657A5-21-401 - Drawings R2_Part4 - 19 pages.pdf

PDF 15 MB Posted

Attached to
Z2DA--657A5-21-401, Construct New Campus Chiller Plant, MRN
Solicitation number
36C25526R0129
Issued by

About this file

This document is a comprehensive set of contract drawings and mechanical engineering documents for the Marion VA Medical Center's New Energy Center project, prepared by RMF Engineering and FFE as the architect/engineer of record. The drawings detail the complete HVAC system design including ductwork, piping, controls, and equipment specifications for a new facility construction project.

The mechanical scope includes two air handling units (AHU-1 and AHU-2) with capacities of 8,000 CFM and 3,500 CFM respectively, serving the chiller plant, electrical rooms, and control room functions. The system incorporates variable air volume (VAV) terminal units with electric reheat, exhaust fans for refrigerant and toilet exhaust, gravity roof ventilators, split system AC units, and propeller-type electric unit heaters. Chilled water distribution utilizes 12-inch and 8-inch piping with three centrifugal chillers and condenser water cooling towers. The control system features a building automation system (BAS) with direct digital controls, including zone sensors, air flow measuring stations, fire and smoke dampers, and extensive safety interlocking. Ductwork construction specifies SMACNA standards with external insulation on supply runs, acoustic lining where required, and sealing classes ranging from +3" to -2" water column static pressure. The documents include detailed specifications for equipment bases, seismic bracing, roof curb installations, and comprehensive piping connection details for chilled water, condenser water, and miscellaneous hydronic systems. Design conditions are based on 93.4°F summer and 5.4°F winter outdoor air with 479-foot design altitude.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4"

P-103

P-414

P-502

P-806

DWH-1

TMV-E

P-709

P-801

P-801

P-801

0.5"

1"

1.5"

0.5"

0.5"

0.5"

0.75"

1.5"

0.75"

0.75"

3"

3"

ET-1

P-802

0.5"

0.75" 0.75"

0.75"

P-802

P-802

P-801

1.5"

2.5"

2.5"

1"

0.5"

1ST FLR

1.25" 0.5"0.5"

N.T.S.Scale:

DOMESTIC WATER ISOMETRIC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

P903

DOMESTIC ISOMETRIC

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

PLAN NOTES

1 FROM SITE.

2 TO FIRE PROTECTION.

3 WATER METER.

4 BACKFLOW PREVENTER

5 TO HVAC.

1 CONTRACT DOCUMENTS 05/07/2026

NOTE:

ALL SYMBOLS AND ABBREVIATIONS ARE

SUBJECT TO MODIFICATIONS ON OTHER

DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT

NOT NECESSARILY BE USED ON THIS

PROJECT.

ABBREVIATIONS

AC - AIR COMPRESSOR OR AIR CONDITIONER

ACCU - AIR COOLED CONDENSING UNIT

AD - ACCESS DOOR OR AREA DRAIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AFMS - AIR FLOW MEASURING STATION

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATC - AUTOMATIC TEMPERATURE CONTROL

(SYNONYMOUS WITH BAS)

BAS - BUILDING AUTOMATION SYSTEM

BDD - BACK DRAFT DAMPER

BFP - BACKFLOW PREVENTER

BLDG - BUILDING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BTU - BRITISH THERMAL UNIT

BTUH - BRITISH THERMAL UNIT PER HOUR

CBD - COUNTER BALANCED BACKDRAFT DAMPER

CFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CFM - CUBIC FEET PER MINUTE

CHS - CHILLED WATER SUPPLY

CHR - CHILLED WATER RETURN

CHGR - CHILLED WATER GLYCOL SOLUTION RETURN

CHGS - CHILLED WATER GLYCOL SOLUTION SUPPLY

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CO - CLEAN OUT

CO2 - CARBON DIOXIDE

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CT - COOLING TOWER

CTR - CENTER

CU - COPPER

CW - COLD WATER

CWR - CONDENSER WATER RETURN

CWS - CONDENSER WATER SUPPLY

D - DRAIN LINE

DB - DRY BULB

DDC - DIRECT DIGITAL CONTROLS

DI - DEIONIZED WATER

DIA - DIAMETER

DIM - DIMENSION

DN - DOWN

DWG - DRAWING

EA - EACH OR EXHAUST AIR

EAT - ENTERING AIR TEMPERATURE

EC - ELECTRICAL CONTRACTOR (DIVISION 26)

EF - EXHAUST FAN

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATOR

EQUIP - EQUIPMENT

ET - EXPANSION TANK

ETR - EXISTING TO REMAIN

EQS - EQUIPMENT SUPPLIER

EWT - ENTERING WATER TEMPERATURE

EXH - EXHAUST

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

FD - FLOOR DRAIN

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FOB - FLAT ON BOTTOM

FOF - FUEL OIL FLOW

FOG - FUEL OIL GAUGE

FOR - FUEL OIL RETURN

FOS - FUEL OIL SUPPLY

FOT - FLAT ON TOP

FPM - FEET PER MINUTE

FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)

FT - FEET

FTG - FOOTING

G - GAS OR NATURAL GAS

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GC - GENERAL TRADES CONTRACTOR

GPM - GALLONS PER MINUTE

HB - HOSE BIBB

HC - HVAC CONTRACTOR (DIVISION 23)

HD - HUB DRAIN

HG - REFRIGERANT HOT GAS

HP - HORSEPOWER

HPC - HIGH PRESSURE CONDENSATE RETURN

HPS - HIGH PRESSURE STEAM SUPPLY

HR - HOUR

HT - HEAT TRACE

HTR - HEATER

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

INV - INVERT ELEVATION

IN - INCHES

KEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTH

LAT - LEAVING AIR TEMPERATURE

LAV - LAVATORY

LBS - POUNDS

LPC - LOW PRESSURE CONDENSATE RETURN

LPS - LOW PRESSURE STEAM SUPPLY

LWT - LEAVING WATER TEMPERATURE

MAX - MAXIMUM

MDD - MOTORIZED DAMPER

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

MPC - MEDIUM PRESSURE CONDENSATE

RETURN

MPS - MEDIUM PRESSURE STEAM SUPPLY

MU - WATER MAKE-UP

N/C - NORMALLY CLOSED

NIC - NOT IN CONTRACT

N/O - NORMALLY OPEN

NOM - NOMINAL

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

OA - OUTDOOR AIR

OBD - OPPOSED BLADE DAMPER

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR

INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

P - PROPANE GAS

PC - PLUMBING CONTRACTOR (DIVISION 22)

OR PUMPED CONDENSATE RETURN

PLBG - PLUMBING

PRESS - PRESSURE

PRV - PRESSURE REGULATING VALVE

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSIG - POUNDS PER SQUARE INCH GAUGE

PTAC - PACKAGED TERMINAL AIR CONDITIONER

RA - RETURN AIR

RAD - RADIUS

RCP - REFLECTED CEILING PLAN

RD - ROOF DRAIN

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RL - REFRIGERANT LIQUID

ROS - REVERSE OSMOSIS WATER SUPPLY

ROR - REVERSE OSMOSIS WATER RETURN

RPM - REVOLUTIONS PER MINUTE

RS - REFRIGERANT SUCTION

S - SPRINKLER (WET)

SA - SUPPLY AIR

SAN - SANITARY OR SANITARY DRAIN

SCH - SCHEDULE

SCW - SOFT COLD WATER

SHT - SHEET

SPEC - SPECIFICATIONS

SQ - SQUARE

SR - SUPPLY RISER

SRV - SAFETY RELIEF VALVE

SS - STAINLESS STEEL

STD - STANDARD

STM - STORM OR STORM DRAINAGE

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TA - TRANSFER AIR

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQUIPMENT

TOF - TOP OF FOOTING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TYP - TYPICAL

UH - UNIT HEATER

UNO - UNLESS NOTED OTHERWISE

V - VENT

VAC - VACUUM

VAV - VARIABLE AIR VOLUME

VEL - VELOCITY

VFD - VARIABLE FREQUENCY DRIVE

(ADJUSTABLE FREQUENCY

MOTOR CONTROLLER)

VIB - VALVE IN BOX

VOL - VOLUME

VTR - VENT THROUGH ROOF

VR - VENT RISER

W/ - WITH

W/O - WITHOUT

WB - WET BULB

WCO - WALL CLEANOUT

GENERAL FLOOR PLAN NOTES

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN UNLESS

NOTED OTHERWISE.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

A1

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS

REFER TO SCHEDULES.

H1 H1OR

EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO

SCHEDULES.

