This document is a Request for Proposal (RFP) for interior and exterior repairs to Building 143 at the Fleet Readiness Center East (FRCE). The procurement is restricted to the General MACC contractors listed on the RFP cover letter. The scope of work and any applicable drawings are attached. The solicitation number is N400857031567, and the contracting agency is the Department of the Navy Naval Facilities Engineering Command. No other details about pricing terms, award dates, or set-asides are provided in the information given.

View the file

Other files

File Type Posted
Amendment 0002.pdf PDF
Amendment 0001.pdf PDF
RFP 7031567.pdf PDF
7031567 DrawingsAsOne SIGNED.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE NAVY

NAVAL FACILITIES ENGINEERING COMMAND, MID-ATLANTIC

MARINE CORPS AIR STATION, CHERRY POINT, NORTH CAROLINA

INTERIOR AND EXTERIOR REPAIRS TO BUILDING 143

AT THE

MARINE CORPS AIR STATION

CHERRY POINT, NORTH CAROLINA

PROJECT

WO #7031567

DESIGNED BY:

PACE COLLABORATIVE

VIRGINIA BEACH, VIRGINIA

SPECIFICATION PREPARED BY:

NICHOLAS A. HALL, P.E.

TIMOTHY N. HAHN, P.E.

KEYEN MEARS, P.E.

KEVIN ROOMSBURG, P.E.

CHRIS WALKER, AIA

KEVIN AVOLIS, P.E.

SPECIFICATION APPROVED BY:

Design Director: _____________________________________________

PATRICK FAULKNER, PE.

Date: ___________________

06/14/2024

7/5/24

INTERIOR AND EXTERIOR REPAIRS TO BUILDING 143

PROJECT TABLE OF CONTENTS

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

00 01 15 02/11 LIST OF DRAWINGS

00 22 13.00 20 02/14 SUPPLEMENTARY INSTRUCTIONS TO OFFERORS

DIVISION 01 - GENERAL REQUIREMENTS

01 11 00 02/24 SUMMARY OF WORK

01 14 00 11/22, CHG 1: 02/23 WORK RESTRICTIONS

01 20 00 11/20, CHG 3: 02/23 PRICE AND PAYMENT PROCEDURES

01 30 00 11/20, CHG 3: 08/23 ADMINISTRATIVE REQUIREMENTS

01 30 01.00 22 DESIGN, PROCUREMENT AND INSTALLATION

OF FURNITURE, FIXTURES AND EQUIPMENT

01 31 23.13 20 08/23 ELECTRONIC CONSTRUCTION AND FACILITY

SUPPORT CONTRACT MANAGEMENT SYSTEM

(eCMS)

01 32 16.00 20 08/18, CHG 1: 08/20 SMALL PROJECT CONSTRUCTION PROGRESS

SCHEDULES

01 33 00 08/18, CHG 4: 02/21 SUBMITTAL PROCEDURES

01 33 29 02/21 SUSTAINABILITY REQUIREMENTS AND

REPORTING

01 35 26 11/20, CHG 4: 08/23 GOVERNMENTAL SAFETY REQUIREMENTS

01 42 00 02/19, CHG 1: 08/23 SOURCES FOR REFERENCE PUBLICATIONS

01 45 00 08/23 QUALITY CONTROL

01 50 00 11/20, CHG 2: 08/22 TEMPORARY CONSTRUCTION FACILITIES AND

CONTROLS

01 57 19 08/22 TEMPORARY ENVIRONMENTAL CONTROLS

01 78 00 05/19, CHG 1: 08/21 CLOSEOUT SUBMITTALS

01 78 23 05/23 OPERATION AND MAINTENANCE DATA

01 78 30.00 22 02/16 GIS DATA DELIVERABLES

01 80 00 04/15 REPORTS

01 91 00.15 05/23, CHG 2: 11/23 BUILDING COMMISSIONING

01 91 19 05/2023 BUILDING ENCLOSURE COMMISSIONING

DIVISION 02 - EXISTING CONDITIONS

02 41 00 08/22 DEMOLITION

02 82 00 11/18, CHG 1: 11/19 ASBESTOS REMEDIATION

02 83 00 11/18 LEAD REMEDIATION

DIVISION 03 - CONCRETE

03 30 00 02/19, CHG 7: 02/24 CAST-IN-PLACE CONCRETE

03 30 53 05/14 MISCELLANEOUS CAST-IN-PLACE CONCRETE

(SIDEWALKS)

03 45 00 05/16, CHG 2: 11/21 PRECAST ARCHITECTURAL CONCRETE

DIVISION 04 - MASONRY

04 20 00 11/15, CHG 2: 05/19 UNIT MASONRY

DIVISION 05 - METALS

05 12 00 08/18, CHG 2: 05/21 STRUCTURAL STEEL

05 40 00 05/15, CHG 1: 08/18 COLD-FORMED METAL FRAMING

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

PROJECT TABLE OF CONTENTS Page 1

INTERIOR AND EXTERIOR REPAIRS TO BUILDING 143 7031567

06 10 00 08/16, CHG 2: 11/18 ROUGH CARPENTRY

06 20 00 08/16, CHG 2: 11/18 FINISH CARPENTRY

06 61 16 08/20 SOLID SURFACING FABRICATIONS

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 21 16 08/23 MINERAL FIBER BLANKET INSULATION

07 22 00 08/23 ROOF AND DECK INSULATION

07 27 10 08/23 BUILDING AIR BARRIER SYSTEM

07 41 13 05/11, CHG 4: 02/21 METAL ROOF PANELS

07 42 13 05/11, CHG 2: 02/18 METAL WALL PANELS

07 60 00 08/23 FLASHING AND SHEET METAL

07 92 00 08/23 JOINT SEALANTS

DIVISION 08 - OPENINGS

08 11 13 08/20 STEEL DOORS AND FRAMES

08 14 00 08/16, CHG 1: 08/18 WOOD DOORS

08 31 00 05/17, CHG 1: 08/18 ACCESS DOORS AND PANELS

08 41 13 08/18, CHG 1: 08/18 ALUMINUM-FRAMED ENTRANCES AND

STOREFRONTS

08 51 13 05/19 ALUMINUM WINDOWS

08 71 00 02/16, CHG 4: 02/22 DOOR HARDWARE

08 81 00 05/19 GLAZING

DIVISION 09 - FINISHES

09 22 00 02/10, CHG 2: 08/18 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00 08/16, CHG 4: 02/20 GYPSUM BOARD

09 30 10 08/20 CERAMIC, QUARRY, AND GLASS TILING

09 51 00 08/20 ACOUSTICAL CEILINGS

09 65 00 08/10, CHG 3: 08/18 RESILIENT FLOORING

09 68 00 11/17, CHG 2: 08/20 CARPETING

09 90 00 02/21 PAINTS AND COATINGS

DIVISION 10 - SPECIALTIES

10 14 00.20 08/20 INTERIOR SIGNAGE

10 21 13 08/20 TOILET COMPARTMENTS

10 26 00 08/20 WALL AND DOOR PROTECTION

10 28 13 08/20 TOILET ACCESSORIES

10 44 16 11/19 FIRE EXTINGUISHERS

DIVISION 12 - FURNISHINGS

12 24 13 08/20 ROLLER WINDOW SHADES

DIVISION 21 - FIRE SUPPRESSION

21 13 13 08/20 WET PIPE SPRINKLER SYSTEMS, FIRE

PROTECTION

DIVISION 22 - PLUMBING

22 00 00 11/15, CHG 4: 05/21 PLUMBING, GENERAL PURPOSE

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

PROJECT TABLE OF CONTENTS Page 2

INTERIOR AND EXTERIOR REPAIRS TO BUILDING 143 7031567

23 03 00.00 20 08/10 BASIC MECHANICAL MATERIALS AND METHODS

23 05 93 11/15 TESTING, ADJUSTING, AND BALANCING FOR

HVAC

23 07 00 02/13 THERMAL INSULATION FOR MECHANICAL

SYSTEMS

23 08 00 05/23 COMMISSIONING OF MECHANICAL AND

PLUMBING SYSTEMS

23 09 00 02/19, CHG 3: 05/21 INSTRUMENTATION AND CONTROL FOR HVAC

23 09 13 11/15, CHG 2: 05/21 INSTRUMENTATION AND CONTROL DEVICES

FOR HVAC

23 09 23.02 02/19, CHG 1: 02/20 BACNET DIRECT DIGITAL CONTROL FOR HVAC

AND OTHER BUILDING CONTROL SYSTEMS

23 30 00 05/20, CHG 1: 02/22 HVAC AIR DISTRIBUTION

23 81 00 05/18, CHG 1: 02/21 DECENTRALIZED UNITARY HVAC EQUIPMENT

23 82 00.00 20 02/16 TERMINAL HEATING UNITS

DIVISION 26 - ELECTRICAL

26 20 00 08/23 INTERIOR DISTRIBUTION SYSTEM

26 41 00 08/23 LIGHTNING PROTECTION SYSTEM

26 51 00 05/20, CHG 2: 11/21 INTERIOR LIGHTING

DIVISION 27 - COMMUNICATIONS

27 10 00 08/11 BUILDING TELECOMMUNICATIONS CABLING

SYSTEM

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 31 76 08/20 INTERIOR FIRE ALARM AND MASS

