ADDENDUM MEMORANDUM
Work Order Number: 90155-009
Solicitation Number: 70FA5018R00000013
Project: Building 413 Historic Rehabilitation and Code Compliance
Date: 8 August 2018
Subject: Addendum #3
BUILDING 413 HISTORIC REHABILITATION AND CODE COMPLIANCE – ADDENDUM #3
7 AUGUST 2018
The following modifications shall be incorporated into the Contract Documents:
ADD 3.1: ADDITION OF FALL PROTECTION ANCHORS SPECIFICATION
Description: Add Fall Protection Anchors Specification (112433) to project requirements.
ADD specification 112433 “Fall Protection Anchors”
ADD 3.2: ADDITION OF INFRASTRUCTURE FOR MICROPHONES AND SPEAKERS
Description: Added conduit and backbox information to support ceiling mounted conferencing devices.
REPLACE Drawing Sheet T1-001 and Sheet T1-201 with revised drawing sheets attached.
ADD 3.3: MODIFICATIONS TO PIPE ROUTING
Description: Hydronic piping in 2nd floor ceiling adjusted.
REPLACE Drawing Sheet M1-103 with revised drawing sheets attached.
ADD 3.4: MODIFICATIONS TO JOISTS FOR DUCTWORK
Description: Modify existing floor joists and add sistered joists to support ductwork openings in existing floor.
REPLACE Drawing Sheets S1-005, S1-104, and S1-105 with revised drawing sheets attached.
UNCLASSIFIED
Building 413 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000013 August 6, 2018
FALL PROTECTION ANCHORS 112433 - 1
SECTION 112433 - FALL PROTECTION ANCHORS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Fixed roof anchor.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Fixed roof anchor.
B. Shop Drawings:
1. Fixed roof anchor including signed and sealed calculations.
1.4 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in the design, fabrication, and installation of fall protection systems and maintenance equipment with at least 5 years of successful documented experience.
B. Installer Qualifications: If different than the manufacturer, shall be approved by the manufacturer for the installation of their products.
C. Loading and Safety Assurance: Work of this Section to meet the requirements of governing codes and jurisdiction and to comply with properly engineered loading and safety criteria for the intended use.
D. Liability Insurance: Manufacturer shall have specific liability insurance (products and completed operations) insurance in the amount of $2,000,000.00 minimum. This insurance shall cover the failure of any part of the fall protection system and equipment installed or supplied on this project.
Building 413 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000013 August 6, 2018
FALL PROTECTION ANCHORS 112433 - 2
1.5 DELIVERY, STORAGE, AND HANDLING
A. Protect from corrosion, deformation, and other types of damage. Store items in an enclosed area free from contact with soil and weather. Remove and replace damaged items with new items.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Structural Carbon Steel: ASTM A36/A36M, ASTM A 1011.
B. Structural Tubing: ASTM A500/A500M.
C. Steel Pipe: ASTM A53/A53M, Type E or S, Grade B.
D. Anchor Bolts: ASTM A307. Where exposed, shall be of the same material, color, and finish as the metal to which applied.
1. Bolts, Nuts, Studs and Rivets: ASME B18.2.2 or ASTM A307.
2. Powder Actuated Fasteners: Follow safety provisions of ASSE/SAFE A10.3.
3. Washers: Provide plain washers to conform to ASME B18.21.1. Provide beveled washers for American Standard beams and channels, square or rectangular, tapered in thickness, and smooth. Provide lock washers to conform to ASME B18.21.1.
2.2 FABRICATION FINISHES
A. Galvanizing: Hot-dip galvanize items specified to be zinc-coated, after fabrication where practicable. Galvanizing: ASTM A123/A123M, ASTM A153/A153M, ASTM A653/A653M or ASTM A924/A924M, G90, as applicable.
B. Galvanize: Anchor bolts, grating fasteners, washers, and parts or devices necessary for proper installation, unless indicated otherwise.
C. Repair of Zinc-Coated Surfaces: Repair damaged surfaces with galvanizing repair method and paint conforming to ASTM A780/A780M or by application of stick or thick paste material specifically designed for repair of galvanizing, as approved by Contracting Officer. Clean areas to be repaired and remove slag from welds. Heat surfaces to which stick or paste material is applied, with a torch to a temperature sufficient to melt the metallics in stick or paste; spread molten material uniformly over surfaces to be coated and wipe off excess material.
2.3 FIXED ROOF ANCHOR PERFORMANCE REQUIREMENTS
A. Characteristics: Fall protection strap anchors designed to connect to the building structure given the different mounting conditions encountered.
1. Exposed top of anchor shall be completely watertight.
Building 413 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000013 August 6, 2018
FALL PROTECTION ANCHORS 112433 - 3
2. Anchor shall be configured to allow the flashing to slip easily into place over the top of the anchor and allow the sealing of the flashing to the anchor and adjacent roofing.
3. Material: Hot dipped galvanized; tensile strength, size and wall thickness as required by anchor design.
4. Connection to Building Structure: Coordinate with structural framing at retro-fit roof framing.
B. Source Manufacturers: Subject to their ability to conform to the requirements of this Section and the Drawings, the following manufacturers are acceptable:
1. SuperAnchor / (855) 301-4575 / www.superanchor.com
2. Guardian Fall Protection Inc. (800) 466-6385/www.guardianfall.com.
3. Pro-Bel (800) 461-0575/www.pro-belgroup.com.
4. Atlas Anchor Systems (206) 870-7840/www.atlas-anchor.com.
C. Design Criteria: AISC S342L and AISC SG 971. Fall protection anchors shall be designed by either the manufacturer or a single, separate company specializing in both the design and installation of fall protection systems and that has been trained and is authorized to design the manufacturer’s fall protection systems. Design fall protection anchors that comply with all
OSHA Std 1910.66-I requirements and the references listed above and provide a safe, functional anchor point.
1. Industry Standards: Anchors shall conform to accepted industry standards and engineering principles and shall be designed by a Professional Engineer qualified in the design of fall protection equipment, its application and safety requirements. Design anchor that is compatible with fall protection industry standard equipment.
2. Design Data: Anchor design shall be engineered and stamped by a Structural Engineer currently licensed in the State in which the project is constructed, who is experienced and qualified in the design of fall protection systems, their application and safety requirements. Design the connection of the fall protection anchors to the building structure to resist the design loads required by OSHA without overstressing any part of the system components or the structure beyond allowable values.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine building structure and job conditions before commencement of work. Commencement of work will denote acceptance of building structure and job conditions.
3.2 INSTALLATION
A. Install fall protection equipment in accordance with the manufacturer’s design and installation instructions and conforming to OSHA requirements and this Section.
http://www.superanchor.com/
Building 413 Historic Rehabilitation and Code Compliance Issued For Construction
Solicitation No. 70FA5018R00000013 August 6, 2018
FALL PROTECTION ANCHORS 112433 - 4
1. All field welding shall be done by welders certified by the local jurisdiction having authority.
2. Attach anchors securely to building structural members in accordance with manufacturer’s design to achieve the full design load of the anchor.
3. Install anchorage and mounting devices required for the installation of each product.
B. Completed installation shall be completely watertight.
3.3 FIELD QUALITY CONTROL
A. Employ/assign quality control personnel to monitor the work of this Section for conformance to the requirements of this Section and to good construction practices. Contractor is solely responsible for managing and controlling the quality of the work and conformance with the requirements of this Section.
B. Tests: Engage an independent testing and inspection agency to perform field inspections and tests as required to ensure proper installation of each support unit and prepare test reports validating installation.
1. Coordinate inspection of field connections by independent testing company when connections are accessible and prior to cover.
2. Provide testing agency with access to the work to allow required inspections and testing.
3. Correct deficiencies or remove and replace any work that inspections and test reports indicate do not comply with specified requirements.
4. Testing agency shall confirm current qualifications of each field welder working on this project.
5. Testing agency shall inspect each anchor field weld for conformance with the manufacturer’s design requirement as well as conformance with AWS.
6. Non-conforming work will be reinspected and tested for compliance at Contractor’s expense.
C. Inspections: Verify that all work done under this section has been completed correctly and that all installed products function properly. Adjust items where necessary to ensure satisfactory operation. Field verify that the structure at each anchor connection location conforms to the size and layout shown on the Drawings.
