23-02-17_ZDC second floor auto_sprinkler fire alarm_OPTION B.pdf
PDF 674 KB Posted
- Attached to
- Replace Fire and Sprinkler Detection Systems Leesburg, VA Federal contract opportunity
- Solicitation number
- 697DCK-24-R-00103
About this file
This document is a schematic diagram outlining proposed modifications to the sprinkler and fire alarm system for the second floor of a building. The diagram depicts relocating and adding sprinkler branch lines, sprinklers, strobe lights, and heat detectors throughout the affected area. It also indicates performing hydraulic calculations for the area.
The related federal contract opportunity is a solicitation from the Department of Transportation Federal Aviation Administration Southwestern Region to replace fire and sprinkler detection systems in Leesburg, Virginia. The schematic diagram appears to outline proposed work that could be performed under this contract, showing modifications needed to bring the sprinkler and alarm system up to current codes for the second floor area. Key aspects of the work shown include relocating and adding sprinklers, branch lines, strobe lights and heat detectors throughout the floor and corridors. Hydraulic calculations will also be required.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 697DCK-24-R-00103.pdf | ||
| Wage Determination - Leesburg VA.pdf | ||
| ZDC TRG Egress Auto AHU-110_SOW (002).pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Callout Existing sprinkler branch lines
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Arrow
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Callout Relocate existing branch line by either extending main or adding elbows.
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey PolyLine
Zachary T Jeffrey Callout Remove existing branch line. Reuse existing outlet from main and add T to add sprinklers to both rooms.
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Callout Add 2 new sprinklers to existing branch lines (typ)
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Callout Add sprinklers to new corridor
Zachary T Jeffrey Strobe Only With Rating
Zachary T Jeffrey Line
Zachary T Jeffrey Line
Zachary T Jeffrey Line
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Typewritten Text
Zachary T Jeffrey Strobe Only With Rating
Zachary T Jeffrey Line
Zachary T Jeffrey Line
Zachary T Jeffrey Line
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Typewritten Text
Zachary T Jeffrey Callout Add new strobe to each room. Recommend ceiling mount. If possible to mount in center, 30cd will be sufficient for coverage.
Zachary T Jeffrey Horn/Strobe Wall
Zachary T Jeffrey Polygon
Zachary T Jeffrey Ellipse
Zachary T Jeffrey PolyLine
Zachary T Jeffrey PolyLine
Zachary T Jeffrey PolyLine
Zachary T Jeffrey PolyLine
Zachary T Jeffrey Typewritten Text W
Zachary T Jeffrey Callout Add new strobe to end of corridor, within 15 ft. of end. Does not matter if wall or ceiling mounted. 15cd.
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Heat Detector
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Heat Detector
Zachary T Jeffrey Callout Relocate existing Firecycle heat detector midway between sprinklers
Zachary T Jeffrey Callout Add new Firecycle heat detector midway between sprinklers
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Heat Detector
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Heat Detector
Zachary T Jeffrey Callout Relocate existing Firecycle heat detector and add new detector to be 12-18" from sprinkler.
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Heat Detector
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Heat Detector
Zachary T Jeffrey Callout Add new Firecycle heat detectors to corridor, 12-18" from sprinklers.
Zachary T Jeffrey Callout Relocate Firecycle heat detectors. Must be 12-18" from sprinkler. Each heat detector can cover up to 40'x40' (40 ft. between detectors, 20 ft. from walls).
Zachary T Jeffrey Line
Zachary T Jeffrey Line
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Cloud+
Zachary T Jeffrey Cloud+ Based on existing layout, existing sprinklers may be at proposed wall location. Relocate 3 sprinklers into corridor, add 3 sprinklers to classroom. Minimum 4" from walls, minimum 6 ft from adjacent sprinklers, maximum 15 ft from adjacent sprinklers.
Zachary T Jeffrey Ellipse
Zachary T Jeffrey Line
Zachary T Jeffrey Heat Detector
Zachary T Jeffrey Cloud+
Zachary T Jeffrey Cloud+ If classroom is less than 400 sq. ft., only one Firecycle heat detector is required and should be located as centrally as possible with regards to sprinkler placement. If greater than 400 sq. ft., heat detectors should be located as remotely as possible but still within 12-18" of a sprinkler.
Zachary T Jeffrey Horn/Strobe Wall
Zachary T Jeffrey Polygon
Zachary T Jeffrey Ellipse
Zachary T Jeffrey PolyLine
Zachary T Jeffrey PolyLine
Zachary T Jeffrey PolyLine
Zachary T Jeffrey PolyLine
Zachary T Jeffrey Typewritten Text W
Zachary T Jeffrey Callout Add exit signs
Olesya E-CTR Cooper Text Box
OPTION B
Olesya E-CTR Cooper Text Box
SPRINKLER CONTRACTOR TO PERFORM HUDRAULIC CALCULATIONS FOR THE AFFECTED AREA