6 Drawings B35 HVAC.pdf
PDF 1 MB Posted
- Solicitation number
- 36C25924Q0064
About this file
This document package includes construction drawings and specifications for HVAC remodel work at a Department of Veterans Affairs medical center in Sheridan, Wyoming, as well as the corresponding federal contract opportunity notice.
The drawings detail proposed HVAC system upgrades for Building 35, including replacement of an exhaust hood and fan in Room 224, extension of direct digital controls and building automation systems, and installation of new roof-top HVAC equipment. Specifications require furnishing and installing materials in accordance with NFPA and NEC standards, as well as completion of electrical, insulation, and ductwork. The related federal contract opportunity is a solicitation from the VA Veterans Health Administration seeking offers for the project, identified as solicitation number 36C25924Q0064 and opportunity number VA-24-00006694. Responses are due to the contracting office in Sheridan.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25924Q0064_Revised Bid Schedule_ Page 5.docx | DOCX document | |
| 36C25924Q0064 0002.docx | DOCX document | |
| 36C25924Q0064 0001.docx | DOCX document | |
| Asbestos Report B35.pdf | ||
| TF-35 Low Side.jpg | JPG image | |
| TF-35 Low Side Open.jpg | JPG image | |
| S02-3-10-2021 Past Performance Questionnaire_Blank_Fillable PDF.pdf | ||
| 36C25924Q0064_2.docx | DOCX document | |
| 6 Specifications 24-126 B35 HVAC.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AREA MAP
VA SITE MAP
14 13
303132
55110
41 42
23 24
71N
AREA OF
WORK
B35 HVAC REMODEL
SHEET INDEX
NORTH
NORTH
VA
HEALTHCARE
AutoCAD SHX Text COVER - AREA AND SITE MAPS AND SHEET INDEX M100 - BASEMENT, FIRST, AND SECOND FLOOR HVAC PLANS
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text
VA FORM 08-6231, OCT 1978
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Initials
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text Project Title
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Location
AutoCAD SHX Text
SHERIDAN, WY
AutoCAD SHX Text
B35 HVAC REMODEL
AutoCAD SHX Text
JUL 13, 2023
AutoCAD SHX Text 666-24-126
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA
AutoCAD SHX Text
HEALTHCARE
AutoCAD SHX Text Office of Facilities Management
AutoCAD SHX Text
SP
AutoCAD SHX Text
STEPHEN PETZOLD CHIEF - FACILITIES MANAGEMENT SERVICES PHONE: (307) 675-3671
AutoCAD SHX Text
AREA AND SITE MAPS AND SHEET INDEX
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COVER
AutoCAD SHX Text
LAS
1 PROVIDE EXPOSED CEILING MOUNTED EF-1 AND 8" EXHAUST HOOD WITH
BACK DRAFT DAMPER. CONNECT TO EXISTING POWER. PROVIDE
DISCONNECT AT UNIT. PROVIDE 10 MINUTE TIMER. INTERLOCK WITH ROOM
LIGHT SWITCH. INSULATE EXHAUST DUCT WITH 1" FIBERGLASS WITH ALL
SERVICE JACKET (ASJ) AND SELF LAPPING SEAMS. PROVIDE PVC
INSULATION COVER AND FITTING COVERS.
REMOVE WIRE MESH FROM WALL.
INSULATE EXTERIOR DUCTWORK WITH 2" CLOSED CELL INSULATION.
COVER WITH TEXTURED ALUMINUM TO MATCH PRODUCT USED ON
BUILDING 37. SEAL WEATHER PROOF. SUPPORT DUCTWORK ON GROUND
WITH UNISTRUT STAND 3'-0" O.C. MAXIMUM. SUPPORT DUCTWORK FROM
WALL WITH UNISTRUT FRAME SURROUNDING DUCT EVERY FIVE FEET.
1) EXHAUST FAN EF-1 SHALL OPERATE CONTINUOUS DURING OCCUPIED
TIME, AND BE OFF DURING UNOCCUPIED PERIOD.
