP
FUEL
TANK FUEL
TANK
G
G
G
G
G
G G
G
G G
G
G
G
G
G
G
G
043801
TROY O . GRADY
SEAL
R
EENI GN
P R
OF E S S I ON
A
E
L
NO
RT H CAROL I NA
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
M
ID
AT
LA
NT
IC
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
2246 Yaupon Dr.
Wilmington, NC
28401
Tel: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2023 CBHF Engineers, PLLC NC# P-0506
Engineers, PLLC
FINAL SUBMISSION - 10-12-2023
RE
PA
IR
F
UE
L D
IS
PE
NS
IN
G
SY
ST
EM
(B
7328491
1/16" = 1'-0" 0 16' 32'8'1 FLOOR PLAN
PLAN
NORTH
EXISTING FUEL DISPENSERS AND SUMP WILL BE REUSED.
EXISTING UNDERGROUND DOUBLE WALL FUEL PIPING TO BE DEMOLISHED AS
SHOWN TO EXISTING 2-1/2" UNION AT ABOVE GROUND STORAGE TANKS.
REMOVE AND DISPOSE PIPING OFF SITE, PER STATE FEDERAL AND LOCAL
REGULATIONS.
1. SEE CIVIL DRAWINGS FOR PAVEMENT SAW-CUT LOCATIONS AND INSTRUCTIONS.
M E
C H
A N
IC
A
L D
E M
O
LI
TI
O
N P
LA
N
12882702
MD101
10/10/2023
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
CB
CB
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
FUEL
TANK FUEL
TANK
SS
SS
SS
SS
SS
SS
W W W W W
W W W W
W
G
G
G
G
G
G G
G
G
G
G
G
G
G
G
G
V
V
V
V
V
V
V
V
V
V
V
V
V V
V
043801
TROY O . GRADY
SEAL
R
EENI GN
P R
O F E S S I ON
A
E
L
NO
RT H CAROL I NA
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
M
ID
AT
LA
NT
IC
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
2246 Yaupon Dr.
Wilmington, NC
28401
Tel: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2023 CBHF Engineers, PLLC NC# P-0506
Engineers, PLLC
FINAL SUBMISSION - 10-12-2023
RE
PA
IR
F
UE
L D
IS
PE
NS
IN
G
SY
ST
EM
(B
7328491
1/16" = 1'-0" 0 16' 32'8'1 SITE PLAN
PLAN
NORTH
PROVIDE FRP TRANSITION SUMP, SEE CIVIL DRAWINGS FOR MORE
INFORMATION.
DOUBLE WALL UL971 FLEXIBLE PIPE WITH 2-1/2" MINIMUM CARRIER PIPE AND
OUTER CONTAINMENT PIPE. SLOPE PIPING TOWARDS EXISTING DISPENSER
SUMP LOCATED UNDER EACH DISPENSER. EACH EXISTING ABOVE GROUND
STORAGE TANK SUPPORTS A SINGLE DISPENSER WITH DUAL PUMPS.
SEE DETAIL A3/M-501 FOR TIE-IN LOCATION AND PIPE ARRANGEMENT.
DOUBLE WALL UL971 FLEXIBLE PIPE WITH 3/4" MINIMUM CARRIER PIPE AND
OUTER CONTAINMENT PIPE. SLOPE TOWARDS EXISTING WATER-TIGHT
DISPENSER SUMP LOCATED UNDER EACH DISPENSER.
REFER TO CIVIL FOR CONCRETE CUT LINE.
M E
C H
A N
IC
A
L
FU
E L
P
LA
N
12882703
MP101
1. SEE CIVIL DRAWINGS FOR PAVEMENT SAW-CUT LOCATIONS AND INSTRUCTIONS.
2. REFER TO CIVIL DRAWINGS FOR EXISTING UNDERGROUND PIPING LOCATIONS.
3. EACH EXISTING ABOVE GROUND STORAGE TANK SUPPORTS A SINGLE DISPENSER
WITH DUAL PUMPS.
