Text version
08-03-2018
A00002
Q1. Ref: Spec. Section 013591‐5 “Historic Treatment Procedures”, para. 1.8.A. Is it a requirement to hire outside full‐time supervisors to perform this work, or can our onsite General Superintendent perform this work? Or can a qualified subcontractor perform this work with their own supervisors?
A1. The intent of paragraph 1.8.A in the Quality Assurance section of the Historic Treatment Procedures is two‐fold:
1. To make sure that the specified project work is being done by a firm with successful experience that is similar in nature, materials, design, and extent to the type of work indicated in the project documents; and
2. The crew performing said work is being overseen by full‐time supervisors (with successful experience that is similar in nature, materials, design and extent to the type of work being performed) when the work starts and throughout its execution, and that there’s a continuity in the full‐time supervisors for the duration of the project.
If the proposed General Superintendent has demonstrated experience in historic preservation, historic repair, and/or historic restoration similar to the work being performed (example: masonry and tile cleaning and repair and/or historic carpentry and/or finish restoration), then said General Superintendent would be qualified to serve as a Supervisor for the work crews performing the historic work. If a General Superintendent does not have experience in the historic work being performed, but senior staff do within the experienced subcontractor’s firm performing the work then said senior staff would be qualified to serve as a Supervisor for the work crews of the subcontractor performing the historic work.
Q2. Is a fulltime Safety Manager, with no other duties, required to be onsite throughout construction?
A2. The Safety Manager may be the same person as the QC Manager as long as the individual meets the required qualifications for both positions. (HLR)
Q3. Please provide an “Allowance” amount per Item 0002 on bid form.
A3. Hazardous Material removal shall be included in the base bid. See attached revised OF336 which shall replace the original OF336 issued with the solicitation.
Q4. The Bid Form (Optional Form 336) calls for “Allowances: Hazardous Materials”, as the second Bid Item #0002, following the Optional CLIN: East Porch which is also Item #0002. Please provide us with the “Allowance” amount that we are to include in our bid for the Removal of the HazMat, and also correct the duplicate numbering on the Bid Form.
A4. See A3 above.
Q5. The Bid Form lists quantities for Unit Price Items #0003 to 0007 as 1 SF each, but the Spec Section 012200 – UNIT PRICES lists quantities which are much greater than what is listed on the Bid Form and also has different Units of Measure. Please update the Bid Form to reflect the quantities and units that you want us to bid on.
3.1 SCHEDULE OF UNIT PRICES
A. Unit Price No. 1: Replacement of damaged roof sheathing (plywood).
1. Description: Remove and dispose of damaged roof sheathing and replace with new and in accordance with applicable specifications. Approximate quantity 700 square feet.
2. Unit of Measurement: Square foot.
B. Unit Price No. 2: Replacement of damaged roof decking.
1. Description: Remove and dispose of damaged roof decking and replace with new to match existing and in accordance with applicable specifications. Approximate quantity 100 square feet.
2. Unit of Measurement: Square foot.
C. Unit Price No. 3: Historic Brick Unit Masonry Replacement
1. Description: Removal of mismatched brick and replacing with better-matching historic clay brick masonry in accordance with applicable specifications. Approximate quantity 100 bricks.
2. Unit of Measurement: Each
D. Unit Price No. 4: Historic Brick Masonry Repointing.
1. Description: Repointing brick masonry joints in accordance with applicable specifications.
Approximate quantity 2400 linear feet.
2. Unit of Measurement: Linear foot.
E. Unit Price No. 5: Hardwood floor patching and repair.
1. Description: Patching, repairing, or replacing wood flooring in areas not already denoted or indicated on the drawings. This unit cost does not include cutting and patching wood floors to install below-floor utilities as indicated on the contract documents.
Approximate quantity 100 square feet.
2. Unit of Measurement: Square foot.
A5. See attached revised OF336 which shall replace the original OF336 issued with the solicitation.
Q6. Spec Section 051200 – Struct Steel Framing, para 1.8.A, calls for an AISC Certified Steel Fabricator. There is a very limited amount of steelwork on this project, and there are no steel subcontractors in this area who meet the AISC qualifications and who are interested in bidding such a small steel project. This strict requirements should not apply to a project of this nature.
Please WAIVE or DELETE the AISC Certification requirements for this project so that we can obtain subcontract bids.
A6. AISC lists 50 certified fabricators within 100 miles of the project site. If we waive the fabricator certification requirement, the scope of Special Inspections will need to increase such that the Fabricators Shop and all shop fabricated items are reviewed by the Special Inspector (paid for by the Contractor).
Q7. Spec Section 051200 – Structural Steel Framing, para 1.8.B, calls for the fabricator to have AISC’s Sophisticated‐Paint Endorsement or SSPC‐QP3 . There are no steel subcontractors in this area who meet this requirement and who are interested in bidding such a small steel project. Please WAIVE or DELETE the Shop‐Painting qualifications for this project so that we can obtain subcontract bids.
A7. The Spec Section 051200 – Structural Steel Framing, para 1.8.B requirement, which calls for the fabricator to have AISC’s Sophisticated‐Paint Endorsement or SSPC‐QP3, may be waived.
