630-26-101 HVAC SPECIFICATIONS.pdf

PDF 3 MB Posted

Attached to
Y1DA--NRM-CONST 630-26-101 CONSTRUCTION ONCOLOGY PHARMACY CHILLER USP 800
Solicitation number
36C24226B0040
Issued by

About this file

This document collection comprises technical specifications, submittal data sheets, and equipment selections for an oncology pharmacy renovation project involving Daikin HVAC and refrigeration systems.

The primary component is a Technical Data Sheet for AC-1 (Humidifier), a Daikin Applied humidifier unit (Model CAH008GDAM) designed for the "Renovate Oncology Pharmacy" project (Job Number QAPN17, dated 12/11/2019). The unit supplies 2,400 cfm at 4.65 inWc total static pressure with external dimensions of 42" height × 44" width × 162" length. Key components include: a steam coil with 129,715 Btu/hr capacity, a chilled water coil with 116,796 Btu/hr total and 76,346 Btu/hr sensible capacity, combination filters (MERV 8 and MERV 13), internal mixing boxes with UltraSeal dampers, a supply fan with 5.0 HP motor and VFD control at 2,447 rpm, and AHRI-certified coil performance. The unit is ETL listed, utilizes R-13 foam insulation, and includes standard one-year parts warranty. Sound power data ranges from 46-85 dB across frequencies.

The secondary component is a Daikin WebXpress Selection project report for "South Oncology Pharmacy" (Project 625911/784401) specifying a VRV EMERION-B heat pump system (Model RXYA72AATJA, 6-ton, 230V, R32 refrigerant) paired with an AHU Integration Kit W-Control Box (EKEQFCBAV3-US), AHU Integration Valve Kit (EKEXV200-SK), Navigation Remote Controller (BRC1NRV71), and associated expansion valve kits. The outdoor unit operates at 208/230V 3-phase with 33.0 MCA and 35.0 MOP, producing 72,057 Btu/hr cooling capacity at 95°F ambient and 84,621 Btu/hr heating capacity at 47°F. The system includes BACnet interface capability (DMS502B71) for building automation integration, supporting up to 128 groups/256 indoor units and 20 outdoor units. A complementary DX cooling coil (Mainstream AHU AC-60) specifies 81.0 MBH total and 54.9 MBH sensible capacity with 3 rows, 12 fins per inch, R32 refrigerant charge, and 0.163 inWc air-side pressure drop at 2,400 cfm.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Technical Data Sheet for AC-1 (Humidifier)

Job Number: QAPN17 Page Prepared Date: 12/11/2019 Job Name: Renovate Oncology Pharmacy 1 of 15 www.DaikinApplied.com

Technical Data Sheet for A C-1 (H umidifier)

Job Information Technical Data Sheet

Job Name Renovate Oncology Pharmacy Date December 11 2019 Submitted By AB Software Version 11.90 Unit Tag AC-1 (Humidifier)

Unit Overview

Model Number

Supply Air Volume cfm Static Pressure External Dimensions

External inWc

Total inWc

Height in

Width in

Length in

CAH008GDAM 2400 2.00 4.65 42* 44* 162**

*Not including base rails, coil connectors, drain connectors and control boxes.

**Total lower deck length.

Unit Model Number: CAH008GDAM

Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label) Outer Panel: 24 gauge G90 Galvanized Steel (unpainted)

Liner: 24 gauge Galvanized Steel (unless noted per section) Insulation: R-13 Injected Foam

Unit Configuration: Stacked / vertical Drive (Handling) Location: Left Base: 4" formed channel Wall Thickness: 2 in

Shipping Stretch Wrap: Yes Altitude: 0 ft Parts Warranty: Standard One Year

Mixing Box Component: 1 Length: 20 in Shipping Section: 1 Portion Damper Rated CFM Air Pressure

Drop Quantity

Size (length x width) Location Type Overall Opening

Outside Air 16 in x 40 in 12 in x 30 in End UltraSeal Low Leak 2400 cfm 0.07 insWg 1

Return Air 16 in x 40 in 12 in x 30 in Top UltraSeal Low Leak 2400 cfm 1

Door Location Width Opening

Drive side 16 in Outward

Job Name: Renovate Oncology Pharmacy 2 of 15 www.DaikinApplied.com

Combination Filter Component: 2 Length: 16 in Shipping Section: 1 Access Face Velocity Face Area Air Volume Side 293 ft/min 8.2 ft² 2400 cfm

Portion Type Efficiency Air Pressure Drop Number of Filters

Height Width Depth Clean Air Mean Air Dirty Air

Pre-Filter Pleated MERV 8 0.11 inWc 0.56 inWc 1.00 inWc 2 24 in 20 in 2 in 1 12 in 24 in 2 in

Filter Pre Pleat MERV 13 0.10 inWc 0.55 inWc 1.00 inWc 2 24 in 20 in 4 in 1 12 in 24 in 4 in

Door

Drive side 12 in Outward

Internal Face and Bypass Component: 3 Length: 12 in Shipping Section: 1 Face Air Pressure Drop Bypass Air Pressure Drop Opening Location Type

0.02 inWc 0.51 inWc Internal Opposed blade - low leak Note: Cabinet height for bypass extended 0.00 inches above ‘External cabinet height’ referenced above.

