H
G
F
E
D
C
B
A
U.S. DEPARTMEf~T
FEDERAL AVIATION
OF TRANSPORTATION
ADMINISTRATION
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
DESIGN PLANS:
SALMON RCLT /
SALMON, IDAHO
AWOS UIS TOWER REPLACEMENT
SITE DRAWINGS:
DRAWING NUMBER TITLE
GENERAL
SMN-1305160-G001
CIVIL
SMN-1305160-C001
SMN-1305160-C002
SMN-1305160-C003
SMN-1305160-C004
DEMOLITION
SMN-1305160-D001
SMN-1305160-D002
STRUCTURAL
SMN-1305160-S001
SMN-1305160-S002
SMN-1305160-S003
SMN-1305160-S004
SMN-1305160-SOO 5
SMN-1305160-S006
ELECTRICAL
SMN-1305160-E001
SMN-1305160-E002
SMN-1305160-E003
SMN-1305160-E004
SMN-1305160-EOOS
SMN-1305160-E006
REFERENCE
NMSD-D-RCF-Q124
COVER SHEET, DRAWING INDEX & VICINITY MAP
GENERAL NOTES AND ABBREVIATIONS
EXISTING SITE PL.Ai~
PROPOSED SITE PLAN
MISCELLANEOUS DETAILS
PHASE I DEMOLITION SITE PLAN
PHASE II DEMOLITION SITE PLAN
STRUCTURAL GENERAL NOTES
FOUNDATION
TOWER ELEVATION AND CONNECTION DETAILS
TOWER PLATFORM DETAILS
HATCH, LADDER, AND DOWN CONDUCTOR DETAILS
TOWER PLATFORM STRUCTURAL DETAILS
SYMBOLS, LEGEND, NOTES AND ABBREVIATIONS
RF CABLE ROUTING & GROUNDING PLAN
ELECTRICAL DETAILS
CABLE SUPPORT ASSEMBLY ELEV A TION VIEW
LIGHTNING PROTECTION SYSTEM DETAILS
TOWER ANTENNA JUNCTION BOX LAYOUT
10 POSITION OFFSET, RIGHT ANGLE MOUNT
N-TYPE COAXIAL CABLE ADAPTER
7 6 5
4 3
4 3
N i , RANCHETTE
\ ROAD
LEMHI COUNTY
ROAD & BRIDGE
(SMN RCL T / AWOS SITE)
SALMON
AIRPOR=Tc----
VICINITY MAP
1- (f)
(f)
_J _J
I t') Ol ' (f)
I 2 r---.- 1 :\Iii LES
,-FAA LEASED PROPERTY
1 SMN RCLT/AWOS SHELTER
AND COMMUNICATIONS TOWER,
SEE EXISTING SITE PLAN
... ···-LEMHI COUNTY--·-··- - - -- /i:i"C:01, FOR DETAILS
._L __ c, ROAD & BRIDGE ---
L______j COUNTY YARD 1
7 \
AWOS-C CDP SITE MAP
REV APPROVED
DATE
NOT TO SCALE
FINAL
DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE APVD
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
RCLT
SALMON RCLT / AWOS SITE
UIS TOWER REPLACEMENT
COVER SHEET, DRAWING INDEX & VICINITY MA
SALMON
REVIEWED BY SUBMiTT~~.!3'( A
/ -;:C:<~P.--"- ·t:'/ .. t.--~--t-.<:.---~-.~
XIAO JUN 'MEI
PROJECT ENGINEER MGR: ENGINEERING - SEATTLE
DESIGNED XM i ISSUED BY DAT_E __ O 3/, ?~/ ,'leJt"f I JCN
... .. DRAWN ! ENGINEERING SERVICES DRAWING NO ; -
CHECKED . ":R'XM: INFRASTRUCTURE 1SMN-1305160-G001
2 1
ID
1305160
REV
H
G
F
E
D
C
' C
II
7i
Ag:
!;'.}i ' C
E " :ii w
G
F
E
D
C
B
A
8 7
ABBREVIATIONS
AB AGGREGATE BASE
ABDN ABANDON
AGG AGGREGATE
ALIGN ALIGNMENT
AWOS AUTOMATED WEATHER OBSERVING SYSTEMS
BLDG BUILDING
C CENTERLINE
CL CLASS
CLR CLEAR, CLEARANCE
CMU CONCRETE MASONRY UNIT
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUOUS
DC DIRECT CURRENT
DIA DIAMETER
DEB DIRECT EARTH BURIAL
E EASTING, EXISTING
EA EACH
EES EARTH ELECTRODE SYSTEM
EG EXISTING GRADE
ELEC ELECTRICAL
EL ELEVATION
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EX EXISTING
FAA FEDERAL AVIATION ADMINISTRATION
FF FINISHED FLOOR
GAL V GALVANIZED
GEOR GEOTECHNICAL ENGINEER ON RECORD
GPRS GROUND PENETRATING RADAR SYSTEMS
HDG HOT-DIPPED GALVANIZED
HDPE HIGH DENSITY POLYETHYLENE
HH HANDHOLE
IN
JB
LBS
LF
MAX
MIN
N N.I.C oc
PSI
PVC
PWR
R
INVERT
JUNCTION BOX
POUNDS
LINEAR FOOT
MAXIMUM
MINIMUM
NEW
NOT IN CONTRACT
ON CENTER
POUNDS PER SQUARE INCH
POLYVINYL CHLORIDE
POWER
RADIUS
RELATIVE COMPACTION RC
RCLT
RD
RADIO COMMUNICATION LINK TERMINAL
ROAD
RE
REINF
RGSC
SQ
ss
SSC
TEL
TEMP
TYP
VAR
V,J
WI
W/0
XFMR
RESIDENT ENGINEER
REINFORCEMENT, REINFORCING
RIGID GALVANIZED STEEL CONDUIT
SQUARE
STAINLESS STEEL
SYSTEM SUPPORT CENTER
TELECOMMUNICATIONS
TEMPORARY
TYPICAL
VARIABLE
WIDE
WITH
WITHOUT
TRANSFORMER
6 5
GENERAL NOTES
1. THE CONTRACTOR CONSTRUCTION SAFETY MANUAL SHALL COMPLY
WITH OSHA 29 CFR 1910 AND 29 CFR 1926.
2. LOCATIONS AND ELEVATIONS OF EXISTING FEATURES TO BE VERIFIED
BY FIELD MEASUREMENTS PRIOR TO CONSTRUCTION OF NEW WORK.
3. ALL DIMENSIONS ARE TO BE VERIFIED IN THE FIELD. ANY
DISCREPANCIES FOUND BETWEEN THE DRAWINGS AND SPECIFICATIONS
AND SITE CONDITION OR ANY INCONSISTENCIES OR AMBIGUITIES IN
THE DRAWINGS OR SPECIFICATIONS SHALL BE IMMEDIATELY REPORTED
TO THE RESIDENT ENGINEER (RE) IN WRITING, WHO SHALL CORRECT
SUCH INCONSISTENCIES OR AMBIGUITIES IN WRITING. THE CONTRACTOR
SHALL NOT PERFORM ANY WORK BEFORE VERIFICATION AND AFTER
DISCOVERY OF SUCH DISCREPANCIES, INCONSISTENCIES, OR AMBIGUITIES
WITHOUT WRITTEN RE AUTHORIZATION. ANY WORK PERFORMED BY THE
CONTRACTOR AFTER DISCOVERY OF SUCH DISCREPANCIES WITHOUT
PRIOR WRITTEN AUTHORIZATION BY RE WILL BE CONSIDERED TO BE
DONE AT THE CONTRACTOR'S RISK.
4. FINISHED GRADE SHALL BE SLOPED AT A UNIFORM SLOPE BETWEEN
SPOT ELEVATIONS.
5. ALL FILL MATERIAL SHALL MEET REQUIREMENTS AS OUTLINED IN THE
PROJECT SPECIFICATIONS.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT ALL
SLOPES ARE BUil T IN ACCORDANCE WITH THESE PLANS. IF THERE IS
ANY QUESTION REGARDING THESE PLANS, THE CONTRACTOR SHALL
REQUEST AN INTERPRETATION BEFORE DOING ANY WORK. THE
CONTRACTOR SHALL ALSO TAKE NECESSARY STEPS TO PROTECT
THE PROJECT AND ADJACENT PROPERTY FROM ANY EROSION AND
SILTATION THAT RESULT FROM THEIR OPERATIONS BY APPROPRIATE
MEANS, (SAND BAGS, TEMPORARY DESIL TING BASINS, DIKES, ETC.) UNTIL
SUCH TIME THAT THE PROJECT IS COMPLETED AND ACCEPTED BY FAA.
7. PRIOR TO ANY EXCAVATIONS UNDER THIS CONTRACT, THE
CONTRACTOR SHALL PERFORM GPRS UTILITY LOCATE TO IDENTIFY
ALL UTILITIES AT THE SITE. SUBCONTRACTOR SHALL POTHOLE AND
HAND EXCAVATE NEAR KNOWN UTILITY LINES TO PREVENT EXCAVATION
DAMAGE TO UNDERGROUND UTILITIES.
8. THE CONTRACTOR SHALL TAKE PRECAUTIONARY MEASURES TO
PROTECT WITHIN THE SITE, ALL UTILITY LINES, EXISTING PERMANENT
STRUCTURES AND ANY OTHER EXISTING LINES THAT ARE NOT OF
RECORD OR SHOWN ON PLANS. ANY UTILITIES OR STRUCTURES
DAMAGED DURING THE COURSE OF CONSTRUCTION SHALL BE
IMMEDIATELY REPAIRED AND/OR REPLACED BY THE SUBCONTRACTOR,
UNLESS APPROVED OTHERWISE BY THE RE, TO A CONDITION EQUAL
TO OR BETTER THAN THE EXISTING AND AS APPROVED BY THE RE.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING ANY
MONUMENT ATION AND/OR BENCHMARKS THAT ARE DISTURBED OR
DESTROYED BY CONSTRUCTION. SUCH POINTS SHALL BE REFERENCED
AND REPLACED WITH APPROPRIATE MONUMENT ATION BY A LICENSED
SURVEYOR AT THE CONTRACTOR'S SOLE EXPENSE.
10. THE CONTRACTOR SHALL SECURE ANY REQUIRED PERMITS FOR
CONSTRUCTION PRIOR TO THE ST ART OF CONSTRUCTION.
11. THE CONTRACTOR IS HEREBY NOTIFIED THAT ESSENTIAL AND
PERTINENT INFORMATION REGARDING THE CONSTRUCTION AND
COMPLETION OF WORK FOR THIS PROJECT IS CONTAINED IN THE
CONTRACT DOCUMENTS AND SPECIFICATIONS. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO READ AND REVIEW THIS INFORMATION TO THEIR
OWN SATISFACTION PRIOR TO PERFORMING ANY WORK. ANY DEFICIENT,
INCOMPLETE OR INCORRECT WORK SHALL BE REDONE TO MEET
REQUIREMENTS AT THE CONTRACTOR'S SOLE EXPENSE.