Q8. Spec Section 051200 – Structural Steel Framing lists 9 different types of Surface Preparation under para 2.7.B. Which one will apply to the new steel framing on this project?
A8. New steel framing Surface Preparation must be SSPC‐SP 3, “Power Tool Cleaning”; delete the other surface preparations under paragraph 2.7B.
Q9. Due to the major amount of restoration work called for, we will need another site visit for our subcontractors to inspect the site. Otherwise, the risk will be too high for them to take. When can another site visit be arranged?
A9. Due to the milestones to a desired award date, another site visit will not be held prior to proposals being due.
Q10. Specification Section 122413, 1.6.A.1 specifies 5% attic stock. There are not many dual motorized shades in the project.
What attic stock is required for dual motorized shades?
A10. Refer to Addendum item 2.3, no fewer than one unit shall be provided for each type.
Q11. Specification Section 122413, 2.2.F.3 specifies side channels. Are side channels only required for 0% blackout shades?
A11. Delete Sentence 2.2.F.3. Refer to Addendum Item 2.3.
Q12. Specification Section 122413, 2.3.A.4. specifies Crank‐Operator Override. This feature is not available from Hunter Douglas or Lutron. Can this be excluded?
A12. Delete sentence 2.3.4. Refer to Addendum item 2.3.
Q13. Window Notes on Drawing A‐802 says to provide WS‐1 at Window Types W1‐W9A. Are WS‐1 manual shades required at the Basement, Vestibules, Corridors, Stairs, Entrance Hall, Restrooms, Mechanical 406, Reception Lounge 400 West Elevation W8?
A13. Provide manual shades at locations as specified on Drawing Sheet A‐802.
Q14. On Drawing A‐802, detail WH1A, WH1B what type of top treatment is required for these details, recessed shade pockets?
Closure Panel?
A14. Details refer to the roller shade being installed in a recessed shade pocket. Manufacturer’s standard closure panel shall be provided.
Q15. On Drawing A‐802, detail WH3, WH5 what type of top treatment is required for these details, front fascia?
A15. No top treatment is required. Manufacturer’s standard front and side fascia shall be provided.
Q16. Specification Section 312000, para 3.3 notes that the excavation for the project is unclassified. Are there any soil borings? If not, can a quantity/allowance be provided by the Architect for rock/unsuitable materials that would be included in the project bid by all contractors for rock & unsuitable material excavation and replacement with good material?
A16. A geotechnical memo for this project is attached for your reference.
Q17. Specification Section 051200, para 1.8 requires that the steel fabricator participate in the AISC Quality Certification Program. There is a limited amount of structural steel on this project. Can this requirement be waived?
A17. The requirement of Specification Section 051200, para 1.8, which calls for the steel fabricator to participate in the AISC Quality Certification Program, may be waived.
Q18. Drawing C‐101, Note 8, remove the underground storage tank. Are there any requirements for the disposal of this tank?
Can it be left on site?
A18. The fuel oil underground storage tank shall be removed in accordance with all Federal and State regulations. The tank may not be left on site, but shall be disposed of.
Q19. Due to the complexities of this project, can the date for asking questions be extended to August 3rd, 2018?
A.19 Due to the milestones to a desired award date, the due date for additional questions will not be extended to 08‐03‐2018.
Q20. Dwg. C‐202 calls for a concrete encased telecom duct bank. Can you please provide a detail of the required concrete duct bank?
A20. Detail has been added to Drawing Sheet C‐501. Refer to attachment.
Q21. Can another day be provided to allow subcontractors access to the building prior to the bid?
A.21 Due to the milestones to a desired award date, another site visit will not be held prior to proposals being due.
Q22. Can you please verify that the Bid Bond Requirement is to be 25% of the value or $4,000,000 whichever is lower?
A.22 Section I.8 FAR 52.228‐1 Bid Guarantee (Sep 1996) reads correctly in the solicitation.
Q23. Does ALL debris from demo operations have to be hauled and disposed of off‐site?
A23. Yes, all debris shall be disposed of legally off Government Property. Refer to Specification Section 017419, Paragraph 3.6.
Q24. Can the QC Manager for the project be the Contractor’s Site Superintendent or Project Manager?
A24. No.
Q25. Can the Contractor’s Site Superintendent oversee the work at both Building 405 & 413 or will separate Superintendents be required?
A25. No, they cannot oversee both projects.
&217,18$7,21�6+((7
5()(5(1&(�12��2)�'2&80(17�%(,1*�&217,18(' 3$*(6
1$0(�2)�2))(525�25�&2175$&725
,7(0��12� 6833/,(6�6(59,&(6 48$17,7< 81,7 81,7��35,&( $02817
161����������������� 237,21$/�)250�����������
6SRQVRUHG�E\�*6$�)$5�����&)5��������
UNCLASSIFIED
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROUGH CARPENTRY 061000 - 1
SECTION 061000 - ROUGH CARPENTRY
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Wood blocking, cants, and nailers.
2. Wood furring and grounds.
3. Plywood backing panels.
4. Wood connector.
1.3 DEFINITIONS
A. Boards or Strips: Lumber of less than 2 inches nominal (38 mm actual) size in least dimension.
B. Dimension Lumber: Lumber of 2 inches nominal (38 mm actual) size or greater but less than 5 inches nominal (114 mm actual) size in least dimension.
