595-19-340_BID-SET_DRAWINGS.pdf

PDF 10 MB Posted

Attached to
Y1DB--Renovate for PET/CT Scanner, Construction Project # 595-19-340
Solicitation number
36C24421B0005
Issued by

About this file

This federal contract opportunity is for renovation work to install a PET/CT scanner at the Lebanon VA Medical Center in Lebanon, Pennsylvania. The solicitation number is 36C24421B0005 and seeks bids for Construction Project #595-19-340 to perform renovations in accordance with the statement of work, specifications, drawings, and applicable federal, state and local codes. This is a 100% set-aside for verified Service-Disabled Veteran-Owned Small Businesses, with a bid submission deadline of February 8, 2021 at 9:30 AM. The construction value is between $250,000 and $500,000, the NAICS code is 236220 for commercial and institutional building construction, and the small business size standard is $39.5 million. The Davis Bacon wage determination PA20200093 applies. Bids must be submitted according to the instructions in the solicitation, which is available on SAM.gov where any updates or amendments will also be posted. The Department of Veterans Affairs Veterans Health Administration VISN 4 is the contracting agency.

View the file

Other files

File Type Posted
36C24421B0005.docx DOCX document
Wage Determination PA2020093.pdf PDF
595-19-340_BID-SET_SPECS-REV1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A-#

#X#

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

BID SET

GENERAL NOTES

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A

FURRED CHASE, ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL TILE CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR

INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM,

TERMINAL UNITS, FILTERS, COILS, ETC. LOSS FOR FILTERS SHALL BE FOR FILTERS AT

50% LOADING.

4. FOR TYPICAL HYDRONIC AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE

STANDARD EQUIPMENT DETAILS.

5. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.

6. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO

PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR COORDINATION OF

CEILING DIFFUSERS, REGISTERS, AND GRILLES WITHIN CEILING.

PLUMBING

MECHANICAL AND PLUMBING SYMBOLS AND ABBREVIATIONS

ABBREVIATIONSDUCT SYMBOLS

HVAC PIPING

FIRE PROTECTION SYSTEM

PIPE FITTINGS

VALVES

TEMPERATURE CONTROL/MONITORING

DRAWING NOTATIONSMEDICAL SECTIONS AND DETAILS

REFRIGERATION VALVES/FITTINGS

SANITARY LINE

VENT LINE

HOT WATER RETURN

HOT WATER

COLD WATER

STRAINER

FLANGED CONNECTION

UNION

END CAP

CONCENTRIC REDUCER

TEE DOWN

TEE UP

ELBOW DOWN

ELBOW UP

(DOWN IN ARROW DIRECTION)