H2

B

H2

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION

H2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

H2 = SHEET WHERE DETAIL IS LOCATED

A1 "UP TO" SYMBOL (ITEM ON FLOOR ABOVE)

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF

EQUIPMENT, UNLESS NOTED OTHERWISE

10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOD: 8' - 10"

BOD: 7' - 2"

20x20

20x20

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF

DUCTWORK, UNLESS NOTED OTHERWISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE,

UNLESS NOTED OTHERWISE

DL-1

UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH

UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE WITH GC.

DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.

CONNECT TO EXISTING

HVAC PIPING DESIGNATIONS

CHILLED WATER SUPPLY PIPECHS

CONDENSER WATER SUPPLY PIPECWS

CONDENSER WATER RETURN PIPECWR

DRAIN LINE. PITCH IN DIRECTION INDICATEDD

HEATING HOT WATER SUPPLY PIPEHWS

HEATING HOT WATER RETURN PIPEHWR

WATER MAKE-UP PIPEMU

VENT PIPEV

REFRIGERANT LIQUID LINERL

REFRIGERANT SUCTION LINERS

EXPANSION TANK PIPEET

REFRIGERANT HOT GAS LINEHG

LOW PRESSURE CONDENSATE RETURN PIPELPC

LOW PRESSURE STEAM SUPPLY PIPELPS

MEDIUM PRESSURE CONDENSATE RETURN PIPEMPC

MEDIUM PRESSURE STEAM SUPPLY PIPEMPS

PUMPED CONDENSATE RETURN PIPEPC

HIGH PRESSURE CONDENSATE RETURN PIPEHPC

HIGH PRESSURE STEAM SUPPLY PIPEHPS

STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.10

MISC SYMBOLS

DUCTWORK SYMBOLS

ROUND BRANCH DUCTWORKCONICAL

FITTING

ACOUSTIC

FITTING

ACOUSTIC

FITTING

ADAD

D

R R

D

RECTANGULAR BRANCH DUCTWORK

SQUARE TEE WITH TURNING VANES

NOTE: ALL SQUARE ELBOWS IN

RECTANGULAR AND ROUND / OVAL

DUCTWORK SHALL BE PROVIDED WITH

TURNING VANES. REFER TO

SPECIFICATIONS FOR ADDITIONAL DETAILS.

EXISTING DUCTWORK TO REMOVED

RETURN AIR, RELIEF AIR, OR TRANSFER AIR

DUCTWORK. (UP AND DOWN) RADIUSED

OR SQUARE WITH TURNING VANES.

SUPPLY AIR OR OUTDOOR AIR DUCTWORK.

(UP AND DOWN) RADIUSED OR SQUARE

WITH TURNING VANES.

EXHAUST AIR DUCTWORK. (UP AND DOWN)

RADIUSED OR SQUARE WITH TURNING

VANES.

RECTANGULAR AND ROUND / OVAL

DUCTWORK RISE / DROP WITH 90° RADIUSED

OR SQUARE ELBOWS AND TURNING VANES.

RADIUS ELBOW

90° SQUARE ELBOW (WITH TURNING VANES)

NOTE: ALL SQUARE ELBOWS IN

RECTANGULAR AND ROUND DUCTWORK

SHALL BE PROVIDED WITH TURNING VANES.

ACCESS DOOR OR PANEL

DUCTWORK RISE IN DIRECTION OF AIR

FLOW

DUCTWORK DROP IN DIRECTION OF AIR

FLOW

DUCTWORK WITH ACOUSTICAL LINER.

LISTED DUCT SIZES ARE INSIDE CLEAR

DIMENSIONS.

RECTANGULAR ROUND / OVAL

FLEXIBLE DUCTWORK

FLEXIBLE CONNECTION

DUCTWORK CONSTRUCTED OF SPECIAL

MATERIAL AS NOTED

DIRECTION OF PITCH

RECTANGULAR DUCTWORK DIMENSIONS

(W x H)26x20

ROUND DUCTWORK DIMENSIONS (DIA)26ø

OVAL DUCTWORK DIMENSIONS (W x H)26x20 OV

DUCTWORK DEVICE SYMBOLS

CEILING, WALL, OR DUCTWORK MOUNTED SUPPLY, RETURN, OR EXHAUST AIR DEVICE.

T10 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE SCHEDULE FOR VARIOUS

DESIGNATIONS). 20x12 = DEVICE SIZE (IN INCHES). 300 = REQUIRED CFM. FOR NON-CEILING

MOUNTED DEVICES, 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF GRILLE.

A10 10ø

MANUAL BALANCING DAMPER WITH LOCKING DEVICE

BDD = BACK DRAFT DAMPER

CBD = COUNTER-BALANCED BACK DRAFT DAMPER

SD = SMOKE DAMPER

FS = COMBINATION FIRE - SMOKE DAMPER

MDD = MOTORIZED DAMPER

AFMS = AIR FLOW MEASURING STATION

DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.

HUMIDITY SENSOR - DUCT MOUNTED

T10 20x12

BOG: 9'-0"

XXX

A-D

XX

H

SD

SP

CEILING MOUNTED SUPPLY AIR DEVICE. ALL AIR DEVICES DISCHARGE 4-WAY UNLESS NOTED

OTHERWISE ON PLANS WITH FLOW ARROWS. A10 = DESIGNATION (REFER TO FLOOR PLANS

AND AIR DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS). 10ø = NECK SIZE (IN INCHES).

300 = REQUIRED CFM.

FIRE DAMPER

A = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)

D OR S = DYNAMIC OR STATIC

STATIC PRESSURE SENSOR - DUCT MOUNTED

C

CARBON DIOXIDE SENSOR - DUCT MOUNTED

S

TEMPERATURE SENSOR - DUCT MOUNTED

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON

APPLICATIONS)

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUGE OR THERMOMETER

VALVES AND FITTINGS

10"

TOE: 3' - 0"

BOE: 0' - 6"

CHILLED WATER GLYCOL SOLUTION RETURN PIPECHGR

CHILLED WATER GLYCOL SOLUTION SUPPLY PIPECHGS

CHILLED WATER RETURN PIPECHR

SQUARE THROAT / RADIUS HEEL

FITTINGS NOT ACCEPTABLE

PIPING SYMBOLS

DOUBLE LINE SINGLE LINE

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE:

BULLHEAD TEE'S ARE NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOWN

ELBOW UP

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

DD

RR

PIPE RISER

RADIUS'D BRANCH

RADIUS'D TEE

EXISTING DUCTWORK TO REMAIN

UNLESS NOTED OTHERWISE ON DRAWINGS,

15° MAX FOR DIVERGING, 30° MAX FOR

CONVERGING TRANSITION

EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERWISE.

SPACE TEMPERATURE SENSOR / THERMOSTAT. WHEN WALL MOUNTED, MOUNTING

HEIGHT 46" TO MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH

COORDINATE WITH ARCHITECT.

T

DP

DIFFERENTIAL PRESSURE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO

MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH

ARCHITECT.

H

HUMIDITY SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.

CARBON DIOXIDE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.

C

CO

CARBON MONOXIDE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET

ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH

ARCHITECT.

TEMPERATURE SENSOR. WHEN WALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH

ARCHITECT.

S

S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.

STATIC PRESSURE SENSOR.SP

DRAIN VALVE WITH HOSE END CONNECTION

EXPANSION JOINT

MANUAL AIR VENT

AUTOMATIC AIR VENT

PRESSURE REDUCING VALVE

QUICK OPENING MANUAL VALVE

VACUUM BREAKER

NEEDLE VALVE

PRESSURE AND TEMPERATURE TEST PLUG

VACUUM GAUGE WITH STOP

END CAP

GLOBE VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE ON RISER

A

M

M

N

V

VB

SOLENOID VALVE

S

SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE DISCHARGE AIR GAPPED TO

FLOOR DRAIN UNLESS NOTED OTHERWISE. FOR STEAM SYSTEMS PIPE DISCHARGE

TO OUTDOORS.

WATER METERM

PRESSURE GAUGE WITH COCK AND SIPHON LOOP

BI-METALIC STEAM TRAP AND DRIP ASSEMBLY

THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY

BM

TD

IB

FT

TS

FLOW METER

F

UNION

CLEANOUT

STRAINER

M

MODULATING 2 PORT AUTOMATIC CONTROL VALVE

M

MODULATING 3 PORT AUTOMATIC CONTROL VALVE

M

COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

STRAINER WITH A BLOW DOWN VALVE AND HOSE CONNECTION

AUTOMATIC FLOW CONTROLLER WITH P/T PLUG IN AND OUT

2 PORT AUTOMATIC CONTROL VALVE, 2-POSITION UNLESS SPECIFIED OTHERWISE

3 PORT AUTOMATIC CONTROL VALVE, 2-POSITION UNLESS SPECIFIED OTHERWISE

AUTOMATIC PRESSURE INDEPENDENT CONTROL VALVE

THERMODYNAMIC STEAM TRAP AND DRIP ASSEMBLY

INVERTED BUCKET STEAM TRAP AND DRIP ASSEMBLY

FLOAT AND THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY

DEMOLISH TO POINT INDICATED

CEILING OR WALL MOUNTED LINEAR SLOT AIR DEVICE. S10 = DESIGNATION (REFER TO

FLOOR PLANS AND AIR DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS). 48"L = DEVICE

LENGTH. 8ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM.