2) EXTEND DDC CONTROLS FROM BUILDING 37 THROUGH UNUSED
ELECTRICAL CONDUIT.
3) EXTEND ENSEMBLE CONTROLS SYSTEM AND USER INTERFACE TO
CONTRACTOR PROVIDED VA COMPATIBLE PC IN ROOM 224 BUILDING 5.
1) ELECTRICAL WORK SHALL MEET NFPA 70E AND NEC REQUIREMENTS.
2) PROVIDE 3/8" STEEL BARS SPACED 9" OC, IN 2"X 1/4" ANGLE IRON
FRAME, IN DUCT PENETRATIONS THROUGH EXTERIOR WALLS
3) TRIM DUCT WINDOW PENETRATIONS WITH WHITE ANODIZED
DIFFUSER REGISTER AND GRILLE SCHEDULE
EQUIP MFGR MODEL SP LOSS NOTES
TAG NUMBER MAX CFM IN WC COLOR
S-1 KRUEGER 880H 3620 0.25" WHITE 1, 2
R-1 KRUEGER S80H 3620 0.25" WHITE 1, 2, 3, 4
NOTES: 1. MANUFACTURER INFORMATION IS SHOWN FOR BASIS OF DESIGN ONLY,
APPROVED MANUFACTURERS MAY SUBMIT.
2. DUCT MOUNTED
3. PROVIDE 4" DEEP DUCTWORK PLENUM ABOVE OBD AND GRILLE.
4. PROVIDE OBD.
ROOFTOP UNIT SCHEDULE
HEAT HEAT PUMP COOLING
EQUIP MFGR MODEL TYPE TOTAL ESP MIN KW EAT LAT BTUH EAT LAT HEAD BTUH EAT LAT SP FILTERS MCA MOP VOLTAGE NOTES
TAG CFM (IN) OA (°F) (°F) (°F) (°F) LOSS (°F) (°F) LOSS AMPS AMPS V/PH/HZ
RTU-1 TRANE WSJ300A3S0N HEAT PUMP 10,000 0.5 0 36 65 78 253,030 65 92 <10 FT 255,290 80 56 0.25" MERV 13 213 225 208/3/60 1,2,3,4,5,6
NOTES: 1. PROVIDE INTEGRAL VARIABLE FREQUENCY DRIVE, AND UNIT MOUNTED DISCONNECT SWITCH WITH SINGLE POINT CONNECTION.
2. PROVIDE ECONOMIZER DRY BULB 0-100% WITH BAROMETRIC RELIEF.
3. MANUFACTURER INFORMATION IS SHOWN FOR BASIS OF DESIGN ONLY, APPROVED MANUFACTURERS MAY SUBMIT.
4. PERFORMANCES BASED ON -30°F OAT HEATING, AND 100°F OAT COOLING. UNIT CASING SHALL BE DOUBLE WALL WITH INSULATION.
5. PROVIDE CO2 SENSOR FOR OUTSIDE AIR VOLUME CONTROL
6. PROVIDE WIRE, CONDUIT, AND REQUIRED BREAKER AT NEAREST PANEL WITH SPACE AVAILABLE. INSTALL ELECTRICAL WORK PER NEC.
TF-35
4 PROVIDE LOW-E, DOUBLE PANE, INSULATED FRAME, WHITE VINYL WINDOW
TO FILL WINDOW SPACE BELOW DUCTWORK. APPROXIMATELY 36x36.
FIELD VERIFY ACTUAL SIZE.
ALUMINUM SHEET METAL INSIDE AND OUTSIDE.
4) PROVIDE MEANS PROCURE AND INSTALL FOR A COMPLETE
WORKING INSTALLATION.
5 CUT FLOOR JOISTS AS REQUIRED. DOUBLE FLOOR JOIST ON EACH SIDE
AND HANG FROM HEADER JOIST ON EACH END. USE SIMPSON HANGERS.
6 PROVIDE VOLUME DAMPER WITH LOCKING QUADRANT IN DUCT.
7 RELOCATE STEAM UNIT HEATER. EXTEND EXISTING PIPING, ELECTRICAL
WIRING, AND THERMOSTAT WIRING.