PIPE PITCH ARROW

PRESSURE GAUGE

AUTOMATIC AIR VENT

FLOW ARROW

ELBOW

TEE

CLEANOUT FLOOR

PIPE SLEEVE

ECCENTRICAL REDUCER

THERMOMETER

CO

T

REFRIGERANT DISCHARGE

CHILLED WATER SUPPLY

CHILLED WATER RETURN

HEATING WATER SUPPLY

HEATING WATER RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

CHWS

CHWR

HR

HS

RD

RL

RS

SAFETY/PRESSURE RELIEF VALVE

FLOW CONTROL VALVE

MAKEUP WATER VALVE

PRESSURE REDUCING VALVE

CHECK VALVE

BALANCING VALVE

VERTICAL SHUT-OFF/NEEDLE VALVE

SHUT-OFF VALVE

AUTOMATIC AIR VENT

TEMP/PRESSURE RELIEF VALVE

MOTORIZED VALVE

3-WAY MOTORIZED VALVE

THROTTLING VALVE

CHARGING VALVE

SIGHT GLASS

FILTER-DRYER

THERMOSTATIC EXPANSION VALVE

EVAPORATOR PRESSURE REGULATOR

MANUAL REFRIGERATION VALVE

S

D

RETURN OR EXHAUST DUCT DOWN

RETURN OR EXHAUST DUCT UP

FIRE DAMPER (FD) IN DUCT

SUPPLY DUCT DOWN

VOLUME DAMPER

SUPPLY DUCT UP

ACCESS PANEL

COMBINATION FIRE/SMOKE DAMPER

(FSD) IN DUCT

SMOKE DAMPER (SD) IN DUCT

INTERNAL LINED DUCT

AP

SD

FSD

FD

PENDANT SPRINKLER HEAD

UPRIGHT SPRINKLER HEAD

FIRE PROTECTION PIPINGF

OXYGEN

VACUUM LINE

NITROUS OXIDE

NITROGEN

OXYGEN OUTLET

MEDICAL AIR OUTLET

NITROGEN OUTLET

NITROUS OXIDE OUTLET

VACUUM OUTLET

SLIDE

MEDICAL AIR

N

NO

V

MA

S

V

NO

N

MA

FSD COMBINATION FIRE/SMOKE DAMPER

FD FLOOR DRAIN OR FIRE DAMPER

EXTG, E. EXISTING

ET EXPANSION TANK

ER EXHAUST REGISTER

ELEV ELEVATION

ELEC ELECTRICAL

EF EXHAUST FAN

EG EXHAUST GRILLE

EAT ENTERING AIR TEMPERATURE

EA EXHAUST AIR

DIFF DIFFUSER

DIA DIAMETER

DB DRY BULB

CW COLD WATER

COND CONDENSATE

CO CLEANOUT

CL CENTERLINE

BV BALANCE VALVE

BTU BRITISH THERMAL UNIT

AFF ABOVE FINISHED FLOOR

AD AREA DRAIN

GEN GENERAL

GC GENERAL CONTRACTOR

LAT

WB

W

VTR

VS

VFD

VAV

TYP

TG

SS

SR

SG

SD

SAN

SA

RR

RG

RD

RA

PLBG

OD

OA

NO

NC

MC

MECH

RETURN GRILLE

ROOF DRAIN

RETURN AIR

PLUMBING

OUTSIDE DIAMETER

OUTSIDE AIR

NORMALLY OPEN

NORMALLY CLOSED

MECHANICAL CONTRACTOR

MECHANICAL

LEAVING AIR TEMPERATURE

RETURN REGISTER

STAINLESS STEEL

SUPPLY REGISTER

SUPPLY GRILLE

SMOKE DAMPER

SANITARY

SUPPLY AIR

VARIABLE FREQUENCY DRIVE

VARIABLE AIR VOLUME

TYPICAL

TRANSFER GRILLE

WET BULB

WASTE

VENT THRU ROOF

VENT STACK

TEMPERATURE SENSOR

ROOM THERMOSTAT (COOL)

ROOM THERMOSTAT (HEAT/COOL)

ROOM THERMOSTAT (HEAT)

FLOW SWITCH

T

H,C T

T

H T

FS

C

TO EXISTING

CONNECTION

WORK

EXISTING

DENOTED

NEW WORK

DENOTED

8"E.

DUCT

PIPE OR

SIZE OF

EXISTING

DENOTED

SECTION OR ELEVATION

NUMBER

SECTION OR ELEVATION

SHEET NUMBER OF

DETAIL (LETTER)

DETAIL LOCATION

SHEET NUMBER OF

M

M

V

CLEANOUT

S

DIFFUSER OR REGISTER TAG

A-#

#Ø

AIRFLOW (CFM)

RECTANGULAR DUCT

CONNECTION SIZE

DIFFUSER OR REGISTER TAG

AIRFLOW (CFM)

ROUND DUCT CONNECTION

SIZE

BALANCE VALVE

MBH 1000 BTU/HOUR

ID INDIRECT DRAIN

HTG HEATING

HW HOT WATER

HWR HOT WATER RECIRCULATE

CU CONDENSER UNIT

EVAP EVAPORATOR

V VENT

SPLIT SYSTEM AIR CONDITIONER - INDOOR UNIT SCHEDULE

TAG LOCATION ROOM MODEL NOMINAL

TONNAGE TYPE

CONNECTED TO

AIR FLOW RATE

DRY/WET (CFM)

COOLING CAPACITY ELECTRICAL

DIMENSIONS

WXHXD WEIGHT NOTES

COND. UNIT ZONE CHANGE OVER

DEVICE TOTAL BTU/H SENSIBLE BTU/H ENTERING AIR °F

DB/°F WB

POWER SUPPLY

VOLTAGE - PHASE

MIN CIRCUIT

(AMPS)

MAX OVERCURRENT

PROTECTION (AMPS)

