7-Attachment A4. Extracted pages from 754578-051 N.pdf

PDF 271 KB Posted

Attached to
Generator Installation at Tallahassee Animal Service Center
Solicitation number
IFB-070-26-KM
Issued by
Leon County, Florida

About this file

This is a technical drawing specification document for ASCO Power Technologies related to an automatic transfer switch system with a 1000-1200 ampere rating, Type 3R/3RX enclosure (96 x 41 x 62 inches), designed for the City of Tallahassee Animal Service Center generator installation project in Tallahassee, Florida. The drawing (Document No. 754578-051, Revision SV, dated 09-26-25) provides comprehensive technical specifications for a floor-mounted electrical enclosure featuring a Square "D" RJF circuit breaker with ground fault protection and H-frame automatic/non-automatic transfer switch capabilities. The system accommodates both normal (Source 1) and emergency (Source 2) power sources with full-rated neutral connections available in solid, switched, or overlapping neutral pole configurations. The enclosure is constructed from code gauge steel with ANSI 61 gray polyester semi-gloss electrostatic powder finish for Type 3R units, or Type 304 or 316 stainless steel for Type 3RX units, and includes padlockable exterior doors with three-point latches designed for front and rear access.

The technical specifications detail termination requirements for 1000-1200 ampere systems supporting (4) 1/0-600MCM copper or aluminum cable per phase and neutral for all three sources (Source 1 Normal, Source 2 Emergency, and Load), with (12) 1/0-600MCM ground connections. Manufacturing tolerances conform to ASCO Procedure MP-I-003, with all bus constructed from silver-plated copper based on 1000 amperes per square inch density. The system is rated for 50,000 RMS symmetrical short circuit amperes at 240V and 480V for Source 1, and across 240V, 480V, and 600V for Source 2, with 25,000 RMS symmetrical at 600V for Source 1. The enclosure has an approximate weight of 2,050 pounds and includes lifting plates for proper handling, with recommended clearances of 36 inches front and 30 inches rear. Exterior vents with polyester dust filters are supplied for the 1200A configuration only.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASCO ®

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text

MANUFACTURING TOLERANCES TO BE IN

AutoCAD SHX Text

ACCORDANCE WITH ASCO PROCEDURE MP-I-003.

AutoCAD SHX Text

FOR PLASTIC PARTS SEE MP-I-055

AutoCAD SHX Text

PROJECT

AutoCAD SHX Text

APPROVAL

AutoCAD SHX Text

APPROVAL

AutoCAD SHX Text

FINAL

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

CHECKED

AutoCAD SHX Text

BY

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NAME:

AutoCAD SHX Text

ECN NO.

AutoCAD SHX Text

ECN

AutoCAD SHX Text

NO.

AutoCAD SHX Text

COMPUTER GENERATED DRAWING

AutoCAD SHX Text

ASSEM. REF. NO.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

DWG. NO.

AutoCAD SHX Text

DRAWING

AutoCAD SHX Text

REV.

AutoCAD SHX Text

DS

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

PROJECTION

AutoCAD SHX Text

THIRD ANGLE

AutoCAD SHX Text

REV. TO

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

BY

AutoCAD SHX Text

APP.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROPERTY OF ASCO POWER TECHNOLOGIES. USE PERMITTED FOR OUR

AutoCAD SHX Text

WORK ONLY. ALL RIGHTS OF DESIGN OR INVENTION ARE RESERVED.

AutoCAD SHX Text

ASCO P

AutoCAD SHX Text

OWER

AutoCAD SHX Text T

AutoCAD SHX Text

ECHNOLOGIES, L.P.

AutoCAD SHX Text

FLORHAM PARK, NEW JERSEY 07932 U.S.A.