C. Exposed Framing: Framing not concealed by other construction.
D. Timber: Lumber of 5 inches nominal (114 mm actual) size or greater in least dimension.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details.
1. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Indicate type of preservative used and net amount of preservative retained.
2. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Include physical properties of treated materials based on testing by a qualified independent testing agency.
3. For fire-retardant treatments, include physical properties of treated lumber both before and after exposure to elevated temperatures, based on testing by a qualified independent testing agency according to ASTM D 5664.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROUGH CARPENTRY 061000 - 2
4. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site.
1.5 INFORMATIONAL SUBMITTALS
A. Material Certificates: For dimension lumber specified to comply with minimum allowable unit stresses. Indicate species and grade selected for each use and design values approved by the ALSC
Board of Review.
B. Wood connectors: Design of connectors are to be delegated; submit cut sheets or documentation to show that the joist hangers and fasteners submitted can support the load shown on the contract drawings. Submittal must be stamped and signed by a Professional Engineer licensed in the
Commonwealth of Virginia who is responsible for the design and selection of the connectors and fasteners.
C. Evaluation Reports: For the following, from ICC-ES:
1. Wood-preservative-treated wood.
2. Fire-retardant-treated wood.
3. Power-driven fasteners.
4. Post-installed anchors.
5. Metal framing anchors.
6. Wood connectors.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Stack wood products flat with spacers beneath and between each bundle to provide air circulation.
Protect wood products from weather by covering with waterproof sheeting, securely anchored.
Provide for air circulation around stacks and under coverings.
PART 2 - PRODUCTS
2.1 WOOD PRODUCTS, GENERAL
A. Maximum Moisture Content of Lumber: 19 percent
2.2 WOOD-PRESERVATIVE-TREATED LUMBER
A. Preservative Treatment by Pressure Process: AWPA U1; Use Category UC2
1. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no arsenic or chromium.
2. For exposed items indicated to receive a stained or natural finish, chemical formulations shall not require incising, contain colorants, bleed through, or otherwise adversely affect finishes.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROUGH CARPENTRY 061000 - 3
B. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent. Do not use material that is warped or that does not comply with requirements for untreated material.
C. Application: Treat items indicated on Drawings, and the following:
1. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.
2. Wood sills, sleepers, blocking, furring, stripping, and similar concealed members in contact with masonry or concrete.
3. Wood framing and furring attached directly to the interior of below-grade exterior masonry or concrete walls.
4. Wood framing members that are less than 18 inches (460 mm) above the ground in crawlspaces or unexcavated areas.
5. Wood floor plates that are installed over concrete slabs-on-grade.
2.3 FIRE-RETARDANT-TREATED MATERIALS
A. General: Where fire-retardant-treated materials are indicated, materials shall comply with requirements in this article, that are acceptable to authorities having jurisdiction, and with fire-test-response characteristics specified as determined by testing identical products per test method indicated by a qualified testing agency.
B. Fire-Retardant-Treated Lumber and Plywood by Pressure Process: Products with a flame-spread index of 25 or less when tested according to ASTM E 84, and with no evidence of significant progressive combustion when the test is extended an additional 20 minutes, and with the flame front not extending more than 10.5 feet (3.2 m) beyond the centerline of the burners at any time during the test.
1. Treatment shall not promote corrosion of metal fasteners.
2. Interior Type A: Treated materials shall have a moisture content of 28 percent or less when tested according to ASTM D 3201 at 92 percent relative humidity. Use where exterior type is not indicated.
3. Design Value Adjustment Factors: Treated lumber shall be tested according to
ASTM D 5664 and design value adjustment factors shall be calculated according to
ASTM D 6841
C. Kiln-dry lumber after treatment to maximum moisture content of 19 percent. Kiln-dry plywood after treatment to maximum moisture content of 15 percent.
D. Identify fire-retardant-treated wood with appropriate classification marking of qualified testing agency.
E. For exposed items indicated to receive a stained or natural finish, chemical formulations shall not bleed through, contain colorants, or otherwise adversely affect finishes.
F. Application: Treat items indicated on Drawings, and the following:
1. Framing for raised platforms.
2. Framing for stages.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROUGH CARPENTRY 061000 - 4
3. Concealed blocking.
4. Framing for non-load-bearing partitions.
5. Framing for non-load-bearing exterior walls.
6. Roof construction.
7. Plywood backing panels.
2.4 DIMENSION LUMBER FRAMING
A. Joists, Rafters, and Other Framing Not Listed Above: No. 1 grade.
1. Species:
a. Southern Pine, or approved equal.
2.5 MISCELLANEOUS LUMBER
A. General: Provide miscellaneous lumber indicated and lumber for support or attachment of other construction, including the following:
1. Blocking.
2. Nailers.
3. Rooftop equipment bases and support curbs.
4. Cants.
5. Furring.
6. Grounds.
B. Dimension Lumber Items: Construction or No. 2 grade lumber of any species.
C. Concealed Boards: 19 percent maximum moisture content and any of the following species and grades:
1. Mixed southern pine or southern pine; No. 2 grade; SPIB.
2. Hem-fir or hem-fir (north); Construction or No. 2 Common grade; NLGA, WCLIB, or
WWPA.