S10-48"L 8ø

GENERAL NOTES

A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.

B. THE DRAWINGS AND SPECIFICATIONS SHALL BE CAREFULLY STUDIED DURING THE COURSE OF BIDDING. ANY ERRORS, OMISSIONS OR DISCREPANCIES ENCOUNTERED SHALL BE REFERRED IMMEDIATELY TO THE

ARCHITECT/ENGINEER FOR INTERPRETATION OR CORRECTION.

C. INSULATE DUCTWORK AND PIPING WHERE EXISTING INSULATION HAS BEEN DAMAGED AND/OR REMOVED IN

THE PERFORMANCE OF WORK IN THIS PROJECT.

D. PROVIDE ALL ROOFING PENETRATION, REPAIR & REINFORCEMENT IN THE EXISTING BUILDING FOR WORK INDICATED. ENGAGE A ROOFING SUBCONTRACTOR TO PERFORM THE ROOFING WORK. WHERE ROOFING WORK IS REQUIRED, THE EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT, REMOVED AND RESTORED AS REQUIRED TO ATTAIN A WATERTIGHT CONDITION. THE ROOFING SUB-CONTRACTOR SHALL BE A CERTIFIED INSTALLER FOR SUCH INSTALLATION TO MAINTAIN THE EXISTING WARRANTY ON THE ROOF.

E. REFER TO ALL SPECIFICATION SECTIONS AND THESE DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY ARRANGEMENT FOR WORK. THE VARIOUS DRAWINGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT ALL TIMES. REFER TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE CONTRACTING OFFICERS REPRESENTATIVE (COR) THRU

THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE PROCEEDING.

F. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR THE CONDITIONS ON THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. THIS WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. SEE SPECIFICATIONS FOR MORE SPECIFIC DETAILS ON

RESPONSIBILITIES.

G. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND COR TO MAINTAIN OPERATION OF

THE EXISTING FACILITY.

H. COORDINATE ALL WORK WITH THE WORK OF OTHERS. KEEP INFORMED OF THE PROGRESS AND DETAIL DEVELOPMENT OF THE WORK OF OTHERS. COORDINATE AND EXPEDITE WORK WITH OTHERS SO THAT THE

PROGRESS OF THE TOTAL WORK SHALL BE KEPT ON SCHEDULE.

I. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL GOVERNING CODES AND STANDARDS.

J. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON VISUAL OBSERVATION AND/OR AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.

K. FITTING OR PLACING WORK INTO OR ON THE WORK OF OTHERS CONSTITUTES ACCEPTANCE OF THE SUITABILITY OF THE WORK IN PLACE. IF THE WORK OF OTHERS IS NOT ACCEPTABLE, NOTIFY THE CONTRACTING OFFICERS REPRESENTATIVE (COR) FOR THE WORK TO BE CORRECTED. ANY NEW WORK INSTALLED IN UNSUITABLE EXISTING CONDITIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR TRADE INSTALLING THE NEW WORK. NO CLAIMS FOR ADDITIONAL COMPENSATION FOR CORRECTING WORK

INSTALLED IN UNSUITABLE EXISTING CONDITIONS WILL BE CONSIDERED.

L. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND FIRE-RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE-STOPPED AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED. COORDINATE WITH ALL TRADES

TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS AND DETAILS ARE MET.

M. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT & OTHER SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS THROUGH 0-HOUR RATED WALLS SHALL BE SEALED

WITH ACOUSTICAL CAULK TO RETARD PASSAGE OF SMOKE.

N. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET

INSIDE DIMENSIONS.

O. PROVIDE DUCT ACCESS PANELS AS REQUIRED BY 23 31 00 FOR ACCESS TO FIRE DAMPERS, SMOKE DAMPERS, SMOKE DETECTORS, AUTOMATIC CONTROL DAMPERS, AND HUMIDIFIER DISPERSION TUBES. REFER TO DETAIL ON SHEET 00. COORDINATE SIZES AND LOCATIONS WITH ACCESSORIES PROVIDED BY OTHER TRADES.

P. ACCESS PANELS IN NON ACCESSIBLE SUSPENDED CEILINGS SHALL BE PROVIDED FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, FLOW METERS, CONTROLS, ETC. COORDINATE SIZES AND LOCATIONS WITH OTHER

TRADES.

Q. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS, COILS, ETC.

R. FOR TYPICAL STEAM, WATER AND REFRIGERANT PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD

DETAILS AND PIPING SCHEMATICS.

S. DIFFUSER SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES. REGISTER AND GRILLE SIZES SHOWN ARE FACE

SIZES.

T. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING DIFFUSERS, REGISTERS, AND GRILLES.

U. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO PROVIDE COUNTER

FLOW BETWEEN WATER AND AIR.

V. WHERE DUCTS OR PIPES ARE REMOVED THRU WALL/FLOOR/ROOF THAT IS TO REMAIN, PATCH

WALL/FLOOR/ROOF OPENING TO MATCH EXISTING WHERE OPENING IS NOT RE-USED.

W. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE CONTRACT. REFINISH

ANY SURFACE DISTURBED UNDER THIS WORK TO MATCH EXISTING.

X. IN GENERAL, KEEP DUCT AND PIPING MAINS TIGHT TO UNDERSIDE OF STRUCTURE.

Y. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED BY THE VA SHALL BE

REMOVED FROM THE PREMISES AND DISPOSED OF PROPERLY BY THE CONTRACTOR.

Z. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES

AND REPORT IMMEDIATELY ANY DIFFICULTIES WHICH CAN BE ANTICIPATED.

AA. FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND EQUIPMENT SIZES, SERVICES AND

LOCATIONS PRIOR TO PERFORMING WORK.

BB. ALL ABANDONED EXTRANEOUS PIPING, DUCTWORK, SUPPORTS, CONTROLS, ETC. SHALL BE REMOVED.

CC. ALL EXISTING DUCTWORK, PIPING, EQUIPMENT, CONTROLS, ETC. SHOWN ON REMOVAL PLAN(S) SHALL BE REMOVED. THE MAJORITY OF WORK TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL AND/OR ABANDONED DUCTWORK, PIPING, ETC. THAT MAY NOT BE SHOWN BUT IS ASSOCIATED WITH THE REMOVAL

WORK.

DD. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE BY PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON PORTABLE LADDERS. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL

TYPES OF VALVES, FILTERS AND STRAINER, TRANSMITTERS, CONTROL DEVICES, ETC.

EE. WHERE EXISTING HVAC UTILITIES IN SERVICE WILL BE DISRUPTED DURING THE CONSTRUCTION OF THIS PROJECT, THIS WORK SHALL BE PERFORMED ON WEEKENDS OR WEEK NIGHTS. DOWNTIME SHALL BE KEPT TO

A MINIMUM, AND SHALL BE COORDINATED AND SCHEDULED WELL IN ADVANCE WITH THE COR.

FF. REFER TO ELECTRICAL DRAWINGS FOR VARIABLE SPEED MOTOR CONTROLLERS ASSOCIATED WITH

MECHANICAL EQUIPMENT.

GG. ALL INSULATED DUCTWORK AND PIPING SHALL HAVE DAMPER/VALVE HANDLE EXTENSIONS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:0

P M

M001

ABBREVIATIONS, LEGEND, &

GENERAL NOTES

05/07/2026 WJS MGN

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SHEET LIST

SHEET NUMBER SHEET NAME

M001 ABBREVIATIONS, LEGEND, & GENERAL NOTES

MD101 BUILDING 49 DEMOLITION PLAN

MH101 FIRST FLOOR PLAN - HVAC

MH102 MEZZANINE PLAN - HVAC

MH103 ROOF PLAN - HVAC

M401 SECTIONS & AHU DETAILS

M501 DETAILS

M502 DETAILS

M503 DETAILS & SCHEDULES

M601 SCHEDULES

M701 CONTROLS

M702 CONTROLS

M703 CONTROLS

PTAC

EF

ON ROOF

EF

UH

M

UH

UH

UH

UH

EF

EF

ON ROOF

CHILLERCHILLERCHILLER

CT CT CT

PUMP PUMP PUMP

PUMP

PUMP

PUMP

PUMPPUMPPUMP

EF

ON ROOF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:2

P M

MD101

BUILDING 49 DEMOLITION PLAN

05/07/2026 WJS MGN

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

FIRST FLOOR - DEMOLITION PLAN

A. REMOVAL PLANS MAY NOT NECESSARILY SHOW ALL ITEMS REQUIRED TO BE REMOVED.

B. REMOVE ALL ABANDONED EXTRANEOUS CONDUITS, SUPPORTS, CONTROLS, ETC.

C. ALL EXISTING CONDUIT, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED SHALL BE REMOVED. THE

MAJORITY OF HVAC WORK TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL ITEMS ASSOCIATED

WITH THE DEMOLITION WORK.

