697DCK-21-R-00189 Amendment 0001.pdf

PDF 597 KB Posted

Attached to
CRAC Unit Replacement at FAA's Automated Flight Service Station (AFSS) in Juneau, Alaska - AMENDMENT 0001
Solicitation number
697DCK-21-R-00189
Issued by

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

1. CONTRACT ID CODE

5. PROJECT NO. (If applicable)2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ.NO.

PAGE OF PAGES

6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6)

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

CODE

9A. AMENDMENT OF SOLICITATION NO.

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NO.

10B. DATED (SEE ITEM 13)

CODE FACILITY CODE

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

Items 8 and 15, and returning is extended, is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required.)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

(x) A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO THE AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation date, etc.) SET FORTH IN ITEM 14.

E. IMPORTANT: Contractor is not, is required to sign this document and return

ORDER NO. IN ITEM 10A.

1 6

0001 05/20/2021

FEDERAL AVIATION ADMINISTRATION

AAQ-500 - REGIONAL ACQUISITIONS

2200 S. 216TH STREET

DES MOINES WA 98198-6547

AAQ530ANM-AFN

x

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

separate letter or telegram which includes a reference to the solicitation and amendment number. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT

THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By ___________ 1 x x

697DCK-21-R-00189

1 copies to the issuing office.

05/20/2021

(x)

Amendment 0001 is to post & incorporate answers to questions received.

No other changes.

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. CONTRACT AUTHORITY 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Cynthia A. Tjelde

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

RFO 697DCK-21-R-00189 Juneau CRAC Unit Replacement Project

Questions & Answers

1) Question: Are Zoom Lock Refrigeration Fittings acceptable for use? See attached PDF for specifications.

Answer: Zoom Lock Refrigeration Fittings are acceptable for use provided they are installed in accordance with manufacturer’s recommendations.

2) Question: During the site visit, it was unclear where the electrical for existing CRAC unit is to be terminated. Terminate in panel and abandon or remove all or a portion of conduit?

Answer: Demo to wall penetration inside GEN/MECH/ELECT Rm 120, above Panel E/G.

Abandon In Place from wall penetration to Main Distribution Panel.

3) Question: Specs call out for MA Simple Controllers for each indoor unit, but location(s) of controllers are not shown. Please identify location(s).

Answer: Locate all MA Simple Controllers on the wall behind the existing Liebert indoor unit. Left side when facing unit.

4) Question: Once thermostat locations are determined, can we use wire mold and surface mount or will wires be required to fish wires in walls?

Answer: Install MA Simple Controllers on switch boxes with EMT.

5) Question: Bacnet controller spec’d can control indoor units without having the MA Simple controllers. Please verify both are required.

Answer: Both are required. MA Simple Controllers also have thermostat function. Bacnet controllers do not.

Page 6 / Catalog K-3, ZoomLock MAX

TECHNICAL DATA

ZoomLock MAX Press-to-Connect Refrigerant Fittings

Approved Refrigerants 32** 422D 454A** 125 427A 454B** 134a 438A 454C** 290** 444A** 457A** 404A 447A** 459A** 407A 447B** 507A 407C 448A 513A 407F 449A 513B 407H 450A 600A** 410A 452A 718 417A 452B** 1234yf** 421A 452C 1234ze**

422B HYCOOL 20

Fitting Materials

■ Fitting Body:

Refrigerant Grade Copper (UNS C12200 min 99.9% pure)

■ O-Ring:

HNBR

Fitting Warranty

■ 10-year warranty. Refer to page 26 for more details.

Compatibility

■ Approved Lubricants: POE, PAO, PVE, AB and MO

■ Approved Connections:

Copper to Copper

■ Approved Tube:

Copper tube conforming to*

ASTM B280, ASTM B88,

or ASTM B743

■ Approved Copper Tubing:

Hard Copper (Drawn)

- Type ACR, L, K

Soft Copper (Annealed)

- Type ACR, L, K

* Please refer to ZoomLock MAX Tube Compatibility Table, page 18.

** When using refrigerants classified A2L (lower flammability), A2 (flammable) and A3 (higher flammability) additional/ specific standards, local rules and regulations, codes of practice and by-laws may be applicable.

ZoomLock MAX fittings are NOT suitable for R-717, R-723, R-764, R-744 refrigerants.

Refer to ZoomLockMAX.com for the latest approved refrigerants list.