Steam Coil Component: 4 Length: 24 in Shipping Section: 1 Coil Model Total Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing

(Face x Row) 5JA0701B 129715 Btu/hr 1 1 7 0.625 in 1.50 in x 1.299 in

Air Volume Air Temperature Coil Air Pressure Drop

Finned Height Finned Length Face Area Face Velocity Entering Leaving Dry Bulb Dry Bulb

2400 cfm 40.0 °F 89.4 °F 0.08 inWc 24 in 28 in 4.67 ft² 514 ft/min Fluid Max. Superheat Temp. in Steam Coil Inlet

Steam Pressure Condensate Load

15.00 psig 137.00 lb/hr 30.0 °F

Connection [Data Per Coil] Min. Fin Surface Temp. Min. Tube Wall Surface Temp. Type Size Location Material

Threaded 2.000 in Drive side Carbon steel 32.0 °F 32.0 °F Material

Fin Tube Header Case Aluminum .0075 in Copper .020 in Copper Galvanized track

AHRI 410 Certification

Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the

Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org Panel

Removable panels - in Outward

Access Section Component: 5 Length: 22 in Shipping Section: 1

Air Pressure Drop

0.00 inWc

Door

Drive side 18 in Outward

Job Name: Renovate Oncology Pharmacy 3 of 15 www.DaikinApplied.com

Chilled Water Coil Component: 6 Length: 28 in Shipping Section: 1 Coil Model Total Capacity Sensible Capacity Number of Coils Number of Rows Fins per Inch Tube Diameter Tube Spacing

(Face x Row) 5WH1008B 116796 Btu/hr 76346 Btu/hr 1 8 10 0.625 in 1.50 in x 1.299 in

Air Volume Air Temperature Coil Air Pressure

Drop

Finned Height

Finned Length

Face Area Face Velocity Entering Leaving

Dry Bulb Wet Bulb Dry Bulb Wet Bulb 2400 cfm 80.0 °F 67.0 °F 50.9 °F 50.7 °F 0.54 inWc 33 in 31 in 7.10 ft² 338 ft/min

Water Flow Rate Pressure Drop Velocity Volume Weight Entering Leaving

45.0 °F 54.9 °F 23.50 gpm 5.00 ftHd 2.30 ft/s 8.0 gal 71.00 lb

Connection [Data Per Coil] Min. Fin Surface Temp.

Min. Tube Wall Surface Temp.

Fouling Factor Type Size Location Material

Threaded 1.50 in Drive side Carbon steel 45.0 °F 45.0 °F 0.000 Material Drain Pan Drain Side

Fin Tube Header Case Aluminum .0075 in Copper .020 in Copper Galv. steel Stainless steel Drive side

AHRI 410 Certification Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org

Future Chilled Water Coil Component: 7 Length: 40 in Shipping Section: 2 Number of Coils Number of Rows

1 4 Coil Air Pressure Drop Finned Height Finned Width Face Area Face Velocity

0.30 inWc 33 in 31 in 7.10 ft² 338 ft/min Connection Location Connection Material

Drive side Carbon steel Coil Model Drain Pan Drain Pan Side

Future Coil (Not Supplied) Stainless steel Drive side AHRI 410 Certification

Coil is NOT certified by AHRI Door

Location Width Opening Drive side 26 in Outward

Special Options Special Text

A "future" cooling coil section with a minimum length of 36" must be chosen for mounting humidifier grid into.

NOTE: Price includes internal mounting of header, steam tubes, mounting frame, and inlet adapter.

Accessories including valve, strainer, trap, actuator, etc. will be shipped loose for field installation.

Access Section Component: 8 Length: 24 in Shipping Section: 3 Air Pressure Drop

0.00 inWc Door

Drive side 20 in Outward

Job Name: Renovate Oncology Pharmacy 4 of 15 www.DaikinApplied.com

Supply Fan Component: 9 Length: 32 in Shipping Section: 3 Fan Performance

Air Volume Static Pressure Brake Horsepower Speed Outlet Velocity External Total Cabinet Operating Maximum

2400 cfm 2.00 inWc 4.65 inWc 0.13 inWc 3.51 BHP 2447 rpm 2896 rpm 2474 ft/min Fan Data

Fan Type Blade Type / Class Quantity of Fans Wheel Diameter Number of Blades Discharge Motor Location Centrifugal DWDI Forward Curved /

1 9.50 in N/A Up blast CW To Side of Fan

Motor Data Power Electrical

Supply Speed Efficiency Enclosure Frame Size Supplier Number of

Poles Lock Rotor

Current Full Load Current

5.0 HP 200/60/3

V/Hz/Phase

1750 rpm Premium ODP 184 T frame Generic 4 122.70 A 15.30 A

Fan Options Isolator Type: Rubber in shear

Drive Package Data* Fan Sheave Motor Sheave Belt Number of Belts Actual Drive S.F. Bearing Type

AK51H AK69H A31 1 1.12 Standard - L50 (200K) *Daikin Applied reserves the right to provide a different but equivalent drive package

VFD/Starter/Disconnect Data Selection Type: VFD Vendor: Daikin Applied

Voltage: 200 V Height x Width x Depth: 11.78 in x 6.63 in x 7.80 in Mounting: Door Side Enclosure: NEMA 1

VFD Quantity: 1 Door

Drive side 20 in Outward

Unit Sound Power (dB)

Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Radiated: 75 75 64 60 59 54 46 51

Unit Discharge: 85 85 82 81 81 82 79 76 Unit Return: 75 75 64 60 59 55 46 51

Job Name: Renovate Oncology Pharmacy 5 of 15 www.DaikinApplied.com

Shipping Section Details Section Length in Weight lb Corner Weights (lb) Center of Gravity (in)

P1 P2 P3 P4 XX YY ZZ

1 122 1241 258 278 362 342 69 23 22 2 40 361 88 88 93 93 21 22 19 3 56 488 114 94 130 149 32 20 22

Entire Unit 162 Lower level only

2090 n/a n/a n/a n/a n/a n/a n/a

NOTE: Special components aren't included in the corner weights and center of gravity data.

AHRI Certification

Supply fan performance is certified in accordance with the Central Station Air-Handling Unit Certification Program, which is based on AHRI Standard 430.

Notes Standard

1. As a standalone component, unit meets or exceeds requirements of ASHRAE 90.1 - 2007. The approving authority is responsible for compliance of multi - component building systems.