D. COORDINATE WITH THE OWNER IN REGARD TO REMOVALS. SALVAGE EQUIPMENT AS DIRECTED BY THE

OWNER AND STORE IN A LOCATION DESIGNATED BY THE OWNER. ALL OTHER EQUIPMENT AND

MATERIALS NOT SALVAGED SHALL BE REMOVED FROM THE PREMISE.

GENERAL NOTES

1. THE ENTIRE AREA WITHIN THE DASHED LINES SHALL BE REMOVED MECHANICALLY. MAJOR EQUIPMENT SHOWN. REMOVE ALL HVAC AND MECHANICAL EQUIPMENT, AND ALL ASSOCIATED DUCTWORK, AIR

DEVICES, PUMPS, PIPING, CONTROLS, ETC.

PLAN NOTES

T

T

T T

T

T

T

T

A

D

632 54

B

C

ELECTRICAL ROOM

ELECTRICAL ROOM

H.A.C.

AC-1

TR

CONTROL

ROOM

VAV-1

VAV-2

VAV-3

x1

UP22x10 EA

UP22x10 EA

22x10

UP22x10 EA

CHILLER PLANT

TOILET

8x10

22x12

UH-1

UH-2

UH-4

UH-3

1230 CFM

BG2

18x18

BOG: 0' - 7"

1230 CFM

BG2

18x18

BOG: 0' - 7"

1230 CFM

BG2

18x18

BOG: 0' - 7"

R

R

R

3000 CFM

BG1

24x42

BOG: 0' - 7"

UP24x16

18x14

20x10

730 CFM

TR1

20x10

730 CFM

TR1

1250 CFM

TG1

36x16

18x16

20x10

615 CFM

TR1

20x10

615 CFM

TR1

20x10

620 CFM

TR1

8ø

CD1

190 CFM

1580 CFM

TG1

48x16

6ø

CR1

115 CFM

8ø

CR1

150 CFM

8ø

CG1

170 CFM

12x10

UH-5

UP10x8 EA

A-S

B-S

A-S

AC-2

R

R

R

R

7 UP10x8 EA

UP22x10 RA

UP22x12 RA

UP14x34 SA

310 CFM

BG2

10x10

BOG: 0' - 7"

B-S

AHU-1

TYP.

TYP.

TYP.

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:2

P M

MH101

FIRST FLOOR PLAN - HVAC

05/07/2026 WJS MGN

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN - HVAC

GENERAL NOTES

1. TERMINATE EXHAUST DUCT 0'-6" A.F.F. DUCT IN VERTICAL SHALL BE CONSTRUCTED OF 18 GAUGE SHEET

METAL.

2. REFRIGERANT LEAK DETECTION MONITORING CONTROL PANEL. PROVIDE REFRIGERANT SENSORS AS

SHOWN ON THE FLOOR PLAN.

3. REFRIGERANT LEAK DETECTION ALARM SYSTEM, SIGNAGE, AND LABELING PER THE FIRE CODE AND APPROVED BY THE AHU. ALARM SYSTEM SHALL INCLUDE A HORN AND STACK LIGHT, WITH A SILENCE BUTTON FOR THE HORN. SUBMIT LAYOUT AND PRODUCT INFORMATION TO ENGINEER FOR REVIEW PRIOR

TO SEEKING AHJ APPROVAL.

4. SUSPEND UNIT HEATER FROM STRUCTURE AT APPROXIMATELY 8'-0" A.F.F.

5. EXTEND CONDENSATE DRAIN PIPING TO HAC. TERMINATE IN MOP SINK.

6. REFRIGERANT LEAK DETECTION SENSOR. MOUNT AT HEIGHT AS RECOMMENDED BY THE CHILLER

MANUFACTURER.

7. TERMINATE EXHAUST DUCT 0'-6" ABOVE PIT FLOOR. DUCT IN VERTICAL SHALL BE CONSTRUCTED OF 18

GAUGE SHEET METAL. COORDINATE EXACT LOCATION WITH OTHER TRADES.

8. CHILLED WATER SYSTEM EQUIPMENT SHOWN FOR REFERENCE ONLY REFER TO MP SERIES SHEETS FOR

ADDITIONAL DETAIL.

PLAN NOTES

A. REFER TO SHEET M001 ABBREVIATIONS, LEGEND, AND ADDITIONAL GENERAL NOTES.

A

D

632 54

B

C

MEZZANINE

CHILLER PLANT

DN22x10 EA

DN22x10 EA

28x18

DN10x8 EA

UP10x8 EAUP26x18 OA

AHU-1

M401

14x12 x1

DN24x16

5000 CFM

TG2

56x16

20x12

900 CFM

TR1

20x12

900 CFM

TR1

20x12

900 CFM

TR1

20x12

900 CFM

TR1

20x12

900 CFM

TR1

20x12

900 CFM

TR1

20x12

900 CFM

TR1

20x12

900 CFM

TR1

x1 x1

22x10

UP26x26

18x8

400 CFM

TR1

80x42 L1 x2

26x26

2 2

RF-2

DN22x10 EA

BOD: 6' - 3"

M401

3 4 5

3 4 5

24x20 20x20 20x20

6 6

7 8

24x20

MD

MD

VD

VDVD

VD

VD

VD VD

VD

VD

VD

12x12

400 CFM

TR2

VD

28x16

VD

VD

VD6

BOD: 16' - 9"

DN10x8 EA x1

D

22x22

48x16

BOD: 5' - 9"

BOD: 17' - 4"

D

VD

x1

3" - CHR

3" - CHS

3"

C H

R

3"

C H

S

3"

C H

R 3"

C

H S

2"

C H

S 2"

C

H R x1

52x16

10x8

UP&DN

D

DN22x12 RA

VD

D

DN22x10 RA

AHU-2

R x1

D

D

10x8

BOD: 5' - 5"

2.5"2.5"

B O

D : 1

7'

0"

VD

AHU-1

TYP.

TYP.

TYP.

VD

SCALE: 1/4" = 1'-0"

MEZZANINE FLOOR PLAN - HVAC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:2

P M

MH102

MEZZANINE PLAN - HVAC

05/07/2026 WJS MGN

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

GENERAL NOTES

1. SLOPE BOTTOM OF RELIEF AIR PLENUM TOWARD LOUVER.

2. FIX AIR DEVICE AT 45 DEGREE ANGLE DOWN.

3. PROVIDE CONCRETE EQUIPMENT PAD PER DETAIL ON SHEET M502.

4. EXTEND CONDENSATE DRAIN PIPING TO FLOOR DRAIN PER DETAIL ON SHEET M502.

5. TRANSITION DUCTWORK TO FULL SIZE OF UNIT CONNECTIONS. PROVIDE FLEXIBLE DUCT CONNECTIONS

PER DETAIL ON SHEET M501.

6. TRANSITION DUCT TO FULL SIZE OF FAN INLET. APPROXIMATE SIZE SHOWN.

7. SUSPEND FAN FROM STRUCTURE WITH VIBRATION ISOLATION HANGERS.

8. PROVIDE 3 DUCT DIAMETERS STRAIGHT RUN AT INLET AND OUTLET.

9. REFER TO MP SERIES SHEETS FOR ISOLATION VALVES.

10. FIX AIR DEVICE IN HORIZONTAL POSITION.

11. EXTEND DUCT THRU MEZZANINE FLOOR. SEAL WATER TIGHT.

12. PROVIDE REFRIGERANT PIPING AND ACCESSORIES PER MANUFACTURER'S RECOMMENDATIONS.

APPROXIMATE ROUTE SHOWN. EXTEND THRU MEZZANINE FLOOR. SEAL WATER TIGHT.

13. APPROXIMATE LOCATION OF ROOF HATCH. COORDINATE DUCT ROUTING AND AIR DEVICE LOCATIONS

ACCORDINGLY.

14. EXTEND AHU DRAIN PIPING TO FLOOR DRAIN.

15. PROVIDE ROLL OVER PIPE PROTECTOR.

16. COVER EXHAUST FAN OPENING WITH HARDWARE CLOTH.

17. CHILLED WATER SYSTEM PIPING SHOWN FOR REFERENCE ONLY REFER TO MP SERIES SHEETS FOR

ADDITIONAL DETAIL.

