70Z03326QSEAT0007 QandA.docx
DOCX document 23 KB Posted
- Attached to
- USCG Station Depoe Bay Electrical Installation
- Solicitation number
- 70Z03326QSEAT0007
About this file
This is a Questions and Answers (Q&A) document for USCG Station Depoe Bay Electrical Installation solicitation 70Z03326QSEAT0007. The document addresses technical inquiries regarding the electrical installation project at U.S. Coast Guard Station Depoe Bay in Depoe Bay, Oregon. Key technical specifications clarified include: the existing emergency generator system rated at 23.0 KW/KVA with 120v/240v supply and 94.8 amps capacity; seven new circuits required to serve equipment in the galley, berthing rooms, recreation room, offices, and gym, including a residential electrical stove/oven, refrigerator, air handler unit, hot water heater, lighting, and outlets; and a new 100-amp, 120v/240v subpanel with 3-wire configuration matching the main panel. The government confirmed the new subpanel may be installed as close as practical to the existing emergency panel while maintaining code-required clearances and accessibility standards.
This solicitation is set aside 100% for small business under NAICS code 238210 (Electrical Contractors and Other Wiring Installation Contractors) with a size standard of $19 million. The work requires all labor, materials, equipment, and supervision for subpanel installation and branch circuit routing, with all work tied to the existing emergency generator distribution panel and compliant with the National Electrical Code. A mandatory site visit is required for all prospective quoters on June 17, 2026, at 0900 hours at the project location, with failure to attend rendering proposals non-responsive and ineligible for award. Interested parties must RSVP with Ava Stow at ava.m.stow@uscg.mil.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| STA Depoe Bay E-Gen_SOW_Revision 1.docx | DOCX document | |
| SF1449 70Z03326QSEAT0007_Revised.pdf | ||
| Emergency power diagram.pdf | ||
| Station Depoe electrical drawing.pdf | ||
| RSVP List for 70Z03326QSEAT0007 Depoe Bay Electrical Subpanel Installation.docx | DOCX document | |
| Wage Determination Lincoln County.txt | TXT text file | |
| Provisions and Clauses.pdf | ||
| SF1449 70Z03326QSEAT0007.pdf | ||
| E-Generator Subpanel SOW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
70Z03326QSEAT0007 Depoe Bay Electrical Installation QandA
1. Can the Government provide the existing panel schedule, one-line diagram, and generator capacity information for the emergency generator system?
FREQ: 60
Rated KW: 23.0 KVA:23.0
PF: 1.0
Volts: 120v/240v Supply: 94.8 Amps
1. How many new circuits are required, and what specific equipment/loads will each circuit serve in the galley, berthing rooms, recreation room, offices, and gym?
7 circuits.
Associated equipment standard residential electrical stove/oven, fridge, air handler unit, hot water heater, lighting and outlets.
1. What is the required amperage/rating for the new subpanel?
Rating: 120v/240v AMPS: 100 Wire: 3 (same as main panel)
1. Could the Government please confirm the approximate distance between the existing emergency panel and the intended location for the new subpanel? If the location has not been finalized, can the new subpanel be installed as close as practical to the existing emergency panel, assuming code-required clearances and accessibility are maintained?
The location can be installed as close to the existing panel and/or same location.
1. Could the Government please confirm the required amperage/rating for the new subpanel? Would a 100-amp subpanel be acceptable for this requirement, or does the Government require a different rating based on the intended circuits and loads?
Please see Q#3.