This document provides sampling results from an asbestos and lead based paint survey conducted at the Millville (MIV) RCAG facility. Lab analyses identified that green floor tiles in the equipment room contained 7.9% chrysotile asbestos in the tiles and 1.4% and unspecified percentages in the black and yellow mastic.
The related federal contract opportunity is a solicitation from the Department of Transportation Federal Aviation Administration Franchise Acquisition Services for contract number 6973GH-23-R-00218 to perform floor tile and painting work at the MIV RCAG facility to address the asbestos and lead based paint issues identified in the survey results. The solicitation includes removal and disposal of asbestos containing materials and lead based paint from impacted areas.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Millville (MIV) RCAG – Facility Rehabilitation Project – November 15, 2022
MILLVILLE (MIV) RCAG
FACILITY REHABILITATION PROJECT
PHOTO-LOG & SAMPLING REPORT
Site Visit – November 15, 2022
Murtaza Kamal (NISC) December 8, 2022
BACKGROUND:
Asbestos and Lead Based Paint survey and sampling was performed at Millville (MIV) RCAG on November 15, 2022. Lab analyses of the samples indicate the following results;
1. EQUIP RM - 9" x 9" Green Floor Tile 7.9% Chrysotile Asbestos
2. EQUIP RM - 9" x 9" Green Floor Tile Black Mastic 1.4% Chrysotile Asbestos
3. EQUIP RM - 9" x 9" Green Floor Tile Yellow Mastic <0.1% Chrysotile Asbestos
4. EQUIP RM - 12" x 12" Beige/Brown Floor Tile No Asbestos Detected
5. EQUIP RM - 12" x 12" Beige/Brown Floor Tile Yellow Mastic No Asbestos Detected
6. EQUIP RM - Block Wall White/Green Paint 0.1% wt. Lead
7. STORAGE RM - Ceiling Black/White Paint 11% wt. Lead
Site Aerial View
Site Address: 30 Bogden Blvd, Millville, New Jersey 08332
Site Coordinates: 39.377667, -75.072444
Floor Plan
9” X 9” GREEN FLOOR TILE & 12”
X 12” BEIGE FLOOR TILE SAMPLE
LOCATION
CEILING
CONDUIT
BLACK/WHITE
PAINT SAMPLE
LOCATION
WALL WHITE PAINT
SAMPLE LOCATION
SITE VIEW – LOOKING EAST SITE VIEW – LOOKING SOUTH
SITE VIEW – LOOKING NORTHEAST SITE VIEW – LOOKING NORTHWEST
EQUIP RM – SOUTH WALL EQUIP RM – WEST WALL (WHITE/GREEN WALL
PAINT SAMPLE LOCATION)
EQUIP RM – EAST WALL EQUIP RM – BEIGE FLOOR TILES
EQUIP RM – WHITE TILES OVER EXPOSED GREEN TILES EQUIP RM – BEIGE FLOOR TILES
EQUIP RM – BEIGE FLOOR TILES EQUIP RM – 12” X 12” BEIGE/BROWN & 9” X 9” GREEN
FLOOR TILE SAMPLE LOCATION
EQUIP RM – WHITE WALL PAINT SAMPLE LOCATION STORAGE RM – NORTH WALL
STORAGE RM – EAST WALL STORAGE RM – GRAY PAINTED CONCRETE FLOOR
STORAGE RM – CEILING PANELS & CONDUITS STORAGE RM – CEILING/CONDUIT
BLACK/WHITE PAINT SAMPLE LOCATION
OrderID: 042229751
EMSL
Order ID TestCust Sample TAT Due Date
Received Date
Confirmation of Samples Received Shipping Tracking Number:
Attn: Murtaza Kamal USDOT/FAA/Independence SMO Airport Corporate Center 340 Scotch Road W. Trenton, NJ 08628
Customer PO:
Received: 11/30/22 10:55 AM
Customer ID: FAA53
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone: (800) 220-3675 Fax: (856) 786-5974 Email: cinnasblab@EMSL.com
PLM EPA NOB 12/7/2022
10:55:00 AM
1-Floor Tile 1 Week11/30/2022
10:55:00 AM
042229751-0001
PLM EPA NOB 12/7/2022
10:55:00 AM
1-Mastic 1 Week11/30/2022
10:55:00 AM
042229751-0001A
PLM EPA NOB 12/7/2022
10:55:00 AM
2-Floor Tile 1 Week11/30/2022
10:55:00 AM
042229751-0002
PLM EPA NOB 12/7/2022
10:55:00 AM
2-Mastic 1 Week11/30/2022
10:55:00 AM
042229751-0002A
111/30/2022 11:48:05 AMDate Sent mailto:cinnasblab@EMSL.com
EMSL Analytical, Inc.