END OF SECTION 112433
GENERAL NOTES
AC
AFF
AFG
AHU
AWG AMERICAN WIRE GAUGE
ABOVE FINISHED FLOOR
ALTERNATING CURRENT
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERESAMP
ACS ACCESS CONTROL SYSTEM
ADA
AHJ
AM AMPLITUDE MODULATION
AP ACCESS POINT
APC ANGLE PHYSICAL CONNECTOR
AV AUDIOVISUAL
A/E ARCHITECT/ENGINEER
AP ACCESS PROVIDER
AMERICAN WITH DISABILITIES ACT
AUTHORITY HAVING JURISDICTION
ACT ACOUSTICAL CEILING TILE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
BUILDINGBLDG
BAS BUILDING AUTOMATION SYSTEM
BCT
BER
BIM
BMS BUILDING MANAGEMENT SYSTEM
BMS
BTS
BC BONDING CONDUCTOR
BONDING CONDUCTOR FOR
TELECOMMUNICATIONS
BD BUILDING DISTRIBUTOR
BIT ERROR RATE
BALANCED MAGNETIC SWITCH
BASE TRANSCEIVER STATION
CAD
CAN
CAT
CATV
COMPUTER AIDED DESIGN
CAMPUS AREA NETWORK
CATEGORY
CBC COUPLED BONDING CONDUCTOR
CD CAMPUS DISTRIBUTOR
CD CONSTRUCTION DOCUMENT
CER COMMON EQUIPMENT ROOM
CMP COMMUNICATIONS PLENUM
CMR COMMUNICATIONS RISER
CONSOLIDATION POINT
CRAC
CTR
CP
CR COMPUTER ROOM
COMPUTER ROOM AIR CONDITIONER
COMMON TELECOMMUNICATIONS ROOM
CDMA CODE DIVISION MULTIPLE ACCESS
BUILDING INFORMATION MODELING
CELL CELLULAR
BICSI BUILDING INDUSTRY CONSULTING SERVICES
INTERNATIONAL
CCTV CLOSED CIRCUIT TELEVISION
COMMUNITY ANTENNA TELEVISION
COMSAT COMMUNICATIONS SATELLITE
CR CARD READER
DRAWINGDWG
EF
FAAP
FACP
FC
FT FOOT OR FEET
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
EMT
DECIBELDB
DBM DECIBEL MILLIWATT
DAS DISTRIBUTED ANTENNA SYSTEM
DC DIRECT CURRENT
DD DESIGN DEVELOPMENT
DD DESIGN DOCUMENT
DS DISTRIBUTION SYSTEM
DVR DIGITAL VIDEO RECORDER
EBC EQUIPMENT BONDING CONDUCTOR
ENTRANCE FACILITY
EMI ELECTROMAGNETIC INTERFERENCE
EMR ECLECTROMAGNETIC RADIATION
ELECTRICAL METALLIC TUBING
EP ENTRANCE PROTECTOR
EPO EMERGENCY POWER OFF
ER EQUIPMENT ROOM
ESS ELECTRONIC SECURITY SYSTEM
FA FIRE ALARM
FIBER CONNECTOR
FCC FEDERAL COMMUNICATIONS COMMISSION
FD FLOOR DISTRIBUTOR
FM FREQUENCY MODULATION
FMC FLEXIBLE METAL CONDUIT
FMT FLEXIBLE METAL TUBING
FO FIBER OPTIC
FOV FIELD OF VIEW
DEMARC DEMARCATION POINT
FSO FREE SPACE OPTICS
DBI DECIBEL ISOTROPIC
DTF DISTANCE TO FAULT
FSL FREE SPACE LOSS
DOOR POSITION SENSORDPS
EOC EMERGENCY OPERATIONS CENTER
HH
HZ HERTZ
HANDHOLE
GB GIGABIT
GHZ GIGAHERTZ
IN INCH OR INCHES
GE GROUNDING EQUALIZER
GEC GROUNDING ELECTRODE CONDUCTOR
GPON
GUI
GIGABIT PASSIVE OPTICAL NETWORK
GRAPHICAL USER INTERFACE
HDA
HDTV
HC HORIZONTAL CROSS-CONNECT
HD HIGH DEFINITIION
HORIZONTAL DISTRIBUTION AREA
HVAC HEATING, VENTILATION, & AIR CONDITIONING
IC INTERMEDIATE CROSS-CONNECT
ID INSIDE DIAMETER
ID INTERMEDIATE DISTRIBUTOR
IDC INSULATION DISPLACEMENT CONNECTOR
IDF INTERMEDIATE DISTRIBUTION FRAME
IDS INTRUSION DETECTION SYSTEM
IG ISOLATED GROUND
ISP
ITE
ITS
IP INTERNET PROTOCOL
IR INFRARED
INSIDE PLANT
IT INFORMATION TECHNOLOGY
INFORMATION TECHNOLOGY EQUIPMENT
INFORMATION TECHNOLOGY SYSTEM
GND GROUND
GPS GLOBAL POSITIONING SYSTEM
HDMI HIGH DEFINITION MULTIMEDIA INTERFACE
HIGH DEFINITION TELEVISION
ID IDENTIFICATION/IDENTIFIER
HD HEAT DETECTOR
JB
KV
KVA KILOVOLT AMPERE
KILOVOLT
JUNCTION BOX
KW KILOWATT
MINIMUMMIN
NATIONAL ELECTRICAL CODENEC
NEMA
NOT TO SCALENTS
NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
MH
MHZ MEGAHERTZ
KB KILOBIT
KHZ KILOHERTZ
KILOMETERKM
M METER
MA MILLIAMP
MB MEGABIT
MV MILLIVOLT
MW MILLIWATT
NM NANOMETER
KVM KEYBOARD, VIDEO, MOUSE
LCD
LED
LMR
LOS
LSZH
LC LATCHING CONNECTOR
LIQUID CRYSTAL DISPLAY
LIGHT EMITTING DIODE
LAND MOBILE RADIO
LINE OF SIGHT
LP LIGHTNING PROTECTOR
LOW SMOKE ZERO HALOGEN
MC MAIN CROSS-CONNECT
MD MAIN DISTRIBUTOR
MDA MAIN DISTRIBUTION AREA
MDP MAIN DISTRIBUTION PANEL
MDU MULTI-DWELLING UNIT
MAINTENANCE HOLE
MM MULTIMODE
MPO MULTI-FIBER PUSH ON
MTR MAIN TELECOMMUNICATIONS ROOM
MUTOA
NIC NETWORK INTERFACE CARD
NIC
MAXIMUMMAX
NID NETWORK INTERFACE DEVICE
NOT IN CONTRACT
MULTI-USER TELECOMMUNICATION
OUTLET ASSEMBLY
NESC NATIONAL ELECTRICAL SAFETY
CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
LIU LIGHT INTERFACE UNIT
NVR NETWORK VIDEO RECORDER
PVC POLYVINYL CHLORIDE
RM ROOM
PTP
RU RACK UNIT
OD OUTSIDE DIAMETER
OM
OS
OFCP OPTICAL FIBER CONDUCTIVE
PLENUM
OFCR OPTICAL FIBER CONDUCTIVE RISER
OFNP OPTICAL FIBER NONCONDUCTIVE
PLENUM
OFNR OPTICAL FIBER NONCONDUCTIVE RISER
OLT OPTICAL LINE TERMINAL
OPTICAL MULTIMODE
ONT OPTICAL NETWORK TERMINAL
OPTICAL SINGLEMODE
OSP OUTSIDE PLANT
OTDR OPTICAL TIME DOMAIN REFLECTOMETER
PA PUBLIC ADDRESS
PB PULL BOX
PBX PRIVATE BRANCH EXCHANGE
PCS PERSONAL COMMUNICATIONS SERVICE
PDU
PET
POE
PON
POTS
PPE
POWER DISTRIBUTION UNIT
PE POLYETHYLENE
PROTECTED ENTRANCE TERMINAL
PM PROJECT MANAGEMENT/MANAGER
POWER OVER ETHERNET
PASSIVE OPTICAL NETWORKING
PLAIN OLD TELEPHONE SERVICE
PERSONAL PROTECTIVE EQUIPMENT
PSI POUNDS PER SQUARE INCH
POINT-TO-POINT
PTZ PAN, TILT, ZOOM
QOS QUALITY OF SERVICE
RF RADIO FREQUENCY
RFI RADIO FREQUENCY INTERFERENCE
RFI
RFID
RFP
RFQ
RGB
REQUEST FOR INFORMATION
RADIO FREQUENCY IDENTIFICATION
REQUEST FOR PROPOSAL
REQUEST FOR QUOTATION
RED, GREEN, BLUE
RJ REGISTERED JACK
RMC
RPP
RIGID METAL CONDUIT
REMOTE POWER PANEL
