Y1DA--620A4-18-212 Pharmacy USP 800 Renovation
Solicitation number
36C24223B0001
Issued by

About this file

This solicitation is for a Pharmacy USP 800 Renovation project for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2. The solicitation seeks bids for construction services to renovate pharmacy spaces in accordance with USP 800 standards for hazardous drugs. Small businesses are encouraged to respond. Bids are due by April 15, 2022 and the contract is expected to be awarded by May 15, 2022. The renovation scope includes construction of a new containment segregated compounding area, hazardous drug storage room, and anteroom with interlocking doors. Facility upgrades such as HVAC, plumbing and electrical work are also required. The project is to be completed within 180 calendar days of the award date.

View the file

Other files

File Type Posted
36C24223B0001 0001.docx DOCX document
620A4 18 212 Bid Docs Specs Volume II.pdf PDF
620A4 18 212 Bid Docs Specs Volume I.pdf PDF
Salient Characteristics 620A4 18 212.pdf PDF
WAGE DETERMINATION 02.pdf PDF
36C24223B0001_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOCATION MAP SITE MAP

DRAWING INDEX

AREA OF WORK

BUILDING #15H

PROJECT LOCATION

COVER SHEET

& DRAWING INDEX

GI001

HWRMP

NO. DESCRIPTION DATE

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

B

A

C

D

E

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT PHARMACY USP 800 RENOVATION 620A4-18-212

15H

Project Director

2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

NORTH

PULL

A .F

.F M

A X

RADIOLOGY

RECORDS

RECOVERY

RECEPTION

M

MAINT

MECH

MACH MACHINE ROOM

MALE

MAINTENANCE

RECD

RECP

RECOV

RAD

ROOM

STAFF

REHABILITATION

SHOWER

SUPPLY

STAFF TOILET

SOILED UTILITY

SECRETARY

STAIRS

SUPPORT

STATION

STERILIZER

SERVICE

SWITCHGEAR

SUPERVISOR

SURGERY/ ICAL

STORAGE

MGR

MED

MRI

OFF

OR

ORTHO

OH

OB/GYN

OPERATING ROOM

MANAGER

OFFICE

MEDICATION/ MEDICAL

ORTHOPEDICS

OBSTETRICS/ GYNECOLOGY

ORAL HYGIENIST

MAGNETIC RESONANCE

IMAGING

SWGR

ST

STA

RM

S TLT

SVCE

SHR

S

STOR

SUPVR

SPRT

SPLY

SOIL

SECY

REHAB

STER

SURG

MECHANIC(AL)

EDUCATION

ELEVATOR

ELECTRIC(AL)

ED

ELEV

EMG

ELEC

ADMIN

ASSY

AUD

AMB

ASSEMBLY

ADMINISTRATION(OR)

AMBULATORY

AUDIOLOGY

"DN"

S

SIMILARSIM

SPEC

SF

SOUTH/ SINK

SQUARE FEET/ STOREFRONT

(NON - NCS ABBREVIATIONS ARE SHOWN

UNDERLINED) EXAMPLE:

ENDOSCOPY

EQUIPMENT

EXECUTIVE

ENDO

ENT

EQUIP

EXEC

FREEZER

FEMALE

FRZ

F

BALCONYBALC

CHEMICALCHEM

CHGN

CLASSCL

CHIRO CHIROPRACTOR

CHARGE NURSE

GENERAL

GYMNASIUM

GEN

GYM

HEAD

HOUSEKEEPINGHSKPG

HD

ICCU

HAZ MAT

CLERICAL

CLN

CLER

CLOSETCLO

CLRM CLASSROOM

CLEAN (ING)/ CLEAN UTILITY

COMM

CONF

CORRIDORCORR

COPY

COMMUNICATIONS

CONFERENCE

COPY/ WORK ROOM

COMMANDER/ COMMANDCMD

SQUARESQ

SST

STEEL

STC

STL

TREADT

THROUGHTHRU

TEMP

SOUND TRANSMISSION CLASS

STAINLESS STEEL

TEMPERATURE/ TEMPORARY

TOP OF

TOC

TO

TOF

TOM

TYPICALTYP

U

UC

TOS

HEAT TRANSFER COEFFICIENT

TOP OF FOOTING

TOP OF CONCRETE (CURB)

UNDERCUT

TOP OF MASONRY

TOP OF STEEL

SPECIFICATION(S)

HAZARDOUS MATERIALS

EAR NOSE THROAT

ELECTROMYOGRAPHY

INTENSIVE CARDIAC CARE UNIT

TECHNICIAN

TELEPHONE

TOILET

URINAL

TREATMENT

WAITING

WAREHOUSE

WATER CLOSET

WEIGHTS AND MEASURES

WEIGHT

WORK STATION, WORK ROOM

EXECUTIVE OFFICER

VESTIBULE

P

PHAR

PHYS

PEDS

PO

PYSCH

PRIN

PREP

POST OFFICE

PRINCIPAL

PHARMACY

PATIENT

PREPARATION

PEDIATRICS

PHYSICAL

PSYCHOLOGY

PROCTO

PROC

PUB

PT/OT

PULMO

PUBLIC

PHYSICAL / OCCUPATIONAL

THERAPY

PROCTOLOGY

PROCEDURE

PULMONARY

PARKINGPRKG

WT

WHSE

WAIT

VEST

UR

WORK

TRT

TECH

XO

WC

W & M

TEL

TLT

INFORMATION

ISOLATION

INJECTION

INFO

ICU

ISO

INJ

JANITOR

KITCHEN

JAN

JC

KIT

CSR

CT

CONTROLCTRL

CENTRAL STERILE ROOM

CAT SCAN

DRESSING

DEPT

D

DIRECTOR

DICTATION

DIR

DICT

DEPARTMENT

LAUNDRY

LABORATORY

LAU

LAB

LDRP

LCPO

LIBRARY

LOCKER

LIT/ FORMS

LIB

LPO

LKR

L/W

L/F

DOCTORDR

DOR

DRK

DTR

DARKROOM

DENTAL TREATMENT ROOM

DENTAL OPERATORY ROOM

DISP DISPENSING

UL

U/C/B

VACUUMV

U0N

VARIESVAR

VCT

VERTICAL

VTR

VERT

VENT THRU ROOF

UNLESS OTHERWISE NOTED

UNDERWRITERS LABORATORY

VINYL COMPOSITION TILE

UNDER COUNTER BASE

W

WITHW/

W

WITHOUT

WOOD

W/0

WD

WEIGHTWT

WP

WH WALL HUNG/ WATER HEATER

WEST /WATT

WATERPROOF / WORKING POINT

WIDTH /WIDE FLANGE

VWC VINYL WALL COVERING

WWF WELDED WIRE FABRIC

JANITOR'S CLOSET

LABOR DELIVERY RECOVERY POST PARTUM

LEADING CHIEF PETTY OFFICER

LEADING PETTY OFFICER

LITTER WHEELCHAIR

INTENSIVE CARE UNIT

KILOPASCAL

POUND

ANGLE

KPA

L

LB

EACH

ELEVATION

EACH END

EXPANSION JOINT

EA

EJ

EL

EE

AND&

DOLLAR (USD)

@ AT

NUMBER / POUND

NATIONAL CAD STANDARD ABBREVIATIONS

LINEAR FEET

METERS

MAXIMUM

LF

M

MAX

MINIMUM

MILLIMETERS

MISCELLANEOUS

MASONRY OPENING

MIN

MM

MISC

MO

ET CETERA

EQUAL

EYE WASH STATION

ELECTRIC WATER COOLER

EXISTING

FILLER

NORTH

NOT APPLICABLE

NUMBER

NOT IN CONTRACT

NA

N

NO

NIC

NOT TO SCALE

OXYGEN

ON CENTER

NTS

OC

O

NOMINALNOM

FACSIMILE

FIRE EXTINGUISHER

FINISHED FLOOR

FIRE EXTINGUISHER CABINET

FLOOR

FACE OF

FIBERGLASS REINFORCED POLYMER

FACE OF SLAB (STUD)

FIRE HOSE CABINET

EQ

F

A/C

A/E

ADA

ACT

AHJ

AHU

AFF

ALUM

AUTHORITY HAVING JURISDICTION

AMERICANS WITH DISABILITY ACT

ACOUSTICAL CEILING TILE

ABOVE FINISHED FLOOR

AIR HANDLING UNIT

ALUMINUM

ARCHITECT-ENGINEER

AIR CONDITIONED

FE

FF

FLR

FO

FRP

BEAM

BLDG

BM

BOS

BO

CG

CCT

CL

CJ

BUILDING

BOTTOM OF STEEL

CENTER LINE

CONTROL/ CONSTRUCTION JOINT

CORNER GUARD

BY OWNER/ BOTTOM OF

CUBICLE CURTAIN TRACK

FOS

FAX

EWS

ETC

FEC

FHC

EXIST

EWC

OPPOSITE HAND

OUTSIDE DIAMETER

PLATE

OPENING

OPH

OD

PL

OPNG

PAIR

PLASTIC LAMINATEPLAM

PR

PSI

PSF

GAS

GRAB BAR

GALVANIZED

GAGE

HIGH

GYPSUM BOARD

GENERAL CONTRACTOR

QUANTITY

PTS

QTY

RISER/RADIUS

REQUIRED

ROUGH OPENING

RENOVATE(TION)

R

RAL

RO

REQ

RENOHARDWARE

HOUR

HOLLOW METAL

INTERCOM

INTRAVENOUS

INCH(ES)