AutoCAD SHX Text 1/16" = 1"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text 319020

AutoCAD SHX Text 754578-051

AutoCAD SHX Text

SV

AutoCAD SHX Text 09-26-25

AutoCAD SHX Text

JPB

AutoCAD SHX Text 09-26-25

AutoCAD SHX Text

OUTLINE

AutoCAD SHX Text

MOUNTING

AutoCAD SHX Text

HAUS 1000A-1200A, RJF SE BREAKER

AutoCAD SHX Text

TYPE 3R/3RX, 96 X 41 X 62

AutoCAD SHX Text 32.6

AutoCAD SHX Text 32.6

AutoCAD SHX Text [827.9]

AutoCAD SHX Text

INTERFACE

AutoCAD SHX Text

USER

AutoCAD SHX Text

CONTROLLER

AutoCAD SHX Text 16.00

AutoCAD SHX Text 16.00

AutoCAD SHX Text [406.40]

AutoCAD SHX Text 41.00

AutoCAD SHX Text 41.00

AutoCAD SHX Text [1041.40]

AutoCAD SHX Text 29.00

AutoCAD SHX Text 29.00

AutoCAD SHX Text [736.60]

AutoCAD SHX Text 12.00

AutoCAD SHX Text 12.00

AutoCAD SHX Text [304.80]

AutoCAD SHX Text 62.00

AutoCAD SHX Text 62.00

AutoCAD SHX Text [1574.80]

AutoCAD SHX Text

CONDUIT AREA

AutoCAD SHX Text

BOTTOM

AutoCAD SHX Text F R O N T

AutoCAD SHX Text R E A R

AutoCAD SHX Text 6.00

AutoCAD SHX Text 6.00

AutoCAD SHX Text

%%UPLAN VIEW

AutoCAD SHX Text 12.00

AutoCAD SHX Text 12.00

AutoCAD SHX Text [304.80]

AutoCAD SHX Text 2.50

AutoCAD SHX Text 2.50

AutoCAD SHX Text 3.13

AutoCAD SHX Text 3.13

AutoCAD SHX Text [79.38]

AutoCAD SHX Text 36.00

AutoCAD SHX Text 36.00

AutoCAD SHX Text [914.47]

AutoCAD SHX Text

OPTIONAL ERMS SWITCH

AutoCAD SHX Text

SOURCE 2 (EMERGENCY)

AutoCAD SHX Text 3.13

AutoCAD SHX Text 3.13

AutoCAD SHX Text [79.38]

AutoCAD SHX Text

.63 [15.88] MOUNTING HOLES 4 PLACES4 PLACES

AutoCAD SHX Text

%%ULEFT SIDE VIEW

AutoCAD SHX Text

%%UWITHOUT COVER

AutoCAD SHX Text

%%UWITHOUT COVER

AutoCAD SHX Text

%%UFRONT VIEW

AutoCAD SHX Text 52U

AutoCAD SHX Text

LOAD

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text N

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

(WITH SWITCHED/OVERLAPPING NEUTRAL)

AutoCAD SHX Text

(WITH SOLID NEUTRAL)

AutoCAD SHX Text

JUMPER

AutoCAD SHX Text

%%UONE LINE DIAGRAMS

AutoCAD SHX Text

GROUND

AutoCAD SHX Text L

AutoCAD SHX Text

TRANSFER

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text

DISCONNECT

AutoCAD SHX Text

LINK

AutoCAD SHX Text

NEUTRAL

AutoCAD SHX Text

BONDING

AutoCAD SHX Text S1N

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

LN

AutoCAD SHX Text S2N

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text

TRANSFER

AutoCAD SHX Text

AutoCAD SHX Text S1(N)

AutoCAD SHX Text L

AutoCAD SHX Text

NEUTRAL

AutoCAD SHX Text S2(E)

AutoCAD SHX Text

(EMERGENCY)

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

DISCONNECT

AutoCAD SHX Text

LINK

AutoCAD SHX Text

BONDING

AutoCAD SHX Text

JUMPER

AutoCAD SHX Text

LOAD

AutoCAD SHX Text U

AutoCAD SHX Text

AUTOMATIC

AutoCAD SHX Text

AUTOMATIC

AutoCAD SHX Text

SOURCE 2

AutoCAD SHX Text

(EMERGENCY)

AutoCAD SHX Text

SOURCE 2

AutoCAD SHX Text

(NORMAL)

AutoCAD SHX Text

SOURCE 1

AutoCAD SHX Text

(NORMAL)

AutoCAD SHX Text

SOURCE 1

AutoCAD SHX Text S1(N)

AutoCAD SHX Text S2(E)