NOTIFICATION SYSTEM, ADDRESSABLE

DIVISION 31 - EARTHWORK

31 00 00 08/23 EARTHWORK

31 11 00 11/18 CLEARING AND GRUBBING

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 11 23 05/22 AGGREGATE BASE COURSE

32 11 26 05/20 HOT-MIX BITUMINOUS BASE COURSE FOR

ROADS AND STREETS

32 92 23 04/06, CHG 1: 08/21 SODDING

DIVISION 33 - UTILITIES

33 11 00 02/18, CHG 2: 11/23 WATER UTILITY DISTRIBUTION PIPING

33 30 00 05/18 SANITARY SEWERAGE

33 82 00 04/06 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)

-- End of Project Table of Contents --

PROJECT TABLE OF CONTENTS Page 3

I NTERI OR AND EXTERI OR REPAI RS TO BUI LDI NG 143

DOCUMENT 00 01 15

LI ST OF DRAWI NGS

02/ 11

PART 1 GENERAL

1. 1 SUMMARY

Thi s sect i on l i s t s t he dr awi ngs f or t he pr oj ect pur suant t o cont r act c l ause " DFARS 252. 236- 7001, Cont r act Dr awi ngs, Maps and Speci f i cat i ons. "

1. 2 CONTRACT DRAWI NGS

Cont r act dr awi ngs ar e as f ol l ows:

DRAWI NG NO. NAVFAC DWG NO. TI TLE

G- 001 12816111 COVER SHEET

GI 001 12816112 LI FE SAFETY CODE ANALYSI S

GI 002 12816113 LI FE SAFETY SI TE PLAN

GI 101 12816114 LI FE SAFETY PLAN

H101 12816115 LEAD & ASBESTOS LOCATI ON PLAN

CD101 12816116 SI TE PLAN - EXI STI NG CONDI TI ONS AND DEMOLI TI ON

CS101 12816117 SI TE PLAN - LAYOUT AND STRI PI NG

CG101 12816118 SI TE PLAN - GRADI NG & EROSI ON CONTROL

CU101 12816119 SI TE UTI LI TY PLAN

CS501 12816120 DETAI LS

CS502 12816121 DETAI LS

CG501 12816122 DETAI LS

CU501 12816123 DETAI LS & PROFI LE

S- 001 12816124 GENERAL NOTES

DOCUMENT 00 01 15 Page 1

DRAWI NG NO. NAVFAC DWG NO. TI TLE

S- 002 12816125 GENERAL NOTES AND ABBREVI ATI ONS

SD101 12816126 STRUCTURAL DEMOLI TI ON PLANS

S- 101 12816127 FOUNDATI ON PLAN

S- 102 12816128 ROOF FRAMI NG PLAN

S- 301 12816129 SECTI ONS

S- 302 12816130 SECTI ONS

S- 501 12816131 TYPI CAL DETAI LS

S- 502 12816132 TYPI CAL DETAI LS

AD101 12816133 DEMOLI TI ON FLOOR PLAN

AD102 12816134 DEMOLI TI ON REFLECTED CEI LI NG PLAN

AD103 12816135 DEMOLI TI ON ROOF PLAN

AD201 12816136 DEMOLI TI ON ELEVATI ONS

AD301 12816137 DEMOLI TI ON BUI LDI NG SECTI ON

A- 001 12816138 WALL SCHEDULE

A- 101 12816139 CONSTRUCTI ON FLOOR PLAN

A- 102 12816140 CONSTRUCTI ON REFLECTED CEI LI NG PLAN

A- 103 12816141 CONSTRUCTI ON ROOF PLAN

A- 201 12816142 CONSTRUCTI ON ELEVATI ONS

A- 301 12816143 CONSTRUCTI ON BUI LDI NG SECTI ON

A- 401 12816144 ENLARGED PLAN AND I NTERI OR ELEVATI ONS

A- 501 12816145 CONSTRUCTI ON BUI LDI NG SECTI ON

A- 502 12816146 CONSTRUCTI ON BUI LDI NG SECTI ON

A- 503 12816147 DETAI LS

DOCUMENT 00 01 15 Page 2

A- 504 12816148 CONSTRUCTI ON BUI LDI NG SECTI ON

A- 505 12816149 DETAI LS

A- 506 12816150 DETAI LS

A- 507 12816151 DETAI LS

A- 508 12816152 DETAI LS

A- 601 12816153 DOOR SCHEDULE AND DETAI LS

A- 602 12816154 DETAI LS

A- 603 12816155 DETAI LS

I - 101 12816156 I NTERI OR FLOOR PLAN AND EQUI PMENT LI ST

I - 102 12816157 I NTERI OR FLOOR FI NI SH PLAN

I - 103 12816158 I NTERI OR ELEVATI ONS AND DETAI LS

I - 104 12816159 I NTERI OR ELEVATI ONS & DETAI LS

I - 601 12816160 I NTERI OR FI NI SH SCHEDULE & DETAI LS

FX001 12816161 GENERAL NOTES LEGEND AND ABBREVI ATI ONS

FXD101 12816162 DEMOLI TI ON FLOOR PLAN - SPRI NKLER

FX101 12816163 FLOOR PLAN - SPRI NKLER

P- 001 12816164 GENERAL NOTES, LEGEND, AND ABBREVI ATI ONS

PD101 12816165 DEMOLI TI ON FLOOR PLAN

P- 101 12816166 FLOOR PLAN - SANI TARY WASTE

P- 102 12816167 FLOOR PLAN - DOMESTI C WATER

P- 501 12816168 FI XTURE PLATES

P- 502 12816169 FI XTURE PLATES AND SCHEDULES

P- 503 12816170 DETAI LS

DOCUMENT 00 01 15 Page 3

P- 601 12816171 RI SER DI AGRAMS

M- 001 12816172 MECHANI CAL GENERAL NOTES AND LEGEND

MD101 12816173 MECHANI CAL DEMOLI TI ON PLAN

MH101 12816174 MECHANI CAL CONSTRUCTI ON PLAN

M- 501 12816175 MECHANI CAL DETAI LS

M- 502 12816176 MECHANI CAL DETAI LS

M- 601 12816177 MECHANI CAL SCHEDULES

M- 701 12816178 MECHANI CAL CONTROLS

M- 702 12816179 MECHANI CAL CONTROLS

E- 001 12816180 GENERAL NOTES, LEGEND, AND ABBREVI ATI ONS

ED101 12816181 DEMOLI TI ON - FLOOR PLAN

E- 101 12816182 CONSTRUCTI ON - LI GHTI NG PLAN

E- 201 12816183 CONSTRUCTI ON - POWER PLAN

E- 202 12816184 LI GHTI NG PROTECTI ON PLAN

E- 501 12816185 LI GHTI NG DETAI LS

E- 502 12816186 ELECTRI CAL DETAI LS

E- 503 12816187 PANEL SCHEDULES

E- 601 12816188 RI SER DI AGRAM

FA001 12816189 FI RE ALARM GENERAL NOTES, LEGEND, AND ABBREVI ATI ONS

FA101 12816190 FI RE ALARM CONSTRUCTI ON FLOOR PLAN

DOCUMENT 00 01 15 Page 4

FA501 12816191 FI RE ALARM DETAI LS AND RI SER DI AGRAM

T- 001 12816192 TELECOM GENERAL NOTES, LEGEND, AND ABBREVI ATI ONS

T- 002 12816193 TELECOMMUNI CATI ONS SI TE PLAN

T- 101 12816194 TELECOMMUNI CATI ONS CONSTRUCTI ON FLOOR PLAN

T- 501 12816195 TELECOMMUNI CATI ONS DETAI LS

T- 502 12816196 TELECOMMUNI CATI ONS SI TE DETAI LS

- - End of Document - -

DOCUMENT 00 01 15 Page 5

SECTI ON 01 11 00

SUMMARY OF WORK

02/ 24

PART 1 GENERAL

1. 1 SUBMI TTALS

Gover nment appr oval i s r equi r ed f or al l submi t t al s. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

