This document outlines a federal contract opportunity for construction services at Isle Royale National Park. The US Department of Transportation is seeking to repair and expand the Rock Harbor dock to accommodate vessels and address congestion. Services required include marine construction work, removal and replacement of existing decking and infrastructure, installation of new pilings and structures, and upgrades to fuel and electrical systems. The project location is the Rock Harbor dock on Isle Royale in Lake Superior, and the estimated value is between $1 million to $5 million. The solicitation number will be 6913G621R200006 and will utilize NAICS code 237990 with an SBA size standard of $36.5 million. The acquisition will be set aside for small businesses as a 100% small business set aside. The contract type will be firm fixed price awarded to a single contractor.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

100% DESIGN - FOR REVIEW ONLY

A

C C

A

B

A A

A

B

B

C

C

BB

C

C

AA

D

D

E

E

G

G

F

F

H H

AA

AA

AA

B

B

A A A A

B

B

B

B

A A

AA BB

CC

EXISTING WASTEWATER

PUMP STATION

EXISTING

SIGN

EXISTING FUEL

MANHOLES

EXISTING 2 EACH 2" SINGLE

WALLED DIESEL AND GASOLINE

FUEL LINES BENEATH

CONCESSIONS DOCK

EXISTING 2 EACH 2" DOUBLE

WALLED DIESEL AND GASOLINE

FUEL LINES BURIED BELOW GRADE

EXISTING DIESEL AND GASOLINE

FUEL DISPENSERS ON

CONCESSIONS DOCK

EXISTING WASTEWATER

PUMP FOR SMALL BOATS

VISITORS

CENTER

C O

N C

ES

SI

O N

S

ST

O R

AG

E

4" HOSE FOR EMERGENCY

WASTEWATER PUMPING TO BE

PROVIDED BY CONTRACTOR

REMOVE EXISTING 2" DOUBLE

WALLED DIESEL FUEL LINE AND

4" GALVANIZED STEEL CASING

PIPE FROM SIDE OF DOCK

PROVIDE 2" DOUBLE WALLED DIESEL

FUEL LINE IN 4" SCHEDULE 10

STAINLESS STEEL PIPE EMBEDDED IN

CONCRETE DECK SLAB

REFER TO STRUCTURAL

DRAWINGS FOR REMOVAL

AND REPAIR TO CONCRETE

DECK SLAB

4" QUICK CONNECTION TO THE

RANGER III DOCK EXTENSION

WALKWAY EXTENSION

4"SAN

3"FM

EXISTING PLUMBING

DRAIN LINE

EXISTING FORCE MAIN TO

WASTEWATER TREATMENT PLANT

SEWER CONNECTION

SEE SHEET M501

GASOLINE SPILL BOX

SEE SHEET M501

DIESEL SPILL BOX

SEE SHEET M501

EMERGENCY WASTEWATER PUMPING:

A. USE WASTEWATER PUMPS ON THE RANGER III TO PUMP TO THE

WASTEWATER PUMP STATION THROUGH A FLEXIBLE 4" HOSE.

B. THE WASTEWATER PUMP STATION LEVEL MUST BE CLOSELY

MONITORED AND COORDINATED WITH OPERATION OF THE

WASTEWATER PUMP ON THE RANGER III TO PREVENT AN

OVERFLOW.

C. THE 4" HOSE CONNECTIONS MUST BE MONITORED TO PREVENT

LEAKS OF RAW WASTEWATER ONTO PUBLIC WALKWAY AREAS.

D. THE 4" HOSE MUST BE COMPLETELY DRAINED OF WASTEWATER,

CLEANED, ROLLED UP, AND STORED AFTER EACH USE.

E. CONTRACTOR SHALL PROVIDE FLEXIBLE 4" HOSE AND OUTDOOR

STORAGE CONTAINER. CONTRACTOR SHALL FIELD VERIFY THE

ACTUAL REQUIRED LENGTH BASED ON FINAL LOCATIONS OF

CONNECTIONS (ASSUME 250' FOR BIDDING).