12. THE CONTRACTOR SHALL DESIGN, CONSTRUCT, AND MAINTAIN ALL
SAFETY DEVICES, AND SHALL BE SOLELY RESPONSIBLE FOR CONFORM.ING
TO ALL LOCAL, STATE, AND FEDERAL SAFETY AND HEAL TH ST AND ARDS,
LAWS AND REGULATIONS.
13. THE CONTRACTOR AGREES TO ASSUME SOLE AND COMPLETE
RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF
CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL PERSONS
AND PROPERTY. CONTRACTOR FURTHER AGREES THAT THIS REQUIREMENT
SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING
HOURS AND THAT THE CONTRACTOR SHALL DEFEND; INDEMNIFY AND
HOLD THE FAA HARMLESS FROM ANY AND ALL LIABILITY, REAL OR
ALLEGED IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS
PROJECT.
14. EXISTING VEHICULAR ACCESS TO SITE SHALL BE KEPT IN SERVICE
DURING THE COURSE OF CONSTRUCTION. THE CONTRACTOR SHALL
PREPARE A PLAN SHOWING PROPOSED LOCATIONS OF STAGING, STORAGE
OF MATERIALS, AND VEHICLES ON SITE TO BE SUBMITTED TO THE
RESIDENT ENGINEER FOR REVIEW, COMMENT AND/OR APPROVAL PRIOR
TO ST ART OF CONSTRUCTION. DUE TO LIMITED SPACE ON SITE,
CONTRACTOR SHALL COORDINATE WITH RE FOR ADDITIONAL AREAS
REQUIRED FOR MATERIAL AND EQUIPMENT STORAGE.
6 5
4 3
15. THE NORMAL ACTIVITIES WITHIN THE FACILITY WILL CONTINUE DURING
CONSTRUCTION. CONTRACTOR SHALL DEVISE A DETAILED WORK
SCHEDULE AND CLOSELY COORDINATE WITH THE RE FOR ALL
ACTIVITIES. THE CONTRACTOR SHALL USE GREAT CARE AND
CAUTION WHILE WORKING WITHIN THE EXISTING FACILITY
(SITE AND BUILDINGS) AS NOT TO DISRUPT THE FUNCTIONS OF
THIS FAA FACILITY.
16. IT IS ABSOLUTELY MANDATORY THAT THE CONTRACTOR PROTECT
ALL NEW AND EXISTING COMMUNICATION EQUIPMENT, ELECTRICAL AND
MECHANICAL EQUIPMENT, BOTH INSIDE AND OUTSIDE THE BUILDING
FROM DAMAGE.
17. STAGING AND STORAGE OF CONSTRUCTION MATERIAL AND EQUIPMENT
SHALL BE LIMITED TO THE CONSTRUCTION ST AGING AREA.
CONTRACTOR'S PARKING AREA SHALL BE DETERMINED AT THE
PRE-CONSTRUCTION CONFERENCE. MATERIALS SHALL BE NEATLY
STORED AND PROTECTED AT ALL TIMES. UPON COMPLETION OF
WORK THE CONTRACTOR SHALL RESTORE THIS AREA BACK TO
ITS ORIGINAL PRE-CONSTRUCTION CONDITION.
18. ALL CONSTRUCTION MATERIAL SHALL BE PREASSEMBLED TO AN
OPTIMUM SIZE AND WEIGHT TO MINIMIZE ACTIVITIES WITHIN THE FACILITY.
CONTRACTOR SHALL VERIFY ACCESS PATHWAYS WITH RE BEFORE
ST ART OF CONSTRUCTION.
19. WELDING REQUIRES A HOT WORK PERMIT. WELDING AND HEAVY
CONSTRUCTION SHALL BE DONE OUTSIDE IN TEMPORARY CONSTRUCTION
AREAS AS DETERMINED BY THE RE AND TO BE CLEANED UP AT THE
END OF THE DAY. CONTRACTOR SHALL PROVIDE THEIR OWN POWER
FOR THESE OPERATIONS. NO WELDING OR HEAVY CONSTRUCTION IS
PERMITTED INSIDE THE BUILDING AS IT MAY DAMAGE OR INTERFERE
WITH ELECTRONICS EQUIPMENT.
20. THE CONTRACTOR SHALL PROVIDE, OPERATE AND MAINTAIN THE
CONSTRUCTION LIGHTING NECESSARY TO ILLUMINATE THE AREA
ADEQUATELY FOR SAFE WORK. ALL LIGHTING SHALL BE SUBMITTED
TO AND APPROVED BY FAA BEFORE USE. UPON COMPLETION OF
CONSTRUCTION, REMOVE ALL CONSTRUCTION LIGHTING. ALL AREAS
AND SURF ACES DISTURBED SHALL BE REP AIRED OR REPLACED BY
THE CONTRACTOR.
21. ENCLOSED DUMPSTERS FOR DISPOSAL OF CONSTRUCTION DEBRIS
SHALL BE PROVIDED BY THE CONTRACTOR WITHIN AREA
DESIGNATED BY RE AT THE PRE-CONSTRUCTION MEETING. THE AREA
AROUND THE DUMPSTERS SHALL BE KEPT CLEAN AND FREE OF
EXCESS DEBRIS AND DUST DURING CONSTRUCTION. ALL DEBRIS
SHALL BE REMOVED BY CONTRACTOR.ANY WASTE THAT CAN
ATTRACT WILDLIFE SHALL BE REMOVED FROM THE SITE DAILY.
FAA DUMPSTER SHALL NOT BE USED BY CONTRACTOR.
CONSTRUCTION DEBRIS MUST BE REMOVED DAILY.
22. CONTRACTOR SHALL PROVIDE TEMPORARY UTILITIES DURING
CONSTRUCTION. VERIFY TEMPORARY UTILITIES LOCATIONS AND
USE AS PERMITTED BY RE.
23. THE CONTRACTOR SHALL PROVIDE SANITARY TOILET FACILITIES
WITH WATER FOR THE WORKERS AND RE.
24. THE CONTRACTOR SHALL PROVIDE TEMPORARY POWER FOR ALL
CONSTRUCTION ACTIVITIES. CONSTRUCTION TOOLS SHALL BE
POWERED FROM THE TEMPORARY POWER SOURCE ONLY. ALL
POWER TOOLS SHALL BE PRE-APPROVED BY THE RE.
25. THE CONTRACTOR SHALL ENSURE THAT ALL WALL PENETRATIONS,
NEW AND EXISTING ARE WATER SEALED. PROVIDE WATERTIGHT
ASSEMBLY FOR OPENINGS REQUIRING NEW SEALANT APPLICATION.
CONTRACTOR SHALL INFORM THE RE PRIOR TO INSTALLATION
OF WATERTIGHT ASSEMBLY.
26. SHUTDOWN AND CUTOVERS OF ENVIRONMENT AL AND ELECTRICAL
SYSTEMS SHALL BE PERFORMED BY FAA PERSONNEL AND NOT
BY CONTRACTOR. ALL PREPARATORY WORK FOR SHUTDOWN
AND CUTOVER SHALL BE SCHEDULED AND COORDINATED WITH THE
RE A MINIMUM OF 10 WORKING DAYS IN ADVANCE.
27. WHERE NEW WORK IS TO BE CONNECTED TO EXISTING WORK,
EXERCISE CARE NOT TO DISTURB OR DAMAGE EXISTING WORK.
28. THE CONTRACTOR SHALL PROVIDE 7-PIN REMOVABLE CORE
CORMAX BEST LOCK PADLOCKS FOR EACH LOCKABLE DEVICE,
EQUIPMENT, ETC. THIS INCLUDES EXTERNAL CABINETS, PANELS,
DISCONNECT SWITCHES, TOWER HATCH DOORS, ANTI-CLIMB
DEVICES, ETC. THE PADLOCKS SHALL BE SIZED APPROPRIATELY
FOR THE PARTICULAR EQUIPMENT AND USE. ALL PADLOCKS
SHALL BE DYE ST AMPED IN ACCORDANCE WITH FAA REQUIREMENTS
AND DISPLAY THE NUMBER PS1173X1175. THE LOCKS SHALL BE
EQUIPPED WITH CONSTRUCTION CORES AND A CONSTRUCTION CORE
REMOVAL KEY.
29. REFERENCE AS REQUIRED:
GEOTECHNICAL ENGINEERING REPORT DATED AUGUST 20, 2018 BY
MATERIAL TESTING & INSPECTION, MTI FILE NUMBER E180017G,
1230 N SKYLINE DRIVE, SUITE C, IDAHO FALLS, ID 83402
(208) 529-8242
• 4 3
2 1 i
HI
30. USE SACRIFICIAL LAYERS OF PROPER MATERIAL AT THE POINT OF
CONNECTIONS BETWEEN DISSIMILAR METALS OUTSIDE OF EQUIPMENT
ROOM WHERE IT APPLIES.
31. CONTRACTOR TO PROPERLY DISPOSE/REMOVE HAZARDOUS
MATERIALS IN ACCORDANCE WITH SPECIFICATION SECTION 02 82 00.
32. SEE DRAWING SMN-1305160-C003 FOR PROPOSED SITE PLAN AND
SMN-D-RCL T-D001 & SMN-1305160-D001 FOR SITE DEMOLITION
REQUIREMENTS. CONTRACTOR SHALL COORDINATE WITH RE FOR
PROPER REMOVAL AND TURNOVER OF TOWER ANTENNAS AND CABLES.
33. REPAIR DAMAGED GALVANIZATION PER SPECIFICATIONS
SECTION 09 97 00, SPECIAL COATINGS.
34. ALL HOT-DIPPED _GALVANIZED METALS SHALL BE PAINTED PER
SPECltlCATIONS SECTION 09 97 00, SPECIAL COATINGS.