Sal vage Pl an

1. 2 WORK COVERED BY CONTRACT DOCUMENTS

1. 2. 1 Pr oj ect Descr i pt i on

The wor k i ncl udes i ncl udes r econf i gur at i on; r epl acement of i nt er i or f i ni shes and pai nt i ng, pl umbi ng f i xt ur es i ncl udi ng wat er suppl y wast e, and vent pi pi ng, HVAC syst ems, i nt er i or l i ght f i x t ur es; modi f i cat i ons t o f i r e suppr essi on and f i r e al ar m syst ems; add addi t i onal out l et s and t el ecommuni cat i ons; FF&E package; r epl acement of ext er i or s i di ng, r oof , gut t er s, downspout s, f l ashi ng, wi ndows, door s, f r ames, and har dwar e; and i nci dent al r el at ed wor k.

1. 2. 2 Locat i on

The wor k i s l ocat ed at MCAS Cher r y Poi nt , appr oxi mat el y as i ndi cat ed. The exact l ocat i on wi l l be shown by t he Cont r act i ng Of f i cer .

1. 3 OCCUPANCY OF PREMI SES

Bef or e wor k i s st ar t ed, ar r ange wi t h t he Cont r act i ng Of f i cer a sequence of pr ocedur e, means of access, space f or st or age of mat er i al s and equi pment , and use of appr oaches, cor r i dor s, and st ai r ways.

1. 4 EXI STI NG WORK

Remove or al t er exi st i ng wor k i n such a manner as t o pr event i nj ur y or damage t o any por t i ons of t he exi st i ng wor k whi ch r emai n.

Repai r or r epl ace por t i ons of exi st i ng wor k whi ch have been al t er ed dur i ng const r uct i on oper at i ons t o mat ch exi st i ng or adj oi ni ng wor k, as appr oved by t he Cont r act i ng Of f i cer . At t he compl et i on of oper at i ons, exi st i ng wor k must be i n a condi t i on equal t o or bet t er t han t hat whi ch exi st ed bef or e new wor k st ar t ed.

1. 5 LOCATI ON OF UNDERGROUND UTI LI TI ES

Obt ai n di ggi ng per mi t s pr i or t o st ar t of excavat i on, and compl y wi t h I nst al l at i on r equi r ement s f or l ocat i ng and mar ki ng under gr ound ut i l i t i es.

Cont act l ocal ut i l i t y l ocat i ng ser vi ce a mi ni mum of 48 hour s pr i or t o excavat i ng, t o mar k ut i l i t i es, and wi t hi n suf f i c i ent t i me r equi r ed i f wor k occur s on a Monday or af t er a Hol i day. Ver i f y exi st i ng ut i l i t y l ocat i ons i ndi cat ed on cont r act dr awi ngs, wi t hi n ar ea of wor k.

SECTI ON 01 11 00 Page 1

I dent i f y and mar k al l ot her ut i l i t i es not managed and l ocat ed by t he l ocal ut i l i t y compani es. Scan t he const r uct i on s i t e wi t h Gr ound Penet r at i ng Radar ( GPR) , el ect r omagnet i c, or soni c equi pment , and mar k t he sur f ace of t he gr ound or paved sur f ace wher e exi st i ng under gr ound ut i l i t i es ar e di scover ed. Ver i f y t he el evat i ons of exi st i ng pi pi ng, ut i l i t i es, and any t ype of under gr ound obst r uct i on not i ndi cat ed, or speci f i ed t o be r emoved, t hat i s i ndi cat ed or di scover ed dur i ng scanni ng, i n l ocat i ons t o be t r aver sed by pi pi ng, duct s, and ot her wor k t o be conduct ed or i nst al l ed.

Ver i f y el evat i ons bef or e i nst al l i ng new wor k c l oser t han near est manhol e or ot her st r uct ur e at whi ch an adj ust ment i n gr ade can be made.

1. 5. 1 Not i f i cat i on Pr i or t o Excavat i on

Not i f y t he Cont r act i ng Of f i cer at l east 15 days pr i or t o st ar t i ng excavat i on wor k.

1. 6 NAVY AND MARI NE CORPS I NTRANET ( NMCI ) COORDI NATI ON REQUI REMENTS

1. 6. 1 NMCI Cont r act or Access

Al l ow t he NMCI Cont r act or access t o t he f aci l i t y t owar ds t he end of const r uct i on ( f i ni shes 90 per cent compl et e, r ough- i n 100 per cent compl et e, I nsi de Pl ant ( I SP) / Out si de Pl ant ( OSP) i nf r ast r uct ur e i n pl ace) t o pr ovi de equi pment i n t he t el ecommuni cat i ons r ooms and make f i nal connect i ons.

Coor di nat e ef f or t s wi t h t he NMCI Cont r act or t o f aci l i t at e j oi nt use of bui l di ng spaces dur i ng t he f i nal phases of const r uct i on. Af t er t he Cont r act i ng Of f i cer has f aci l i t at ed coor di nat i on meet i ngs bet ween t he t wo cont r act or s, wi t hi n one week, i ncor por at e t he ef f or t of addi t i onal coor di nat i on wi t h t he NMCI Cont r act or i nt o t he const r uct i on schedul e t o demonst r at e a pl an f or mai nt ai ni ng t he cont r act dur at i on.

1. 7 SALVAGE MATERI AL AND EQUI PMENT

Al l equi pment , machi ner y, met al l i c pi pi ng, wi r e, and ot her scr ap met al shal l r emai n t he Gover nment ' s pr oper t y. Recycl e t hese i t ems as par t of demol i t i on and deconst r uct i on oper at i ons. Pr ovi de separ at e cont ai ner s t o col l ect t hese i t ems and t r anspor t t o t he FRC East r ecycl i ng f aci l i t y i n Bui l di ng 4785. Coor di nat e wi t h t he r ecycl i ng per sonnel at Bui l di ng 4785 t o ar r ange an appr opr i at e t i me f or del i ver y.

Pr ovi de a sal vage pl an, l i s t i ng mat er i al and equi pment t o be sal vaged, and t hei r st or age l ocat i on. Mai nt ai n pr oper t y cont r ol r ecor ds f or mat er i al or equi pment desi gnat ed as sal vage. Pr ovi de a syst em f or pr oper t y cont r ol i n t he sal vage pl an. St or e and pr ot ect sal vaged mat er i al s and equi pment unt i l di sposi t i on by t he Cont r act i ng Of f i cer .

PART 2 PRODUCTS

Not used.

PART 3 EXECUTI ON

Not used.

- - End of Sect i on - -

SECTI ON 01 11 00 Page 2

SECTI ON 01 14 00

WORK RESTRI CTI ONS

11/ 22, CHG 1: 02/ 23

PART 1 GENERAL

1. 1 SUBMI TTALS

Gover nment appr oval i s r equi r ed f or al l submi t t al s. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

Li st of Cont act Per sonnel Heal t h And Saf et y Pl an f or Wor k i n Land Use Cont r ol ( LUC) Ar eas

1. 2 SPECI AL SCHEDULI NG REQUI REMENTS

a. Have mat er i al s, equi pment , and per sonnel r equi r ed t o per f or m t he wor k at t he s i t e pr i or t o t he commencement of t he wor k.

b. Per mi ssi on t o i nt er r upt any Act i v i t y r oads, r ai l r oads, or ut i l i t y ser vi ce must be r equest ed i n wr i t i ng a mi ni mum of 15 cal endar days pr i or t o t he desi r ed dat e of i nt er r upt i on.

c. The Cont r act or shal l devel op and submi t a pr oj ect speci f i c Heal t h and Saf et y Pl an f or Wor k i n Land Use Cont r ol ( LUC) Ar eas f or r evi ew and appr oval by t he Envi r onment al Pr ot ect i on Agency and t he St at e of Nor t h Car ol i na pr i or t o any wor k occur r i ng i n ar eas desi gnat ed t o be wi t hi n t he boundar i es of an est abl i shed Land Use Cont r ol ( LUC) Ar ea and i nvol v i ng excavat i on i nt o t he gr oundwat er t abl e.