REMOVE EXISTING PLASTIC SPILL

BOX FOR GASOLINEREMOVE EXISTING PLASTIC SPILL

BOX FOR DIESEL

CONNECT TO EXISTING 2" THREADED

GASOLINE AND DIESEL FUEL LINES

SCALE: 1"=10'

MECHANICAL PLAN

1"=10' 0' 10' 20' 30'

4" THREADED ELBOW

4" THREADED

VENT PIPE

4" WOVEN

POLYESTER HOSE

THREADED SWIVEL

CONNECTION

4" QUICK HOSE CONNECTIONS

CONCRETE WASTEWATER

PUMP STATION ±1000

GALLONS CAPACITY

4"Ø SCHEDULE 10

STAINLESS STEEL PIPE

±12" TO 16"

CONCRETE

DECK

DIESEL CABINET SPILL BOX

(DESIGN BASED ON OPW

MODEL 211)

STONE FILL

WOOD

CRIBBING

4"

SUMP PENETRATION

(SEE DRAWING M501)

2" 90 ELBOW TO ALUMINUM

CAM & GROOVE COUPLER

TRANSITION BOX

(SEE DRAWING M501)

NOTES FOR SPILL BOXES:

1. SUPPORT PIPE AND VALVES INSIDE SPILL

BOXES.

2. SEAL ALL PIPE PENETRATIONS THROUGH THE

BOXES WITH FLEXIBLE BOOTS.

3. COMPONENTS MUST BE COMPATIBLE WITH

DIESEL AND GASOLINE AND RESISTANT TO

CORROSION.

34"

CLAMSHELL

FITTING

CLAMSHELL

90° ELBOW

FLEXIBLE ENTRY BOOT

(SEE DRAWING M501)

4"Ø SCHEDULE 10

STAINLESS STEEL PIPE

WITH 2" DIESEL LINE

FROM DIESEL CABINET

SPILL BOX

±12" TO 16" CONCRETE DECK

GASOLINE CABINET SPILL

BOX (DESIGN BASED ON

OPW MODEL 211)

2" CHECK VALVE

2" BALL VALVE

STONE FILL

WOOD

CRIBBING

4"

SUMP PENETRATION

(SEE DRAWING M501)

2" 90 ELBOW TO ALUMINUM

CAM & GROOVE COUPLER

TRANSITION BOX

(SEE DRAWING M501)

34"

CLAMSHELL

FITTING

CLAMSHELL

90° ELBOW

FLEXIBLE ENTRY BOOT

(SEE DRAWING M501)

EXTEND 2" THREADED PIPES FOR

DIESEL AND GASOLINE THROUGH

THE BACK OF THE BOX AND DOWN

TO CONNECT TO THE EXISTING

THREADED PIPES.

2" BALL VALVE

2" CHECK VALVE

4"Ø SCHEDULE 10 STAINLESS

STEEL PIPE CASING, EXTEND

1" INSIDE OF BOX FOR

ATTACHING FLEXIBLE BOOT

±12" TO 16"

CONCRETE

DECK

TOP OF WOOD

CRIBBING WITH

STONE FILL

3/8"Øx4" STAINLESS STEEL

HEADED BOLTS

(TYPICAL AT 12" ON CENTER

ALL AROUND BOX)

REMOVE CONCRETE AND

REPAIR IN ACCORDANCE

WITH STRUCTURAL PLANS

4"Ø SCHEDULE 10

STAINLESS STEEL PIPE

4"x2"x1/4"THICK

STAINLESS

STEEL CHANNEL

1/4"

±34"

3/8"Øx4" STAINLESS STEEL

HEADED BOLTS SET AT 6"

FROM BOTTOM OF BOX

(TYPICAL AT 12" ON CENTER

ALL AROUND BOX)