EXISTING ABOVE
GROUND
STORAGE TANKS
EXISTING DISPENSER
WITH EXISTING
SUMPS BELOW
10/10/2023
043801
TROY O . GRADY
SEAL
R
EENI GN
P R
OF E S S I ON
A
E
L
NO
RT H CAROL I NA
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
M
ID
AT
LA
NT
IC
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
2246 Yaupon Dr.
Wilmington, NC
28401
Tel: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2023 CBHF Engineers, PLLC NC# P-0506
Engineers, PLLC
FINAL SUBMISSION - 10-12-2023
RE
PA
IR
F
UE
L D
IS
PE
NS
IN
G
SY
ST
EM
(B
7328491
NOT TO SCALEA3 EXISTING JP-5 TANK AND PUMPS DETAIL
WARNING
NO SMOKING
STOP MOTOR
IN CASE
OF FIRE
OR SPILL
EXISTING WATER TIGHT DISPENSER SUMP WITH
DISCRIMINATING SENSOR
PRESSURE REGULATOR VALVE. PIPE
VENT TO TOP OF STORAGE TANK.
3/4HP SUCTION PUMP, TYP
FIRE EXTINGUISHER, 4A 60 B:C TALL TYPE.
MOUNT FIRE EXTINGUISHER SIGN ON OTHER SIDE
EXISTING DISPENSER
REMOVE AND
REINSTALL AS NEEDED
STEEL ISLAND FORM
" M
IN
. SLOPE
NEW WORKEXISTING
EXISTING 6" BOLLARD
EMERGENCY SHUT-OFF VAVLE
PROVIDE AND INSTALL TEE AT EXISTING TANK VENT PIPE.
TIE IN AT EXISTING UNION.
3/4" MINIMUM DOUBLE WALL UL971 FLEXIBLE
PIPE. SLOPE TOWARDS WATER-TIGHT
DISPENSER SUMP.
THERMAL
RELIEF VALVE
2-1/2" MINIMUM DOUBLE WALL UL971 FLEXIBLE PIPE. SLOPE PIPING
TOWARD DISPENSER SUMP. EACH EXISTING ABOVE GROUND STORAGE
TANK SUPPORTS A SINGLE DISPENSER WITH DUAL PUMPS.
PROVIDE 3/4" STEEL VENT PIPING FROM
RELOCATED PRESSURE REGULATORS TO
TANK VENT PIPE
NEW FRP TRANSITION SUMP
EXISTING FILL PIPE CONTAINMENT
BOX. REMOVE AND AN REINSTALL
AS NEEDED FOR CUTTING OF
CONCRETE.
SEAL PIPE PENETRATIONS WATER TIGHT, TYP
SEAL PIPE PENETRATIONS WATER TIGHT, TYP
1. ALL PIPING BELOW GRADE IN CONTACT WITH SOIL TO BE DOUBLE WALL UL971
FLEXIBLE PIPE.
2. ALL PIPING EXPOSED AND ABOVE GRADE TO BE CARBON STEEL PIPE WITH HIGH
PERFORMANCE PROTECTIVE COATING.