The Cont r act or shal l al l ow f or a 120 cal endar day r evi ew per i od f r om r ecei pt of an appr oved Heal t h and Saf et y Pl an ( H&SP) .

The H&SP shal l be submi t t ed t o t he Cont r act i ng Of f i cer who wi l l f or war d i t t o t he appr opr i at e r evi ew aut hor i t i es.

The H&SP shal l cont ai n and/ or addr ess as a mi ni mum t he f ol l owi ng el ement s:

1. Gener al Pr oj ect Scope and Descr i pt i on.

2. Ant i c i pat ed i mpact s t o soi l and/ or gr oundwat er .

3. Pr ot ocol f or mi ni mi zi ng exposur e t o pot ent i al cont ami nat ed mat er i al s i ncl udi ng, but not l i mi t ed t o:

a. Tr ai ni ng

b. Wor k Ar ea Pr ecaut i ons

c. Per sonnel Saf et y and Heal t h Pr ecaut i ons

d. Chemi cal Hazar d Communi cat i ons Pr ogr am

The Cont r act or shal l submi t seven ( 7) dr af t copi es of t he HS&P t o t he Cont r act i ng Of f i cer f or r evi ew. Wr i t t en comment s wi l l be pr ovi ded and shal l be i ncor por at ed i nt o t he H&SP.

SECTI ON 01 14 00 Page 1

The Cont r act or shal l submi t seven ( 7) copi es of t he f i nal H&SP.

d. The wor k under t hi s cont r act r equi r es speci al at t ent i on t o t he schedul i ng and conduct of t he wor k i n connect i on wi t h exi st i ng oper at i ons. I dent i f y on t he const r uct i on schedul e each f act or whi ch const i t ut es a pot ent i al i nt er r upt i on t o oper at i ons.

1. 3 CONTRACTOR ACCESS AND USE OF PREMI SES

1. 3. 1 Act i v i t y Regul at i ons

Ensur e t hat Cont r act or per sonnel empl oyed on t he Act i v i t y become f ami l i ar wi t h and obey Act i v i t y r egul at i ons i ncl udi ng saf et y, f i r e, t r af f i c and secur i t y r egul at i ons. Keep wi t hi n t he l i mi t s of t he wor k and avenues of i ngr ess and egr ess. Wear appr opr i at e per sonal pr ot ect i ve equi pment ( PPE) i n desi gnat ed ar eas. Do not ent er any r est r i ct ed ar eas unl ess r equi r ed t o do so and unt i l c l ear ed f or such ent r y. Ensur e al l Cont r act or equi pment , i ncl udi ng del i ver y vehi c l es, ar e c l ear l y i dent i f i ed wi t h t hei r company name.

1. 3. 1. 1 Subcont r act or s and Per sonnel Cont act s

Pr ovi de a l i s t of cont act per sonnel of t he Cont r act or and subcont r act or s i ncl udi ng addr esses and t el ephone number s f or use i n t he event of an emer gency. As changes occur and addi t i onal i nf or mat i on becomes avai l abl e, cor r ect and change t he i nf or mat i on cont ai ned i n pr evi ous l i s t s.

1. 3. 1. 2 I nst al l at i on Access

Obt ai n access t o Navy i nst al l at i ons t hr ough par t i c i pat i on i n t he Def ense Bi omet r i cs I dent i f i cat i on Syst em ( DBI DS) . Requi r ement s f or Cont r act or empl oyee r egi st r at i on, and t r ansi t i on f or empl oyees cur r ent l y under Navy Commer ci al Access Cont r ol Syst em ( NCACS) , ar e avai l abl e at ht t ps: / / www. cni c. navy. mi l / Oper at i ons- and- Management / Base- Suppor t / DBI DS/ .

No f ees ar e associ at ed wi t h obt ai ni ng a DBI DS cr edent i al .

Par t i c i pat i on i n t he DBI DS i s not mandat or y, and Cont r act or per sonnel may appl y f or One- Day Passes at t he Base Vi s i t or Cont r ol Of f i ce t o access an i nst al l at i on.

1. 3. 1. 2. 1 Regi st r at i on f or DBI DS

Regi st r at i on f or DBI DS i s avai l abl e at ht t ps: / / www. cni c. navy. mi l / Oper at i ons- and- Management / Base- Suppor t / DBI DS/ .

Pr ocedur e i ncl udes:

a. Pr esent a l et t er or of f i c i al awar d document ( i . e. DD For m 1155 or SF 1442) f r om t he Cont r act i ng Of f i cer , t hat pr ovi des t he pur pose f or access, t o t he base Vi s i t or Cont r ol Cent er r epr esent at i ve.

b. Pr esent val i d i dent i f i cat i on, such as a passpor t or Real I D Act - compl i ant st at e dr i ver ' s l i cense.

c. Pr ovi de compl et ed SECNAV FORM 5512/ 1 t o t he base Vi s i t or Cont r ol Cent er r epr esent at i ve t o obt ai n a backgr ound check. Thi s f or m i s avai l abl e f or downl oad at ht t ps: / / www. cni c. navy. mi l / Oper at i ons- and- Management / Base- Suppor t / DBI DS/ .

d. Upon successf ul compl et i on of t he backgr ound check, t he Gover nment

SECTI ON 01 14 00 Page 2 wi l l compl et e t he DBI DS enr ol l ment pr ocess, whi ch i ncl udes Cont r act or empl oyee phot o, f i nger pr i nt s, base r est r i ct i on and sever al ot her assessment s.

e. Upon successf ul compl et i on of t he enr ol l ment pr ocess, t he Cont r act or empl oyee wi l l be i ssued a DBI DS cr edent i al , and wi l l be al l owed t o pr oceed t o wor ksi t e.

1. 3. 1. 2. 2 DBI DS El i gi bi l i t y Requi r ement s

Thr oughout t he l engt h of t he cont r act , t he Cont r act or empl oyee must cont i nue t o meet backgr ound scr een st andar ds. Per i odi c backgr ound scr eeni ngs ar e conduct ed t o ver i f y cont i nued DBI DS par t i c i pat i on and i nst al l at i on access pr i v i l eges. DBI DS access pr i v i l eges wi l l be i mmedi at el y suspended or r evoked i f at any t i me a Cont r act or empl oyee becomes i nel i gi bl e.

An adj udi cat i on pr ocess may be i ni t i at ed when a backgr ound scr een f ai l ur e r esul t s i n di squal i f i cat i on f r om par t i c i pat i on i n t he DBI DS, and Cont r act or empl oyee does not agr ee wi t h t he r eason f or di squal i f i cat i on.

The Gover nment i s t he f i nal aut hor i t y.

1. 3. 1. 2. 3 DBI DS Not i f i cat i on Requi r ement s

a. I mmedi at el y r epor t i nst ances of l ost or st ol en badges t o t he Cont r act i ng Of f i cer .

b. I mmedi at el y col l ect DBI DS cr edent i al s and not i f y t he Cont r act i ng Of f i cer i n wr i t i ng under t he f ol l owi ng ci r cumst ances:

( 1) An empl oyee has depar t ed t he company wi t hout havi ng pr oper l y r et ur ned or sur r ender ed t hei r DBI DS cr edent i al s.

( 2) Ther e i s a r easonabl e basi s t o concl ude t hat an empl oyee, or f or mer empl oyee, mi ght pose a r i sk, compr omi se, or t hr eat t o t he saf et y or secur i t y of t he I nst al l at i on or anyone t her ei n.