SSAC-E4 PET EQUIPMENT

ROOM

PET EQUIPMENT

ROOM MSY-GL18NA 1.5 WALL MOUNTED

UNIT SSAC-C4 NO 646/581 18,000 12,802 78.8/65.5 208-230V 1 PH 1 15 37X10X12 28 1, 2, 3, 4

OUTDOOR CONDENSER UNIT SCHEDULE

TAG LOCATION ROOM MODEL NOMINAL

TONNAGE

COOLING

CAPACITY

BTU/H

AIRFLOW

RATE (CFM)

REFRIGERANT

CHARGE

CONNECTION

RATIO

VOLTAGE

PHASE

MIN CIRCUIT

(AMPS)

MAX OVERCURRENT

PROTECTION (AMPS)

RUNNING

CURRENT(RLA) SEER DIMENSIONS

WXHXD WEIGHT REFRIGERANT NOTES

SSAC-C4 ROOF PET EQUIPMENT

ROOM MUY-GL18NA 1.5 22,000 1,691 3 125 208-230V 1PH 14 15 15.3 20.5 34X35X13 121 R410 1, 2, 3

ROOFTOP EXHAUST FAN

TAG LOCATION SERVICE MODEL DESIGN CFM TYPE ROOF OPENING OPENING

WITH CURB MOTOR HP BHP DIRECT

DRIVE RPM TOTAL SP V/PH/HZ MIN CIRCUIT

AMPS

DIMENSIONS

WXHXD WEIGHT NOTES

EF-3 ROOF PET/CT SCANNER

ROOM CUBE-099 1065 DIRECT DRIVE 14.5X14.5 19X19 VG-1/4 0.23 1725 0.25 115 /1/60 4.2 25X28X19 58 1

VARIABLE AIR VOLUME BOX

TAG LOCATION SERVICE MODEL DESIGN CFM OUTLET INLET

STATIC

PRESSURE

INLET

STATIC

PRESSURE

DOWN

STATIC

PRESSURE

MIN

MBH V/PH/HZ EAT EWT LAT LWT APD GPM WPD COIL ROWS V/PH/HZ NOTES

TU1- G08 G013 PET/CT SCANNER

ROOM DESV-10 800 14X12.5 10 1 0.25 0.38 18.3 115 /1/60 55 180 75 140 0.37 0.9 0.1 2 115 /1/60 1, 2, 3

NOTES:

1. PROVIDE INTEGRAL FLOW RING TUPE AIR FLOW MEASUREMENT SENSOR ON VAV INLET.

2. PROVIDE WALL MOUNTED THERMOSTAT.

3. PROVIDE STRAINER AND MOTORIZED CONTROL VALVES ON HWS AND BALANCE VALVE ON HWR.

NOTES:

1. PROVIDE WITH VFD MOUNTED IN NEMA ENCLOSURE.

NOTES:

1. PROVIDE WALL MOUNTING BRACKET.

2. INTEGRAL DX, ELECTRIC CONDENSATE PUMP

3. WIRELESS REMOTE CONTROLLED THERMOSTAT.

4. PROVIDE SOLENOID VALVE AND THERMAL EXPANSION VALVE.

NOTES:

1. PROVIDE PRE-ENGINEERED ROOF SUPPORT.

2. COORDINATE WITH ARCHITECTURAL DRAWINGS ROOF PENETRATIONS AND ROOF SUPPORT FLASHING.

3. PROVIDE ISOLATION VALVES, STRAINERS, AND FILTER.

VFD SCHEDULE

TAG SERVICE LOCATION ENCLOSURE NOTES

V-EF-3 EF-3 PANEL ROOM NEMA 12 1

NOTES:

1. VFD PROVIDED BY MANUFACTURER. REFER TO MECHANICAL DRAWINGS

AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

DIFFUSER, REGISTER, & GRILLE SCHEDULE

TAG TYPE DUCT CONN. GRILLE MATERIAL FINISH/ COLOR BLADES DEFLECTION MODEL MANUFACTURER

R-2 SUPPLY 8X8 12X12 ALUMINUM WHITE 45° DEFLECTION DOUBLE 310FS TITUS

SYMBOLS

DEMOLITION PLAN KEYNOTE

POINT OF DISCONNECTION

POINT OF CONNECTION

NEW PLAN KEYNOTE

G030

STAIR

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

ELEC ROOM

G018

NM SUITE

CORRIDOR

G002

WAITING

ROOM

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G020

STRESS LAB

G014

CAMERA

G015

CAMERA G012

CONTROL

ROOM

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL

G031

PATIENT

CORRIDOR

G011

G034IT CLOSET

CHANGE

3" FP

2" FP

2" FP

1 1/2" FP

2" FP

3/4"