INSIDE DIAMETER

PT

HANDICAP

G

GB

GA

GC

H

CLL

CLG

CM

CMU

CLR CLEAR

CONC

CO2

CONT

CTJ

CENTIMETER

CONCRETE

COLUMN LINE

CONTINUED (OUS)

CONCRETE MASONRY UNIT

CEILING

CONTRACTION JOINT

CARBON DIOXIDE

HM

HR

ID

IC

IV

INCTR

DBA

D

DEG

DIA

DR

DWG

DN DOWN

DEGREE

UNIT OF SOUND

CENTER

DEEP/ DEPTH

DIAMETER

DOOR/

DRAWING(S)

COORDINATECOORD

HC

HDW

GALV

GYP BD

ROICC

JOINTJT

DWR DRAWER

PAINT

POUNDS/SQUARE FOOT

POUNDS/SQUARE INCH

RESIDENT OFFICER IN CHARGE

OF CONST

FEDERAL COLOR PALETTE

PNEUMATIC TUBE STATION

VOL VOLUNTEER

ASSISTANTAST

COMPUTERCOMP

COORD COORDINATOR

CLIN CLINIC (AL)

PERSONNELPERS

MANAGEMENTMGNTANALYSISTANLST

COMPR COMPTROLLER

CUBICLESCBCL

DEGREE(S)°

AIR

A

/ DIVIDE BY, PER

EQUALS, EQUAL TO

' FOOT, FEET

> GREATER THAN

> GREATER THAN OR EQUAL TO

INCH(ES)"

MINUS, NEGATIVE

< LESS THAN

LESS THAN OR EQUAL TO

MULTIPLY BY, BYX

% PERCENT

PLUS

+/- PLUS OR MINUS

NATIONAL CAD STANDARD ROOM NAME ABBREVIATIONS

"DN"

(NON - NCS ABBREVIATIONS ARE SHOWN

UNDERLINED) EXAMPLE:

FOOT/FEETFT

TELEVISIONT.V.

P.T. PRESSURE TREATED

MOUNTEDMNTD

FIRE RETARDANTF.R.

SS STAINLESS STEEL

WHEELCHAIRW/C

FIRE TREATEDF.T.

ABA ARCHITECTURAL BARRIERS ACT

SAB SOUND ATTENUATION BATTS

EXPOSEDEXP

DEMO DEMOLISH

A101

SIM

A101

SIM

A101

SIM

BUILDING ELEVATION/SECTIONDetail No.

Sheet No.

Reference Label

Detail No.

Sheet No.

Reference Label

Detail No.

Sheet No.

Reference Label

Room No.

Room Area

Door/Room No.

Partition Configuration

Partition Configuration

Key Note No.

ALIGN

WALL SECTION

DETAIL SECTION/CALLOUT

ROOM TAG

DOOR TAG

PARTITION TAG

KEYNOTE

ALIGNED SURFACES

Room Name

150 SF

Room Name

Area

AREA TAG

Area NameArea Name

150 SF

WL_Type 2S 86

SCOPE OF PROJECT

Project Limit Line

Grid No.

CENTERLINE

COLUMN GRID LINE

SPOT ELEVATIONSpot Elevation AFF

Level/Datum Elevation AFF

LEVEL MARKER

Level/Datum Name

Window Type WINDOW TYPE TAG1t

CL

Highpoint @ Tail SLOPE INDICATOR

Starting Point @ Center DIMENSION CROSSHAIR

NORTH ARROW

Plan North Reference Label

Name Elevation

Revision Reference Number

Revision Cloud Depicting Area Revised

REVISION

CEILING TAG1'-0" Clg Height

0' - 8" 0' - 8"

AUDIO/VISUAL

FIRE ALARM

EXIT SIGN WALL

SWITCH

WALL

PHONE

JACK

FIRE ALARM

PULL STATION

(GENERALLY

LOCATE UNDER

A/V ALARM)

T.V./DATA/

PHONE

POWER

RECEPTACLES

LIGHT

SWITCHES

OCCUPANCY

SENSOR

CARD

READER

THERMOSTAT

POWER

DISCONNECT

REMOTE DOOR

RELEASE

" 3

TYPICAL

WORKSTATION

ASSEMBLY

3' - 3"

CLEAR

2' - 6"

D/V L

TV

D/V

TV E

E

ED/V

L L OS CR T DR

E

EM E

D/V

SOAP

DISPENSER

HAND SANITIZER

DISPENSER

GLOVE BOX

DISPENSER

M A

X

IM

U M

FIRE

EXTINGUISHE

R WALL

HUNG

FIRE

EXTINGUISHER

IN RECESSED

CABINET

METAL TRIM

LETTERS BY

CABINET

MANUFACTURER

CONTINUOUS

HINGE

SEE FLOOR

PLAN FOR

PARTITION TYPE

METAL PULL

F I

R E

E X

T I

N G

U I

S H

E R

METAL STUDS

EACH SIDE OF CABINET

GYP. BD.

PLAN ELEVATION

SIZE FIRE EXTINGUISHER CABINET LARGE ENOUGH TO

HANDLE A 2.5-GALLON PRESSURIZED WATER EXTINGUISHER.

VISION PANEL

RECESSED FIRE EXTINGUISHER

CABINET; INTERIOR DIMENSIONS:

8" X 8" X 27"

A S e rv ic e

D i s a b le d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

Drawing Title

Approved: Project Director

Project Title

Issue Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANT Office of o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

PLAN

NORTH

PHARMACY USP 800 RENOVATION 620A4-18-212

15H

U.S. Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

ACTUAL

NORTH

Phase

BID DOCUMENTS

FULLY SPRINKLERED

Construction and Facilities Management

ENGINEER OF RECORD GENERAL NOTES, SYMBOLS, ABBREVIATIONS,

STANDARD & BARRIER FREE MOUNTING

HEIGHTS

G-001 2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

JBS JDW

ABBREVIATIONS PLAN SYMBOLS

COLOR & MATERIAL ABBREV.

ACT ACOUSTIC CEILING TILE & GRID

ACT (SC) ACOUSTIC CEILING TILE & GRID (SPECIALTY COATING)

ACT (SP) ACOUSTIC CEILING TILE & GRID (WITH SPRAYED PLASTIC FINISH)

C CONCRETE

CC CUBICLE CURTAIN

CG CORNER GUARD

CPT MODULAR CARPET TILE

CS CONCRETE SEALER

CT CERAMIC TILE

CWT CERAMIC WALL TILE

EF ENTRANCE FLOORING

EFTR EXISTING FINISH TO REMAIN

EPY EPOXY FLOOR

EX EXISTING

EXP EXPOSED

GL GLASS (GLAZING)

GRT GROUT

GT GLASS TILE

GWB GYPSUM BOARD

GWB (SC) GYPSUM BOARD (WITH SPECIAL COATING)

ME MATCH EXISTING

MP METAL PAINT

PBT PORCELAIN TILE - COVE BASE

PFT PORCELAIN FLOOR TILE

PL PLASTIC LAMINATE

PT PAINT

PT(A) PAINT - FLAT FINISH

PT(B) PAINT - EGGSHELL FINISH

PT(C) PAINT - ALKYD/ ENAMEL FINISH

PT(D) PAINT - EPOXY

PWT PORCELAIN WALL TILE

QT QUARRY TILE

RB RUBBER BASE

RS RUBBER SHEET

RT RUBBER TILE

SDT STATIC DISSIPATIVE TILE

SQA SOLID QUARTZ AGGREGATE

SS SOLID SURFACE

TP TOILET PARTITION

TS TRANSITION STRIP

VCT VINYL COMPOSITION TILE

WD WOOD DOOR

WF WALL FABRIC

WP WALL PROTECTION - SHEET

WT WINDOW TREATMENT

WV WALL VINYL

PLAN SYMBOLS

ELECTRICAL CONTROL DEVICES

STANDARD & BARRIER FREE MOUNTING HEIGHTS

EQUIPMENT AND ACCESSORIES FIRE PROTECTION EQUIPMENT

1 1/2" = 1'-0"F8 FEC

H A

N D

IC

A

P S

P A

C E

S

WOODED AREA

WOODED AREA

O/S 16

O/S 03

O/S 04

WOODED AREA

PARCEL 1

112.851 ACRES

APPROXIMATE

PROJECT LIMITS

X X

X X

X X

X X

X

X

X

X X

X

X

X

X

X

NO. DESCRIPTION DATE

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

B

A

C

D

E

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT PHARMACY USP 800 RENOVATION 620A4-18-212

15H

Project Director

2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

CONSTRUCTION SITE

LOGISTICS PLAN

G-002

ARFDJ

DN

UP

PATH OF TRAVEL (FEET)

EXIT FLOW

START OF TRAVEL

WALL MOUNTED EXIT SIGN

(COORDINATE W/ ELECTRICAL)

RECESSED CABINET FIRE EXTINGUISHER

(COORDINATE W/ FIRE MARSHAL)