023311
LA
W
RCNLE
I
BB
SEAL
R
EENI GN
P R
OF E S S I ON
A
E
L
NO
RT H CAROL I NA
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
M
ID
AT
LA
NT
IC
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
2246 Yaupon Dr.
Wilmington, NC
28401
Tel: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2023 CBHF Engineers, PLLC NC# P-0506
Engineers, PLLC
FINAL SUBMISSION - 10-12-2023
RE
PA
IR
F
UE
L D
IS
PE
NS
IN
G
SY
ST
EM
(B
7328491
E
LE
C
TR
IC
A
L D
E
TA
IL
S
, A B
B R
E V
IA
TI
O N
S A
N D
L E
G E
N D
S
12882705
E-001
TYPICAL ABBREVIATIONS:
A, AMP AMPERE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BOF BOTTOM OF FIXTURE
BRKR BREAKER
C, CND CONDUIT
CAB CABINET
CAT CATALOG
CL CHLORINE
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CP CONTROL PANEL
CR CONTROL RELAY, CORROSION RESISTANT
CS CONTROL SWITCH
CV CONTROL VALVE
CT CURRENT TRANSFORMER
CU COPPER
EF EXHAUST FAN
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EQ, EQIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EPRF EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FBO FURNISHED BY OTHERS
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FLR FLOOR
FWE FURNISHED WITH EQUIPMENT
GEN GENERATOR
G, GND GROUND
GFI, GFCI GROUND FAULT CIRCUIT INTERRUPTER
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTO
HP HORSE POWER
HPF HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
HTR HEATER
HV HIGH VOLTAGE
Hz HERTZ
IMC INTERMEDIATE METALLIC CONDUIT
INCAND INCANDESCENT
JB JUNCTION BOX
K THOUSAND
Kcmil THOUSAND CIRCULAR MILLS
KVA KILOVOLT AMPERE
KW KILOWATTS
KWH KILOWATT-HOURS
LP LIGHTING PANEL, LIGHT POLE
LTG LIGHTING
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH MANHOLE
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
N, NEUT NEUTRAL
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
P POLE
PA PUBLIC ADDRESS
PB PULL BOX, PUSH-BUTTON
PF POWER FACTOR
PH,ɸ PHASE
PLC PROGRAMMABLE LOGIC CONTROLLER
PNL PANEL
PP POWER PANEL, POWER POLE
PT POTENTIAL TRANSFORMER
PWR POWER
RECPT,RCP RECEPTACLE
REQ'D REQUIRED
RGS RIGID GALVANIZED STEEL CONDUIT
RM ROOM
RTU REMOTE TELEMETRY UNIT
SCR DC MOTOR DRIVE
SH SHEET
SM SURFACE MOUNTED
SPEC SPECIFICATION
SS SELECTOR SWITCH
SST STAINLESS STEEL
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCH GEAR
TEL TELEPHONE
TPS TWISTED PAIR SHIELDED
TVSS, SPD TRANSIENT VOLTAGE SURGE SUPPRESSER
TYP TYPICAL
UG, UGND UNDERGROUND
UH UNIT HEATER
UON UNLESS OTHERWISE NOTED
UTIL UTILITY
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WIRE, WATT
WH WATT-HOUR
WP WEATHERPROOF
XFMR TRANSFORMER
(X) EXISTING
ELECTRICAL LEGEND
PHOTOCELL, REMOTE MOUNTED, 120V, 10 SECOND TIME DELAY, UL WET LOCATION,
RATED FOR 1500 W @ 120 VAC AND 4000 W @ 277 VAC (FOR USE WITH LAMP SOURCE(S)
SHOWN.
PE
CONDUIT, HOME RUN TO PANEL BOARD
POWER & SWITCH LEG
UNSWITCHED LEG
WEATHERPROOF SWITCH, SINGLE POLE 120/277 VAC, 20A, MOUNTED AT 46" AFF UNLESS
OTHERWISE NOTED.S WP
DISCONNECT SWITCH, FUSED, HEAVY DUTY, SIZE AS INDICATED ON DRAWINGS
##A = DISCONNECT SIZE / # = NUMBER OF POLES / # = NEMA RATING, / ##AF = FUSE SIZE
30A/3/4X
W/ 30AF
MANUAL MOTOR STARTER, ELECTRICAL CONTRACTOR SHALL COORDINATE POLES
AND SIZE WITH EQUIPMENT
## = AMPERAGE RATING WHEN INDICATED ON DRAWING
SM ##
(X)PANELBOARD, SURFACE OR RECESSED MOUNTED AS SHOWN. SIZE, RATINGS, AND
MOUNTING AS INDICATED ON PANEL SCHEDULE. CONTRACTOR IS RESPONSIBLE FOR
REQUIRED CLEARANCE IN FRONT OF ELECTRICAL PANEL. SEE NEC TABLE 110.26
WORKING SPACES FOR ADDITIONAL CLEARANCE CONDITIONS.
