652-19-108 Renovate 4A Combined Dwg BD Final.pdf
PDF 28 MB Posted
- Solicitation number
- 36C24621R0117
About this file
This document provides details on a federal contract opportunity for renovations to an existing facility. The Department of Veterans Affairs is seeking a contractor to completely prepare an area for building operations, including demolition and removal of existing structures, and furnish all labor, materials, and work for Area 4A in Building 500 at their Richmond, Virginia location. The estimated construction value is between $5 million and $10 million. The solicitation is anticipated to be a total service-disabled veteran-owned small business set-aside. The solicitation number is 36C24621R0117 and will be available on July 20, 2021, with proposals due approximately 30 days later. Interested parties should register on the website provided and check for any amendments, with SAM and VetBiz registration required to be eligible for award.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24621R0117 0002.docx | DOCX document | |
| 652-19-108 Renovate 4A Combined Specs Bid Docs Final.pdf | ||
| 36C24621R0117 0001.docx | DOCX document | |
| Attachment C - Past Performance Questionnaire.docx | DOCX document | |
| 652-19-108 Renovate 4A Combined Specs Bid Docs.pdf | ||
| Attachment A - Base Proposal Item Price Breakdown.xlsx | XLSX spreadsheet | |
| 652-19-108 Renovate 4A Combined Dwg BD.pdf | ||
| Safety Handbook.pdf | ||
| Wage Determination.pdf | ||
| 36C24621R0117_1.docx | DOCX document | |
| Attachment B - Corp Experience Form.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
PROJECT SITE MAP PROJECT LOCATION MAP
PROJECT IMAGE
/2
/2
:0
:2
A
M
GI001
TITLE SHEET AND INDEX OF
DRAWINGS
1 6ED
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 5/26/2020
BID DOCUMENTS
652-19-10819-127
IMPROVE PATIENT PRIVACY 4A
HUNTER HOLMES MCGUIRE VAMC 1201 BROAD ROCK BLVD
RICHMOND, VA 23249
VA PROJECT #: 652-19-108 APOGEE PROJECT #: 19-127
LW
RICHMOND VAMC
N
PROJECT SCOPE
BUILDING 500
DRAWING LIST
PLUMBING
P-001 PLUMBING GENERAL INFORMATION 1 12
PD101 FOURTH FLOOR WASTE & VENT DEMOLITION PLAN 2 12
PD102 FOURTH FLOOR DOMESTIC WATER DEMOLITION PLAN 3 12
PD103 FOURTH FLOOR MEDICAL GAS DEMOLITION PLAN 4 12
PW101 FOURTH FLOOR DRAIN, WASTE, AND VENT PLAN 5 12
PP101 FOURTH FLOOR DOMESTIC WATER PLAN 6 12
PG101 FOURTH FLOOR MEDICAL GAS PLAN 7 12
P-501 PLUMBING DETAILS 8 12
P-601 PLUMBING SCHEDULES 9 12
P-901 WASTE & VENT RISER PLAN 10 12
P-902 DOMESTIC WATER RISER PLAN 11 12
P-903 MEDICAL GAS RISER PLAN 12 12
MECHANICAL
M-001 MECHANICAL GENERAL INFORMATION 1 12
MD101 FOURTH FLOOR AIR TERMINAL MECHANICAL DEMOLITION PLAN 2 12
MD102 FOURTH FLOOR INTERSTITIAL FLOOR MECHANICAL DEMOLITION PLAN 3 12
MD103 FOURTH FLOOR INTERSTITIAL FLOOR MECHANICAL PIPING DEMOLITION PLAN 4 12
MH101 FOURTH FLOOR MECHANICAL HVAC PLAN 5 12
MH102 FOURTH FLOOR INTERSTITIAL HVAC PLAN 6 12
MH103 FOURTH FLOOR MECHANICAL OIT 4B-123 PLAN 7 12
MP101 FOURTH FLOOR INTERSTITIAL MECHANICAL PIPING PLAN 8 12
M-501 MECHANICAL DETAILS 9 12
M-502 MECHANICAL CONTROLS AND DETAILS 10 12
M-601 MECHANICAL SCHEDULES 11 12
M-602 MECHANICAL SCHEDULES 12 12
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 13
ED101 FOURTH FLOOR ELECTRICAL DEMOLITION PLAN 2 13
ED102 FOURTH FLOOR LIGHTING DEMOLITION PLAN 3 13
EP101 FOURTH FLOOR POWER PLAN 4 13
EP102 4B OIT ROOM UPGRADE - ELECTRICAL PLANS 5 13
EL101 FOURTH FLOOR LIGHTING PLAN 6 13
EM101 FOURTH FLOOR MECHANICAL POWER PLAN 7 13
E-401 ELECTRICAL ENLARGEMENTS 8 13
E-501 ELECTRICAL DETAILS 9 13
E-502 ELECTRICAL DETAILS 10 13
E-503 ELECTRICAL DETAILS 11 13
E-601 ONE-LINE DIAGRAM 12 13
E-602 ELECTRICAL SCHEDULES 13 13
TECHNOLOGY
TK001 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 1 6
TK101 FOURTH FLOOR TECHNOLOGY PLAN 2 6
TK102 FOURTH FLOOR SECURITY PLAN 3 6
TK401 TECHNOLOGY ENLARGEMENTS 4 6
TK501 TECHNOLOGY DETAILS 5 6
TK601 TECHNOLOGY RISERS 6 6
FIRE ALARM
FA001 FIRE ALARM GENERAL NOTES, SYMBOL LEGEND, AND RISER 1 2
FA101 FOURTH FLOOR FIRE ALARM PLAN 2 2
DRAWING LIST
GENERAL
GI001 TITLE SHEET AND INDEX OF DRAWINGS 1 6
GI002 GENERAL NOTES ABBREVIATIONS SYMBOLS AND DETAILS 2 6
GI003 SITE PLAN - CONSTRUCTION STAGING 3 6
GI004 FOURTH FLOOR ILSM PLAN 4 6
GI005 GENERAL NOTES, ABBREVIATIONS, SYMBOLS AND DETAILS 5 6
LS101 FOURTH FLOOR LIFE SAFETY AND ANALYSIS 6 6
ABATEMENT
AH101 OVERALL FOURTH FLOOR DEMOLITION PLAN - HAZARDOUS MATERIALS 1 1
STRUCTURAL
S-100 PATIENT LIFT SUPPORT PLAN 1 2
S-101 PATIENT LIFT SUPPORTS 2 2
ARCHITECTURAL
A-001 ARCHITECTURAL SYMBOLS, ABBREVIATIONS AND NOTES 1 13
A-002 PARTITION TYPES AND DETAILS 2 13
AD101 FOURTH FLOOR DEMOLITION PLAN 3 13
AD111 FOURTH FLOOR DEMOLITION REFLECTED CEILING PLAN 4 13
AE101 FOURTH FLOOR PLAN 5 13
AC111 FOURTH FLOOR REFLECTED CEILING PLAN 6 13
AE201 EXTERIOR ELEVATIONS 7 13
AE401 ENLARGED PLANS 8 13
AE501 ENLARGED COLUMN DETAILS 9 13
AE502 ENLARGED COLUMN DETAILS 10 13
AE503 PATIENT HEADWALL DETAILS 11 13
AE601 DOOR SCHEDULE, TYPES, DETAILS 12 13
AE602 WINDOW TYPES AND DETAILS 13 13
INTERIORS
I-001 FINISH SCHEDULE 1 21
I-101 FOURTH FLOOR FINISH PLAN 2 21
I-120 FOURTH FLOOR FLOOR PATTERN PLAN 3 21
I-130 FOURTH FLOOR WALL PROTECTION PLAN 4 21
I-131 WALL PROTECTION DETAILS 5 21
I-201 CASEWORK ELEVATIONS 6 21
I-202 MILLWORK 7 21
I-203 MILLWORK 8 21
I-204 CASEWORK DETAILS 9 21
I-205 INTERIOR ELEVATIONS 10 21
I-206 INTERIOR ELEVATIONS 11 21
I-207 INTERIOR ELEVATIONS 12 21
I-208 INTERIOR ELEVATIONS 13 21
I-401 OVERALL FOURTH FLOOR FFE FLOOR PLAN 14 21
I-402 ENLARGED EQUIPMENT PLANS 15 21
I-403 ENLARGED EQUIPMENT PLANS 16 21
I-404 ENLARGED EQUIPMENT PLAN 17 21
I-405 ENLARGED EQUIPMENT PLAN 18 21
I-406 ENLARGED TOILET PLANS 19 21
I-601 EQUIPMENT SCHEDULE 20 21
I-602 EQUIPMENT SCHEDULE 21 21
FIRE PROTECTION
FX001 FIRE SUPPRESSION GENERAL INFORMATION 1 4
FD101 FOURTH FLOOR FIRE SUPPRESSION DEMOLITION PLAN 2 4
FX101 FOURTH FLOOR FIRE SUPPRESSION PLAN 3 4
FX102 FOURTH FLOOR FIRE SUPPRESSION REFLECTED CEILING PLAN 4 4
DocuSign Envelope ID: AE84D337-75BD-4E12-9512-360FCAB23E7F
5/26/2020
1-1/2"
DIAMETER
GRAB BAR
TOILET
TISSUE
DISPENSER
SANITARY
NAPKIN
DISPOSAL
TOILET
FIXTURE
TOILET
FIXTURE
TOILET
TISSUE
DISPENSER
1-1/2"
DIAMETER
GRAB BAR
EXPOSED
PLUMBING AT
BARRIER
FREE
LAVATORIES
SHALL BE
INSULATED.
LEVER OPERATING
CONTROLLED
SOAP DISPENSER
NOTE: SINKS IN COUNTERS TO BE
MOUNTED WITH RIM NO MORE
THAN 2'-10" HIGH AND WITH AT
LEAST 2'-3" KNEE CLEARANCE.