TWO HOUR FIRE WALL CONSTRUCTION

BUSINESS OCCUPANCY

ONE HOUR FIRE WALL CONSTRUCTION

EXISTING ELECTRICAL EXIT SIGN

125 SF

ADMIN OFFICE

251C

66 SF

ADMIN OFFICE

251B

154 SF

ADMIN OFFICE

251D

155 SF

RECEPTION

341 SF

ROLLING SHELF

STORAGE

246C

551 SF

PRESCRIPTION

AREA

246B

52 SF

COMM. CLOSET

61 SF

ELECT. CLOSET

220 SF

RECEIVING

STAGING

246A

444 SF

RECEIVING

STAGING

90 SF

ADMIN OFFICE

129 SF

PRESCRIPTION

RECEPTION

45 SF

STORAGE

100 SF

CLINIC EXAM

223 SF

BULK STORAGE

251F

53 SF

MENS TOILET

52 SF

WOMENS TOILET

292 SF

STAFF LOUNGE

251E

134 SF

CLINIC EXAM

144 SF

NEG. BUFFER

250D

140 SF

NEG. ANTE

250C-B

186 SF

POS. ANTE

103 SF

POS. BUFFER

250A

44 SF

RECEIVING /

BREAK DOWN

249B

147 SF

PRESCRIPTION

VAULT

171 SF

SECURED

DISPENSING

249A

761 SF

MECHANICAL

ROOM

87 SF

ELEVATOR

95 SF

ELEVATOR

199 SF

STAIR

H-01

882 SF

LOBBY AREA

C2-03A

80 SF

WOMENS TOILET

49 SF

EMS CLOSET

73 SF

MENS TOILET

339 SF

CONFERENCE

ROOM

58 SF

WOMENS TOILET

52 SF

MENS TOILET

1019 SF

CORRIDOR

C2-03B

212 SF

ELEVTOR LOBBY

C2-01

887 SF

CORRIDOR

C2-02

130 SF

CLINIC EXAM

140 SF

CLINIC EXAM

103 SF

CLINIC EXAM

129 SF

CLINIC EXAM

H-228

129 SF

CLINIC EXAM

H-227

99 SF

CHEMO PREP

H-226

103 SF

CLINIC EXAM

H-225

104 SF

CLINIC EXAM

H-224

89 SF

CLINIC EXAM

H-223

146 SF

CLINIC EXAM

H-242

119 SF

CLINIC EXAM

H-241

113 SF

CLINIC EXAM

H240

93 SF

CLINIC EXAM

97 SF

CLINIC EXAM

93 SF

CLINIC EXAM

311 SF

CORRIDOR

C2-08

343 SF

CORRIDOR

C2-07

219 SF

CORRIDOR

C2-06

219 SF

SPECIALTY

CLINIC

RECEPTION

84 SF

CLINIC EXAM

1275 SF

OPTI-FILL 2 AREA

246D

201 SF

CHEMO NURSE

STATION

H-220

142 SF

PRIVATE

TREATMENT

H-220C

94 SF

ONCOLOGY EXAM

H-221 21 SF

STOR.

H-222A

461 SF

CORRIDOR

C2-04

187 SF

STAIR

H-02

111 SF

ONCOLOGY EXAM

H-213

246I

117 SF

ONCOLOGY EXAM

H-214

120 SF

ONCOLOGY EXAM

H-215

103 SF

ONCOLOGY EXAM

H-216

213 SF

CORRIDOR

C2-05

77 SF

PATIENT TOILET

H-220B

409 SF

CHEMO

TREATMENT

ROOM

H-220A 10 SF

STOR.

220D

10 SF

ELEC. CL.

H-222B

6 SF

M.C.03

6 SF

M.C.02

8 SF

M.C.01

106 SF

ONCOLOGY EXAM

H-218

93 SF

ONCOLOGY EXAM

H-217

59 SF

ONCOLOGY EXAM

H-219

PATH

"COMMON"

PATH "A"

PATH "B"

PATH "A"

CLEAN

AGENT

49 SF

AIRLOCK

250C

PROJECT LOCATION

A S e rv ic e

D i s a b le d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

Drawing Title

Approved: Project Director

Project Title

Issue Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANT Office of o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

PLAN

NORTH

PHARMACY USP 800 RENOVATION 620A4-18-212

15H

U.S. Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

ACTUAL

NORTH

Phase

BID DOCUMENTS

FULLY SPRINKLERED

Construction and Facilities Management

ENGINEER OF RECORD LIFE SAFETY SHEET

G-003 2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

JBS JDW

Path ID Common Path

Distance Allowable Common

Path Actual Travel

Distance Allowable Travel

Distance

A 0' - 0" 100' - 0" 131' - 6" 300' - 0"

B 0' - 0" 100' - 0" 209' - 1" 300' - 0"

COMMON 48' - 1" 100' - 0" 0' - 0" 300' - 0"

GENERAL SHEET NOTES

LIFE SAFETY LEGEND

EXIT ACCESS TRAVEL DISTANCE

1. PROVIDE EGRESS DOORS WITH CODE COMPLIANT EXIT DEVICES.

2. PROVIDE MINIMUM 1-FT CANDLE ILLUMINATION AT MEANS OF EGRESS

AND EXIT DISCHARGE WHEN BUILDING IS OCCUPIED.

3. KEEP EGRESS PATH FREE OF OBSTRUCTIONS.

4. PROVIDE FIRE EXTINGUISHERS AT LOCATIONS IN ACCORDANCE WITH

NFPA 10 PG18-3 AND AS DIRECTED BY LOCAL AUTHORITY.

5. LIFE SAFETY PLANS APPLY TO THE PROJECT SCOPE OF WORK ONLY

AND ARE PROVIDED FOR REFERENCE ONLY. INFORMATION IS BASED

ON OWNER PROVIDED DATA. CONTACT VAMC FOR ADDITIONAL LIFE

SAFETY INFORMATION OUTSIDE THE SCOPE OF WORK.

PROJECT SUMMARY:

THIS PROJECT CONSISTS OF AN ONCOLOGY RENOVATION OF THE SECOND FLOOR, BUILDING 15H, ROOMS 251A AND 250A-D . THIS PROJECT IS TO INCORPORATE INTERIOR PARTITIONS, FINISHES, MEDICAL EQUIPMENT, AND MEPFP SYSTEMS TO BRING THE EXISTING COMPOUNDING AREA INTO USP 800 COMPLIANCE. THE CONSTRUCTION SCOPE

INCLUDES COMPLIANCE WITH THE SUITE REQUIREMENTS AS FOLLOWS:

APPLICABLE CODES

VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION OR IMPROVEMENT OR ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MATER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:

VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE IN

THE TECHNICAL INFORMATION LIBRARY (TIL)

NFPA 101 LIFE SAFETY CODE 2018 EDITION

VA FIRE PROTECTION DESIGN GUIDE 7TH EDITION

NFPA NATIONAL FIRE CODE (EXCEPTION OF NFPA 5000 AND NFPA 900)

USP 797

USP 800

VA SEISMIC DESIGN REQUIREMENTS, H-18-8

NATIONAL ELECTRICAL CODE (NEC)

INTERNATIONAL PLUMBING CODE (IPC)

ENERGY POLICY ACT OF 2005 (EPACT)

FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU) EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND TRANSPORTATION MANAGEMENT

THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGN

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 -2004

SAFETY STANDARD FOR REFRIGERATION SYSTEMS - ASHRAE STANDARD 15-2007

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)

TRAVEL DISTANCE AND COMMON PATH OF TRAVEL (38.2.5 & 38.2.6):

BUSINESS (CHAPTER 38): MAX TRAVEL DISTANCE MAX COMMON PATH OF TRAVEL MAX DEAD END CORRIDOR

SPRINKLED = 300' - 0" SPRINKLED = 100' - 0" SPRINKLED = 50' - 0"

INTERIOR WALLS :

• NONCOMBUSTIBLE PARTITIONS (4.6.13)

• LIMITED-COMBUSTIBLE PARTITIONS (4.6.14)

1. PARTITIONS CONSTRUCTED WITH FIRE-RETARDANT, TREATED WOOD ENCLOSED WITH NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE

MATERIALS

2. SUCH PARTITIONS SHALL NOT BE REQUIRED TO BE FIRE RATED

EXIT ACCESS:

• CORRIDOR EXIT ACCESS - MINIMUM OF (1) (38.2.4.3)

• CORRIDOR WIDTH - MINIMUM OF 44" (38.2.3.2)

HAZARDOUS CLASSIFICATION

THE CLASSIFICATION OF "HAZARDOUS" IN THE NFPA 100 DIFFERS FROM USP 800. ROOMS LABELED "HAZARDOUS" IN THE CONSTRUCTION DOCUMENTS REFER TO USP 800 REQUIREMENTS. "HAZARDOUS" REGARDING USP 800 RELATES TO THE TYPE OF DRUGS COMPOUNDED IN THE

PHARMACY AND NOT THE COMBUSTIBILITY OF THE MATERIALS IN THE PHARMACY.

PROJECT CODE SUMMARY

1/8" = 1'-0"F1 LIFE SAFETY PLAN

OCCUPANCY LEGEND

NO. DESCRIPTION DATE

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

B

A

C

D

E

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT PHARMACY USP 800 RENOVATION 620A4-18-212

15H

Project Director

2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

STRUCTURAL

ABBREVIATIONS & NOTES

S-001

DSER

STOR

H-3

STOR

H-3

D

C

B

A

1 2 3 4 5 6 7

NO. DESCRIPTION DATE

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

PLAN

NORTH

ACTUAL

NORTH

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

B

A

C

D

E

F

KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT PHARMACY USP 800 RENOVATION 620A4-18-212

15H

Project Director

2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

STRUCTURAL

ROOF PLAN

SF131

SGCER

S-501

STRUCTURAL

SECTIONS & DETAILS

ER RP

NO. DESCRIPTION DATE

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

B

A

C

D

E

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT PHARMACY USP 800 RENOVATION 620A4-18-212

15H

Project Director

2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

EF

V

V V

V

V

HP

RC

HP

HP

HP

HP

HP

R .V

R .V

R .V

V

VTR

EF

EF

EF

EF

EF

EF

EF

HP

RO

OF

B

EL

OW

RD

RD

r 4

RD

r 5

ELEVATOR 01 ELEVATOR 02

STORAGE

H-300

E

LE

V

ATO

R

LO

BBY

C 3-

RD

r 5

EXISTING CONSTRUCTION TO BE

DEMOLISHED

EXISTING CONSTRUCTION TO

REMAIN

EXISTING DOOR TO REMAIN

EXISTING DOOR TO BE REMOVED

(DEMO)

EXISTING LIGHT TO BE SALVAGED

1. VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK.

DEMOLITION WORK HAS BEEN DERIVED FROM EXISTING DRAWINGS

AND ARE INTENDED TO REASONABLY REPRESENT CURRENT

CONDITIONS. ACTUAL CONDITIONS MAY VARY. NOTIFY COR IF

MATERIAL DISCREPANCIES ARE ENCOUNTERED.