208/120V
480/277V
WALL MOUNTED 120V EMERGENCY OFF PUSH BUTTON WITH RED MUSHROOM STYLE HEAD
WITH MANUAL PULL REST, NORMALLY OPEN, WITH CLEAR PROTECTIVE COVER. MOUNTED
AT 46" AFF UNLESS OTHERWISE NOTED.
EPO
RECEPTACLE, DUPLEX, GROUND FAULT CIRCUIT INTERRUPTER TYPE, 120VAC, 20A, MOUNTED
16" AFF, UNLESS OTHERWISE NOTED. (SEE ELECTRICAL MOUNTING HEIGHT DETAIL)
HATCHING INDICATES ITEMS TO BE DEMOLISHED. REMOVE DEVICE, EQUIPMENT, FIXTURE
INDICATED, CIRCUIT, AND CONDUIT BACK TO SOURCE UNLESS OTHERWISE NOTED.
DEMOLITION KEY NOTE SYMBOL
KEY NOTE SYMBOL
FIXTURE DESIGNATION
HAND HOLE, IN GRADE, TIER 22 HEAVY TRAFFIC RATING
JUNCTION BOX - WPJ WP
UGP
(X)UGP
UNDERGROUND POWER AND CONTROL CONDUIT AND CONDUCTORS
UNDERGROUND POWER AND CONTROL CONDUIT AND CONDUCTORS - EXISTING
C C CONTROL CABLE CONDUIT
"EQUIPMENT NAME"
SOURCE: PANEL "###"
SOURCE LOCATION "###"
RATING: ### AMPS
VOLTAGE: 120/208V, 3Ø, 4WRATING DESIGNATION 1/4"
WHITE ENGRAVED LETTERS
SOURCE DESIGNATION 1/4"
WHITE ENGRAVED LETTERS
3/
4"
LENGTH AS REQUIRED
EQUIPMENT DESIGNATION 3/8"
WHITE ENGRAVED LETTERS
VOLTAGE & PHASE DESIGNATION
1/4" WHITE ENGRAVED LETTERS
MACHINE SCREW WITH ACORN
NUT AND LOCKWASHER, TYP.
SOURCE LOCATION DESIGNATION
1/4" WHITE ENGRAVED LETTERS
NOTE: SEE SPECIFICATIONS FOR NAMEPLATE
MATERIAL AND ENGRAVING COLORS.
NOT TO SCALEC1 TYPICAL EQUIPMENT NAMEPLATE DETAIL
EX
E-XXX
DETAIL, SECTION OR
PLAN NUMBER
DRAWING SHEET PLAN,
DETAIL OR SECTION
APPEARS ON
EX
E-XXX
ENLARGED PLAN ELEVATION
POLE MOUNTED DUAL HEAD LIGHT FIXTURES
EMERGENCY
SHUT-OFF
PUSH
LIFT HERE
ENGRAVED FACEPLATE AS INDICATED
NON-ILLUMINATED MUSHROOM TYPE PUSHBUTTON
- NORMALLY CLOSED/PUSH TO OPEN-TURN OFF -
PULL TO RESET
MOUNT 60" TO CENTER
CLEAR FLIP-UP COVER
NOT TO SCALEB1 EMERGENCY FUEL OFF "EFO" BUTTON DETAIL
NOTES:
1. HOUSING SHALL BE A POLYMER CONCRETE REINFORCED WITH A
HEAVY WEAVE FIBERGLASS.
2. BOX AND COVER SHALL CONFORM TO TIER 22 REQUIREMENTS.
3. PROVIDE STAINLESS STEEL BOLTS AND INSERTS.
4. PROVIDE WITH (IN & OUT) 3/4" AND 1" MOUSEHOLES, SEE DRAWINGS
FOR CONDUIT SIZES.