CLEAR
TYPICAL ACCESSIBLE TOILET TYPICAL ACCESSIBLE
CLEARANCE AT LAVATORY
TYPICAL ACCESSIBLE
LAVATORY AND MIRROR
1'-3" 1'-3"
M
IN
M A
X
M
A X
M
A X6
A
.F .F
1'-6"
5'-6" CLEAR
3'-0" 6"
3'-0"
" 3
1'-0" 3'-6"
2'-4"
5'-6" CLEAR
MIN
8"
MAX
6"
M
IN9
M
IN
M
IN
M A
X
17" MIN
W H
E R
E H
.C
A C
C E
S S
R E
Q 'D
CLOCK
NURSE
CALL
DOME
LIGHT
CLOCK OUTLET
TOWEL BAR
ACCESSIBLE
ROBE/COAT HOOK
ROBE/COAT
HOOK
TELEVISION
OUTLET
WALL MOUNTED TVCOAT RACK / COAT HOOK CLOCK & NURSE CALL DEVICESTOILET ACCESSORIES
6"
T
Y P
M A
X
F O
R S
T A
N D
IN
G
O
.C
TELEVISIO
N OUTLET
F O
R S
E A
T E
D
O
.C
WALL MOUNTED TACKBOARD
AND MARKERBOARD
PAPER TOWEL
DISPENSER
2'-0" AT SIDEWALLS
AT COUNTER SINKS
1'-6" AT SIDEWALLS
AT LAVATORY
4'-0" MAX TO
HIGHEST OPERABLE
POINT - IF FIRE
EXTINGUISHER
OVER 40 LBS
3'-6" MAX HT.
FIRE EXTINGUISHER
CABINET
ELECTRICAL CABINET
DUPLEX
OUTLET
SWITCH
THERMOSTAT
TELEPHONE
OR DATA
OUTLET
FIRE ALARM
PULL
INTERCOM
STATION
DUPLEX
OUTLET
COMPUTER
TERMINAL
FIRE ALARM
CHIME WITH
VISUAL
ALARM LIGHT
FIRE ALARM
PULL STATION
FIRE ALARM
ANNUNCIATOR
FIRE ALARM
INTERCOM
STATION
INTERCOM
MASTER
STATION
INTERCOM
WALL
OUTLET
INTERCOM STATION
WALL PROTECTION
BUMPERGUARD
HANDRAIL
OR DOOR FRAME
3" TO CORNERGUARD
CORNERGUARD
MISC. WALL DEVICES
/8
/4
T O
B O
T T
O M
O F
R
E F
L E
C T
IV
S
U R
F A
C E
F
M
IR
R
O R
WALL GUARD
BASE
BID ITEM I (BASE BID):
The Base Bid shall include all work shown in the drawings and specifications. Work includes general construction, asbestos abatement, alterations, plumbing, mechanical, electrical and fire suppression work. It includes all labor, material, equipment and supervision to perform and complete the work as shown on the construction documents.
BID ITEM 2 (DEDUCT ALTERNATE)
(Deduct Alternate #1): Shall be work described in Bid Item 2 minus that work shown in the drawings and/or designated in the Specifications as “Deduct Alternate No. 1”. Work includes material and labor for the provision of the Renovation of the OIT Room 4B-123 and Related Work.
BID ITEM 3 (DEDUCT ALTERNATE)
(Deduct Alternate #2): Shall be all work described in Bid Item 1 minus that work shown in the drawings and/or designated in the specifications as “Deduct Alternate No. 2”. Work includes material and labor for the Replacement of Exterior Windows at the South Elevation and related work. This alternate does NOT include interior windows, stools and blinds.
WALL SECTION
SYMBOL
INTERIOR ELEVATION
SYMBOL
COLUMN GRID
ELEVATION SYMBOL
REVISION NOTE
ENLARGED DETAIL CALLOUT
ROOM DESIGNATION
SYMBOL
BREAK LINE
ROOF SLOPE
DIRECTION SYMBOL
TYPICAL GRAPHIC SCALE
DETAIL #
PAGE #
DETAIL #
PAGE #
TRUE NORTH ARROW
PROJECT NORTH ARROW
A8.1
EXTERIOR ELEVATION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
A8.1
BUILDING SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
WALL GRID
(REPRESENTS
FACE OF EXISTING
WALL)
XX.X
XX.X
ELEVATION
0'-0"
ROOM
NAME
101A
NORTH
PLAN
NORTH
TRUE
0 4 8 16
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:2
:1
P
M
GI002
GENERAL NOTES ABBREVIATIONS
SYMBOLS AND DETAILS
2 6ED
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 5/26/2020
BID DOCUMENTS
652-19-10819-127
LW
Scale: 3/8" = 1'-0"
STANDARD MOUNTING HEIGHTS
BASE BID AND ALTERNATES
GENERAL SYMBOL LEGEND
N
AREA OF WORK
FOURTH FLOOR
KEY PLAN
SCALE: NO SCALE
5TH ST.
T H
S T
N
D S
T
R
D S
T
E A
S T
A V
E N
U
ES O U T H D R I V E
6TH ST.1ST ST.
C E
N T
E R
C
IR
C L E
H U
N T
H
L
M E
S
D
R I V
E
E . B
E
LT
B
LV
D
E. B
ELT BLVD.
B R
O A
D R
O C
K
B O
U L
E V
A R
D
DELIV
ERY D
RIV
E
H O
P K
IN
A D
F
IT
N E
S S
T R
A
IL
H E
L
IP
A D
D E
T E
N T
IO
N
B A
S
IN
D E
T E
N T
IO
N
B A
S
IN
C O
U R
T
W
ALL
W
ALL
W
ALL
W A
L L
W
ALL
W A
L L
M R
I
F E
N C
E D
A R
E A
PARKING
PARKIN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
N O T H E R E
REF .
A1120.5330GHMGHGS 10.000000
F53/30G B
A1120.5330GHMGHG
S
10.000000
F53/30G B
A1120.5330GHMGHGS 10.000000
F53/30G B
A1120.5330GHMGHG
S
10.000000
F53/30G B
A1120.5330GHMGHG
S
10.000000
F53/30G
B A1120.5330GHMGHG
S 10.000000
F53/30G B
A1120.5330GHMGHGS 10.000000
F53/30G
BA1120.5330GHMGHGS 10.000000
F53/30G B
A1120.5324GHMGHG
S
10.000000
F5 3/
G
B
A1120.5324GHMGHG
S 10.000000
F5 3/
G
B
A1120.5336GHM
I
HAO10.000000
F5 3/
G
B
A1120.5330GHMGHGS 10.000000
F53/30G B
A1120.5330GHMGHG
S
10.000000
F53/30G B
A1120.5330GHMGHG
S
10.000000
F53/30G
B A1120.5330GHMGHG
S 10.000000
F53/30G B
A1120.5330GHMGHGS 10.000000
F53/30G
BA1120.5330GHMGHGS 10.000000
F53/30G B
A1120.5324GHMGHG
S
10.000000
F5 3/
G
B
A1120.5324GHMGHG
S 10.000000
F5 3/
G
B
A1120.5336GHM
I
HAO10.000000
F5 3/
G
B
A1120.5330GHMGHGS 10.000000
F53/30G B
A1120.5330GHMGHG
S
10.000000
F53/30G B
A1120.5330GHMGHGS 10.000000
F53/30G B
A1120.5330GHMGHG
S
10.000000
F53/30G B
A1120.5330GHMGHG
S
10.000000
F53/30G B
A1120.5330GHMGHGS 10.000000
F53/30G B
A1120.5324GHMGHG
S
10.000000
F5 3/
G
B
A1120.5324GHMGHG
S 10.000000
F5 3/
G
B
A1120.5336GHM
I
HAO10.000000
F5 3/
G
B
A2310.2424LHM IHAO129.000000
24/ 24
J
A2333.2436LHM IHAO129.000000
J
A2310.2424LHM
I
HAO129.000000
JA2310.2424LHM
I
HAO129.000000
J
A2310.2424LHM IHAO129.000000
24/ 24
J
A2333.2436LHM IHAO129.000000
J
A2310.2424LHM IHAO129.000000
24/ 24
JA2333.2436LHM IHAO129.000000
2 4
JA2310.2424LHM IHAO129.000000
24/ 24
J
A2310.2424LHM IHAO129.000000
24/ 24
J
A2310.2424LHM
I
HAO129.000000
J
A2333.2436LHM IHAO129.000000
J
A2310.2424LHM IHAO129.000000
24/ 24
JA2333.2436LHM IHAO129.000000
2 4
JA2310.2424LHM IHAO129.000000
24/ 24
J
A2333.2436LHM
I
HAO129.000000
J
A2310.2424LHM IHAO129.000000
24/ 24
J
A2310.2424LHM
I
HAO129.000000
J
A2333.2436LHM IHAO129.000000
J
A2310.2424LHM IHAO129.000000
24/ 24
J
A2310.2424LHM
I
HAO129.000000
J
A2333.2436LHM IHAO129.000000
J
A2310.2424LHM IHAO129.000000
24/ 24
J
A2333.2436LHM
I
HAO129.000000
J
A2333.2436LHM
I
HAO129.000000
J
NOR TH
48" HIGH WALL
E. J. CO VE R
PL AT E
E.J.
COVER
PLATE E.J.
COVER
PLATE
NUCLEAR MEDICINE
E.J .
CO VE R
PL AT E
E. J. CO VE R PL AT E
E.J. COVER
PLATE
PLATE
E.J. COVER
E.J. COVER
PLATE
CHA IRS
DA IL Y L OGS
PSYC H IA T RI C DAY TRE AT M EN T
(INPATIENT
PHARMACY)
ORTHOPAEDIC DENTAL RENOVATION AREA
E.J.
COVER
PLATE
CO VE R
E. J. PL AT E
E.J .
CARE
COM MU NI TY
CARE
COM MU NI TY
WOM EN S
CLIN IC
STA TI ON
TU G DOC K
DI SCH A RGE B O X
COOK
CHILL
COOK
CHILL
COOK
CHILL
COOK
CHILL
COOK
CHILL
FR IDGECOF FE
R
EF
U C R
BLK
BLK
BLK
TRANSPORT
CORE NO. 1
SHELVING
FIRE ARM
LOCKERS
VAULT
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
LOW C OU NT ER
COU NT ER
FC
FCFC
FC
FC
FC
FC
FC
FC
FC
F.C .