Fan Curve for AC-1 (Humidifier)

Job Name: Renovate Oncology Pharmacy 6 of 15 www.DaikinApplied.com

Fan Curve for A C-1 (H umidifier)

400 rpm 600 rpm 800 rpm 1000 rpm

1200 rpm

1400 rpm

1600 rpm

1800 rpm

2000 rpm

2200 rpm

2400 rpm

2600 rpm 2800 rpm 3000 rpm

1 bhp

1.5 bhp 2 bhp 3 bhp 5 bhp

7.5 bhp

10 bhp

15 bhp 0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

STATIC

PR

ESSU

R

E (IN

. O

F W

ATER

0.0

2.0

4.0

6.0

CFM (IN 1,000's) 9X9 Forward Curved Supply Fan at Standard Conditions

Daikin AHU Fan Curve

Air volume 2400 cfm Total static 4.65 insWg Brake horsepower 3.5 bhp

Fan speed 2447 rpm Max speed 2896 rpm Efficiency 50.0 %

Unit tagging AC-1 (Humidifier) Job name Renovate Oncology Pharmacy

Date December-11-2019 Time 17:53

Supply fan performance is certified in accordance with the Central Station Air-Handling Unit Certification Program, which is based on AHRI Standard 430.

Job Name:

Job Number:

Drawing for AC-1 (Humidifier)

Renovate Oncology Pharmacy

QAPN17

Page

Prepared Date:

www.DaikinApplied.com 12/11/2019

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 1

WebXpress Selection Project Report

Report details Produced on: 11/5/2025

Application version: 2025.11.4.2

Project details Project name: South Oncology Pharmacy

Solution name: Unnamed solution (1)

Client Name:

Customer reference:

Quotation reference:

Project number: 625911/784401

Selection parameters of the indoor units can be found in the Engineering Data Books.

Selection parameters of the outdoor units can be found in the Engineering Data Books.

Only the data published in the data book are correct. This program uses close approximations of these data.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 2

Material list Model Quantity Description

RXYA72AATJA 1 VRV EMERION-B-(208-230V) (VRV EMERION (208-

230V))

EKEXV200-SK 1 AHU INTEGRATION VALVE KIT

BRC1NRV71 1 Navigation Remote Controller EKEQFCBAV3-US 1 AHU Kit W-Control box

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 3

Indoor unit details Table of abbreviations

Abbreviation Description Name Logical name of the device FCU Device model name Tmp C Indoor conditions in cooling Rq TC Required total cooling capacity Rv TC Revised total cooling capacity (asked from outdoor) Max TC Available total cooling capacity Rq SC Required sensible cooling capacity Tevap Evaporating temperature of indoor unit coil Tdis C Indoor unit discharge air temperature in cooling based on maximum capacities Max SC Available sensible cooling capacity Tmp H Indoor temperature in heating Rq HC Required heating capacity Max HC Available heating capacity Tdis H Indoor unit discharge air temperature in heating based on maximum capacities Sound Sound pressure level low and high PS Power supply (voltage and phases) MCA Minimum Circuit Amps MOP Maximum Overcurrent Protection WxHxD WidthxHeightxDepth Weight Weight of the device Air Flow Rate Air Flow Rate Mrel Maximum Refrigerant Amount that can be released. Equals the total refrigerant charge in the system when there are no shut-off valves.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 4

CU- 1 - RXYA72AATJA

Capacity data at conditions and connection ratio (94) as entered

Name FCU Cooling Tmp C Rq TC Rv TC Max TC Rq SC Tevap Tdis C Max SC

°F

(DBT/WBT)

BTU/h BTU/h BTU/h BTU/h °F °F BTU/h

AHU 1 box 1 EKEXV200-SK n/a 72,000 n/a 83,939 n/a 42.8 n/a n/a

Name FCU Heating Tmp H Rq HC Max HC Tdis H Min coil Max coil Air Flow Rate

°F BTU/h BTU/h °F in³ in³ cfm AHU 1 box 1 EKEXV200-SK n/a n/a n/a n/a n/a n/a n/a

Name FCU Room Sound PS MCA MOP WxHxD Weight dBA A inch lbs

AHU 1 box 1 EKEXV200-SK - 12 1ph 8.5 x 15.8 x 3.1 6.4

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 5

Outdoor unit details Table of abbreviations

Abbreviation Description Name Logical name of the device Model Device model name CR Connection ratio Tmp C Outdoor conditions in cooling WFR per module Water flow per outdoor unit module CC Available cooling capacity Rq CC Required cooling capacity PIC Power input in cooling mode InC Water inlet temperature in cooling mode OutC Water outlet temperature in cooling mode Tmp H Outdoor conditions in heating (dry bulb temp. / RH) HC Available heating capacity (integrated heating capacity) Rq HC Required heating capacity PIH Power input in heating mode InH Water inlet temperature in heating mode OutH Water outlet temperature in heating mode Piping Largest distance from indoor unit to outdoor unit Bse Refr Standard factory refrigerant charge (16.4ft actual piping length) excluding extra refrigerant charge. For calculation of extra refrigerant charge refer to the databook Ex Refr Extra refrigerant charge PS Power supply (voltage and phases) MCA Minimum Circuit Amps MOP Maximum Overcurrent Protection FLA Fan Motor Input FCIDI Fan Compressor Inverter Drive Input RLA Nominal Running Amps WxHxD WidthxHeightxDepth Weight Weight of the device EER EER value at nominal condition EER2 EER2 value at nominal condition IEER IEER value at nominal condition COP47 COP value at nominal condition and at ambient temperature of 47°F COP17 COP value at nominal condition and at ambient temperature of 17°F

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 6

Outdoor details

Name Model CR Cooling Heating Piping Tmp C CC Rq CC Tmp H HC Rq HC

% °F BTU/h BTU/h °F

(DBT/WBT)