3. Spruce-pine-fir (south) or spruce-pine-fir; Construction or No. 2 Common grade; NeLMA, NLGA, WCLIB, or WWPA.
4. Eastern softwoods; No. 2 Common grade; NLMA.
5. Northern species; No. 2 Common grade; NLGA.
6. Western woods; Construction or No. 2 Common grade; WCLIB or WWPA.
D. For blocking not used for attachment of other construction, Utility, Stud, or No. 3 grade lumber of any species may be used provided that it is cut and selected to eliminate defects that will interfere with its attachment and purpose.
E. For blocking and nailers used for attachment of other construction, select and cut lumber to eliminate knots and other defects that will interfere with attachment of other work.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROUGH CARPENTRY 061000 - 5
F. For furring strips for installing plywood or hardboard paneling, select boards with no knots capable of producing bent-over nails and damage to paneling.
2.6 FASTENERS
A. General: Fasteners shall be of size and type indicated and shall comply with requirements specified in this article for material and manufacture.
1. Where rough carpentry is exposed to weather, in ground contact, pressure-preservative treated, or in area of high relative humidity, provide fasteners with hot-dip zinc coating complying with ASTM A 153/A 153M.
B. Nails, Brads, and Staples: ASTM F 1667.
C. Lag Bolts: ASME B18.2.1.
D. Power-Driven Fasteners: Fastener systems with an evaluation report acceptable to authorities having jurisdiction, based on ICC-ES AC70.
E. Post-Installed Anchors: Fastener systems with an evaluation report acceptable to authorities having jurisdiction, based on ICC-ES AC01 as appropriate for the substrate.
1. Material: Carbon-steel components, zinc plated to comply with ASTM B 633, Class Fe/Zn 5.
2. Material: Stainless steel with bolts and nuts complying with ASTM F 593 and
ASTM F 594, Alloy Group 1 or 2 (ASTM F 738M and ASTM F 836M, Grade A1 or A4).
2.7 METAL FRAMING ANCHORS
A. Allowable design loads, as published by manufacturer, shall meet or exceed those indicated.
Manufacturer's published values shall be determined from empirical data or by rational engineering analysis and demonstrated by comprehensive testing performed by a qualified independent testing agency. Framing anchors shall be punched for fasteners adequate to withstand same loads as framing anchors.
B. Galvanized-Steel Sheet: Hot-dip, zinc-coated steel sheet complying with ASTM A 653/A 653M, G60 (Z180) coating designation.
1. Use for interior locations unless otherwise indicated.
C. Hot-Dip, Heavy-Galvanized Steel Sheet: ASTM A 653/A 653M; structural steel (SS), high-strength low-alloy steel Type A (HSLAS Type A), or high-strength low-alloy steel Type B
(HSLAS Type B); G185 (Z550) coating designation; and not less than 0.036 inch (0.9 mm) thick.
1. Use for wood-preservative-treated lumber and where indicated.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROUGH CARPENTRY 061000 - 6
2.8 MISCELLANEOUS MATERIALS
A. Sill-Sealer Gaskets: Glass-fiber-resilient insulation, fabricated in strip form, for use as a sill sealer; 1-inch (25-mm) nominal thickness, compressible to 1/32 inch (0.8 mm); selected from manufacturer's standard widths to suit width of sill members indicated.
B. Sill-Sealer Gaskets: Closed-cell neoprene foam, 1/4 inch (6.4 mm) thick, selected from manufacturer's standard widths to suit width of sill members indicated.
C. Water-Repellent Preservative: NWWDA-tested and -accepted formulation containing 3-iodo-2-propynyl butyl carbamate, combined with an insecticide containing chloropyrifos as its active ingredient.
2.9 WOOD CONNECTORS
A. Allowable design loads, as published by manufacturer, shall meet or exceed those indicated.
B. Connectors (Joist hanger): Hot-dip, zinc-coated steel sheet complying with G90 coating designation.
2.10 ROOF SHEATHING
A. Plywood Sheathing: DOC PS 1, Exterior, Structural I sheathing.
1. Span Rating: Not less than 32/16
2. Nominal Thickness: Not less than 1/2 inch
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. Framing Standard: Comply with AF&PA's WCD 1, "Details for Conventional Wood Frame
Construction," unless otherwise indicated.
B. Set rough carpentry to required levels and lines, with members plumb, true to line, cut, and fitted.
Fit rough carpentry accurately to other construction. Locate furring, nailers, blocking, grounds, and similar supports to comply with requirements for attaching other construction.
C. Install metal framing anchors to comply with manufacturer's written instructions. Install fasteners through each fastener hole.
D. Install sill sealer gasket to form continuous seal between sill plates and foundation walls.
E. Do not splice structural members between supports unless otherwise indicated.
F. Provide blocking and framing as indicated and as required to support facing materials, fixtures, specialty items, and trim.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROUGH CARPENTRY 061000 - 7
1. Provide metal clips for fastening gypsum board or lath at corners and intersections where framing or blocking does not provide a surface for fastening edges of panels. Space clips not more than 16 inches (406 mm) o.c.
