This document is an Agency Requirements exhibit (Exhibit B) for RLP No. 6OH0315, establishing LAN Room Standards for U.S. Citizenship and Immigration Services (USCIS) facilities under the Office of Information Technology in collaboration with the Office of Facilities and Space Management Branch. The standards document, dated March 2026 (Version 2.4), provides comprehensive specifications for Computer/Telephone LAN Rooms, Computer Staging Rooms, and Telecommunication Rooms (TR) / Remote Wire Closets (RWC) to ensure uniformity across all USCIS facilities. Inquiries regarding the document should be directed to the USCIS Field Support Center Chief at (802) 872-4114.
The document details specific requirements across three primary room types: Computer/Telephone LAN Rooms (275-350 square feet depending on facility size), Computer Staging Rooms (minimum 150 square feet), and Telecommunication Rooms/Remote Wire Closets (75-225 square feet depending on facility size). Critical specifications include dedicated electrical panels with 20% spare capacity, 24/7 HVAC units maintaining 65-70°F with 40-50% humidity, direct/indirect lighting at 50-foot candles, ladder runways per USCIS Structured Cable Plant Standards (24" for LAN Rooms, 18" for TR/RWC), 2 CAT 6 cables per drop, emergency power systems (EPO switches), separate ground TMGB bus bars, and fire suppression systems with type ABC extinguishers. Physical security requirements include lockable 42U cabinets, 19" stand-alone equipment racks with minimum clearances (4 feet for two-post racks, 3 feet for four-post racks), wall-mounted phones at 48" AFF, and painted fire-rated plywood backboards. The document references compliance with Telecommunications Industry Association (TIA) and Electronic Industries Alliance (EIA) standards (TIA/EIA-568, 569, 570, 607). USCIS IT staff coordinate equipment disconnection and movement through the Office of Information Technology's Converged Services Implementation Branch. Responsibility for IT equipment decommissioning belongs to the Enterprise Infrastructure Engineering and Implementation group, while non-reusable equipment disposal is handled by local office asset management.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LAN Room Standards
RLP No. 6OH0315 - Exhibit B Agency Requirements
LESSOR: ______ GOVERNMENT: ______
Computer & Telephone - LAN Room Standard
March 2026
Office of Information Technology in collaboration with
Office of Facilities and Space Management Branch
US Citizenship and Immigration Services
6/2/2026 2 USCIS Computer and Telephone
- LAN Room Standard Version 2.4
1.0 INTRODUCTION 3
1.1 Purpose 3
1.2 Background 3
1.3 Scope 3
1.3.1 Documentation 3
2.0 GENERAL NOTES: 4
2.1 Disconnect and Movement of Equipment 4
2.2 Cable Installation 4
2.3 Authority to have Telephones 4
2.4 Shared Computer and Telephone Rooms 4
2.5 Fire Suppression System 4
2.6 Decommissioning and Disposal of IT Equipment 4
2.7 Physical Security LAN room requirements 5
3.0 COMPUTER/TELEPHONE – LAN ROOM 5
3.1 SIZE & GENERAL REQUIREMENTS 5
3.2 Electrical 6
3.3 HVAC 7
4.0 COMPUTER STAGING ROOM 7
4.1 SIZE & GENERAL REQUIREMENTS 7
4.2 HVAC 7
4.2 Electrical 7
5.0 TELECOMMUNICATION ROOMS (TR) / REMOTE WIRE CLOSETS (RWC) 8
5.1 SIZE & GENERAL REQUIREMENTS 8
5.2 Electrical 9
5.3 HVAC 9
5.4 Uninterrupted Power Supply System 9
6/2/2026 3 USCIS Computer and Telephone
- LAN Room Standard Version 2.4
1.0 INTRODUCTION
1.1 Purpose
The United States Citizenship and Immigration Services (USCIS) Office of Facilities and Space Management Branch have prepared this document with the specific purpose of setting standards for MDF / Computer and Telephone – LAN Rooms and Equipment. This document will be used to provide the following:
• Facilitate the planning and installation of MDF / Computer and Telephone – LAN Rooms and Equipment.
• To ensure uniformity of MDF / Computer and Telephone – LAN Rooms and Equipment in all USCIS facilities.
The primary focus of this document is to define the standards for space, materials, infrastructure, design and installation for USCIS facilities. For questions or comments regarding this document, contact the USCIS Field Support Center Chief, Facilities and Space Management branch Chief at
(802) 872-4114.
1.2 Background
United States Citizenship and Immigration Services (USCIS) is a component of the U.S. Department of Homeland Security (DHS). The mission USCIS is to secure America's promise as a nation of immigrants by providing accurate and useful information to our customers, granting immigration and citizenship benefits, promoting an awareness and understanding of citizenship, and ensuring the integrity of our immigration system. Because of increasing demands on Service resources, USCIS personnel must be able to share information rapidly and efficiently in order to succeed in fulfilling the Service mission.