FINAL
i I
---+----+-----------------+---+-----+--I
··--+----+-----------------t---+-----t---1 i JCN REV APPROVED
DATE DESCRIPTION
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE APVD
- ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
SALMON
REVIEWED BY
RCLT
SALMON
UIS TOWER REPLACEMENT
GENERAL NOTES AND ABBREVIATIONS
ID
G
F
E
D
C l :;i :
;i. '
~ I 0 -
0 i "' ' :, ' (I) i !!l I I
C, 0\ ~-I SUBMITTED BY,_ ./,' APPROVED BY '1/f>,_;7 f n_~<,:n:, /_/_., _ / 'r . .,.,-y,.,;,c,,', .
i 7 - -- / ' /- /'? ?_;i'ef¾'' / c7J/
,____~, ~,f~Jf6:c7ut ti£;=-·- -~, sauRADtr-t/'s%rsMA ~i
PROJECT ENGINEER MGR: ENGINEERING - SEATTLE A~! ------I ~,
DESIGNED XM i ISSUED BY DATE(;;;; 112-1 '2D!_°I I JCN - - 1305160 ?i
1------t---+o=RAwN - ENGINEERING SERVICES ~ii<ia- -~ Ei t---------+1----+,cc,-;HEc:;;cKE=-o ---,f½''-'11:"1-',,) ~~=-iM INFRASTRUCTURE SMN-1305160-C001 I R:v i:
wi
G
F
E
D
C
B
A
X
X
X
X
X
X
X
NOTES
G) 12'-0" X 12'-0" RCL T / AWOS SHELTER
0 AWOS HELIAX CABLE AND MICROWAVE WAVEGUIDE ICE BRIDGE
0 18" X 18" X 6" JUNCTION BOX
0 POWER METER
0 RCL T / AWOS TIMBER TOWER WITH PLATFORM
rc\ RCL T / AWOS TIMBER TOWER DIAGONAL
\.V BRACE MEMBER
0 RCL T / AWOS TIMBER TOWER GUY WIRE
fo\ PARTIALLY DEMOLISHED 16'-0" X 9'-6" CONCRETE v FOUNDATION WITH 8" WIDE BY 4'-0' DEE? PERIMETER FOOTING
0 PERIMETER FENCE
® 12' WIDE GATE
® RCL T / AWOS SHELTER WALL MOUNTED H\/ AC UNIT
@ 4" X 4" X 12" TINNED COPPER PLATE
@) CONDULET <COPPER WIRE)
X ------ X ---- X ---- X ---- X
UNDERGROUND TELE
/~ COMMUNICATION LINE
LEGEND
I I
I I
FENCE
EES
\ GRAVEL~
- - X
0--
X
SITE
TERMINATED
SITE EES
I i I I I I I I I I I I
I I I I I I I
2 1
X
X
X
X
X
- - - -----;x:-c--------=-----=-~=---::::-_ -~\ =x =-=------=-=--x-====-c:c.c:___=-1x --
EXISTING SITE PLAN
SCALE: NOT TO SCALE
UNDERGROUND
POWER CONDUIT
APPROX. 20" DEEP
\_0
FINAL
,_____,_, ----+---·-----·--- ______ ,..,..,,.-----------+---+---=:::-:::::----t-----J
REDUNE
REV i APPROVED DESCRIPTION JCN DATE DATE
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
ATO - TECHNICAL OPERATIONS WESTERN SERVICE
SALMON
RCLT
SALMON
UIS TOWER REPLACEMENT
EXISTING SITE PLAN
SUBMlTTEDBY 1 APPROVED BY ,,:;~:Y- i~'ll((' /~' _./
REV!EWED BY . / .- _/.: fr',/ , ,, ,..'-:.?§"· _ _/r?/l ,___ ___ 1.,.,,,-~-z;::,,e-.-,r_.,--r• .. / t-~-~c_::, __ ;=-= /" v.,;,~ ! ,A- r, <• '-I> lxtAO JUN MEI SOURADETH SAYSANA t------cl------J-P'..'..R'.'...O.:::JE-C=T ENGttliEE-R------+-M-G-R,-E-NGINEERING - SEATTLE
APVD
AREA
ID
DESIGNED ,ssuEo sv DATE cl'3J1 ?-''2b1'i I JcN
1-------+--+D-RA_W_N ---~X=,M ENGINEERING SERVICES DRAWING a .. -'---L----~~= 1305160
REV
>-----+--+--CH-EC-KE-D ---~,-""Y INFRASTRUCTURE SMN-1305160-C002
ft.' 1 'AZ i
2 1
H
G
F
E
D
C
.I.
"' 0 I,,.
Q uJ ::, !!l
C
-~1
" A@ m n
' C E' ~1 " 0
G
F
E
-t>
D
C
B
A
"'"""'"'-"" ''""""",''"'' ,,w- "''" """ ,, ""'-""'"""" "·""'"" -- ,,,-~_,.,,,,~~----
I 7 I 6 I 5 •
X X X X X X X X X X X
X ~ UNDERGROUND TELE -: L COMMUNICATION LINE,
i _ FIELD VERIFY
~~ / ----/- i
X
I•
X
X
X
X ,.
i I
-----<---· /.---"un-+i ------,,~--,s~;:---------,11-',---t-J l ----~ '------- L_j_ ___ -----JC.-------'1'-c-.,-"~~~--~----~
. -!\ GALVANIZED / HEAVY-DUTY
/ CHANNEL, .// \ ~ CLIP ANGLES,
-----------~n~___;-,_~=i_ __ L_C/ 1
• / ~iiTfRsi501 / 0--.__~ ~iiT:RCOA38
OR APPROVED "'--~ ? R APPROVED
_/ EQUAL _j ~QUAL
·------~-J
-~ 3 1/2" DIAMETER
- ..------+---------, ASTM A53 GRADE B,
-- --0 \
SCHEDULE 40 HOT
DIP GALVANIZED PIPE
WITH PIPE HEAD,
SITE PRO PART* 3174
AND SP509 OR
APPROVED EQUAL, SEE
DETAIL 1 ON SHEET
C004 FOR FOUNDATION
REQUIREMENT
4 I
X X I I
I X
X
X
X
X
X
I I
L------------ ----~u----[-- !T ______ _ \ L ____________ ~
~GRAVEL--~
,· 0·\.I ~ \CB
\ i X X X
L_ -------
Ii i I, i \ I I
I \
I X ----+\--- X ------------ X ------------ X ------- X ---- X ---- X -~ ' ' I
/'------ UNDERGROUND
POWER CONDUIT
\ APPROXIMATELY 20" DEEP,
. FIELD VERIFY, TO l BE PROTECTED AT ALL
TIMES
PROPOSED SITE PLAN 1 5 6 7 s g
SCALE: NOT TO SCALE
5 • 4
CD
(j)
I 2 r 1
NOTES
PREPARE THE SITE FOR NEW CONSTRUCTION, LOCATE AND SETUP
THE ST AGING AREA AND TEMPORARY FACILITIES. COORDINATE WITH
RE AND SSC. CONTRACTOR TO COORDINATE WITH RE FOR
ACCESS ROUTE AS NEEDED. VERIFY SITE UTILITIES BEFORE
ST ART OF EXCAVATION.
NEV\/ SELF -SUPPORTING TOWER
NEW 40' SELF-SUPPORTING TOWER FOUNDATION TO BE DESIGN
BY OTHERS. MAXIMUM PLAN DIMENSIONS OF 10' X 10'. THE
CONSTRUCTION OF TOWER FOUNDATION SHALL BE COMPLETE
AFTER PHASE I DEMOLITION.
PROVIDE A 40' SELF -SUPPORTING TOWER.
PROVIDE NEW ICE BRIDGE AND INTEGRATE INTO EXISTING ICE BRIDGE.
CONSTRUCT NEW ICE BRIDGE FOUNDATION AND RELOCATE EXISTING ICE
BRIDGE AS REQUIRED. COORDINATE WITH SSC AND RE.
DEMOLISH AND PROPERLY RECYCLE / DISPOSE EXISTING TIMBER
TOWER WITH DIAGONAL BRACE AND GUY WIRES, AFTER NEW
SELF-SUPPORTING TOWER HAVE BEEN CONSTRUCTED,
COMMISSIONED AND DEEMED ACTIVE. COORDINATE WITH RE AND SSC.
BACK FILL ALL HOLES CREATED BY CONSTRUCTION AND DEMOLITION.
COMPACT THE SOIL TO 951/. DENSITY AND PATCH THE AFFECTED
AREA TO MATCH EXISTING GRADE AND ADJACENT PAVING MATERIAL.
REMOVE ALL OBSOLETE MATERIAL AND DISCARD THEM PROPERLY.
COORDINATE WITH RE AND SSC.
SEE DRAWING SMN-1305160-D001 AND SMN-1305160-D002 FOR
DEMOLITION REQUIREMENTS.
SEE DRAWING SMN-1305160-E002 FOR GROUNDING AND BONDING
REQUIREMENTS.
LEGEND
-x-- FENCE
NEW CONSTRUCTION
FINAL
H
G
F
E
D
C
- -----+'- ------------------+-----+---------t-- -
1------1-------+-----------------------+----+----+-----I
REV APPROVED
DATE i DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE APVD
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
SALMON
REVIEWED BY
RCLT
SALMON
UIS TOWER REPLACEMENT
PROPOSED NEW SITE PLAN
'! ID
1305160
REV
C I w I :::, -f/l !!l I c•
'"' u:
n:
:Si
A~!
!{JC
01 ,,,, :;i E W!
8 I 7 I 6 I 5 • 4 I 3 I 2 ( 1
H H
11r- I z f--
I -- 0 --z
0 1·· 3 1/2" DIAMETER
.. GALVANIZED
z / ICE-BRIDGE COLUMN f-
X i - I - !
G w (Di G !
!/ I
I ' ' 0 ._i ,-- FINISHED GRADE f- I <(
2:. I I
/a D I-- i ' I!
i ,J Ii b b ~i 'I I, -- ! --
! I' ~
~11--·;- 0 ,, r--i ! i !-·-----
! ,------1, I" I =! i Ii I I 'i I
' I I I! : 'I _, I i I ' ! i ,: I ' D. b ,-----,i·''• I fl ~111111~' ,,
- t, b -- , I'~ - .... ; ,_
- ~: i _I--- / /
/) > L
F ./ i F b fl
L ,, 2 i i
I p D :::i / i \ 2 \ z b " \
-- 2 D b \ --
- b b
0 " > '
I " , \ -sq- i i
6 LI \ '
b b
'-- CONCRETE SHAFT
b 6
E i > E " I " ' /
I
!:, b
6 /~
= I b b n, i /
I ! D D _. ! I / /
~ I
I
L ____ b 5 ·t, l I 1'-0" . I i
MINIMUM
D I 1 ' ICE BRIDGE FOUNDATION D
\ I SCALE: 11/2" 1'-0" - = , -
C C
FINAL
REV APPROVED DESCRIPTION JCN REDLINE APVD
DATE. DATE
DEPARTMENT OF TRANSPORTATION
B FEDERAL AVIATION ADMINISTRATION
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
RCLT <I! ;.:;
SALMON ...
UIS TOWER REPLACEMENT 0
Q -- MISCELLANEOUS DETAILS w iil
SALMON - ID
SUBMITTED BY .... ~ /! APPROVED BY . /:1/;,f -;;- ;f., ./ )/ / C
REV!EWEDBY / /_,., ": I '" -,.,.,,,y~-t~i;,,~j ,· 't-/ ~
XJArJ~u-,/:~iT-"''"---- ,,,-, Yr , Z -,--- "· '· souRArluft" s~rsANA 0
--- A~ A
PROJECT ENGINEER MGR 0 ENGINEERING - SEATTLE
DATE-_-:,a [1'2 1·2f:1:[ IJCN "" DESIGNED !SSUEDBY 0
XM 130519_Q CJ
----- . ----·-- ENGINEERING SERVICES
V ... :1 -i ,:,,,1 le ,-------
DRAWN DRAWING NO REV [
XM INFRASTRUCTURE m
I CHECKED \,;)~\ AZ SMN-1305160-C004 - " 0
w
8 I 7 I 6 I 5 • I I
I 4 3 2 1
G
F
E
D
C
B
A
7 6 5 4 r X ---- X ----- X ---- X ---- X ---- X ---- X ---- X ---- X ---- X ---- X ---- X ---
X i X
X
X
X
X
X r- UNDERGROUND TELE -
// COMMUNICATION LINE,
FIELD VERIFY
SITE EES,
FIELD VERIFY~
/ " I , I i .