G. Provide fire blocking in furred spaces, stud spaces, and other concealed cavities as indicated and as follows:
1. Fire block furred spaces of walls, at each floor level, at ceiling, and at not more than 96 inches (2438 mm) o.c. with solid wood blocking or noncombustible materials accurately fitted to close furred spaces.
2. Fire block concealed spaces of wood-framed walls and partitions at each floor level, at ceiling line of top story, and at not more than 96 inches (2438 mm) o.c. Where fire blocking is not inherent in framing system used, provide closely fitted solid wood blocks of same width as framing members and 2-inch nominal (38-mm actual) thickness.
3. Fire block concealed spaces between floor sleepers with same material as sleepers to limit concealed spaces to not more than 100 sq. ft. (9.3 sq. m) and to solidly fill space below partitions.
4. Fire block concealed spaces behind combustible cornices and exterior trim at not more than
20 feet (6 m) o.c.
H. Sort and select lumber so that natural characteristics do not interfere with installation or with fastening other materials to lumber. Do not use materials with defects that interfere with function of member or pieces that are too small to use with minimum number of joints or optimum joint arrangement.
I. Comply with AWPA M4 for applying field treatment to cut surfaces of preservative-treated lumber.
1. Use inorganic boron for items that are continuously protected from liquid water.
2. Use copper naphthenate for items not continuously protected from liquid water.
J. Where wood-preservative-treated lumber is installed adjacent to metal decking, install continuous flexible flashing separator between wood and metal decking.
K. Securely attach rough carpentry work to substrate by anchoring and fastening as indicated, complying with the following:
1. Table 2304.9.1, "Fastening Schedule," in ICC's International Building Code (IBC).
2. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in ICC's International Residential Code for One- and Two-
Family Dwellings.
3. ICC-ES evaluation report for fastener.
L. Use steel common nails unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials.
Make tight connections between members. Install fasteners without splitting wood. Drive nails snug but do not countersink nail heads unless otherwise indicated.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROUGH CARPENTRY 061000 - 8
3.2 WOOD BLOCKING, AND NAILER INSTALLATION
A. Install where indicated and where required for attaching other work. Form to shapes indicated and cut as required for true line and level of attached work. Coordinate locations with other work involved.
B. Attach items to substrates to support applied loading. Recess bolts and nuts flush with surfaces unless otherwise indicated.
C. Provide permanent grounds of dressed, pressure-preservative-treated, key-beveled lumber not less than 1-1/2 inches (38 mm) wide and of thickness required to bring face of ground to exact thickness of finish material. Remove temporary grounds when no longer required.
3.3 PROTECTION
A. Protect wood that has been treated with inorganic boron (SBX) from weather. If, despite protection, inorganic boron-treated wood becomes wet, apply EPA-registered borate treatment.
Apply borate solution by spraying to comply with EPA-registered label.
B. Protect rough carpentry from weather. If, despite protection, rough carpentry becomes wet, apply
EPA-registered borate treatment. Apply borate solution by spraying to comply with EPA-registered label.
END OF SECTION 061000
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised Aug 3, 2018
RESILIENT BASE AND ACCESSORIES 096513 - 1
SECTION 096513 - RESILIENT BASE AND ACCESSORIES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Thermoset-rubber base.
2. Thermoplastic-rubber base.
3. Rubber molding accessories.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples for Initial Selection: For each type of product indicated.
C. Product Schedule: For resilient base and accessory products. Use same designations indicated on
Drawings.
1.4 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Furnish not less than 10 linear feet for every 500 linear feet or fraction thereof, of each type, color, pattern, and size of resilient product installed.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Store resilient products and installation materials in dry spaces protected from the weather, with ambient temperatures maintained within range recommended by manufacturer, but not less than
50 deg F or more than 90 deg F.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised Aug 3, 2018
RESILIENT BASE AND ACCESSORIES 096513 - 2
1.6 FIELD CONDITIONS
A. Maintain ambient temperatures within range recommended by manufacturer, but not less than 70 deg F or more than 95 deg F, in spaces to receive resilient products during the following periods:
1. 48 hours before installation.
2. During installation.
3. 48 hours after installation.
B. After installation and until Substantial Completion, maintain ambient temperatures within range recommended by manufacturer, but not less than 55 deg F 95 deg F.
C. Install resilient products after other finishing operations, including painting, have been completed.
PART 2 - PRODUCTS
2.1 THERMOPLASTIC-RUBBER BASE
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Burke Mercer Flooring Products; a division of Burke Industries Inc.
2. Flexco.
3. Johnsonite; A Tarkett Company.
4. Roppe Corporation, USA.
B. Product Standard: ASTM F 1861, Type TP (rubber, thermoplastic).
1. Group: I (solid, homogeneous) or II (layered).
2. Style and Location:
a. Style A, Straight: Provide in areas with carpet.
b. Style B, Cove: Provide in areas with resilient floor coverings.
C. Thickness: 0.125 inch.
D. Height: 6 inches.
E. Lengths: Cut lengths 48 inches long or coils in manufacturer's standard length.
F. Outside Corners: Job formed.
G. Inside Corners: Job formed.
H. Colors: As indicated on drawings.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised Aug 3, 2018
RESILIENT BASE AND ACCESSORIES 096513 - 3
2.2 RUBBER MOLDING ACCESSORY
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Allstate Rubber Corp.