1. 3. 1. 2. 4 One- Day Passes

Per sonnel appl y i ng f or One- Day passes at t he Base Vi s i t or Cont r ol Of f i ce ar e subj ect t o dai l y mandat or y vehi c l e i nspect i on, and wi l l have l i mi t ed access t o t he i nst al l at i on. The Gover nment i s not r esponsi bl e f or any cost or l ost t i me associ at ed wi t h obt ai ni ng dai l y passes or added vehi c l e i nspect i ons i ncur r ed by non- par t i c i pant s i n t he DBI DS.

1. 3. 1. 3 No Smoki ng Pol i cy

Smoki ng i s pr ohi bi t ed wi t hi n and out si de of al l bui l di ngs on i nst al l at i on, except i n desi gnat ed smoki ng ar eas. Thi s appl i es t o exi st i ng bui l di ngs, bui l di ngs under const r uct i on, and bui l di ngs under r enovat i on. Di scar di ng t obacco mat er i al s ot her t han i nt o desi gnat ed t obacco r ecept acl es i s consi der ed l i t t er i ng and i s subj ect t o f i nes. The Cont r act i ng Of f i cer wi l l i dent i f y desi gnat ed smoki ng ar eas.

1. 3. 2 Wor ki ng Hour s

Regul ar wor ki ng hour s wi l l consi st of an 8 1/ 2 hour per i od , bet ween 7

a. m. and 3: 30 p. m. , Monday t hr ough Fr i day, excl udi ng Gover nment hol i days.

SECTI ON 01 14 00 Page 3

1. 3. 3 Wor k Out si de Regul ar Hour s

Wor k out si de r egul ar wor ki ng hour s r equi r es Cont r act i ng Of f i cer appr oval .

Make appl i cat i on 15 cal endar days pr i or t o such wor k t o al l ow ar r angement s t o be made by t he Gover nment f or i nspect i ng t he wor k i n pr ogr ess, gi v i ng t he speci f i c dat es, hour s, l ocat i on, t ype of wor k t o be per f or med, cont r act number , and pr oj ect t i t l e. Based on t he j ust i f i cat i on pr ovi ded, t he Cont r act i ng Of f i cer may appr ove wor k out si de r egul ar hour s. Dur i ng per i ods of dar kness, t he di f f er ent par t s of t he wor k must be l i ght ed i n a manner appr oved by t he Cont r act i ng Of f i cer . Make ut i l i t y cut over s af t er nor mal wor ki ng hour s or on Sat ur days, Sundays, and Gover nment hol i days unl ess di r ect ed ot her wi se.

1. 3. 4 Ut i l i t y Cut over s and I nt er r upt i ons

a. Make ut i l i t y cut over s and i nt er r upt i ons af t er nor mal wor ki ng hour s or on Sat ur days, Sundays, and Gover nment hol i days. Conf or m t o pr ocedur es r equi r ed i n par agr aph WORK OUTSI DE REGULAR HOURS.

b. Ensur e t hat new ut i l i t y l i nes ar e compl et e, except f or t he connect i on, bef or e i nt er r upt i ng exi st i ng ser vi ce.

c. I nt er r upt i on t o wat er , sani t ar y sewer , st or m sewer , t el ephone ser vi ce, el ect r i c ser vi ce, ai r condi t i oni ng, heat i ng, f i r e al ar m, compr essed ai r , and st eam ar e consi der ed ut i l i t y cut over s pur suant t o t he par agr aph WORK OUTSI DE REGULAR HOURS.

d. Oper at i on of St at i on Ut i l i t i es: The Cont r act or must not oper at e nor di st ur b t he set t i ng of cont r ol devi ces i n t he st at i on ut i l i t i es syst em, i ncl udi ng wat er , sewer , el ect r i cal , and st eam ser vi ces. The Gover nment wi l l oper at e t he cont r ol devi ces as r equi r ed f or nor mal conduct of t he wor k. The Cont r act or must not i f y t he Cont r act i ng Of f i cer gi v i ng r easonabl e advance not i ce when such oper at i on i s r equi r ed.

e. Connect i on t o Exi st i ng Sani t ar y Sewer Li ne: Pr ovi de posi t i ve ver i f i cat i on t hat t he exi st i ng l i ne conveys sani t ar y sewer ; ver i f y l i ne i s not i ncor r ect l y connect ed t o a st or m dr ai n. Obt ai n I nst al l at i on' s Sani t ar y Sewer Connect i on Per mi t 2 weeks pr i or t o connect i on and i n accor dance wi t h Sect i on 33 30 00 SANI TARY SEWERAGE.

1. 4 SECURI TY REQUI REMENTS

1. 4. 1 St at i on Regul at i ons

No empl oyee or r epr esent at i ve of t he cont r act or wi l l be admi t t ed t o t he wor k s i t e wi t hout an I dent i f i cat i on Badge or i s speci f i cal l y aut hor i zed admi t t ance t o t he wor k s i t e by t he FEAD, Faci l i t i es Engi neer i ng & Acqui s i t i on Di v i s i on.

I MPORTANT NOTE: FEAD per sonnel ( Const r uct i on Manager s, Engi neer s/ Ar chi t ect s, Engi neer i ng Techni c i ans, Cont r act Speci al i st s, or Cont r act Sur vei l l ance Repr esent at i ves) wi l l not r ecei ve, pr ocess, r e- t r ansmi t , or ot her wi se handl e I N ANY WAY Per sonal l y I dent i f i abl e I nf or mat i on ( PI I ) r el at ed t o t he badgi ng pr ocess. Do NOT f or war d any of t hi s i nf or mat i on t o t he FEAD.

SECTI ON 01 14 00 Page 4

1. 4. 2 Cont r act or Access t o MCAS Cher r y Poi nt and Out l y i ng Ar eas

1. Document at i on r equi r ement s f or gr ant i ng access t o MCAS Cher r y Poi nt f or commer ci al and cont r act empl oyer s and empl oyees. Thi s document i s an ai d i n meet i ng ASO 5560. 6B r equi r ement s and i s not a subst i t ut e f or t he or der .

2. The Pass & I dent i f i cat i on Of f i ce at Bui l di ng 251 wi l l i ssue cr edent i al s t o aut hor i zed cont r act or s. Sub- Cont r act or s and suppl i er s must coor di nat e t hr ough t he Pr i me- Cont r act or .

3. Cr i mi nal Act i v i t y. I n accor dance wi t h ASO 5560. 6B, t he bel ow l i s t of cr i mi nal act i v i t i es wi t hi n an appl i cant ' s r ecor d ar e consi der ed not i n t he best i nt er est of t he Mar i ne Cor ps and wi l l be gr ounds f or aut omat i c deni al of access aboar d t he I nst al l at i on:

a. Convi ct i on f or espi onage, sabot age, sedi t i on, t r eason, t er r or i sm, ar med r obber y, or mur der .

b. Fel ony convi ct i on f or a f i r ear ms or expl osi ves v i ol at i on, r egar dl ess of t he dat e of convi ct i on.

c. Convi ct i on of cr i mes encompassi ng sexual assaul t or r ape.

d. Convi ct i on of cr i me encompassi ng chi l d mol est at i on, or t he possessi on or pr oduct i on of chi l d por nogr aphy.

e. Convi ct i on of t r af f i ck i ng i n per sons.

f . Convi ct i on of dr ug possessi on wi t h i nt ent t o sel l or di st r i but e.

g. Convi ct ed of t hr ee or mor e mi sdemeanor v i ol at i ons, or at t empt ed vi ol at i ons, wi t hi n t he pr evi ous 10 year s of t he f ol l owi ng of f enses:

( 1) Sex cr i me

( 2) Assaul t

( 3) Lar ceny

( 4) Dr ugs

( 5) Weapons

4. Per sons r equest i ng access t o MCAS Cher r y Poi nt wi l l be deni ed access based on t he f ol l owi ng:

a. The i ndi v i dual i s a r egi st er ed sex of f ender .

b. The i ndi v i dual has an act i ve ar r est war r ant f r om Feder al , St at e, l ocal , or ot her c i v i l l aw enf or ecement aut hor i t i es, r egar dl ess of of f ense or v i ol at i on.

c. The i ndi v i dual has a f el ony convi ct i on wi t hi n t he l ast 10 year s, r egar dl ess of t he of f ense or v i ol at i on.

d. The i ndi v i dual ' s name appear s on any Feder al or St at e agency wat ch l i s t f or cr i mi nal behavi or or t er r or i st act i v i t y.

