This document is a comprehensive set of contract drawings and mechanical engineering documents for the Marion VA Medical Center's New Energy Center project, prepared by RMF Engineering and FFE as the architect/engineer of record. The drawings detail the complete HVAC system design including ductwork, piping, controls, and equipment specifications for a new facility construction project.
The mechanical scope includes two air handling units (AHU-1 and AHU-2) with capacities of 8,000 CFM and 3,500 CFM respectively, serving the chiller plant, electrical rooms, and control room functions. The system incorporates variable air volume (VAV) terminal units with electric reheat, exhaust fans for refrigerant and toilet exhaust, gravity roof ventilators, split system AC units, and propeller-type electric unit heaters. Chilled water distribution utilizes 12-inch and 8-inch piping with three centrifugal chillers and condenser water cooling towers. The control system features a building automation system (BAS) with direct digital controls, including zone sensors, air flow measuring stations, fire and smoke dampers, and extensive safety interlocking. Ductwork construction specifies SMACNA standards with external insulation on supply runs, acoustic lining where required, and sealing classes ranging from +3" to -2" water column static pressure. The documents include detailed specifications for equipment bases, seismic bracing, roof curb installations, and comprehensive piping connection details for chilled water, condenser water, and miscellaneous hydronic systems. Design conditions are based on 93.4°F summer and 5.4°F winter outdoor air with 479-foot design altitude.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4"
P-103
P-414
P-502
P-806
DWH-1
TMV-E
P-709
P-801
P-801
P-801
0.5"
1"
1.5"
0.5"
0.5"
0.5"
0.75"
1.5"
0.75"
0.75"
3"
3"
ET-1
P-802
0.5"
0.75" 0.75"
0.75"
P-802
P-802
P-801
1.5"
2.5"
2.5"
1"
0.5"
1ST FLR
1.25" 0.5"0.5"
N.T.S.Scale:
DOMESTIC WATER ISOMETRIC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
C :\U se rs
\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\
R ev it\ Au to de sk R ev it
\C ol la bo ra tio nC ac he \F
G L2
C N
YF
N
2R
VU
3\
5d 1a c9
-2 ae
8-
-b f-c ff8 3c
3d
3a \e e-fd
-4 d-ab
-2 dc f.r vt 5/
5/
:4 4:
P
M
P903
DOMESTIC ISOMETRIC
05/07/2026 EWL BSG
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
PLAN NOTES
1 FROM SITE.
2 TO FIRE PROTECTION.
3 WATER METER.
4 BACKFLOW PREVENTER
5 TO HVAC.
1 CONTRACT DOCUMENTS 05/07/2026
NOTE:
ALL SYMBOLS AND ABBREVIATIONS ARE
SUBJECT TO MODIFICATIONS ON OTHER
DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT
NOT NECESSARILY BE USED ON THIS
PROJECT.
ABBREVIATIONS
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AFMS - AIR FLOW MEASURING STATION
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATC - AUTOMATIC TEMPERATURE CONTROL
(SYNONYMOUS WITH BAS)
BAS - BUILDING AUTOMATION SYSTEM
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED WATER SUPPLY
CHR - CHILLED WATER RETURN
CHGR - CHILLED WATER GLYCOL SOLUTION RETURN
CHGS - CHILLED WATER GLYCOL SOLUTION SUPPLY
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CT - COOLING TOWER
CTR - CENTER
CU - COPPER
CW - COLD WATER
CWR - CONDENSER WATER RETURN
CWS - CONDENSER WATER SUPPLY
D - DRAIN LINE
DB - DRY BULB
DDC - DIRECT DIGITAL CONTROLS
DI - DEIONIZED WATER
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DWG - DRAWING
EA - EACH OR EXHAUST AIR
EAT - ENTERING AIR TEMPERATURE
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EF - EXHAUST FAN
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
EQS - EQUIPMENT SUPPLIER
EWT - ENTERING WATER TEMPERATURE
EXH - EXHAUST
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
FD - FLOOR DRAIN
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES CONTRACTOR
GPM - GALLONS PER MINUTE
HB - HOSE BIBB
HC - HVAC CONTRACTOR (DIVISION 23)
HD - HUB DRAIN
HG - REFRIGERANT HOT GAS
HP - HORSEPOWER
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HR - HOUR
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LAT - LEAVING AIR TEMPERATURE
LAV - LAVATORY
LBS - POUNDS
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LWT - LEAVING WATER TEMPERATURE
MAX - MAXIMUM
MDD - MOTORIZED DAMPER
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE
RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - WATER MAKE-UP
N/C - NORMALLY CLOSED
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NOM - NOMINAL
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
OA - OUTDOOR AIR
OBD - OPPOSED BLADE DAMPER
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GAS
PC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PLBG - PLUMBING
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSIG - POUNDS PER SQUARE INCH GAUGE
PTAC - PACKAGED TERMINAL AIR CONDITIONER
RA - RETURN AIR
RAD - RADIUS
RCP - REFLECTED CEILING PLAN
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS WATER SUPPLY
ROR - REVERSE OSMOSIS WATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
S - SPRINKLER (WET)
SA - SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD WATER
SHT - SHEET
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SRV - SAFETY RELIEF VALVE
SS - STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TA - TRANSFER AIR
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TYP - TYPICAL
UH - UNIT HEATER
UNO - UNLESS NOTED OTHERWISE
V - VENT
VAC - VACUUM
VAV - VARIABLE AIR VOLUME
VEL - VELOCITY
VFD - VARIABLE FREQUENCY DRIVE
(ADJUSTABLE FREQUENCY
MOTOR CONTROLLER)
VIB - VALVE IN BOX
VOL - VOLUME
VTR - VENT THROUGH ROOF
VR - VENT RISER
W/ - WITH
W/O - WITHOUT
WB - WET BULB
WCO - WALL CLEANOUT
GENERAL FLOOR PLAN NOTES
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN UNLESS
NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
A1
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS
REFER TO SCHEDULES.
H1 H1OR
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO
SCHEDULES.
H2
B
H2
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
H2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
H2 = SHEET WHERE DETAIL IS LOCATED
A1 "UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF
EQUIPMENT, UNLESS NOTED OTHERWISE
10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOD: 8' - 10"
BOD: 7' - 2"
20x20
20x20
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF
DUCTWORK, UNLESS NOTED OTHERWISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE,
UNLESS NOTED OTHERWISE
DL-1
UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH
UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE WITH GC.
DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.
CONNECT TO EXISTING
HVAC PIPING DESIGNATIONS
CHILLED WATER SUPPLY PIPECHS
CONDENSER WATER SUPPLY PIPECWS
CONDENSER WATER RETURN PIPECWR
DRAIN LINE. PITCH IN DIRECTION INDICATEDD
HEATING HOT WATER SUPPLY PIPEHWS
HEATING HOT WATER RETURN PIPEHWR
WATER MAKE-UP PIPEMU
VENT PIPEV
REFRIGERANT LIQUID LINERL
REFRIGERANT SUCTION LINERS
EXPANSION TANK PIPEET
REFRIGERANT HOT GAS LINEHG
LOW PRESSURE CONDENSATE RETURN PIPELPC
LOW PRESSURE STEAM SUPPLY PIPELPS
MEDIUM PRESSURE CONDENSATE RETURN PIPEMPC
MEDIUM PRESSURE STEAM SUPPLY PIPEMPS
PUMPED CONDENSATE RETURN PIPEPC
HIGH PRESSURE CONDENSATE RETURN PIPEHPC
HIGH PRESSURE STEAM SUPPLY PIPEHPS
STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.10
MISC SYMBOLS
DUCTWORK SYMBOLS
ROUND BRANCH DUCTWORKCONICAL
FITTING
ACOUSTIC
FITTING
ACOUSTIC
FITTING
ADAD
D
R R
D
RECTANGULAR BRANCH DUCTWORK
SQUARE TEE WITH TURNING VANES
NOTE: ALL SQUARE ELBOWS IN
RECTANGULAR AND ROUND / OVAL
DUCTWORK SHALL BE PROVIDED WITH
TURNING VANES. REFER TO
SPECIFICATIONS FOR ADDITIONAL DETAILS.