2. SHADED AREAS ARE NOT IN CONTRACT EXCEPT AS NEEDED TO

PROVIDE SERVICES OR ACCESS FOR WORK.

3. COORDINATE WORK INDICATED WITH SPECIALTY DEMOLITION WORK

INDICATED IN OTHER CONSTRUCTION DOCUMENTS.

4. PROTECT EXISTING CONDITIONS INDICATED TO REMAIN FROM

DAMAGE OR DETERIORATION DUE TO PERFORMANCE OF WORK.

PATCH AND REPAIR EXISTING WORK IN MANNER TO ELIMINATE

EVIDENCE OF REPAIR WORK.

5. CEASE WORK, SECURE AREA AND NOTIFY COR IF POTENTIALLY

HAZARDOUS MATERIALS ARE ENCOUNTERED.

6. DO NOT CUT STRUCTURAL COMPONENTS UNLESS INDICATED

OTHERWISE.

7. COORDINATE REMOVAL OF DEMOLISHED MATERIALS WITH COR.

PREVENT DUST AND DEBRIS FROM INFILTRATING OCCUPIED AREAS.

PROVIDE ENCLOSED CHUTES AND NEGATIVE AIR PRESSURE AS

REQUIRED TO PREVENT CONTAMINATION. DISPOSE OF DEMOLISHED

MATERIALS IN LAWFUL MANNER, OFF SITE.

8. PROVIDE AND MAINTAIN TEMPORARY PARTITIONS, PROTECTIVE

BARRIERS AND SECURITY DEVICES AS REQUIRED TO PROTECT

BUILDING, CONTENTS AND OCCUPANTS FROM HARM DUE TO

DEMOLITION ACTIVITIES.

9. MATERIALS AND COMPONENTS TO BE SALVAGED ARE INDICATED.

REMOVE SALVAGE ITEMS AS COMPLETE UNITS TO THE EXTENT

POSSIBLE AND PROTECT FROM FURTHER DAMAGE. CLEAN

COMPONENTS OF DUST AND DIRT. STORE ON SITE AS DIRECTED BY

COR.

10. COORDINATE SCHEDULE WITH COR PRIOR TO COMMENCING

DEMOLITION WORK THAT MAY INTERRUPT SERVICES. SCHEDULE

WORK AND PROVIDE TEMPORARY CONNECTIONS OR NEW SERVICES

AS NECESSARY TO ELIMINATE DISRUPTIONS AFFECTING THE

OWNER'S OPERATIONS.

11. LOCATE AND MARK UTILITIES TO REMAIN WITH TAGS INDICATING

UTILITY TYPE. PROTECT UTILITIES FROM DAMAGE.

12. TO EXTENT POSSIBLE, DEMOLISH INDICATED ITEMS IN THEIR

ENTIRETY. REMOVE PARTITIONS TO DECK ABOVE. DEMOLISH

SERVICES SERVING EQUIPMENT AND UTILITIES TO THEIR SOURCE,

UNLESS INDICATED OTHERWISE.

13. DEMOLITION OF PARTITIONS INCLUDES WALL MOUNTED ITEMS,

ACCESSORIES AND SERVICES.

14. ACCESS FOR EXTERIOR CONSTRUCTION IS SHOWN FOR REFERENCE

ONLY AND DEMONSTRATING VAMC'S PREFERRED OPTION.

COORDINATE EXTERIOR ACCESS WITH COR.

B

A

2 3 4

EXST. OPEN OFFICE

251A

EXST. I.V. ROOM B

250D

EXST. ANTE ROOM

250A

EXST. I.V. ROOM A

250C

EXIST. FREEZER AND

SUPPLIES

250B

001 001

3' - 4"3' - 6"3' - 2"11"2' - 5"5' - 7"

019 019 019

019 018 019

X-CPT

X-EPY

X-EPY

X-EPY

X-EPY

AREA OF CONSTRUCTION

026026 025

3' - 4" 2' - 8"

B

A

2 3 4

EXST. OPEN OFFICE

251A

EXST. I.V. ROOM B

250D

EXST. ANTE ROOM

250A

EXST. I.V. ROOM A

250B

EXIST. FREEZER AND

SUPPLIES

250C

013 013

013 013 013

013 013

X-ACT

8' - 6"A.F.F.

X-ACT

8' - 6"A.F.F.

X-ACT

8' - 6"A.F.F. X-ACT

8' - 6"A.F.F.

X-ACT

8' - 3"A.F.F.

AREA OF CONSTRUCTION

1234567

LEVEL 3

30' - 0"

LEVEL 1

10' - 0"

LEVEL 2

20' - 0"

BASEMENT FLOOR

(GROUND FLOOR)

2' - 0"

025 002

D

C

B

A

3 4 5 6 7 N 9

Q R

T

C.1

D.1

032032032032

032032032

DEMOLITION SHEET NOTES

LEGEND

# NOTE

001 DEMO FLOORING AND WALL BASE. PREP SUBFLOOR TO RECEIVE NEW FLOOR FINISH. LEVEL

FLOOR AS REQUIRED.

002 DEMO GLAZING PANEL AND PREPARE OPENING TO RECEIVE NEW SPANDREL PANEL.

004 DEMO CEILING TILE, CEILING GRID, SUSPENSION SYSTEM AND CEILING COMPONENTS IN ITS

ENTIRETY. REFER TO MEP/FP DRAWINGS FOR ADDITIONAL INFORMATION.

005 REMOVE EXISTING PLUMBING FIXTURE(S) IN THEIR ENTIRETY. REFER TO DRAWING P-121 FOR

ADDITIONAL INFORMATION.

006 DEMO DOOR FRAME AND HARDWARE. INFILL OPENING WITH CONSTRUCTION TO MATCH

EXISTING WALL CONSTRUCTION. PREP WALLS TO RECEIVE FINISH INDICATED.

007 DEMO PARTITION. PATCH AND REPAIR ADJACENT SURFACES TO REMAIN IN MANNER TO

ELIMINATE EVIDENCE OF REPAIR.

013 SALVAGE LIGHT FIXTURES. CLEAN FIXTURES THEN WRAP PACKAGE AND MARK CONTAINER

WITH CONTENTS. STORE ON SITE AS DIRECTED BY COR.

014 DEMO SINK.

018 DEMO PORTION OF EXISTING PARTITION AS REQUIRED TO ACCOMODATE NEW DOOR AND

FRAME. PATCH AND REPAIR ADJACENT CONSTRUCTION AS REQUIRED TO ELIMINATE

EVIDENCE OF REPAIR. PREP WALLS TO RECEIVE NEW WALL FINISH.

019 PATCH AND PREP WALLS AS REQUIRED TO RECEIVE NEW FINISHES.

025 DEMOLITION OF WINDOW SHOWN AS PREFERRED LOCATION FOR DEMOLITION MATERIAL

WASTE CHUTE. COORDINATE REQUIREMENTS WITH COR. IF USED, PREP OPENING FOR NEW

INFILL.

026 DEMO WINDOW TRIM. PREP AREA FOR INFILL.

027 DEMOLISH EXISTING CEILING MOUNTED EXIT SIGNS

028 DEMO DOOR, FRAME AND HARDWARE.

029 INFILL EXISTING OPENING TO MATCH ADJACENT CONSTRUCTION. PREP WALLS TO RECEIVE

NEW WALL FINISHES.

030 EXISTING ROOF EXHAUST FAN TO REMAIN

031 EXISTING ROOF EXHAUST FAN TO BE DEMOLISHED AND EXISTING CURB TO BE CAPPED.

032 EXISTING PLUMBING VENT TO BE DMEOLISHED; PATCH AND REPAIR ROOF TO MEET ROOF

MANUFACTURER'S WARRANTY, REQUIREMENTS AND STANDARDS.

KEYNOTES

A S e rv ic e

D i s a b le d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

Drawing Title

Approved: Project Director

Project Title

Issue Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANT Office of o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

PLAN

NORTH

PHARMACY USP 800 RENOVATION 620A4-18-212

15H

U.S. Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

ACTUAL

NORTH

Phase

BID DOCUMENTS

FULLY SPRINKLERED

Construction and Facilities Management

ENGINEER OF RECORD DEMOLITION SECOND FLOOR PLAN

,ELEVATION & ROOF PLAN

AD-100

2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

JBS JTK

1/4" = 1'-0"B1 COMPOUNDING SUITE DEMO PLAN

1/4" = 1'-0"B4 COMPOUNDING SUITED DEMO RCP

AREA OF DEMOLITION

1/8" = 1'-0"E1 PARTAIL DEMOLITION NORTH ELEVATION

1" = 10'-0"F1 ENLARGED DEMOLITION ROOF PLAN

ROOF PROTECTION NOTES

1. PROTECT EXISTING ROOFING FROM DAMAGE OR DETERIORATION

DURING PERFORMANCE OF THE WORK.