1.3 Scope
1.3.1 Documentation
This document is intended to address the following responsibilities and specifications for all USCIS MDF / Computer and Telephone LAN Rooms and Equipment:
• Movement of Equipment.
• Installation of Cabling.
• Distribution of Telephones.
• Size of Rooms.
• Finishes for Rooms.
• Utilities for Rooms.
• Physical Security Requirements.
6/2/2026 4 USCIS Computer and Telephone
- LAN Room Standard Version 2.4
2.0 GENERAL NOTES:
2.1 Disconnect and Movement of Equipment
Disconnection of the IT equipment should be by the USCIS IT staff. The funding to accomplish this will be provided through the project RWA. Movement of any existing USCIS computer room equipment will be coordinated by End User Support Division. The CIS contact for IT related issues is:
Office of Information Technology Chief –Converged Services Implementation Branch (CSI) Converged Services Implementation 70 Kimball Ave., South Burlington, Vermont 05403
(802) 872-9500
2.2 Cable Installation
Cable maintenance and installation will be installed in accordance with the USCIS Structured Cable Plant Standard.
All USCIS facilities will contain 2 CAT 6 cables per drop as per the USCIS Cable Plant Standard.
2.3 Authority to have Telephones
The Director along with OIT will decide which workstations will receive telephones, softphones, etc. This coordination will occur when the USCIS Telecommunications project manager develops the scope of work with the field office.
2.4 Shared Computer - LAN Room
USCIS and other DHS entities will have separate phone switches and servers although they will be allowed to collocate within a shared Computer/LAN Room at collocated DHS sites where applicable.
2.5 Fire Suppression System
Standard fire suppression systems shall be installed for the Computer / LAN Room and TR's/RWC's, computer rooms located in buildings that are required to have sprinkler systems by code. High temperature sprinkler heads within the Computer -LAN Rooms and TR's/RWC's room shall be in their own zone only if a new system is installed so they’re not daisy chained to other heads in the system. Additionally, type ABC fire extinguishers will be required adjacent to each door entering this room and mounted on a support bracket accordingly. Extinguishers shall be non-corrosive such as Ansul Clean Guard with Dupont FE-36 or equal.
2.6 Decommissioning and Disposal of IT Equipment
The USCIS Enterprise Infrastructure Engineering and Implementation group will be responsible for the decommissioning of any reusable IT equipment. Non-reusable equipment disposal will be the responsibility of the local office asset management group.
6/2/2026 5 USCIS Computer and Telephone
- LAN Room Standard
Version 2.4
2.7 Physical Security Computer - LAN Room requirements
A space will be provided in the computer /LAN Room for full-size 42U lockable cabinet(s) along with U space the 19" stand-alone equipment rack in the TR's / RWC's and 8 feet of wall space to mount associated physical security equipment with dedicated 5-20R electrical outlet requirements @ 18” & 90” AFF. Two (2) dedicated L14-30R single phase electrical outlets shall also be installed above the security cabinet. Painted fire rated plywood backboard is provided in the Computer – LAN and Telecommunication Rooms / Remote Wire Closets to mount enclosures and hardware.
3.0 COMPUTER - LAN ROOM
3.1 SIZE & GENERAL REQUIREMENTS
The Computer & Telephone – LAN Room size shall be determined by the total number of cable drops in the servicing area of the USCIS building space. Please refer to the chart below for required minimum square footage and contact OIT if needed for exceptions. Rooms should be open space and free from architectural structures, i.e. columns, posts, utilities, exterior windows, roof hatchways etc.
Facility Size
Authorized Staff
Computer Room size
Small Up to 25 275 sq ft Medium 25 to 75 325 sq ft Large 75 to 200 350 sq ft Unique ** **
** = Please see OIT representative for specifications.
• 24” Ladder runway to be installed in Computer / LAN Room in accordance with USCIS Structured Cable Plant Standard.
• The telephone server, physical security, CATV, horizontal and vertical cable plant terminations, data infrastructure, and USCIS backbone fiber and copper tie cables extended from the Main Building Demarcation shall be installed in the room.
• Lighting for this room shall be direct/indirect lighting with 50-foot candles at 3’-0” above finished floor.
• A minimum 4 ft clearance behind and in front of 19” two-post/stand-alone racks.
• A minimum 3 ft clearance behind and in front of four-post racks, cabinets and enclosures.
• There will be two (2) wall mount phones, mounted at 48” AFF, one near the door and one on the opposite wall.