2. Armstrong World Industries, Inc.
3. Burke Mercer Flooring Products; a division of Burke Industries Inc.
4. Flexco.
5. Johnsonite; A Tarkett Company.
6. Nora Systems, Inc.
7. Roppe Corporation, USA.
8. VPI Corporation.
B. Description: Rubber carpet edge for glue-down applications nosing for resilient floor covering, transition strips.
C. Profile and Dimensions: As indicated on drawings.
D. Locations: Provide rubber molding accessories in areas indicated.
E. Colors and Patterns: As indicated on drawings.
2.3 INSTALLATION MATERIALS
A. Trowelable Leveling and Patching Compounds: Latex-modified, portland-cement-based or blended hydraulic-cement-based formulation provided or approved by resilient-product manufacturer for applications indicated.
B. Adhesives: Water-resistant type recommended by resilient-product manufacturer for resilient products and substrate conditions indicated.
C. Floor Polish: Provide protective, liquid floor-polish products recommended by resilient stair-tread manufacturer.
2.4 RUBBER STAIR ACCESSORIES
A. Fire-Test-Response Characteristics: As determined by testing identical products according to
ASTM E648 or NFPA 253 by a qualified testing agency.
1. Critical Radiant Flux Classification: Class I, not less than 0.45 W/sq. cm.
B. Stair Treads: ASTM F2169.
1. Type: TS (rubber, vulcanized thermoset)
2. Class: 2 (pattern; embossed, grooved, or ribbed)
3. Group: 2 (with contrasting color for the visually impaired).
4. Nosing Style: Square
5. Nosing Height: 2 inches.
6. Thickness: Manufacturer’s standard
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised Aug 3, 2018
RESILIENT BASE AND ACCESSORIES 096513 - 4
7. Size: Lengths and depths to fit each stair tread in one piece.
C. Separate Risers: Smooth, flat; in height that fully covers substrate; produced by same manufac-turer as treads and recommended by manufacturer for installation with treads.
1. Style: Toeless, by length matching treads.
2. Thickness: Manufacturer's standard.
D. Locations: Provide rubber stair accessories in areas indicated on finish schedule.
E. Colors and Patterns: As indicated on finish schedule.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, with Installer present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work.
1. Verify that finishes of substrates comply with tolerances and other requirements specified in other Sections and that substrates are free of cracks, ridges, depressions, scale, and foreign deposits that might interfere with adhesion of resilient products.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
1. Installation of resilient products indicates acceptance of surfaces and conditions.
3.2 PREPARATION
A. Prepare substrates according to manufacturer's written instructions to ensure adhesion of resilient products.
B. Concrete Substrates for Resilient Stair Accessories: Prepare horizontal surfaces according to
ASTM F 710.
1. Verify that substrates are dry and free of curing compounds, sealers, and hardeners.
2. Remove substrate coatings and other substances that are incompatible with adhesives and that contain soap, wax, oil, or silicone, using mechanical methods recommended by manufacturer. Do not use solvents.
3. Alkalinity and Adhesion Testing: Perform tests recommended by manufacturer. Proceed with installation only after substrate alkalinity falls within range on pH scale recommended by manufacturer in writing, but not less than 5 or more than 9 pH.
4. Moisture Testing: Perform tests so that each test area does not exceed 200 sq. ft., and perform no fewer than three tests in each installation area and with test areas evenly spaced in installation areas.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised Aug 3, 2018
RESILIENT BASE AND ACCESSORIES 096513 - 5
a. Anhydrous Calcium Chloride Test: ASTM F 1869. Proceed with installation only after substrates have maximum moisture-vapor-emission rate of 3 lb of water/1000
sq. ft. in 24 hours.
b. Relative Humidity Test: Using in-situ probes, ASTM F 2170. Proceed with installation only after substrates have a maximum 75 percent relative humidity level measurement.
C. Fill cracks, holes, and depressions in substrates with trowelable leveling and patching compound;
remove bumps and ridges to produce a uniform and smooth substrate.
D. Do not install resilient products until materials are the same temperature as space where they are to be installed.
1. At least 48 hours in advance of installation, move resilient products and installation materials into spaces where they will be installed.
E. Immediately before installation, sweep and vacuum clean substrates to be covered by resilient products.
3.3 RESILIENT BASE INSTALLATION
A. Comply with manufacturer's written instructions for installing resilient base.
B. Apply resilient base to walls, columns, pilasters, casework and cabinets in toe spaces, and other permanent fixtures in rooms and areas where base is required.
C. Install resilient base in lengths as long as practical without gaps at seams and with tops of adjacent pieces aligned.
D. Tightly adhere resilient base to substrate throughout length of each piece, with base in continuous contact with horizontal and vertical substrates.
E. Do not stretch resilient base during installation.
F. On masonry surfaces or other similar irregular substrates, fill voids along top edge of resilient base with manufacturer's recommended adhesive filler material.
G. Job-Formed Corners:
1. Outside Corners: Use straight pieces of maximum lengths possible and form with returns not less than 3 inches in length.
a. Form without producing discoloration (whitening) at bends.
