Range Exposure Test
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| QUESTIONS_AND_ANSWERS.docx | DOCX document | |
| Price_Schedule_Clauses_Provisions.pdf | ||
| Attachment_A_-_Cleaning_Maintenance_log.docx | DOCX document | |
| Attachment_C_-_NON_DISCLOSURE_DHS_Form_11000-6_(08-18).pdf | ||
| Attachment_B_-_Performance_Work_Statement_-_Final.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RANGE: _________________________________________
Exposure Testing (Required Every 90 Days)
| Date |
| Last Firing Exercise by CBP |
| Lead |
| Carbon Monoxide |
| Smoke Tests |
| Air Flow |
| Measurement |
| Meets or Exceeds |
| Lead Dust In The Range Area-Measurement |
| Meets or Exceeds |
| Measurement |
| Meets or Exceeds |
| Measurement |
| Meets or Exceeds |
| Measurement |
| Meets or Exceeds |
| Date of last HVAC filter replacement |
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Corrective Action taken to address measurements not meeting requirements, if any:
| Date |
| Action |
Measurement Standards:
· Micrograms of lead levels per centimeter of air immediately following live fire exercise. (Measurements which demonstrate the effectiveness of the ventilation system capture velocity, static pressure and proper air flow/velocity throughout the shooting area.)
· Airborne lead levels must meet or exceed the OSHA action level of 30 micrograms per centimeter of air on personal exposure to lead in air during live fire exercises
· Does the firing range meet or exceed all Federal, State and Local requirements established for safety, health, and noise and air quality?
· Lead dust in the range area (except downrange from shooting line must measure less than 200 micrograms per foot.
· Carbon monoxide must be less than 50 ppm (OSHA PEL) and preferably less than 25 ppm (ACGIH TLV) as an 8-hour time-weighted average.
· Air flow at the firing line should be 75 feet per minute (fpm) plus or minus 10%.
· Smoke tests at the firing line should show laminar flow to downrange locations without lingering in or around the shooting line.