QUESTIONS & RESPONSES
1. Question: Remove combustible carpeting from walls and replace with decorative sheet metal to match existing finish around the CAB floor stair. Please provide manufacturer and model/color of decorative sheet metal.
Response: It is the vendor’s responsibility to match the existing finish around the CAB floor stair.
2. Question: Can we use an alternate fire alarm system?
Response: An alternate fire alarm system may be proposed; however, it must be compatible with other the devices and modules. The Contracting Officer Representative must approve an alternative fire alarm system prior to installation.
3. Question: Our PM has done an ATCT FLS Project for a previous employer. Can we use this personnel experience or is it required to be company specific?
Response: Personal experience will not be accepted or evaluated. Offerors must submit company experience similar in scope.