This document is a pricing template and specification sheet for a diesel generator system with automatic transfer switch (ATS) components.
The primary product specified is a C80D6C diesel genset rated at 60Hz, 60kW, configured for U.S. EPA stationary emergency applications with standby power (ESP) duty rating. The genset includes EPA Tier 3 emissions certification and NSPS CI stationary emergency compliance. Key generator components include a PowerCommand 2.3 controller, 60Hz alternator with full output capability at 105°C and 40°C ambient temperatures with increased motor starting capacity (IMS), and an aluminum sound-attenuated Level 1 enclosure with exhaust system. The unit features a green aluminum enclosure rated for 180 MPH wind loads (ASCE7-10 standard), housing-ready skidbase, and a 48-hour minimum diesel fuel tank with dual-wall basic construction. Engine specifications include an electronic isochronous governor, 12VDC starter motor, normal-duty air cleaner, battery charging alternator with 6-amp regulated charging, high ambient air temperature cooling with ship-fitted radiator, and a 2-year base warranty. Fluids and maintenance items including 50/50 antifreeze/water coolant mixture, cold ambient coolant heater, and engine oil are specified.
The Automatic Transfer Switch (ATS) is specified as a CBLC bypass transfer switch with PowerCommand control, configured for 150A/225A/260/300/400/600A capacity with a CBL225 model rated at 225 amps. The ATS meets UL 1008/CSA certification standards, operates at 208 volts AC in a 3-phase, 4-wire configuration with delayed transition transfer mode, includes Type 4X cabinet construction with 4 poles, utilizes PC80 control with premium customer I/O interface, and carries a 2-year comprehensive warranty. The unit is designed for utility-to-genset application with 12VDC genset starting battery capability.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation - FA441726Q0198.pdf | ||
| 100kW with ATS.pdf | ||
| 60kW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATS
CBLC, Bypass Transfer Switch-Power Command: 150A/225A/260/300/400/600A CBL225, Transfer Switch-Bypass, PowerCommand, 225 Amp Listing-UL 1008/CSA Certification Application-Utility to Genset Cabinet-Type 4X Poles-4 System - 3 Phase, 4-Wire (Solid or Switched Neutral) Transfer Mode-Delayed Transition Frequency-60 Hz Voltage-208 Volts AC PC80 Control Premium Customer I/O Genset Starting Battery-12VDC
Transfer Switch Warranty - 2 Year Comprehensive