RAF RAISED ACCESS FLOOR
RCDD REGISTERED COMMUNICATIONS
DISTRIBUTION DESIGNER
PDS PROTECTIVE DISTRIBUTION SYSTEM
RX RECEIVE
RSSI RECEIVED SIGNAL STRENGTH INDICATOR
PID PASSIVE INFRARED DETECTOR
RCP REFLECTED CEILING PLAN
SCTP
SFF
SMA
SOW
SCREENED TWISTED-PAIR
SD SCHEMATIC DESIGN
SMALL FORM FACTOR
SM SINGLEMODE
SUBMINIATURE A
SCOPE/STATEMENT OF WORK
SP SERVICE PROVIDER
ST STRAIGHT TERMINUS
STP SHIELDED TWISTED-PAIR
SC SUBSCRIBER CONNECTOR
SATCOM SATELLITE COMMUNICATIONS
SAN STORAGE AREA NETWORK
SCS STRUCTURED CABLING SYSTEM
SD SMOKE DETECTOR
SMS SECURITY MANAGEMENT SYSTEM
TYP
UON
V
W
VOLTS OR VOLTAGE
UNLESS OTHERWISE NOTED
TYPICAL
UHF
WATT
VA VOLT AMPS
VAC VOLTS ALTERNATING CURRENT
µM MICRON
@ AT
± PLUS OR
MINUS
TBB
TDR
TEBC
TGB
TMGB
TECHNOLOGY DISTRIBUTION ROOM
TE TELECOMMUNICATIONS ENCLOSURE
TO TELECOMMUNICATIONS OUTLET
TP TRANSITION POINT
TR TELECOMMUNICATIONS ROOM
ULTRAHIGH FREQUENCY
UPS UNINTERRUPTIBLE POWER SUPPLY
USB UNIVERSAL SERIAL BUS
UTP UNSHIELDED TWISTED PAIR
VDC VOLTS DIRECT CURRENT
VCSEL VERTICAL CAVITY SURFACE EMITTING LASER
VFL VISUAL FAULT LOCATOR
VHF VERY HIGH FREQUENCY
VLAN VIRTUAL LOCAL AREA NETWORK
VOIP VOICE OVER INTERNET PROTOCOL
WAN
WAP
WLAN WIRELESS LOCAL AREA NETWORK
WMTS
WAO WORK AREA OUTLET
WIDE AREA NETWORK
WIRELESS ACCESS POINT
WI-FI WIRELESS FIDELITY
WIRELESS MEDICAL TELEMETRY SERVICE
W/ WITH
ZDA ZONE DISTRIBUTION AREA
TELECOMMUNICATIONS BONDING BACKBONE
TELECOMMUNICATIONS EQUIPMENT
BONDING CONDUCTOR
TELECOMMUNICATIONS GROUNDING
BUSBAR
TELECOMMUNICATIONS MAIN GROUNDING
BUSBAR
TIA TELECOMMUNICATIONS INDUSTRY
ASSOCIATION
UFC UNIFIED FACILITIES CRITERIA
TX TRANSMIT
UMTS UNIVERSAL MOBILE TELECOMMUNICATIONS
SYSTEM
WCDMA WIDEBAND CODE DIVISION MULTIPLE ACCESS
TS TAMPER SWITCH
VSS VIDEO SURVEILLANCE SYSTEM
WO/ WITHOUT
VWM VERTICAL WIRE MANAGER
HWM HORIZONTAL WIRE MANAGER
SE SOUTH EAST
SW SOUTH WEST
NORTH EASTNE
NW NORTH WEST
TDR TECHNOLOGY DISTRIBUTION ROOM
TELECOMMUNICATIONS SYMBOLS ABBREVIATIONS
WALL PHONE TELECOMMUNICATIONS OUTLET, CONSISTING OF (1) GREEN CATEGORY 6 PLENUM
RATED 4 PAIR UTP CABLE IN 4" SQUARE BY 2-1/8" DEEP BACK BOX, WITH SINGLE GANG REDUCER
RING AND FACEPLATE, EQUIPPED WITH MOUNTING LUGS. PROVIDE 1" EMT AND EXTEND UP TO
ACCESSIBLE CEILING SPACE. MOUNT BACK BOX AT 48" AFF. TERMINATE CABLE ON GREEN RJ-45
CATEGORY 6 JACK IN FACEPLATE AND ON RACK MOUNTED CATEGORY 6 PATCH PANEL IN
RESPECTIVE TELECOM ROOM.
COMMUNICATIONS OUTLET CONSISTING OF (4) GREEN CATEGORY 6 PLENUM RATED 4 PAIR UTP CABLES IN A 4" SQUARE 2-1/8" DEEP BACKBOX WITH A SINGLE GANG REDUCING RING AND 4 PORT FACEPLATE.
PROVIDE 1" EMT UP TO ACCESSIBLE CEILING SPACE . TERMINATE CABLES ON GREEN RJ-45 CATEGORY 6 JACKS IN FACEPLATE AND ON RACK MOUNTED CATEGORY 6 PATCH PANEL IN RESPECTIVE TELECOM
ROOM.
SECURE TELECOMMUNICATIONS OUTLET CONSISTING OF (2) GREEN CATEGORY 6 PLENUM RATED 4 PAIR UTP CABLES, (1) ORANGE OM-3 4 STRAND FIBER OPTIC CABLE, AND (1) YELLOW OM-3 4 STRAND FIBER OPTIC CABLE IN 4" SQUARE BY 2-1/8" DEEP BACK BOX, WITH SINGLE GANG REDUCER RING AND FACEPLATE. PROVIDE 1" EMT AND EXTEND UP TO ACCESSIBLE CEILING SPACE. MOUNT BACK BOX AT 18" AFF.TERMINATE GREEN CATEGORY UTP 6 CABLE WITH GREEN CATEGORY 6 RJ-45 JACK IN FACEPLATE AT WAO. TERMINATE OTHER END OF CATEGORY 6 UTP ON RACK MOUNTED CATEGORY 6 PATCH PANEL IN RESPECTIVE IT RACK.
TERMINATE ORANGE FIBER CABLE WITH ORANGE LC CONNECTORS IN FACEPLATE AT WAO. TERMINATE YELLOW FIBER CABLE WITH YELLOW LC CONNECTORS IN FACEPLATE AT WAO. TERMINATE OTHER END OF FIBER CABLES IN DEDICATED RACK MOUNTED FIBER SHELVES IN SECURE RACK LOCATED IN RESPECTIVE
COMMS ROOM.
TELECOMMUNICATIONS GROUNDING BUS BAR
CATV OUTLET MOUNTED IN WALL CONSISTING OF (1) WHITE RG-6 QUAD SHIELD PLENUM RATED COAXIAL CABLE IN 4" SQUARE BY 2-1/8" DEEP BACK BOX WITH SINGLE GANG REDUCER RING AND 3-PORT FACEPLATE AT WAO WITH 1" EMT EXTENDED UP TO CEILING SPACE. MOUNT BACK BOX AT 65" AFF. TERMINATE COAX CABLE WITH F-CONNECTORS ON BOTH ENDS. CONNECT RG-6 CABLE TO FEMALE BARREL ADAPTOR IN FACE PLATE AND ON CATV TAP LOCATED AT CLOSEST CONNECTION POINT TO BACKBONE CABLE.
GROUNDING
1. THE TELECOMMUNICATIONS CONTRACTOR SHALL BE RESPONSIBLE FOR
THE INSTALLATION, TERMINATION AND TESTING OF ALL HORIZONTAL
CATEGORY 6,FIBER AND COAXIAL CABLING AND TERMINATION HARDWARE,
INTERNAL, COPPER, COAXIAL AND FIBER OPTIC BACKBONE CABLING AND
TERMINATION HARDWARE, AND EQUIPMENT RACKS AND ASSOCIATED
CABLE MANAGEMENT DEVICES. THE TELECOMMUNICATIONS WORK SHALL
BE MANAGED BY A BICSI REGISTER COMMUNICATIONS DISTRIBUTION
DESIGNER (RCDD) AND PERFORMED UNDER THE DIRECT SUPERVISION OF A
BICSI CERTIFIED TECHNICIAN.
2. INSTALLATION OF ALL TELECOMMUNICATIONS WORK SHALL CONFORM TO
THE LATEST EDITION OF THE TIA COMMUNICATIONS CABLING STANDARDS,
NATIONAL ELECTRICAL CODE (NFPA 70), AND ALL APPLICABLE LOCAL
CODES.
3. DRAWINGS ARE DIAGRAMMATIC. ACTUAL LOCATION OF EQUIPMENT TO BE
DETERMINED IN THE FIELD. NEW EQUIPMENT SHALL FIT INTO AVAILABLE
SPACE. CONFLICTS WITH EQUIPMENT PLACEMENT SHALL BE SUBMITTED IN
THE FORM OF AN RFI FOR RESOLUTION.