6/2/2026 6 USCIS Computer and Telephone
- LAN Room Standard
Version 2.4
• Above every cabinet and four-post rack, will be mounted a minimum of one (1) 12 port zero U patch panel which ties to the main cable plant in the 19” two-post racks along with one (1) on the plywood backboard near the voice tie cable termination blocks. (Typically, a minimum of five in the Computer – LAN Room. See the Structured Cable Plant Standard)
• Two (2) 4" EMT conduit raceways must be installed from the Computer - LAN Room directly to the Main Demarcation Room on the 1st floor or basement level dedicated for USCIS data, voice and CATV requirements only. The conduit size may be reduced to 3" EMT if the USCIS space is on a higher floor or due to routing challenges with prior OIT approval.
• Three (3) 4" EMT conduit sleeves with plastic bushings shall be placed along the perimeter at each of the ladder runways for the transition of OIT and security cabling from the plenum above onto the 19” two-port stand-alone equipment racks and cabinets, and wall-mounted enclosures. See the Viso room layout provided by OIT for placement.
3.2 Electrical
• A dedicated electrical panel(s) shall be located in this room to control all power and lighting in this room. The power panel servicing this room shall provide an additional a minimum of 20% spare capacity for future growth. The dedicated 24/7 HVAC CRAC unit may also be connected to the dedicated electrical panel.
• OIT will provide and install an APC NetBotz device which will connect to the USIS network to monitor heat and humidity levels.
• All electrical outlets in the Computer - LAN Room that are to be used for computer equipment shall be dedicated. Six (6) dedicated duplex outlets will be provided for every 150 sq ft (at least one on each wall of the room). If a raised floor is utilized these outlets will be located on 10-foot flexible conduit “whips” under the raised floor.
• Two (2) L14-30R single phase outlets are to be installed above each rack and cabinet in the room. Outlets are to be located at a minimum of 8 ft above finished floor and placed in the ceiling tiles of the ACT within the room.
• Dedicated outlets, L6-30R, L5-30R, 5-20R, etc. need to be additional 5-20R duplex outlets will be specified @ 90" AFF for the IDS and ACS wall-mounted enclosures, installed for security system, please refer to security specification and OIT for direction.
• Convenience quadplex outlet shall be installed on the walls per NEC standard.
• A separate ground TMGB bus bar will be in this room, behind the data rack. All electrical components in this room will ground at this location, with # 6 copper ground. This Bus bar will be the TMGB and connected to the main building electrical service. A secondary ground connection, minimum AWG # 4 will be required to building steel.
• An EPO, emergency “KILL” switch with cover or safety ring is required adjacent to all doors exiting this room. This system shall be designed to shut down all computer equipment power to this room. The UPS units installed by USCIS shall be wired to the EPO following IT deployments, by the lessor’s electrician.
• Electrical Panels will be flush mounted with the wall, surface panels and /or framing out of wall will not be permitted. Minimal furring is acceptable for the electrical panel cover.
• Computer - LAN Room and TR's/RWC's, and related spaces shall meet applicable Telecommunications Industry Association (TIA) and Electronic Industries Alliance (EIA) standards. These standards include the following:
6/2/2026 7 USCIS Computer and Telephone
- LAN Room Standard Version 2.4
a. TIA/EIA-568, Commercial Building Telecommunications Cabling Standard,
b. TIA/EIA 569, Commercial Building Standard for Telecommunications Pathways and Spaces,
c. TIA/EIA-570, Residential and Light Commercial Telecommunications Wiring Standard,
d. TIA/EIA-607, Commercial Building Grounding and Bonding Requirements for Telecommunications Standard
3.3 HVAC
• A separate stand-alone HVAC unit, capable of providing temperatures of between 65 degrees F and 70 degrees F, and a humidity level of between 40% and 50% 24 hours a day seven days a week. If the above ceiling unit is utilized, it shall be located entirely outside the Computer / LAN Room and ducted in unless it is determined that a raised computer room floor will be used. Floor and wall-mount CRAC units within the Computer – LAN Room are acceptable, and location will be provided by OIT in the Visio layouts provided to accommodate space required. Under-floor ducting will be required if a raised floor application is utilized. USCIS data engineers will provide OIT, and security equipment lists with manufacturer parts numbers and quantities typically installed in the spaces to calculate sizing. Overall cooling requirements will need to be determined by a SME, certified HVAC / Mechanical engineer. The hot and cold aisles will also be identified by OIT for the supply and return defusser placement accordingly.
• Mounting of monitoring/control hardware must be coordinated with OIT representatives.
4.0 COMPUTER STAGING ROOM
4.1 SIZE & GENERAL REQUIREMENTS
• The minimum size of the Computer Staging Room shall be 150 square feet. Contact OIT if needed for exceptions
• There will be a work surface area running the length of the longest wall in the room for staging/ repair of OIT equipment. The height of this work surface is not to exceed 36” AFF.