EXISTING DUCTWORK TO REMOVED
RETURN AIR, RELIEF AIR, OR TRANSFER AIR
DUCTWORK. (UP AND DOWN) RADIUSED
OR SQUARE WITH TURNING VANES.
SUPPLY AIR OR OUTDOOR AIR DUCTWORK.
(UP AND DOWN) RADIUSED OR SQUARE
WITH TURNING VANES.
EXHAUST AIR DUCTWORK. (UP AND DOWN)
RADIUSED OR SQUARE WITH TURNING
VANES.
RECTANGULAR AND ROUND / OVAL
DUCTWORK RISE / DROP WITH 90° RADIUSED
OR SQUARE ELBOWS AND TURNING VANES.
RADIUS ELBOW
90° SQUARE ELBOW (WITH TURNING VANES)
NOTE: ALL SQUARE ELBOWS IN
RECTANGULAR AND ROUND DUCTWORK
SHALL BE PROVIDED WITH TURNING VANES.
ACCESS DOOR OR PANEL
DUCTWORK RISE IN DIRECTION OF AIR
FLOW
DUCTWORK DROP IN DIRECTION OF AIR
FLOW
DUCTWORK WITH ACOUSTICAL LINER.
LISTED DUCT SIZES ARE INSIDE CLEAR
DIMENSIONS.
RECTANGULAR ROUND / OVAL
FLEXIBLE DUCTWORK
FLEXIBLE CONNECTION
DUCTWORK CONSTRUCTED OF SPECIAL
MATERIAL AS NOTED
DIRECTION OF PITCH
RECTANGULAR DUCTWORK DIMENSIONS
(W x H)26x20
ROUND DUCTWORK DIMENSIONS (DIA)26ø
OVAL DUCTWORK DIMENSIONS (W x H)26x20 OV
DUCTWORK DEVICE SYMBOLS
CEILING, WALL, OR DUCTWORK MOUNTED SUPPLY, RETURN, OR EXHAUST AIR DEVICE.
T10 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE SCHEDULE FOR VARIOUS
DESIGNATIONS). 20x12 = DEVICE SIZE (IN INCHES). 300 = REQUIRED CFM. FOR NON-CEILING
MOUNTED DEVICES, 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF GRILLE.
A10 10ø
MANUAL BALANCING DAMPER WITH LOCKING DEVICE
BDD = BACK DRAFT DAMPER
CBD = COUNTER-BALANCED BACK DRAFT DAMPER
SD = SMOKE DAMPER
FS = COMBINATION FIRE - SMOKE DAMPER
MDD = MOTORIZED DAMPER
AFMS = AIR FLOW MEASURING STATION
DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.
HUMIDITY SENSOR - DUCT MOUNTED
T10 20x12
BOG: 9'-0"
XXX
A-D
XX
H
SD
SP
CEILING MOUNTED SUPPLY AIR DEVICE. ALL AIR DEVICES DISCHARGE 4-WAY UNLESS NOTED
OTHERWISE ON PLANS WITH FLOW ARROWS. A10 = DESIGNATION (REFER TO FLOOR PLANS
AND AIR DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS). 10ø = NECK SIZE (IN INCHES).
300 = REQUIRED CFM.
FIRE DAMPER
A = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)
D OR S = DYNAMIC OR STATIC
STATIC PRESSURE SENSOR - DUCT MOUNTED
C
CARBON DIOXIDE SENSOR - DUCT MOUNTED
S
TEMPERATURE SENSOR - DUCT MOUNTED
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON
APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
VALVES AND FITTINGS
10"
TOE: 3' - 0"
BOE: 0' - 6"
CHILLED WATER GLYCOL SOLUTION RETURN PIPECHGR
CHILLED WATER GLYCOL SOLUTION SUPPLY PIPECHGS
CHILLED WATER RETURN PIPECHR
SQUARE THROAT / RADIUS HEEL
FITTINGS NOT ACCEPTABLE
PIPING SYMBOLS
DOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
PIPE RISER
RADIUS'D BRANCH
RADIUS'D TEE
EXISTING DUCTWORK TO REMAIN
UNLESS NOTED OTHERWISE ON DRAWINGS,
15° MAX FOR DIVERGING, 30° MAX FOR
CONVERGING TRANSITION
EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERWISE.
SPACE TEMPERATURE SENSOR / THERMOSTAT. WHEN WALL MOUNTED, MOUNTING
HEIGHT 46" TO MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH
COORDINATE WITH ARCHITECT.
T
DP
DIFFERENTIAL PRESSURE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO
MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH
ARCHITECT.
H
HUMIDITY SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.
CARBON DIOXIDE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.
C
CO
CARBON MONOXIDE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET
ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH
ARCHITECT.
TEMPERATURE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH
ARCHITECT.
S
S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.
STATIC PRESSURE SENSOR.SP
DRAIN VALVE WITH HOSE END CONNECTION
EXPANSION JOINT
MANUAL AIR VENT
AUTOMATIC AIR VENT
PRESSURE REDUCING VALVE
QUICK OPENING MANUAL VALVE
VACUUM BREAKER
NEEDLE VALVE
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM GAUGE WITH STOP
END CAP
GLOBE VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
A
M
M
N
V
VB
SOLENOID VALVE
S
SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE DISCHARGE AIR GAPPED TO
FLOOR DRAIN UNLESS NOTED OTHERWISE. FOR STEAM SYSTEMS PIPE DISCHARGE
TO OUTDOORS.
WATER METERM
PRESSURE GAUGE WITH COCK AND SIPHON LOOP
BI-METALIC STEAM TRAP AND DRIP ASSEMBLY
THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY
BM
TD
IB
FT
TS
FLOW METER
F
UNION
CLEANOUT
STRAINER
M
MODULATING 2 PORT AUTOMATIC CONTROL VALVE
M
MODULATING 3 PORT AUTOMATIC CONTROL VALVE
M
COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
STRAINER WITH A BLOW DOWN VALVE AND HOSE CONNECTION
AUTOMATIC FLOW CONTROLLER WITH P/T PLUG IN AND OUT
2 PORT AUTOMATIC CONTROL VALVE, 2-POSITION UNLESS SPECIFIED OTHERWISE
3 PORT AUTOMATIC CONTROL VALVE, 2-POSITION UNLESS SPECIFIED OTHERWISE
AUTOMATIC PRESSURE INDEPENDENT CONTROL VALVE
THERMODYNAMIC STEAM TRAP AND DRIP ASSEMBLY
INVERTED BUCKET STEAM TRAP AND DRIP ASSEMBLY
FLOAT AND THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY
DEMOLISH TO POINT INDICATED
CEILING OR WALL MOUNTED LINEAR SLOT AIR DEVICE. S10 = DESIGNATION (REFER TO
FLOOR PLANS AND AIR DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS). 48"L = DEVICE
LENGTH. 8ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM.
S10-48"L 8ø
GENERAL NOTES
A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
B. THE DRAWINGS AND SPECIFICATIONS SHALL BE CAREFULLY STUDIED DURING THE COURSE OF BIDDING. ANY ERRORS, OMISSIONS OR DISCREPANCIES ENCOUNTERED SHALL BE REFERRED IMMEDIATELY TO THE
ARCHITECT/ENGINEER FOR INTERPRETATION OR CORRECTION.
C. INSULATE DUCTWORK AND PIPING WHERE EXISTING INSULATION HAS BEEN DAMAGED AND/OR REMOVED IN
THE PERFORMANCE OF WORK IN THIS PROJECT.
D. PROVIDE ALL ROOFING PENETRATION, REPAIR & REINFORCEMENT IN THE EXISTING BUILDING FOR WORK INDICATED. ENGAGE A ROOFING SUBCONTRACTOR TO PERFORM THE ROOFING WORK. WHERE ROOFING WORK IS REQUIRED, THE EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT, REMOVED AND RESTORED AS REQUIRED TO ATTAIN A WATERTIGHT CONDITION. THE ROOFING SUB-CONTRACTOR SHALL BE A CERTIFIED INSTALLER FOR SUCH INSTALLATION TO MAINTAIN THE EXISTING WARRANTY ON THE ROOF.