FC
ST ORE
IV
NIC
2DRB
ST ORE
IV
5 6 7 81 2 3 4
FECFEC
F E C
F E C
FC
CO PY ST AN D
FIL ES FIL ES
FAX
FLA T FI LE
PA PER ST
TAB LE
PL OT TE R
PR IN T PR IN T PR IN T
PL OT TE R
CO PY ST AN D
SC RE E N
CU TT E R
FIL ES FIL ES
DN
INDUSTRIAL
STAIR
DN UP
UP
UP
DN
DN
UP
DN
1 W- 1 1 8
1 E - 1 0 0 A
1 E - 1 0 0
1 E - 1 0 0 B
1 E - 1 0 0 C
1 E - 1 0 3
1 E - 1 0 41 E - 1 0 51 E - 1 0 7
1 E - 1 0 8
1 E - 1 0 6
1 4
1 E - 1 0 9
C I X - 4
D T - 1
P 4
P - 1 0
P - 9 D T - 3
REF .
F5 3/
G
F5 3/
G
F5 3/
G
F53/30G
F53/30G F53/30G
F53/30G
F53/30G
F53/30G
F5 3/
G
F5 3/
G
F5 3/
G
F53/30G F53/30G
F53/30G
F53/30G
F53/30G
F53/30G
F5 3/
G
F5 3/
G
F5 3/
G
F53/30G F53/30G
F53/30G
F53/30G
F53/30G
F53/30G
F53/30G
F53/30G
24/ 24
24/ 24
24/ 24
24/ 24
2 4
24/ 24
24/ 24
24/ 24
2 4
24/ 24
24/ 24
24/ 24
5/ 5/
5/
15/18
5/
5/
TB
TB
TB
TB
TB
TB
TBTB
TBLT
LT/
LT
LT/
LT
LT/
LT
LT/
LT/48
LT
LT/
LT
LT/
LT/
F D U/
F D U/
F D U/
F D U/
F D U/
F D U/
F D U/
F D U/
F D U/
F D U/
FDU/48FDU/48
F D U/
F D U/
F D U/
F D U/
F D U/
F D U/
F D U/
4/
4/
4/
4/
4/
4/
4/
4/
4/
0/
60TS/48
0/
60TS/48
0/
60TS/48
0/
60TS/48
0/
TS/483
0/
TS/48
TS/48TS/48
0/
60TS/48
0/
60TS/48
AE
RO
N
A
ERO
N
A
ERO
N
A
ERO
NAERO
N
NOR TH
48" HIGH WALL
E. J. CO VE R
PL AT E
E.J.
COVER
PLATE E.J.
COVER
PLATE
NUCLEAR MEDICINE
E.J .
CO VE R
PL AT E
E. J. CO VE R PL AT E
E.J. COVER
PLATE
PLATE
E.J. COVER
E.J. COVER
PLATE
CHA IRS
DA IL Y L OGS
PSYC H IA T RI C DAY TRE AT M EN T
(INPATIENT
PHARMACY)
ORTHOPAEDIC DENTAL RENOVATION AREA
E.J.
COVER
PLATE
CO VE R
E. J. PL AT E
E.J .
CARE
COM MU NI TY
CARE
COM MU NI TY
WOM EN S
CLIN IC
STA TI ON
TU G DOC K
DI SCH A RGE B O X
COOK
CHILL
COOK
CHILL
COOK
CHILL
COOK
CHILL
COOK
CHILL
FR IDGECOF FE
R
EF
U C R
BLK
BLK
BLK
TRANSPORT
CORE NO. 1
SHELVING
FIRE ARM
LOCKERS
VAULT
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
LOW C OU NT ER
COU NT ER
FC
FCFC
FC
FC
FC
FC
FC
FC
FC
F.C .
FC
ST ORE
IV
NIC
2DRB
ST ORE
IV
5 6 7 81 2 3 4
FECFEC
F E C
F E C
FC
CO PY ST AN D
FIL ES FIL ES
FAX
FLA T FI LE
PA PER ST
TAB LE
PL OT TE R
PR IN T PR IN T PR IN T
PL OT TE R
CO PY ST AN D
SC RE E N
CU TT E R
FIL ES FIL ES
DN
INDUSTRIAL
STAIR
DN UP
UP
UP
DN
DN
UP
DN
1 W- 1 1 8
1 E - 1 0 0 A
1 E - 1 0 0
1 E - 1 0 0 B
1 E - 1 0 0 C
1 E - 1 0 3
1 E - 1 0 41 E - 1 0 51 E - 1 0 7
1 E - 1 0 8
1 E - 1 0 6
1 4
1 E - 1 0 9
C I X - 4
D T - 1
P 4
P - 1 0
P - 9 D T - 3
FD FD
DT-1
P4
PRIMARY AREA OF WORK THIS PHASE
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:2
A
M
GI003
SITE PLAN - CONSTRUCTION
STAGING
3 6ED
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 5/26/2020
BID DOCUMENTS
652-19-10819-127
LW
N
AREA OF WORK
FOURTH FLOOR
KEY PLAN
SCALE: NO SCALE
Scale: 1" = 200'-0"
SITE PLAN
Scale: 1" = 80'-0"
FIRST FLOOR PLAN
Scale: 1" = 40'-0"
FOURTH FLOOR PLAN
DELIVERY
ENTRANCE
DELIVERY
ENTRANCE
PATH OF CONSTRUCTION TRAFFIC TO ACCESS 4TH FLOOR WORK AREA VIA
ELEVATORS TO BE CONFIRMED BY COR
SERVICE ELEVATOR TO BE
CONFIRMED BY COR
1" = 20'-0"
ENLARGED PLAN @ ELEVATORS
NORTH
PLAN
NORTH
PLAN
NORTH
PLAN
A. CONTRACTOR TO VERIFY LAY DOWN AREA AND
CONSTRUCTION PARKING AREA WITH COR.
S SS
S S
S
S SS
S S
S
S S
S S
S S
S S
S
S S
S
S S
S S
S S
S
S SS S S S
S SS
S S
S SS S S S S S S S
S S
S S
S
S SS
S S
S S
SS
SS
SS
8 10 11 12 13 14 16
W
X
Y
Z
AA
FF
X.1
PRIMARY AREA OF WORK
PATIENT RM
4A-166
PATIENT RM
4A-165
CORRIDOR
C4A-10
PATIENT RM
4A-164
PATIENT RM
4A-164
NURSE OFFICE
4A-156
LINEN
4A-155A
OFFICE
4A-155
STRETCH
C4A-8
INTERN ON CALL
4A-151STAFF OFFICE
4A-167
PATIENT RM
4A-168
CONTROL CENTER
C4A-11
PATIENT RM
4A-171
STORAGE
4A-170
SOILED UTILITY
4A-169
CLEAN UTILITY
4A-173
ELECTRICAL RM
4A-172
PATIENT RM
4A-177
STORAGE
4A-176
SOILED UTILITY
4A-175
MEDICAL RM
4A-174
STAIR
CONTROL CENTER
C4A-13
PATIENT RM
4A-178
STAFF OFFICE
4A-179
PATIENT RM
4A-180
PATIENT RM
4A-181
PATIENT RM
4A-182
PATIENT RM
4A-183
HEAD NURSE
4A-190
LINEN
4A-191A
LINEN
4A-191
STRETCH
C4A-15
INTERN OFFICE
4A-196
SHOWER
4A-198
TOILET
4A-197
ANTE RM
4A-186
PATIENT RM
4A-184
TOILET
4A-185
CORRIDOR
C4A-16
PATIENT RM
4A-187
ANTE RM
4A-188
TOILET
4A-189
ANTE RM
4A-163
ANTE RM
4A-160
PATIENT RM
4A-158
TOILET
4A-159
PATIENT RM
4A-161
TOILET
4A-162
TOILET
4A-154
TOILET
4A-152
SHOWER
4A-153
MALE LOCKER
4A-147
MALE LOCKER
4A-148
MALE LOCKER
4A-143
FEMALE LOCKER
4A-144
STORAGE
4A-142
PATIENT WAITING
C4A-4
CORRIDOR
C4A-5
OFFICE
4A-145
OFFICE
4A-100
TOILET
4A-101 OFFICE
4A-102
CARDIAC ELEC
TROPHYSIOLOGY
4A-104
RECOVERY
4A-105
EP LAB
4A-108
SOILED UTILITY
4A-108
CONTROL
4A-107
TOILET
4B-169
CORRIDOR
C4B-8
ELEC
TROPHISIOLOGY
4A-204A
TEAM ROOM MED.
PUL. OFFICE
4A-193
FAMILY WAITING
4A-149
LINEN
4A-200
TRASH
4A-201
STAFF TOILET
4A-192
HAC
4A-199
STORAGE
4A-195
CORRIDOR
C4A-17
ELEV LOBBY
C4A-1
STAIR
ELEV
P-3
ELEV
P-2
ELEV
P-1
EMERGENCY
PRESSURE EQUIP
4A-204
CONVEYOR
CM-1
ELEV
P-4
ELEV
DT-1
CORRIDOR
C4B-1
HSK STORAGE
4B-104
CORRIDOR
C4B-2
REG. DIETICIAN
OFFICE
4B-105
TSC-2
CONVEYOR
4A-205
PULMONARY
FELLOWS OFFICE
4A-194
TOILET
4A-162
4 BED PATIENT RM
4B-168
CRITICAL CARE
4A-110
STORAGE
4A-109
OFFICE
4A-111
CHIEF RESP CARE
4A-138
CORRIDOR
C4A-5
CLEAN UP/ REPAIR
4A-112
MECHANICAL SVC
BAY-G
4A-202
ELECTRICAL SVC
BAY
4A-203
PATIENT RM
4A-100
TOILET
4B-101
PATIENT RM
4B-102
TOILET
4B-103
ICRA BARRIER WALL
CONSTRUCTION
ACCESS DOOR
CONSTRUCTION
ACCESS DOUBLE
DOORS
MAINTAIN ACCESS TO
THIS STAIR
THROUGHOUT
CONSTRUCTION.
CONSTRUCTION ACCESS
ELEVATORS CONFIRM USE
OF ELEVATOR WITH COR.