HANDRAIL

1/4" THICK

STAINLESS STEEL

PLATES (TYP)

BACK OF DOCK

TOP ANGLE NOT

SHOWN FOR

CLARITY TO SHOW

HEADED BOLTS AT

BOTTOM OF BOX

±2 1"

1/4" 4"

1/4" 1/4"

AA

COORDINATE TRANSITION

BOX DIMENSIONS WITH THE

DIESEL FILL CABINET

DIMENSIONS

4"

LIGHT POLE AND CONDUIT

(SEE E401)

6"

8"

FLEXIBLE ENTRY BOOT WITH

HARDWARE MOUNTING FROM

TOPSIDE BY PIPING

MANUFACTURER

SCALE: NONE

SUMP PENETRATION DETAIL

AIR STEM FOR

PRESSURE TESTING

BAND CLAMP

DOUBLE-WALL

PIPING

DOUBLE-WALL

FLEXIBLE PIPING

DOUBLE WALL COUPLING

WITH TEST PORT

UNION

SINGLE-WALL

THREADED PIPING

SPACER

CABINET BOTTOM

BAND CLAMP

BAND CLAMP

FLEXIBLE

RUBBER BOOT

CASING PIPE

DOUBLE WALLED

FUEL PIPE

SCALE: NONE

SEWER CONNECTION

SCALE: NONE

SECTION A-A

SCALE: NONE

TRANSITION BOX

SCALE: NONE

DIESEL SPILL BOX

SCALE: NONE

FLEXIBLE ENTRY BOOT

SCALE: NONE

GASOLINE SPILL BOX

01 01

01 01 01 01

01 01

05 04 07

09 09

VISITORS

CENTER

ST

O

R

AG

E

SIGN

MAIN ELECTRICAL RACK -

WITH SHORE POWER

DISCONNECT AND

PANELBOARD 'B'.

PHOTOCELL FOR DOCK LIGHTS

MOUNTED ON ELECTRICAL RACK

PROVIDE WITH TYPE III

DISTRIBUTION, 3' MOUNTING

ARM, AND ZERO DEGREE TILT

TO MAIN

ELECTRICAL RACK

TO MAIN

ELECTRICAL RACK

4'-9"40'-3"79'-9"

LOCATE BASE PLATE

6" FROM EDGE OF

DOCK (TYP OF 3)

3'-10"

'-8

SCALE: 1"=10'

ELECTRICAL PLAN

1"=10' 0' 10' 20' 30'

01 DEMOLISH LIGHT FIXTURE AND POLE. REMOVE WIRING AND CONDUIT BACK

TO FIRST LIGHT POLE. RETAIN WIRING BACK TO MAIN PANEL.

02 DEMOLISH NAVIGATION BEACON AND POLE. RETAIN WIRING.

03 DEMOLISH SHORE POWER CONNECTION. DEMOLISH CABLES BACK TO MAIN

ELECTRICAL RACK. RETAIN CONDUIT.

04 REMOVE PHOTOCELL AND DUPLEX RECEPTACLE. RETAIN FOR RELOCATION.

REMOVE CONDUIT BETWEEN RECEPTACLE AND PHOTOCELL, AND

PHOTOCELL CONDUIT FITTING.

DEMOLITION NOTES #

01 PROVIDE LIGHT FIXTURE AND POLE. PROVIDE 2#12 + 1#12 GROUND IN

EXISTING CONDUIT BETWEEN LIGHT POLES.

02 PROVIDE NAVIGATION BEACON AND POLE. CONNECT TO EXISTING CIRCUIT.

03 PROVIDE SHORE POWER CONNECTION EQUIPMENT AND WIRING BACK TO

MAIN ELECTRICAL RACK. SEE SHORE POWER ELECTRICAL RACK DETAIL ON

E-501.

04 PROVIDE FLUSH-MOUNTED JUNCTION BOX AND CONNECT WITH EXISTING

CONDUIT.