13/4"

3/4"

3/4" 3/4"

3/4" 3/4"

1" 3/4"3/4"

3/4"3/4"

3/4"

1 1/4"

1" 1"

1"

3/4"

1"1"1"

3/4"3/4"3/4"3/4"

DEMOLITION PLAN NOTES:

1 DISCONNECT AND REMOVE SPRINKLER AND

FP PIPING BACK TO MAIN.

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

BID SET

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

ELEC ROOM

G018

NM SUITE

CORRIDOR

G002

WAITING

ROOM

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G020

STRESS LAB

G014

CAMERA

G015

CAMERA

G012

CONTROL

ROOM

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL G031

PATIENT

CORRIDOR

G011 G034

IT CLOSET CHANGE

1/2" O 3/4" V

3/4" V

3/4" V 1/2" O 1/2" A

1" A 1 1/4" V 1" O

DEMOLITION PLAN NOTES:

1 DISCONNECT AND CAP VACUUM PIPE FOR RECONNECTION.

2 DISCONNECT AND CAP VACUUM PIPING AT DISCONNECTION

POINTS FOR REUSE AND RECONNECTION. REMOVE OXYGEN PIPING

FROM DISCONNECTION POINT DOWN TO HOT LAB. CAP OXYGEN

PIPE AT DISCONNECTION POINT FOR RECONNECTION AND REUSE.

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

BID SET

GENERAL NOTES:

1. MEDICAL GAS SYSTEM MAY ONLY BE TAKEN OFFLINE BETWEEN THE

HOURS OF 6:00 PM FRIDAY TO 5:00 AM THE FOLLOWING MONDAY.

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

ELEC ROOM

G018

NM SUITE

CORRIDOR

G002

WAITING

ROOM

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G014

CAMERA

G015

CAMERA

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL

G031

PATIENT

CORRIDOR

G034

CHANGE

G020

G012

CONTROL

ROOM

G011

IT CLOSET

12Ø

10Ø

TU1-G06

x2

14x14 x6

10x1010x6

8Ø

10x6 10x10

TU1-G08

14x12

14x12 x1

2 14 x1

BY

PA

SS

TU1-G03

TU1-G07

TU1-G14

TU1-G05

x1

6x

D-1 6Ø

D-1 6Ø

D-3 8Ø

R-3 24x24

D-3 8Ø

D-3 8Ø

D-3 8Ø

D-3 8Ø

D-1

6ØD-1

6Ø

R-2

12x12

R-2

12x12

R-2

24x12D-1 8Ø

D-1 8Ø

R-2

12x12

6Ø

6Ø

D-1 6Ø

D-1 6Ø

R-3 6Ø

D-1 6Ø

TU1-G01

24x20 16x20

D-1 6Ø

12x18

TU1-G02

R-2

12x12

STRESS

LAB

14x14 DUCT

UP TO EF-3

14x14 DUCT

UP TO EF-5

48x20

DUCT UP

TO AHU-1

30x18

DUCT UP

TO AHU-1

SSAC-02 (E)

DEMOLITION PLAN NOTES:

1 DISCONNECT AND REMOVE VAV BOX AND ASSOCIATED

DUCTWORK AND BYPASS IN ITS ENTIRETY AS SHOWN. CLEAN

AND SAVE DIFFUSERS FOR REUSE.

2 DISCONNECT AND REMOVE RETURN DUCTWORK AS SHOWN. CAP

AND PROTECT EXISTING OPEN ENDED DUCTWORK FOR

RECONNECTION. CLEAN AND SAVE REGISTER FOR REUSE AND

RELOCATION.

3 DISCONNECT AND REMOVE 14X14 EXHAUST DUCT UP TO ROOF.

CLEAN AND SAVE EXHAUST GRILLE FOR REUSE. REFER TO

MD-102 FOR CONTINUATION.

4 DISCONNECT AND REMOVE DUCTWORK BACK TO POINT AS

SHOWN.