BTU/h BTU/h ft

CU- 1 RXYA72AATJA 94.2 95.0 72,057 72,000 47.0/46.0 84,621 24.6

Name Model PS MCA MOP RLA WxHxD Weight A A A inch lbs

CU- 1 RXYA72AATJA 208V - 230V

3ph

33.0 35.0 11.1 36.6 x 65.4 x 30.1 549

Name Efficiency Metrics - Non Ducted

EER EER2 IEER COP47 COP17 SCHE SEER SEER2 HSPF HSPF2

CU- 1 12.5 23.2 3.64 2.4

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 7

Sound Data

Name Model Sound Power Sound Pressure

Cooling Heating Cooling Heating dBA dBA dBA dBA

CU- 1 RXYA72AATJA - - 58 -

Refrigerant information

Name Model Refrigerant type GWP Base charge lbs

Extra charge lbs

Total refrigerant charge lbs

Total CO2 equivalent tonnes

CU- 1 RXYA72AATJA R32 2087.5 13.9 unknown unknown 14.40 The system(s) contain fluorinated greenhouse gases.

When extra refrigerant charge requirements are not calculated, TCO2 equivalent is calculated only considering the base refrigerant charge. Depending on the field pipe length extra refrigerant needs to be added which will increase the TCO2 equivalent.

For some outdoor units, piping lengths were not entered manually causing the determination of refrigerant amounts to be inaccurate.

CU- 1 - RXYA72AATJA

Model Quantity Description

RXYA72AATJA 1 VRV EMERION-B-(208-230V) (VRV EMERION (208-230V))

EKEXV200-SK 1 AHU INTEGRATION VALVE KIT

BRC1NRV71 1 Navigation Remote Controller EKEQFCBAV3-US 1 AHU Kit W-Control box

Refrigerant information

Refrigerant type GWP Base charge lbs

Extra charge lbs

Total refrigerant charge lbs

Total CO2 equivalent tonnes R32 2087.5 15.21 unknown unknown 14.40

The system(s) contain fluorinated greenhouse gases.

When extra refrigerant charge requirements are not calculated, TCO2 equivalent is calculated only considering the base refrigerant charge. Depending on the field pipe length extra refrigerant needs to be added which will increase the TCO2 equivalent.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 8

Piping lengths were not entered manually causing the determination of refrigerant amounts to be inaccurate.

Pipe capacities

Maximum Connection Index Diameters

53.9 3/8"x5/8"

71.9 3/8"x3/4"

110.9 3/8"x7/8"

161.9 1/2"x1 1/8"

229.9 5/8"x1 1/8"

299.9 3/4"x1 3/8" > 299.9 3/4"x1 5/8" Main pipe size up 1/2"x7/8"

Piping limitations

Description Value Maximum total length 3,280.8ft Maximum longest actual length 541.3ft Maximum longest equivalent length 623.4ft Maximum main pipe length (size up of main pipe required if longer) - Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 131.2ft Maximum length first branch to indoor unit 295.3ft Maximum length of indoor units to nearest branch 131.2ft Maximum length difference between longest and shortest distance to indoor units 131.2ft Maximum height difference, outdoor unit below indoor units 295.3ft Minimum connection ratio, outdoor unit below indoor units - Maximum height difference, outdoor unit above indoor units 295.3ft Minimum connection ratio, outdoor unit above indoor units - Maximum height difference in low ambient cooling, outdoor unit below indoor units 295.3ft Maximum height difference in low ambient cooling, outdoor unit above indoor units 295.3ft Maximum height difference between indoor units 131.2ft Connection ratio range 50.0% - 200.0% Refrigerant pipe diameters 1/2" (liquid) x 7/8" (gas) Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate pipes required if longer)

Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 295.3ft Maximum actual length between CM and HM - Maximum height difference between CM and HM -

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 10

Piping diagrams Piping CU- 1

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter might be required.

CU- 1

RXYA72AATJA

AHU 1 box 1

EKEXV200-SK

AHU 1

3/8 x 3/4 "

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 11

Wiring diagrams Wiring CU- 1

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT = AWG 18-2 is required - however always refer to local code for further information

Note:

RXYQ72AATJB

IN F1,F2

CU- 1

RXYQ72AATJB L1, L2, L3 27.3A 3ph

EKEQFCBAV3-US

P1,P2

Y1Y6

F1,F2

L1, L2 1ph

BRC1NRV71

1(*) AHU 1

AHU 1 box 1

EKEXV200-SK

6 x 0.75

Low ambient cooling operation down to -4° F (-20° C) with a field setting and the addition of wind covers onto the outdoor unit Expanded Heating operation down to -22°F as standard New improved D4 net provides faster communication speeds and larger data volume compared to the D3 net up to 30 times the amount of data compared to D3 net Reduced install and commissioning time through auto addressing feature with D4 communications protocol R-32 system with lower Global Warming Potential (GWP), provides improved efficiency compared to R410A and requires lower total system charge Increased energy savings through new improved VRT technology with evaporation temperature control at each indoor unit (SSOV required) New remote field setting option that allows data retrieval and field setting changes of units on the system from anywhere, without the need for physical access to each room Seven segment display to read refrigerant temperatures and pressure on digital display Vertical separation up to 361 FT with field setting New field setting that allows reuse of R410Aa piping network for new R32 system, eliminating need to replace for retrofit applications Hot gas defrost circuit allows for installation without base pan heater High dust moisture protection with an IP55 rated sealed E-box Design flexibility to enlarge system from single to a dual-module without changes to installed main pipe sizes for phased installation or tenant fit-out buildings Engineered for ease of installation and service with three-segment panel design Ease of field piping connections to service valves Built-in data recorder to store up to 45 minutes of operational data Integrates with new Daikin HERO ecosystem, an IoT -based remote monitoring and diagnostics platform Extend benefits of inverter technology to custom terminal units and AHUs through AHU integration kits