2. PROVIDE BARRIERS AS REQUIRED TO PREVENT TRAFFIC ON ROOFING.

IF ROOF MUST BE ACCESSED, PROVIDE PROTECTIVE COVERING

SUFFICIENT TO PREVENT PUNCTURES, WEAR AND OTHER DAMAGE TO

ROOFING.

3. PERFORM NO WORK ON ROOFING THAT MAY JEOPARDIZE OR VOID

EXISTING WARRANTIES.

4. REPAIR OR REPLACE ROOFING DAMAGED BY PERFORMANCE OF THE

WORK. PROVIDE ANY REPAIRS OF REPLACEMENTS IN MANNER TO

PROTECT EXISTING WARRANTIES.

5. USE MATERIALS, METHODS AND SYSTEMS TO MATCH EXISTING AND AS

APPROVED BY ORIGINAL ROOFING MANUFACTURER.

D

C

B

A

3 4 5 6

M

N 9

Q

R

T

23222119

A-100

C6

299 SF

EDUCATION

OFFICE

H-047A

143 SF

OFFICE

H-048

1034 SF

EMPLOYEE

FITNESS AND

WELLNESS

CENTER

H-047

478 SF

PT OFFICE

H-046J

142 SF

KT OFFICE

H-046E

403 SF

OT OFFICES

H-046D

59 SF

OFFICE

H-046C

160 SF

PT STORAGE

H-046D1

64 SF

TOILET

H-046B

111 SF

CHIEF OFFICE

046I

58 SF

LEAD OFFICE

046H

3295 SF

PHYSICAL

THERAPY CLINIC

H-046

147 SF

AGENT CASHIER

H-042

123 SF

TRAVEL CLERK

H-041

55 SF

VACANT TOILET

H-045

78 SF

TOILET

H-043

13 SF

TELE. CL.

H-044

1003 SF

CORRIDOR

CB-02

591 SF

TRAVEL ROOM

H022

253 SF

MULTI-PURPOSE

ROOM

H022A

46 SF

TOILET

H-046A

222 SF

ELECTRICAL

ROOM

H-051A

88 SF

ELECTRICAL

ROOM

H-051

133 SF

OFFICE

H-052

148 SF

ELEVATOR MECH.

ROOM

H-053

473 SF

ELEVATOR

LOBBY

CB-01

95 SF

ELEVATOR

87 SF

ELEVATOR

81 SF

STOR.

H-001

101 SF

DATA-TELE

H-049

46 SF

E.M.S. CLOSET

H-050

ELECTRICAL

ROOM

H-051A

OFFICE

H-052

ELECTRICAL

ROOM

H-051

E.M.S. CLOSET

H-050

DATA-TELE

H-049

PROJECT LIMIT LINE

D

C

B

A

3 4 5 6 7

N 9

Q

R

T

2221194.1

275 SF

2 BEDROOM

H-125

273 SF

2 BEDROOM

H-126

70 SF

BATHROOM

H-126A

41 SF

W/C STORAGE

H-127

360 SF

2 BEDROOM

H-128

25 SF

TOILET

H-128A

1158 SF

DAYROOM

H-129

361 SF

2 BEDROOM

H-130

26 SF

TOILET

H-130A

44 SF

W/C STORAGE

H-131

274 SF

2 BEDROOM

H-132

71 SF

BATHROOM

H-132A

275 SF

2 BEDROOM

H-133

70 SF

BATHROOM

H-133A

25 SF

STORAGE

H-134

298 SF

2 BEDROOM

H-135

323 SF

2 BEDROOM

H-136

70 SF

BATHROOM

H-136A

70 SF

BATHROOM

H-135A

532 SF

4 BEDROOM

H-138

37 SF

TOILET

H-138A

69 SF

ELECTRICAL

H-137 114 SF

DATA CLOSET

H-139

276 SF

LOUNGE

H-100

408 SF

CORRIDOR

C1-02

209 SF

ELEVATOR

LOBBY

C1-01

95 SF

CLEAN LINEN

H-101

695 SF

MECH. EQUIP.

ROOM

H-103

102 SF

EQUIP. STORAGE

H-102

30 SF

E.M.S CLOSET

H-141

99 SF

SOILED UTILITY

H-104

119 SF

OFFICE

H-106

144 SF

EXAM ROOM

H-106A

55 SF

NUTRITION ROOM

H-110

67 SF

MED. ROOM

H-112

199 SF

STAIR HALL

NO. 01

145 SF

CORRIDOR

C1-04

712 SF

CORRIDOR

C1-07

629 SF

CORRIDOR

C1-06

A-100

F6

4 BEDROOM

H-138

DATA CLOSET

H-139

TOILET

H-138A

ELECTRICAL

H-137

BATHROOM

H-136A

2 BEDROOM

H-136

CORRIDOR

C1-02

PROJECT LIMIT LINE

A S e rv ic e

D i s a b le d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

Drawing Title

Approved: Project Director

Project Title

Issue Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANT Office of o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

PLAN

NORTH

PHARMACY USP 800 RENOVATION 620A4-18-212

15H

U.S. Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

ACTUAL

NORTH

Phase

BID DOCUMENTS

FULLY SPRINKLERED

Construction and Facilities Management

ENGINEER OF RECORD BASEMENT AND FIRST FLOOR PLANS

A-100 2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

JBS JDW

1/8" = 1'-0"C1 PARTIAL BASEMENT FLOOR PLAN (GROUND FLOOR)

1/4" = 1'-0"C6 ENLARGED ELECTRICAL/DATA ROOM PLAN

SHEET NOTES

1/8" = 1'-0"F1 PARTIAL FIRST FLOOR PLAN

1/4" = 1'-0"F6 ENLARGED ELECTRICAL/DATA ROOM PLAN

1. SHADED AREAS ARE NIC, EXCEPT AS NEEDED TO PROVIDE SERVICES FOR

WORK.

2. ALL DIMENSIONS ARE TO FACE OF STUD OR BLOCK FACE.

3. WHERE INDICATED TO MATCH EXISTING FINISH, NEW FINISH TO MATCH IN

MANUFACTURER, PRODUCT, COLOR, STYLE, SIZE AND ALL OTHER

ATTRIBUTES.

4. ALL DIMENSIONS ARE TO FINISHED FACE OF WALL OR GRIDLINE. DO NOT

SCALE DRAWINGS.

5. PROTECT EXISTING SURFACES AND MATERIALS INDICATED TO REMAIN FROM

DAMAGE OR DETERIORATION DUE TO PERFORMANCE OF WORK. PATCH AND

REPAIR EXISTING MATERIALS AND SURFACES DAMAGES OR AFFECTED BY

PERFORMANCE OF THE WORK.

6. WORK INCLUDES PREPARATION OF EXISTING SURFACES TO RECEIVE NEW

WORK WHERE INDICATED.

7. ALL ANGLES ARE 90 DEGREES UNLESS NOTED OTHERWISE.

8. COORDINATE FIRE EXTINGUISHER, FIRE ALARM STROBES AND PULL STATION

LOCATIONS WITH COR. MOUNT IN ACCORDANCE WITH FEDERAL ABA

STANDARDS.

9. VERIFY DIMENSIONS AND LOCATIONS OF OPENINGS, BASES AND SUPPORTS

FOR EQUIPMENTS, DUCTS, PIPING , CONDUITS, ETC. WHERE REQUIRED FOR

NEW WORK, NEATLY CUT OPENINGS IN EXISTING CONSTRUCTION USING

POWER SAWS OR CORE DRILLS. DO NOT USE IMPACT TOOLS. REVIEW

OPENING LOCATIONS WITH COR PRIOR TO STARTING WORK. KEEP

OPENINGS TO MINIMUM REQUIRED TO ALLOW FOR NEW WORK. PROVIDE

FIRE STOPPING AS REQUIRED.

10. OBTAIN BURN PERMIT FROM COR PRIOR TO PERFORMING ANY WORK

REQUIRING OPEN FLAME.

11. PROVED FIRE RETARDANT TREATED WOOD FOR BLOCKING AND ROUGH

BUCKS. COORDINATE LOCATIONS WITH EQUIPMENT INSTALLER. INSTALL

PRIOR TO CLOSING WALLS.

12. EXAMINE EXISTING SUBSTRATES TO RECEIVE NEW MATERIAL OR FINISH.

PREPARE SUBSTRATE AS REQUIRED TO MEET MANUFACTURER'S

INSTRUCTIONS OR RECOMMENDATIONS FOR PROPER APPLICATION OF NEW

MATERIALS.

13. WHERE FLOOR FINISHES CHANGE AT COMMUNICATING ROOMS, PLACE

TRANSITION UNDER CENTER OF DOOR OR FINISHED OPENING.

14. PROVIDE SMOKE-TIGHT, NON-COMBUSTIBLE 1-HR RATED TEMPORARY

PARTITIONS TO DECK WHERE REQUIRED TO SEPARATE AREAS WHERE

WORK IS BEING PERFORMED FROM OTHER SPACES.

15. IF ANY FIRE RATED PARTITION FALLS DIRECTLY BENEATH AND PARALLEL TO

A FLOOR JOIST OR BEAM, NOTIFY THE ARCHITECT PRIOR TO FRAMING THE

PARTITION.