E. REFER TO ALL SPECIFICATION SECTIONS AND THESE DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY ARRANGEMENT FOR WORK. THE VARIOUS DRAWINGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT ALL TIMES. REFER TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE CONTRACTING OFFICERS REPRESENTATIVE (COR) THRU
THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE PROCEEDING.
F. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR THE CONDITIONS ON THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. THIS WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. SEE SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON
RESPONSIBILITIES.
G. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND COR TO MAINTAIN OPERATION OF
THE EXISTING FACILITY.
H. COORDINATE ALL WORK WITH THE WORK OF OTHERS. KEEP INFORMED OF THE PROGRESS AND DETAIL DEVELOPMENT OF THE WORK OF OTHERS. COORDINATE AND EXPEDITE WORK WITH OTHERS SO THAT THE
PROGRESS OF THE TOTAL WORK SHALL BE KEPT ON SCHEDULE.
I. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL GOVERNING CODES AND STANDARDS.
J. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON VISUAL OBSERVATION AND/OR AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.
K. FITTING OR PLACING WORK INTO OR ON THE WORK OF OTHERS CONSTITUTES ACCEPTANCE OF THE SUITABILITY OF THE WORK IN PLACE. IF THE WORK OF OTHERS IS NOT ACCEPTABLE, NOTIFY THE CONTRACTING OFFICERS REPRESENTATIVE (COR) FOR THE WORK TO BE CORRECTED. ANY NEW WORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE INSTALLING THE NEW WORK. NO CLAIMS FOR ADDITIONAL COMPENSATION FOR CORRECTING WORK
INSTALLED IN UNSUITABLE EXISTING CONDITIONS WILL BE CONSIDERED.
L. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND FIRE-RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE-STOPPED AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED. COORDINATE WITH ALL TRADES
TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS AND DETAILS ARE MET.
M. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT & OTHER SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS THROUGH 0-HOUR RATED WALLS SHALL BE SEALED
WITH ACOUSTICAL CAULK TO RETARD PASSAGE OF SMOKE.
N. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET
INSIDE DIMENSIONS.
O. PROVIDE DUCT ACCESS PANELS AS REQUIRED BY 23 31 00 FOR ACCESS TO FIRE DAMPERS, SMOKE DAMPERS, SMOKE DETECTORS, AUTOMATIC CONTROL DAMPERS, AND HUMIDIFIER DISPERSION TUBES. REFER TO DETAIL ON SHEET 00. COORDINATE SIZES AND LOCATIONS WITH ACCESSORIES PROVIDED BY OTHER TRADES.
P. ACCESS PANELS IN NON ACCESSIBLE SUSPENDED CEILINGS SHALL BE PROVIDED FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, FLOW METERS, CONTROLS, ETC. COORDINATE SIZES AND LOCATIONS WITH OTHER
TRADES.
Q. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS, COILS, ETC.
R. FOR TYPICAL STEAM, WATER AND REFRIGERANT PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD
DETAILS AND PIPING SCHEMATICS.
S. DIFFUSER SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES. REGISTER AND GRILLE SIZES SHOWN ARE FACE
SIZES.
T. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING DIFFUSERS, REGISTERS, AND GRILLES.
U. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO PROVIDE COUNTER
FLOW BETWEEN WATER AND AIR.
V. WHERE DUCTS OR PIPES ARE REMOVED THRU WALL/FLOOR/ROOF THAT IS TO REMAIN, PATCH
WALL/FLOOR/ROOF OPENING TO MATCH EXISTING WHERE OPENING IS NOT RE-USED.
W. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE CONTRACT. REFINISH
ANY SURFACE DISTURBED UNDER THIS WORK TO MATCH EXISTING.
X. IN GENERAL, KEEP DUCT AND PIPING MAINS TIGHT TO UNDERSIDE OF STRUCTURE.
Y. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED BY THE VA SHALL BE
REMOVED FROM THE PREMISES AND DISPOSED OF PROPERLY BY THE CONTRACTOR.
Z. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES
AND REPORT IMMEDIATELY ANY DIFFICULTIES WHICH CAN BE ANTICIPATED.
AA. FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND EQUIPMENT SIZES, SERVICES AND
LOCATIONS PRIOR TO PERFORMING WORK.
BB. ALL ABANDONED EXTRANEOUS PIPING, DUCTWORK, SUPPORTS, CONTROLS, ETC. SHALL BE REMOVED.
CC. ALL EXISTING DUCTWORK, PIPING, EQUIPMENT, CONTROLS, ETC. SHOWN ON REMOVAL PLAN(S) SHALL BE REMOVED. THE MAJORITY OF WORK TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL AND/OR ABANDONED DUCTWORK, PIPING, ETC. THAT MAY NOT BE SHOWN BUT IS ASSOCIATED WITH THE REMOVAL
WORK.
DD. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE BY PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON PORTABLE LADDERS. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL
TYPES OF VALVES, FILTERS AND STRAINER, TRANSMITTERS, CONTROL DEVICES, ETC.
EE. WHERE EXISTING HVAC UTILITIES IN SERVICE WILL BE DISRUPTED DURING THE CONSTRUCTION OF THIS PROJECT, THIS WORK SHALL BE PERFORMED ON WEEKENDS OR WEEK NIGHTS. DOWNTIME SHALL BE KEPT TO
A MINIMUM, AND SHALL BE COORDINATED AND SCHEDULED WELL IN ADVANCE WITH THE COR.
FF. REFER TO ELECTRICAL DRAWINGS FOR VARIABLE SPEED MOTOR CONTROLLERS ASSOCIATED WITH
MECHANICAL EQUIPMENT.
GG. ALL INSULATED DUCTWORK AND PIPING SHALL HAVE DAMPER/VALVE HANDLE EXTENSIONS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:0
P M
M001
ABBREVIATIONS, LEGEND, &
GENERAL NOTES
05/07/2026 WJS MGN
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SHEET LIST
SHEET NUMBER SHEET NAME
M001 ABBREVIATIONS, LEGEND, & GENERAL NOTES
MD101 BUILDING 49 DEMOLITION PLAN
MH101 FIRST FLOOR PLAN - HVAC
MH102 MEZZANINE PLAN - HVAC
MH103 ROOF PLAN - HVAC
M401 SECTIONS & AHU DETAILS
M501 DETAILS
M502 DETAILS
M503 DETAILS & SCHEDULES
M601 SCHEDULES
M701 CONTROLS
M702 CONTROLS
M703 CONTROLS
PTAC
EF
ON ROOF
EF
UH
M
UH
UH
UH
UH
EF
EF
ON ROOF
CHILLERCHILLERCHILLER
CT CT CT
PUMP PUMP PUMP
PUMP
PUMP
PUMP
PUMPPUMPPUMP
EF
ON ROOF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:2
P M
MD101
BUILDING 49 DEMOLITION PLAN
05/07/2026 WJS MGN
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
FIRST FLOOR - DEMOLITION PLAN
A. REMOVAL PLANS MAY NOT NECESSARILY SHOW ALL ITEMS REQUIRED TO BE REMOVED.
B. REMOVE ALL ABANDONED EXTRANEOUS CONDUITS, SUPPORTS, CONTROLS, ETC.
C. ALL EXISTING CONDUIT, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED SHALL BE REMOVED. THE
MAJORITY OF HVAC WORK TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL ITEMS ASSOCIATED
WITH THE DEMOLITION WORK.
D. COORDINATE WITH THE OWNER IN REGARD TO REMOVALS. SALVAGE EQUIPMENT AS DIRECTED BY THE
OWNER AND STORE IN A LOCATION DESIGNATED BY THE OWNER. ALL OTHER EQUIPMENT AND
MATERIALS NOT SALVAGED SHALL BE REMOVED FROM THE PREMISE.
GENERAL NOTES
1. THE ENTIRE AREA WITHIN THE DASHED LINES SHALL BE REMOVED MECHANICALLY. MAJOR EQUIPMENT SHOWN. REMOVE ALL HVAC AND MECHANICAL EQUIPMENT, AND ALL ASSOCIATED DUCTWORK, AIR
DEVICES, PUMPS, PIPING, CONTROLS, ETC.
