This document is a technical specification sheet for a diesel generator system and associated automatic transfer switch (ATS) equipment.

The primary equipment specified is a C100D6C diesel genset rated at 60Hz and 100kW capacity for U.S. EPA stationary emergency application, designated for standby power (ESP) duty. The genset includes comprehensive features including EPA Tier 3 emission certification (NSPS CI Stationary Emergency), UL 2200 listing, NFPA 110 Type 10 Level 1 capability, a 48-hour minimum diesel fuel tank with dual wall basic construction, 120V/208V three-phase four-wire electrical configuration, and an aluminum sound-attenuated Level 1 enclosure rated for 180 MPH wind load (ASCE7-10). The engine package includes an electronic isosynchronous governor, 12V DC starter motor, battery charging alternator, 6-amp regulated battery charger, high-ambient-air-temperature radiator, and 50% antifreeze/50% water coolant mixture. Additional standard components include fuel water separator, mechanical fuel gauge, coolant heater for cold ambient operation, oil pressure gauge, AC output analog meters, emergency stop switch, PowerCommand 2.3 controller, and comprehensive warranty coverage (2 years base). The quantity requested is one unit.

The ATS specification details a CBLC bypass transfer switch rated at 400 amperes with PowerCommand control, UL 1008/CSA certification, Type 4X cabinet construction, configured for three-phase four-wire utility-to-genset application at 60Hz with PC80 control and delayed transition transfer mode operation.

View the file

Other files

File Type Posted
Solicitation - FA441726Q0198.pdf PDF
60kW with ATS.pdf PDF
60kW.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATS

CBLC, Bypass Transfer Switch-Power Command: 150A/225A/260/300/400/600A

CBL400, Transfer Switch-Bypass, PowerCommand, 400 Amp

Listing-UL 1008/CSA Certification

Application-Utility to Genset

Poles-4

Cabinet-Type 4X

System - 3 Phase, 4-Wire (Solid or Switched Neutral)

Frequency-60 Hz

PC80 Control

A078-7 Transfer Mode-Delayed Transition