Submittal Data Sheet 6 Ton, 230V R32 EMERION HP

RXYA72AATJA

FEATURES

Daikin North America LLC, 19001 Kermier Rd, Waller, TX 77484 Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

Submittal Date: 08/25/2025 Page 1 of 3

Submittal Data Sheet 6 Ton, 230V R32 EMERION HP

RXYA72AATJA

PERFORMANCE

Outdoor Unit Model No. RXYA72AATJA Outdoor Unit Name: 6 Ton, 230V R32 EMERION HP

Type: Heat Pump

Rated Cooling Conditions: Indoor (°F DB/WB): 80 / 67 Ambient (°F DB/WB): 95 / 75

Rated Heating Conditions: Indoor (°F DB/WB): 70 / 60 Ambient (°F DB/WB): 47 / 43

OUTDOOR UNIT DETAILS

Power Supply (V/Hz/Ph): 208/230 / 60 / 3 Compressor Stage:

Power Supply Connections: L1, L2, L3 GROUND Capacity Control Range (%): 8 - 100

Min. Circuit Amps MCA (A): 33.0

Max Overcurrent Protection (MOP) (A): 35

Airflow Rate (H) (CFM): 6210

Gas Pipe Connection (inch): 3/4

Rated Load Amps RLA(A): 11.1 Liquid Pipe Connection (inch): 3/8

Dimensions (Height) (in): 65-3/8

Dimensions (Width) (in): 36-5/8

Dimensions (Depth) (in): 30-1/8

Sound Pressure (H) (dBA): 58

Net Weight (lb): 549

Sound Power Level (dBA): 80

INVERTER

Daikin North America LLC, 19001 Kermier Rd, Waller, TX 77484 Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

Submittal Date: 08/25/2025 Page 2 of 3

6 Ton, 230V R32 EMERION HP

RXYA72AATJA

SYSTEM DETAILS

Refrigerant Type: R-32 Cooling Operation Range (°F DB): 23 - 122

Holding Refrigerant Charge (lbs): 13.9 Heating Operation Range (°F WB): -22 - 60

Additional Charge (oz/ft): Max. Pipe Length (Vertical) (ft): 361

Cooling Range w/Baffle (°F DB): -4 - 122Max. Pipe Length (Total) (ft): 3,280

Max Height Separation (Ind to Ind ft):

DIMENSIONAL DRAWING

Check install manual or selection tool

Daikin North America LLC, 19001 Kermier Rd, Waller, TX 77484 Daikin City Generated Submittal Data www.daikinac.com www.daikincomfort.com

(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

Submittal Date: 08/25/2025 Page 3 of 3

AHU Integration Kit – W-Control Box

EKEQFCBAV3-US

Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056 www.daikinac.com www.daikincomfort.com

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations

DESCRIPTION

Allows for connection and control of non-VRV air handling equipment to Daikin VRV condensing units.

EKEQFCBAV3-US controls the EKEXV_-US expansion valve kit based on input from field-provided 0-10V DC signal (W-control). Each EKEQFCBAV3-US can be paired with one EKEXV expansion valve kit.

FEATURES

• Ideal for discharge air temperature control applications

• Support for extended on-coil air temperatures suitable for ventilation applications

• Compatible with Heat Pump VRV systems

• For 1-to-1 VRV-to-AHU system design

• Weather resistant enclosure suitable for outdoor installation

• Requires field provided 0-10V DC control input

• Centralized control capability via Itouch Manager (DCM601A71)

Model No. EKEQFCBAV3-US

Control Type W-Control

Power Supply 208-230VAC / 1Φ / 60 Hz

Height (in.) 5 - 13/64"

Width (in.) 15 - 3/4"

Depth (in.) 9 - 3/8"

Weight (lb.) 8.0 lb

Casing Material Carton / EPS / Plastic

Design Ambient Temperature 14°F - 104°F

Certifications UL1995

SPECIFICATIONS

VRV IV (RXYQ_TA*) ✓

VRV IV (RXYQ_T*) ✓

VRV Aurora (RXLQ_TA*) ✓

VRV T Series (RWEQ_TA*) ✓

VRV- WIV (RWEYQ_PC*) ✓

VRV-IVS (RXTQ_TA) ✓

*All voltages are compatible

**All heat pump voltages are compatible

VRV HEAT PUMP COMPATIBILITY

Note: W-control connection with heat recovery systems is not supported http://www.daikinac.com/ http://www.daikincomfort.com/

EKEQFCBAV3-US

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this

EKEQFCBAV3-US

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this

Daikin VRV condensing units.

EKEQFCBAV3-US controls the EKEXV_-US expansion valve kit based

• Support for extended on-coil air temperatures suitable for ventilation applications

• Compatible with Heat Pump VRV systems

• For 1-to-1 VRV-to-AHU system design

• Weather resistant enclosure suitable for outdoor installation

Power Supply 208-230VAC / 1Φ / 60 Hz

Height (in.) 5 - 13/64"

Width (in.) 15 - 3/4"

Depth (in.) 9 - 3/8"

Weight (lb.) 8.0 lb

Casing Material Carton / EPS / Plastic

Design Ambient Temperature 14°F - 104°F

Certifications UL1995

SPECIFICATIONS

VRV IV (RXYQ_TA*) ✓

VRV IV (RXYQ_T*) ✓

VRV Aurora (RXLQ_TA*) ✓

VRV T Series (RWEQ_TA*) ✓

VRV- WIV (RWEYQ_PC*) ✓

VRV-IVS (RXTQ_TA) ✓

*All voltages are compatible

**All heat pump voltages are compatible

VRV HEAT PUMP COMPATIBILITY

Note: W-control connection with heat recovery systems is not supported

EKEQFCBAV3-US

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this

EKEQFCBAV3-US

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this

Daikin VRV condensing units.