PLAN NOTES
T
T
T T
T
T
T
T
A
D
632 54
B
C
ELECTRICAL ROOM
ELECTRICAL ROOM
H.A.C.
AC-1
TR
CONTROL
ROOM
VAV-1
VAV-2
VAV-3
x1
UP22x10 EA
UP22x10 EA
22x10
UP22x10 EA
CHILLER PLANT
TOILET
8x10
22x12
UH-1
UH-2
UH-4
UH-3
1230 CFM
BG2
18x18
BOG: 0' - 7"
1230 CFM
BG2
18x18
BOG: 0' - 7"
1230 CFM
BG2
18x18
BOG: 0' - 7"
R
R
R
3000 CFM
BG1
24x42
BOG: 0' - 7"
UP24x16
18x14
20x10
730 CFM
TR1
20x10
730 CFM
TR1
1250 CFM
TG1
36x16
18x16
20x10
615 CFM
TR1
20x10
615 CFM
TR1
20x10
620 CFM
TR1
8ø
CD1
190 CFM
1580 CFM
TG1
48x16
6ø
CR1
115 CFM
8ø
CR1
150 CFM
8ø
CG1
170 CFM
12x10
UH-5
UP10x8 EA
A-S
B-S
A-S
AC-2
R
R
R
R
7 UP10x8 EA
UP22x10 RA
UP22x12 RA
UP14x34 SA
310 CFM
BG2
10x10
BOG: 0' - 7"
B-S
AHU-1
TYP.
TYP.
TYP.
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:2
P M
MH101
FIRST FLOOR PLAN - HVAC
05/07/2026 WJS MGN
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - HVAC
GENERAL NOTES
1. TERMINATE EXHAUST DUCT 0'-6" A.F.F. DUCT IN VERTICAL SHALL BE CONSTRUCTED OF 18 GAUGE SHEET
METAL.
2. REFRIGERANT LEAK DETECTION MONITORING CONTROL PANEL. PROVIDE REFRIGERANT SENSORS AS
SHOWN ON THE FLOOR PLAN.
3. REFRIGERANT LEAK DETECTION ALARM SYSTEM, SIGNAGE, AND LABELING PER THE FIRE CODE AND APPROVED BY THE AHU. ALARM SYSTEM SHALL INCLUDE A HORN AND STACK LIGHT, WITH A SILENCE BUTTON FOR THE HORN. SUBMIT LAYOUT AND PRODUCT INFORMATION TO ENGINEER FOR REVIEW PRIOR
TO SEEKING AHJ APPROVAL.
4. SUSPEND UNIT HEATER FROM STRUCTURE AT APPROXIMATELY 8'-0" A.F.F.
5. EXTEND CONDENSATE DRAIN PIPING TO HAC. TERMINATE IN MOP SINK.
6. REFRIGERANT LEAK DETECTION SENSOR. MOUNT AT HEIGHT AS RECOMMENDED BY THE CHILLER
MANUFACTURER.
7. TERMINATE EXHAUST DUCT 0'-6" ABOVE PIT FLOOR. DUCT IN VERTICAL SHALL BE CONSTRUCTED OF 18
GAUGE SHEET METAL. COORDINATE EXACT LOCATION WITH OTHER TRADES.
8. CHILLED WATER SYSTEM EQUIPMENT SHOWN FOR REFERENCE ONLY REFER TO MP SERIES SHEETS FOR
ADDITIONAL DETAIL.
PLAN NOTES
A. REFER TO SHEET M001 ABBREVIATIONS, LEGEND, AND ADDITIONAL GENERAL NOTES.
A
D
632 54
B
C
MEZZANINE
CHILLER PLANT
DN22x10 EA
DN22x10 EA
28x18
DN10x8 EA
UP10x8 EAUP26x18 OA
AHU-1
M401
14x12 x1
DN24x16
5000 CFM
TG2
56x16
20x12
900 CFM
TR1
20x12
900 CFM
TR1
20x12
900 CFM
TR1
20x12
900 CFM
TR1
20x12
900 CFM
TR1
20x12
900 CFM
TR1
20x12
900 CFM
TR1
20x12
900 CFM
TR1
x1 x1
22x10
UP26x26
18x8
400 CFM
TR1
80x42 L1 x2
26x26
2 2
RF-2
DN22x10 EA
BOD: 6' - 3"
M401
3 4 5
3 4 5
24x20 20x20 20x20
6 6
7 8
24x20
MD
MD
VD
VDVD
VD
VD
VD VD
VD
VD
VD
12x12
400 CFM
TR2
VD
28x16
VD
VD
VD6
BOD: 16' - 9"
DN10x8 EA x1
D
22x22
48x16
BOD: 5' - 9"
BOD: 17' - 4"
D
VD
x1
3" - CHR
3" - CHS
3"
C H
R
3"
C H
S
3"
C H
R 3"
C
H S
2"
C H
S 2"
C
H R x1
52x16
10x8
UP&DN
D
DN22x12 RA
VD
D
DN22x10 RA
AHU-2
R x1
D
D
10x8
BOD: 5' - 5"
2.5"2.5"
B O
D : 1
7'
0"
VD
AHU-1
TYP.
TYP.
TYP.
VD
SCALE: 1/4" = 1'-0"
MEZZANINE FLOOR PLAN - HVAC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:2
P M
MH102
MEZZANINE PLAN - HVAC
05/07/2026 WJS MGN
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
GENERAL NOTES
1. SLOPE BOTTOM OF RELIEF AIR PLENUM TOWARD LOUVER.
2. FIX AIR DEVICE AT 45 DEGREE ANGLE DOWN.
3. PROVIDE CONCRETE EQUIPMENT PAD PER DETAIL ON SHEET M502.
4. EXTEND CONDENSATE DRAIN PIPING TO FLOOR DRAIN PER DETAIL ON SHEET M502.
5. TRANSITION DUCTWORK TO FULL SIZE OF UNIT CONNECTIONS. PROVIDE FLEXIBLE DUCT CONNECTIONS
PER DETAIL ON SHEET M501.
6. TRANSITION DUCT TO FULL SIZE OF FAN INLET. APPROXIMATE SIZE SHOWN.
7. SUSPEND FAN FROM STRUCTURE WITH VIBRATION ISOLATION HANGERS.
8. PROVIDE 3 DUCT DIAMETERS STRAIGHT RUN AT INLET AND OUTLET.
9. REFER TO MP SERIES SHEETS FOR ISOLATION VALVES.
10. FIX AIR DEVICE IN HORIZONTAL POSITION.
11. EXTEND DUCT THRU MEZZANINE FLOOR. SEAL WATER TIGHT.
12. PROVIDE REFRIGERANT PIPING AND ACCESSORIES PER MANUFACTURER'S RECOMMENDATIONS.
APPROXIMATE ROUTE SHOWN. EXTEND THRU MEZZANINE FLOOR. SEAL WATER TIGHT.
13. APPROXIMATE LOCATION OF ROOF HATCH. COORDINATE DUCT ROUTING AND AIR DEVICE LOCATIONS
ACCORDINGLY.
14. EXTEND AHU DRAIN PIPING TO FLOOR DRAIN.
15. PROVIDE ROLL OVER PIPE PROTECTOR.
16. COVER EXHAUST FAN OPENING WITH HARDWARE CLOTH.
17. CHILLED WATER SYSTEM PIPING SHOWN FOR REFERENCE ONLY REFER TO MP SERIES SHEETS FOR
ADDITIONAL DETAIL.
PLAN NOTES
A. REFER TO SHEET M001 ABBREVIATIONS, LEGEND, AND ADDITIONAL GENERAL NOTES.
A
D
632 54
B
C
CU-1
M401
EF-1
EF-2
M401
CU-2
EF-3
SCALE: 1/4" = 1'-0"
ROOF PLAN - HVAC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:2
P M
MH103
ROOF PLAN - HVAC
05/07/2026 WJS MGN
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
A. REFER TO SHEET M001 ABBREVIATIONS, LEGEND, AND ADDITIONAL GENERAL NOTES.
B. COORDINATE ANY CHANGES REQUIRED TO STRUCTURAL SUPPORT FRAMING WITH ACTUAL PURCHASED
EQUIPMENT AS SHOWN ON APPROVED SHOP DRAWINGS.
C. MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURE IN ACCORDANCE WITH THE INTERNATIONAL
BUILDING AND MECHANICAL CODE. REFER TO SPECIFICATIONS 23 05 11 FOR REQUIREMENTS.
GENERAL NOTES
1. MAINTAIN MINIMUM 25'-0" DISTANCE FROM ANY EXHAUST OR PLUMBING VENT.
2. PROVIDE 36" HIGH ROOF CURB.
3. ROOF CURB HEIGHT PER SPECIFICATIONS.
4. PROVIDE EQUIPMENT/PIPE SUPPORT CURB PER DETAIL ON SHEET M502.
5. PROVIDE REFRIGERANT PIPING AND ACCESSORIES PER MANUFACTURER'S RECOMMENDATIONS.
APPROXIMATE ROUTE SHOWN.
6. PROVIDE PIPE PENETRATION ROOF CURB WITH CAP. PIPING TO PENETRATE SIDE OF CURB. SEAL WATER
TIGHT.
PLAN NOTES
02-MEZZANINE
481' - 7"
03-ROOF
490' - 6"
1 32
03-ROOF
490' - 6"
03-ROOF
490' - 6" x4
AHU-116x52 - RA
12345689 7
02-MEZZANINE
482' - 6"
03-ROOF
490' - 6"
ROOF 490'-6"
490' - 6"
MEZZANINE 481-7
481' - 7"
16x52 - SA
16x48
2" - CHR
2" - CHS
14x58 - SA
CU-1
GIV-1
02-MEZZANINE
481' - 7"
03-ROOF
490' - 6"
1 32
03-ROOF
490' - 6"
03-ROOF
490' - 6"
02-MEZZANINE
482' - 6"
03-ROOF
490' - 6"
20x24 - RA
MDD
MDD
80x42 L1
24x20 - RA
10x37 - RA
10x37 - RA
26x18 - OA
2" - CHS2" - CHR
DN14x34 SA
GIV-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:0
P M
M401
SECTIONS & AHU DETAILS
05/07/2026 WJS MGN
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/2" = 1'-0"
AHU-1
SCALE: 1/2" = 1'-0"
AHU-2
NOTES
1. DISCHARGE PLENUM
2. COOLING COIL
3. ACCESS
4. ELECTRIC HEATER
5. SUPPLY FAN
6. ACCESS
7. FLAT FILTER
8. AIR BLENDER
9. MIXING BOX
NOTES
1. DISCHARGE PLENUM
2. COOLING COIL
3. ACCESS
4. ELECTRIC HEATER
5. SUPPLY FAN
6. ACCESS
7. FLAT FILTER
8. AIR BLENDER
9. MIXING BOX
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1-1/2" POCKET
SLIP
DUCT
1" FLANGE & HEM
BOLT ON 4" CENTERS
1"x1/8" BAND IRON
FLEXIBLE MATERIAL
AS SPECIFIED
ALTERNATE
POSITION
OF BOLT
WASHER
FLANGED
CONNECTION
ON FAN SIDE
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1-1/2" MIN. TO 3" MAX. INSTALLED.
6" NOMINAL WITH MATERIAL TAUT
RECTANGULAR FLEXIBLE CONNECTION
5/16" FLANGE
BOLT ON 4" CENTERS
1"x1/8" BAND IRON
1"x1/8" DRAW BAND
FLEXIBLE
MATERIAL AS
SPECIFIED
SHEET METAL SCREWS ON
12" CENTERS
RIVET ON 4"
CENTERS
DUCT
ROUND FLEXIBLE CONNECTION
FLANGED CONNECTION
ON FAN SIDE
WASHER 1-1/2" MIN. TO 3" MAX. INSTALLED.
6" NOMINAL WITH MATERIAL TAUT
1/2" 1/2" 1-1/2"
STEEL EXPANSION SHIELD FOR EXISTING CONSTRUCTION AND
INSERTS FOR NEW CONSTRICTION. THIS TYPE SHALL BE
USED ONLY IN SLABS OR BEAMS OF 4" MIN DEPTH
3/8" MIN DIA EXPANSION BOLTS FOR
EXISTING CONSTRUCTION AND INSERTS
FOR NEW CONSTRUCTION
CONCRETE
FLOOR SLAB
CLIP
ANGLE
3/8" MIN DIA
INSERTS NEW
CONSTRUCTION ONLY.
NUTS & WASHERS
3/8" MIN DIA
HANGER RODS
FOR PIPES UNDER 2" IN SIZE USE
1-1/2"x1-1/2"x1/4" ANGLE. ALL PIPES 2" & LARGER USE 3"x3"x1/4" ANGLE
TURNBUCKLE
3/8" MIN DIA
HANGER RODS
CURB CAP
SEE NOTE 1
SEE NOTE 2
ROOF
TRANSITION DUCT TO
FULL SIZE OF DAMPER
SUPPLIED WITH ROOF
VENTILATOR
DUCT
MOTOR HOUSING
ELECTRICAL
CONDUIT GUIDE
WOOD NAILING
STRIP
PREFABRICATED
ROOF CURB
SEE NOTE 2
RIGID CONDUIT TO
ACCOMMODATE
ELECTRICAL WIRES
GRAVITY OR MOTORIZED BACKDRAFT
DAMPER, REFER TO SPECIFICATIONS.
NOTES:
1. SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" CADMIUM PLATED LAG BOLTS
NOT OVER 12" ON CENTER.
2. SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).
3. SIZE OF DUCT THROUGH ROOF SHALL NOT BE LARGER THAN CURB SUPPLIED WITH
ROOF VENTILATOR.
4. RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER,
THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.
PLAN VIEW
MAIN SUPPLY
FLOW
SMACNA FIGURE 4-6
45° LEED IN RIGID DUCT
TO AIR TERMINAL UNIT.
F
LO
W
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
M
AX
M
AX
M A
X
M A
X
M
AX
M A
X
E Q
U
IP
M E
N T
AIR
FLOW
AIR
FLOW
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOW SHALL
APPLY.
45° M A
X
"D"
ROUND SHEET METAL
DUCT.
MAIN SUPPLY
RIGID DUCT TO AIR TERMINAL
UNIT.
PLAN VIEW
STIFFEN BLADE
AS REQUIRED
INSULATION SEE
SPECIFICATION
DUCT
INSULATION
STAND-OFF
DAMPER BLADE
HANDLE WITH
LOCKING
QUADRANT
INSIDE END BEARING
⅛” [6mm]
CLEARANCE
ALL AROUND
½” [15mm]
ROUND ROD PIN
OUTSIDE END BEARING
SIDE ELEVATION SECTION
NOTE:
1. DELETE INSULATION STAND-OFF ON DUCTWORK EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
MANUAL
DAMPER
RETURN/
EXHAUST DUCT
CEILING
CEILING DEVICE
DAMPER WHERE
SCHEDULED
TURNING VANES
STRAP HANGER
RECTANGULAR
DUCT, NOTE 1
SPIN-IN TAP
FITTING
STRAP HANGER
SPIN-IN BRANCH TAP FITTING
WITH MANUAL DAMPER
ROUND DUCT - NOTE 2
STRAP HANGER
SHEETMETAL PLENUM
SAME SIZE AS AIR DEVICE
FLEXIBLE AIR DUCT
CONNECTOR. SEE
DETAIL ON THIS SHEET
6" MIN
NOTES:
1 BRANCH DUCT TAKE-OFF WITH MANUAL DAMPER.
2 BRANCH DUCT SIZES, UNLESS NOTED ON PLANS
ARE TO BE SIZED AS FOLLOWS:
100 CFM AND LESS - 6" DIA.
101 CFM TO 250 CFM - 8" DIA.
251 CFM TO 400 CFM - 10" DIA.
401 CFM TO 700 CFM - 12" DIA.
NOTE:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE
ROUND.