1 PROVIDE 600 AMP, 3PH, 60 HZ 100 BREAKER DISTRIBUTION PANEL. T DDC TEMPERATURE SENSOR
2 PROVIDE 3" PVC PULL BOX TO MATCH EXISTING PULL BOX
INSTALLATIONS. CORE DRILL THROUGH WALL. SEAL WEATHERPROOF.
REVERSE ACTING THERMOSTAT
SUPPLY DUCT UP
3 PROVIDE SCH 40 3" PVC CONDUIT FROM PULL BOX TO TF-35 208V SIDE.
INSTALL A MINIMUM OF 2'-0" DEEP OR DEEPER AS REQUIRED BY THE
NEC. BED AND COVER WITH 4" THICK CONCRETE. PROVIDE WIRE IN
CONDUIT FOR 208V, 3PH, 600 AMP SERVICE. CUT AND PATCH
PAVEMENT TO MATCH EXISTING.
SUPPLY DUCT DOWN
RETURN DUCT UP
RETURN DUCT DOWN
4 RE-FEED THREE MAIN 100 AMP 208 VOLT CIRCUITS FROM B37 FROM
EXISTING J-BOX LOCATION TO NEW DISTRIBUTION PANEL. PROVIDE
CONDUIT. PROVIDE NEW J-BOX FOR EACH CIRCUIT. REMOVE
EXISTING WIRE AND TURN OVER TO VA FOR REUSE. INSTALL NEW
PULL STRING IN EXISTING CONDUIT.
5 PROVIDE PULL BOX FOR DDC HVAC CONTROLS. MOUNT ON
FOUNDATION WALL. EXTEND 208v/3PH/60HZ WIRE AND CONDUIT TO
NEW DISTRIBUTION PANEL. PROVIDE CONDUIT TO RTU-1 MOUNTED
ON GALVANIZED STEEL UNISTRUT.
TO
B37 4
8"Ø EF-1 34x14
3 1 UP
REVERSE
ACTING
T'STAT
T R-1 36x36
RTU-1
RTU-1
S-1 36x26
30x36
36x30
UP
34x14
UP 6
TO
B37 4
TYPICAL
EACH
FLOOR
EF-2
15'-105" 8
22x22
DN
36x14
R-1
36x36 S-1 3300 36x28
22x22
DN
RELOCATE STEAM UNIT
HEATER TO MISS
SUPPLY AIR DUCT
36x30 DN 22x22 UP 34x14
DN
R-1 36x36
S-1 36x30
36x30 DN 22x22 UP
34x14
DN 6
34x24 5 x1 x2 x3 x1
EXHAUST FAN SCHEDULE
EQUIP MFGR MODEL ESP NOTES
TAG NUMBER CFM IN WC HP FLA V/PH/HZ
EF-1 BROAN L100E 130 0.25" 0.1 0.3 120/1/60 1, 2, 3
EF-2 VES ENVIRO 101308 1,080 0.25" 0.1 1.35 120/1/60 1, 2, 4, 5, 6
NOTES: 1. MANUFACTURER INFORMATION IS SHOWN FOR BASIS OF DESIGN ONLY, APPROVED MANUFACTURERS
MAY SUBMIT.
2. PROVIDE BREAKER, CONDUIT, AND WIRE, PER NEC, TO NEAREST PANEL WITH REQUIRED CAPACITY.
3. MOUNT ON WALL WITH ADJUSTABLE DIRECTION PIVOTING FRAME MADE OF UNISTRUT AND BOLTS.
4. PROVIDE ALUMINUM ENCLOSURE WITH 1/4" HARDWARE CLOTH EACH SIDE.
5. PROVIDE THREE FANS. ONE FOR EACH FLOOR.
6. PROVIDE VARIABLE SPEED CONTROL AND REVERSE ACTING THERMOSATAT
| B35 HVAC Cover |
| Sheets and Views |
| 22x34 |
B35 HVAC Plans M100