4. PROVIDE UL LISTED FIRE RATED SLEEVING SYSTEMS AT EACH THROUGH
FLOOR AND FIRE RATED WALL PENETRATION PER NATIONAL ELECTRICAL
CODE (NEC) AND NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
REQUIREMENTS AND PER STATE AND LOCAL CODES. REFER TO
SPECIFICATIONS FOR FIRE STOPPING MATERIAL SPECS.
5. ANY CONDUIT ROUTING SHOWN ON PLANS IS SCHEMATIC AND IS NOT
INTENDED TO REPRESENT INSTALLED PATHS OR DISTANCES. ACTUAL
ROUTING OF CONDUITS AND JUNCTION / PULL BOX LOCATIONS SHALL BE
FIELD VERIFIED AND COORDINATED WITH ALL OTHER DISCIPLINES BY THE
CONTRACTOR. CONTRACTORS SHALL KEEP ALL COMMUNICATIONS
CONDUIT INSTALLATION AWAY FROM ALL MECHANICAL AND ELECTRICAL
SERVICES.
6. PROVIDE ELECTRICAL METALLIC TUBING (EMT) FOR ALL INDOOR
COMMUNICATIONS CONDUIT UON. MINIMUM CONDUIT SIZE TO BACK BOXES
FOR COMMUNICATIONS OUTLETS SHALL BE 1" UON.
7. PROVIDE BUSHINGS ON THE ENDS OF ALL COMMUNICATIONS CONDUITS
AND IN EACH ENCLOSURE/JUNCTION BOX. PROVIDE PULL STRINGS IN ALL
CONDUITS AND ATTACH EACH PULL STRING END TO A NON-MOVABLE
ANCHOR.
8. THE CONTRACTOR SHALL TEST AND CERTIFY EVERY INSTALLED
TELECOMMUNICATIONS CABLE IN ACCORDANCE WITH CURRENT TIA
STANDARDS AND THE MANUFACTURER'S REQUIREMENTS. PROVIDE SOFT
COPY OF THE TEST RESULTS TO THE OWNER FOR ALL COMMUNICATIONS
CABLES (HORIZONTAL AND BACKBONE).
9. PROVIDE TWO FACTORY ASSEMBLED PATCH CORDS FOR EVERY (4) FOUR
COMMUNICATIONS OUTLETS (ALL CONFIGURATIONS) INSTALLED.
COORDINATE COLOR AND LENGTH OF PATCH CORDS WITH OWNER. OWNER
WILL ACTIVATE NEW COMMUNICATIONS CABLING. PATCH CORDS SHALL BE
FROM SAME MANUFACTURER AS BACKBONE OR HORIZONTAL CABLING
THEY ARE USED TO CONNECT.
10. LABEL ALL COMMUNICATIONS CABLING AND HARDWARE PER CURRENT TIA
STANDARDS.
11. PENETRATIONS OF PERIMETER WALL OF THE SECURE AREAS BY
COMMUNICATION INFRASTRUCTURE MUST BE KEPT TO A MINIMUM.
12. METALLIC PENETRATIONS IN THE SECURE BOUNDARY REQUIRE
COUNTERMEASURES. USE APPROVED DIELECTRIC BREAKS AND OR
GROUNDING AS REQUIRED.
13. COMMUNICATIONS INFRASTRUCTURE SERVICING AREAS OTHER THAN THE
SECURE AREA CANNOT TRANSIT THE SECURE AREA UNLESS MITIGATED
WITH GOVERNMENT AHJ APPROVAL.
14. COMMUNICATIONS INFRASTRUCTURE AND CABLING MUST ENTER THE
SECURE AREA AT A SINGLE POINT.
15. ALL COMMUNICATIONS CABLING AND DEVICES LOCATE ON THE INTERIOR
OF A PERIMETER WALL TREATED FOR ACOUSTICS OR RF SHIELDING SHALL
BE SURFACE MOUNTED, CONTAINED IN A RACEWAY, OR AN ADDITIONAL
WALL SHALL BE CONSTRUCTED USING FURRING STRIPS AS A STAND-OFF
FROM THE EXISTING WALL ASSEMBLY.
TV
S
W
BUILDING COMMUNICATIONS OUTLET CONSISTING OF (1) GREEN CATEGORY 6 PLENUM RATED 4 PAIR UTP CABLE TERMINATED AT THE ELEVATOR CONTROL DEVICE PANEL. PROVIDE 1" EMT UP TO ACCESSIBLE CEILING SPACE. TERMINATE CABLE ON GREEN RJ-45 CATEGORY 6 JACK IN SURFACE MOUNTED BISCUIT TYPE BOX. COORDINATE SPECIFIC MOUNTING REQUIREMENTS WITH ELEVATOR CONTRACTOR. TERMINATE OTHER END OF CABLE ON RACK MOUNTED CATEGORY 6 PATCH PANEL IN RESPECTIVE TELECOM ROOM.
B
1"DX18"W LADDER TRAY IN TELECOMMUNICATIONS ROOMS.
4" EMT TELECOMMUNICATIONS CONDUIT WITH HILTI FS-1
MECHANICAL FIRESTOP ASSEMBLY UNITS AT BOTH ENDS.
3/4" FIRE RATED PLYWOOD PAINTED WITH BENJAMIN MOORE
M59-220 INTUMESCENT PAINT. TYPICAL
F FLOOR MOUNTED COMMUNICATIONS OUTLET IN FLOOR BOX. PROVIDE (4) GREEN CATEGORY 6 PLENUM RATED 4 PAIR UTP CABLES AND TERMINATE UTP CABLES ON GREEN RJ-45 CATEGORY 6 JACKS IN FACEPLATE AND ON RACK MOUNTED CATEGORY 6 PATCH PANEL IN RESPECTIVE TELECOM ROOM. PROVIDE (1) ADDITIONAL GRAY CATEGORY 6
RJ-45 JACK IN FACEPLATE FOR PC EXTENDER CONNECTION TO TV.
CATV OUTLET MOUNTED IN WALL CONSISTING OF (1) WHITE RG-6 QUAD SHIELD PLENUM RATED COAXIAL CABLE AND (1) GRAY CATEGORY 6 UTP 4 PAIR UTP CABLE FOR PC EXTENDER IN 4" SQUARE BY 2-1/8" DEEP BACK BOX WITH SINGLE GANG REDUCER RING AND 6-PORT FACEPLATE AT WAO. PROVIDE 1" EMT EXTENDED UP TO CEILING SPACE AND 1" EMT DOWN TO FLOOR BOX OR ACCESSIBLE SPACE BELOW FLOOR. MOUNT BACK BOX AT 65" AFF. TERMINATE COAX CABLE WITH F-CONNECTORS ON BOTH ENDS.
CONNECT RG-6 CABLE TO FEMALE BARREL ADAPTOR IN FACE PLATE AND ON CATV TAP LOCATED AT CLOSEST CONNECTION POINT TO BACKBONE CABLE. TERMINATE GRAY UTP CABLE ON CATEGORY 6 RJ-45 IN FACEPLATE AND EXTEND TO AND TERMINATE OTHER END AT DESIGNATED COMMUNICATIONS OUTLET
LOCATED IN SAME ROOM.
TD
COMMUNICATIONS OUTLET CONSISTING OF (4) GREEN CATEGORY 6 PLENUM RATED 4 PAIR UTP CABLES IN A 4" SQUARE 2-1/8" DEEP BACKBOX WITH A SINGLE GANG REDUCING RING AND SINGLE GANG FACEPLATE. PROVIDE 1" EMT UP TO ACCESSIBLE CEILING SPACE . TERMINATE CABLES ON GREEN RJ-45 CATEGORY 6 JACKS IN FACEPLATE AND ON RACK MOUNTED CATEGORY 6 PATCH PANEL IN RESPECTIVE TELECOM ROOM. PROVIDE (1) ADDITIONAL GRAY CATEGORY 6 RJ-45 JACK IN FACEPLATE FOR PC
EXTENDER CONNECTION TO TV.
D
4 11/16" SQUARE 3-1/4" DEEP BACKBOX WITH BLANK COVER PLATE. COORDINATE SPECIFIC MOUNTING HEIGHT WITH MWITS AV. PROVIDE 1-1/2" EMT UP TO ACCESSIBLE CEILING SPACE OR SURFACE
MOUNTED RACEWAY.
C
SURFACE MOUNTED COMMUNICATIONS PEDESTAL OUTLET. PROVIDE (2) GREEN CATEGORY 6 PLENUM RATED 4 PAIR UTP CABLES, (1) ORANGE OM-3 4 STRAND FIBER OPTIC CABLE, AND (1) YELLOW OM-3 4 STRAND FIBER OPTIC CABLE. TERMINATE CATEGORY 6 CABLES ON GREEN RJ-45 JACK IN DEVICE FACEPLATE AND ON RACK MOUNTED CATEGORY 6 PATCH PANEL IN RESPECTIVE TELECOM ROOM. TERMINATE ORANGE FIBER CABLE WITH ORANGE LC CONNECTORS IN FACEPLATE. TERMINATE YELLOW FIBER CABLE WITH YELLOW LC CONNECTORS IN FACEPLATE.