DP
DP
DP
DP DP
DP
DP
DP
DP
DP
d
DP
DP
DP
SEE SHEET GI005 FOR TEMP PARTITION TYPE
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:5
:2
P
M
GI004
FOURTH FLOOR ILSM PLAN
4 6ED
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 5/26/2020
BID DOCUMENTS
652-19-10819-127
LW
N
AREA OF WORK
FOURTH FLOOR
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
FOURTH FLOOR ILSM AND ICRA PLAN 0 4 8 16
NORTH
PLAN
PROVIDE CONSTRUCTION SIGN:
"CONSTRUCTION IN PROGRESS-
NO ENTRANCE"
ICRA WALL BARRIER
ICRA WALL BARRIER
COMPLY WITH VA MEDICAL CENTER INTERIM LIFE
SAFETY MEASURE POLICIES.
THE PROJECT SITE MUST BE COMPLETELY
CONTAINED WITH CONSTRUCTION BARRIERS. THE
BARRIERS MUST CONSIST OF SOLID WALL
CONSTRUCTION (I.E., GWB THAT EXTENDS FROM
FLOOR TO THE UNDERSIDE OF THE ABOVE
STRUCTURE.
PROVIDE LEVEL OF SAFETY COMPARABLE TO THAT
DESCRIBED IN NFPA 101 AND NFPA 241 .
8.6.2 TEMPORARY SEPARATION WALLS
8.6.2.1 PROTECTION SHALL BE PROVIDED TO
SEPARATE AN OCCUPIED PORTION OF THE
STRUCTURE FROM A PORTION OF THE STRUCTURE
UNDERGOING ALTERATION, CONSTRUCTION OR
DEMOLITION OPERATIONS WHEN SUCH OPERATIONS
ARE CONSIDERED AS HAVING A HIGHER LEVEL OF
HAZARD THAN THE OCCUPIED PORTION OF THE
BUILDING.
8.6.2.2 WALLS SHALL HAVE AT LEAST A 1-HOUR FIRE
RESISTANCE RATING.
8.6.2.3 OPENING PROTECTIVES SHALL HAVE AT
LEAST A 45 MINUTE FIRE PROTECTION.
8.6.2.4 NON-RATED WALLS AND OPENING
PROTECTIVES SHALL BE PERMITTED WHEN AN
APPROVED AUTOMATIC SPRINKLER SYSTEM IS
INSTALLED. (THIS ONLY APPLIES IF SPRINKLER
SYSTEM IS MAINTANED OPERATIONAL IN BOTH THE
NON-CINSTRUCTION AND CONSTRUCTION AREAS).
DUST PARTITION PER NFPA 241 (TEMPORARY SEPARATION WALLS);
SEE DEMOLITION PLANS AS01 & AS02 FOR TYPE DP WALL LOCATIONS.
UL DESIGN U425, 1-HOUR RATED
DUST PARTITION PER NFPA 241 (TEMPORARY SEPARATION WALLS); SEE
DEMOLITION PLANS AD101 FOR TYPE DP WALL LOCATIONS.
UL DESIGN U425, 1-HOUR RATED
DP
DP
5/8" TYPE 'X' GWB ON
METAL STUDS @ 24" O.C.
EXISTING CEILING ON OCCUPIED
SIDE TO REMAIN
5/8" TYPE 'X' GWB ON BOTH
SIDES OF METAL STUDS @ 24"
O.C.; CARRY TO UNDERSIDE OF
STRUCTURE ABOVE.
FINISHED FLOOR.
SEALANT, TYP.
SECTION: HEAD
PLAN:
SECTION: SILL
NON-PROJECT AREA
OCCUPIED SIDE
PROJECT AREA
CONSTRUCTION SIDE
TEMPORARY SEPARATION
WALL NOTES:
NFPA 241:
EXTEND DUST PARTITION TO
INTERSTITIAL FLOOR ASSEMBLY
ABOVE. BRACE AS REQUIRED.
1. VERIFY ALL EXISTING CONDITIONS. NOTIFY COR OF ANY CONFLICTS
PRIOR TO PROCEEDING WITH DEMOLITION.
2. REMOVE ALL EXISTING ITEMS OF CONSTRUCTION AND EQUIPMENT
WITHIN THE PROJECT AREA INDICATED ON DEMOLITION PLAN,
WHETHER SHOWN OR NOT, INCLUDING BUT NOT LIMITED TO FLOOR
MATERIAL, BASE, WALLS, CEILINGS, DOORS, DOOR FRAMES,
CASEWORK, ELECTRICAL, MECHANICAL, PLUMBING FIXTURES AND
SYSTEM, AS REQUIRED TO ACCOMMODATE NEW CONSTRUCTION.
3. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS FOR ADDITIONAL NOTES AND LOCATION OF
ADDITIONAL ITEMS TO BE REMOVED.
4. SEE AD111 FOR OVERALL REFLECTED CEILING DEMOLITION PAN AND
NOTES. COORDINATE PHASING LIMITS AS SHOWN ON GI102.
5. PRIOR TO DEMOLITION, THE CONTRACTOR SHALL PROVIDE ALL
NECESSARY SAFEGUARDS TO MAINTAIN ALL PARTS OF THE PROJECT
IN A SAFE CONDITION AT ALL TIMES DURING THE PROCESS OF
CONSTRUCTION AND TO PROTECT FROM DAMAGE OF THOSE
PORTIONS OF THE EXISTING BUILDING WHICH ARE TO REMAIN.
6. EXISTING WORK TO REMAIN, IF DAMAGED BY ANY TRADE OR NEW
CONSTRUCTION, SHALL BE PATCHED, REPAIRED OR REPLACED TO
MATCH EXISTING.
7. PATCH ALL HOLES IN WALLS, FLOORS AND CEILING AND OTHER PARTS
OF THE STRUCTURE AFFECTED BY THIS CONTRACT. HOLES SHALL BE
FILLED, SEALED, PAINTED, CAULKED OR PLUGGED NEATLY WITH
ORIGINAL TYPE OF MATERIALS TO MATCH THE EXISTING PART OF
THE STRUCTURE AFFECTED.
8. WHERE DEMOLITION IS INDICATED ON THE DRAWINGS, OR REQUIRED
FOR INSTALLATION OF NEW CONSTRUCTION, REMOVE EXISTING
CONSTRUCTION AS REQUIRED TO PERFORM THE WORK INDICATED.
REMOVE SETTING BEDS AND INFILL FLUSH WITH ADJACENT CONCRETE
SLAB.
9. REFER TO HAZARDOUS MATERIAL SURVEY REPORT. FOLLOW PROPER
ABATEMENT AND DISPOSAL PROCEDURES.
10. CONTRACTOR SHALL PROVIDE ALL NECESSARY BARRICADES AND
OTHER FORMS OF PROTECTION AS REQUIRED TO PROTECT
PERSONNEL, OTHER TENANTS AND THE GENERAL PUBLIC FROM
INJURY DUE TO DEMOLITION WORK.
11. CONTRACTOR SHALL ENSURE THAT DEMOLITION WORK DOES NOT
INTERFERE WITH OR PROHIBIT THE CONTINUING OCCUPATION OF THE
ADJACENT BUILDING OPERATIONS. THIS INCLUDES BUT IS NOT LIMITED
TO THE SELECTIVE DEMOLITION OF PARTITIONS, ELECTRICAL,
PLUMBING, FIRE PROTECTION AND MECHANICAL SYSTEMS.
CONTRACTOR SHALL INFORM THE COR A MINIMUM OF 72 HOURS PRIOR
TO DEMOLITION ACTIVITIES THAT WILL AFFECT THE NORMAL
OPERATION OF THE BUILDING. COORDINATE A SCHEDULE WITH THE
COR.
12. INTERIOR WALLS WITHIN THE LIMITS OF CONSTRUCTION THAT ARE TO
REMAIN SHALL NOT BE DISTURBED , EXCEPT TO SCRAPE LOOSE PAINT
AND PATCH AS NECESSARY. CLEAN/RESURFACE AND PREPARE TO
RECEIVE NEW PAINT TO MATCH ADJACENT WALLS AND FINISHES.
GENERAL DEMOLITION
NOTES:
1. ALL WORK SHALL BE COMPLETED IN COMPLIANCE WITH APPLICABLE
CODES AND TO THE SATISFACTION OF LOCAL BUILDING INSPECTORS.
2. WHERE DISCREPANCIES IN THE CONTRACT DOCUMENTS, DRAWINGS
OR SPECIFICATIONS ARE DISCOVERED BY THE CONTRACTOR PRIOR TO
BID, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE VA COR AND
REQUEST CLARIFICATION.CONTRACTOR INTERPRETATION OF
DRAWINGS, DETAILS OR SPECIFICATIONS SHALL BE BASED UPON THE
MOST RESTRICTIVE OR DIFFICULT SOLUTIONS AND SHALL BE
CONSIDERED AS INCLUDED IN THE CONTRACTOR'S BID PROPOSAL.
POST BID OR POST CONTRACT REQUESTS FOR INFORMATION ARE NOT
CONSIDERED AS BASIS FOR CHANGE ORDER UNLESS SO CLARIFIED OR
DOCUMENTED AS PART OF ORIGINAL BID PROPOSAL PACKAGE.
3. ALL DIMENSIONS OF EXISTING FEATURES AND ITEMS ARE
APPROXIMATE. FIELD VERIFY ALL CONDITIONS. NOTIFY COR OF ANY
CONFLICTS PRIOR TO PROCEEDING WITH ANY RENOVATION.
4. WIPE ALL PAINTED GYPSUM WALLS.
5. CONTRACTOR SHALL COORDINATE WITH COR TO RELOCATE ANY
BOXES, SUPPLIES, AND STORAGE EQUIPMENT IN ALL ROOMS.
6. REFER TO MECHANICAL, ELECTRICAL, PLUMBING, TECHNOLOGY AND
FIRE PROTECTION DRAWINGS FOR ADDITIONAL WORK NOTES AND
COORDINATION. CONTRACTOR SHALL COORDINATE ALL VA
FURNISHED/VA INSTALLED AND ALL VA FURNISHED/ CONTRACTOR
INSTALLED WORK WITH THE COR.