PLAN NOTES

A. REFER TO SHEET M001 ABBREVIATIONS, LEGEND, AND ADDITIONAL GENERAL NOTES.

A

D

632 54

B

C

CU-1

M401

EF-1

EF-2

M401

CU-2

EF-3

SCALE: 1/4" = 1'-0"

ROOF PLAN - HVAC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:2

P M

MH103

ROOF PLAN - HVAC

05/07/2026 WJS MGN

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

A. REFER TO SHEET M001 ABBREVIATIONS, LEGEND, AND ADDITIONAL GENERAL NOTES.

B. COORDINATE ANY CHANGES REQUIRED TO STRUCTURAL SUPPORT FRAMING WITH ACTUAL PURCHASED

EQUIPMENT AS SHOWN ON APPROVED SHOP DRAWINGS.

C. MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURE IN ACCORDANCE WITH THE INTERNATIONAL

BUILDING AND MECHANICAL CODE. REFER TO SPECIFICATIONS 23 05 11 FOR REQUIREMENTS.

GENERAL NOTES

1. MAINTAIN MINIMUM 25'-0" DISTANCE FROM ANY EXHAUST OR PLUMBING VENT.

2. PROVIDE 36" HIGH ROOF CURB.

3. ROOF CURB HEIGHT PER SPECIFICATIONS.

4. PROVIDE EQUIPMENT/PIPE SUPPORT CURB PER DETAIL ON SHEET M502.

5. PROVIDE REFRIGERANT PIPING AND ACCESSORIES PER MANUFACTURER'S RECOMMENDATIONS.

APPROXIMATE ROUTE SHOWN.

6. PROVIDE PIPE PENETRATION ROOF CURB WITH CAP. PIPING TO PENETRATE SIDE OF CURB. SEAL WATER

TIGHT.

PLAN NOTES

02-MEZZANINE

481' - 7"

03-ROOF

490' - 6"

1 32

03-ROOF

490' - 6"

03-ROOF

490' - 6" x4

AHU-116x52 - RA

12345689 7

02-MEZZANINE

482' - 6"

03-ROOF

490' - 6"

ROOF 490'-6"

490' - 6"

MEZZANINE 481-7

481' - 7"

16x52 - SA

16x48

2" - CHR

2" - CHS

14x58 - SA

CU-1

GIV-1

02-MEZZANINE

481' - 7"

03-ROOF

490' - 6"

1 32

03-ROOF

490' - 6"

03-ROOF

490' - 6"

02-MEZZANINE

482' - 6"

03-ROOF

490' - 6"

20x24 - RA

MDD

MDD

80x42 L1

24x20 - RA

10x37 - RA

10x37 - RA

26x18 - OA

2" - CHS2" - CHR

DN14x34 SA

GIV-2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:0

P M

M401

SECTIONS & AHU DETAILS

05/07/2026 WJS MGN

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/2" = 1'-0"

AHU-1

SCALE: 1/2" = 1'-0"

AHU-2

NOTES

1. DISCHARGE PLENUM

2. COOLING COIL

3. ACCESS

4. ELECTRIC HEATER

5. SUPPLY FAN

6. ACCESS

7. FLAT FILTER

8. AIR BLENDER

9. MIXING BOX

NOTES

1. DISCHARGE PLENUM

2. COOLING COIL

3. ACCESS

4. ELECTRIC HEATER

5. SUPPLY FAN

6. ACCESS

7. FLAT FILTER

8. AIR BLENDER

9. MIXING BOX

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1-1/2" POCKET

SLIP

DUCT

1" FLANGE & HEM

BOLT ON 4" CENTERS

1"x1/8" BAND IRON

FLEXIBLE MATERIAL

AS SPECIFIED

ALTERNATE

POSITION

OF BOLT

WASHER

FLANGED

CONNECTION

ON FAN SIDE

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1-1/2" MIN. TO 3" MAX. INSTALLED.

6" NOMINAL WITH MATERIAL TAUT

RECTANGULAR FLEXIBLE CONNECTION

5/16" FLANGE

BOLT ON 4" CENTERS

1"x1/8" BAND IRON

1"x1/8" DRAW BAND

FLEXIBLE

MATERIAL AS

SPECIFIED

SHEET METAL SCREWS ON

12" CENTERS

RIVET ON 4"

CENTERS

DUCT

ROUND FLEXIBLE CONNECTION

FLANGED CONNECTION

ON FAN SIDE

WASHER 1-1/2" MIN. TO 3" MAX. INSTALLED.

6" NOMINAL WITH MATERIAL TAUT

1/2" 1/2" 1-1/2"

STEEL EXPANSION SHIELD FOR EXISTING CONSTRUCTION AND

INSERTS FOR NEW CONSTRICTION. THIS TYPE SHALL BE

USED ONLY IN SLABS OR BEAMS OF 4" MIN DEPTH

3/8" MIN DIA EXPANSION BOLTS FOR

EXISTING CONSTRUCTION AND INSERTS

FOR NEW CONSTRUCTION

CONCRETE

FLOOR SLAB

CLIP

ANGLE

3/8" MIN DIA

INSERTS NEW

CONSTRUCTION ONLY.

NUTS & WASHERS

3/8" MIN DIA

HANGER RODS

FOR PIPES UNDER 2" IN SIZE USE

1-1/2"x1-1/2"x1/4" ANGLE. ALL PIPES 2" & LARGER USE 3"x3"x1/4" ANGLE

TURNBUCKLE

3/8" MIN DIA

HANGER RODS

CURB CAP

SEE NOTE 1

SEE NOTE 2

ROOF

TRANSITION DUCT TO

FULL SIZE OF DAMPER

SUPPLIED WITH ROOF

VENTILATOR

DUCT

MOTOR HOUSING

ELECTRICAL

CONDUIT GUIDE

WOOD NAILING

STRIP

PREFABRICATED

ROOF CURB

SEE NOTE 2

RIGID CONDUIT TO

ACCOMMODATE

ELECTRICAL WIRES

GRAVITY OR MOTORIZED BACKDRAFT

DAMPER, REFER TO SPECIFICATIONS.

NOTES:

1. SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" CADMIUM PLATED LAG BOLTS

NOT OVER 12" ON CENTER.

2. SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS

(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).

3. SIZE OF DUCT THROUGH ROOF SHALL NOT BE LARGER THAN CURB SUPPLIED WITH

ROOF VENTILATOR.

4. RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER,

THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.

PLAN VIEW

MAIN SUPPLY

FLOW

SMACNA FIGURE 4-6

45° LEED IN RIGID DUCT

TO AIR TERMINAL UNIT.

F

LO

W

TYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEW

M

AX

M

AX

M A

X

M A

X

M

AX

M A

X

E Q

U

IP

M E

N T

AIR

FLOW

AIR

FLOW

NOTE:

UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOW SHALL

APPLY.

45° M A

X

"D"

ROUND SHEET METAL

DUCT.

MAIN SUPPLY

RIGID DUCT TO AIR TERMINAL

UNIT.

PLAN VIEW

STIFFEN BLADE

AS REQUIRED

INSULATION SEE

SPECIFICATION

DUCT

INSULATION

STAND-OFF

DAMPER BLADE

HANDLE WITH

LOCKING

QUADRANT

INSIDE END BEARING

⅛” [6mm]

CLEARANCE

ALL AROUND

½” [15mm]

ROUND ROD PIN

OUTSIDE END BEARING

SIDE ELEVATION SECTION

NOTE:

1. DELETE INSULATION STAND-OFF ON DUCTWORK EXTERIOR INSULATION.

2. DETAIL SHOWS SINGLE BLADE. DAMPER INSTALLATION SHALL BE SIMILAR

FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.

MANUAL

DAMPER

RETURN/

EXHAUST DUCT

CEILING

CEILING DEVICE

DAMPER WHERE

SCHEDULED

TURNING VANES

STRAP HANGER

RECTANGULAR

DUCT, NOTE 1

SPIN-IN TAP

FITTING

STRAP HANGER

SPIN-IN BRANCH TAP FITTING

WITH MANUAL DAMPER

ROUND DUCT - NOTE 2

STRAP HANGER

SHEETMETAL PLENUM

SAME SIZE AS AIR DEVICE

FLEXIBLE AIR DUCT

CONNECTOR. SEE

DETAIL ON THIS SHEET

6" MIN

NOTES:

1 BRANCH DUCT TAKE-OFF WITH MANUAL DAMPER.

2 BRANCH DUCT SIZES, UNLESS NOTED ON PLANS

ARE TO BE SIZED AS FOLLOWS:

100 CFM AND LESS - 6" DIA.

101 CFM TO 250 CFM - 8" DIA.

251 CFM TO 400 CFM - 10" DIA.

401 CFM TO 700 CFM - 12" DIA.

NOTE:

1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE

ROUND.