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

BID SET

GENERAL NOTES:

1. AIRFLOW RATES SHOWN IN MD-101 ARE CURRENT SUPPLY,

RETURN, AND EXHAUST AIR FOR EACH ROOM. AIRFLOW RATES

PROVIDED FROM LATEST AIR BALANCE REPORT.

MMM

M

M

M

M

G030

STAIR

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

ELEC ROOM

G018

NM SUITE

CORRIDOR

WAITING

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G020

STRESS LAB

G014

CAMERA

G015

CAMERA

G012

CONTROL

ROOM

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL

G031

PATIENT

CORRIDOR

G011

G034

IT CLOSET

CHANGE

T

T

T T

T

TU1-G02

TU1-G06

TU1-G08

TU1-G03

TU1-G07

TU1-G04

2 1/2" HWS

2 1/2" HWR

TU1-G01

2 2

SSAC-E2

(E)

3" CHWS

3" CHWR

UP TO

AHU-1

3/4" HWS

3/4" HWR

UP TO AHU-1

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

1 1/4" HWS

1 1/4" HWR

1" HWR

1" HWS

1 1/4" HWS

1 1/4" HWR

TO

TU1-G08

TO

TU1-G02

TO

TU1-

G06

TO

TU1-G03

TO

TU1-G04

2 1/2" HWS

2 1/2" HWR

AHU-1

EF-1

EF-2

EF-3

SSAC-C2

DEMOLITION PLAN NOTES:

1 DISCONNECT AND REMOVE HWS AND HWR BACK TO MAIN. DISCONNECT

AND REMOVE THERMOSTAT.

2 DISCONNECT EXISTING THERMOSTAT FOR RELOCATION TO

ACCOMMODATE WALL REMOVAL. SAVE FOR REINSTALLATION.

3 REMOVE EXHAUST FAN IN ITS ENTIRETY. EXISTING FAN ROOF CURB TO

REMAIN. REPAIR RUBBER ROOF AS REQUIRED. REFER TO MD-101 FOR

CONTINUATION.

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

ELEC ROOM

G018

NM SUITE

CORRIDOR

G002

WAITING

ROOM

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G020

STRESS LAB

G015

CAMERA

G012

CONTROL

ROOM

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL

G031

PATIENT

CORRIDOR

G011

G034

IT CLOSET

CHANGE

1/2" HWR

3/4" HWS

3/4" CWS

1 1/2" SAN

4" SAN

3/4" HWR

3/4" CWS

3/4" HWS

1 1/2" SAN

1/2" CWS

1/2" HWS 1/2"

HWR

1/2" HWS

1/2" CWS

1/2" CWS

1 1/4" V

1/2" HWS

1/2" HWR

1 1/2" SAN

1/2" CWS

1/2" HWS

1/2" HWRCO

1 1/4" HWS

1 1/2" CWS

3/4" HWR

IN CRAWLSPACE

CO

1 1/4" V

1 1/2" V

4" V

1 1/2" SAN DN

FROM EACH

SINK

1/2" CWS

1 1/2" SAN

1/2" HWS

DEMOLITION PLAN NOTES:

1 DISCONNECT AND REMOVE SANITARY PIPING BACK TO MAIN

LINE IN CRAWLSPACE BELOW.

2 DISCONNECT AND REMOVE HWS, HWR, AND CWS PIPING AND

VALVES BACK TO MAIN LINE IN CRAWLSPACE BELOW.

3 DISCONNECT AND REMOVE VENT LINE BACK TO CEILING ABOVE.

CAP FOR RECONNECTION.

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

3/4"

3/4"

3/4" 3/4"

3/4" 3/4"

1" 3/4"

3/4"3/4"

3/4"

1 1/4"

1" 1"

1" 1" 1"

1"

3/4"3/4"

1"

3/4"3/4"

G030

STAIR

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

ELEC ROOM

G018

NM SUITE

CORRIDOR

G002

WAITING

ROOM

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G014

CAMERA

G015

CAMERA

G012

CONTROL

ROOM

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL

G031

PATIENT

CORRIDOR

G034

IT CLOSET

G020

G011

1" 3/4"

3" FP

2" FP

2" FP

1 1/2" FP

2" FP

3/4"

SCANNER

EQUIPMENT

STRESS

LAB

PLAN KEYNOTES:

1 PROVIDE UPRIGHT SPRINKLER AND PIPING.

TIE INTO EXISTING FP BRANCH.