TERMINATE OTHER END OF FIBER CABLES IN DEDICATED RACK MOUNTED FIBER SHELVES IN SECURE RACK LOCATED IN RESPECTIVE COMMS ROOM. PROVIDE (1) ADDITIONAL GRAY CATEGORY 6 RJ-45 JACK IN FACEPLATE
FOR PC EXTENDER CONNECTION TO TV.
S
4" PVC CONDUIT PENETRATION INTO REAR OF NEMA RATED
JUNCTION.
CEILING MOUNTED COMMUNICATIONS OUTLET FOR WAP. PROVID (1) GREEN CATEGORY 6 PLENUM RATED 4 PAIR UTP CABLE IN A 2 1/8" DEEP BACK BOX MOUNTED FLUSH IN CEILING . PROVIDE 1" EMT CONDUIT TO PATHWAY LEADING BACK TO TELECOMMUNICATIONS ROOM B003. TERMINATE 4 PAIR CABLE WITH CATEGORY 6, RJ45 PLUG IN CEILING, AND ON RACK MOUNTED CATEGORY 6 PATCH PANEL
IN TELECOM ROOM 205.
M CEILING MOUNTED MICROPHONE FOR VDV INTEGRATED COMMUNICATIONS. PROVIDE A 4 11/16" SQUARE, 2 1/8" DEEP BACK BOX WITH A SINGLE GANG REDUCING MUD RING, MOUNTED FLUSH IN CEILING . PROVIDE 1" EMT CONDUIT WITHIN CEILING FURRED OUT SPACE BELOW TS PARTITION TO CONFERENCE ROOM TR
WITHIN THE SAME SPACE.
VDV VOICE DATA VIDEO
S CEILING MOUNTED SPEAKER FOR VDV INTEGRATED COMMUNICATIONS. PROVIDE A 4 11/16" SQUARE, 2 1/8" DEEP BACK BOX WITH A SINGLE GANG REDUCING MUD RING, MOUNTED FLUSH IN CEILING . PROVIDE 1" EMT CONDUIT WITHIN CEILING FURRED OUT SPACE BELOW TS PARTITION TO CONFERENCE ROOM TR
WITHIN THE SAME SPACE.
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
DRAWING NO.
SCALE:
DATE:
DES: DRAWN: CHECK:
SHEET OF 160
SIGNATURE
GRAPHIC SCALES
KEY PLAN
NOT TO SCALE
1 3 4 5 62
A
B
C
D
E
1 3 4 5 62
SOLICITATION NO: 70FA5018R00000013
UNCLASSIFIED // FOR OFFICIAL USE ONLY
UNCLASSIFIED // FOR OFFICIAL USE ONLY8/
6/
:1
7:
P M
T1-001
DA KF RL
05/23/2018
MT. WEATHER
EMERGENCY
OPERATIONS CENTER
(MWEOC)
BUILDING 413
HISTORIC
REHABILITATION AND
CODE COMPLIANCE
LEGEND, ABBREVIATIONS AND
GENERAL NOTES
19844 BLUERIDGE
MOUNTAIN ROAD,
MT WEATHER, VA 20135
REVISIONS
1 ADDENDUM 2 07/27/2018
2 ADDENDUM 3 08/07/2018
UP
UPDN
C
B
A
C
A
873 4 65
B
OFFICE
JC
CORRIDOR
1C-3
OFFICE
OFFICE
ELEC
CORRIDOR
1C-3
TS CONFERENCE
ROOM
CORRIDOR
1C-2
OFFICE
OFFICE
OFFICE
109CORRIDOR
110A
STAIR
S1
VESTIBULE
ELEVATOR
EL-1
STAIR
S2
M
M
S
S S
S
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
DRAWING NO.
SCALE:
DATE:
DES: DRAWN: CHECK:
SHEET OF 160
SIGNATURE
GRAPHIC SCALES
KEY PLAN
1 3 4 5 62
A
B
C
D
E
1 3 4 5 62
SOLICITATION NO: 70FA5018R00000013
UNCLASSIFIED // FOR OFFICIAL USE ONLY
UNCLASSIFIED // FOR OFFICIAL USE ONLY
1/4" = 1'-0"
8/ 6/
:1
7:
P M
T1-201
DA KF RL
05/23/2018
MT. WEATHER
EMERGENCY
OPERATIONS CENTER
(MWEOC)
BUILDING 413
HISTORIC
REHABILITATION AND
CODE COMPLIANCE
TELECOMMUNICATIONS REFLECTED
CEILING PLAN - FIRST FLOOR
19844 BLUERIDGE
MOUNTAIN ROAD,
MT WEATHER, VA 20135
GENERAL SHEET NOTES
1. FOR LEGEND, AND ABBREVIATIONS SEE SHEET T1-001
SHEET KEYNOTES
4" CONDUIT BETWEEN BASEMENT COMMS ROOM 205.1
4" CONDUIT BETWEEN 1ST FLOOR AND COMMS ROOM 205.2
4" PVC CONDUIT PENETRATION INTO SECURE AREA
MOUNTED TO REAR OF JUNCTION BOX.
NEMA 1 JUNCTION BOX 1' X 1' X 8" WITH LID.3
0 8'4'2'
1/4" = 1'-0"SCALE:
REVISIONS
1 ADDENDUM 2 07/27/2018
2 ADDENDUM 3 08/07/2018
5 CEILING MOUNTED COMMUNICATIONS OUTLET FOR WAP.
6 CEILING MOUNTED BACKBOX FOR VDV INTEGRATION.2
UP
DN
UP
DN
8x8
6x8
6x6
6x6
ACU-2
C
2 4 5 71 8
B
A
E
F
3 6
SG-1
SG-1
SG-1
SG-1
SG-1
SG-1
8x8
6ø
4ø
4ø
4ø
6x8
10x10
12x10
6x6
FCU-215B
FCU-215AFCU-214BFCU-214A
FCU-213
FCU-211
FCU-210
FCU-209
FCU-201
FCU-208
FCU-207
FCU-206
FCU-204
3/4" HWS/R
3/4" CHWS/R
1" HWS/R
1" CHWS/R
1" CHWS/R
1" HWS/R
1-1/2" CHWS/R 1" HWS/R
1" CHWS/R
3/4" HWS/R
3/4" HWS/R
1" CHWS/R
1" HWS/R
1-1/4" CHWS/R3/4" HWS/R
3/4" CHWS/R 1" CHWS/R
3/4" HWS/R
3/4" CHWS/R
3/4" HWS/R
COMM
CORRIDOR
2C-2
CORR
OFFICE
OPEN OFFICE
WC
WC
FRONT HALL
OFFICE
CONFERENCE ROOM
ELEVATOR
EL-1
TS HOT
TS OFFICE
OFFICE
PANTRY
OFFICE
STORAGE
214A
ELEC
CORRIDOR
2C-3
OPEN OFFICE
F/S
SG-2
SG-2
SG-2
SG-2
SG-2
3/4" CHWS/R AND
3/4" HWS/HWR
RUNNING BELOW IN
ENCLOSURE TO
FCU-210
3/4" CHWS/R AND
3/4" HWS/HWR
RUNNING BELOW IN
ENCLOSURE TO
FCU-211
SD-1
EG-1
EG-1
T FCU-208
T FCU-207
T FCU-206
T
FCU-215A/FCU-215B
T
FCU-214A/FCU-214B
T FCU-213
T
FCU-209
T
FCU-210
T
FCU-211
T
FCU-204
T
FCU-201
T ACU-2
6x6
6x6
FD
EG-1
EG-1
EG-1
EG-1
8x8 10 x1
8x
6x6 6x6 6x
RS/RL RACKED
ON WALL
TG-1
TG-1
TG-1
TG-1
EG-2
SG-1
2" CHWS/R
1-1/4" HWS/R
AD
AD
SG-2
DN UP DN DN DNUP UP
UP DN UP DN RS/RL DN
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
DRAWING NO.
SCALE:
DATE:
DES: DRAWN: CHECK:
SHEET OF 160
SIGNATURE
GRAPHIC SCALES
KEY PLAN
1 3 4 5 62
A
B
C
D
E
1 3 4 5 62
SOLICITATION NO: 70FA5018R00000013
UNCLASSIFIED // FOR OFFICIAL USE ONLY
UNCLASSIFIED // FOR OFFICIAL USE ONLY
1/4" = 1'-0"
8/ 7/
:2
2:
A M
M1-103
TJM KJS CAH
05/23/2018
MT. WEATHER
EMERGENCY
OPERATIONS CENTER
(MWEOC)
BUILDING 413
HISTORIC
REHABILITATION AND
CODE COMPLIANCE
SECOND FLOOR PLAN
19844 BLUERIDGE
MOUNTAIN ROAD,
MT WEATHER, VA 20135
0 8'4'2'
1/4" = 1'-0"SCALE:
GENERAL SHEET NOTES
1. REFER TO SHEET M1-001 FOR LEGEND, ABBREVIATIONS,
AND NOTES.