16. VERIFY THAT ALL BUILDING CORE PARTITIONS AND COLUMNS SHOWN AS

EXISTING CONSTRUCTION ARE READY TO RECEIVE NEW FINISHES AS

SPECIFIED. IF NOT, PROVIDE DRYWALL FINISH AS REQUIRED. DRYWALL

THICKNESS TO MATCH BUILDING STANDARD NOTED ON PARTITION TYPES. AT

ALL EXISTING GYPSUM BOARD CORNERS, VERIFY THAT ALL CORNER BEADS

ARE STRAIGHT, UNBROKEN AND NOT DAMAGED. PROVIDE NEW CORNER

BEADS AS REQUIRED.

KEYNOTES

# NOTE

149 EXISTING CEILING TILES TO BE REMOVED AND PROTECTED DURING

CONSTRUCTION. TILES TO BE REINSTALLED WHEN CONSTRUCTION IS COMPLETED.

NEW PARTITION

EXISTING PARTITION TO REMAIN

RATED PARTITION

EXISTING DOOR

NEW CONSTRUCTION

DOOR

NEW CONSTRUCTION

SLIDING DOOR

B

A

2 3

PPE

TR

ST

PPE

INT

TR

SAN

LP

IV

S

H

SH1

REF

NHD

SHOE

IVSH

SAN

DISP

SAN

INT

CH1

A-200

B2

A-200

A1

A-200 D1

A-200

C3

E2

E1

D2 B4

B1B5

A2

C1

C2

AREA OF CONSTRUCTION

PASS

B

-A

-A

B

-A

250A-A

140 SF

NEG. ANTE

250C-B144 SF

NEG. BUFFER

250D

103 SF

POS. BUFFER

250A

186 SF

POS. ANTE

44 SF

RECEIVING /

BREAK DOWN

249B

C7

A-200

WS

A-200

A6

A5

A3

INT

INT

IN

TR

ST

D E

M A

R K

LH

D E

M A

R K

C

-B

49 SF

AIRLOCK

250C

HW/EW

HW/EW

SHOE

FEC

SH1

PIVPIV

DS

FILE

WKT1

SOAP

PT

PT

SOAP

SS500

A-200

C5

ST

TR

PH

STO

WKT1

WKT2

REF

WKT4

NOTE: ITEMS/TAGS SHOWN IN GREY REPRESENT VA FURNISHED/INSTALLED EQUIPMENT AND ARE FOR REFERENCE ONLY

SAN

SAN

WKT2

/4

9'

1"

CS600

CS500

WKT3

STO

A-200

D3

A-200 D3

COM

LH

DSDS

DS

DSDS

DS

DS

250C-A

B

A

2 3 4

NEG. BUFFER

250D

NEG. ANTE

250C-B

POS. BUFFER

250A

POS. ANTE

RECEIVING /

BREAK DOWN

249B

EQ.7' - 0"EQ

AIRLOCK

250C

EQEQ

AREA OF CONSTRUCTION

E Q

4'

0" E

Q

2' - 0" 2' - 0"

2'

1/

4" 2'

0"

EQ4' - 0"EQE

Q

E Q

EQ 4' - 0" 4' - 0" EQ

2'

0" 4'

6"

1' - 8"1' - 6"1' - 6"1' - 8"

E Q

1'

6" 1'

6"

E Q

GYP. CLG.

9' - 0"A.F.F.

GYP. CLG.

9' - 0"A.F.F.

GYP. CLG.

9' - 0"A.F.F.

GYP. CLG.

9' - 0"A.F.F.

GYP. CLG.

9' - 0"A.F.F.

GYP. CLG.

9' - 0"A.F.F.

B

A

2 3 4

16' - 1"

35' - 9 1/4"

37' - 2"

2' - 8"3' - 4" R.O.

4"

4' - 10 1/4"3' - 4" R.O.3' - 8 3/4"3' - 4" INFILL3' - 6"3' - 2" INFILL8' - 11"

-A

NEG. BUFFER

250D

NEG. ANTE

250C-B

POS. ANTE

POS. BUFFER

250A RECEIVING /

BREAK DOWN

249B

250A-A

B

-A

B

-A

EPY-1

EPY-1

EPY-1

EPY-1

EPY-1

A 1 a

A 2 a

A 1 a

A 2 a A 1 a

B 1 a B 1 a

7' - 6 1/4"

MASONRY INFILL

3' - 10"

3'

1/

2" 9'

1"

AREA OF CONSTRUCTION

132 132

C7

A-200

AIRLOCK

250C

IN

EPY-1

D E

M A

R K

D E

M A

R K

C

-BC L

ALIGN

10' - 3 1/4" 19' - 4 1/4"

9'

1"

/4

9'

3/

4"

6'

/2

/2

1/

4"

1' - 3" C L

CLEAR

3' - 2"

5' - 11"CL

10' - 5" 1' - 4 1/4"

B 5 a B 5 a

5' - 5" 13' - 1"

6' - 4"6' - 9"

E7

A-200

A 1 a

CL

3' - 6"

4'

144144

144 144144

4'

250C-A

FEC

150 150

NOT TO SCALE. ARCHITECTURAL INFORMATION SHOWN FOR REFERENCE ONLY. MEP/HVAC DRAWINGS

SHALL GOVERN.

WALL MOUNTED EXIT

SIGN

RECESSED TROFFER

(1x4,2X2, 2X4, ETC)

SEE ELECTRICAL

RETURN AIR

RECESSED CAN

ACOUSTICAL

CEILING AND GRID

MS MOTION SENSOR

SUPPLY AIR

LINEAR DIFFUSER

EXHAUST FAN

GYPSUM BOARD CEILING

12" X 12" ACCESS PANEL

PROJECT LOCATION

5/8" GYPSUM

BOARD

ACCESS PANEL

ATTACH PER MFR

RECOMMENDATIONS

1" x 1-9/16" x 1"

KNURLED CHANNEL

MOLDING

MAX.

0' - 3"

CROSS TEE

SHEET NOTES

PLAN LEGENDKEYNOTES

# NOTE

128 RES-3, 6" FLOORING STRIPE ON FLOOR TO INDICATE PHARMACY DEMARK LINE. DEMARK LINE TO BE CONTRASTING COLOR FROM EXISTING FLOOR. COORDINATE FINAL LOCATION, COLOR AND/OR MARKINGS WITH PHARMACY DIRECTOR.

129 PROVIDE SPANDREL PANEL. COLOR TO MATCH BUILDING STANDARD.

132 WALL INFILL TO MATCH EXISTING CONSTRUCTION.

141 VA TO PROVIDE USP COMPLIANT HAZARDOUS DRUG HANDLING SIGNAGE IN THIS ROOM

142 VA TO PROVIDE SPILL KIT FOR RECEIVING AND BREAKDOWN ROOM

143 NEW MASONRY INFILL TO MATCH ADJACENT EXTERIOR CONSTRUCTION. SEE C8/A-200.

144 MECHANICAL RETURN GRILLE; REF. MECHANICAL DRAWINGS MH121 & M702 FOR ADDITIONAL INFORMATION AND SIZING.

150 ROOM IDENTIFICATION SIGNAGE LOCATION. CONFIRM FINAL COPY WITH COR. REFERENCE A501 FOR SIGNAGE SCHEDULE.

1/4" = 1'-0"E1 COMPOUNDING SUITE EQUIPMENT PLAN

1/4" = 1'-0"C4 COMPOUNDING SUITE NEW WORK RCP

1/4" = 1'-0"C1 COMPOUNDING SUITE NEW WORK PLAN

RCP LEGEND

A S e rv ic e

D i s a b le d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

Drawing Title

Approved: Project Director

Project Title

Issue Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANT Office of o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

PLAN

NORTH

PHARMACY USP 800 RENOVATION 620A4-18-212

15H

U.S. Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

ACTUAL

NORTH

Phase

BID DOCUMENTS

FULLY SPRINKLERED

Construction and Facilities Management

ENGINEER OF RECORD COMPOUNDING SUITE NEW WORK PLANS

A-101 2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

JBS JDW

QTY

TYPE

MARK DESCRIPTION PRODUCT #

FURNISH

ED BY

INSTALLED

BY REMARK

1 CH1 CHAIR ON CASTERS WITH CUSHIONED BACK N/A VA VA

1 COM COMPUTER, REQUIRES POWER AND DATA N/A VA VA

1 CS500 CLASS II BIOLOGICAL SAFETY CABINET WITH

TOUCHSCREEN MONITOR, DUAL POWER OUTLETS, AND

CLOSED CONTAINMENT SYSTEM FOR HAZARDOUS WASTE.

CS500 VA CON. COORDINATE WITH CORE AND PHARMACY

1 CS600 CLASS II BIOLOGICAL SAFETY CABINET WITH

TOUCHSCREEN MONITOR, DUAL POWER OUTLETS, AND

CLOSED CONTAINMENT SYSTEM FOR HAZARDOUS WASTE.

CS600 VA CON. COORDINATE WITH CORE AND PHARMACY

1 DISP WALL MOUNT MASK, BEARD, HAIR COVER DISPENSER. N/A VA VA

8 DS WALL MOUNTED DOOR SENSOR - HAND WAVED N/A CON. CON.

1 FE SURFACE MOUNTED FIRE EXTINGUISHER N/A CON. CON. LOCATED IN ROOFTOP AHU. SEE MECH. DRAWINGS

FOR ADDITIONAL INFORMATION

1 FEC FULLY RECESSED FIRE EXTINGUISHER CABINET N/A CON. CON.

1 FILE FILE CABINET N/A VA VA

2 HW/EW HAND WASHING SINK WITH EYE WASH - STAINLESS STEEL JPH-ADA-22

24-CT

CON. CON. PLUMBING CONNECTION REQUIRED.