SECTI ON 01 14 00 Page 5

e. The i ndi v i dual i s debar r ed ent r y or access t o a Mar i ne Cor ps si t e, ot her DoD i nst al l at i ons or f aci l i t i es, or ot her Feder al s i t e or f aci l i t y .

f . The i ndi v i dual engaged i n act s or act i v i t i es desi gned t o over t hr ow t he U. S. Gover nment by f or ce.

g. The i ndi v i dual i s known t o be or r easonabl y suspect ed of bei ng a t er r or i st or bel ongs t o an or gani zat i on wi t h known t er r or i sm l i nks/ suppor t .

h. The i ndi v i dual i s i dent i f i ed i n t he Nat i onal Cr i me I nf or mat i on Cent er ( NCI C) known suspect ed t er r or i st ( KST) f i l e, or t he Ter r or i st Scr eeni ng Dat abase ( TSDB) r epor t as known t o be, or suspect ed of bei ng, a t er r or i st or bel ongi ng t o an or gani zat i on wi t h known l i nks t o t er r or i sm or suppor t of t er r or i st act i v i t y. I f an i ndi v i dual i s i dent i f i ed on t he NCI C KST f i l es or TSDB, t he Pr ovost Mar shal ' s Of f i ce ( PMO) wi l l i mmedi at el y cal l t he NCI S Mul t i pl e Thr eat Al er t Cent er ( MTAC) f or f ur t her coor di nat i on. The MTAC wi l l coor di nat e wi t h t he Depar t ment of Just i ce or Feder al Bur eau of I nvest i gat i on ( FBI ) and pr ovi de handl i ng i nst r uct i ons t o MCAS Cher r y Poi nt Pol i ce, Cr i mi nal I nvest i gat i ons Di v i s i on ( CI D) , or NCI S.

i . The i ndi v i dual i s i l l egal l y pr esent i n t he U. S.

j . The i ndi v i dual has knowi ngl y submi t t ed an empl oyment quest i onnai r e wi t h f al se or f r audul ent i nf or mat i on.

k. The i ndi v i dual i s a pr i soner on a wor k- r el ease pr ogr am or cur r ent l y on f el ony pr obat i on or par ol e.

l . The i ndi v i dual i s pendi ng any f el ony char ge.

m. The i ndi v i dual has cr i mi nal ar r est i nf or mat i on t hat t he s i t e commander det er mi nes t he per son pr esent s a t hr eat t o good or der , di sci pl i ne, or heal t h and saf et y on t he Mar i ne Cor ps si t e.

n. Any r eason t he I nst al l at i on Commander deems r easonabl e f or good or der and di sci pl i ne.

1. 4. 3 FLEET READI NESS CENTER, EAST ( FRC EAST) REQUI REMENTS

Wor k i nvol ved under t hi s cont r act i s i n t he FRC East Mai nt enance Depot and Fl i ght l i ne Ar ea. No empl oyee or r epr esent at i ve of t he Cont r act or wi l l be admi t t ed t o t he wor k s i t e unl ess t hey ( 1) ar e speci f i cal l y aut hor i zed admi t t ance by t he FEAD, and ( 2) has a secur i t y badge. The Cont r act or shal l obt ai n c l ear ance and FRC East secur i t y badges f or al l per sonnel r equi r ed t o be on t he pr oj ect s i t e pr i or t o per f or mi ng any wor k. The Cont r act or shal l submi t a wr i t t en r equest f or secur i t y badges t o t he FEAD and t o FRC East Secur i t y. Each empl oyee wi l l be r equi r ed t o go t o Tr ai l er 32 t o obt ai n a secur i t y badge wi t h FRC East access. A l i mi t ed number of Cont r act or vehi c l es wi l l be al l owed access t o t he s i t e of wor k subj ect t o meet i ng r egul ar access r equi r ement s. No per sonal vehi c l es wi l l be al l owed behi nd t he secur i t y f ence. Par ki ng of vehi c l es shal l be r est r i ct ed t o t he i mmedi at e pr oj ect s i t e as det er mi ned by t he FRC East Secur i t y. The secur i t y badges i ssued under t hi s cont r act ar e val i d f or t hi s speci f i c pr oj ect and ar e not t r ansf er abl e t o anot her pr oj ect .

FRC East i s r egi st er ed t o t he I SO 9001, AS 9110, I SO 14001, and OSHAS

SECTI ON 01 14 00 Page 6

18001 st andar ds. I n addi t i on t o t hese, r egi st r at i on under t he Occupat i onal Saf et y and Heal t h Admi ni st r at i on' s Vol unt ar y Pr ot ect i on Pr ogr am i s i n pr ogr ess. To adher e t o t he st andar ds r equi r ed of t hese pr ogr ams, FRC East must ensur e t hat al l i ndi v i dual s accessi ng t he f aci l i t y ar e awar e of t he condi t i ons and f act or s t hat af f ect t he wel l - bei ng of al l empl oyees, t empor ar y wor ker s, cont r act or per sonnel , v i s i t or s, and any ot her per son i n t he wor kpl ace.

The f ol l owi ng ar e r equi r ement s f or gr ant i ng access t o Fl eet Readi ness Cent er East ( FRC East ) f or commer ci al and cont r act empl oyer s and empl oyees.

a. The Cont r act or shal l compl et e a " Cont r act or Wor k Not i ce- For m FRC- East 5000/ 10" and pr ovi de t he Not i ce t o t he appr opr i at e shop super vi sor f or s i gnat ur e and l eave t he t op par t of t he Not i ce wi t h t he shop super vi sor t o post i n a pr omi nent l ocat i on i n t he wor k ar ea. The Cont r act or shal l keep t he bot t om por t i on of t he " Cont r act or Wor k Not i ce" f or hi s r ecor ds and pr ovi de a copy t o t he Cont r act i ng Of f i cer . For pr oj ect s occur r i ng on f aci l i t y r oof s ( r oof i ng r epai r , HVAC r epl acement , or s i mi l ar wor k) , t he Cont r act or shal l compl et e a " Cont r act or Wor k Not i ce" f or m and pr ovi de t he Not i ce t o t he shop di r ect l y under t he ar ea bei ng wor ked, even i f no di r ect i mpact t o t he shop i s ant i c i pat ed. A bl ank copy of t hi s f or m i s i ncl uded at t he end of t hi s sect i on.

b. I n t he event of an emer gency, i ncl udi ng hazar dous mat er i al spi l l s , t he i ndi v i dual di scover i ng t he emer gency shal l cal l 911 f r om any FRC East phone. Rel ay t he gr i d number l i s t ed on t he phone f or l ocat i on assi st ance. I f you ar e cal l i ng f r om a cel l phone, cal l 252- 466- 3616 - Fi r e Depar t ment Di spat ch.

c. Badges wi l l be di spl ayed at al l t i mes and shal l be r et ur ned upon compl et i on of v i s i t / wor k. Ever y badge i s consi der ed Gover nment Pr oper t y and al l l ost badges wi l l be r epor t ed t o t he FRC East Badge and Decal Of f i ce l ocat ed i n Tr ai l er 32.

d. The f aci l i t y must be kept c l ean and or der l y at al l t i mes.

Ensur e t hat you pl ace al l wast e i n pr oper r ecept acl es so t hat t he f aci l i t y i s mai nt ai ned i n a " Cl ean as you go" condi t i on.

e. When i n t he FRC East i ndust r i al ar eas, wear t he per sonal pr ot ect i ve equi pment ( PPE) r equi r ed f or t hat ar ea. PPE r equi r ement s ar e gener al l y mar ked but i f t her e i s uncer t ai nt y, check wi t h t he ar ea super vi sor . Typi cal l y, saf et y gl asses wi t h s i de shi el ds and st eel t oed shoes ar e r equi r ed i n most shops.

f . Smoki ng i s NOT aut hor i zed whi l e t r avel i ng f r om one f aci l i t y l ocat i on t o anot her whi l e wal k i ng or i n a vehi c l e bei ng oper at ed anywher e wi t hi n t he FRC East compound. ABSOLUTELY NO SMOKI NG on t he pr oper t y except i n Desi gnat ed Smoki ng Ar eas.

g. Ext r a caut i on shal l be t aken ar ound t he f l i ght l i ne and ai r cr af t t ur n- up ar eas t o cont r ol t r ash, debr i s, and mat er i al s.