2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSITITUTED WITH SHORT RADIUS

ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE

CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENED BY

SMACNA

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W W

W

R

R

SHALL

EQUAL

OR BE

GREATER

THAN W. VANE

R

SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

⅔ W

R

⅓ W

VANE

R

SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

⅓ W½

W

R

W1

W

NOTE:

1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY

SMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE

TYPE REGARDLESS OF W DIMENSION.

3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, ½" [40mm] MAXIMUM SPACE BETWEEN VANES AND A ¾" [20mm] TRAILING

EDGE.

4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL

BE DOUBLE VANE TYPE.

NOTE:

1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A

MINIMUM OF 3 TIMES THE DIAMETER OF

INLET

2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET

TO THIS BOX. BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS.

MAXIMUM LENGTH 3'-0"

[900mm].

3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME

SIZE AS THE BOX INLET. PROVIDED THE EQUIVALENT LENGTH OF

THE BRANCH DUCT. AS SHOWN. DOES NOT EXCEED 10 FEET(3

METERS). FOR LONGER LENGTHS. INCREASE THE DUCT SIZE AND

PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT SIZE AND

PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m].

4. FLEXIBLE AIR DUCT CONNECTORS. WHEN USED FROM TERMINAL

UNIT SUPPLY AIR DUCT TO DIFFUSER. SHALL NOT EXCEED 5'-0"

[1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION

GREATER THAN

45°.

5. COMPONENT ARRANGMENT MAY VARY BY MANUFACTURER. PROVIDE

INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT

SECTIONS.

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT

(TYP.)

AIR TERMINAL

UNIT (CV OR VAV)

SEE NOTE

SEE NOTE

SEE NOTE

SEE NOTE

S E

E N

O T

E

SOUND ATTENUATOR

SEE EQUIPMENT

SCHEDULE

REHEAT

COIL

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL

DIFFUSER

(TYP.)

AIR FLOW AIR

FLOW

BRANCH

DUCT

¼W OR 4"

[100mm] MIN.

VD

PROVIDE VOLUME

DAMPER

AT EACH BRANCH DUCT

W

PLAN VIEW

MAIN EXHAUST OR RETURN

CEILING

[300mm]

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

VOLUME DAMPER W/

LOCKINGQUAD

12"

SHEET METAL

SADDLE

THERMAL INSULATION

SEE SPECIFICATIONS

CONICAL OUTLET

BRANCH DUCT

SEE SPECIFICATIONS FOR CLAMPS

AND SEALANT (TYP.)

SUPPORT SADDLE

FROM STRUCTURE

FLEXIBLE DUCT SIZE

SAME AS DIFFUSER

INLET: 5'-0" MAX

LENGTH

USE RIGID ELBOWS

FOR CHANGE OF

DIRECTION GREATER

THAN 45°

DUCT RISER - SEE FLOOR

PLANS FOR SIZES

EXTEND ANGLE 3"

BEYOND DUCT

FLOOR

SHEET METAL SCREWS 4" ON

CENTER

1-1/2"x1-1/2"x1/8" ANGLE.

INSTALL ON BOTH LONG DIMENSION

SIDES OF DUCT. FOR DUCTS OVER

60" USE 2"x2"x1/8" ANGLE.

HOLE IN STRUCTURAL FLOOR

DUCT RISER

SEAL HOLE WITH FIREPROOFING

MATERIAL AFTER DUCT INSTALLATION

0.5 INCH WG TO 2 INCHES WG (LOW PRESSURE) DUCT RISER SUPPORT

DUCT RISER - SEE FLOOR

PLANS FOR SIZES

2"x2"x1/4" ANGLE. INSTALL

ON BOTH LONG DIMENSION

SIDES OF DUCT

SEAL HOLE WITH FIREPROOFING

MATERIAL AFTER DUCT INSTALLATION

2 INCHES WG TO 4 INCHES WG (HIGH AND MEDIUM PRESSURE) DUCT RISER SUPPORT

NOTE:

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS

AND MECHANICAL ROOM FLOORS SHALL BE PROVIDED WITH A 3" HIGH CONCRETE CURB

AROUND OPENING FOR DUCT.

HOLE IN STRUCTURAL FLOOR

DUCT RISER

ARRANGE RISER SO

REINFORCER TRANSVERSE JOINT

IS AT RISER SUPPORT POINT

FLOOR

NOTE:

TABULATED DATA FROM SMACNA

ALLOWS FOR DUCT REINFORCING AND

INSULATION, BUT NO EXTERNAL LOAD.

HANGER STRAPS OR RODS

MAX. DUCT

DIA. - IN.

QUANTITY/SIZE

IN.

MAX. LOAD

LBS.

MAX.

SPACING

IN.

260 144

ONE 1 x 22 GA. STRAP

ONE 1 x 18 GA. STRAP

ONE 1 x 16 GA. STRAP

TWO 3/8 DIA. RODS

TWO 1/2 DIA. RODS

LOAD RATED

FASTENERS

BAND OF SAME

SIZE AS HANGER

STRAP

50" DIA. &

UNDER

HANGER RODS

BAND

OVER 50" DIA.

TURNING VANES

SEE FLOOR PLAN FOR

SPLIT DIMENSION

MAIN

SUPPLY

DUCT

SQUARE ELBOW SHOWN.

PROVIDE ROUND ELBOW

WHEN SHOWN ON PLANS

SUPPLY REGISTER

OR BRANCH DUCT

AIR

FLOW

AIR

FLOW

A

IR

F

LO

W

MANUAL VOLUME

DAMPER

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

A

IR

F

LO

W

AIR

FLOW

BRANCH DUCT

MANUAL VOLUME

DAMPER

MAIN SUPPLY

DUCT

W

1/4 W OR

4" MIN.

BRANCH DUCT TAKE-OFF PLAN VIEW

NOTES:

THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM ANYTIME,

AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000 FPM OR LESS. THE AIR SPLIT DUCT

TAKE-OFF SHALL BE USED IN ALL OTHER CASES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:1

P M

M501

DETAILS

05/07/2026 WJS MGN

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: NONE

FLEXIBLE DUCT CONNECTIONS

SCALE: NONE

SECURING HANGER RODS IN CONCRETE

SCALE: NONE

POWER ROOF VENTILATOR

SCALE: NONE

ALTERNATE SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS

SCALE: NONE

DUCTWORK TRANSITIONS

SCALE: NONE

SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS

SCALE: NONE

VOLUME DAMPER DETAIL

SCALE: NONE

RETURN OR EXHAUST GRILLE/REGISTER CONNECTION

SCALE: NONE

DUCTWORK RADIUS ELBOWS

SCALE: NONE

DUCTWORK SQUARE VANE ELBOWS

SCALE: NONE

DUCT CONNECTION-AIR TERMINAL UNITS

SCALE: NONE

EXHAUST OR RETURN BRANCH DUCTWORK

SCALE: NONE

FLEXIBLE AIR DUCT CONNECTOR

SCALE: NONE

DUCT RISER SUPPORTS

SCALE: NONE

ROUND DUCT HANGERS

SCALE: NONE

SUPPLY DUCTWORK TAKE-OFFS

HOUSING WELDED

TO DUCT SECTION

ROUND OR FLAT

OVAL DUCT SECTION

COVER WITH HANDLE AND

CHAIN RETAINER GASKETED

AND PRESSURE SEALED

INSULATION

DUCT

GASKET

INSULATION

SECTION "A-A"

ACCESS PANEL

"A"

"A"

ACCESS DOOR

INSULATION

SECTION "B-B"

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCH

CASING

GASKET

HANDLE INSIDE

"B" "B"

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

LAG SCREW

WOOD NAILER

4"x4"x1/4"

STEEL PLATE

INSULATION

ROOFING

ROOF DECK

1. PROVIDE COUNTER-FLASHING.

2. HEAVY GAUGE CONTINUOUS SUPPORT

EXTENDS 6" BEYOND LAST EQUIPMENT LEG.

SCREW ATTACHMENT TO DECK.

3. MINIMUM 12 INCHES.

4. EXPANSION LAGS TO DECK.

5. 18 INCH HIGH INSULATED STEEL CURB.