\ ~ UNDERGROUND
-J~
PHASE I DEMOLITION SITE PLAN~
SCALE: NOT TO SCALE
6 5
POWER CONDUIT
APPROXIMATELY 20" DEEP,
FIELD VERIFY, TO
BE PROTECTED AT ALL
TIMES
X
X
2 1
DEMOLITION NOTES
r,'\ PREPARE THE AREA FOR DEMOLITION AND PROTECT ALL EXISTING
\.V UTILITIES IN PREPARATION FOR CONSTRUCTION OF NEW 40'
SELF-SUPPORT RCLT / AWOS TOWER.
ICE BRIDGE
G) PROVIDE TEMPORARY SUPPORT FOR HELIAX CABLE AND WAVEGUIDE
ICE BRIDGE. RELOCATE ICE BRIDGE AS REQUIRED. COORDINATE WITH
RE AND SSC.
DECOMMISSIONED SHELTER AND FOUNDATION
N REMOVE REMNANTS OF DECOMMISSIONED SHELTER FOUNDATION.
\.::_) AND PREPARE SOIL PER GEOTECHNICAL RECOMMENDATION FOR
NEW SELF-SUPPORTING TOWER FOUNDATION.
SITE CLEAN-UP
0 REMOVE ALL OBSOLETE CABLES AND THEIR FITTING AND PATCH
THE PORTION OF WALL, CEILING AND FLOORING AFFECTED BY
THIS REMOVAL. COORDINATE WITH RE AND SSC.
("';'\ BACK FILL ALL HOLES CREATED BY CONSTRUCTION AND DEMOLITION.
\.::_) COMPACT THE SOIL TO 951/. DENSITY AND PATCH THE AFFECTED
AREA TO MATCH EXISTING GRADE AND ADJACENT PAVING MATERIAL.
("';'\ DISCARD ALL OBSOLETE MATERIAL PROPERLY. COORDINATE WITH
\V RE AND SSC.
LEGEND
-X FENCE
-··. -·-··- ··--· ---· -·- - EES
///// DEMOLITION
FINAL
I
REV APPROVED
DATE DESCRIPTION JCN
REDLINE
DATE
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
ATO - TECHNICAL OPERATIONS WESTERN SERVICE
SALMON
RCLT
SALMON
UIS TOWER REPLACEMENT
PHASE I DEMOLITION SITE PLAN
REVIEWED BY SUBM!TTED ~.t--· ~-- / APPROVED BY /,;"//~/_ )(;y·.h[_i /7 / 1--~-_, 4~.--:..·,:z_-::::.~-.--c.:.4-~-"'=---~=-- 11~~/f':'- .{/ii½)(¼ __ ,~~}
KIM JUN WEI SOURADETH SAYSANA
AREA
ID
,PROJECT ENGINEER MGR: ENGINEE~ING - SEATlJ_E __ ----.1
DESIGNED xM ,ssuED BY DATE O rz..J '2.!Jtc I JcN
1------+---+-D_RA_w;;··------- ---'---'--'-j ENGINEERING SERVICES 6iiAw1Nc.,,G +';,a--'--~'-+. ~----~~"'-I 1305160
REV
CHECKED 'f: i : INFRASTRUCTURE SMN-1305160-D001
2 1
H
G
F
E
D
C
-.i.
"' 0 C w !12
:,j
~I \.l 1 '. Ao, ~I m1 o, co ' C e co
G
F
E
D
C
B
A
7 6 5 4
--- X ----- X ---- X ---- X ---- X --------- X - --- X ----- X ~--- X ---- -- X ------- X --
X
~UNDERGROUND TELE-
/ COMMUNICATION LINE,
/ FIELD VERIFY
~:JCD E~~RIFY~ ------------------ --------- ---~
//_22 -- rrr,,z~~~¥H'/4~/4--rY 7/~~,~\, •/ /'-,~"..+-;fL,/'-,1'--;<'-,lf'-7"-.,,,.__,;L,,'-,lf'-r-c/',~'-r,i'-c/',l'-3/ m I
\-GRAVEL-~
X
----·-··"'""" __________ ---- // ----------- ----- ---~=======-=-=--=;-~-::r-.0T/f/7f/.T;r;1 \ ------- -------~-~/,.. ___. : \ /'-... _________ ,.,,, i
X
X
X
X
X
SITE EES,
FIELD VERIFY\
i /----- - / _,,.,,.~ ~ //
I \
I '
X ~---x----x-~
///~-~~/-:-~--to-;·----- \,
- -- - - 7 .......----\
/ ( \ '1 I
' . I
--l
\_ I •
I I i / _j ___ _-.,'
/ I \; L ________________ ___,,,_,__,,, I \ i I I
I
X
X
X
X
X
-~ I /
---~ x---~--+\---~=-:·--------=~----~-------=~--;-~--J __ ------- x--_-__ ---_ x ----- x - _ _j
X i I
-J-
PHASE II DEMOLITION SITE PLAN~
SCALE: NOT TO SCALE
6 5
UNDERGROUND
POWER CONDUIT
APPROXIMATELY 20" DEEP,
FIELD VERIFY, TO
BE PROTECTED AT ALL
TIMES
2 I 1
DEMOLITION NOTES
r;\ PREPARE THE AREA FOR DEMOLITION AND PROTECT ALL EXISTING v UTILITIES_ PHASE II DEMOLITION SHALL COMMENCE ONLY WHEN
THE NEW RCL T / AWOS TOWER HAS BEEN CONSTRUCTED,
COMMISSIONED AND DEEMED ACTIVE.
EXISTING TIMBER TOWER
0 VERIFY WITH RE AND SSC THAT TOWER IS DECOMMISSIONED.
r,'\ REMOVE ALL ANTENNAS, AIR TERMINALS, JUMPER CABLES, \::!_} GROUNDING WIRES, MICROWAVE DISH, AND MAIN COAXIAL CABLES
FROM TOWER. COORDINATE WITH RE AND SSC ON DISPOSITION
OF ANTENNAS AND MICROWAVE DISH. REFER TO SPECIFICATION
SECTION 02 41 31.
0 SECURE TOWER THEN REMOVE GUY WIRES AND DIAGONAL BRACES.
® SAFELY DISMANTLE AND PROPERLY RECYCLE / DISPOSE TOWER.
r:;'\ REMOVE TOWER AND GUY WIRE FOUNDATION A MINIMUM OF
\.V 12" BELOW GRADE.
ICE BRIDGE
0 PROVIDE TEMPORARY SUPPORT FOR HELIAX CABLE AND WAVEGUIDE
ICE BRIDGE. RELOCATE ICE BRIDGE AS REQUIRED. COORDINATE WITH
RE AND SSC.
SITE CLEAN-UP
REMOVE ALL OBSOLETE CABLES AND THEIR FITTING AND PATCH
ro\. THE PORTION OF WALL, CEILING AND FLOORING AFFECTED BY
\.V THIS REMOVAL. COORDINATE WITH RE AND SSC.
r;:;'\ BACK FILL ALL HOLES CREATED BY CONSTRUCTION AND DEMOLITION.
~ COMPACT THE SOIL TO 951/. DENSITY AND PATCH THE AFFECTED
AREA TO MATCH EXISTING GRADE AND ADJACENT PAVING MATERIAL.
Q.. DISCARD ALL OBSOLETE MATERIAL PROPERLY. COORDINATE WITH
\..'V RE AND SSC.
LEGEND
- X -------
FENCE
EES
DEMOLITION
FINAL
i 4-----+-------------------,------t-------i-, REV APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE APVD
A TO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
SALMON
REVIEWED BY
RCLT
SALMON
UIS TOWER REPLACEMENT
PHASE II DEMOLITION SITE PLAN
ID
PROJECT ENGINEER MGR, ENGINEERING - SEATTLE
--+--+=o=Es=1GN=E~D ------,---IS-SU_E_DB=Y----t;o=ArE03 /';2. f']-,;:);'1 JCN 1305160
---i--------r-=DRAWN- ----~XM ENGINEERING SERVICES DRAWING NO -- ---+--~----,=Re=v
CHECKED l ~:,) :~ INFRASTRUCTURE SMN-1305160-D002
2 1
H
G
F
E
D'
C
:s
H
G
F
E
D
C
B
A
8 7 6
GENERAL NOTES:
A. CODE AND DESIGN REQUIREMENTS:
1. ALL WORK INCLUDING BUT NOT LIMITED TO STRUCTURAL SHALL BE IN ACCORDANCE
WITH THE LATEST REQUIREMENTS OF TIA ST Ai'-IDARD, TIA-222-H EFFECTIVE JANUARY
1, 2018. "STRUCTURAL STANDARDS FOR STEEL ANTENNA TOWERS AND ANTENNA
SUPPORTING STRUCTURES."
2. ALL TOWERS SHALL BE SELF -SUPPORTING. THE DESIGN VERTICAL AND LATERAL
LOADS SHALL INCLUDE THE EFFECTS OF THE CABLES AND OTHER APPURTENANCES
ATTACHED TO THE TOWER.
3. ALL TOWERS SHALL BE CLASSIFIED AS TYPE Ill - ESSENTIAL COMMUNICATION.
4. ALL TOWERS SHALL BE ANALYZED IN ACCORDANCE WITH NONLINEAR <P-LARGE
DELTA) METHOD.
5. SEISMIC ANALYSIS PROCEDURE METHOD SHALL BE IN ACCORDANCE WITH EQUIVALENT
LATERAL FORCE PROCEDURE (METHOD 1). SITE CLASS D, IMPORTANCE F ACTOR=1.5,
Ss=0.522, S1 =0.159, SEISMIC DESIGN CATEGORY=D.
6. WIND EXPOSURE CATEGORY C.
7. • MINIMUM BASIC WIND SPEED = 120 MPH (3 s;::c GUST, SERVICE) e IMPORTANCE FACTOR WITHOUT ICE = 1.15.
8. ICE THICKNESS = 1/ 4 INCH.
9. PLATFORM LIVE LOAD REQUIREMENT UNIFORM: 100 LBS/ SQ. FT CONCENTRATED:
500 LBS/ONE SQ. FT.
10. TOWER MANUFACTURER SHALL DESIGN AND COORDINATE THE LOCATIONS OF TOWER
PLATFORM, J-BOX, TOWER HATCH, LIGHTNING PROTECTION, SWING ARM MOUNTS, AND
OTHER APPURTENANCES SO AS NOT TO INTERFERE WITH EACH OTHER.
8. STRUCTURAL STEEL:
1. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN
ACCORDANCE WITH THE 14th EDITION OF AISC STEEL CONSTRUCTION MANUAL. STEEL
TUBING OF ANY KIND IS NOT ALLOWED. SUBMIT CERTIFIED MILL TEST REPORTS TO
SUBSTANTIATE REQUIRED PROPERTIES AND ACTUAL MODULUS OF ELASTICITY.