2. ALL SUPPLY DUCTWORK PENETRATING THE CHASE
REQUIRES A COMBINATION FIRE/SMOKE DAMPER.
3. ALL RETURN AIR DUCTWORK PENETRATING THE CHASE
REQUIRES A FIRE DAMPER.
4. ALL PIPING TO BE HELD TIGHT TO STRUCTURE, DO NOT
HANG BELONG WINDOW HEADS.
SHEET KEYNOTES
2" CHWS/R AND 1-1/4" HWS/R UP,
2-1/2" CHWS/R AND 2" HWS/R DN.
3/4" CHWS/R AND 3/4" HWS/R UP TO FCU-301.
3/4" CHWS/R AND 3/4" HWS/R UP TO FCU-305.
3/4" CHWS/R AND 3/4" HWS/R UP TO FCU-306.
3/4" CHWS/R AND 3/4" HWS/R UP TO FCU-307.
3/4" CHWS/R AND 3/4" HWS/R UP TO FCU-311A.
3/4" CHWS/R AND 3/4" HWS/R UP TO FCU-311B.
3/4" CHWS/R AND 3/4" HWS/R UP TO FCU-312.
3/4" CHWS/R AND 3/4" HWS/R UP TO FCU-313.
REFER TO DETAIL 5/M1-602 FOR PIPING SCIF PENETRATION
REQUIREMENTS.
RUN PIPING DOWN BELOW FAN COIL UNITS.
SIZE AND ROUTE REFRIGERANT PIPING IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS.
FLEX JOINT.
REFER TO DETAIL 12/M1-602 FOR DUCTWORK SCIF
PENETRATION REQUIREMENTS.
CHWS/R AND HWS/R WITHIN ENCLOSURE, FCU FED FROM
BELOW. REFER TO M1-102 FOR CONTINUATION.
8 9
13 13
11 11 11 11
REVISIONS
1 ADDENDUM 3 08/07/2018
EDGE OF SLAB, SEE
TYPICAL COMPOSITE
STEEL DECK AT SLAB EDGE
1/2" THICK BENT PLATE OR
ANGLE, VERTICAL LEG 5"
MINIMUM (TYPICAL)
1/2" THICK PLATE
L3x3x5/16 DECK
SUPPORT, SEE NOTE
4 OR SEE ALTERNATE
SP
AN
5/16
1/4
5/16
(TYP)
2" MAX
DETAIL AT CORNER COLUMN
DETAIL AT EDGE COLUMN
EDGE OF SLAB, SEE TYPICAL COMPOSITE
STEEL DECK AT SLAB EDGE
L3x3x5/16 DECK
SUPPORT, SEE NOTE
4 OR SEE ALTERNATE
5/16 5
1/4
SP
AN
1/2" THICK BENT PLATE
OR ANGLE, VERTICAL LEG
5" MINIMUM (TYPICAL)
DETAIL AT EDGE COLUMN
EDGE OF SLAB, SEE TYPICAL
COMPOSITE STEEL DECK AT SLAB EDGE
L3x3x5/16 DECK
SUPPORT, SEE NOTE
4 OR SEE ALTERNATE
1/4
TYPICAL
1/4
SP
AN
1/2" THICK BENT PLATE
OR ANGLE, VERTICAL LEG
5" MINIMUM (TYPICAL)
5/16 6 5/16 6
DETAIL AT INTERIOR COLUMNS
L3x3x5/16 DECK
SUPPORT, SEE NOTE
4 OR SEE ALTERNATE
1/4
EACH END
(TYPICAL)
SP
AN
ALTERNATE DECK SUPPORT
L3x3x5/16 DIAGONAL ANGLES LEG
DOWN AS ALTERNATE TO DECK
SUPPORT COORDINATE WITH OTHER
TRADE CONTRACTORS SEE NOTE 4.
TYPICAL DECK SUPPORT AT COLUMN
NOTES:
1. SEE ADDITIONAL DETAILS AT EXTERIOR WALL SUPPORTS.
2. ATTACH DECK (ENDS AND SIDE LAPS) TO SUPPORT ANGLES OR PLATES TYPICAL.
3. SEE TYPICAL SLAB REINFORCEMENT AT COLUMN DETAILS.
4. CONTRACTOR SHALL COORDINATE AND PROVIDE ANGLES AS REQUIRED FOR SUPPORT OF DECK NOTED AROUND COLUMN TYPICAL AT ALL FLOORS AT COLUMNS SIZED SHOWN ARE MINIMUM CONTRACTOR TO VERIFY FOR ACTUAL CONDITIONS.
NO SCALE
TYPICAL SLAB REINFORCEMENT
AT INTERIOR COLUMN
NOTE:
1. SEE TYPICAL DECK SUPPORT AT COLUMN DETAIL.
NO SCALE
(TY
PICAL)
2" (
CLE
AR)
1 - #4x4'-0" TOP BAR, TYPICAL AT EACH COLUMN
C COLUMNL
C COLUMNL
TYPICAL SLAB REINFORCEMENT AT EXTERIOR
COLUMN FURTHER THAN 2" FROM EDGE
NOTE:
1. SEE TYPICAL DECK SUPPORT AT COLUMN DETAIL.
NO SCALE
1 - #4x4'-0" TOP
BAR (TYPICAL)
C COLUMNL
C COLUMNL
(TY
PICAL)
2" (
CLE
AR)
2" M
IN
IM
UM
2' - 0"
4' - 0"
EQ
EQ
(TYPICAL)
2" (MAX)
1 - #4 TOP BAR
(TYPICAL)
SEE TYPICAL COMPOSITE
STEEL DECK AT SLAB EDGE
TYPICAL SLAB REINFORCEMENT AT
EXTERIOR COLUMN UNDER 2" FROM EDGE
NOTE:
1. SEE TYPICAL DECK SUPPORT AT COLUMN DETAIL.
NO SCALE
C COLUMNL
C COLUMNL
(TY
PICAL)
2" (
CLE
AR)
2" M
AX
IM
UM
1 - #4 TOP BAR
(TYPICAL)
2' - 0"
4' - 0"
SEE TYPICAL COMPOSITE
STEEL DECK AT SLAB EDGE
1" 4'
- 0
ROUND OFF CONCRETE
AT TOP OF BOLLARD.
6" STANDARD PIPE. HOT-DIP
GALVANIZED. FILL WITH CONCRETE.
EXTERIOR PAVING.
SEE CIVIL DRAWINGS.
6"
TYP
6" CONCRETE
3'- 0"
SAFETY YELLOW BOLLARD COVER
TYPICAL EXTERIOR BOLLARD
NO SCALE
TYPICAL EXTERIOR LIGHT/CAMERA
POLE MOUNT DETAIL
NO SCALE
HANDHOLE AND COVER
ANCHOR BASE AND COVER ACCORDING
TO MANUFACTURER'S REQUIREMENTS
FINISHED
GRADE
GROUND
CONNECTION
6#6 VERTICAL
(EQUALLY SPACED)
ANCHOR BOLTS PER
MANUFACTURER'S
RECOMMENDATIONS
(4 REQUIRED)
#4@10 TIES
2#4 WITHIN TOP 5" OF
PIER
2'-0" AUGURED HOLE
3"
2'- 0"
6'- 6"
CMU WALL
NO SCALE
TYPICAL STEEL LINTEL
PACK SOLID
WITH MASONRY
BRICK
MASONRY
WALL
NOTES:
1. PROVIDE 3 GALVANIZED STEEL L5x3 1/2x5/16 LINTELS IN MASONRY
OPENINGS UP TO 5'-0" CLEAR.
2. PROVIDE A MINIMUM OF 8" BEARING FOR LINTELS AT EACH END.
NO SCALE
TYPICAL SISTERED JOIST
EXISTING
WOOD JOIST
3x12 WOOD JOIST
20D NAILS AT 2’-0”, TOP AND
BOTTOM, STAGGERED ON
OPPOSITE SIDES
3x12 WOOD
JOIST
EXISTING
WOOD JOIST
SECTIONPLAN
(T
YP
IC
AL
1'
- 0
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
DRAWING NO.