05 RELOCATE PHOTOCELL AND RECEPTACLE SO IT IS OUTSIDE THE

HAZARDOUS AREA AROUND DIESEL FUEL PIPING FLANGES.

06 PROVIDE MANUAL OVERRIDE SWITCH MOUNTED TO POLE WHICH WILL

OVERRIDE PHOTOCELL CONTROL. SEE LIGHTING CONTROL WIRING

DIAGRAM, THIS SHEET.

07 PROVIDE BLANK COVER PLATE ON RECEPTACLE BOX AND SPLICE WIRING

INSIDE. PROVIDE NEW CONDUIT AND WIRE TO THE RELOCATED

RECEPTACLE/PHOTOCELL LOCATION WITH A CONDUIT SEAL WHERE THE

CONDUIT LEAVES THE BOX. SEE PHOTOCELL MOUNTING DETAIL ON SHEET

E-501.

08 PROVIDE 4#4 AWG WIRE IN 1 1/4" PVC-COATED CONDUIT EMBEDDED IN SLAB

BETWEEN JUNCTION BOX AND NEW SHORE POWER RACK.

09 PROVIDE 3/4" PVC-COATED CONDUIT EMBEDDED IN SLAB BETWEEN

EXISTING FLUSH-MOUNTED JUNCTION BOX AND LIGHT POLE.

#NEW WORK NOTES

1. LED AREA LUMINAIRES SHALL BE PROVIDED WITH TYPE IV DISTRIBUTION

AND FIVE DEGREE TILT UNLESS OTHERWISE NOTED.

2. SIGNAGE MUST BE PROVIDED TO COMPLY WITH THE REQUIREMENTS OF

NFPA 70, ARTICLE 555.24.

3. DURING COMMISSIONING, COORDINATE FINAL FIELD ADJUSTABLE

LUMINAIRE OUTPUT SETTINGS WITH OWNER.

GENERAL NOTES

MANUAL

OVERRIDE

SWITCH

CKT B-3

(MAIN ELECTRICAL RACK) N

LIGHTING

LOADS

PC

SCALE: NOT TO SCALE

LIGHTING CONTROL

WIRING DIAGRAM

NOTE:

RECONFIGURE EXISTING LIGHTING WIRING

TO ACHIEVE THIS CONTROL SCHEME.

PC

PHOTOCELL

(EXISTING AT MAIN

ELECTRICAL RACK)

H

6"x6"x1/4" STEEL BASE PLATE

WITH (4) 3/4"Ø HOLES (TYP)

1" THICK NON-SHRINK GROUT

1/8

AS REQUIRED

METAL SLOTTED

CHANNEL SUPPORT,

1 5/8" GALVANIZED,

AS REQUIRED

CONCRETE

VERTICAL SHALL BE

DOUBLE CHANNEL

3/4"x6" LONG STAINLESS STEEL

EXPANSION ANCHOR OR EPOXY

SET (TYP OF 4 PER SUPPORT)

EQUIPMENT RACK, SEE

DETAIL THIS SHEET

FUSED RECEPTACLE

SWITCH, 100A FUSES,

100A RECEPTACLE MUST

BE COMPATIBLE WITH

RUSSELL-STOLL PLUG

NUMBER JPS1044F

8W" x 8D" WIREWAY, NEMA 4X

ENCLOSED CIRCUIT

BREAKER, 30A, 1Ø

TWIST-LOCK RECEPTACLE,

NEMA L5-30R WITH

WEATHERPROOF COVER

1' -6

NOTE:

PROVIDE #8 AWG BONDING CONDUCTOR

BETWEEN WIREWAY AND EQUIPMENT RACK.