Product Parameters

■ Applications:

- Refrigeration

- Air Conditioning

- Heat Pump (Refrigeration side)

- VRF and VRV

■ Continuous Operating Temperature:

-40°F to 250°F / -40°C to 121°C

■ O-ring Temperature Range:

-40°F to 284°F / -40°C to 140°C

■ Maximum Rated Operating and Abnormal Pressure:

700 psi / 48 bar / 4800 kPa

■ Burst Pressure:

>3X Maximum operating and abnormal pressure >2,100 psig / >14400 kPa / >144 bar

■ Vacuum Pressure Capability:

200 Microns

■ Leak Tightness:

Helium ≤ 7.5 × 10-7 Pa.m3/s at +20°C, 10 bar

■ Size Availability (Inches):

1/4, 3/8, 1/2, 5/8, 3/4, 7/8, 1-1/8, 1-3/8

Agency Approvals and Certifications

■ UL Listed Refrigerant fitting SA7511

■ UL Listed: Approved use for field and factory installations

■ UL 109 - 7 Pull test, compliant

■ UL 109 - 8 Vibration test, compliant

■ UL 1963 - 79 Tests of gaskets and seals used in refrigerant systems, compliant

■ ISO 5149-2:2014, Refrigerating systems and heat pumps - Safety and environmental requirements - Part 2: Design, construction, testing, marking and documentation compliant

■ ISO 5149-2, 5.3.2.2.3 Strength pressure test, compliant

■ ISO 14903 - 7.4 Tightness test, compliant

■ ISO 14903 - 7.6 Pressure temperature vibration tests (PTV), compliant

■ ISO 14903 - 7.8 Freezing test, compliant

■ ASTM G85 salt spray (fog) compliant

■ ASHRAE 15 - 2016 Safety Standard for Refrigeration Systems, compliant

■ ASME B31.5 - 2016 Refrigeration Piping and Heat Transfer Components, compliant

■ 2018, 2015, 2012, 2009 and 2006 International Mechanical Code (IMC), certified, ICC-ES, PMG-1440

■ 2018, 2015, 2012, 2009 and 2006 International Residential Code (IRC), certified, ICC-ES, PMG-1440

■ 2018, 2015, 2012, 2009 and 2006 Uniform Mechanical Code (UMC), certified, ICC-ES, PMG-1440

Mechanical joints shall not be used on annealed temper copper tube in sizes larger than 7/8 inch (22.2 mm) OD size per International Mechanical Code (IMC) and 3/4 inch nominal size per Uniform Mechanical Code (UMC).

Quality Assurance ZoomLock MAX is manufactured in an ISO 9001 certified facility committed to providing quality products and support.

Catalog K-3, ZoomLock MAX / Page 7

PRESS TOOLS AND JAWS

Parker Hannifin recommends the use of ROTHENBERGER press tools in combination with ZoomLock MAX ROTHENBERGER jaws. However other press tools may be used in combination with ROTHENBERGER ZoomLock MAX jaws. See table below for tool compatibility.

COMPATIBLE PRESS TOOLS 32 kN 24 kN 19 kN

ROTHENBERGER

ROMAX® 3000 ✔ — —

ROMAX® 3000 AC ✔ — —

ROMAX® 4000 ✔ — —

ROMAX® AC ECO ✔ — —

Twin Turbo US (TT US) — ✔ — ROMAX® Compact TT — — ✔ ROMAX® Compact — — ✔

DEWALT DCE200 ✔ — —

KLAUKE

UAP2/UNP2 ✔ — —

UAP3L/UAP4L ✔ — —

UP2EL14 ✔ — —

MAP2L19 — — ✔

MAP219 — — ✔

MILWAUKEE

M12 Force Logic — ✔ — M18 Force Logic ✔ — —

HILTI NPR 019 — — ✔

NIBCO

PC-100 ✔ — —

PC-280 ✔ — —

REMS

Power-Press ✔ — — Akku-Press ✔ — —

RIDGID

320-E ✔ — —

CT400 ✔ — —

RP 241 — ✔ —

RP 240 — ✔ —

RP 210-B — ✔ —

RP 200-B — ✔ —

RP 330-B ✔ — —

RP 330-C ✔ — —

RP 340 ✔ — —

RP 350 ✔

VIRAX

Viper® P25+ ✔ — — Viper® P25+ ✔ — —

ZoomLock MAX fittings are only compatible with ROTHENBERGER press jaws as shown on page 8.