EKEQFCBAV3-US controls the EKEXV_-US expansion valve kit based

• Support for extended on-coil air temperatures suitable for ventilation applications

• Compatible with Heat Pump VRV systems

• For 1-to-1 VRV-to-AHU system design

• Weather resistant enclosure suitable for outdoor installation

Power Supply 208-230VAC / 1Φ / 60 Hz

Height (in.) 5 - 13/64"

Width (in.) 15 - 3/4"

Depth (in.) 9 - 3/8"

Weight (lb.) 8.0 lb

Casing Material Carton / EPS / Plastic

Design Ambient Temperature 14°F - 104°F

Certifications UL1995

SPECIFICATIONS

VRV IV (RXYQ_TA*) ✓

VRV IV (RXYQ_T*) ✓

VRV Aurora (RXLQ_TA*) ✓

VRV T Series (RWEQ_TA*) ✓

VRV- WIV (RWEYQ_PC*) ✓

VRV-IVS (RXTQ_TA) ✓

*All voltages are compatible

**All heat pump voltages are compatible

VRV HEAT PUMP COMPATIBILITY

Note: W-control connection with heat recovery systems is not supported

EKEQFCBAV3-US

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this

Model No. EKEXV140-SK EKEXV200-SK EKEXV250-SK EKEXV400-SK EKEXV500-SK

Nominal Capacity (MBh) 60 72 96 144 192

Liquid Pipe Connection* 3/8" 3/8" 3/8" 1/2" 5/8"

Gas Pipe Connection 5/8" 3/4" 7/8" 1-1/8" 1-1/8"

Power Supply

Model No. EKEXV50-SK EKEXV63-SK EKEXV80-SK EKEXV100-SK EKEXV125-SK

Nominal Capacity (MBh) 18 24 30 36 48

Liquid Pipe Connection* 1/4" 3/8" 3/8" 3/8" 3/8"

Gas Pipe Connection 1/2" 5/8" 5/8" 5/8" 5/8"

Power Supply 12V DC from EKEQ box

12V DC from EKEQ box

SPECIFICATIONS

SPECIFICATIONS

AHU Integration Kit – Expansion Valve

EKEXV***-SK

Allows for connection and control of non-VRV air handling equipment to Daikin VRV condensing units.

EKEXV***-SK operates in conjunction with EKEQ Control Kits.

• Electronic expansion valve capable of 2000 steps

• 18 MBH to 192 MBH individual coil capacity capability

• Suitable for indoor and outdoor installation

Project Name:

Location: Approval:

Engineer: Date:

Submitted to: Construction:

Submitted by: Unit #:

Reference: Drawing #:

Daikin Comfort Technologies North America LLC, 19001 Kermier Road, Waller TX 77484 www.daikinac.com www.daikincity.com

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

BRC1NRV71 – Navigation Remote Controller

MODEL COMPATIBILITY:

Compatible with R-32 VRV Indoor units: FXTA, FXFA, FXMA, FXSA Compatible with VRV and VRV LifeTM indoor unit models: FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXMQ_MF, FXNQ, FXSQ, FXTQ, FXUQ, FXZQ, VAM, CXTQ

Compatible with SkyAir indoor unit models: FAQ, FBQ, FCQ, FHQ, FTQ Compatible with Single and Multi-zone system indoor unit model: FFQ, FDMQ

SPECIFICATIONS: PRODUCT IMAGE:

FEATURES:

1. Up to 16 indoor units are controllable within one group

2. Within one group, up to 2 Navigation Remote Controllers can be used, one as a main and one as a sub

3. Backlit LCD displays in English, Spanish or French

4. Temperature sensor built-in with configurable offset

5. Display of Temperature and Setpoint in 1°F / °C increments

6. Three configurable display options: Detailed, Standard and Simple

7. Dual setpoints (independent cooling and heating setpoints) with configurable minimum setpoint differential or Single

Setpoint (occupied period)

Model BRC1NRV71

Description Navigation Remote Controller

Maximum Connections 16 indoor units

Communication Wire 18AWG-2, No polarity Stranded, Non-shielded

Total Wiring Length 1,640 ft. (500 m)

Communication Protocol

Daikin proprietary P1P2 protocol

Power 16VDC supplied by indoor unit (1.58VA maximum)

Comfort Setpoint Range 60 to 90 °F (16 to 32 °C)

Setback Setpoint Range 40 to 95 °F (5 to 35°C)

Operating Temp Range 14 to 122°F (-10 to 50°C)

Operating Humidity Range

75% or less (RH) (without condensation)

Dimensions (WxHxD) 4.72x4.72x0.75 inch (120x120x19 mm)

Weight (Mass) 0.42 lbs. (0.19 kg) Notes:

(1) 1 of 3 display options – Detailed display shown

(2) http://www.daikincity.com/

Engineer: Date:

Submitted to: Construction:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

8. Setpoint range limit for cooling and heating modes

9. Independent cooling and heating setback setpoints (unoccupied period)

10. Auto changeover control with configurable primary and secondary changeover dead bands and guard timer

11. Airflow – Individual air flow direction, dual airflow and auto draft prevention (prevents air blowing directly on occupants)*

12. Built-in 7 days, weekdays+weekend, weekdays+Sat+Sun, and Everyday schedules with up to 5 actions per day with independent cooling and heating or setback setpoints

13. Automatic Setback by occupancy sensor*

14. Automatic Off by occupancy sensor*

15. Configuration for Self-cleaning filter panel*

16. Automatic adjustment for Daylight Savings Time (DST)

17. 48 hour clock/calendar battery backup (protects schedule timing in cases of short term power loss from indoor unit)

18. Real-time monitoring of system malfunctions with immediate display of unit in error and error code

19. The buttons on the remote controller are selectable by locking out the unwanted buttons

20. The operation modes can be restricted to provide only the desired mode(s) of operation

21. Display can be configured to show “Off” and room temperature only when indoor unit is turned off

22. To prevent unwanted changes, fan speed selection and display may be hidden

23. Override timer configurable in 10 minute increments (range 30-10 hours)

24. Enhanced error monitoring for R32 VRV Indoor units

25. Supports new addressing scheme of DIV-NET

*Requires support by indoor unit.