• There will be 6 standard cable drops provided in this room. (Please refer to CD’s for drop specification with a minimum of six (6) 2D locations.)
• If applicable, a 4 ft X 3ft-tempered glass window shall be installed between the computer room and computer room staging area.
4.2 HVAC
• Building standard HVAC will be required for this room.
4.3 Electrical
• Lighting for this room shall be direct/indirect lighting with 50-foot candles at 3’-0” above
6/2/2026 8 USCIS Computer and Telephone
- LAN Room Standard Version 2.4 finished floor.
• Three dedicated 5-20R quad outlets shall be installed above the required work surface.
(Typically, 42” AFF).
• Standard convenience outlets will also be provided.
5.0 Telecommunication Room /(TR) / Remote Wire Closet (RWC)
5.1 SIZE & GENERAL REQUIREMENTS
The Telecommunication Room / Remote Wire Closet size shall be determined by the total number of cable drops in the servicing area of the USCIS building space. Please refer to the chart below for required minimum square footage and contact OIT if needed for exceptions. These rooms will only be required if the total cable runs between desktop computers and the Computer - LAN Room exceeds 328 feet (100 meters) and/or spans multiple floors. Rooms should be open space and free from architectural structures, i.e. columns, posts, utilities, roof hatchways etc.
Facility Size Authorized
Staff TR size
Small Up to 25 75 sq ft Medium 25 to 75 100 sq ft Large 75 to 200 225 sq ft Unique ** **
** = Please see OIT representative for specifications.
• 18” Ladder runway to be installed in Telecommunication Room / Remote Wire Closet in accordance with USCIS Structured Cable Plant Standard.
• Fiber, copper, and CATV riser backbone, horizontal and / or vertical cable will be extended from the MDF / Computer – LAN Room.
• The lighting level shall be 50-foot candles at 3’-0” above finished floor. This lighting will also be on its own emergency backup power source.
• There will be one (1) wall mount phone, mounted at 48” AFF, one near the door.
• Three (3) 4" EMT conduit sleeves with plastic bushings shall be placed along the perimeter at each of the ladder runways for the transition of OIT and security cabling from the plenum above onto the 19” two-port stand-alone equipment racks and cabinets, and wall-mounted enclosures. See the Viso room layout provided by OIT for placement.
6/2/2026 9 USCIS Computer and Telephone
- LAN Room Standard Version 2.4
5.2 Electrical
• A dedicated electrical panel shall be located in this room to control all power and lighting in this room. The power panel servicing this room shall provide an additional a minimum of 20% spare capacity for future growth. The dedicated 24/7 HVAC CRAC unit may also be connected to the dedicated electrical panel.
• If applicable, OIT will provide and install an APC NetBotz device which will connect to the USIS network to monitor heat and humidity levels.
• Two (2) L14-30R outlets are to be installed above each rack in the room. Outlets are to be located at a minimum of 8 ft. AFF and placed in the ceiling tiles of the ACT within the room.
• Dedicated outlets, L6-30R, L5-30R, 5-20R, etc. need to be additional 5-20R duplex outlets will be specified @ 90" AFF for the IDS and ACS wall-mounted enclosures, installed for security system, please refer to security specification and OIT for direction.
• A separate ground TGB bus bar will be in the Telecommunication Room / Remote Wire Closet, behind the data racks. All electrical components in this room will ground at this location, with # 6 copper ground. Bus bar will terminate to TMGB in the Computer – LAN Room with an AWG # 3/0 and secondary ground, minimum AWG # 4 will be required to building steel.
5.3 HVAC
• A separate standalone HVAC unit, capable of providing temperatures of between 65 degrees F and 70 degrees F, and a humidity level of between 40% and 50% 24 hours a day seven days a week. If the above ceiling unit is utilized, it shall be located entirely outside the Telecommunication Room / Remote Wire Closet and ducted in unless it is determined that a raised computer room floor will be used. Floor and wall-mount CRAC units within the Telecommunication Room / Remote Wire Closet are acceptable and location will be provided by OIT in the Visio layouts provided to accommodate space required. Under-floor ducting will be required if a raised floor application is utilized. USCIS data engineers will provide a max. BTU count for the original install. Overall cooling requirements will need to be determined by a certified HVAC engineer. The hot and cold aisles will also be identified by OIT for the supply and return defusser placement accordingly.
• Mounting monitoring/control hardware must be coordinated with OIT representative.
5.4 Uninterrupted Power Supply System
(Determined by USCIS OIT representative)
• In the advent that a whole room UPS is deemed necessary by OIT, details will be provided.