7. DIMENSIONS ARE TO FACE OF STUD AND/OR FACE OF MASONRY
UNLESS OTHERWISE NOTED.
8. ALL PATIENT HEADWALLS ARE TO BE PLACED ON THE CENTERLINE
DIMENSION SHOWN IN EACH PATIENT ROOM. THE BED WILL BE
POSITIONED AT THE CENTER OF THE HEADWALL.
9. THE CONTRACTOR SHALL FIRESTOP ALL RATED WALLS, FLOORS AND
INTERSTITIAL FLOOR AT PENETRATIONS FOR NEW AND OLD UTILITIES
USING THE APPROPRIATE UL THRU-PENETRATION FIRESTOP SYSTEM
FOR EACH PENETRATING ITEM. PATCH, REPAIR AND FIRESTOP AT
DEMOLISHED UTILITIES, TYPICAL. MAINTAIN INTEGRITY OF RATED
SYSTEMS.
10. INSTALL NEW FLOOR DRAINS AND TRENCH DRAINS WHERE INDICATED.
CONTRACTOR SHALL VERIFY EXISTING STRUCTURAL ELEMENTS THAT
MUST NOT BE DISTURBED. SEE DETAILS DEPICTING STRUCTURAL
LIMITATIONS AND ADHERE TO THE LIMITS.
GENERAL RENOVATION
NOTES:
1"
1"
2-1/2" STEEL C-H STUD AT
12" MAX., (CENTERED IN
OPENINGS LARGER THAN
12", UP TO 24")
UL DESIGN NO. U415, SYSTEM E
FIRESTOP SEALANT ALL SIDES
EXISTING TRUSS TEE
EXISTING GYPSUM CONCRETE
INTERSTITIAL FLOOR DECK.
FIRESTOP SEALANT ALL SIDES
CONT. 2-1/2" STEEL J-RUNNER
INSTALLED OVER EDGE OF GYPSUM
CONCRETE DECK AT
FULL PERIMETER OF OPENING
CONT. 2-1/2" STEEL E-STUDS
FASTENED TO J-RUNNER
NOTE: WHEN THE EXISTING CONDITIONS DO NOT PERMIT PROPER INSTALLATION OF THE VARIOUS COMPONENTS SHOWN IN THIS DETAIL, THE CONTRACTOR
SHALL:
1. GRIND AND/OR SAW CUT AS NECESSARY TO MAKE OPENING SIDES VERTICAL AND SQUARE.
2. SAW CUT AS NECESSARY TO MODIFY ROUND OPENINGS LARGER THAN 7" DIAMETER TO MAKE RECTANGULAR.
8" 2' - 1 1/2" 8" 2' - 1 1/2" 8" 2' - 1 1/2" 8" 2' - 1 1/2" 8" 2' - 1 1/2" 8"
/2
/2
/2
/2
POSSIBLE LOCATION
8"
WIDTH A
COLUMN 8" 8 1/4"
W
ID
T H
B
C O
L U
M N
POSSIBLE LOCATION
VOIDED
SHEAR
AREA
VOIDED SHEAR
AREA
WAFFLE SLAB RIB, DO NOT
DISTURB UNLESS IN SHADED
AREA, TYP. - SEE PLAN BELOW
STRUCTURAL SLAB
REINFORCING
TOPPING SLAB
LINE OF HOLE,
BEYOND
COLUIMN,
BEYOND
COLUMN
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:4
A
M
GI005
GENERAL NOTES, ABBREVIATIONS,
SYMBOLS AND DETAILS
5 6ED
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 5/26/2020
BID DOCUMENTS
652-19-10819-127
LW
N
AREA OF WORK
FOURTH FLOOR
KEY PLAN
SCALE: NO SCALE
Scale: 3" = 1'-0"
INTERSTIAL FLOOR DECK REPAIR DETAIL AT RECTANGULAR OPENING
Scale: 1/2" = 1'-0"
HOLE/OPENING PLACEMENT IN EXISTING WAFFLE SLAB
FD FD
S
S
S
S S
S
S
S S
S S
S
S S
S
SS
S
S SS
S SS
S S
S
S SS
S S
S
S S
S S
S
S S
S
1. OCCUPANCY CLASSIFICATION
(SMOKE COMPARTMENTS)
IBC 2018 6. INSTITUTIONAL (I-2)
2018 NFPA 1010 LIFE SAFETY CHAPTER 19-EXISTING HEALTHCARE
2. CONSTRUCTION TYPE
IBC 2018 2018 NFPA 101 LIFE SAFETY
SECTION 601 TABLE A.7.2.1
TYPE IA I(332)
3. FIRE SPRINKLERS
IBC 2018 2018 NFPA LIFE SAFETY
EXISTING BUILDING IS SPRINKLERED
4. HEIGHT / AREA LIMITATIONS - EXISTING
PER IBC 2018 TABLE 503
AREA: MAX ALLOWABLE AREA ACTUAL AREA
(TABLE 503)
VA NURSING UNIT 4A UL 10,913 SF
HEIGHT: MAX ALLOWABLE ACTUAL BUILDING HEIGHT
AREA (TABLE 503)
HEIGHT IN FEET UL EXISTING
HEIGHT IN STORIES 5 + BASEMENT
5. OCCUPANCY LOAD
NOTES: INSTITUTIONAL OCCUPANCY TOTAL
1. CALCULATIONS ARE (PRINCIPAL INTENDED USE) OCCUPANCY
PER NFPA TBL. 7.3.1.2 AREA / FACTOR = OCCUPANTS
VA NURSING UNIT 4A (ICU) 10,913 SF 240/SF 46
TOTAL 10,913 SF 46
6. EGRESS REQUIREMENTS
PER NFPA 101 TABLE 7.3.3.1
LEVEL COMPONENT STAIR COMPONENT
.2" PER OCCUPANT .3" PER OCCUPANT
MIN ACTUAL MIN ACTUAL
VA NURSING UNIT 4A (ICU) 96" 9.2" 36" 14.8"
NUMBER OF EXITS (UNIT 4A. AREA ONLY)
MIN. PER NFPA 101 ACTUAL
VA NURSING UNIT 4A (ICU) 2 2
7. TRAVEL DISTANCE
NOTES:
1. PER NFPA 101 TABLE A7.6.1.
2. PER NFPA 101 TABLE A7.6.1. NO DEAD END CORRIDORS CAN EXCEED 20'
TRAVEL DISTANCE LIMIT
NFPA 101 TABLE A7.6.1 ACTUAL
200 FT.
8. APPLICABLE CODES - DEPARTMENT OF VETERANS AFFAIRS
LIFE SAFETY CODE NFPA 101, 2018 EDITION
INTERNATIONAL BUILDING CODE 2018 EDITION, WITH STATE AMENDMENTS
AMERICAN DISABILITIES ACT 2010 WITH REVISED STANDARDS
INTERNATIONAL MECHANICAL CODE 2015 EDITION, WITH STATE AMENDMENTS
INTERNATIONAL PLUMBING CODE 2012 EDITION, WITH STATE AMENDMENTS
INTERNATIONAL GAS CODE 2012 EDITION, WITH STATE AMENDMENTS
NATIONAL ELECTRIC CODE 2020 EDITION, WITH NO STATE AMENDMENTS
INTERNATIONAL FIRE PROTECTION CODE 2012 EDITION, WITH NO STATE AMENDMENTS
INTERNATIONAL FUEL GAS CODE 2012 EDITION, WITH STATE AMENDMENTS
INTERNATIONAL ENERGY CONSERVATION CODE 2015 EDITION, WITH STATE AMENDMENTS
NFPA 13 2013 EDITION
TABLE 102. 10: CODES REFERENCE GUIDE
OCCUPANCY CLASSIFICATION
BUILDING CONSTRUCTION TYPES INCLUDING ALLOWABLE HEIGHT,
ALLOWABLE BUILDING AREAS, AND REQUIREMENTS FOR THE
SPRINKLER PROTECTION RELATED TO MINIMUM BUILDING CONSTRUCTION TYPES
MEANS OF EGRESS
STANDPIPES
INTERIOR FINISH
HVAC SYSTEMS
VERTICAL OPENINGS
SPRINKLER SYSTEMS MINIMUM CONSTRUCTION STANDARDS
FIRE ALARM SYSTEMS
SMOKE ALARM AND SMOKE DETECTION SYSTEMS
PORTABLE FIRE EXTINGUISHERS
COOKING EQUIPMENT
FUEL FIRE APPLIANCES
LIQUID PETROLEUM GAS
COMPRESSED NATURAL GAS
4A RENOVATION OF EXISTING SPACE
PRIMARY
LSC
IBC
LSC
IBC
LSC
IMC
LSC
LSC
LSC
LSC
IFC
LSC & NFPA
IFGC
NFPA 58
NFPA 52
SECONDARY
IBC
LSC
NONE
IFC
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NFPA 54
NFPA 54 & IFGC
NONE
ICU NURSING UNIT (8 ROOMS)
181 FT. (MAX)
VA FIRE PROTECTION DESIGN MANUAL 2015, 7TH EDITION, DECEMBER
NOT IN CONTRACT
EGRESS PATH
EGRESS PATH TAG
EGRESS PATH TAG - COMMON PATH
EGRESS IDENTIFICATION
AREA OF REFUGE
HAZARDOUS LOCATION
FIRE EXTINGUISHER BRACKET
FIRE EXTINGUISHER CABINET
FIRE BLANKET CABINET
EMERGENCY RESPONSE REFERENCE
CONTROLLED ACCESS - ALWAYS
UNLOCKED IN DIRECTION OF EGRESS
KNOX BOX
DELAYED EGRESS W/ ALARM
CA
DE
KB
XXX
XXX
FEB
FEC
FBC
CAPACITYCLR
EXTERIOR
EXIT
XX" ###
EXIT
IDENTIFICATION
EGRESS CLEAR
WIDTH
EGRESS
CAPACITY
LEGEND
EXIT DISTANCE 181'-0''
EXIT DISTANCE 76'-6''
E X