SYSTEM DIAGRAM:

Multiple indoor units group control

Main Sub 2 controllers used for single group control Stand-alone group control

Up to 16 indoor units

P1P2

DIII-Net

Engineer: Date:

Submitted to: Construction:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

FACE DECAL OPTIONS:

Face decal options are used to hide unnecessary buttons:

1. The face decal is designed to adhere to the faceplate

2. Hidden buttons can be accessed by service personnel without removing the face decal due to its flexibility

DIMENSIONS:

4-3/4”

4-3/4” ¾””

Engineer: Date:

Submitted to: Construction:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

DOCUMENTATION:

Documentation available on www.daikincity.com and/or www.daikinac.com:

• Installation Manual

• Operation Manual

• Submittal

• Guide Specifications

Engineer: Date:

Submitted to: Construction:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

DMS502B71 – Interface for use in BACnet

MODEL COMPATIBILITY:

Compatible with VRV and VRV Life

TM

indoor unit models: FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXMQ_MF, FXNQ, FXSQ, FXTQ, FXUQ, FXZQ, CXTQ, VAM

Compatible with SkyAir indoor unit models: FAQ, FBQ, FCQ, FHQ, FTQ Compatible with Single Zone/Multi Zone/SkyAir system indoor unit models:

FDMQ, FFQ_Q

FFQ_LVJU with the use of the Interface Adaptor DTA112BA51

FTXS, CTXS, CTXG, FTXG, FDXS, CDXS, FVXS with the use of the DIII-Net Adapter KRP928BB2S

FTX, FTXN, FTK, and FTKN with the use of the DIII-Net Adapter KRP928BB2S and an Interface adaptor

KRP067A41E/KRP980B1/KRP980B2E

SPECIFICATIONS: PRODUCT IMAGE:

Model DMS502B71

Description BACnet Interface

Maximum Indoor Units 128 groups/256 indoor units (256 groups/512 indoor units with

DAM411B51)

Maximum Outdoor Units 20 (40 with DAM411B51)

DIII-Net Communication Wire

18AWG-2, No polarity Stranded, Non-shielded

BACnet IP Communication Wiring

10Base-T/100Base-TX

Communication Protocol

Daikin Proprietary DIII-Net protocol / BACnet IP

IP Setting Range Class C network

Power 24VAC (field supplied) (40VA maximum)

Comfort Setpoint Range 60 to 90 °F (16 to 32 °C)

Setpoint Single Setpoint

Temperature Units Degrees Fahrenheit or Celsius

Operating Temp Range 14 to 122°F (-10 to 50°C)

Operating Humidity Range

90% or less (RH) (w/o condensation)

Dimensions (WxHxD)

10.81 x 10.34 x 2.69 inch (274.57 x 262.13 x 68.33 mm)

Weight (Mass) 6.2 lbs. (2.8 kg)

Certification FCC Part 15 Subpart B Class A

Notes:

Image shows BACnet Interface (DMS502B71) with Optional DIII Board (DAM411B51) inserted

Engineer: Date:

Submitted to: Construction:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

OPTIONS:

Option DIII Board DAM411B51 can be applied to add two additional DIII-Net ports to the BACnet Interface

FEATURES:

Integrate Daikin VRV, SkyAir, Single and Multi-zone systems with third party building automation systems supporting the BACnet protocol

BACnet Application Specific Controller (B-ASC) device profile compatible with BACnet (ANSI / ASHRAE-135)

BACnet IP Data Link Layer (Annex J)

Supports COV – Change of Value, Property Array Index and Segmented requests

IPv4 and Foreign Device registration for use with BACnet Broadcast Management Devices (BBMD)

BTL listed (operating system version 6.2 and later)

Diagnostic LEDs

2 Alarm Output contacts DO-1 and DO-2

4 Digital Inputs for Forced Off function

The following programing is required from BMS:

o Auto-changeover o Setpoint Range Limitation o Setback o Scheduling o Dual Setpoints

SYSTEM DIAGRAM:

Engineer: Date:

Submitted to: Construction:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

INDOOR UNIT MONITORING AND CONTROL POINTS:

Check the appropriate box indicating the required integrated points for this project.

Function Description

O p e ra ti o n c o n fi g u ra ti o n a n d m o n it o ri n g

On/Off (Note2) Start / stops the indoor unit and monitors the latest status

Operation Mode (Note 2) Sets the cool / Heat / Fan/ Dry mode for the indoor unit and monitors the latest mode

Setpoint setting (Note 2) Sets the setpoint of the indoor unit and monitors the latest setpoint.

Filter sign and reset Monitors filter run time, provides service alert, and allows a manual reset of the status as required.

Remote controller permit/prohibit Permits or prohibits the remote controller so that it can or cannot be used to control the indoor unit’s On/Off/Operation mode/Setpoint

Lower Centralized Controller operation enable/disable

Enables or disables operation of a Centralized Controller connected to the DIII network.

Fan Speed setting (Note 2) Sets the fan speed and monitors the latest setting.

Airflow direction setting (Note 2) Sets the airflow direction and monitors the latest setting.

Forced system stop The forced system stop command will force the indoor units to stop running based upon a received emergency alarm input. Remote controllers will be locked out from restarting indoor units during a forced system stop event.