AutoCAD SHX Text

%%USECTION 1T

AutoCAD SHX Text

%%USYSTEM NOTES

AutoCAD SHX Text

1. SYSTEM RATING: 1000 AMPS, 1200 AMPS.

AutoCAD SHX Text

5. APPLICABLE LABEL(S): U.L. 891, SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT.

AutoCAD SHX Text

2. ALL BUS IS SILVER-PLATED COPPER, BASED ON 1000A PER SQ. IN. DENSITY.

AutoCAD SHX Text

4. NEUTRAL: 100%%% RATED.

AutoCAD SHX Text

3. GROUND: AS PER NEC.

AutoCAD SHX Text

3. A FULL RATED NEUTRAL CONNECTION FOR EACH SOURCE AND THE LOAD IS OPTIONAL.

AutoCAD SHX Text

WHEN PROVIDED IT IS IN ONE OF THE FOLLOWING FORMATS.

AutoCAD SHX Text

A. SOLID NEUTRAL

AutoCAD SHX Text

C. OVERLAPPING NEUTRAL POLE (NOT AVAILABLE ON ADTS, ACTS, NDTS & NCTS UNITS)

AutoCAD SHX Text

B. SWITCHED NEUTRAL POLE

AutoCAD SHX Text

%%UTRANSFER SWITCH

AutoCAD SHX Text

1. H FRAME AUTOMATIC/NON-AUTOMATIC TRANSFER SWITCH.

AutoCAD SHX Text

2. TRANSFER SWITCH RATING: 1000 AMPS, 1200 AMPS.

AutoCAD SHX Text

4. UL 1008 OR CSA C22.2 No. 178.1

AutoCAD SHX Text

%%UTERMINATIONS 1000A-1200A

AutoCAD SHX Text

1. SWITCH CAN BE SUPPLIED WITHOUT LUGS (SEE SHEET 2).

AutoCAD SHX Text

A. SOURCES, LOAD AND GROUND LUG KITS ARE ORDERED SEPARATELY.

AutoCAD SHX Text

2. MECHANICAL (SCREW TYPE) LUGS FOR COPPER (CU) OR ALUMINUM (AL) CABLE

AutoCAD SHX Text

A. SUITABLE WIRE BENDING SPACE IS PROVIDED AS PER NEC.

AutoCAD SHX Text

SOURCE 2 (EMERGENCY): (4) 1/0-600MCM PER PHASE & NEUTRAL

AutoCAD SHX Text

LOAD: (4) 1/0-600MCM PER PHASE & NEUTRAL

AutoCAD SHX Text

SOURCE 1 (NORMAL): (4) 1/0-600MCM PER PHASE & NEUTRAL

AutoCAD SHX Text

GROUND: (12) 1/0-600MCM

AutoCAD SHX Text

%%UCIRCUIT BREAKER: ITEM 52U

AutoCAD SHX Text

1. SQUARE "D" 80%%% RATED, TYPE 'RJF', 3000AF/1000AT OR 3000AF/1200AT STATIONARY

AutoCAD SHX Text

GROUND FAULT TRIP SETTINGS.

AutoCAD SHX Text

2. OPTIONAL ENERGY REDUCTION MAINTENANCE SETTING SYSTEM AVAILABLE UPON REQUEST.

AutoCAD SHX Text

MOUNTED, MANUALLY OPERATED WITH LONG DELAY, SHORT DELAY, INSTANTANEOUS AND

AutoCAD SHX Text

%%UWIRING/CABLING

AutoCAD SHX Text

4. U.L. 489

AutoCAD SHX Text

3. OPTIONAL 100%%% RATED AVAILABLE UPON REQUEST.

AutoCAD SHX Text

2. WIRE SIZE TO BE BASED ON AMPACITY OF 75°C WIRE.

AutoCAD SHX Text

3. USE 60°C MINIMUM CU WIRE FOR CONTROLS.

AutoCAD SHX Text

FOR 80%%% RATED BREAKER - USE 75°C MINIMUM CU/AL WIRE FOR POWER CABLES.