4 INT INTERCOM, HANDS FREE N/A VA CON.

2 IVSH IV SUPPLY STORAGE WIRE SHELVING UNIT ON CASTORS. N/A VA VA

2 LH LADDER HANGER, STAINLESS STEEL N/A VA VA COORDINATE FINAL LOCATION IN THE FIELD WITH

COR.

1 LP IV LABEL MAKER 105SL VA VA

1 NHD WIRE SHELVING UNIT N/A VA VA

1 PASS WALL MOUNTED PASS-THROUGH WINDOW. CAP25WX2

4HX25XD

CON. CON. BASIS OF DESIGN - CLEAN AIR CAP18WHF-SST.

WITH HEPA FILTRATION.

1 PH TELEPHONE N/A VA VA

2 PIV ELECTRONIC CARD READER N/A CON. CON.

2 PPE WIRE RACK ON CASTORS WITH PLASTIC BINS FOR

SUPPLIES

N/A VA VA

2 PT AUTOMATIC PAPER TOWEL DISPENCER, WALL MOUNTED N/A VA CON.

2 REF SINGLE GLASS DOOR MEDICAL GRADE REFRIGERATOR FOR

HD STORAGE.

00926378 VA VA 29.75" W x 35" D x 79.5" H

5 SAN AUTOMATIC HAND SANITIZER DISPENSER N/A VA CON.

2 SH1 WIRE SHELVING, STAINLESS STEEL N/A VA VA

2 SHOE AUTOMATIC SHOE COVER DISPENSER N/A VA VA 12.5" W x 27" D x 8.5" H

2 SOAP AUTOMATIC SOAP DISPENSER, WALL MOUNTED N/A VA CON.

1 SS500 STERILSHIELD 500 BIOLOGICAL SAFETY CABINET WITH

TOUCHSCREEN

SS500 VA CON. COORDINATE WITH CORE AND PHARMACY

5 ST STAINLESS STEEL WORK STOOL WITH FOOTREST N/A VA VA

2 STO MOBILE STORAGE CART N/A VA VA

5 TR HAZARDOUS WASTE RECEPTACLE FOR CONTAMINATED

GARB MATERIALS, STAINLESS STEEL

N/A VA VA

3 WKT1 7' STAINLESS STEEL WORKTABLE N/A VA VA

2 WKT2 6' STAINLESS STEEL WORKTABLE N/A VA VA

1 WKT3 5' STAINLESS STEEL WORKTABLE N/A VA VA

1 WKT4 2'-6" STAINLESS STEEL WORKTABLE N/A VA VA

1 WS STAINLESS STEEL STORAGE CABINET WITH GLASS DOORS

AND SHELVES

N/A VA VA

EQUIPMENT SCHEDULE

1. TO THE GREATEST EXTENTS POSSIBLE, PHARMACY BUFFER AND

COMPOUNDING ROOMS MUST HAVE SMOOTH SURFACES TO PROVIDE FOR

PROPER AND THOROUGH CLEANING. TO THE GREATEST EXTENTS

POSSIBLE, ELIMINATE UNNECESSARY JOINTS AND GAPS IN THE

CONSTRUCTION MATERIALS.

2. SEE SHEET A-500 FOR PARTITION TYPES AND DOOR SCHEDULE.

FINISH SCHEDULE

Number RM NAME

FLOOR

FINISH

BASE

FINISH

WALL FINISH CEILING

FINISH COMMENTSNORTH EAST WEST SOUTH

249B RECEIVING / BREAK

DOWN

RES-3 RES-3 P-1 P-1 P-1 P-1 P-1

250 POS. ANTE RES-3 RES-3 P-1 P-1 P-1 P-1 P-1

250A POS. BUFFER RES-3 RES-3 P-1 P-1 P-1 P-1 P-1

250C AIRLOCK RES-3 RES-3 P-1 P-1 P-1 P-1 P-1

250C-B NEG. ANTE RES-3 RES-3 P-1 P-1 P-1 P-1 P-1

250D NEG. BUFFER RES-3 RES-3 P-1 P-1 P-1 P-1 P-1

P-1 RESINOUS SPECIALTY GLAZED

COATING SYSTEMS FOR WALLS,

CEILINGS, WALLBOARD, AND BLOCK

CMU

RES-3 EPOXY FLOORING

RESINOUS (WITH INTEGRAL COVE

BASE) HIGH PERFORMANCE

DECORATIVE MORTAR FLOORING.

SS-1 STAINLESS STEEL

INTERIOR FINISH NOTES

REFLECTED CEILING NOTES

1. WHERE COLOR IS SHOWN AS BEING SPECIFIC TO ONE MANUFACTURER, AN EQUIVALENT COLOR BY

ANOTHER MANUFACTURER MAY BE SUBMITTED FOR APPROVAL. MANUFACTURERS AND MATERIALS

SPECIFIED ARE NOT INTENDED TO LIMIT THE SELECTION OF EQUAL COLORS FROM OTHER MANUFACTURERS.

THE WORD "COLOR" AS USED HEREIN INCLUDES SURFACE COLOR PATTERN.

2. ALL DOOR FRAMES AND METAL DOORS ARE TO BE PAINTED PTC1.

3. ALL VENTS AND ACCESS PANELS TO BE PAINTED TO MATCH ADJACENT SURFACE WITH ALKYD ENAMEL

PAINT.

4. ALL FLOORING TO BE INSTALLED FLUSH WITH ADJACENT FLOORING FINISH, UNLESS NOTED OTHERWISE.

5. WHERE FLOOR FINISHES CHANGE AT COMMUNICATING ROOMS, PLACE TRANSITION UNDER CENTER OF

DOOR OR FINISHED OPENING.

6. DEMARK LINE TO BE CONTRASTING COLOR TO ADJACENT RESINOUS FLOORING COLOR. COLOR TO BE HIGH

VISIBILITY YELLOW.

1. SEE SPECIALTY DOCUMENTS FOR WORK AFFECTING CEILINGS.

2. COORDINATE SEQUENCE OF SPECIALTY WORK TO ENSURE ORDERLY

INSTALLATION. ALLOW FOR CEILING HANGERS AND ADEQUATE ACCESS TO

VALVES, TURNING VANES, JUNCTION BOXES AND SIMILAR ITEMS THAT MAY

REQUIRE ADJUSTMENT OR SERVICE. INSTALL ABOVE CEILING HEIGHTS

INDICATED.

3. INDEPENDENTLY SUPPORT CEILING MOUNTED EQUIPMENT AND LOCATE

CENTERED ON CEILING TILE. PROVIDE TRIM OR ESCUTCHEONS AROUND

TILE PENETRATIONS.

4. EXCEPT AS INDICATED OTHERWISE, LOCATE SOFFITS AND BULKHEADS 2"

BELOW ADJOINING ACOUSTICAL CEILING.

5. SEE SHEET A-500 FOR CEILING DETAILS.

6. ALL CEILINGS TO BE CLG-1 @ 9'-0" AFF UNLESS NOTED OTHERWISE.

7. "EQ" DIMENSIONS INDICATE EQUAL DIMENSIONS ON A CONTINUOUS

DIMENSION STRINGER AND ARE NOT INTENDED TO REPRESENT EQUAL

DIMENSIONS ACROSS DISCONTINUOUS DIMENSION STRINGERS.

ACCESS PANEL DETAIL

6" = 1'-0"C7 ACCESS PANEL DETAIL

(N)VTR

(N)VTR

(N)VTR

HP HP

HP

HP

HP

H P

H P

RC

HP

HP

HP

HP

HP

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

V

V V

V V

V

V

VT

R VT

R

VT

R

V

V

V

V

V

EF

EF

EF

EF

EF

EF

E F

EF

EF

EF

EF

EF

EF

EF

EF

ECEC

ECEC

SF

PP

PP

HP

RO

OF

B

ELO

W

RD

R D

RD

RD

r 4

RD

r 5

ELEVATOR 01 ELEVATOR 02

STORAGE

H-300

ELE

VATO

R

LO

BBY

C 3-

RD

r 5

D

D

1.7

GPM

HP HP

HP

HP

HP

H P

H P

RC

HP

HP

HP

HP

HP

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

R .V

V

V V

V V

V

V

VT

R VT

R

VT

R

V

V

V

V

V

EF

EF

EF

EF

EF

EF

E F

EF

EF

EF

EF

EF

EF

EF

EF

ECEC

ECEC

SF

PP

PP

HP

RO

OF

B

ELO

W

RD

R D

RD

RD

r 4

RD

r 5

ELEVATOR 01 ELEVATOR 02

STORAGE

H-300

ELE

VATO

R

LO

BBY

C 3-

RD

r 5

K

J

H

G

F

E

D

C

B

A

1 2 3 4 5 6 7

N 9

Q R

T

C.1

D.1

4.13.12.1S

FE

PROJECT LOCATION

A S e rv ic e

D i s a b le d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

Drawing Title

Approved: Project Director

Project Title

Issue Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANT Office of o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

PLAN

NORTH

PHARMACY USP 800 RENOVATION 620A4-18-212

15H

U.S. Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

ACTUAL

NORTH

Phase

BID DOCUMENTS

FULLY SPRINKLERED

Construction and Facilities Management

ENGINEER OF RECORD ROOF PLAN

A-102 2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

JBS JTK

1/8" = 1'-0"F2 ROOF PLAN

1. PERFORM ROOF WORK IN MANNER TO MAINTAIN ANY ROOF WARRANTIES

THAT MAY STILL BE IN EFFECT. COORDINATE WITH COR.