2. THE PROVISIONS OF TIA-222-H SHALL GOVERN IN THE EVENT THAT CONFLICTS
ARISE BETWEEN THE AISC AND TIA-222-H. IF HOWEVER THE TIA-222-H DOES NOT
INCLUDE PROVISIONS OR REQUIREMEN1S THAT WILL FACILITATE THE STEEL
CONSTRUCTION THEN THE PROVISIONS OF AISC WILL GOVERN.
3. ALL STRUCTURAL STEEL SHALL BE HOT DIP GALVANIZED IN ACCORDANCE WITH
ASTM STANDARD A123. THE GALVANIZING SHALL BE APPLIED AFTER FABRICATION.
WELDING IS NOT PERMITTED AFTER THE APPLICATION OF THE GALVANIZING. FIELD
APPLIED GALVANIZING FOR REPAIRS SHALL MEET THE REQUIREMENTS OF ASTM
A-780 USING ZINC-BASED ALLOYS WITH SURFACE PREPARATION PER ANNEX A1.
4. STRUCTURAL STEEL FOR PLATES, ANGLES, CHANNELS SHALL CONFORM TO ASTM
A36, EXCEPT AS OTHERWISE NOTED. WIDE FLANGE SHAPE SHALL CONFORM TO ASTM
A992.
5. ANCHOR BOLTS SHALL MEET OR EXCEED THE REQUIREMENTS OF ASTM F1554-S2,
S5 GRADE 105 AND SHALL BE TIGHTENED TO A SNUG TIGHT CONDITION, <FULL
EFFORT OF A MAN USING AN ORDINARY SPUD WRENCH). ANCHOR BOLTS SHALL BE
HOT DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A153.
6. ALL BOLTS SHALL BE ASTM A325, HOT DIPPED GALVANIZED IN ACCORDANCE WITH
ASTM /\153, HIGH STRENGTH SOL TS UNLESS OTHERWISE NOTED. THE MINIMUM BOLT
DIAMETER SHALL BE 3/8".
7. ALL BOLTS INCLUDING ANCHOR BOLTS SHALL HAVE LOCKING/JAM NUTS 11\JSTALLED
AFTER TORQUING THE STRUCTURAL BOLT.
8. COLUMN BASE PLATES, CAP PLATES, BEARING PLATES, CONNECTION PLATES, AND
STIFFENER PLATES SHALL BE WELDED ALL ,'\ROUND.
C. REINFORCED CONCRETE:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO THE LATEST EDITION OF ACI 301
AND ACI 318. ALL CAST-IN-PLACE STRUCTURAL CONCRETE SHALL BE IN ACCORDANCE
WITH ACI AND SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF F' C =4000 PSI
AT 28 DAYS (NORMAL WEIGHT).
2. REINFORCING STEEL - ALL DETAILING, FABRICATION AND ERECTION OF REINFORCING
BARS, UNLESS NOTED OTHERWISE, SHALL BE IN ACCORDANCE WITH THE MANUAL OF
STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES (ACl315), LATEST EDITION.
3. ALL REINFORCEMENT SHALL BE NEW BILLET STEEL, DEFORMED BARS, CONFORMING
TO ASTM A615, GRADE 60 WITH A MINIMUM YIELD STRENGTH OF FY = 60000 PSI.
SPLICES IN REINFORCEMENT SHALL NOT BE ALLOWED UNLESS OTHERWISE INDICATED.
4. CONCRETE COVER - CONCRETE CLEAR COVER FOR REINFORCING BARS SHALL BE
AS FOLLOWS:
a. CONCRETE CAST AGAINST GROUND - 3"
b. CONCRETE IN CONT ACT WITH GROUND OR EXPOSED TO WEATHER - 2"
c. CONCRETE NOT PERMANENTLY EXPOSED TO GROUND OR WEATHER - 11/2"
5. EXPOSED EDGES OF CONCRETE SHALL BE CHAMFERED 3/ 4" X 3/ 4" MINIMUM.
8 7 6
5 4 • .
C. REINFORCED CONCRETE <CONT'D):
6. TOP OF FOUNDATION EXPOSED TO WEATHER SHALL BE SLOPED FROM THE CENTER
TO THE OUTSIDE EDGE A MINIMUM OF 1/4" PER FOOT. PROVIDE A FLOATED FINISH.
7. CONCRETE SHALL BE PLACED AGAINST UNDISTURBED SOIL WHEN FOUNDATION IS
BEARING ON SOIL.
8. CONCRETE SHALL BE PLACED IN A MANNER THAT WILL PREVENT SEGREGATION OF
CONCRETE MATERIALS AND OTHER OCCURRENCES WHICH MAY DECREASE THE
STRENGTH OR DURABILITY OF THE FOUNDATION.
9. LOOSE MATERIAL SHALL BE REMOVED FROM BOTTOM OF EXCAVATION PRIOR TO
CONCRETE PLACEMENT. SIDES OF EXCAVATION SHALL BE ROUGH AND FREE OF
LOOSE CUTTINGS. IN THE EVENT THAT THE SIDES DO NOT REMAIN VERTICAL THE
CONTRACTOR FORM THE SIDES.
10. WELDING IS PROHIBITED ON REINFORCING STEEL AND EMBEDMENTS.
11. MAXIMUM AGGREGATE SIZE SHALL NOT EXCEED 3/4".
12. FLOAT FINISH TOP OF PAD FOOTINGS WHEN EXPOSED TO VIEW.
D. EXCAVATION AND FOUNDATION:
1. ESTABLISH BENCHMARKS ON SURROUNDING STRUCTURES AND PAVEMENT PRIOR TO
ANY EXCAVATION AND IDENTIFY AND PROTECT ANY EXISTING UNDERGROUND
UTILITIES, LINES OR OBSTRUCTIONS.
2. COORDINATE, MAINTAIN AND PROVIDE A SAFE ENVIRONMENT DURING TRENCHING,
EXCAVATION, AND COMPACTION IN ACCORDANCE WITH OSHA SAFETY MANUALS. IN
TRENCHES WHERE DEPTH EXCEED 4 FEET, SUBCONTRACTOR SHALL SUBMIT A
DETAILED PLAN TO THE RE FOR APPROVAL SHOWING DESIGN OF SOIL AND
RETENTION SYSTEM PREPARED BY A PROFESSIONAL ENGINEER LICENSED IN THE
ST ATE OF CONSTRUCTION. ALL WORK SHALL BE IN ACCORDANCE WITH THE
GEO TECHNICAL REPORT.
3. FOUNDATION FOR THE TOWER SHALL BE DESIGNED IN ACCORDANCE WITH THE
RECOMMENDATION OF THE GEOTECHNICAL REPORT AND SIGNED AND SEALED BY A
REGISTERED ENGINEER IN THE ST ATE OF CONSTRUCTION.
4. THE BACKFILL SHALL BE PLACED IN 8" LAYERS AND COMPACTED TO 951/. OF
MAXIMUM DRY DENSITY AT OPTIMUM MOISTURE CONTENT IN ACCORDANCE WITH
ASTM D698. ADDITIONALLY, STRUCTURAL BACKFILL MUST HAVE A MINIMUM
COMPACTED UNIT WEIGHT OF 100 POUNDS PER CUBIC FOOT.
5. EXISTING UTILITIES SHALL BE VERIFIED PRIOR TO THE CONSTRUCTION/EXCAVATION
OF CONCRETE PADS, FOUNDATIONS AND DUCTBANKS.
E. LADDER SAFETY SYSTEMS (LSS) SHALL BE PROVIDED IN ACCORDANCE
WITH THE FOLLOWING:
1. MEET REQUIREMENTS OF ANSI A14.3-2008, INTERIM CONSENSUS ST AND ARD
REQUIREMENTS RELATED TO BACKWARD LOADING FALLS AS RELEASED IN 2009, AND
FAA SAFETY EMERGENCY NOTICE SEN-15-07.
2. THE RESPECTIVE LADDER SAFETY SYSTEMS SHALL BE INSTALLED PER THE
MANUFACTURER'S INSTRUCTIONS. EACH LSS INSTALLED SHALL EXTEND THE MAXIMUM
ALLOWABLE DISTANCE ABOVE THE TOP LADDER RUNG, AS SPECIFIED IN THE LSS
MANUFACTURER'S INSTALLATION DRAWINGS AND/OR INSTRUCTIONS.
3. PROVIDE TWO FALL ARRESTER TROLLIES PER SITE.
4. SUBMIT SHOP DRAWINGS OF THE SYSTEM AND PRODUCT DAT A FOR APPROVAL.
5. MSA DYNA GLIDE IS THE ONLY APPROVED PRODUCT.
F. GROUNDING - THE MATERIALS USED FOR THE GROUNDING SYSTEM
SHALL BE COMPATIBLE WITH THE TOWER MATERIALS. THE GROUNDING
AND CONDUIT SHALL BE PLACED AS SHOWN ON THE ELECTRICAL DWG:
1. LIGHTNING PROTECTION AIR TERMINAL SUPPORT PIPE SHALL BE DESIGNED FOR ALL
APPLICABLE LOADS INCLUDING SEISMIC AND WIND, AND PROVIDED BY THE TOWER
MANUFACTURER. SUBMIT DESIGN CALCULATIONS FOR REVIEW PRIOR TO
MANUFACTURE. GUARDRAILS SHALL BE DESIGNED TO SUPPORT LARGEST LOADS
FROM THE AIR TERMINAL SUPPORT PIPES.
G. THE LADDER AND HATCH ENTRY INTO THE ANTENNA TOWER WORK
PLATFORMS SHALL MEET THE FOLLOWING REQUIREMENTS:
1. THE LADDER SHALL BE INSTALLED INSIDE OR OUTSIDE OF THE TOWER FRAME AND
ATTACHED DIRECTLY TO ONE SIDE OF THE TOWER STRUCTURE; THE LADDER SHALL
EXTEND UP THROUGH THE WORK PLATFORM.
2. THERE SHALL BE A SINGLE HATCH DOOR (APPROX. 30-INCHES X 30 INCHES)
INSTALLED AT THE HATCH OPENING. THE LADDER SHALL NOT IMPEDE THE HATCH
OPENING CLEAR SPACE.
3. THERE SHALL BE A PERMANENT "ANCHORAGE ASSEMBLY" INSTALLED DIRECTLY
BEHIND THE LADDER (I.E. AT THE BACKSIDE OF THE LADDER) ONTO THE WORK
PLATFORM FLOOR; THE ANCHORAGE SHALL HAVE AT LEAST A 5,000 POUND RATING
IN ANY DIRECTION WHICHEVER IS THE MORE SEVERE FOR DESIGN AND THE "D-RING"
ANCHOR WILL BE SOLID AND NOT A ROTATING TYPE. SUBMIT ANCHORAGE ASSEMBLY
CALCULATIONS FOR REVIEW CLEARLY SHOWING THE LOAD PATH AND RESISTANCE
BY SUPPORTING FRAMING. CALCULATIONS SHALL BE APPROVED PRIOR TO
FABRICATION.