5. PROVIDE LABEL "ELECTRICAL" & "FUEL CONTROLS" FOR HANDHOLES.
FINISH GRADE
TIER 22 RATED POLYMER
CONCRETE RING AND
HANDHOLE
SWEEP ELBOW
GRAVEL DRAIN FILL
LIFTING EYE
CAST IN I.D., LABELED
"ELECTRICAL" OR
"FUEL CONTROLS"
" M
IN
24" MIN
8"
AS
R
EQ
U
IR
ED
NOT TO SCALEA1 HAND HOLE DETAIL
SEAL OFF IN
HANDHOLE -
TYP.
FUEL DISPENSER
CONTACTOR "FDSP",
6-POLE 20A CONTACTS,
120VAC COIL
ELECTRICAL HELD
'EFO'
PUSHBUTTON
CKT PPA1-36 120VAC
20A
DISPENSER #1 PHASE
CONDUCTOR
20A
PANEL "PPA1"
CKT 38 -120VAC 1Ø
20A
20A
(H) (N)
MOUNTED ON
NOT TO SCALEA2 FUEL DISPENSER CONTACTOR (ELECT. HELD)
PANEL "PPA1"
NEUTRAL BUS
DISPENSER #1
NEUTRAL CONDUCTOR
DISPENSER #1
PANEL "PPA1"
CKT 40 - 120VAC 1Ø
PANEL "PPA1"
NEUTRAL BUS
PANEL "PPA1"
NEUTRAL BUS
DISPENSER #2 PHASE
CONDUCTOR
DISPENSER #2
NEUTRAL CONDUCTOR
DISPENSER #2
VEEDER ROOT FUEL
CONTROLLER PHASE
CONDUCTOR
DISPENSER #1
NEUTRAL CONDUCTOR
VEEDER-ROOT
FUEL CONTROLLER
PANEL "PPA1"
CKT 36 - 120VAC 1Ø
W
RCNLE
I
BB
SEAL
R
EENI GN
P R
OF E S S I ON
A
E
L
NO
RT H CAROL I NA
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
M
ID
AT
LA
NT
IC
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com
N.C. LICENSE # C-1621
2246 Yaupon Dr.
Wilmington, NC
28401
Tel: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com c Copyright 2023 CBHF Engineers, PLLC NC# P-0506
Engineers, PLLC
FINAL SUBMISSION - 10-12-2023
RE
PA
IR
F
UE
L D
IS
PE
NS
IN
G
SY
ST
EM
(B
7328491
E
LE
C
TR
IC
A
L D
E M
O
LI
TI
O
N A
N D
G E
N E
R A
L N
O
TE
S
12882706
E-002
ELECTRICAL GENERAL NOTES
1. ALL ELECTRICAL WORK SHALL BE IN FULL COMPLIANCE WITH NFPA 70, SPECIFICALLY INCLUDING
ART. 500, 501, THE NORTH CAROLINA STATE BUILDING CODE, ALL LOCAL CODES AND ORDINANCES AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.
2. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR SHALL BE LISTED AND LABELED BY A
NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING
JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL MATERIAL, EQUIPMENT AND DEVICES
SHALL BE NEW CURRENT PRODUCTS OF MANUFACTURERS REGULARLY ENGAGED IN THE
PRODUCTION OF SUCH PRODUCTS. EQUIPMENT SHALL BE SUITABLE FOR ITS APPLICATION (E.G.
WHEN INSTALLED OUTDOORS, IT SHALL BE WEATHERPROOF, ETC.)
3. THE CONTRACTOR SHALL REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR WORK
REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL EQUIPMENT, AND LAYOUT
HIS WORK IN A COMPATIBLE AND COMPLEMENTARY MANNER.
4. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR THOROUGHLY FAMILIARIZING HIMSELF WITH
ANY CONTRACTUAL REQUIREMENTS AS MAY BE SET FORTH IN THE OTHER DIVISIONS OF THE
PROJECT SPECIFICATIONS.
5. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED BY THE
ELECTRICAL CONTRACTOR SHALL BE COMPLETE AND FULLY-FUNCTIONING AFTER INSTALLATION.
INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK WHICH MAY BE REASONABLY
IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT REQUIRED FOR THE PROPER OPERATION OF
THE EQUIPMENT OR SYSTEM, SHALL BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE
BID. ADDITIONAL CIRCUITS SHALL BE INSTALLED WHEREVER NEEDED TO CONFORM TO THE
SPECIFIC REQUIREMENTS OF EQUIPMENT.
6. THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT THE
COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR ADJUSTMENTS NECESSARY
FOR THE PROPER FUNCTIONING OF THE SYSTEM AND EQUIPMENT.
7. ALL EQUIPMENT SHOWN DOTTED OR DASHED IS BY OTHERS OR IS EXISTING, AS NOTED.
8. ALL ELECTRICAL EQUIPMENT SHALL, AT ALL TIMES DURING CONSTRUCTION, BE ADEQUATELY
PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER AND/OR THE ELEMENTS.
ELECTRICAL EQUIPMENT SHALL NOT BE STORED OUT OF DOORS, BUT SHALL BE STORED IN DRY
PERMANENT SHELTERS. IF AN APPARATUS HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO
POSSIBLE INJURY BY WATER OR THE ELEMENTS, SUCH DAMAGE SHALL BE REPLACED AT NO
ADDITIONAL COST.
9. DO NOT SCALE ELECTRICAL DRAWINGS. FIELD VERIFY ALL DIMENSIONS.
10. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR OTHER
INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT ROUTING OF FEEDER AND
BRANCH CIRCUIT RACEWAYS AND CABLES IS THE RESPONSIBILITY OF THE CONTRACTOR. RISER
AND GENERAL CIRCUIT ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY.
THE CONTRACTOR SHALL ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE
INSTALLATION.
11. UNLESS DIMENSIONED, DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE.
ADJUST EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO AVOID
CONFLICTS AND INTERFERENCES WITH OTHER TRADES. EXACT DEVICE LOCATIONS SHALL BE AS
INDICATED ON THE DRAWINGS OR AS DIMENSIONED. IF NOT SHOWN ON THE DRAWINGS OR
DIMENSIONED ON THE ELECTRICAL DRAWINGS, VERIFY EXACT LOCATION WITH THE CONTRACTING
OFFICERPRIOR TO ROUGH-IN.
12. CONDUIT TERMINATING IN PRESSED STEEL BOXES SHALL HAVE DOUBLE LOCKNUTS AND
INSULATED BUSHINGS. CONDUITS TERMINATING IN GASKETED ENCLOSURES SHALL BE
TERMINATED WITH GROUNDING TYPE CONDUIT HUBS.
13. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE CONDUCTORS, NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED. ADDITIONAL CONDUCTORS REQUIRED FOR
CONTROL SHALL BE INCLUDED EVEN IF NOT EXPLICITLY SHOWN.
14. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS WATERTIGHT.
15. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES SHALL BE WEATHER-RESISTANT LISTED
WITH WEATHERPROOF WHILE IN USE COVER.
16. ALL RACEWAYS SHALL BE CONCEALED WHERE POSSIBLE. IF APPLICABLE, MATCH EXISTING
RACEWAY INSTALLATION METHODS AND ROUTINGS AT OR NEAR EXISTING FACILITIES.
17. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY SURFACES OR
STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS AS MUCH AS POSSIBLE. NO
DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS SHALL BE RUN STRAIGHT AND TRUE. RUN
PARALLEL OR BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE PRACTICAL. MAKE
BENDS IN PARALLEL OR BANKED RUNS FROM SAME CENTERLINE TO MAKE BENDS PARALLEL.
18. PROVIDE AND PLACE ALL SLEEVES FOR CONDUITS PENETRATING WALLS, FLOORS, PARTITIONS, ETC. LOCATE ALL NECESSARY SLOTS FOR ELECTRICAL WORK AND FORM BEFORE CONCRETE IS
POURED.
19. PATCHING OF WATERPROOFED SURFACES SHALL RENDER THE AREA…
This is the start of the file's text. The full file is on GovTribe.