2. Inside Corners: Use straight pieces of maximum lengths possible and form with returns not less than 3 inches in length.
a. Miter or cope corners to minimize open joints.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised Aug 3, 2018
RESILIENT BASE AND ACCESSORIES 096513 - 6
3.4 RESILIENT ACCESSORY INSTALLATION
A. Comply with manufacturer's written instructions for installing resilient accessories.
B. Resilient Stair Accessories:
1. Use stair-tread-nose filler to fill nosing substrates that do not conform to tread contours.
2. Tightly adhere to substrates throughout length of each piece.
3. For treads installed as separate, equal-length units, install to produce a flush joint between units.
C. Resilient Molding Accessories: Butt to adjacent materials and tightly adhere to substrates throughout length of each piece. Install reducer strips at edges of floor covering that would otherwise be exposed.
3.5 CLEANING AND PROTECTION
A. Comply with manufacturer's written instructions for cleaning and protecting resilient products.
B. Perform the following operations immediately after completing resilient-product installation:
1. Remove adhesive and other blemishes from surfaces.
2. Sweep and vacuum horizontal surfaces thoroughly.
3. Damp-mop horizontal surfaces to remove marks and soil.
C. Protect resilient products from mars, marks, indentations, and other damage from construction operations and placement of equipment and fixtures during remainder of construction period.
D. Cover resilient products subject to wear and foot traffic until Substantial Completion.
END OF SECTION 096513
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROLLER WINDOW SHADES 122413 - 1
SECTION 122413 - ROLLER WINDOW SHADES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Manually operated roller shades with single and double rollers.
2. Motor-operated roller shades with double rollers.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components and profiles, features, finishes, and operating instructions for roller shades.
B. Shop Drawings: Show fabrication and installation details for roller shades, including shadeband materials, their orientation to rollers, and their seam and batten locations.
1. Motor-Operated Shades: Include details of installation and diagrams for power, signal, and control wiring.
C. Samples: For each exposed product and for each color and texture specified, 10 inches long.
D. Samples for Initial Selection: For each type and color of shadeband material.
1. Include Samples of accessories involving color selection.
E. Samples for Verification: For each type of roller shade.
1. Shadeband Material: Not less than 10 inches square. Mark interior face of material if applicable.
2. Roller Shade: Full-size operating unit, not less than 16 inches wide by 36 inches long for each type of roller shade indicated.
3. Installation Accessories: Full-size unit, not less than 10 inches long.
F. Product Schedule: For roller shades. Use same designations indicated on Drawings.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROLLER WINDOW SHADES 122413 - 2
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer.
B. Product Certificates: For each type of shadeband material.
C. Product Test Reports: For each type of shadeband material, for tests performed by a qualified testing agency.
1.5 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For roller shades to include in maintenance manuals.
1.6 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Roller Shades: Full-size units equal to 5 percent of quantity installed for each size, color, and shadeband material indicated, but no fewer than one unit.
1.7 QUALITY ASSURANCE
A. Installer Qualifications: Fabricator of products.
B. Mockups: Build mockups to verify selections made under Sample submittals, to demonstrate aesthetic effects, and to set quality standards for fabrication and installation.
1. Approval of mockups does not constitute approval of deviations from the Contract
Documents contained in mockups unless Architect specifically approves such deviations in writing.
2. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Deliver roller shades in factory packages, marked with manufacturer, product name, and location of installation using same designations indicated on Drawings.
1.9 FIELD CONDITIONS
A. Environmental Limitations: Do not install roller shades until construction and finish work in spaces, including painting, is complete and dry and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROLLER WINDOW SHADES 122413 - 3
B. Field Measurements: Where roller shades are indicated to fit to other construction, verify dimensions of other construction by field measurements before fabrication and indicate measurements on Shop Drawings. Allow clearances for operating hardware of operable glazed units through entire operating range. Notify Architect of installation conditions that vary from
Drawings. Coordinate fabrication schedule with construction progress to avoid delaying the
Work.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Basis of Design Product: Subject to compliance with requirements, provide the following or an approved equal from one of the following:
1. Mechoshade Systems Inc. “Mecho 5 Wide Bracket” (where single rollers are indicated)
2. Mechoshade Systems, Inc. “Electrol 1 / DoubleShade 13” (where electrified double rollers are indicated.
3. Approved equal manufacturers, subject to product fitting in available space, include:
a. Hunter Douglas
b. Lutron Electronics Co., Inc.
2.2 MANUALLY OPERATED SHADES WITH SINGLE ROLLERS
A. Chain-and-Clutch Operating Mechanisms: With continuous-loop bead chain and clutch that stops shade movement when bead chain is released; permanently adjusted and lubricated.
1. Bead Chains: Stainless steel.
a. Loop Length: Full length of roller shade.
b. Limit Stops: Provide upper and lower ball stops.
c. Chain-Retainer Type: Chain tensioner, jamb mounted.
2. Spring Lift-Assist Mechanisms: Manufacturer's standard for balancing roller shade weight and for lifting heavy roller shades.
a. Provide for shadebands that weigh more than 10 lb or for shades as recommended by manufacturer, whichever criterion is more stringent.