ROTHENBERGER

Twin Turbo US 24 kN

ROTHENBERGER

ROMAX 4000

32 kN

ZoomLock MAX Press-to-Connect Refrigerant Fittings

Press Tools

ROTHENBERGER ROMAX 4000

Includes the ROTHENBERGER ROMAX® 32 kN press tool, 2 batteries and battery charger.

■ Description: MZK-TK-R4000

■ Part Number: 871441

ROTHENBERGER Twin Turbo US Includes the ROTHENBERGER Twin Turbo US 24 kN press tool, 2 batteries and battery charger.

■ Description: MZK-TK-RCTT

■ Part Number: 871439

Page 8 / Catalog K-3, ZoomLock MAX

PRESS TOOLS AND JAWS (Continued)

32 kN

ROTHENBERGER

Jaw Set

24 kN

ROTHENBERGER

Jaw Set

19 kN

ROTHENBERGER

Jaw Set

JAW SETS / PART NUMBERS

Jaw Sets 7 Piece 1/4, 3/8, 1/2, 5/8, 3/4, 7/8, 1-1/8

MZK-32KN JAW KIT (7 PIECE)

871408

MZK-24KN JAW KIT (7 PIECE)

871409

MZK-19KN JAW KIT (7 PIECE)

871410

INDIVIDUAL JAWS / PART NUMBERS

1/4” MZK-32KN JAW-1/4”

871428

MZK-24KN JAW-1/4”

871419

MZK-19KN JAW-1/4”

871411

3/8” MZK-32KN JAW-3/8”

871429

MZK-24KN JAW-3/8”

871420

MZK-19KN JAW-3/8”

871412

1/2” MZK-32KN JAW-1/2”

871430

MZK-24KN JAW-1/2”

871421

MZK-19KN JAW-1/2”

871413

5/8” MZK-32KN JAW-5/8”

871431

MZK-24KN JAW-5/8”

871422

MZK-19KN JAW-5/8”

871414

3/4” MZK-32KN JAW-3/4”

871432

MZK-24KN JAW-3/4”

871423

MZK-19KN JAW-3/4”

871415

7/8” MZK-32KN JAW-7/8”

871433

MZK-24KN JAW-7/8”

871424

MZK-19KN JAW-7/8”

871416

1-1/8” MZK-32KN JAW-1 1/8”

871435

MZK-24KN JAW-1 1/8”

871426

MZK-19KN JAW-1 1/8

871418

1-3/8”* MZK-32KN JAW-1 3/8”

871436

*Depth gauge (P/N 870517) is included with the 1-3/8" jaw.

ZoomLock MAX Press-to-Connect Refrigerant Fittings

Jaws ZoomLock MAX fittings are only compatible with ROTHENBERGER press jaws as shown in the table below.

Catalog K-3, ZoomLock MAX / Page 9

ZoomLock MAX Press-to-Connect Refrigerant Fittings

A

B

Size Part Number Description

Dimensions A B

Inch mm Inch mm

1/4 870508 MZK-C4-HNBR 1.54 39.0 0.12 3.0

3/8 870509 MZK-C6-HNBR 1.50 38.0 0.12 3.0

1/2 870503 MZK-C8-HNBR 1.57 40.0 0.20 5.0

5/8 870510 MZK-C10-HNBR 1.77 45.0 0.12 3.0

3/4 870505 MZK-C12-HNBR 1.79 45.5 0.06 1.5

7/8 870506 MZK-C14-HNBR 2.22 56.5 0.33 8.5

1-1/8 870507 MZK-C18-HNBR 2.24 57.0 0.24 6.0

1-3/8 870511 MZK-C22-HNBR 2.80 71.0 0.11 3.0

Size Part Number Description

Dimensions A B

Inch mm Inch mm

1/4 870550 MZK-RC4-HNBR 3.54 90.0 0.71 18.0

3/8 870552 MZK-RC6-HNBR 3.54 90.0 0.71 18.0

1/2 870553 MZK-RC8-HNBR 3.58 91.0 0.69 17.5

5/8 870554 MZK-RC10-HNBR 3.98 101 0.83 21.0

3/4 870555 MZK-RC12-HNBR 3.98 101 0.86 22.0

7/8 870556 MZK-RC14-HNBR 4.17 106 0.95 24.0

1-1/8 870557 MZK-RC18-HNBR 4.17 106 1.00 25.5

1-3/8 870559 MZK-RC22-HNBR 3.94 100 1.34 34.0

Dimensions

Dimensions

COUPLINGS

SLIP COUPLINGS

A

B

Amend form
Questions & Answers
e Attachment - Zoom Lock Specs

File details come from the government source that posted it. Updated .