2. PATCH AND REPAIR ROOF MEMBRANE AND SUBSTRATE DAMAGED BY

PERFORMANCE OF WORK INDICATED.

3. PROVIDE FIRESTOPPING AT PENETRATIONS AS REQUIRED TO MAINTAIN

RATED ROOF ASSEMBLY.

4. LEAVE ROOF IN WATERTIGHT CONDITION AT THE END OF EACH WORKDAY.

5. EXCEPT AS INDICATED OTHERWISE, INSTALL NEW FLASHINGS TO MINIMUM

8" ABOVE ROOF LEVEL.

SHEET NOTES

KEYNOTES

# NOTE

140 NEW MECHANICAL ROOF EQUIPMENT; REF: MECHANICAL DRAWING M-131 FOR

ADDITIONAL INFORMATION

145 SOLID EQUIPMENT COVER; REF. MECHANICAL FOR ADDITIONAL INFORMATION

146 NEW ROOF WALKWAY PADS TO MECHANICAL ACCESS AREAS; REF. MECHANICAL

SHEET M131 FOR ADDITIONAL INFORMATION.

147 NEW 42" RAILING BY GC

148 PROVIDE NEW SURFACE MOUNTED FIRE EXTINGUISHER CABINET INSIDE NEW

ROOFTOP AHU. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.

151 ROOF ACCESS SIGNAGE TO BE LOCATED ON THE INTERIOR SIDE OF ROOF ACCESS

DOOR LEAVING ELEVATOR LOBBY C3-01 AND READ, "NO ROOF ACCESS WITHOUT

PRIOR NOTIFICATION TO PHARMACY." FINAL LOCATION DETERMINED BY V.A.

ROOF PROTECTION NOTES

1. PROTECT EXISTING ROOFING FROM DAMAGE OR DETERIORATION

DURING PERFORMANCE OF THE WORK.

2. PROVIDE BARRIERS AS REQUIRED TO PREVENT TRAFFIC ON ROOFING.

IF ROOF MUST BE ACCESSED, PROVIDE PROTECTIVE COVERING

SUFFICIENT TO PREVENT PUNCTURES, WEAR AND OTHER DAMAGE TO

ROOFING.

3. PERFORM NO WORK ON ROOFING THAT MAY JEOPARDIZE OR VOID

EXISTING WARRANTIES.

4. REPAIR OR REPLACE ROOFING DAMAGED BY PERFORMANCE OF THE

WORK. PROVIDE ANY REPAIRS OF REPLACEMENTS IN MANNER TO

PROTECT EXISTING WARRANTIES.

5. USE MATERIALS, METHODS AND SYSTEMS TO MATCH EXISTING AND

AS APPROVED BY ORIGINAL ROOFING MANUFACTURER.

ROOFELEVATORADMIN. ANTEFREEZER &SECUREDROLLINGRECEPTION RECEIVINGB

PROJECT LOCATION

REF

WKT1

WS

PT-1

EPY-1

PASS

TR

250B-A

INT

SAN

DS

EPY-1

PT-1

CS500

STO

ST

S.S. ANGLE

SHROUD;TERMINATES

AT TOP OF HOOD

EXHAUST RISER

LH

NHD

EPY-1

PT-1

LP

CH1

250B-AIVSH

PT

SOAP

HW/EW

FILE

INT

EPY-1

PT-1

SHOE

SAN

PH

WKT2

COM

DS

NHD

REF250-AFEC SAN PPE

ST

EPY-1

PT-1

WKT4

TR

250A-A

PPE

HW/EW

ST

PT

EPY-1

PT-1

WKT4

DS

A

LEVEL 3

30' - 0"

LEVEL 2

20' - 0"

MASONRY VENEER WALL INTERLOCKING SYSTEM WITH 9 GA.

WIRE REINFORCING AND WIRE TIE CONSTRUCTION. BRICK INFILL

TO MATCH EXISTING ADJACENT. SAW-TOOTH IN NEW BRICK TO

CREATE EVEN TRANSITION BETWEEN NEW AND EXISTING BRICK

6" METAL STUD

M

IN

6" 9'

0"

BATT INSULATION FILL

1/2" PLYWOOD SHEATHING

CONT WEATHER RESISTANT BARRIER.

TIE-IN TO EXISTING WRB SYSTEM.

6" METAL STUD FURRING

EXISTING WALL CONSTRUCTION;

MASONRY VENEER WALL, 1" RIGID

INSULATION, 8" CMU BLOCK, METAL

STUD WALL AND GYPSUM BOARD FINISH

INTERIOR GYP BD FINISH

3'

0" 4'

0"

2'

0"

GWB ON SUSPENDED CEILING GRID SYSTEM

250C-B

TR

PT-1

DS

PPE

SHOE

EPY-1

PT-1

EPY-1

PT-1

PT

SOAP

HW/EW

SAN

TR

INT

EPY-1

PT-1

250C-A

DS

EPY-1

PT-1

WKT3 TR

CS600

S.S. ANGLE

SHROUD;TERMINATES AT TOP

OF HOOD EXHAUST RISER

250A-A

DISP

TR

SANINT

EPY-1

PT-1

DS

TR

EPY-1

PT-1

WKT1

LH

SS500

EPY-1

PT-1

SS500

WKT1

CLEAN AIR PASS THRU

SEE FLOOR PLAN FOR PARTITION TYPE

CONT. SEALANT AT PERIMETER, BOTH SIDES, TYP.

CONT. SEALANT AT PERIMETER, BOTH SIDES, TYP.

STAINLESS STEEL FLUSH MOUNT HINGES

RECEIVING/BREAK DOWNNEG. ANTE

METAL STUD HEADER

T O

P A

S S

T H

R O

U G

H S

U R

F A

C E

3'

2"

PASS

INT

EPY-1

PT-1

WKT2

EXHAUST DUCT RISER

CS500 HOOD

PARTITION AS SCHED.

APPROX. POWER CORD

LOCATION

SEALANT, CONT. EACH

SIDE

ADHESIVE APPLIED S.S. SHEET

METAL ANGLE; ANGLES TO BE ON

ALL (4) SIDES OF EXHAUST RISER

1' - 1"

2"

NOTE: STAINLESS STEEL SHEET METAL ANGLE DEPTH TO BE DETERMINED IN FIELD WHEN

HOODS ARE ON SITE.

A S e rv ic e

D i s a b le d

Ve t e r an Owned S m a l l B u s iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0116

Drawing Title

Approved: Project Director

Project Title

Issue Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANT Office of o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

NO. DESCRIPTION DATE

PLAN

NORTH

PHARMACY USP 800 RENOVATION 620A4-18-212

15H

U.S. Department of Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

ACTUAL

NORTH

Phase

BID DOCUMENTS

FULLY SPRINKLERED

Construction and Facilities Management

ENGINEER OF RECORD INTERIOR ELEVATIONS,SECTIONS & DETAILS

A-200 2022-08-24

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

JBS JDW

INTERIOR ELEVATIONS

1/4" = 1'-0"A1 NEG. ANTE RM - NORTH

1/4" = 1'-0"A2 NEG. ANTE RM - SOUTH

1/4" = 1'-0"C1 NEG. BUFFER RM - SOUTH

1/4" = 1'-0"B1 POS. ANTE RM - EAST

1/4" = 1'-0"B2 POS. ANTE RM - NORTH

1/4" = 1'-0"B4 POS. ANTE RM - SOUTH

1/4" = 1'-0"B5 POS. ANTE RM - WEST

3/4" = 1'-0"C7 WALL INFILL SECTION AT EXISTING WINDOW

1/4" = 1'-0"A3 NEG. ANTE RM - WEST

1/4" = 1'-0"A5 AIRLOCK - NORTH

1/4" = 1'-0"A6 AIRLOCK - SOUTH

1/4" = 1'-0"C2 NEG. BUFFER RM - EAST

1/4" = 1'-0"C3 NEG. BUFFER RM - NORTH

1/4" = 1'-0"D1 POS. BUFFER RM - EAST

1/4" = 1'-0"E1 POS. BUFFER RM - NORTH

1/4" = 1'-0"D2 POS. BUFFER RM - SOUTH

1/4" = 1'-0"E2 POS. BUFFER RM - WEST

SECTIONS

3/4" = 1'-0"E7 PASS THRU SECTION

1/4" = 1'-0"C5 RECEIVING/ BREAK DOWN-NORTH

QTY

TYPE

MARK DESCRIPTION PRODUCT #

FURNISH

ED BY

INSTALLED

BY REMARK

1 CH1 CHAIR ON CASTERS WITH CUSHIONED BACK N/A VA VA

1 COM COMPUTER, REQUIRES POWER AND DATA N/A VA VA

1 CS500 CLASS II BIOLOGICAL SAFETY CABINET WITH

TOUCHSCREEN MONITOR, DUAL POWER OUTLETS, AND

CLOSED CONTAINMENT SYSTEM FOR HAZARDOUS WASTE.

CS500 VA CON. COORDINATE WITH CORE AND PHARMACY

1 CS600 CLASS II BIOLOGICAL SAFETY CABINET WITH

TOUCHSCREEN MONITOR, DUAL POWER OUTLETS, AND

CLOSED CONTAINMENT SYSTEM FOR HAZARDOUS WASTE.

CS600 VA CON. COORDINATE WITH CORE AND PHARMACY

1 DISP WALL MOUNT MASK, BEARD, HAIR COVER DISPENSER. N/A VA VA

8 DS WALL MOUNTED DOOR SENSOR - HAND WAVED N/A CON. CON.

1 FE SURFACE MOUNTED FIRE EXTINGUISHER N/A CON. CON.