Forced Thermo-off In response to the forced thermo-off command, the indoor unit stops actively cooling or heating.

Energy saving Offsets the internal setpoint +3.6 F (2

C) in cooling, and -3.6

F (-2

C) in heating in an indoor unit. The actual setpoint is not changed.

Ventilation mode setting (Note 2) Sets the ventilation mode and monitors the latest mode.

Ventilation amount setting (Note 2)

Sets the ventilation amount and monitors the latest amount.

M o n it o ri n g

On/Off status Monitors the On/Off status of the indoor unit.

Alarm Monitors whether or not the indoor unit is operating normally, and issues an alarm if the indoor unit has a malfunction.

Malfunction code Displays a malfunction code specified by Daikin if an indoor unit in the system has a malfunction.

Operation mode Monitors if the indoor unit is in Cool, Heat, Fan, or Dry mode.

Room temperature (Note 1) Monitors the room temperature.

Filter sign Monitors filter run time and provides service alert.

Thermo-on status Monitors whether or not the indoor unit is in actively cooling or heating.

Compressor status Monitors if the compressor of the outdoor unit connected to the indoor unit is properly operating.

Indoor fan status Monitors if the indoor unit's fan is properly operating.

Heater status Monitors if the indoor unit's heater is properly operating.

Ventilation mode status Monitors the ventilation mode status of the Energy Recover Ventilator

Ventilation amount status Monitors the ventilation amount status of the Energy Recovery Ventilator

1. Room temperature data (BACnet object name RoomTemp_XXX) by default is reported from the Daikin indoor units return air thermistor.

This applies to all VRV indoor unit styles and capacities. During periods when the indoor unit is turned off or during certain operating modes that cycle the fan off including defrost operation, hot-start and system pressure equalization, the reported temperature may not accurately reflect the actual space temperature. For applications where this temperature value will be primary to system control including mode and

Engineer: Date:

Submitted to: Construction:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) temperature setpoint management, it is recommended that the Daikin remote temperature sensor (Part No. KRCS01-1B or 4B depending on model) is specified for each indoor unit and installed within the occupied space or unit be configured to be controlled from temperature sensor in BRC1E73 Navigation Controller if the unit is capable.

2. In the indoor unit, the setpoints, start/stop status, mode, airflow direction, and fan speed are written to the non-volatile memory each time they are changed so the settings are not lost in the event of a power failure. The number of times this non-volatile memory can be written is limited, and writing beyond that limit may cause failure to the indoor unit EEPROM. This will not cause the indoor unit to stop functioning;

however, the volatile memory will not retain the last settings received. Consequently, when the setpoints, start/stop status, mode, airflow direction, and fan speed are frequently changed by automatic control from the BMS, the number of times each setting for each indoor unit is limited to 70,000 – 80,000 times per year (dependent on the indoor unit manufacturing date).If the same value is repeatedly sent, it will not be added to the total “write to” count.

3. BACnet is a registered trademark of ASHRAE.

COMPATIBILITY:

Engineer: Date:

Submitted to: Construction:

(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)

DIMENSIONS:

DOCUMENTATION:

Documentation available on www.daikincity.com and/or www.daikinac.com:

BACnet Design Guide

Installation Manual

Submittal

Guide Specifications

Information

Physical Data Materials Internal Fluid Coils/Bank: 1 Fin Type: 1/2" 1.25" x 1.083" Flat Fin Height: 30" Fin Length: 32" Rows: 3 Fins/Inch: 12 # Feeds: 4 Dry Weight (ea.): 59 Lbs.

Fin Matl: Aluminum 0.0060 in.

Tube Matl: Copper 0.016 in.

Refrigerant: R32 Liquid Temp: 110 °F Evap Temp: 45 °F Lvg. Super Heat: 6 °F

Airside Construction Airflow: 2,400.0 SCFM Altitude: 0 ft.

Ent. DB/WB: 80 °F / 67 °F Capacity Req'd: 72.0 MBH

Coil Style: Standard Coil Hand: Right Casing Matl: 16 Ga Galv Steel Casing Type: Flanged Connection Matl: Copper Connection Type: SWT

Performance

Description UOM Evaporator Perf.

Special Notes:

Coil is NOT certified by AHRI. Coil Is within the scope of the AHRI Forced-Circulation Air-Cooling And AirHeating Coils Certification Program.

Project: 121583 Coil Name: AHU AC-60 (DX Coil)

Rows/FPI fpi 3 / 12.0 Total Capacity MBH 81.0 Sensible Capacity MBH 54.9 Lvg Air DB/WB °F 59.2/56.3 Condensate Rate Lb/Hr 23.3 Face Velocity Sfpm 360 Refrigerant Charge Lbs 2.49 Air Pressure Drop in. H2O 0.163 Ref Pressure Drop Psi 5.5 Coil Circuiting Optimized at 4 Feeds / 18 Pass Tube Vapor Velocity fpm 2,117 Suction Connection NPS 1.375 Suction Line Velocity fpm 1,291 Distributor #1 Model 501-4-1/4-3 Dry Weight (ea.) Lbs 59 Internal Volume (ea.) ft³ 0.30

630-26-101 EXISTNG 12S ONCOLOGY PHARMACY AC-60 SPECIFICATIONS
630-26-101 DAIKIN 6-TON CONDENSING UNIT SPECIFICATIONS
Material list
Indoor unit details
Table of abbreviations
CU- 1 - RXYQ72AATJB
Remarks
Outdoor vs. indoor position
Outdoor unit details
Table of abbreviations
Outdoor details
Sound Data
Refrigerant information
CU- 1 - RXYQ72AATJB
Refrigerant information
Pipe capacities
Piping limitations
Piping diagrams
Piping CU- 1
Piping
Wiring diagrams
Wiring CU- 1
Remarks

121583-AHU AC-60 DX Coil Performance