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSITITUTED WITH SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENED BY
SMACNA
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
W W
W
R
R
SHALL
EQUAL
OR BE
GREATER
THAN W. VANE
R
SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
⅔ W
R
⅓ W
VANE
R
SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
⅓ W½
W
R
W1
W
NOTE:
1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE
TYPE REGARDLESS OF W DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, ½" [40mm] MAXIMUM SPACE BETWEEN VANES AND A ¾" [20mm] TRAILING
EDGE.
4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL
BE DOUBLE VANE TYPE.
NOTE:
1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A
MINIMUM OF 3 TIMES THE DIAMETER OF
INLET
2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET
TO THIS BOX. BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS.
MAXIMUM LENGTH 3'-0"
[900mm].
3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME
SIZE AS THE BOX INLET. PROVIDED THE EQUIVALENT LENGTH OF
THE BRANCH DUCT. AS SHOWN. DOES NOT EXCEED 10 FEET(3
METERS). FOR LONGER LENGTHS. INCREASE THE DUCT SIZE AND
PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT SIZE AND
PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m].
4. FLEXIBLE AIR DUCT CONNECTORS. WHEN USED FROM TERMINAL
UNIT SUPPLY AIR DUCT TO DIFFUSER. SHALL NOT EXCEED 5'-0"
[1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION
GREATER THAN
45°.
5. COMPONENT ARRANGMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT
SECTIONS.
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT
(TYP.)
AIR TERMINAL
UNIT (CV OR VAV)
SEE NOTE
SEE NOTE
SEE NOTE
SEE NOTE
S E
E N
O T
E
SOUND ATTENUATOR
SEE EQUIPMENT
SCHEDULE
REHEAT
COIL
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
DIFFUSER
(TYP.)
AIR FLOW AIR
FLOW
BRANCH
DUCT
¼W OR 4"
[100mm] MIN.
VD
PROVIDE VOLUME
DAMPER
AT EACH BRANCH DUCT
W
PLAN VIEW
MAIN EXHAUST OR RETURN
CEILING
[300mm]
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
VOLUME DAMPER W/
LOCKINGQUAD
12"
SHEET METAL
SADDLE
THERMAL INSULATION
SEE SPECIFICATIONS
CONICAL OUTLET
BRANCH DUCT
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
SUPPORT SADDLE
FROM STRUCTURE
FLEXIBLE DUCT SIZE
SAME AS DIFFUSER
INLET: 5'-0" MAX
LENGTH
USE RIGID ELBOWS
FOR CHANGE OF
DIRECTION GREATER
THAN 45°
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
EXTEND ANGLE 3"
BEYOND DUCT
FLOOR
SHEET METAL SCREWS 4" ON
CENTER
1-1/2"x1-1/2"x1/8" ANGLE.
INSTALL ON BOTH LONG DIMENSION
SIDES OF DUCT. FOR DUCTS OVER
60" USE 2"x2"x1/8" ANGLE.
HOLE IN STRUCTURAL FLOOR
DUCT RISER
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
0.5 INCH WG TO 2 INCHES WG (LOW PRESSURE) DUCT RISER SUPPORT
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
2"x2"x1/4" ANGLE. INSTALL
ON BOTH LONG DIMENSION
SIDES OF DUCT
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
2 INCHES WG TO 4 INCHES WG (HIGH AND MEDIUM PRESSURE) DUCT RISER SUPPORT
NOTE:
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND MECHANICAL ROOM FLOORS SHALL BE PROVIDED WITH A 3" HIGH CONCRETE CURB
AROUND OPENING FOR DUCT.
HOLE IN STRUCTURAL FLOOR
DUCT RISER
ARRANGE RISER SO
REINFORCER TRANSVERSE JOINT
IS AT RISER SUPPORT POINT
FLOOR
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
HANGER STRAPS OR RODS
MAX. DUCT
DIA. - IN.
QUANTITY/SIZE
IN.
MAX. LOAD
LBS.
MAX.
SPACING
IN.
260 144
ONE 1 x 22 GA. STRAP
ONE 1 x 18 GA. STRAP
ONE 1 x 16 GA. STRAP
TWO 3/8 DIA. RODS
TWO 1/2 DIA. RODS
LOAD RATED
FASTENERS
BAND OF SAME
SIZE AS HANGER
STRAP
50" DIA. &
UNDER
HANGER RODS
BAND
OVER 50" DIA.
TURNING VANES
SEE FLOOR PLAN FOR
SPLIT DIMENSION
MAIN
SUPPLY
DUCT
SQUARE ELBOW SHOWN.
PROVIDE ROUND ELBOW
WHEN SHOWN ON PLANS
SUPPLY REGISTER
OR BRANCH DUCT
AIR
FLOW
AIR
FLOW
A
IR
F
LO
W
MANUAL VOLUME
DAMPER
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
A
IR
F
LO
W
AIR
FLOW
BRANCH DUCT
MANUAL VOLUME
DAMPER
MAIN SUPPLY
DUCT
W
1/4 W OR
4" MIN.
BRANCH DUCT TAKE-OFF PLAN VIEW
NOTES:
THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM ANYTIME,
AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000 FPM OR LESS. THE AIR SPLIT DUCT
TAKE-OFF SHALL BE USED IN ALL OTHER CASES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:1
P M
M501
DETAILS
05/07/2026 WJS MGN
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: NONE
FLEXIBLE DUCT CONNECTIONS
SCALE: NONE
SECURING HANGER RODS IN CONCRETE
SCALE: NONE
POWER ROOF VENTILATOR
SCALE: NONE
ALTERNATE SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS
SCALE: NONE
DUCTWORK TRANSITIONS
SCALE: NONE
SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS
SCALE: NONE
VOLUME DAMPER DETAIL
SCALE: NONE
RETURN OR EXHAUST GRILLE/REGISTER CONNECTION
SCALE: NONE
DUCTWORK RADIUS ELBOWS
SCALE: NONE
DUCTWORK SQUARE VANE ELBOWS
SCALE: NONE
DUCT CONNECTION-AIR TERMINAL UNITS
SCALE: NONE
EXHAUST OR RETURN BRANCH DUCTWORK
SCALE: NONE
FLEXIBLE AIR DUCT CONNECTOR
SCALE: NONE
DUCT RISER SUPPORTS
SCALE: NONE
ROUND DUCT HANGERS
SCALE: NONE
SUPPLY DUCTWORK TAKE-OFFS
HOUSING WELDED
TO DUCT SECTION
ROUND OR FLAT
OVAL DUCT SECTION
COVER WITH HANDLE AND
CHAIN RETAINER GASKETED
AND PRESSURE SEALED
INSULATION
DUCT
GASKET
INSULATION
SECTION "A-A"
ACCESS PANEL
"A"
"A"
ACCESS DOOR
INSULATION
SECTION "B-B"
FLEXIBLE
WASHER
FACTORY
FABRICATED
LATCH
CASING
GASKET
HANDLE INSIDE
"B" "B"
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
LAG SCREW
WOOD NAILER
4"x4"x1/4"
STEEL PLATE
INSULATION
ROOFING
ROOF DECK
1. PROVIDE COUNTER-FLASHING.
2. HEAVY GAUGE CONTINUOUS SUPPORT
EXTENDS 6" BEYOND LAST EQUIPMENT LEG.
SCREW ATTACHMENT TO DECK.
3. MINIMUM 12 INCHES.
4. EXPANSION LAGS TO DECK.
5. 18 INCH HIGH INSULATED STEEL CURB.
NOTES
AUXILIARY AIR
DEVICE FRAME
TYPE "A"
DUCT
3" MIN
AIR DEVICE TO BE REMOVABLE
FOR ACCESS TO FIRE DAMPER
DUCT EXTENSION AT
TOP OF DAMPER
DUCT
1TYPE "B" -
FIRE RATED WALL
OR PARTITION
3" MIN3" MIN
4 4
GENERAL NOTES
NOTES
A. FIRE DAMPERS SHALL BE UL LABELED.
B. INSTALLATION OF FIRE DAMPERS AND ACCESSORIES SHALL CONFORM TO NFPA 90A, SMACNA AND MANUFACTURER'S INSTRUCTIONS.
C. DETAILS SHOW INSTALLATION OF FIRE DAMPER IN WALL. DAMPER INSTALLATION IN FLOOR SIMILAR. COORDINATE REQUIRED ACCESS
LOCATIONS.