SCALE:
DATE:
DES: DRAWN: CHECK:
SHEET OF 160
SIGNATURE
GRAPHIC SCALES
KEY PLAN
NOT TO SCALE
1 3 4 5 62
A
B
C
D
E
1 3 4 5 62
SOLICITATION NO: 70FA5018R00000013
UNCLASSIFIED // FOR OFFICIAL USE ONLY
UNCLASSIFIED // FOR OFFICIAL USE ONLY08
/0
8/
6:
:1
S1-005
RJN MKS WC
05/23/2018
MT. WEATHER
EMERGENCY
OPERATIONS CENTER
(MWEOC)
BUILDING 413
HISTORIC
REHABILITATION AND
CODE COMPLIANCE
STRUCTURAL TYPICAL DETAILS
19844 BLUERIDGE
MOUNTAIN ROAD,
MT WEATHER, VA 20135
REVISIONS
1 ADDENDUM
C
A
873 4 65
B
HSS6X6X1/2
HS
S1 0X
6X 1/2
W
X3
HSS6X6X1/2 W14X193 HSS6X6X1/2
HS
S1
0X 6X
1/2
HSS6X6X1/2
W
X3
W
X3
W
X3
W
X3
W
X3
W14X193
C12X20.7
C12X20.7C12X20.7C12X20.7C12X20.7
C12X20.7 C12X20.7 C12X20.7
HSS6X6X1/2 HSS6X6X1/2
W16X31
10' - 6" 7' - 3" 12' - 6" 25' - 0" 12' - 6" 7' - 3" 10' - 6"
1'
- 8
1/ 2"
6" 7'
- 6
4'
- 4
3/ 4"
3"
W12X40 W12X40
W12X40W12X40
C12X20.7
EXISTING BRICK
MASONRY CHIMNEY
EXISTING STONE MASONRY
WALL (TYPICAL)
SPAN
W
X3
12' - 6" 12' - 6"
3" EXPANSION JOINT
OP
EN
EDGE OF
DECK
C12X20.7
W
X3
BRACE
BR
AC
E
BR
AC
E
BRACE
5'
- 9
1'
- 9
C12X20.7C12X20.7
5'
- 9
1'
- 9
G S1-504
H S1-504
J S1-504
(T
YP
O F
7)
W16 (EXIST)
W16 (EXIST)
W16 (EXIST)
W16 (EXIST) W16 (EXIST)
4" 5'
- 4
S1-502
W16 (EXIST)
D S1-503
J S1-503
B S1-503
H S1-503
H S1-504
H S1-504
H S1-504
3x12@16"
3x12@16"
4 1 /2"
3 1/2"
8 1/2" 8 1/2"
3 1/2"
4 1 /2"
EXIST 3x12@16"± (TYPICAL)
C S1-505
W14X30 (TYPICAL)
W
X3
W14X30 W14X30
W
X3
W
X3
W
X3
C S1-5054" ±
1' - 5"
4" ±
1' - 5"
P S1-503
V10 V1
V1
V10
V5
V1
V1
V10
V1
V5 M1
V5 M1
V5 V5
V5 V5
V5 V5 V5 V5 V5 V5
V2
M3
V1
M3
V3
M4
V3
M4
V10
V1
V1
V10
V5
V1
V1
V10
V1
V5
V2
M3
V2
M3
V3
M4
V3
M4
V3
M4
V3
M4
V2
M2
V2
M2
V2
M2
V2
M2
V2
M2
V2
M2
V5 V5 V5V5 V5V5 V5 V5 V5
V10
V5V5V1
V10
V5 V5
V1
V2
M2
V2
M2
V2
M2
V2
M2
V5
S1-103
OPP HAND
S1-103
1S1-503
V5V5 V5
V5 M1
V5 M1
V5 M1
V5 M1
V5 V5
V5
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
DRAWING NO.
SCALE:
DATE:
DES: DRAWN: CHECK:
SHEET OF 160
SIGNATURE
GRAPHIC SCALES
KEY PLAN
1 3 4 5 62
A
B
C
D
E
1 3 4 5 62
SOLICITATION NO: 70FA5018R00000013
UNCLASSIFIED // FOR OFFICIAL USE ONLY
UNCLASSIFIED // FOR OFFICIAL USE ONLY
1/4" = 1'-0"
/0
8/
6:
:1
S1-104
RJN CJS JFG
05/23/2018
MT. WEATHER
EMERGENCY
OPERATIONS CENTER
(MWEOC)
BUILDING 413
HISTORIC
REHABILITATION AND
CODE COMPLIANCE
STRUCTURAL THIRD FLOOR PLAN
19844 BLUERIDGE
MOUNTAIN ROAD,
MT WEATHER, VA 20135
SCALE: 1/4" = 1'-0"S1-104
1 THIRD FLOOR PLAN
GENERAL SHEET NOTES
1. SEE S1-001 FOR GENERAL NOTES.
2. SEE S1-002 THROUGH S1-005 FOR TYPICAL DETAILS.
3. ADDITION FLOOR CONSTRUCTION TO BE OF A COMPOSITE TYPE,
CONSISTING OF 3”X18 GAUGE METAL FLOOR DECK, WITH 2"
NORMAL WEIGHT CONCRETE COVER (5" TOTAL FLOOR
THICKNESS), REINFORCED WITH 6"X6"-W1.4xW1.4 WELDED WIRE
FABRIC. ATTACH STEEL DECK WITH 36/4 PATTERN WITH 5/8"
PUDDLE WELDS. STEEL DECK SIDE LAP CONNECTION SHALL BE
5/8” PUDDLE WELDS AT 12" SPACING.
4. ADDITION THIRD FLOOR TOP OF STEEL ELEVATION = 22.59’
UNLESS OTHERWISE NOTED.
5. PROVIDE 3/4" DIAMETER X 4 1/2" LONG HEADED STUDS AT 12"
SPACING ALONG THE BEAM LENGTH FOR ALL COMPOSITE
FLOOR FRAMING.
6. REFER TO FRAMING ELEVATIONS ON STRUCTURAL 200 SERIES
FOR FRAMING ELEVATIONS AND DIAGONAL BRACING ALONG
COLUMN GRID LINES.
7. VERIFY EXISTING DIMENSIONS AND SIZES PRIOR TO WORK.
8. NEW WOOD JOISTS ARE SHOWN IN A GENERAL ARRANGEMENT.
JOISTS MUST BE LOCATED SO THAT THERE ARE NO
UNSUPPORTED EDGES OF FLOORING AND AROUND ALL PIPING
RUNNING BETWEEN FLOORS.
LEGEND
INDICATES THE DIRECTION OF METAL DECK SPAN.SPAN
INDICATES MOMENT CONNECTION
0 8'4'2'
1/4" = 1'-0"SCALE:
SHEET KEYNOTES
PROVIDE FULL LENGTH SISTERED JOIST PER TYPICAL DETAIL
UNDERNEATH RELOCATED STAIR CORNER POST.
TOOTH IN CMU BLOCK FROM ELEVATOR SHAFT TO MASONRY
CHIMNEY EVERY 6TH COURSE. REBUILD CHIMNEY AROUND
CMU BLOCK AND MORTAR PER UNIT MASONRY
SPECIFICATION.
PROVIDE FULL LENGTH SISTERED JOIST PER TYPICAL DETAIL.
REFER TO TYPICAL WOOD JOIST REPAIR AT STONE WALL
DETAIL FOR CONNECTION OF SISTERED JOIST TO EXISTING
STONE WALL. REFER TO SECTION H ON S1-503 FOR
CONNECTION OF SISTERED JOIST TO EXISTING W16. PROVIDE
JOIST HANGER AT ENDS OF HEADER.
CONNECTION DESIGN FORCE LEGEND
FACTORED FORCES FOR CONNECTION DESIGN ARE SHOWN ON THE
PLAN AND ELEVATIONS ARE AS FOLLOWS:
A INDICATES FACTORED AXIAL LOAD TRANSFERRED THROUGH
CONNECTION IN KIPS.
M INDICATES FACTORED END MOMENT IN KIP-FEET.
V INDICATES FACTORED END SHEAR IN KIPS.
IN SOME CASES, V < 5KIPS. TYPICAL DETAILS WILL CONTROL MINIMUM
CONNECTION.
REFER TO TYPICAL DETAILS FOR CONNECTIONS; IN NO CASE SHALL
THE CONNECTION DESIGN BE LESS THAN THE REQUIREMENTS OF THE
TYPICAL DETAILS.
COMBINE SHEAR FORCES ON THE PLANS AND ELEVATIONS WITH
ADDITIONAL CONNECTION AXIAL FORCES IN KIPS NOTED ON FRAMING
PLANS AND ELEVATIONS.
SEE PLANS FOR LOAD RESISTANCE FACTORED DESIGN MOMENTS IN
FT-KIPS.