AutoCAD SHX Text

%%USOURCE 2 (EMERGENCY)

AutoCAD SHX Text

2. USE 60°C MINIMUM CU WIRE FOR CONTROLS.

AutoCAD SHX Text

1. USE 75°C MINIMUM CU/AL FOR POWER CABLES.

AutoCAD SHX Text

DIMENSION ARE IN INCHES [MILLIMETERS]

AutoCAD SHX Text

14 AWG

AutoCAD SHX Text 2.5mm²

AutoCAD SHX Text

6 AWG

AutoCAD SHX Text

4 AWG

AutoCAD SHX Text

1/0 AWG

AutoCAD SHX Text

2/0 AWG

AutoCAD SHX Text

3/0 AWG

AutoCAD SHX Text 16mm²

AutoCAD SHX Text 25mm²

AutoCAD SHX Text 50mm²

AutoCAD SHX Text 70mm²

AutoCAD SHX Text 95mm²

AutoCAD SHX Text

4/0 AWG

AutoCAD SHX Text 120mm²

AutoCAD SHX Text 120mm²

AutoCAD SHX Text 150mm²

AutoCAD SHX Text 185mm²

AutoCAD SHX Text

250 MCM

AutoCAD SHX Text

300 MCM

AutoCAD SHX Text

350 MCM

AutoCAD SHX Text

400 MCM

AutoCAD SHX Text

500 MCM

AutoCAD SHX Text

600 MCM

AutoCAD SHX Text

750 MCM

AutoCAD SHX Text 240mm²

AutoCAD SHX Text 240mm²

AutoCAD SHX Text 300mm²

AutoCAD SHX Text 400mm²

AutoCAD SHX Text

TABLE 1

AutoCAD SHX Text

SEE TABLE 1 FOR METRIC TERMINATIONS

AutoCAD SHX Text

%%USOURCE 1 (NORMAL) & LOAD

AutoCAD SHX Text

1. FOR 100%%% RATED BREAKER - USE 90°C MINIMUM CU/AL WIRE FOR POWER CABLES.

AutoCAD SHX Text

GFCT

AutoCAD SHX Text H1

AutoCAD SHX Text H2

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text

AutoCAD SHX Text U

AutoCAD SHX Text

%%USECTION 1T

AutoCAD SHX Text

GFCT

AutoCAD SHX Text H1

AutoCAD SHX Text H2

AutoCAD SHX Text

SHORT CIRCUIT RATING:

AutoCAD SHX Text

SOURCE 1 (NORMAL)

AutoCAD SHX Text

%%UFRONT VIEW

AutoCAD SHX Text 41.00

AutoCAD SHX Text 41.00

AutoCAD SHX Text [1041.40]

AutoCAD SHX Text 95.43

AutoCAD SHX Text 95.43

AutoCAD SHX Text [2423.81]

AutoCAD SHX Text

CG

AutoCAD SHX Text 19.5

AutoCAD SHX Text 19.5

AutoCAD SHX Text [495.3]

AutoCAD SHX Text 47.5

AutoCAD SHX Text 47.5

AutoCAD SHX Text [1206.5]

AutoCAD SHX Text

%%U"RIGHT SIDE VIEW"

AutoCAD SHX Text F R O N T

AutoCAD SHX Text R E A R

AutoCAD SHX Text

CG

AutoCAD SHX Text OPTIONAL POWERMANAGER OWERMANAGER MANAGER ANAGER OR ADDITIONAL OPERATOR CONTROLS ESCUTCHEON MOUNTING

AutoCAD SHX Text

%%USECTION 1T

AutoCAD SHX Text

%%USECTION 1

AutoCAD SHX Text 52U

AutoCAD SHX Text

ON

AutoCAD SHX Text

OFF

AutoCAD SHX Text

ERMS

AutoCAD SHX Text 25.9

AutoCAD SHX Text 25.9

AutoCAD SHX Text [657.3]

AutoCAD SHX Text

%%UWITHOUT DOORS

AutoCAD SHX Text

%%UFRONT VIEW

AutoCAD SHX Text 18.00

AutoCAD SHX Text 18.00

AutoCAD SHX Text [457.20]

AutoCAD SHX Text 41.00

AutoCAD SHX Text 41.00

AutoCAD SHX Text [1041.40]

AutoCAD SHX Text 29.00

AutoCAD SHX Text 29.00

AutoCAD SHX Text [736.60]

AutoCAD SHX Text 12.00

AutoCAD SHX Text 12.00

AutoCAD SHX Text [304.80]

AutoCAD SHX Text 62.00

AutoCAD SHX Text 62.00

AutoCAD SHX Text [1574.80]