4. THE ANCHORAGE SHALL BE INSTALLED AT A POSITION TO ACT AS A "REST" FOR
THE SINGLE HATCH DOOR, AND TO ALLOW FOR THE HATCH DOOR TO REST AT A
70-DEGREES POSITION AGAINST THE ANCHORAGE ASSEMBLY WHEN IN THE OPEN
POSITION.
5 • 4
3 2
G. THE LADDER AND HATCH ENTRY (CONT'D):
5. THE ANCHORAGE ASSEMBLY SHALL BE 42" HIGH AND BE DESIGNED TO HAVE THE
SMALLEST "FOOTPRINT" AT THE WORK PLATFORM FLOOR AS POSSIBLE TO ALLOW
FOR THE MAXIMUM CLEARANCE DISTANCE BETWEEN THE INSTALLED ANCHORAGE
AND THE PLATFORM PERIMETER GUARDRAIL; THAT CLEARANCE DISTANCE SHALL NOT
BE LESS THAN 24 INCHES.
6. THE HATCH DOOR WILL BE CONSTRUCTED OF A RELATIVELY LIGHTWEIGHT STEEL
FABRIC/MESH WITH A MINIMUM OF 3 STRUCTURAL JOIST WITHIN THE DOOR FRAME
(I.E. INCLUDE ONE MEMBER IN THE MIDDLE OF THE DOOR FRAME); THE HATCH DOOR
SHALL HAVE A MINIMUM STRENGTH REQUIREMENT OF 250 LBS/SF.
7. THE FORCE REQUIRED TO OPEN THE SINGLE HATCH DOOR SHALL NOT EXCEED 15
LBS; PRIOR TO FINAL FABRICATION TOWER PROVIDER WILL PRESENT TEST
DOCUMENTATION ON THIS TO THE PROJECT ENGINEER THAT INDICATES THIS
REQUIREMENT IS MET.
8. THE HATCH DOOR HINGES SHALL 8E HARDWARE SOURCE SPECIAL TY HINGE 5/16"
DIAMETER TWO PIECE STEEL WELD-ON HINGE FOR EXTERIOR USE. PROVIDE
MULTIPLE HINGES TO SUPPORT THE RATED PLATFORM LIVE LOAD. IF A DIFFERENT
LIKE/EQUAL HINGE IS USED INSTEAD, THAT DESIGN WILL NEED TO BE FORWARDED
BY TOWER PROVIDER TO THE PROJECT ENGINEER FOR APPROVAL PRIOR TO FINAL
FABRICATION.
9. TO AVOID STRESS TO THE DOOR HINGES AND ALLOW FOR A SOLID PLATFORM FOR
WALKING, THE HATCH DOOR FRAMEWORK SHALL HAVE A CONTINUOUS ANGLE AT
BOTH SIDES THAT "RESTS" ON THE STRUCTURAL STEEL THAT IS PART OF THE
FRAMEWORK OF THE HATCH OPENING AT THE PLATFORM FLOOR; THE OUTSIDE
ANGLE OF THE HATCH DOOR FRAME SHALL REST FULLY ON THE HATCH OPENING
FRAMING. WELDED ON "TABS" AT THE PLATFORM HATCH DOOR WILL NOT BE
ACCEPT ABLE.
10. THE TOP OF EACH LADDER SIDE RAIL SHALL BE ROUNDED TO PROVIDE A SMOOTH,
SNAG- FREE FINISH AT THE TOP OF THE LADDER SYSTEM.
11. THE INSTALLED LADDERS SHALL BE OSHA COMPLIANT ST AND- OFF LADDERS.
12. DURING LADDER INSTALLATION, THE VERTICAL ORIENTATION OF THE LADDER SHALL
BE POSITIONED SO WHEN THE LADDER MEETS THE WORK PLATFORM FLOOR THE
LADDER RUNG CLOSEST TO THE PLATFORM FLOOR WILL NOT POSE A TRIP HAZARD;
AMPLE TOE CLEARANCE AT THE WORK PLATFORM FLOOR WILL BE REQUIRED AT
ALL LADDER INSTALLATIONS.
FINAL
-----+-----+---------------1-------+------+-----i
'------....,-------1--------------------+----+--------1------1
REV APPROVED
DATE DESCRIPTION JCN REDLINE
DATE APVD
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
SALMON
REV1EWEDBY
RCLT
SALMON
UIS TOWER REPLACEMENT
STRUCTURAL GENERAL NOTES
PROJECT ENGINEER MGR, ENGINEERING - SEATTLE
DESIGNED xM I 1ssuEosv DATEo;:;_,,fr2-.tn .. 4'J. ;Jj. 1 JCN _
ID
DRAWN ---= 1 ENGINEERING srnv1cEs DRAWING NO -r ··"---- --- 13051feS . /CHECKED qJtill:-1 INFRASTRUCTURE SMN-1305160-S001 -
2 1
H
G
-i
F
E
D
Ci
C' ~· -01 ~o;
0• m
A~I "', o:
E
G
F
E
D
C
B
A
MINIMUM 8 11 CLEAR
TO LADDER RUNG
w O'.:
C)
:c (j) z
LL
w co
<D r t / '\ I
" , I
TOWER ELEVATION
SCALE: 3/8" = 1'-0"
ALL TOWER FACES SIMILAR
S003 w O'.l
O'.:
LL
I-- __J o_
LL
o_ 0 - I--
-' 0 0 I-- "SI- z
I--z
LL
LL
o_ I--
5 4
10'-0" MAX ___________________ c.:..___ ___________ __c_:_ ________ ~---------'
BY TOWER MANUFACTURER/ OTHERS
"' 0
' 0 Q
!!f .
O,.o "
"(' " // 0v
'01,- " " / 1)·
V
0 " "('
(j) O'.:
w :c 1---
X O'.:
<( w 2 O'.:
= 1---
0. o _1 ! <(
Oi LL z 4.
2 ~/
'l,/
"" '0-1,-
O'.:
w I--l~r~
" • 0 "--
O'.l
TOWER FOUNDATION PLAN
SCALE: 3/4" = 1'-0"
ENTER FOUNDATION 24"
MINIMUM BELOW GRADE,
OR DEPTH OF FOUNDATION
IF LESS
-1-----,---,\ ------+
- EXOTHERMIC WELDS
(TYPE RR CADWELD
OR EQUAL)
FOUNDATION EDGE -------- --.1 ~ . ---------
4/0 AWG EES
CONDUCTOR 24"
BELOW GRADE
(TYPICAL) ___ __._./
A E002
I '•"" -----+--::,,- ·· FOUNDATION AND
/ REINFORCING STEEL
SEE STRUCTURAL
I '-~----..L............j DRAWINGS FOR
FOUNDATION DETAILS
L--4/0 AWG BARE COPPER CONDUCTOR
EXOTHERMICALLY WELDED TO EES
AND MAIN HORIZONTAL REBAR
STEEL (TYPICAL 2 PLACES OPPOSITE
SIDES)
FOUNDATION GROUNDING DETAIL
NOT TO SCALE
2 1
NOTES:
1. FOUNDATION DEPTH SHALL BE A MINIMUM OF 4'-0" OR
EXTEND 6 11 BELOW THE REQUIRED FROST DEPTH OR ADJUST
FOR STABILITY, WHICHEVER IS GREATER.
2. FOUNDATIONS AND SOIL CRITERIA SHALL BE BASED ON
GEOTECHNICAL REPORT.
3. THE DIMENSIONS SHOWN ARE APPROXIMATE. HOWEVER,
DUE TO THE LIMITATION OF THE SITE, THE MAXIMUM
SIZE OF THE FOUNDATION IS 10'-0" X 10'-0" IN PLAN.
4. PROVIDE HDG BEAM CLAMP OR UNISTRUT HOG P1001 UNIT
SECTION AT INTERVALS TO SUPPORT CABLES. COORDINATE
LOCATION WITH CABLE LAYOUT. THE UNISTRUT CLAMP SHALL
BE HOG STEEL.
FINAL
REV APPROVED
DATE DESCRIPTION JCN
REDLINE
DATE Af'VD
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
SALMON
RCLT
SALMON
UIS TOWER REPLACEMENT
TOWER ELEVATION & FOUNDATION
ID
REVtEWEDBY SUBMITTED BY / APPROVED BY /J //( (i.~ ,,'(/./; / 1
~ ... ~~.,:,--. / 1/ ~ h{//-;- .?\,;{//;'//...· tl,, X!Aif~:Jui.f J:rE1 ce.-• SOURADBrl"'sAYSANA
-+-------!..:'lp"'..:'.R.':::'OJ':'..E_'CT~ENGINE"ER MGR: ENGINEERING - SEATTLE '----1-------'.:.:.:..: ·~----·--·c.=c==:..:..,.....----
XM ISSUED BY DATED? I :z. ie., I"/ JCN l---f-----4-DRA_W_N ___ --'O"'--j ENGINEERING SERVICES DRAWING N ' .
DESIGNED
INFRASTRUCTURE SMN-1305160-$002 XM
i CHECKED
2 1
1305160
REV
H
G
F
E
D
C cl ~TI
N
" A~
ITT
n
' C
E
~' B:
G
F
E
N
D
C
B
A
I,.
• 0
1·· I I I I I I I I I I I I I I ' I I I I I I I I I I
!"0 I ' r---- I
I I I I I I I I n1 I i I
! i_+ •
"v
0 '),.-
L2 X 2 X 1/4
I I I I
SPLICE
I L4 X 4 X 3/8 I I I I I I I I I I I I I
I l- - 1 _J I • L2 X 2 X 1/4
. , ·r I
~I
!"0 r----
CD
a
I I I I I I I ' I I I I I I I I I I I I I I I
1 5'-8"
ELEVATION O TO 20 FEET
SCALE: 3/ 4" = 1'-0"
ALL TOWER FACES SIMILAR,
BASE PLATE NOT SHOWN FOR CLARITY
'tj-
' l
O'.}
' co
N
= i !"0L
!"0
O'.}
CD
-co
TOWER PLATFORM BEAM,
SEE S004 FOR PLATFORM DETAILS --
I I I I I I I I I I I I I I I I I I I I
I I I I I I I I I I I I I I I I I I I a a
I I I I •• 0 0
I •• I
L2 X 2 X 1/4
SEE DETAIL 4
L2 X 2 X 1/4
L2 X 2 X 1/4
ELEVATION 20 TO 40 FEET
SCALE: 3/ 4" = 1'-0"
ALL TOWER FACES SIMILAR
SEE DETAIL 1
L2 1/2 X 2 1/2 X 1/4
I I i ;-L4
I I I I I I I I I I I I I
X 4 X 3/8
--- SEE DETAIL 2
O'.} tD
0...