IT
D
IS
T
A N
C E
E X
IT
D
IS
T
A N
C E
269 SF
ICU 1
4A-169
279 SF
ICU 2
4A-168
408 SF
ICU 3
4A-167
299 SF
ICU 4
4A-166
303 SF
ICU 5
4A-165
317 SF
ICU 6
4A-164
304 SF
TEAM RM
4A-163
58 SF
ELECTRICAL
4A-164A
381 SF
ISOLATION ICU 7
4A-162
63 SF
CHART
4A-162-179 SF
ANTE RM
4A-161
59 SF
TOILET
4A-162T
59 SF
TOILET
4A-160T
278 SF
ISOLATION ICU 8
4A-160
105 SF
NURSE MGR
4A-155
104 SF
MEDICAL
DIRECTOR
4A-156
52 SF
TOILET
4A-164T
52 SF
TOILET
4A-165T
52 SF
TOILET
4A-166T
52 SF
TOILET
4A-167T
52 SF
TLT
4A-168T
52 SF
TLT
4A-169T
184 SF
CLEAN SUPPLY
4A-159
225 SF
BREAK RM
4A-158
112 SF
FEMALE
LOCKERS
4A-152
63 SF
TOILET
4A-153
57 SF
MALE LOCKERS
4A-151
120 SF
CONSULT
4A-148
28 SF
LINEN
4A-149
34 SF
HAC
4A-154
150 SF
TEAM ROOM
4A-172
147 SF
TEAM RM
4A-173
113 SF
CASE MANAGER
4A-174
164 SF
SOILED UTILITY
4A-170
305 SF
EQUIPMENT
4A-171
39 SF
NOUR
4A-172-1
39 SF
ALC
4A-171-1
115 SF
MEDICATION
4A-175
72 SF
CORR
4A-199
39 SF
MEDS
4A-200
16 SF
P-TUBE
4A-200A
304 SF
CONTROL
CENTER
C4A-11
355 SF
CONTROL
CENTER
C4A-13
25 SF
ALC
4A-154-1
8 SF
ALC
4A-159-1
456 SF
WAITING RM
4A-146
589 SF
CORRIDOR
C4A-10
154 SF
CORRIDOR
C4A-17
224 SF
CORRIDOR
C4A-15
866 SF
CORRIDOR
C4A-14
60 SF
TOILET
4A-150
519 SF
CORRIDOR
C4A-12
131 SF
STAIR
46 SF
CHART
4A-165-1 46 SF
CHART
4A-167-1
45 SF
CHART
4A-169-1
57 SF
STORAGE
4A-201
61 SF
TOILET
4A-147
42 SF
STORAGE
4A-157
PATIENT WAITING
C4A-4
OFFICE
4A-145
OFFICE
4A-100
TOILET
4A-101 OFFICE
4A-102
CARDIAC ELEC
TROPHYSIOLOGY
4A-104
RECOVERY
4A-105
EP LAB
4A-108
SOILED UTILITY
4A-108
CONTROL
4A-107
ELEV
P-3
ELEV
P-2
ELEV
P-1
EMERGENCY
PRESSURE EQUIP
4A-204
CONVEYOR
CM-1
ELEV
P-4
ELEV
DT-1
TSC-2
CONVEYOR
4A-205
CRITICAL CARE
4A-110
STORAGE
4A-109
CHIEF RESP CARE
4A-138
CORRIDOR
C4A-5
CLEAN UP/ REPAIR
4A-112
MECHANICAL SVC
BAY-G
4A-202
ELECTRICAL SVC
BAY
4A-203
PATIENT RM
4A-100
TOILET
4B-101
EXIT DISTANCE 109'-4''
ROOF
ROOF
FEC
FEC
127 SF
STAIR
FEC
OIT
4B-123
(DEDUCT ALTERNATE #1)
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:2
:2
P
M
LS101
FOURTH FLOOR LIFE SAFETY AND
ANALYSIS
6 6ED
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 5/26/2020
BID DOCUMENTS
652-19-10819-127
LW
PROPOSED USE:
OWNED BY:
CODE ENFORCEMENT JURISDICTION:
APPLICABLE CODES:
GENERAL CODE INFORMATION:
NEW CONSTRUCTION
RENOVATION (EXISTING BUILDING)
CONSTRUCTION TYPE:
MIXED CONSTRUCTION
SPRINKLERED
MEZZANINE
MIXED OCCUPANCY
PRIMARY OCCUPANCY:
SECONDARY OCCUPANCY:
PROJECT NAME:
PROJECT ADDRESS:
OWNER OR AGENT:
FEDERAL
SEE LS101
IMPROVE PATIENT PRIVACY 4A
HUNTER HOLMES MCGUIRE VAMC 1201
BROAD ROCK BLVD
RICHMOND, VA 23249
PRIVAY
CODE INFORMATION
N
AREA OF WORK
FOURTH FLOOR
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
ENLARGED LIFE SAFETY PLAN
Scale: 12" = 1'-0"
LIFE SAFETY ANALYSIS
0 4 8 16
NORTH
PLAN
8 9 10 11 12 13 14 16
W
X
Y
Z
AA
FF
PRIMARY AREA OF WORK THIS PHASE
X.1
BB
B
B
B
B
B
B
C
A
A
A
AA
A
A
A
AA
A
B
B B B
B
PATIENT RM
4A-166
PATIENT RM
4A-165
CORRIDOR
C4A-10
PATIENT RM
4A-164
PATIENT RM
4A-164
NURSE OFFICE
4A-156
LINEN
4A-155A
OFFICE
4A-155
STRETCH
C4A-8
INTERN ON CALL
4A-151
STAFF OFFICE
4A-167
PATIENT RM
4A-168
CONTROL CENTER
C4A-11
PATIENT RM
4A-171
STORAGE
4A-170
SOILED UTILITY
4A-169
CLEAN UTILITY
4A-173
ELECTRICAL RM
4A-172
PATIENT RM
4A-177
STORAGE
4A-176
SOILED UTILITY
4A-175
MEDICAL RM
4A-174
STAIR
CONTROL CENTER
C4A-13
PATIENT RM
4A-178
STAFF OFFICE
4A-179
PATIENT RM
4A-180
PATIENT RM
4A-181
PATIENT RM
4A-182
PATIENT RM
4A-183
HEAD NURSE
4A-190
LINEN
4A-191A
LINEN
4A-191
STRETCH
C4A-15
INTERN OFFICE
4A-196
SHOWER
4A-198
TOILET
4A-197
ANTE RM
4A-186
PATIENT RM
4A-184
TOILET
4A-185
CORRIDOR
C4A-16
PATIENT RM
4A-187
ANTE RM
4A-188
TOILET
4A-189
ANTE RM
4A-163
ANTE RM
4A-160
PATIENT RM
4A-158
TOILET
4A-159
PATIENT RM
4A-161
TOILET
4A-162
TOILET
4A-154
TOILET
4A-152
SHOWER
4A-153
MALE LOCKER
4A-147
MALE LOCKER
4A-148
MALE LOCKER
4A-143
FEMALE LOCKER
4A-144
STORAGE
4A-142
PATIENT WAITING
C4A-4
CORRIDOR
C4A-5
OFFICE
4A-145
OFFICE
4A-100
TOILET
4A-101
OFFICE
4A-102
CARDIAC ELEC
TROPHYSIOLOGY
4A-104
RECOVERY
4A-105
EP LAB
4A-108
SOILED UTILITY
4A-108
CONTROL
4A-107
TOILET
4B-169
CORRIDOR
C4B-8
ELEC
TROPHISIOLOGY
4A-204A
TEAM ROOM MED.
PUL. OFFICE
4A-193
FAMILY WAITING
4A-149
LINEN
4A-200
TRASH
4A-201
STAFF TOILET
4A-192
HAC
4A-199
STORAGE
4A-195
CORRIDOR
C4A-17
ELEV LOBBY
C4A-1
STAIR
ELEV
P-3
ELEV
P-2
ELEV
P-1
EMERGENCY
PRESSURE EQUIP
4A-204
CONVEYOR
CM-1
ELEV
P-4
ELEV
DT-1
CORRIDOR
C4B-1
HSK STORAGE
4B-104
CORRIDOR
C4B-2
REG. DIETICIAN
OFFICE
4B-105
TSC-2
CONVEYOR
4A-205
PULMONARY
FELLOWS OFFICE
4A-194
TOILET
4A-162
CRITICAL CARE
4A-110
STORAGE
4A-109
OFFICE
4A-111
CHIEF RESP CARE
4A-138
CORRIDOR
C4A-5
CLEAN UP/ REPAIR
4A-112
MECHANICAL SVC
BAY-G
4A-202
ELECTRICAL SVC
BAY
4A-203
PATIENT RM
4A-100
TOILET
4B-101
PATIENT RM
4B-102
TOILET
4B-103
KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
P
M
AH101
OVERALL FOURTH FLOOR DEMOLITION
PLAN - HAZARDOUS MATERIALS
100% CONSTRUCTION DOCUMENTS
1 1HJM
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 4/03/2020
100% CONSTRUCTION DOCUMENTS
652-19-108
19-127
SDB
Scale: 1/8" = 1'-0"
FOURTH FLOOR PLAN
N
AREA OF WORK
FOURTH FLOOR
KEY PLAN
SCALE: NO SCALE
0 4 8 16
A1. REMOVE APPROXIMATELY 13,900 SQUARE FEET
OF ASBESTOS CONTAINING VINYL FLOOR TILE,
NON-ASBESTOS CONTAINING VINYL FLOOR TILE,
AND ASBESTOS CONTAINING MASTIC INSIDE A
NEGATIVE PRESSURE CONTAINMENT.
A2. REMOVE APPROXIMATELY 30 SQUARE FEET OF
CAULKING LOCATED AROUND THE FRAME OF THE
PATIENT ROOMS DOORS.
A3. REMOVE APPROXIMATELY 310 SQUARE FEET OF
CEMENTITIOUS (TRANSITE-LIKE) PANELS LOCATED
BENEATH PERIMETER WINDOWS FOUND
THROUGHOUT THE 4A AREA.
A4. REMOVE APPROXIMATELY 10 SQUARE FEET OF
WINDOW GLAZING ASSOCIATED WITH THE 3.5' X
2.5' WINDOWS LOCATED IN THE ANTEROOM.