AutoCAD SHX Text

CONDUIT AREA

AutoCAD SHX Text

TOP

AutoCAD SHX Text F R O N T

AutoCAD SHX Text R E A R

AutoCAD SHX Text 6.00

AutoCAD SHX Text 6.00

AutoCAD SHX Text

%%UTOP VIEW

AutoCAD SHX Text 18.00

AutoCAD SHX Text 18.00

AutoCAD SHX Text [457.20]

AutoCAD SHX Text 12.00

AutoCAD SHX Text 12.00

AutoCAD SHX Text [304.80]

AutoCAD SHX Text

CONDUIT AREA

AutoCAD SHX Text

TOP

AutoCAD SHX Text 62.00

AutoCAD SHX Text 62.00

AutoCAD SHX Text [1574.85]

AutoCAD SHX Text

1. FLOOR MOUNTED ENCLOSURE.

AutoCAD SHX Text

%%UGENERAL NOTES

AutoCAD SHX Text

4. RECOMMENDED CLEARANCES: FRONT: 36 [914.4] REAR: 30 [762].

AutoCAD SHX Text

2. EXTERIOR DOOR HAVE PADLOCKABLE HANDLES WITH 3-POINT LATCH

AutoCAD SHX Text

FINISH: ANSI 61 GRAY POLYESTER SEMI GLOSS ELECTROSTATIC POWDER.

AutoCAD SHX Text

TYPE 3R (M) CONSTRUCTED FROM CODE GAUGE STEEL.

AutoCAD SHX Text

3. DESIGNED FOR FRONT & REAR ACCESS.

AutoCAD SHX Text

7. SECTION 1 & SECTION 1T SHIP AS 1 UNIT.

AutoCAD SHX Text

8. CENTER OF GRAVITY.

AutoCAD SHX Text

9. APPROXIMATE WEIGHT: 2050 LBS [930 KG].

AutoCAD SHX Text

TYPE 3RX (R) EXTERIOR CONSTRUCTED FROM CODE GAUGE TYPE 304 STAINLESS STEEL.

AutoCAD SHX Text

TYPE 3RX (S) EXTERIOR CONSTRUCTED FROM CODE GAUGE TYPE 316 STAINLESS STEEL.

AutoCAD SHX Text

6. LIFTING PLATES: SECTIONS ARE SUPPLIED WITH LIFTING PLATES. INSPECT PLATES FOR DAMAGE

AutoCAD SHX Text PROPER HANDLING OF EQUIPMENT. AFTER INSTALLATION OF SECTION, REMOVE LIFTING PLATES.

AutoCAD SHX Text AND TORQUE BOLTS TO 45 FT LBS [61 N m] BEFORE USE. REFER TO ANSI/NEMA PB 2.1 FOR

AutoCAD SHX Text REINSTALL BOLTS INTO EXTERIOR HOLES AND TORQUE TO APPROXIMATELY 20 FT LBS [27 N m].

AutoCAD SHX Text

5. EXTERIOR VENTS: 1000A: NO VENTS,

AutoCAD SHX Text

1200A: VENTS ARE SUPPLIED WITH POLYESTER DUST FILTERS.

AutoCAD SHX Text L

AutoCAD SHX Text

SEE ECN

AutoCAD SHX Text 306943

AutoCAD SHX Text

MCH

AutoCAD SHX Text

SG

AutoCAD SHX Text 12/28/23

AutoCAD SHX Text

WHEN ORDERED WITH SWITCH.

AutoCAD SHX Text M

AutoCAD SHX Text

SEE ECN

AutoCAD SHX Text 317803

AutoCAD SHX Text

SV

AutoCAD SHX Text

SV

AutoCAD SHX Text 09-26-25

AutoCAD SHX Text SOURCE 2 (EMERGENCY) - REFER TO RATING LABEL ON TRANSFER SWITCH FOR ADDITIONAL RATINGS.

AutoCAD SHX Text

SOURCE 1 (NORMAL) : 50,000 RMS SYM @ 240V, 480V.

AutoCAD SHX Text

25,000 RMS SYM @ 600V.

AutoCAD SHX Text

SOURCE 2 (EMERGENCY): 50,000 RMS SYM @ 240V, 480V, 600V.

AutoCAD SHX Text N

AutoCAD SHX Text

SEE ECN

AutoCAD SHX Text 319020

AutoCAD SHX Text

SV

AutoCAD SHX Text

SV

AutoCAD SHX Text 11-27-25

File details come from the government source that posted it. Updated .