I-
~I ~I I , 5'-8" r---------··-.. ·--------~----·-------- ---- 4"
I
I i 2" 'i '---
I - ' ro I 1 --------~------------------
- I
I
1"
,7,, --ct_
0 \ I
~--BRACING
E
BRACING DETAIL
SCALE: 11/2" = 1'-0'
1/2" DIA
A325 HEX BOLT
WITH DOUBLE NUT
-TOWER LEG
SECTION E-E
SCALE: 11/2" = 1'-0"
L2 1/2 X 2 1/2 X 1/4
DIAGONAL MEMBER
Hi
G
L3 X 3 X 1/ 4 - / '
STEEL SHIM PLATE
BETWEEN DIAGONAL
MEMBER, CUT TO FIT
F
5/8" DIA ___ /
HEX BOLT
SECTION A-A
5/8" DIA
HEX BOLT, TYP
SCALE: 1/2" = 1'-0"
ALL SECTION SIMILAR
(4) 1/2" DIAMETER = .r-C6 X 10.5
"------- L2 1/2 X 2 1/2 X 1/ 4
DIAGONAL MEMBER
A325 HEX BOLT N N
WITH DOUBLE NUTS---\ ;= i:=
/ PLATFORM BEAM
SECTION B-B
SCALE: 3" = 1'-0"
l===,i=\;===:e:=i=, :ec==d I o I o o
I l
3/4" 1 1/ 2 "
~TOWER COLUMN
L4 X 4 X 3/8
TOWER PLATFORM TO
COLUMN CONNECTION DETAIL
SCALE: 11/2" = 1'-0'
TOWER LEG
C4l 1/2" DIAMETER
A325 HEX BOLT
-- C6 X 10.5
WITH DOUBLE NUTS-\
TOWER COLUMN \
L4 X 4 X 3/8 \
/ PLATFORM BEAM
j
SECTION C-C
SCALE: 3" = 1'-0"
E
D
(8) 1/2" DIAMETER
A325 HEX BOLT
L4 X 4 X 3/8 !"0
,------ SPLICE PLATE
SEE DETAIL 3
WITH DOUBLE NUTS-'-- r-SPLICE PLATE
/ SEE DETAIL 3
j
= '=rl-.....':O'----.c:'.3:.:./ 41:__",$
SPLICE DETAIL
SCALE: 11/2" = 1'-0'
3" 0~: c3/4 "TYP co
0 0 ---1/4" THICK
O O I PLATE
0 0
1 1/ 2 "
SPLICE PLATE DETAIL
SCALE: 11/2" = 1'-0'
L4 X 4 X 3/8-_/ J 3 " [_ SPLICE PLATE
SEE DETAIL 3
SECTION D-D
SCALE: 3" = 1'-0"
FINAL
REV APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
REDLINE
DATE APVD
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
RCLT
SALMON
UIS TOWER REPLACEMENT
TOWER ELEVATION AND CONNECTION DETAILS
SALMON ID -
C
.;I a:
0 ...
0 w ::, fl!
REVIEWED BY SUBMITTED BY !/ APPROVEDBY ////)' )(11:/;.1/. /' §-
,____~~-___, xfAa::.tfFttlftF~:-- SOURALJE1~1:r~1v;~~ ,/ ~I
!PROJECT ENGIN'==EE=R--------IMGR: ENGINEERING - SEATTLE A~'
.--c=~~'-'r---'---'------.-=--=--'---==---------1 ~ ! ISSUED BY DATE A f::l.)Zjj,' (. JGN g
1-------+-------+=-I oRA=wN~------'x~M i ENGINEERING SERVICES oRA£;;, · ' .. L.....----' 1=30=5~~ev=i0 cHEcKeo cf/J. ~I INFRASTRUCTURE SMN-1305160-S003
DESIGNED
2 1 i5
H
G
F
E
D
C
B
A
0 0
O'.) 0)
A
I
1'-8" ; --·· ..... ---l- --~
8'-0" ----------------1 i I
AIR TERMINAL SUPPORT
PIPES NOT SHOWN, ,
SEE ELECTRICAL DRAWINGS ---i---~
1'-8"
WELD NUTS TO ARM <TYP)
/ PROVIDE SPACERS TO ALLOW
/ EASY SWING ARM ROTATION
/ (TYP)
+ I
11/4" GRATING __ y · I I
,,I
I II
______ , I ____ i1= -- 11 ., ' I I I 1' 3" I ' I -
• I
' - I - -- - - ~ -,- -
: : j 1'-3"
O'.)
LO
O'.)
I ' -----4---- -----------:------ ' I I I
I -~~-
_.--- TOWER COMM
_..---- J-BOX MOUNTED
TO HANDRAIL
l I ! .,-,------
- ---;~-~-~===t~==~9L_=1Jlf ~;<:'=-1--;-~~-.--~--~-~--:--L--j~:;;:::-;_-.1---t·_-==----3 .. ""'· J;: x· ~::;::
\::c======-+t-/____1.
1'-8"
1- PROVIDE LENGTH OF ARM AS NEEDED
TO SATISFY AN 8'-0" MINIMUM
DISTANCE BETWEEN ANTENNAS I
D
N
L_ / I /ii
TRIM GRATING
I i ' I
I j i
I
I i
I I
EXTEND LADDER
AND SAFETY RAIL
ABOVE PLATFORM LEVEL~
HSS 6 X 4 X 3/8
HOLLOW STRUCTURAL
SECTION & 5000 LB
LOAD IN ANY DIRECTION.
ADD BRACING AS
NEEDED FOR ST ABILITY
_...-..,------------ ~~~6~~N A T~ic~~~g~L~~OR
K( ,~\ I
70° \ \ \
AROUND LADDER SAFETY RAIL
TO ALLOW THE HATCH TO
FULLY CLOSE. THE NOTCH
SHALL BE AT LEAST 1/ 4"
LARGER IN PLAN DIMENSION
FOR EACH ORTHOGONAL
DIRECTION OF THE LADDER
SAFETY RAIL AND SHALL
ALLOW THE HATCH DOOR
TO EASILY OPEN WITHOUT
MPEDANCE FROM THE
LADDER SAFETY RAIL.
I \\ \ i'--1 I ii I
• \__HATCH
I
I
I"")
' -~-l ~ oi _i !
I
$ T /LADDER AND
T /SAFETY RAIL
' I ! I ' __l i ,,-TOP OF
I / GRATING
1 / PLATFORM
,~i ~ '~==!!::::;;'ir_.----"'-----"---"--p--{
I '\
~ \ \_BLOCK OUT FOR CABLES NOT
' I
UNISTRUT P1000
X 10" LONG
PLATFORM RAIL ------------
UNISTRUT P1000
X 10" LONG~
F
PLATFORM RAIL---,---~ /
'° ' UNISTRUT P1000 n
X 10" LONG~
y ----" i i----11/4" GRATING I -·
NOTE: NOT ALL MEMBERS ARE
SHOWN FOR CLARITY
(Y, VERTICAL LADDER
WITH SAFETY RAIL
FOR CLIMBING
\ci;' AROUND STIFFENER j'
PLATE AS NEEDED -- , 2'-6 1/ 4" (MIN)
: 7" CLEAR
\ SHOWN. KICK PLATES NOT SHOWN
-~EXTEND GRATING AROUND OPENINGS
TO REDUCE GAP TO LESS THAN
B PLATFORM SECTION
BLOCK OUT FOR CABLES TO
JUNCTION BOX. PROVIDE SUPPORT
FOR ALL FOUR EDGES, AND PROVIDE
A KICK PLATE ALL AROUND. +
y 8'-0" j'
-~-1\ r-·-··r··--, -- V I :
PLATFORM PLAN
SCALE: 1/2" = 1'-0"
I i
I !/~ WASHER
-A ----·---· - --- - ----- ~--1- I /! : // ___ l /1" I
: l //,/ \ : // I
~ A ·,,, ,11// / lA_ "'°,_, I ,.>' I
~ t r I 1 1 · ;: ,- 111_,,li!l\!\\i,\_,., 1, ~ r0: l 11 I' '" ~ I \ ri~'cc:i--y~:' i ~, I \ I '. . ~
~ . Ni \'~ r I i',i J __ --~-~j I : ~"--- 5/8" DIAMETER HIGH STRENGTH
J ~-c. --' I I - ASTM A325 BOLT NUTS, AND i I I WASHER HOT DIP GALVANIZED I• 2 15/16" ., I
D DEE -RING CONNECTION
NOTES: SCALE: 6" = 1'-0"
1. MSA BOLT D - RING WITH HOLE PART
No. 10003213 RATED TO SUPPORT A 5 KIP LOAD
2. SUBCONTRACTOR TO PROVIDE PRODUCT LITERATURE
TAG PERMANENTLY ATTACHED TO THE D-RING.
3. PRODUCT LITERATURE SHALL STATE THAT THE
PRODUCT HAS BEEN TESTED AND PASS ED APPLICABLE
ANSI REQUIREMENTS FOR FALL PROTECTION TIE-OFF.
7 6
~------ NOTES:
1. ANTENNA MOUNT BRACKETS (TYP. OF 8).
2. ALL MEMBERS AND CONNECTION
COMPONENTS SHALL BE HD GALVANIZED.
3. SEE STRUCTURAL STEEL NOTES ON DWG
S001.
4. MOUNTS SHALL BE RETRACT ABLE.
V 3/16"
11/4" GRATING~\ ~
' I
E
/ 3116 ,, v ( 3 SIDES
~L3 X 3 X
10" LONG
1/ 4
WELDED TOE PLATE
CONTINUOUS
~ - PLATFORM FRAMING
CONNECTION TO GUARDRAIL
SCALE: 3" : 1'-0"
5 4
------------------f------j-G,__ SCALE: 11/2" : 1'-0"
TO CENTERLINE OF RUNG (MIN)
1", SEE ALSO OSHA REGULATIONS
NOTE: NOT ALL MEMBERS ARE SHOWN FOR CLARITY
A r r -=
PLATFORM SECTION
SCALE: 11/2" = 1'-0"
ANTENNA MASTS
r-TOP OF
/ PLATFORM GRATING
' I
I /SWING ARM
r I t" • • " • i I ,_ I=
I I= I== = I - ' "' ~-~·· - • • . . '
I I I
I I = = I s ;
/ TOE PLATE, TOP OF
I 4" ABOVE TOP OF
I
II
I =
I ,...