200 Route 130 North Cinnaminson, NJ 08077
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
FAA53
042229751EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Attn:
Proj: MIV RCAG Bldg. Rehab
Phone: (609) 882-2231
Fax: (609) 882-1992
Collected: 11/15/2022
Received: 11/30/2022
Analyzed: 12/07/2022
Murtaza Kamal
USDOT/FAA/Independence SMO
Airport Corporate Center
340 Scotch Road
W. Trenton, NJ 08628
Summary Test Report for Asbestos Analysis in Accordance with N.J.A.C. 8:60 and 12:120 via EPA 600/R-93/116 Client Sample ID:
Sample Description:
Lab Sample ID: 042229751-00011-Floor Tile
MIV RCAG EQUIP RM/9"x9" Green Floor Tile
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
12/07/2022 0.0% 7.9%92.1% ChrysotilePLM Grav. Reduction Green
Client Sample ID:
Sample Description:
Lab Sample ID: 042229751-0001A1-Mastic
MIV RCAG EQUIP RM/Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
12/07/2022 0.0% 0.38%99.6% ChrysotilePLM Grav. Reduction Black
12/07/2022 0.0% 98.6% ChrysotileTEM Grav. Reduction Black 1.4%
Client Sample ID:
Sample Description:
Lab Sample ID: 042229751-0001B1-Mastic 2
MIV RCAG EQUIP RM/Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
12/07/2022 0.0% <0.25%100% ChrysotilePLM Grav. Reduction Yellow
12/07/2022 0.0% 100.0% ChrysotileTEM Grav. Reduction Yellow <0.1%
Client Sample ID:
Sample Description:
Lab Sample ID: 042229751-00022-Floor Tile
MIV RCAG EQUIP RM/12"x12" Beige / Brown Floor Tile
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
12/07/2022 0.0% 100%PLM Grav. Reduction None DetectedGray
12/07/2022 0.0% 100.0%TEM Grav. Reduction None DetectedGray
Client Sample ID:
Sample Description:
Lab Sample ID: 042229751-0002A2-Mastic
MIV RCAG EQUIP RM/Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
12/07/2022 0.0% 100%PLM Grav. Reduction None DetectedYellow
12/07/2022 0.0% 100.0%TEM Grav. Reduction None DetectedYellow
Test Report:EPAMultiTests-7.32.2.D Printed: 12/07/2022 06:17PM Page 1 of 2
EMSL Analytical, Inc.
200 Route 130 North Cinnaminson, NJ 08077
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
FAA53
042229751EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis in Accordance with N.J.A.C. 8:60 and 12:120 via EPA 600/R-93/116
Analyst(s):
TEM Grav. Reduction (4)Daniel Blake
PLM Grav. Reduction (5)Gabrielle DiDonato
Samantha Rundstrom, Laboratory Manager or Other Approved Signatory
Reviewed and approved by:
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. Estimation of uncertainty available upon request. This report is a summary of multiple methods of analysis, fully compliant reports are available upon request. A combination of PLM and TEM analysis may be necessary to ensure consistently reliable detection of asbestos. This report must not be used to claim product endorsement by NVLAP of any agency or the U.S. Government.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ PA ID# 68-00367, NVLAP Lab Code 101048-0 Initial report from: 12/07/202218:17:16
Test Report:EPAMultiTests-7.32.2.D Printed: 12/07/2022 06:17PM Page 2 of 2
OrderID: 202210533
EMSL
Order ID TestCust Sample TAT Due Date
Received Date
Confirmation of Samples Received Shipping Tracking Number:
Attn: Murtaza Kamal USDOT/FAA/Independence SMO Airport Corporate Center 340 Scotch Road W. Trenton, NJ 08628
Customer PO:
Received: 11/30/22 10:55 AM
Customer ID: FAA53
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone: (856) 303-2500 Fax: (856) 786-5974 Email: cinnaminsonleadlab@emsl.com
C-Lead by FLAA 12/7/2022
10:55:00 AM
1 1 Week11/30/2022
10:55:00 AM
202210533-0001
C-Lead by FLAA 12/7/2022
10:55:00 AM
2 1 Week11/30/2022
10:55:00 AM
202210533-0002
112/1/2022 8:19:53 AMDate Sent mailto:cinnaminsonleadlab@emsl.com
Client Sample Description ConcentrationLab ID Analyzed Weight Lead
Collected
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (856) 303-2500 / (856) 786-5974 http://www.EMSL.com cinnaminsonleadlab@emsl.com
Attn: Murtaza Kamal USDOT/FAA/Independence SMO Airport Corporate Center 340 Scotch Road W. Trenton, NJ 08628
Received: 11/30/2022 10:55 AM
MIV RCAG Bldg Rehab
Fax: (609) 882-1992 Phone: (609) 882-2231
Project:
11/15/2022Collected:
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*
202210533 CustomerID: FAA53 CustomerPO:
ProjectID:
EMSL Order:
0.2925 Site: MIV RCAG - Equip Rm Block Wall - white/Green Paint
202210533-00011 0.10 % wt12/1/2022 g11/15/2022
0.2677 Site: MIV RCAG - Storage Rm Ceiling - Black/White Paint
202210533-00022 11 % wt12/1/2022 g11/15/2022
Owen Mckenna, Lead Laboratory Director or other approved signatory
Test Report ChmSnglePrm/nQC-7.32.3 Printed: 12/6/2022 6:54:37 PM
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.
* Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008% wt based on the minimum sample weight per our SOP. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, AIHA LAP, LLC-ELLAP Accredited #100194, A2LA Accredited - Certificate #2845.01
Initial report from 12/06/2022 18:54:37 http://www.EMSL.com mailto:cinnaminsonleadlab@emsl.com
| Report |
| Site Coordinates: 39.377667, -75.072444 |
| Photo Log 11-15-22- Millville (MIV) RCAG Facility Rehabilitation Project |
| Photo Log 11-15-22- Millville (MIV) RCAG Facility Rehabilitation Project |
| 042229751_coc |
| 042229751_conf |
| 042229751_002 |
| 202210533_coc |
| 202210533_conf |
| 202210533_001 |
File details come from the government source that posted it. Updated .