Addi t i onal l y, al l per sonnel on t he f l i ght l i ne must be cont i nuousl y al er t and st ay c l ear of hel i copt er and j et oper at i ons i n pr ogr ess.

h. Vehi c l es must not obst r uct ai r cr af t movement or ot her dai l y oper at i ons.

SECTI ON 01 14 00 Page 7 i . I f an emer gency si t uat i on occur s whi ch woul d endanger t he heal t h or saf et y of per sonnel , t he ar ea shal l be evacuat ed.

Re- ent r y t o af f ect ed bui l di ngs wi l l be at t he di scr et i on of uni f or med guar ds, f i r e depar t ment , or saf et y of f i ce per sonnel onl y.

j . Deci s i ons t o evacuat e wi l l be f r om t he FRC East Commandi ng Of f i cer or hi s/ her r epr esent at i ve. Vi s i t or s/ cont r act or s, al ong wi t h non- essent i al f aci l i t y per sonnel , sout h of Har r i son Dr i ve, adj acent t o Bui l di ng 4224, wi l l evacuat e t he f aci l i t y f i r st .

Fi f t een mi nut es l at er , t he v i s i t or s/ cont r act or s sout h of Cur t i s Road, bet ween Bui l di ngs 83 & 84, wi l l evacuat e t he f aci l i t y .

Fi f t een mi nut es l at er t he v i s i t or s/ cont r act or s nor t h of Cur t i s Road wi l l evacuat e t he f aci l i t y .

k. Cel l ul ar phones and phot ogr aphi c equi pment ar e not aut hor i zed wi t hi n FRC East unl ess t hey ar e appr oved i n advance by t he Secur i t y Of f i ce ( 252- 464- 7999) . Cel l ul ar phones may be used on r oof ar eas f or emer gency pur poses onl y.

l . Al l vehi c l es must have pr oper passes, and no pass may be t r ansf er r ed bet ween vehi c l es.

m. Al l vehi c l es wi l l f ol l ow post ed speed l i mi t s, whi ch ar e: " Do not exceed 5 MPH on t he out si de of bui l di ngs, nor 3 MPH i nsi de of any bui l di ng" .

n. Vehi c l e headl i ght s must be on at al l t i mes wi t hi n t he f aci l i t y .

o. Al l vehi c l es ar e r equi r ed t o s l ow down, sound hor n, and pr oceed wi t h caut i on at al l cr oss ai s l es and ot her l ocat i ons wher e vi s i on i s obst r uct ed.

p. Per sonnel ar e st r i ct l y f or bi dden t o i nt r oduce any subst ance i nt o t he st or m dr ai n syst em i ncl udi ng cat ch basi ns, r oof dr ai ns, and f l oor dr ai ns.

q. Al l f aci l i t y ent r ant s ar e r esponsi bl e f or al l mat er i al s t hey br i ng i nt o t he f aci l i t y and shal l handl e t hem i n such a manner t o ensur e t hey ar e not l ef t as " f or ei gn obj ect s" anywher e i n t he f aci l i t y .

r . I n case of a ut i l i t y emer gency on weekends or af t er nor mal wor k hour s, cal l t he Publ i c Wor ks Depar t ment t r oubl e cal l desk at 252- 466- 4363.

s. The use of gasol i ne i s pr ohi bi t ed f or any pur pose ot her t han f uel i ng mot or vehi c l es. Al l gasol i ne- power ed vehi c l es ar e pr ohi bi t ed i nsi de FRC East bui l di ngs.

1. 4. 4 Mandat or y Cont r act Per f or mance Requi r ement s f or FRC East

a. Al l per sonnel wor ki ng on si t e at FRC East under t hi s cont r act must document t hei r r ecei pt and r evi ew of t he i nf or mat i on l i s t ed i n FRCEASTI NST 5000. 1A annual l y. The Secur i t y Depar t ment wi l l pr ovi de a means of compl et i ng i ni t i al r evi ew pr i or t o FRC East ent r ance.

b. For ei gn obj ect ( FO) i s def i ned as any ar t i c l e or subst ance al i en t o t he ai r cr af t or assembl y whi ch i s al l owed t o i nvade t he

SECTI ON 01 14 00 Page 8 pr oduct . For ei gn Obj ect Damage ( FOD) i s t he damage t hat occur s due t o t hese FOs. Al l FRC East wor k s i t es wi l l be mai nt ai ned i n such a manner as t o pr event FOD t o ai r cr af t and/ or ai r cr af t component s. Wor k s i t es shal l be kept c l ean at al l t i mes. Al l debr i s, scr ap mat er i al , t ool s, and equi pment wi l l be c l ear ed f r om t he wor k s i t e as wor k pr ogr esses. At no t i me wi l l hoses, power cor ds, mat er i al s, et c. be per mi t t ed t o cr eat e t r i ppi ng hazar ds i n ar eas of t he wor k s i t e.

c. I n t hose cases wher e a cont r act or super vi sor det er mi nes t hat sol v i ng a saf et y or heal t h pr obl em i s beyond t hei r cont r ol , but wi t hi n t he cont r ol of FRC East , t he cont r act or shal l not i f y t he Cont r act i ng Of f i cer .

d. Al l cont r act or empl oyees per f or mi ng wor k on si t e at FRC East shal l i mmedi at el y r epor t any saf et y, secur i t y, or envi r onment al v i ol at i on t o t he Cont r act i ng Of f i cer , who wi l l not i f y t he cogni zant FRC East Saf et y/ Secur i t y/ Envi r onment al Of f i ce. The i ni t i al FRC East not i f i cat i on can be made vi a phone or e- mai l and shoul d i ncl ude as many appl i cabl e det ai l s as possi bl e ( dat e, t i me, i dent i f i cat i on number s, t ags, company, et c. ) . Thi s i ni t i al not i f i cat i on wi l l be made as soon as possi bl e. A saf et y i nci dent wi l l r equi r e t he cont r act or t o compl et e and submi t an i nci dent memo t o t he Cont r act i ng Of f i cer , who wi l l f or war d a copy t o t he FRC Saf et y Of f i ce wi t hi n 24 hour s of t he acci dent / i nci dent . Thi s i nci dent memo wi l l i ncl ude t he f ul l name of t he per son i nvol ved i n t he i nci dent , t hei r age, sex, j ob t i t l e, t he name of t he empl oyi ng company, and t he cont r act number / t i t l e. I n addi t i on, t hi s memo wi l l i ncl ude t he sever i t y of t he i l l ness or i nj ur y, i ndi r ect cause( s) of t he acci dent , and whet her per sonal pr ot ect i ve equi pment was avai l abl e and used.

e. Al l cont r act or s and sub- cont r act or s wor ki ng wi t hi n FRC East must devel op and oper at e ef f ect i ve saf et y and heal t h pr ogr ams.