PLATE r·
GRATING
I=
-I _.,- EXTEND 12" AS F/ REQUIRED TO
MEET THE FAA
ANTENNA SUPPORT -+-- REQUIREMENTS
I (TYP)
C PLATFORM ELEVATION FINAL S005 SCALE: 1/2" = 1'-0"
- : -------------v- I ;-u N I s T R u T
.+--~ ~-,!+,, __l J 3 I 16" :'rn1
F
11---+~, ,w4J_j ,'1r;=;t;;::=, ~...,..,, \___RAIL ANGLE
LIGHTNING MAST
CONNECTION TO GUARDRAIL
SCALE: 3" = 1'-0"
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
SALMON
RCLT
SALMON
UIS TOWER REPLACEMENT
TOWER PLATFORM DETAILS
APPROVED BY / .tW±-->:d~,1/) / 1 /
!Ip' IP'i½r 1-, A,ui.,1 ,::C-' Yi.t;1 <:'., C ~
SOURADETH SAYSANA
PROJECT ENGINE'.ER ----+-MG_R_:~EN~Gc-ciN=EERING - SEATTLE
DESIGNED
ID
ISSUED BY DATE (>"'2\ rzj ~tt, l 'JCN 1305160 ,____,_--+-DRA_WN _____ XM---J ENGINEERING SERVICES f-=cDRA=cw=1N=Gcct---+--, ~~-----,-;;;RE=.-;1v
INFRASTRUCTURE SMN-1305160-S004 XM
CHECKED
2 1
H
G
F
E
D
C
I
·c
H
G
F
E
D
C
B
A
PLATFORM
EXTERIOR RAILING-·~
Ct_ OF LADDER
I RUNG
MINIMU:'~
~~ARANCE ~ i 1 ;---LADDER
I • 11 3/4"
~ -···· .. . ---+l ·r.h + I '
' ! 1--------------'-- .J.•
L6 X 6X 3/8 ······
I
RUNG
'I j
I
HINGE
1 ·· (TYP)
I
L2 1/ 2 x 2 1/ 2 X 1/ :~~~ -------..._
1 1/ 4" GRATING-----
EDGE OF ANGLE_/
AND GRATING
PARTIAL PLAN PLATFORM HATCH OPENING
SCALE: 1 1/2" = 1'-0"
GATED END STOP-~
r<J sci-
", ! n .1 1 i ii I , i: ... -------: ! ~:::=c=::::J i I
$ T /LADDER AND
T /SAFETY RAIL
I i- ···-··-- ','---+------ LADDER ARREST ' I I i! SYSTEM SEE NOTE E
I ' 1 , DRAWING S001
i~·::::-~ ... -.. -_.-... .:-J I ·-=-..c=='.:
I ! 1i
I i I
I
I
I i
I I ' I , i !
' I
I i ~~~·,_! __ _.., I f----- --- - -- i '1----·-
I 1
I i I
I
'-----'I ' ' I
I . I
I i I I
' I ' I I ii I
1: I 1: I I I ,r--11/4 GRATING
I, ,I I / I . . ! I I I I !: . . . . j_Ec[= ... = ... = .. = .. =~==3=j!=cjc' ='''==='= l'!i,::::,,f'=li ====li'==='il=~'I ====i'=='='= 11=~1, ===="'==='=11="'=111
• 1· !, . I ' '1: .---~ ---, :: I i I i e--------AJ----·····L-;1··----1-++---+--+---~···------------~ j :; I I I
CHANNEL /
C6 X 10.5 __/
3/4" DIA. STEEL
RUNGS, KNURLED OR
NON SLIP FINISH
PLUG WELD TO SIDES·····
/i !J i I~ -------· -- li "'~"=-~-"-....,i+,i _____ 1_'-_3_"--11--i---.,,_!' ii 7cli i cCC~ '
,: I, i I\ , i I I \ ii I' I \.__L2 1/2 X 2 1/2 X 1/4 (MIN) ii EQ : I I EQ p... i ,······-·-·- .~" " " " ( r "' _, I i: ,:
,i
, Ii
1, ....uv-11- _L /\_ -- ___j__:\ _,__
\__ SAFETY RAIL
A LADDER ELEVATION
SCALE: 11/2" = 1'-0"
6 5
28R DOWN
CONDUCTOR ··\ \\
--··BRACKET L4 X 4 X 3/8 X 6"
/ LONG OR DIAGONAL TABS,
LOCATE BRACKET TO CLEAR
CONNECTION OF TOWER
DIAGONAL MEMBER
. / :/ TOWER ANGLE
(COLUMN)
(SIM, ROTATED) &.
OR \
(SIM, ROTATED) L0 \
_,.,,,--- LADDER ~ \
,.,., AND \
EB .\
OPENING IN GRATING WITH \
TOE KICK PLATE FOR HELIAX
CABLES AND POWER CONDUIT-·\
30" WIDE COMM J-BOX \
MOUNTED ON HANDRAIL\ I
I I I I I I I I I I
\ i I I
/\_. 1--
\_. \,JO /
. --¼-/
WAVEGUIDE I \
COMMUNICATION CABLES
SUPPORTED BY BEAM CLAMPS
(4l - CABLES
(1/2" MAX HELIAX)
/ L2sRT DOWN i CONDUCTOR
I (SIZE, SPACING, QUANTITY, AND
LOCATION ARE REPRESENTATIVE
ONLY, SEE ELECTRICAL DRAWINGS)._.
BRACKET L4 X 4 X 3/8 X 6" LONG j
LOCATE BRACKET TO CLEAR
CONNECTION OF TOWER DIAGONAL MEMBER --
TOWER ANGLE
OR DIAGONAL TABS ··-
TOWERJ
ANGLE
D
I _, E
PLATFORM PARTIAL PLAN
SCALE: 1" = 1'-0"
CADWELD WELDED
DOWN CONDUCTOR
\.....L4 X 4 X 1/4" MIN OR
4 X 1/ 4" MIN STRUCTURAL
PLATE WELDED TO EDGE OF N
\J'--L-3-1-16-·· -< SEAL WELD
DOWN CONDUCTOR SUPPORT DET~L
SCALE: 3" - 1'-0"
;-SECURING CLAMP
// DOWN CONDUCTOR
~IP_ 3/8 X 4 X 5 1/2"
PROVIDE INTERMEDIATE
PLATE
3;15:
SEAL WELD
GROUNDING BRACKET DETAIL
SCALE: 3" = 1'-0"
2 1
NOTES:
1. FOR GENERAL NOTES SEE DWG $001.
2. DOWN CONDUCTOR SUPPORT BRACKETS:
A. PROVIDE BRACKETS PER DETAIL D AND E AT 3'-0"
MAX. SPACING FULL HEIGHT OF TOWER TO SUPPORT
CONDUCTOR.
B. PROVIDE ONE BRACKET PER DETAIL D AT EACH TOWER
MSECTION FOR "CADWELD".
C. PROVIDE INTERMEDIATE BRACKET PER DETAIL E AS
REQUIRED TO SUPPORT DOWN CONDUCTORS AT 3'-0"
SPACING.
/BRACKET AND
/ CADWELD
TOWER FRAMING 1
/// ffi r
+I
CD
I sci-
~---- \ 1--:~~~ f -----------~~ -=-=-----
I
-~ 0
/~~~o
I r<J
~ ,.....--TOWER COLUMN
// CONNECTION
/DOWN CONDUCTOR
,/ +I
TO BE MODIFIED TO
SUIT SPECIFIC TOWER
CONFIGURATION
B DOWN CONDUCTOR TOWER CONNECTION
SCALE:NOT TO SCALE
FINAL
I---+----········-······---------
APPROVED
DATE DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL A VIA TI ON ADMINISTRATION
REDLINE
DATE APVD
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
RCLT
SALMON
UIS TOWER REPLACEMENT
H
G
F
E
D
C
HATCH, LADDER AND DOWN CONDUCTOR DETAILS;
SALMON
REVIEWED BY ' SUBMITTED!;.----:_~ .4 ~ APPROVED BY Lh>:t-- _u1 ll,/;,_ . ., /1 /
____ -- . _________ , ~,~ ::-~rt::f.;_f:>;: ___ //_t. __ _ -"'?-~ ::::.·,..,,. 1/ vt!A £/n:4t._,/ ~-t1i1 . ' .. " (
1-----' ·-- XIAO JUN M: I SOURADETH SAYSANA
PROJECT ENGINEEF<. jMGR: ENGINEERING - SEATTLE DESIGNED ISSUED BY : DA TE,,,.,,? ( 'l f '20 IQ I JCN
DRAWN XM ENGINEERING SERVICES ! DRAW;~t/; '.::.l-C/ ~· ++c..i· ---
CHECKED (. , : 1 INFRASTRUCTURE 1SMN-1305160-S005
2 1
ID
1305160
REV
!12
C
" ,o
A~ ;;;
"' C
E m
:i
G
F
E
D
C
B
A
C6 X 10.5, PLATFORM
FLOOR FRAMING,
9'-0" :------· -·------- ----------- _,, _______ -
STEEL GRATING AND ,
GUARDRAILS ARE NOT ' 2'-0" 1'-11" 1'-8"
SHOWN FOR CLARITY -~ i 1-·--- --------"-
.~_:_-=---------1
-~~ _ I ! I \\ "'"'--•• n::::;::;;::::::;:;~11:;;;;;::;::=;::;;::::~' ====+=====*::;::::==::;;;::;:~;;=====~~- \ \ "' Lr :i I ~ \\"','"- I ! I I I 1\\\ 1,,~,~II I I I I I \ \ -~ r- I i I I
\ I J ~-"- F""""=--=I N \ 'r--7111t-="~~~.:::..:::-:J-_!=..:::-:.:::}1..:::-:.:::}~:.:::.:::..:::-:.:::_':jj!II ,___ __ _,.I _1 \ I I I ,..A....._ I n
1 I I ,./ A 1,. I I '---H-4-....:..:...-~, I
I :
1 - I
I 1~==~=~==========~==~~~======~dlt---_-~1:~~ I u 11
I I i i ~:;;;;::;;;;;::;;jll - · I i I I I i = I I = ct- --- I--------- l-1 ·--- - , --- --ri - -1 - ,~---111+ - ---·-·1·- ~
,-=-,=-··-==== : ,/ ~ ! I \ \ \ I F---====<1·! l-----+-
1 :i1:Ft, ==:=:::::::::=::~~~~±,·:::--r±::Jil 1
I I!,// \ \ \, Ii : ~ I /J \ I I N
I ; ' '-/ I I I ~~ - · I I f---------1•1 t-----+
, ' I I I tt I r-;-
I \
I ' I I
I I ' I I I I
I ' I
I \
I I
Q)
II I I -
!I I I ~ t------'--.L 11
\ I I
II '
/ I L6 X 6 X 3/8 __/ /
TOWER COLUMN___/
I q;_
' L_HSS 4X6X1/4
~w6X15
PLAN PLATFORM STRUCTURAL FRAMING
SCALE= 3/ 4" = 1'-0"
-:/=LADDER
1 L3 X 3 X 1/4 I
~L3 X 3 X 1/4
I I I
I 1 L3 X 3 X 1/4
I I n ' i ' ' ' I -
' 0) I i
I i
B "\.. "~ - /
ELEVATION PLATFORM STRUCTURAL FRAMING
SCALE: 3/ 4" = 1'-0"
I r·-5" X 1/4" THICK
1 KICK PLATE
I 11/4" STEEL GRATING
I I
-tj- co ~ " N
I L ~
I
I ~
I C6 X 10.5 _j f
' J
I
/L4 X 4 X 3/8
/ ANGLE PLATE
II ;- C6 X 10.5
I
\__(4) 1/2" DIA
HEX BOLT
/ A"' TYPICAL BEAM CONNECTION
SCALE= 3" = 1'-0"
r-L4 X 4 X 3/8
/ ANGLE PLATE
' I ,-L3 X 3 X 1/4