NOTES

AUXILIARY AIR

DEVICE FRAME

TYPE "A"

DUCT

3" MIN

AIR DEVICE TO BE REMOVABLE

FOR ACCESS TO FIRE DAMPER

DUCT EXTENSION AT

TOP OF DAMPER

DUCT

1TYPE "B" -

FIRE RATED WALL

OR PARTITION

3" MIN3" MIN

4 4

GENERAL NOTES

NOTES

A. FIRE DAMPERS SHALL BE UL LABELED.

B. INSTALLATION OF FIRE DAMPERS AND ACCESSORIES SHALL CONFORM TO NFPA 90A, SMACNA AND MANUFACTURER'S INSTRUCTIONS.

C. DETAILS SHOW INSTALLATION OF FIRE DAMPER IN WALL. DAMPER INSTALLATION IN FLOOR SIMILAR. COORDINATE REQUIRED ACCESS

LOCATIONS.

D. INSULATE RETAINING ANGLES FOR SYSTEMS REQUIRED TO BE INSULATED.

1. FIRE DAMPER, FOLDED BLADE CURTAIN TYPE, EXCEPT AS NOTED. VERTICAL MOUNT, GRAVITY DROP; HORIZONTAL MOUNT, SPRING LOADED TO CLOSE. REFER TO SPECS FOR VELOCITY LIMITATIONS OF EACH TYPE. REFER TO DRAWINGS FOR STATIC OR DYNAMIC

REQUIREMENTS.

2. SHEET METAL WALL SLEEVE, SAME MATERIAL AS DUCT (EXCEPT GALVANIZED SHEET METAL FOR FIBERGLASS DUCT). SHEET METAL GAUGE PER SMACNA. USE EXTENDED HEAVY GAUGE SLEEVES WHEN INSTALLED CONDITION REQUIRES.

3. DUCT/SLEEVE CONNECTION. BREAKAWAY TYPE SHOWN. CONNECTION MAY BE RIGID TYPE IF ALLOWED BY CODE AUTHORITY.

4. RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MINIMUM OVERLAP OF WALL OPENING. LONGER LEG MAY BE REQUIRED TO

ATTAIN REQUIRED OVERLAP. BOLT, SCREW OR TACK WELD TO WALL SLEEVE. SPACING OF FASTENERS PER SMACNA.

5. DUCT ACCESS PANEL OR DOOR. REFER TO SPECIFICATIONS.

6. CEILING ACCESS PANEL IF CEILING IS NOT ACCESSIBLE.

UNIT TYPE A B

WHERE X = STATIC PRESSURE IN PAN

2" PLUS X X

2X1" MINIMUMBLOW THRU

DRAW THRU

FLOOR SINK

DIELECTRIC

FITTING

NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY

LOCAL VA AND IS INDOORS AND DOES NOT PASS THROUGH

RATED BARRIERS.

2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR

METALS ARE TO BE CONNECTED.

DRAIN

PAN

CLEAN OUT

PITCH DOWN

TOWARD DRAIN

DRAIN LINE SHALL BE AT LEAST THE SAME

SIZE AS THE NIPPLE ON THE DRAIN PAN

PIPING SHALL BE RIGID COPPER TYPE L OR

TYPE M UNLESS NOTE BELOW IS MET

A B

1"

NOTE:

NOT REQUIRED

FOR AIR TERMINAL

UNITS.

EQUIPMENT WEIGHT

250 LBS. [114KG]

OR LESS

SEISMIC BRACING FOR LIGHT

SUSPENDED EQUIPMENT

FLOOR MOUNT EQUIPMENT

RESTRAINED BY RESILIENT PADS

(TYPE DS)

FLOOR

EQUIPMENT

BASE

ANCHOR BOLT

NEOPRENE WASHER

& SLEEVE

BONDED STEEL

PLATE

RESILIENT PAD

HANGER

ROD

(TYP)

CROSS BRACING

RODS ALL FOUR

SIDES

LOCK

NUTS

(TYP)

CLAMP

L

W

A

B

5D

D

2D

5D

1" [2

5m m

PLAN SECTION B-B

16" [400mm]

L/

5" M

IN

[1 m m

SECTION A-A (BASE POURED EITH FLOOR SLAB)

L1

5" M

IN

[1 m m

SECTION A-A (BASE NOT POURED WITH SLAB)

A

B

FLOOR

ANCHOR BOLT (TYP)

PIPE SLEEVE (5D,

(3" [75mm] MIN.)

CONCRETE BASE

WELD HEAD TO PLATE

OR BEND OVER END 5D

TYPICAL ANCHOR BOLT

NUT AND WASHER

EQUIPMENT

BASE PLATE

PROVIDE DOUBLE SLAB

RE-INFORCING IN BASE AREA

TYPICAL ANCHOR BOLT

NUT AND WASHER

EQUIPMENT

BASE PLATE

PROVIDE #3 BARS 12" [300mm]

O.C. EACH WAY IN THE BASE

AND DOWEL BASE TO FLOOR NOTE:

L & W DIMENSIONS

SHALL BE 6" [150mm]

GREATER THAN THE

EQUIPMENT BASEPLATE

LAG SCREW

4"x4"x1/4"

STEEL PLATE

FIBERGLASS INSULATION

INSULATION

ROOF

2x6 WOOD NAILER

ROOFING

ROOF DECK3

NOTES:

1. 18 GAUGE GALVANIZED STEEL COUNTER-FLASHING,

2. WELDED 14 GAUGE EQUIPMENT SUPPORT CURB, MEETING ASTM A-446, 525, 526 AND 527 REQUIREMENTS, WITH WELDED CORNERS WITH SEAMS JOINED BY CONTINUOUS WELDS. CURB SHALL BE INTERNALLY REINFORCED WITH BULKHEADS AND SPREADERS, 24" ON CENTER TO MEET LOAD RATING OF EQUIPMENT.

CURB TO EXTEND 6" BEYOND EQUIPMENT. REFER TO FLOOR PLANS FOR HEIGHT.

3. SECURE CURB TO ROOF WITH EXPANSION BOLTS (CONCRETE ROOF) OR RUST RESISTANT BOLTS

(METAL DECK AND BAR JOIST ROOF), 12" O.C.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:1

P M

M502

DETAILS

05/07/2026 WJS MGN

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: NONE

ACCESS SECTION FOR ROUND/OVAL DUCT

SCALE: NONE

ACCESS PANEL AND DOOR DETAIL

SCALE: NONE

ROOF EQUIPMENT SUPPORT

SCALE: NONE

FIRE DAMPER AT AIR DEVICE - WALL

SCALE: NONE

FIRE DAMPER TYPE "B"

SCALE: NONE

FIRE DAMPER NOTES

SCALE: NONE

AIR HANDLING UNIT DRAIN TRAP DETAIL

SCALE: NONE

SEISMIC BRACING FOR EQUIPMENT

SCALE: NONE

CONCRETE EQUIPMENT BASES

SCALE: NONE

EQUIPMENT/DUCT SUPPORT ROOF CURB

NOTE:

1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST

2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR

4" DIA. PIPE & SMALLER. TYPE "H-P" FOR 5" DIA. PIPE & LARGER.

2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE

SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE

SERVICING OF FILTERS, VALVES, OR EQUIPMENT.

3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED

MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE

RETURN PIPING.

WATER COIL

DRAIN

DOUBLE COIL

WATER COIL

DRAIN WHEN COIL IS

NOT SELF-DRAINING (TYP.)

MV

AIR VENT

WHEN COIL

IS NOT

SELF-VENTING

STRAINER WITH BLOW DOWN (TYP.)

BUTTERFLY VALVE (TYP.)

0.75" BYPASS WITH AUTOMATIC

FLOW CONTROL VALVE (4-57 PSIG RANGE) SET AT 5 GPM

CHR

CHS

REDUCER, IF REQUIRED

MV

MV

MV

MV

CHR

CHS

REDUCER, IF REQUIRED

MVMV

MV

AUTOMATIC FLOW CONTROL VALVE (TYP.)

0.75" BYPASS WITH AUTOMATIC

FLOW CONTROL VALVE (4-57 RANGE)

SET AT 5 GPM

DRAIN

SINGLE COIL

TEST PLUG

(TYP.)

PIPE HANGER SHALL SUPPORT

PIPING INDEPENDENT OF COIL

AIR VENT

WHEN COIL

IS NOT

SELF-VENTING

DRAIN WHEN COIL IS

NOT SELF-DRAINING

PIPE HANGER SHALL SUPPORT

PIPING INDEPENDENT OF COIL

TEST PLUG

(TYP.)

WATER COIL

AUTOMATIC 2-WAY

MODULATING CONTROL

VALVE (TYP.)

AUTOMATIC FLOW CONTROL VALVE (TYP.)

HANGER ROD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF MIN.

DENSITY) UNDER INSULATION SHIELD

INSULATION SHEILD

AT HANGER

WELD

SADDLE

ADJUSTABLE CLEVIS HANGER TYPE 1 -

SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 -

SEE SPECIFICATIONS

PROVIDE INSULATION SHEILD

& INSERT FOR ALL PIPING

(200mm [8"] MIN.)