1. 4. 4. 1 Addi t i onal Cont r act Per f or mance Requi r ement s f or FRC East

a. Wor k above or anywher e near ai r cr af t or passageways shal l be avoi ded whenever possi bl e. I f t hi s i s not possi bl e, t he cogni zant shop super vi sor wi l l be i nf or med so ar r angement s can be made t o pr ot ect , move, or evacuat e asset s f r om t he ar ea t o mi ni mi ze f or ei gn obj ect debr i s pot ent i al . The ar ea bel ow t he el evat ed wor k ar ea wi l l be adequat el y mar ked and bar r i caded at al l t i mes. Under no ci r cumst ances wi l l wor k be per f or med over unpr ot ect ed spaces.

b. Const ant cont r ol of t ool s and mat er i al s i s r equi r ed at al l t i mes i n t he f ol l owi ng cr i t i cal ar eas: Shop 94304 ( Rot or Head Shop) ; Shop 94601 ( Or di nance/ Sur vi val Shop) ; Shop 93117 ( Ai r cr af t Pai nt Shop) ; Shop 93111 ( Ai r cr af t Cl ean Shop) ; Shop 96552, 96555, and 96556 ( Ai r cr af t Engi ne Shops) ; al l shops i n Bui l di ng 4225 ( Bl ade Vane) ; and al l Shop 95000 Ai r cr af t Hangar s.

c. Bui l di ngs 131, 137, 188, 245, 4224, and 4247 ar e c l assi f i ed as hazar dous ar eas and have speci al r equi r ement s. Do not ut i l i ze any i gni t abl e i t ems power ed by el ect r i c mot or s or i nt er nal combust i on engi nes unl ess t hey ar e det er mi ned t o be sui t abl e t o t he condi t i ons of t he bui l di ngs.

d. The r echar gi ng of mobi l e equi pment shal l not t ake pl ace i nsi de

SECTI ON 01 14 00 Page 9 any FRC- East bui l di ng.

e. Tool s and har dwar e wi l l be cont r ol l ed at al l t i mes t o pr event mi gr at i on out of t he wor k s i t e. Lost t ool s shal l be r epor t ed t o t he Cont r act i ng Of f i cer who wi l l t hen not i f y t he FRC East Tool Cont r ol Manager at 252- 464- 9741. Tool s f ound unat t ended wi l l be conf i scat ed and r epor t ed t o t he Cont r act i ng Of f i cer .

f . Per sonnel wor ki ng on t he f l i ght l i ne must be cont i nuousl y al er t , and st ay c l ear of hel i copt er and j et oper at i ons i n pr ogr ess.

g. Wor k r equi r i ng any modi f i cat i on t o an ai r pol l ut i on cont r ol devi ce must be appr oved i n advance by t he Cont r act i ng Of f i cer , who wi l l obt ai n appr oval f r om t he FRC East Ai r Qual i t y Pr ogr am Manager . These devi ces ar e mar ked wi t h a 5" x 9" r ed pl acar d and a cont act number , 252- 464- 7264.

h. Wor k accompl i shed t hat wi l l i mpact i ndust r i al vent i l at i on syst ems or f ans wi l l r equi r e pr i or not i f i cat i on of t he Cont r act i ng Of f i cer , who wi l l t hen not i f y t he FRC East Ai r Qual i t y Pr ogr am Manager at 252- 464- 7264. These syst ems ar e cont i nuousl y moni t or ed.

1. 4. 5 St agi ng Ar ea

As i ndi cat ed on t he pl ans, t he Cont r act or st agi ng ar ea wi l l be ( CM t o coor di nat e) . Amount of mat er i al on s i t e shal l be kept t o a mi ni mum and shal l onl y be mat er i al t hat i s per t i nent t o t he wor k cur r ent l y bei ng per f or med. Al l st ockpi l i ng of equi pment and mat er i al s shal l be c l osel y coor di nat ed wi t h t he Gover nment and shal l not di sr upt act i v i t i es at t he s i t e.

PART 2 PRODUCTS

Not Used

PART 3 EXECUTI ON

Not Used

SECTI ON 01 14 00 Page 10

SECTI ON 01 20 00

PRI CE AND PAYMENT PROCEDURES

11/ 20, CHG 3: 02/ 23

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

U. S. ARMY CORPS OF ENGI NEERS ( USACE)

EP 1110- 1- 8 ( 2021) Engi neer i ng and Desi gn - - Const r uct i on Equi pment Owner shi p and Oper at i ng Expense Schedul e

1. 2 SUBMI TTALS

Gover nment appr oval i s r equi r ed f or al l submi t t al s. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

Ear ned Val ue Repor t

1. 3 EARNED VALUE REPORT

1. 3. 1 Dat a Requi r ed

Thi s Cont r act r equi r es t he use of a cost - l oaded Net wor k Anal ysi s Schedul e ( NAS) . Schedul e of Pr i ces must not be used wi t h cost - l oaded Net wor k Anal ysi s Schedul e ( NAS) . Use Ear ned Val ue Repor t der i ved f r om cost - l oaded NAS. Wi t hi n 15 cal endar days of Cont r act Awar d, pr epar e and del i ver t o t he Cont r act i ng Of f i cer a Ear ned Val ue Repor t ( const r uct i on Cont r act ) as di r ect ed by t he Cont r act i ng Of f i cer . Pr ovi de a det ai l ed br eakdown of t he Cont r act pr i ce, gi v i ng quant i t i es f or each of t he var i ous k i nds of wor k, uni t pr i ces and ext ended pr i ces. Cont r act or over head and pr of i t i ncl udi ng sal ar i es f or f i el d of f i ce per sonnel , i f appl i cabl e, must be pr opor t i onat el y spr ead over al l pay i t ems and not i ncl uded as i ndi v i dual pay i t ems.

1. 3. 2 Payment Schedul e I nst r uct i ons

Payment s wi l l not be made unt i l t he Schedul e of Pr i cesEar ned Val ue Repor t f r om t he cost - l oaded NAS has been submi t t ed t o and accept ed by t he Cont r act i ng Of f i cer .

Addi t i onal l y, t he Ear ned Val ue Repor t must be separ at ed as f ol l ows:

a. Pr i mar y Faci l i t i es Cost Br eakdown:

Def i ned as wor k on t he pr i mar y f aci l i t i es out t o t he 5 f oot l i ne.

Wor k out t o t he 5 f oot l i ne i ncl udes const r uct i on encompassed wi t hi n a t heor et i cal l i ne 5 f oot f r om t he f ace of ext er i or wal l s and i ncl udes at t endant const r uct i on, such as pad mount ed HVAC cool i ng equi pment , SECTI ON 01 20 00 Page 1 cool i ng t ower s, and t r ansf or mer s pl aced beyond t he 5 f oot l i ne.

b. Suppor t i ng Faci l i t i es Cost Br eakdown:

Def i ned as s i t e wor k, i ncl udi ng i nci dent al wor k, out s i de t he 5 f oot l i ne.

1. 3. 3 Schedul e Requi r ement s f or HVAC TAB

The f i el d wor k r equi r ement s i n Sect i on 23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC must be br oken down i n t he Ear ned Val ue Repor t f r om t he cost - l oaded NAS by separ at e l i ne i t ems whi ch r ef l ect measur abl e del i ver abl es. The val ue f or each pay i t em l i st ed bel ow wi l l be est abl i shed on a case by case basi s f or each Cont r act . The l i ne i t ems ar e as f ol l ows:

a. Appr oval of Desi gn Revi ew Repor t : The TABS Agency i s r equi r ed t o conduct a r evi ew of t he pr oj ect pl ans and speci f i cat i ons t o i dent i f y any f eat ur e, or t he l ack t her eof , t hat woul d pr ecl ude successf ul t est i ng and bal anci ng of t he pr oj ect HVAC syst ems. Submi t t he r esul t i ng f i ndi ngs t o t he Gover nment t o al l ow cor r ect i on of t he desi gn. The pr ogr ess payment wi l l not be i ssued unt i l t he r epor t i s r evi ewed and appr oved.

b. Appr oval of t he pr e- f i el d engi neer i ng r epor t : The TABS Agency submi t s a r epor t whi ch out l i nes t he scope of f i el d wor k. The r epor t must cont ai n det ai l s of what syst ems wi l l be t est ed, pr ocedur es t o be used, sampl e r epor t f or ms f or r epor t i ng t est r esul t s and a qual i t y cont r ol checkl i st of wor k i t ems t hat must be compl et ed bef or e TABS f i el d wor k commences.

c. Season I f i el d wor k: I ncr ement al payment s ar e i ssued as t he TABS f i el d wor k pr ogr esses. The TABS Agency mobi l i zes t o t he pr oj ect s i t e and execut es t he f i el d wor k as out l i ned i n t he pr e- f i el d engi neer i ng r epor t . The HVAC wat er and ai r syst ems ar e bal anced and oper at i onal dat a must be col l ect ed f or one seasonal condi t i on ( ei t her summer or wi nt er dependi ng on pr oj ect t i mi ng) .

d. Appr oval of Season I r epor t : On compl et i on of t he Season I f i el d wor k, t he dat a i s compi l ed i nt o a r epor t and submi t t ed t o t…