RELOCATED

PHOTOCELL

CONDUIT FITTING

RELOCATED

RECEPTACLE WITH

WEATHERPROOF

COVER

CONDUIT SEAL

3/4"C CONNECTED

TO EXISTING

JUNCTION/SPLICE

BOX

LIGHTING FIXTURE SCHEDULE

FIXTURE

SYMBOL DESCRIPTION

NUMBER

AND TYPE

OF LAMPS

NOMINAL

LUMENS TEMP

MAXIMUM

ALLOWED

WATTS

VOLTAGE MOUNTING NOTES

AREA

LIGHTING LED 13000 4100 125 120 POLE,

+12'-0" AFG

PROVIDE WITH FIELD

ADJUSTABLE OUTPUT

NAVIGATION

BEACON LED 850 N/A 30 120 POLE, +8'-0"

AFG

PROVIDE POLE WITH TENON

MOUNTING OPTION

12"

A

FINISHED GRADE

CHAMFER ALL EDGES

OF CONCRETE BASE 1/2"

POLE - SEE POLE

SKETCH AND

SPECIFICATION

CONDUIT STUBBED UP

ADJACENT TO

HANDHOLE; NUMBER

AND SIZE AS REQUIRED

COPPER EQUIPMENT

GROUNDING CONDUCTOR,

ATTACH TO INTERNAL LUG

WELDED TO INTERIOR OF

POLE. CONDUCTOR TO BE

SAME SIZE AND TYPE AS

SUPPLY PHASE CONDUCTOR.

CIRCUIT CONDUCTORS

AND CONDUIT TO POWER

SOURCE OR NEXT POLE

CIRCUIT CONDUCTORS

AND CONDUIT TO POWER

SOURCE OR NEXT POLE

ANCHOR BOLT BASE

PLATE EMBEDDED IN

CONCRETE

#4 BARS VERTICAL AT

6" EACH FACE

#3 BARS AT 12" ON

CENTER HORIZONTALLY

SCALE: NOT TO SCALE

ANCHOR BASE

POLE FOUNDATION

TAPERED ALUMINUM POLE.

INTERNAL GROUNDING LUG.

TERMINATE CONDUITS INTERNALLY, ADJACENT TO

HANDHOLE.

FULL BASE COVER - TWO-PIECE GALVANIZED STEEL.

CONCRETE FOUNDATION - SEE ANCHOR BASE POLE

FOUNDATION, THIS SHEET.

SE

E

LI

G

H

TI

N G

F

IX

TU

R

E

SC

H

ED

U

LE

9"

SCALE: NOT TO SCALE

ANCHOR BASE

ALUMINUM POLE

POLE

HEIGHT A

12"8'-12'

TOP VIEW 14 IN

4 IN

POLE AS INDICATED

34.5 IN

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-CAST ALUMINUM OR DIE-CAST AND EXTRUDED

ALUMINUM WITH INTEGRAL, SELF-CLEANING HEAT SINK FINS, RIBS, OR

EQUIVALENT PASSIVE COOLING MECHANISM. HEAT SINK SHALL BE

INCORPORATED DIRECTLY INTO HOUSING TO ENSURE MAXIMUM HEAT

TRANSFER AND DISSIPATION.

2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON

POLYESTER POWDER COAT. FINISH SHALL PASS 2500 HOUR SALT

SPRAY TEST PER ASTM B117. FINISH COLOR: DARK BRONZE.

3. POWER SUPPLY/LED DRIVER - PROVIDE IN SEPARATE COMPARTMENT

ACCESSIBLE WITHOUT THE USE OF HAND TOOLS. CLASS 1 DRIVER

SHALL OPERATE AT 120/277V, 50/60 HZ. POWER FACTOR GREATER

THAN 0.9 AND THD LESS THAN 20% AT FULL LOAD. MINIMUM EFFICACY

SHALL BE 70 LM/W AT MAXIMUM 600 mA OPERATING CURRENT.