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

1/2" O 3/4" V

3/4" V

3/4" V 1/2" O 1/2" A

1" A 1 1/4" V 1" O

3/4" V

1/2" O 3/4" V

3/4" V

G030

STAIR

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

ELEC ROOM

G018

NM SUITE

CORRIDOR

G002

WAITING

ROOM

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G020

STRESS LAB

G014

CAMERA

G015

CAMERA

G012

CONTROL

ROOM

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL

G031

PATIENT

CORRIDOR

G034

IT CLOSETG011

SCANNER

EQUIPMENT

PLAN KEYNOTES:

1 PROVIDE ADDITIONAL VACUUM PIPING AND RELOCATE EXISTING VACUUM

OUTLET. RECONNECT EXISTING PIPING AND VACUUM OUTLET. MAINTAIN

STERILITY OF THE SYSTEM.

2 PROVIDE ADDITIONAL VACUUM AND OXYGEN PIPING TO HOT LAB BELOW.

ROUTE WITHIN NEW WALL. RELOCATE VACUUM AND OXYGEN OUTLET.

CONNECT TO EXISTING BRANCH LINES. MAINTAIN STERILITY OF THE SYSTEM

GENERAL NOTES:

1. MEDICAL GAS SYSTEM MAY ONLY BE TAKEN OFFLINE BETWEEN THE HOURS

OF 6:00 PM FRIDAY TO 5:00 AM THE FOLLOWING MONDAY.

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

8x

Ø

8Ø

8Ø

8Ø

8Ø

14x14 DUCT

UP TO EF-3

14x14 DUCT

UP TO EF-5

30x18

DUCT UP

TO AHU-1

48x20

DUCT UP

TO AHU-1

G030

STAIR

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

ELEC ROOM

G018

NM SUITE

CORRIDOR

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G014

CAMERA

G015

CAMERA

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL

G020

G012

CONTROL

ROOM

G034

IT CLOSET

G011

VD

12Ø

10Ø

TU1-G02

TU1-G06

x2

14x14 x6 8Ø

10x10

TU1-G03

TU1-G07

TU1-G04

TU1-G05

x1

6x

D-1 6Ø

D-1 6Ø

R-3

14x14

D-3 8Ø

R-2

12x12

R-2

24x12

D-1 8Ø

R-2

12x12

6Ø

6Ø

D-1 6Ø

D-1 6Ø

TU1-G01

24x20 12x18

R-2

12x12

10x1010x6 D-1 6Ø

D-1 6Ø

16x20 x1

D-3 8Ø x1

14x4 14x4

D-1 6Ø

R-3 6Ø

D-3 8Ø

R-2

12x12

STRESS

LAB

D-1 6Ø

SCANNER

EQUIPMENT

TU1-G08

D-3 8Ø

D-3 8Ø

R-2

12X12

VD

VD

VD

VD

VD

VD

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

BID SET

PLAN KEYNOTES:

1 PROVIDE REHEAT VAV BOX, ASSOCIATED DUCTWORK,

DAMPERS, AND APPURTENANCES.

2 PROVIDE DUCTWORK, DAMPER, AND 45° TAP TO EXISTING

DUCT. CONNECT TO EXISTING DIFFUSER AND LOCATE

DIFFUSER TO ACCOMMODATE CEILING LAYOUT.

3 PROVIDE DUCTWORK, DAMPER, AND EXHAUST GRILLE (R-2).

REINSTALL EXISTING EXHAUST GRILLE (R-3). LOCATE GRILLE

TO ACCOMMODATE CEILING LAYOUT. CONNECT TO NEW

EXHAUST FAN (EF-3) ON ROOF. REFER O MP-102 FOR

CONTINUATION.

4 PROVIDE 14X4 RETURN DUCT. RELOCATE AND REINSTALL

RETURN GRILLE.