D. INSULATE RETAINING ANGLES FOR SYSTEMS REQUIRED TO BE INSULATED.
1. FIRE DAMPER, FOLDED BLADE CURTAIN TYPE, EXCEPT AS NOTED. VERTICAL MOUNT, GRAVITY DROP; HORIZONTAL MOUNT, SPRING LOADED TO CLOSE. REFER TO SPECS FOR VELOCITY LIMITATIONS OF EACH TYPE. REFER TO DRAWINGS FOR STATIC OR DYNAMIC
REQUIREMENTS.
2. SHEET METAL WALL SLEEVE, SAME MATERIAL AS DUCT (EXCEPT GALVANIZED SHEET METAL FOR FIBERGLASS DUCT). SHEET METAL GAUGE PER SMACNA. USE EXTENDED HEAVY GAUGE SLEEVES WHEN INSTALLED CONDITION REQUIRES.
3. DUCT/SLEEVE CONNECTION. BREAKAWAY TYPE SHOWN. CONNECTION MAY BE RIGID TYPE IF ALLOWED BY CODE AUTHORITY.
4. RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MINIMUM OVERLAP OF WALL OPENING. LONGER LEG MAY BE REQUIRED TO
ATTAIN REQUIRED OVERLAP. BOLT, SCREW OR TACK WELD TO WALL SLEEVE. SPACING OF FASTENERS PER SMACNA.
5. DUCT ACCESS PANEL OR DOOR. REFER TO SPECIFICATIONS.
6. CEILING ACCESS PANEL IF CEILING IS NOT ACCESSIBLE.
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
2" PLUS X X
2X1" MINIMUMBLOW THRU
DRAW THRU
FLOOR SINK
DIELECTRIC
FITTING
NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY
LOCAL VA AND IS INDOORS AND DOES NOT PASS THROUGH
RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR
METALS ARE TO BE CONNECTED.
DRAIN
PAN
CLEAN OUT
PITCH DOWN
TOWARD DRAIN
DRAIN LINE SHALL BE AT LEAST THE SAME
SIZE AS THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR
TYPE M UNLESS NOTE BELOW IS MET
A B
1"
NOTE:
NOT REQUIRED
FOR AIR TERMINAL
UNITS.
EQUIPMENT WEIGHT
250 LBS. [114KG]
OR LESS
SEISMIC BRACING FOR LIGHT
SUSPENDED EQUIPMENT
FLOOR MOUNT EQUIPMENT
RESTRAINED BY RESILIENT PADS
(TYPE DS)
FLOOR
EQUIPMENT
BASE
ANCHOR BOLT
NEOPRENE WASHER
& SLEEVE
BONDED STEEL
PLATE
RESILIENT PAD
HANGER
ROD
(TYP)
CROSS BRACING
RODS ALL FOUR
SIDES
LOCK
NUTS
(TYP)
CLAMP
L
W
A
B
5D
D
2D
5D
1" [2
5m m
PLAN SECTION B-B
16" [400mm]
L/
5" M
IN
[1 m m
SECTION A-A (BASE POURED EITH FLOOR SLAB)
L1
5" M
IN
[1 m m
SECTION A-A (BASE NOT POURED WITH SLAB)
A
B
FLOOR
ANCHOR BOLT (TYP)
PIPE SLEEVE (5D,
(3" [75mm] MIN.)
CONCRETE BASE
WELD HEAD TO PLATE
OR BEND OVER END 5D
TYPICAL ANCHOR BOLT
NUT AND WASHER
EQUIPMENT
BASE PLATE
PROVIDE DOUBLE SLAB
RE-INFORCING IN BASE AREA
TYPICAL ANCHOR BOLT
NUT AND WASHER
EQUIPMENT
BASE PLATE
PROVIDE #3 BARS 12" [300mm]
O.C. EACH WAY IN THE BASE
AND DOWEL BASE TO FLOOR NOTE:
L & W DIMENSIONS
SHALL BE 6" [150mm]
GREATER THAN THE
EQUIPMENT BASEPLATE
LAG SCREW
4"x4"x1/4"
STEEL PLATE
FIBERGLASS INSULATION
INSULATION
ROOF
2x6 WOOD NAILER
ROOFING
ROOF DECK3
NOTES:
1. 18 GAUGE GALVANIZED STEEL COUNTER-FLASHING,
2. WELDED 14 GAUGE EQUIPMENT SUPPORT CURB, MEETING ASTM A-446, 525, 526 AND 527 REQUIREMENTS, WITH WELDED CORNERS WITH SEAMS JOINED BY CONTINUOUS WELDS. CURB SHALL BE INTERNALLY REINFORCED WITH BULKHEADS AND SPREADERS, 24" ON CENTER TO MEET LOAD RATING OF EQUIPMENT.
CURB TO EXTEND 6" BEYOND EQUIPMENT. REFER TO FLOOR PLANS FOR HEIGHT.
3. SECURE CURB TO ROOF WITH EXPANSION BOLTS (CONCRETE ROOF) OR RUST RESISTANT BOLTS
(METAL DECK AND BAR JOIST ROOF), 12" O.C.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:1
P M
M502
DETAILS
05/07/2026 WJS MGN
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: NONE
ACCESS SECTION FOR ROUND/OVAL DUCT
SCALE: NONE
ACCESS PANEL AND DOOR DETAIL
SCALE: NONE
ROOF EQUIPMENT SUPPORT
SCALE: NONE
FIRE DAMPER AT AIR DEVICE - WALL
SCALE: NONE
FIRE DAMPER TYPE "B"
SCALE: NONE
FIRE DAMPER NOTES
SCALE: NONE
AIR HANDLING UNIT DRAIN TRAP DETAIL
SCALE: NONE
SEISMIC BRACING FOR EQUIPMENT
SCALE: NONE
CONCRETE EQUIPMENT BASES
SCALE: NONE
EQUIPMENT/DUCT SUPPORT ROOF CURB
NOTE:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST
2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR
4" DIA. PIPE & SMALLER. TYPE "H-P" FOR 5" DIA. PIPE & LARGER.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE
SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE
SERVICING OF FILTERS, VALVES, OR EQUIPMENT.
3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED
MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE
RETURN PIPING.
WATER COIL
DRAIN
DOUBLE COIL
WATER COIL
DRAIN WHEN COIL IS
NOT SELF-DRAINING (TYP.)
MV
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
STRAINER WITH BLOW DOWN (TYP.)
BUTTERFLY VALVE (TYP.)
0.75" BYPASS WITH AUTOMATIC
FLOW CONTROL VALVE (4-57 PSIG RANGE) SET AT 5 GPM
CHR
CHS
REDUCER, IF REQUIRED
MV
MV
MV
MV
CHR
CHS
REDUCER, IF REQUIRED
MVMV
MV
AUTOMATIC FLOW CONTROL VALVE (TYP.)
0.75" BYPASS WITH AUTOMATIC
FLOW CONTROL VALVE (4-57 RANGE)
SET AT 5 GPM
DRAIN
SINGLE COIL
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
DRAIN WHEN COIL IS
NOT SELF-DRAINING
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
TEST PLUG
(TYP.)
WATER COIL
AUTOMATIC 2-WAY
MODULATING CONTROL
VALVE (TYP.)
AUTOMATIC FLOW CONTROL VALVE (TYP.)
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF MIN.
DENSITY) UNDER INSULATION SHIELD
INSULATION SHEILD
AT HANGER
WELD
SADDLE
ADJUSTABLE CLEVIS HANGER TYPE 1 -
SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 -
SEE SPECIFICATIONS
PROVIDE INSULATION SHEILD
& INSERT FOR ALL PIPING
(200mm [8"] MIN.)
15mm [½"] DIA.
HANGER RODS WITH
900mm [36"] MAX.