A5. REMOVE APPROXIMATELY 400 SQUARE FEET OF
HVAC DUCT MASTIC LOCATED WITHIN THE
INTERSTITIAL WALKWAY (NOT DEPICTED)
1. THE SCOPE OF ASBESTOS ABATEMENT WORK
CONSISTS OF REMOVING VINYL FLOOR TILE,
ASSOCIATED FLOORING MASTICS, CAULKING
AROUND PATIENT ROOM DOOR FRAMES,
CEMENTITIOUS WINDOW SILLS, WINDOW GLAZING,
AND HVAC JOINT MASTIC LOCATED WITHIN THE
INTERSTITIAL WALKWAY, AND ASSUMED FIRE
DOORS. ALL WORK SHALL BE CONDUCTED IN
ACCORDANCE WITH ALL FEDERAL, STATE, AND
LOCAL REGULATIONS AND THE CONTRACT
SPECIFICATIONS.
2. ALL WORK SHALL BE CONDUCTED DURING
ADMINISTRATIVE HOURS (7:00 AM TO 5:00 PM)
MONDAY - FRIDAY EXCLUDING FEDERAL HOLIDAYS.
3. WORK SCHEDULES AND LIMITS OF ABATEMENT
SHALL BE COORDINATED WITH THE VA COR AND
CPIH FOR APPROVALS, UNLESS OTHERWISE
INDICATED ON THE KEYNOTES. THE ABATEMENT
CONTRACTOR SHALL SUBMIT A DETAILED WORK
PLAN AND ABATEMENT SCHEDULE WITH THE
REQUIRED SUBMITTALS. ANY CHANGES TO THE
PROCEDURES, CONTAINMENT LIMITS AND PHASING
SHALL BE SUBMITTED TO THE VA COR FOR
APPROVALS.
4. THE LOCATIONS AND QUANTITIES SHALL BE FIELD
VERIFIED BY THE ABATEMENT CONTRACTOR. THE
LIMITS OF REMOVAL AND EXTENT OF THE
CONTAINMENTS SHALL BE VERIFIED WITH THE VA
COR AND VPIH/CIH.
5. ALL LOADOUT PROCEDURES SHALL BE
COORDINATED WITH THE VA COR AND VPIH.
6. ALL POLYETHYLENE SHEETING USED FOR THE
ABATEMENT PROJECT SHALL BE OF THE FIRE
RETARDANT TYPE.
7. THE LOCATIONS OF ABATEMENT
DECONTAMINATION UNITS AND WASTE DISPOSAL
CONTAINERS SHALL BE FIELD VERIFIED WITH THE VA
COR. ALL LOADOUT PROCEDURES SHALL BE
COORDINATED WITH THE VA COR.
8. ALL AIR MONITORING AND CLEARANCE SAMPLING
SHALL BE CONDUCTED BY THE CPIH.
9. VA PERSONNEL SHALL BE RESPONSIBLE FOR
REMOVING OR RELOCATING ALL DATA EQUIPMENT,
COMPUTERS, SUPPLIES, FURNITURE, DESKS, WALL
HANGINGS, ETC., FROM THE ABATEMENT AREAS.
10. ALL MECHANICAL SYSTEMS, INCLUDING BUT NOT
LIMITED TO, HVAC SYSTEMS, STEAM PIPING, ETC.,
SHALL BE SHUT DOWN DURING ALL ABATEMENT
ACTIVITIES. ABATEMENT OF ASBESTOS PIPE
INSULATION AND FITTING INSULATION FROM THE
STEAM PIPING MUST BE ACCOMPLISHED WHEN THE
STEAM PIPES ARE LESS THAN 150 DEGREES
FAHRENHEIT. ALL REQUIRED STEAM SHUTDOWNS
SHALL BE PROPERLY COORDINATED WITH THE VA TO
MINIMIZE IMPACT TO THE HOSPITAL OPERATIONS.
11. STRICT COORDINATION BETWEEN THE VA
OCCUPANTS, VA COR, CPIH, GENERAL CONTRACTOR
AND ABATEMENT CONTRACTOR SHALL BE
REQUIRED.
LEGEND:
AREAS WITH FLOOR TILE AND ASSOCIATED MASTIC
DOORFRAMES WITH ASBESTOS CONTAINING CAULK
CEMENTITIOUS WINDOW SILLS
WINDOW GLAZING
FROEHLING ROBERTSON
Engineering Stability Since 1881
NO MASTIC FLOORING
IN THESE AREAS
AutoCAD SHX Text
W W
X X
Y Y
Z Z
AA AA
X.1 X.1
PRIMARY AREA OF WORK
a b d e f g h i j k
1.0
2.0
3.0
4.0
5.0
6.0
7.0 c m n p
HSS3X3X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS4X4X3/8 HSS4X4X3/8
HSS4X4X3/8
HSS4X4X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS4X4X3/8
HSS4X4X3/8
HSS4X4X3/8
HSS4X4X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS4X4X3/8
HSS4X4X3/8 HSS4X4X3/8
HSS4X4X3/8 HSS3X3X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS3X3X3/8
HSS4X4X3/8 HSS4X4X3/8
HSS4X4X3/8 HSS4X4X3/8
HSS3X3X3/8
ANGLE BRACE L3 x 3 x
1/4" (TYP.)
X BRACING
o
X BRACING
ANGLE BRACE L3 x 3 x 1/4" (TYP.)
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:2
A
M
S-100
PATIENT LIFT SUPPORT PLAN
1 2ED
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 5/26/2020
BID DOCUMENTS
652-19-10819-127
LCW
Scale: 1/8" = 1'-0"
FOURTH FLOOR PLAN 0 4 8 16
NORTH
PLAN
1. ALL BEAMS SHALL BE W8 x 18 U.N.O.
2. PROVIDE X-BRACING AT BENTS a, e, h, k, 4.0 AND 7.0
3. PROVIDE MOMENT FRAMES AT BENTS b, d, f, g, i, j, 5.0
AND 6.0
4. SEE 9/S-101 FOR ENLARGED TYP. PLAN.
5. ALL VERTICAL FRAMING TO BE CONCEALED WITHIN
NEW WALLS.
6. T.O.S. ELEV ± 10'-3" AFF U.N.O.
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
DocuSign Envelope ID: D09F4E6C-1492-454D-8F93-8210CD7E622A
NOTES:
1.) WELD DECK TO SUPPORTS w/ 5_
" DIA. PUDDLE WELDS USING E60XX ELECTRODES.
2.) SIDELAP FASTENER @ 12" o.c. REQUIRED FOR EACH DECK SPAN. SIDELAP FASTENERS SHALL BE #10-16
SCREWS OR APPROVED ALTERNATIVE.
3.) MINIMUM DECK PROPERTIES
Ip = 0.222 in^4/ft Sp = 0.231 in^3/ft In = 0.186 in^4/ft Sn = 0.224 in^3/ft Va = 3322 plf Fy = 50 ksi
COVER
DECK TO SUPPORTS
(36/4 PATTERN)
3'-0"
1.5C 20 Ga. FLOOR DECK
SEE PLAN
COLUMN
4 x 10 x 1/2" (FOR HSS4 x 4) 3 x 10 x 1/2" (FOR HSS3 x 3)
BASE
3" 3"
7 7
S101 S101
S101 S101
S101
SEE PLAN
SEE PLAN
TYP
SEE PLAN
CONTINUOUS
4TH FLR ELEV
SEE PLAN
%%203
(TYP)
CAP %%220 %%208 x 3 x 0'-3
BEAM
COLUMN
SEE PLAN
BRACE
COLUMN
S
P A
C E
S
"o .c
'-0
SEE PLAN
H O
LE
S
1 _ 2"
1 _ 2"
SEE PLAN SEE PLAN
BOTT/BEAM
SEE PLAN
TOP PLATE
BOTT PLATE
TYP BEAM CONNECTION
w/ 2 ~ 3/4" DIA. BOLTS (A325N)
BEAM
COLUMN
BEAM
Ü Î x 3 x 1'-1" x 3/8"
4 x 6 x 1/4"
4 x 0'-5
SEE PLAN
BOTT/BEAM
SEE PLAN
SEE PLAN
TYP BEAM CONNECTION
w/ 2 ~ 3/4" DIA. (A325N)
BEAM
BEAM
4 x 0'-5
S101
S101
HSS 4
x
4HSS 3 x 3
HSS 3
x
HSS 4 x 4HSS 3 x
N O
T E
N
O T
E
N O
T E
NOTE 4
NOTE 4
NOTE 4
NOTE 4
NOTE 4
NOTE 4
W 8 x 18
W 8 x 18 H
S S x
W 8 x 18
W 8 x 18
W 8 x 18W 8 x 18
H S
S x
W x
L3 x 3 x 1/4
L3 x 3 x 1/4
C A
P A
C
IT
Y P
A T
IE
N
T L
IF
T
C A
P A
C
IT
Y P
A T
IE
N
T L
IF
T
EXISTING
NEW
NEW
NEW CONTINUOUS
ATTACH TO EXISTING SLAB
w/ %%208"%%221 HILTI HAS-V RODS
@ 12" o.c.
INSTALL USING HILTI HIT-HY200
ADHESIVE SYSTEM
DETAIL
OR APPROVED EQUAL
NOTES:
1.) FLOOR CONSTRUCTION TO BE 4" NORMAL WEIGHT CONCRETE ON GALVANIZED
NON-COMPOSITE METAL FLOOR DECK (4" TOTAL SLAB THICKNESS). SEE DETAIL
FOR ATTACHMENT.
(EMBED = 4%%208" MIN)
NOTE 1 SLAB
SLAB INFILL
DECKING
L 4 x 4 x %%204
4"
6 6 S101 S101
4TH FLR ELEV
'-9
'-3
NOTES:
1.) X-BRACE = PL 5/16 x 2" WIDE.
2.) MC = FIELD WELDED MOMENT CONNECTION. SEE DET 4.
3.) BOTT/BM ELEV = (+9'-4) AFF.
4.) 41/2" DIA WEB PENETRATIONS IN ALL W8 BEAMS. SEE DET 8.
5.) CONCEAL POSTS WITHIN INTERIOR WALL.