4. LED OPTICAL ASSEMBLY - NUMBER OF LED ARRAYS SHALL VARY TO

ACCOMMODATE DESIRED LUMINAIRE OUTPUT. PROVIDE WITH

EQUIVALENT NEMA TYPE III OR IV DISTRIBUTION AS INDICATED. BUG

UPLIGHT RATING OF U0, WITH BACKLIGHT AND GLARE RATINGS AS

DETERMINED BY LIGHTING ZONE INSTALLED. MINIMUM COLOR

RENDERING INDEX (CRI) SHALL BE 70 FOR CORRELATED COLOR

TEMPERATURE (CCT) OF 4000 K TO 4500 DEGREES K.

5. SURGE PROTECTION - 6 kV MINIMUM, COMPLIANT WITH ANSI C62.41.2.

6. CERTIFICATION - UL AND/OR ETL LISTED, MINIMUM IP65 RATED PER

ANSI/IEC 60529, AND RoHS COMPLIANT.

7. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS AND IS NOT INTENDED TO INDICATE A

CERTAIN MANUFACTURER'S PREFERENCE. ALL DIMENSIONS ARE

NOMINAL AND VARY PER MANUFACTURER.

SCALE: NOT TO SCALE

LED AREA LUMINAIRE

SCALE: NOT TO SCALE

NAVIGATION BEACON

8 5/8"

TENON OPTION - 2-3/8" TENON

WITH PROVISION FOR WIRING,

COORDINATE WITH LUMINAIRE

LUMINAIRE REQUIREMENTS:

1. BASE - DIE-CAST ALUMINUM OR DIE-CAST AND EXTRUDED ALUMINUM.

ANODIZED FINISH.

2. BEACON - FIXED LED LIGHT SOURCE. LED RATING OF 50,000 HOURS

WITH A CURRENT DRAW OF 250 mA AT 120 VAC.

3. HOUSING DOME - SHATTER-RESISTANT POLYCARBONATE, RED WITH

ABILITY TO PROVIDE SHIELDING TO HALF OF THE DOME (180°

SHIELDING).

4. BIRD-DETERRENT LOCATED ON TOP OF BEACON.

5. CERTIFICATION - UL LISTED, MINIMUM IP65 RATED PER ANSI/IEC 60529,

AND RoHS COMPLIANT.

6. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETARY GRAPHIC

REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE

SPECIFICATION REQUIREMENTS AND IS NOT INTENDED TO INDICATE A

CERTAIN MANUFACTURER'S PREFERENCE. ALL DIMENSIONS ARE

NOMINAL AND VARY PER MANUFACTURER.

BASE

1/

8"

DOME

ANCHOR BOLTS AS RECOMMENDED

BY POLE MANUFACTURER

SCALE: NOT TO SCALE

EQUIPMENT RACK

SCALE: NOT TO SCALE

SHORE POWER

ELECTRICAL RACK

SCALE: NOT TO SCALE

PARTIAL ONE-LINE DIAGRAM

SERVICE

208Y/120V

3P,60 HZ

100A

#2

4#4 + 1#8G IN EXISTING 2"C

MAIN ELECTRICAL RACK

SHORE POWER RACK

2#10 + 1#10G IN 3/4"C

4#4 + 1#8G IN 1 1/4"C

30A

GFCI

WIREWAY

ENCLOSED

CIRCUIT

BREAKER

RECEPTACLE

SWITCH

WITH 100A

CIRCUIT

BREAKER30A TWIST

LOCK RCPT,

NEMA L5-30R

SCALE: NOT TO SCALE

PHOTOCELL

MOUNTING DETAIL

100% DESIGN - FOR REVIEW ONLY

NOTE:

PROVIDE BONDING JUMPER AT WIREWAY, RECEPTACLE

BOX, AND ENCLOSED CIRCUIT BREAKER/SWITCH BOX

BETWEEN THE INCOMING EQUIPMENT GROUNDING

CONDUCTOR AND THE ENCLOSURE.

RUN DECK REINFORCING

THROUGH LIGHT POLE BASE

POUR CONCRETE POLE FOUNDATION

MONOLITHICALLY WITH DECK

File details come from the government source that posted it. Updated .