SPACING ON EACH
CHANNEL
BAND
43mm [1-⅝"] 12 GAUGE CHANNEL OR 50x50x6.4mm [2"x2"x¼"] ANGLE m m [1
M
A X
SIDE VIEW TRAPEZE HANGER FOR UP TO
453KG [1000lb.] UNIFORM LOAD
[1]
[1¼]
THRU 20
[THRU ¾]
[1½]
[2½]
[2]
[3]
[4]
[5]
[6]
[10]
[10]
[12]
[14]
[16]
[18]
[20]
[24]NOM. SIZE
[7]
[7]
[7]
[9]
[11]
[10]
[12]
[14]
[16]
[17]
[19]
[22]
[23]
[25]
[27]
[28]
[30]
[32]PIPE
[6]
[7]
[5]
[8]
[9]
[8]
[10]
[12]
[13]
[14]
[16]
-TUBING
mm
[IN]
mm
[FT]
mm
[FT]
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE:
SEE SPECIFICATIONS FOR DETAILED HANGER REQUIREMENTS
ABOVE 2" DIA. PIPE 2" DIA. & SMALLER
2 1/2" DIA.
ABOVE 2" DIA. PIPE 2" DIA. & SMALLER
2 1/2" DIA.
HORIZONTAL
VERTICAL
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" BALL VALVE
ADAPTER TO 3/4" HOSE
THREAD-PROVIDE HOSE CAP NUT
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
TYPICAL CHILLED PIPING
DRAIN VALVE CONNECTIONS
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE
RISER DIAGRAMS AND/OR PLANS, LOCATE DRAIN
AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2" BALL VALVE
1/4" COPPER TUBING
1/2" x 4" NIPPLE
CIRCULATING WATER PIPING
ELEVATION
TYPICAL MANUAL AIR VENT
NOTES:
1. VENT ALL HIGH POINTS AS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE
TO NEAREST DRAIN.
MV
OR
AV
HVAC DESIGN DATA
GENERAL NOTES:
A. OUTDOOR DESIGN CONDITIONS:
93.4°F DB SUMMER
76.4°F WB SUMMER
5.4°F DB WINTER
NOTES:
1. LISTED RH IS MAXIMUM ANTICIPATED AT LISTED
DB TEMPERATURE.
2. REFER TO ATC SEQUENCES FOR ACTUAL
ROOM SETPOINTS.
3. "FLOATING" MEANS THERE IS NO ACTIVE CONTROL.
4. MINIMUM TOTAL AIR CHANGE RATE IS TO BE BASED ON SUPPLY CFM FOR
POSITIVE AND NEUTRAL SPACES, EXHAUST CFM FOR NEGATIVE SPACES.
SPACE NAME / TYPE °F DB
INTERIOR DESIGN DATA
SUMMER WINTER
% RH
(NOTE 1,3) °F DB
% RH
(NOTE 1,3)
NA NA NATOILET & HAC NA
B. DESIGN ALTITUDE: 479 FT.
OFFICE 75 60 70 FLOATING
MINIMUM
TOTAL AIR
CHANGES
(NOTE 4)
86 FLOATING 40CHILLER & ELECTRIC RMS FLOATING -
80.6 60 64TELECOMMUNICATION FLOATING -
DUCT CONSTRUCTION, SEALING, AND INSULATION
GENERAL NOTES:
A. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:
SHEET METAL DUCT; INTERIOR LINING; EXTERIOR
INSULATION; ETC.
B. DUCT CONSTRUCTION AND SEALING SHALL BE PER
LATEST S.M.A.C.N.A. STANDARDS.
NOTES:
1. ROUND SHEET METAL RUN-OUTS TO AIR DEVICES DOWNSTREAM OF VAV BOXES SHALL BE EXTERNALLY INSULATED.
2. RETURN DUCTWORK FOR AHU-2 SHALL BE INSULATED.
3. WATERTIGHT SEAL.
4. INSULATE FROM 24" UPSTREAM OF BACKDRAFT / ISOLATION DAMPER TO PENETRATION OF WALL / ROOF.
5. CONCEALED ROUND RUNOUT DUCTS TO AIR DEVICES MAY BE 1" S.P. CLASS.
DUCT SYSTEM
S.P. CON-
STRUCT.
SEAL
CLASS
LEAKAGE
CLASS
S.M.A.C.N.A. CLASS.
INTERNALLY
LINED
EXTERNAL
INSULATION
NOT
INSULATED
SEE
NOTE
DOUBLE
WALL
INSULATEDRECT RND
2,5
NOTE 4
NOTE 4
+3" A 8
+1" 16
16 8
16 8
A
A
A
A
A
A
SUPPLY DUCTWORK UPSTREAM OF
VAV BOXES
SUPPLY DUCTWORK DOWNSTREAM OF
VAV BOXES
SUPPLY DUCTWORK DOWNSTREAM
FOR SINGLE ZONE AHU-1
+2"
RETURN DUCTWORK -2"
TOILET OR GENERAL EXHAUST
DUCTWORK
-1"
RELIEF AIR DUCTWORK AND PLENUMS
OUTSIDE AIR DUCTWORK AND
PLENUMS
+1
-1"
NOTES:
1. DRUM LOUVER, ANGLED 45 DEG. DOWN UNLESS NOTED OTHERWISE.
2. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOUVERS, INCLUDING MOUNTING HEIGHT, EXACT LOCATION, AND COLOR.
3. FILTER GRILLE IS FOR ACCESS TO FIRE DAMPER. NO FILTER REQUIRED.
GENERAL NOTES:
A. ALL LAY-IN AIR DEVICES SHALL FIT IN 24"X24" LAY-IN CLG SYSTEM.
VERIFY GRID TYPE AND COORDINATE AIR DEVICE COMPATIBILITY.
B. FINISH KEY: "W.B.E." - WHITE BAKED ENAMEL;
"E.C.L." - ETCHED CLEAR LACQUER OR ANODIZED;
"C.C.B.A." - CUSTOM COLOR SELECTED BY ARCHITECT.
C. SUPPLY AIR DIFFUSERS SHALL BE 4-WAY BLOW, UNLESS
INDICATED OTHERWISE BY ARROWS ON DRAWINGS.
D. PROVIDE AUX. FRAMES FOR AIR DEVICES IN PLASTER,
GYPSUM BOARD, TILE OR OTHER HARD SURFACES.
AIR DISTRIBUTION DEVICES
M A
R K
DESCRIPTION
MOUNTING TYPE SLOTS MATERIAL FINISH
O P
P O
S E
D B
L A
D E
D A
M P
E R
S Q
-T O
-R D
N E
C K
A D
A P
T O
R
BASIS OF DESIGN S
E
E N
O T
E
L A
Y -I
N
S U
R F
A C
E
D U
C T
S P
L
IN
E
S N
A P
-I N
Q U
A N
T
IT
Y
W
ID
T H
S T
E E
L
A L U
M
IN
U M
S T
A
IN
L E
S S
S T
E E
L
W .B
.E
E .C
.L
C .C
.B .A
BG1 HEAVY DUTY RETURN GRILLE ● ● ● TITUS - 30RS
BG2 HEAVY DUTY EXHAUST GRILLE ● ● ● TITUS - 30RS
CD1 STANDARD SQ. PLAQUE CEILING DIFFUSER -
ROUND NECK - 24 X 24
● ● ● TITUS - OMNI
CG1 EGGCRATE CEILING GRILLE ● ● ● TITUS - 50F
CR1 EGGCRATE CEILING REGISTER ● ● ● ● TITUS - 50F
L1 LOUVER ● 2
TG1 SIDEWALL FILTER RETURN GRILLE ● ● ● TITUS - 350RLF 3
TG2 SIDEWALL RETURN GRILLE ● ● ● TITUS - 350ZRS
TR1 DRUM LOUVER ● ● ● TITUS - DL 1
TR2 AEROBLADE SUPPLY GRILLE ● ● ● TITUS - 272FL
SCALE: NONE
INSTALLATION OF THERMOMETER WELLS
SCALE: NONE
CHILLED WATER COILS - PIPING CONNECTIONS
SCALE: NONE
DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC SYSTEMS)
SCALE: NONE
PIPE HANGERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S.…