16' - 10"
(SEE FLOOR PLAN)
1'-6" or 0"
L3 x 3 x 1/4
W6 x 18
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:2
A
M
S-101
PATIENT LIFT SUPPORTS
2 2ED
IMPROVE PATIENT PRIVACY
4A
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249 5/26/2020
BID DOCUMENTS
652-19-10819-127
LCW
N
AREA OF WORK
FOURTH FLOOR
KEY PLAN
SCALE: NO SCALE
Scale: 1 1/2" = 1'-0"
DECK PROFILE
Scale: 3" = 1'-0"
BASE PLATE DETAIL
Scale: 1/2" = 1'-0"
ELEVATION @ HEADWALL
Scale: 6" = 1'-0"
COLUMN PENETRATION
Scale: 1 1/2" = 1'-0"
BEAM CONNECTION DETAIL
Scale: 1 1/2" = 1'-0"
BEAM CONNECTION DETAIL
Scale: 1/2" = 1'-0"
TYPICAL PATIENT RAIL SUPPORT PLAN
Scale: 1 1/2" = 1'-0"
SLAB INFILL DETAIL
Scale: 1/2" = 1'-0"
ELEVATION @ FOOTWALL (RIGID FRAME)
DocuSign Envelope ID: D09F4E6C-1492-454D-8F93-8210CD7E622A
AFF ABOVE FINISHED FLOOR
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CEM CEMENT(ITIOUS)
CMU CONCRETE MASONRY UNIT
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTR CENTER(ED)
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG(S) DRAWING(S)
E EAST
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EJ EXPANSION JOINT
EW EACH WAY
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EXIST EXISTING
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISH FLOOR ELEVATION
FV FIELD VERIFY
FEC FIRE EXTINGUISHER CABINET
FDN FOUNDATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FRP RESILIENT PANEL
FT FOOT/FEET
FTG FOOTING
GC GENERAL CONTRACTOR
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GYP GYPSUM
HM HOLLOW METAL
HDWR HARDWARE
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
IDPH ILLINOIS DEPARTMENT OF
PUBLIC HEALTH
ID INSIDE DIAMETER
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAV LAVATORY
LB(S) POUND(S)
L/S LANDSCAPE
LT LIGHT
LVT LUXURY VINYL TILE
MO MASONRY OPENING
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MGR MANAGER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NOM NOMINAL
OC ON CENTER
OD OUTSIDE DIAMETER
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PEB PRE-ENGINEERED BUILDING
PJF PREFORMED JOINT FILLER
PT PRESSURE TREATED
PERIM PERIMETER
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PTD PAINTED
PWR POWER
RB RUBBER BASE
RD ROOF DRAIN
RO ROUGH OPENING
RAD RADIUS
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RM ROOM
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET
SS STAINLESS STEEL
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
T&G TONGUE AND GROOVE
T/O TOP OF
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WWF WELDED WIRE FABRIC
WD WOOD
WH WATER HEATER
WT WEIGHT
CL
DEMOLITION KEYNOTE
WINDOW TYPE
TOILET ACCESSORY
WALL TYPE
ROOF PITCH SYMBOL
DOOR NUMBER
TYPICAL KEYNOTE CEILING/ SOFFIT
HEIGHT A.F.F.
MATL
1'-0"
-1
1. INDICATIONS OF PROJECT LIMITS OR LINES OF DEMARCATION ARE SHOWN FOR GENERAL SCOPE DEFINITION AND REFLECT THE UNDERSTANDING OF THE DESIGNER AS TO THE LIMITATIONS OF THE WORK AREA IN AN OCCUPIED AREA. ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY AGREEMENT BETWEEN THE COR AND
CONTRACTOR BEFORE THE START OF THE WORK.
2. DRAWINGS ARE PREPARED USING DIMENSIONS AND PRODUCT DRAWINGS FOR SPECIFIC PRODUCTS THAT
MAY CHANGE BEFORE THEY ARE INCORPORATED INTO THE WORK, AND PRODUCTS BY OTHER
MANUFACTURERS ARE ALSO ACCEPTABLE. THEREFORE, INSTALLATION DETAILS AND DIMENSIONS MAY DIFFER FROM THOSE SHOWN. CONTRACTOR SHALL VERIFY INSTALLATION REQUIREMENTS FOR ALL PRODUCTS TO BE INCORPORATED IN THE WORK (INCLUDING THICKNESS FOR RECESSED OR SEMI-RECESSED PRODUCTS) AND IS RESPONSIBLE FOR ACCOMMODATING AND COORDINATING CHANGES TO OTHER MATERIALS OR PRODUCTS
THAT ARE NECESSARY BECAUSE OF THESE DIFFERENCES.
3. THE DRAWINGS AND SPECIFICATIONS ARE SEPARATED INTO DISCIPLINES FOR CONVENIENCE. THE SEPARATIONS ARE USED ONLY FOR THE PURPOSES OF CONVENIENCE AND REFERENCE AND IN NO WAY DO THEY DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY PART OF THE DRAWINGS, OR OF THE DRAWINGS AND SPECIFICATIONS AS A WHOLE. THE FACT THAT THE DRAWINGS ARE SEPARATED IN NO WAY SUGGESTS THAT
THE WORK IS NOT TO BE CONSTRUCTED AS A COMPLETE, INTEGRATED AND UNIFIED WHOLE.
4. THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS PREPARED BY SPECIFIC ENGINEERING DISCIPLINES ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN THE DRAWINGS SHALL BE CONSIDERED TO BE REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION. IN THE EVENT OF AN INCONSISTENCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE CONTRACTOR SHALL SEEK CLARIFICATION OR INTERPRETATION FROM THE COR PRIOR TO BIDDING. WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO BIDDING, AND WHERE THE ACTUAL SOLUTION OR INTENT CANNOT BE REASONABLY INFERRED, THE CONTRACTOR SHALL PROVIDE THE BETTER QUALITY OR GREATER
QUANTITY OF WORK.
5. USE OF THE WORD "VERIFY" POINTS OUT A SITUATION WHICH MUST BE CONFIRMED PRIOR TO PROCEEDING WITH THE WORK, FABRICATION OF EQUIPMENT, OR ORDERING MATERIAL. NOTIFY THE COR OF ANY
DISCREPANCY DISCOVERED.
6. THE CONTRACTOR SHALL NOTIFY THE COR IMMEDIATELY SHOULD DISCREPANCIES BE FOUND IN THE
DRAWINGS AND SPECIFICATIONS.
7. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL FIELD CONDITIONS AND DIMENSIONS AS THEY RELATE TO THIS PROJECT. SHOULD DISCREPANCIES EXIST BETWEEN THE WORK INDICATED AND ACTUAL FIELD
CONDITIONS NOTIFY THE COR PRIOR TO PROCEEDING WITH THE WORK.
8. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR REFERENCE ONLY AND ARE NOT INTENDED TO ACCURATELY DEPICT ACTUAL OR DESIGNATED CONDITIONS. WRITTEN DIMENSIONS SHALL
GOVERN.
9. COORDINATE WORK OF ALL TRADES PRIOR TO STARTING CONSTRUCTION.
10. THE CONTRACTOR AND SUBCONTRACTORS INVOLVED IN THIS PROJECT SHALL BE RESPONSIBLE FOR DESIGNING AND INSTALLING THEIR RESPECTIVE WORK AND SYSTEMS TO MEET ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES, LAWS, SAFETY REGULATIONS, HAZARDOUS WASTE LAWS, ETC. THE CONTRACTOR
SHALL FURNISH ALL NECESSARY PERMITS.
11. THE CONTRACTOR SHALL REVIEW THE DRAWINGS AND UNDERSTAND THE SCOPE OF THE DRAWINGS TO BE THE FOLLOWING: THESE CONSTRUCTION DOCUMENTS (DRAWINGS, SPECIFICATIONS, ADDENDA, ETC.)
INDICATE THE GENERAL SCOPE OF THE PROJECT IN TERMS OF ARCHITECTURAL DESIGN CONCEPTS, THE DIMENSIONS OF THE BUILDING, THE MAJOR ARCHITECTURAL ELEMENTS, AND THE MAJOR STRUCTURAL, MECHANICAL, ELECTRICAL, AND DATA SYSTEMS. THE DOCUMENTS DO NOT AND ARE NOT INTENDED TO INDICATE OR DESCRIBE IN DETAIL ALL THE NECESSARY WORK REQUIRED FOR FULL PERFORMANCE OF, AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT. ON THE BASIS OF THE GENERAL SCOPE INDICATED IN THESE DOCUMENTS, THE TRADE CONTRACTORS SHALL FURNISH ALL ITEMS REQUIRED FOR THE PROPER EXECUTION AND COMPLETION OF THEIR WORK. ALL WORK SHALL BE COMPLETE IN EVERY DETAIL AND THE CONTRACTORS SHALL PROVIDE A ONE YEAR WARRANTY FOR THEIR WORK UNLESS A LONGER WARRANTY IS
INDICATED IN THE SPECIFICATIONS.
12. CONTRACTORS SHALL FOLLOW AND OBEY ALL FEDERAL, STATE AND LOCAL CODES, LAWS, SAFETY
REGULATIONS AND HAZARDOUS WASTE LAWS, ETC.
1. KEY NOTES AND DRAWINGS ARE INTENDED TO GRAPHICALLY REPRESENT
GENERAL WORK AND DO NOT PORTRAY FULL SCOPE OF THE PROJECT. SEE
SPECIFICATIONS FOR DETAILED REQUIREMENTS.
2. REMOVE EXISTING CONSTRUCTION AS DESIGNATED HEREIN AND CLEAR AREA
OF DEBRIS PRIOR TO PROCEEDING WITH NEW CONSTRUCTION.
3. EXISTING EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OFF MEDICAL
CENTER GROUNDS.
4. PATCH WALL OPENING SHALL MATCH THE INTEGRITY OF ADJACENT
CONSTRUCTION UNLESS INDICATED OTHERWISE.
5. NOTIFY COR OF ANY DEMOLITION REQUIRED AND NOT INDICATED FOR
INSTALLATION OF ELECTRICAL OR DATA ITEMS. AFTER SUCH DEMOLITION AND
INSTALLAT…