15mm [½"] DIA.

HANGER RODS WITH

900mm [36"] MAX.

SPACING ON EACH

CHANNEL

BAND

43mm [1-⅝"] 12 GAUGE CHANNEL OR 50x50x6.4mm [2"x2"x¼"] ANGLE m m [1

M

A X

SIDE VIEW TRAPEZE HANGER FOR UP TO

453KG [1000lb.] UNIFORM LOAD

[1]

[1¼]

THRU 20

[THRU ¾]

[1½]

[2½]

[2]

[3]

[4]

[5]

[6]

[10]

[10]

[12]

[14]

[16]

[18]

[20]

[24]NOM. SIZE

[7]

[7]

[7]

[9]

[11]

[10]

[12]

[14]

[16]

[17]

[19]

[22]

[23]

[25]

[27]

[28]

[30]

[32]PIPE

[6]

[7]

[5]

[8]

[9]

[8]

[10]

[12]

[13]

[14]

[16]

-TUBING

mm

[IN]

mm

[FT]

mm

[FT]

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE:

SEE SPECIFICATIONS FOR DETAILED HANGER REQUIREMENTS

ABOVE 2" DIA. PIPE 2" DIA. & SMALLER

2 1/2" DIA.

ABOVE 2" DIA. PIPE 2" DIA. & SMALLER

2 1/2" DIA.

HORIZONTAL

VERTICAL

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

3/4" BALL VALVE

ADAPTER TO 3/4" HOSE

THREAD-PROVIDE HOSE CAP NUT

ELEVATION

THREADED PIPING

ELEVATION

WELDED PIPING

TYPICAL CHILLED PIPING

DRAIN VALVE CONNECTIONS

NOTES:

1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.

2. WHERE SCALE POCKETS ARE SHOWN ON PIPE

RISER DIAGRAMS AND/OR PLANS, LOCATE DRAIN

AT BOTTOM OF SCALE POCKET.

AIR VENT

1/2" BALL VALVE

1/4" COPPER TUBING

1/2" x 4" NIPPLE

CIRCULATING WATER PIPING

ELEVATION

TYPICAL MANUAL AIR VENT

NOTES:

1. VENT ALL HIGH POINTS AS INDICATED ABOVE.

2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE

TO NEAREST DRAIN.

MV

OR

AV

HVAC DESIGN DATA

GENERAL NOTES:

A. OUTDOOR DESIGN CONDITIONS:

93.4°F DB SUMMER

76.4°F WB SUMMER

5.4°F DB WINTER

NOTES:

1. LISTED RH IS MAXIMUM ANTICIPATED AT LISTED

DB TEMPERATURE.

2. REFER TO ATC SEQUENCES FOR ACTUAL

ROOM SETPOINTS.

3. "FLOATING" MEANS THERE IS NO ACTIVE CONTROL.

4. MINIMUM TOTAL AIR CHANGE RATE IS TO BE BASED ON SUPPLY CFM FOR

POSITIVE AND NEUTRAL SPACES, EXHAUST CFM FOR NEGATIVE SPACES.

SPACE NAME / TYPE °F DB

INTERIOR DESIGN DATA

SUMMER WINTER

% RH

(NOTE 1,3) °F DB

% RH

(NOTE 1,3)

NA NA NATOILET & HAC NA

B. DESIGN ALTITUDE: 479 FT.

OFFICE 75 60 70 FLOATING

MINIMUM

TOTAL AIR

CHANGES

(NOTE 4)

86 FLOATING 40CHILLER & ELECTRIC RMS FLOATING -

80.6 60 64TELECOMMUNICATION FLOATING -

DUCT CONSTRUCTION, SEALING, AND INSULATION

GENERAL NOTES:

A. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:

SHEET METAL DUCT; INTERIOR LINING; EXTERIOR

INSULATION; ETC.

B. DUCT CONSTRUCTION AND SEALING SHALL BE PER

LATEST S.M.A.C.N.A. STANDARDS.

NOTES:

1. ROUND SHEET METAL RUN-OUTS TO AIR DEVICES DOWNSTREAM OF VAV BOXES SHALL BE EXTERNALLY INSULATED.

2. RETURN DUCTWORK FOR AHU-2 SHALL BE INSULATED.

3. WATERTIGHT SEAL.

4. INSULATE FROM 24" UPSTREAM OF BACKDRAFT / ISOLATION DAMPER TO PENETRATION OF WALL / ROOF.

5. CONCEALED ROUND RUNOUT DUCTS TO AIR DEVICES MAY BE 1" S.P. CLASS.

DUCT SYSTEM

S.P. CON-

STRUCT.

SEAL

CLASS

LEAKAGE

CLASS

S.M.A.C.N.A. CLASS.

INTERNALLY

LINED

EXTERNAL

INSULATION

NOT

INSULATED

SEE

NOTE

DOUBLE

WALL

INSULATEDRECT RND

2,5

NOTE 4

NOTE 4

+3" A 8

+1" 16

16 8

16 8

A

A

A

A

A

A

SUPPLY DUCTWORK UPSTREAM OF

VAV BOXES

SUPPLY DUCTWORK DOWNSTREAM OF

VAV BOXES

SUPPLY DUCTWORK DOWNSTREAM

FOR SINGLE ZONE AHU-1

+2"

RETURN DUCTWORK -2"

TOILET OR GENERAL EXHAUST

DUCTWORK

-1"

RELIEF AIR DUCTWORK AND PLENUMS

OUTSIDE AIR DUCTWORK AND

PLENUMS

+1

-1"

NOTES:

1. DRUM LOUVER, ANGLED 45 DEG. DOWN UNLESS NOTED OTHERWISE.

2. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOUVERS, INCLUDING MOUNTING HEIGHT, EXACT LOCATION, AND COLOR.

3. FILTER GRILLE IS FOR ACCESS TO FIRE DAMPER. NO FILTER REQUIRED.

GENERAL NOTES:

A. ALL LAY-IN AIR DEVICES SHALL FIT IN 24"X24" LAY-IN CLG SYSTEM.

VERIFY GRID TYPE AND COORDINATE AIR DEVICE COMPATIBILITY.

B. FINISH KEY: "W.B.E." - WHITE BAKED ENAMEL;

"E.C.L." - ETCHED CLEAR LACQUER OR ANODIZED;

"C.C.B.A." - CUSTOM COLOR SELECTED BY ARCHITECT.

C. SUPPLY AIR DIFFUSERS SHALL BE 4-WAY BLOW, UNLESS

INDICATED OTHERWISE BY ARROWS ON DRAWINGS.

D. PROVIDE AUX. FRAMES FOR AIR DEVICES IN PLASTER,

GYPSUM BOARD, TILE OR OTHER HARD SURFACES.

AIR DISTRIBUTION DEVICES

M A

R K

DESCRIPTION

MOUNTING TYPE SLOTS MATERIAL FINISH

O P

P O

S E

D B

L A

D E

D A

M P

E R

S Q

-T O

-R D

N E

C K

A D

A P

T O

R

BASIS OF DESIGN S

E

E N

O T

E

L A

Y -I

N

S U

R F

A C

E

D U

C T

S P

L

IN

E

S N

A P

-I N

Q U

A N

T

IT

Y

W

ID

T H

S T

E E

L

A L U

M

IN

U M

S T

A

IN

L E

S S

S T

E E

L

W .B

.E

E .C

.L

C .C

.B .A

BG1 HEAVY DUTY RETURN GRILLE ● ● ● TITUS - 30RS

BG2 HEAVY DUTY EXHAUST GRILLE ● ● ● TITUS - 30RS

CD1 STANDARD SQ. PLAQUE CEILING DIFFUSER -

ROUND NECK - 24 X 24

● ● ● TITUS - OMNI

CG1 EGGCRATE CEILING GRILLE ● ● ● TITUS - 50F

CR1 EGGCRATE CEILING REGISTER ● ● ● ● TITUS - 50F

L1 LOUVER ● 2

TG1 SIDEWALL FILTER RETURN GRILLE ● ● ● TITUS - 350RLF 3

TG2 SIDEWALL RETURN GRILLE ● ● ● TITUS - 350ZRS

TR1 DRUM LOUVER ● ● ● TITUS - DL 1

TR2 AEROBLADE SUPPLY GRILLE ● ● ● TITUS - 272FL

SCALE: NONE

INSTALLATION OF THERMOMETER WELLS

SCALE: NONE

CHILLED WATER COILS - PIPING CONNECTIONS

SCALE: NONE

DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC SYSTEMS)

SCALE: NONE

PIPE HANGERS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S.…

This is the start of the file's text. The full file is on GovTribe.