REVISIONS
1 ADDENDUM
F S1-503
E S1-503
SPAN
EXISTING CHIMNEY
EXISTING WALL
W8X15
HSS3x3 POST UP
[ 42.33' ]
TOW EL 37.67'
TOS EL 37.33'
HOIST BEAM
PROVIDED BY
ELEVATOR
MANUFACTURER
C
A
874 5
B
W
X3
W
X4
W
X4
W10X30
C12X20.7
W10X30
W
X4
C12X20.7C12X20.7
W
X4
W
X3
W10X30
W10X30
W12X26 W12X26 W12X26
10' - 6" 19' - 9" 25' - 0" 19' - 9" 10' - 6"
6" 7'
- 6
EXISTING STONE
MASONRY WALL
(TYPICAL)
SP
AN
SP
AN
SP
AN
W16X31
W10X49
W12X26
W10X30
W10X30
W10X30
W10X30
W12X26W12X26
W16X31
C12X20.7C12X20.7C12X20.7
W
X3
W
X3
W
X3
W
X3
1'
- 8
" 4" 4"
7"
4 1 /2"
EDGE OF DECK
3 1/2"
(TOS EL 34.53' )
W12X26W12X26
(TOS EL 34.61' )
BRACE
BR
AC
E
BR
AC
E
BRACE
EDGE OF DECK
K S1-504
L S1-504
M S1-504
A S1-505
B S1-505
L S1-504
M S1-504
4 1 /2"
3 1/2"
(TOS EL 34.53' ) (TOS EL 34.53' )
4 1 /2"
4'
- 3
1/ 4"
4 1 /2"
EDGE OF DECK
W16 (EXIST)
W16 (EXIST)
W16 (EXIST)
W16 (EXIST) W16 (EXIST)
4"
4'
- 8
4"
W12X26
(TOS EL 33.68' )(TOS EL 33.68' ) (TOS EL 33.68' )
EXISTING BRICK
MASONRY CHIMNEY
1'
- 8
(TOS EL 34.61' ) (TOS EL 34.61' )
(TOS EL 34.11' ) (TOS EL 34.11' ) (TOS EL 34.11' )
(TOS EL 33.63' ) (TOS EL 33.63' ) (TOS EL 33.63' )
TOS EL 31.67'STAIR TOWER
TOS EL 31.67'
STAIR TOWER
K S1-503
3x12@16"
3X12@16"
EXIST 3x12@16" O.C. (TYP, UON)
L S1-503
2x 8@
EQ
S
PC
B S1-503
H S1-503
2x8
2x8
A S1-505
L S1-504
SIM
L S1-504
SIM
L S1-504
SIM
L S1-504
SIM
HS
S3
X3 X1
/4
HSS3X3X1/4
M
S1-503
N S1-503
REMOVABLE FLOOR
3' - 6" ±
1' - 5" 1' - 5"
W
X2
W
X2
W12X26
W12X26
4" ±4" ±
V5
V1
V5
V5 V15
V5
V5
V10V5
V1
V5 V5
V5 V5
V5
A10 V10
V15 V15
V10 V10
V5 V5
V10 V10
V5 V5
V15 V15 V15
V10 A10 V10
A10 V10
V10
V5 V5 V5 V5
V5
V1
V5
V5V15
V5
V5
V10 V5
V1
V5V5
V5V5
V5
A10 V10
V15
EXIST 2x12@16"± EXIST 2x12@16"± EXIST 2x12@16"±
EXIST 2x12@16"± EXIST 2x12@16"±
2 - 3x
D
S1-503
S1-505
V5 M1
V5 M1
V5
V5 M1
V5 M1
V5V5 V5
V5 V5
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
DRAWING NO.
SCALE:
DATE:
DES: DRAWN: CHECK:
SHEET OF 160
SIGNATURE
GRAPHIC SCALES
KEY PLAN
1 3 4 5 62
A
B
C
D
E
1 3 4 5 62
SOLICITATION NO: 70FA5018R00000013
UNCLASSIFIED // FOR OFFICIAL USE ONLY
UNCLASSIFIED // FOR OFFICIAL USE ONLY
1/4" = 1'-0"
/0
8/
6:
:1
S1-105
RJN CJS JFG
05/23/2018
MT. WEATHER
EMERGENCY
OPERATIONS CENTER
(MWEOC)
BUILDING 413
HISTORIC
REHABILITATION AND
CODE COMPLIANCE
STRUCTURAL ATTIC AND ELEVATOR
ROOF PLAN
19844 BLUERIDGE
MOUNTAIN ROAD,
MT WEATHER, VA 20135
SCALE: 1/4" = 1'-0"S1-105
2 ELEVATOR ROOF PLAN
SCALE: 1/4" = 1'-0"S1-105
1 ATTIC FLOOR PLAN
0 8'4'2'
1/4" = 1'-0"SCALE:
GENERAL SHEET NOTES
1. SEE S1-001 FOR GENERAL NOTES.
2. SEE S1-002 THROUGH S1-005 FOR TYPICAL DETAILS.
3. ADDITION ROOF CONSTRUCTION TO BE TYPE 3N20, CONSISTING
OF 3” METAL ROOF DECK. ATTACH STEEL DECK WITH 24/4
PATTERN WITH 5/8" PUDDLE WELDS. STEEL DECK SIDE LAP
CONNECTION SHALL BE #10 SCREWS AT 12" SPACING.
4. REFER TO FRAMING ELEVATIONS ON STRUCTURAL 200 SERIES
FOR FRAMING ELEVATIONS AND DIAGONAL BRACING ALONG
COLUMN GRID LINES.
5. VERIFY EXISTING DIMENSIONS AND SIZES PRIOR TO WORK.
6. NEW WOOD JOISTS ARE SHOWN IN A GENERAL ARRANGEMENT.
JOISTS MUST BE LOCATED SO THAT THERE ARE NO
UNSUPPORTED EDGES OF FLOORING AND AROUND ALL PIPING
RUNNING BETWEEN FLOORS.
LEGEND
INDICATES THE DIRECTION OF METAL DECK SPAN.SPAN
INDICATES MOMENT CONNECTION
SHEET KEYNOTES
RELOCATE EXISTING STAIR TO NEW LOCATION. REFER TO
ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
ELEVATOR HOIST BEAM. COORDINATE SIZE, LOCATION, AND
ELEVATION WITH ELEVATOR MANUFACTURER.
REMOVABLE FLOOR COMPOSED OF 2X8 JOISTS TO BE
LOCATED NEXT TO THE ELEVATOR BETWEEN THE CHIMNEY
AND NEW WIDE FLANGE GIRDER. CONTRACTOR TO PROVIDE
RECESSED LIFT POINT TO ALLOW FLOOR TO BE REMOVED
FROM ANGLE SUPPORTS PROVIDING ACCESS TO FLOOR
BELOW.
TOOTH IN CMU BLOCK FROM ELEVATOR SHAFT TO MASONRY
CHIMNEY EVERY 6TH COURSE. REBUILD CHIMNEY AROUND
CMU BLOCK AND MORTAR PER UNIT MASONRY
SPECIFICATION.
PROVIDE FULL LENGTH SISTERED JOIST PER TYPICAL
DETAIL. REFER TO TYPICAL WOOD JOIST REPAIR AT STONE
WALL DETAIL FOR CONNECTION OF SISTERED JOIST TO
EXISTING STONE WALL. REFER TO SECTION H ON S1-503 FOR
CONNECTION OF SISTERED JOIST TO EXISTING W16. PROVIDE
JOIST HANGER AT ENDS OF HEADER.
CONNECTION DESIGN FORCE LEGEND
FACTORED FORCES FOR CONNECTION DESIGN ARE SHOWN ON THE
PLAN AND ELEVATIONS ARE AS FOLLOWS:
A INDICATES FACTORED AXIAL LOAD TRANSFERRED THROUGH
CONNECTION IN KIPS.
M INDICATES FACTORED END MOMENT IN KIP-FEET.
V INDICATES FACTORED END SHEAR IN KIPS.
IN SOME CASES, V < 5KIPS. TYPICAL DETAILS WILL CONTROL MINIMUM
CONNECTION.
REFER TO TYPICAL DETAILS FOR CONNECTIONS; IN NO CASE SHALL
THE CONNECTION DESIGN BE LESS THAN THE REQUIREMENTS OF THE
TYPICAL DETAILS.
COMBINE SHEAR FORCES ON THE PLANS AND ELEVATIONS WITH
ADDITIONAL CONNECTION AXIAL FORCES IN KIPS NOTED ON FRAMING
PLANS AND ELEVATIONS.
SEE PLANS FOR LOAD RESISTANCE FACTORED DESIGN MOMENTS IN
FT-KIPS.