B. Rollers: Corrosion-resistant steel or extruded-aluminum tubes of diameters and wall thicknesses required to accommodate operating mechanisms and weights and widths of shadebands indicated without deflection. Provide with permanently lubricated drive-end assemblies and idle-end assemblies designed to facilitate removal of shadebands for service.
1. Roller Drive-End Location: Right side of interior face of shade.
2. Direction of Shadeband Roll: Regular, from back (exterior face) of roller.
3. Shadeband-to-Roller Attachment: Removable spline fitting into integral channel in tube.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROLLER WINDOW SHADES 122413 - 4
C. Mounting Hardware: Brackets or endcaps, corrosion resistant and compatible with roller assembly, operating mechanism, installation accessories, and mounting location and conditions indicated.
D. Roller-Coupling Assemblies: Coordinated with operating mechanism and designed to join up to three inline rollers into a multiband shade that is operated by one roller drive-end assembly.
E. Shadebands:
1. Shadeband Material: Light-filtering fabric and Light-blocking fabric.
2. Shadeband Bottom (Hem) Bar: Steel or extruded aluminum.
a. Type: Enclosed in sealed pocket of shadeband material.
b. Color and Finish: As indicated on Drawings.
F. Installation Accessories:
1. Recessed Shade Pocket: Rectangular, extruded-aluminum enclosure designed for recessed ceiling installation; with front, top, and back formed as one piece, end plates, and removable bottom closure panel.
a. Height: Manufacturer's standard height required to enclose roller and shadeband assembly when shade is fully open, but not less than 4 inches.
b. Provide pocket with lip at lower edge to support acoustical ceiling panel.
2. Closure Panel and Wall Clip: Removable aluminum panel designed for installation at bottom of site-constructed ceiling recess or pocket and for snap-in attachment to wall clip without fasteners.
a. Closure-Panel Width: 2 inches.
3. Side Channels: With light seals and designed to eliminate light gaps at sides of shades as shades are drawn down. Provide side channels with shadeband guides or other means of aligning shadebands with channels at tops.
4. Bottom (Sill) Channel or Angle: With light seals and designed to eliminate light gaps at bottoms of shades when shades are closed.
5. Installation Accessories Color and Finish: As selected from manufacturer's full range.
2.3 MOTOR-OPERATED, DOUBLE-ROLLER SHADES
A. Motorized Operating Systems: Provide factory-assembled, shade-operator systems of size and capacity and with features, characteristics, and accessories suitable for conditions indicated, complete with electric motor and factory-prewired motor controls, power disconnect switch, enclosures protecting controls and operating parts, and accessories required for reliable operation without malfunction. Include wiring from motor controls to motors. Coordinate operator wiring requirements and electrical characteristics with building electrical system.
1. Electrical Components: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2. Electric Motor: Manufacturer's standard tubular, enclosed in rollers.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000014 Revised August 3, 2018
ROLLER WINDOW SHADES 122413 - 5
a. Electrical Characteristics: 110-V ac, 60Hz.
b. Maximum Total Shade Width: As required to operate roller shades indicated.
c. Maximum Shade Drop: As required to operate roller shades indicated.
d. Maximum Weight Capacity: As required to operate roller shades indicated.
3. Remote Control: Electric controls with NEMA ICS 6, Type 1 enclosure for surface mounting. Provide the following for remote-control activation of shades:
a. Individual/Group Control Station: Momentary-contact, three-position, rocker-style, wall-switch-operated control station with open, close, and center off functions for individual and group control.
b. Microprocessor Control: Electronic programmable means for setting, changing, and adjusting control features; isolated from voltage spikes and surges.
c. Color: As selected by Architect from manufacturer's full range.
4. Crank-Operator Override: Crank and gearbox operate shades in event of power outage or motor failure.
5. Limit Switches: Adjustable switches, interlocked with motor controls and set to stop shade movement automatically at fully raised and fully lowered positions.
6. Operating Features:
a. Group switching with integrated switch control; single faceplate for multiple switch cutouts.
b. Capable of interface with audiovisual control system.
c. Capable of accepting input from building automation control system.
d. Override switch.
B. Rollers: Corrosion-resistant steel or extruded-aluminum tubes of diameters and wall thicknesses required to accommodate operating mechanisms and weights and widths of shadebands indicated without deflection. Provide with permanently lubricated drive-end assemblies and idle-end assemblies designed to facilitate removal of shades for service.
1. Double-Roller Mounting Configuration: Offset, outside shade over and inside shade under.
2. Inside Roller:
a. Drive-End Location: Right side of interior face of shade.
b. Direction of Shadeband Roll: Regular, from back (exterior face) of roller.
3. Outside Roller:
a. Drive-End Location: Right side of interior face of shade.
b. Direction of Shadeband Roll: Regular, from back (exterior face) of roller.
4. Shadeband-to-Roller Attachment: Manufacturer's standard method.
C. Mounting Hardware: Brackets or endcaps, corrosion resistant and compatible with roller mounting configuration, roller assemblies, operating mechanisms, installation accessories, and installation locations and conditions indicated.
Building 405 Historic Rehabilitation and Code Compliance Issued For Construction