5 CAP EXISTING DUCT END.

GENERAL NOTES:

1. PROVIDE A PRE-BALANCE TEST.

TO

TU1- G08

MMM

M

M

M

3" CHWS

3" CHWR

UP TO

AHU-1

3/4" HWS

3/4" HWR

UP TO AHU-1

3/4" HWS

3/4" HWR

1 1/4" HWS

1 1/4" HWR

1" HWR

1" HWS

1 1/4" HWS

1 1/4" HWR

G030

STAIR

G017A

CLOSET

G019

WATER

SERVICE

ENTRY

G028

NORTH

CORRIDOR

G010

TOILET

G016

TOILET

G009

G018

NM SUITE

CORRIDOR

G002

WAITING

ROOM

G023

HOT LAB

G026

TOILET

G025

THYROID

UPTAKE

G022

DOSING

G017

NM TECH

OFFICE

G021

DEXASCAN

G020

STRESS LAB

G014

CAMERA

G015

CAMERA

G012

CONTROL

ROOM

G013

PET/CT

CLOSET

G018A

ROOM

G014A

CONTROL

G031

PATIENT

CORRIDOR

G034

IT CLOSET

G011

DN TO

CRAWL

SPACE

1" CHWR

1" CHWS

1/4" RL

1/2" RS TO

SSAC-C4

3/4" HWS

3/4" HWR

T TT

T

T

TO

TU1-G02

TO

TU1-

G06

TO

TU1-G03

TO

TU1-G04

1/4" RL

1/2" RS

1/

4" C

H W

S

1/ 4"

C H

W R

M

IN

C

R

AW

LS

PA

C E

1/

4" D

SSAC-E4

5/8" D DN TO

HUB DRAIN

TU1-G06

TU1-G02

TU1-G03

TU1-G07

TU1-G04

2 1/2" HWR

TU1-G01

SCANNER

EQUIPMENT

CWC-1

IN CRAWSPACE

SSAC-E2

(E)

ELEC

ROOM

2 1/2" HWS2 1/2" HWS

2 1/2" HWR

1/4" RL

1/2" RS TO

SSAC-C4

ROOF RAILS

AHU-1

EF-1

EF-2

EF-3

SSAC-C2

5 2

SSAC-C4

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

BID SET

PLAN KEYNOTES:

1 PROVIDE HWS AND HWR PIPING TO VAV BOX WITH ISOLATION VALVES AT CONNECTIONS.

PROVIDE STRAINER AND MOTORIZED CONTROL VALVES ON HWS AND BALANCE VALVE ON

HWR. RECONNECT TO EXISTING PIPING. PROVIDE NEW WALL MOUNT THERMOSTAT.

2 PROVIDE WALL MOUNT SPLIT AIR CONDITION UNIT, AND PIPING AS SHOWN. ROUTE RL AND

RS ABOVE CEILING TO CONDENSER UNIT ON ROOF. ROUTE CONDENSATE DRAIN TO HUB

DRAIN, PROVIDE P-TRAP IN CRAWLSPACE BELOW AND CONNECT TO EXISTING DRAIN.

PROVIDE CONDENSER UNIT AND ROOF RAIL SUPPORT. COORDINATE WITH ARCHITECTURAL

PLANS FOR FLASHING DETAILS.

3 CHWS AND CHWR CONNECTION ASSEMBLY AND TRIM AT PET/CT SCANNER, PROVIDED BY

SEIMENS, CONTRACTOR TO INSTALL. PROVIDE BALL VALVES AT EACH PIPING CONNECTION

TO CWC-1 AND PET/CT SCANNER. INSTALL AND ROUTE PIPING BETWEEN EXISTING CHWS

AND CHWR MAIN AND CWC-1 THROUGH CEILING AND CHASE. PROVIDE BALL VALVES AT

EACH PIPING CONNECTION TO CWC-1 AND TAPS OFF MAIN. CONTRACTOR SHALL INSTALL

AND ROUTE PIPING BETWEEN MAIN, CWC-1 AND PET/CT SCANNER THROUGH CRAWLSPACE

AND CEILING.

4 RELOCATE EXISTING THERMOSTAT TO APPROXIMATE LOCATION SHOWN.

5 PROVIDE NEW EXHAUST FAN; INSTALL ON EXISTING ROOF CURB. PROVIDE CURB ADAPTER

AS REQUIRED FOR AIR TIGHT INSTALLATION. PROVIDE WITH VFD MOUNTED IN NEMA

ENCLOSURE. CONNECT TO 14X14 EXHAUST DUCT IN G013. REPAIR RUBBER ROOF AS

REQUIRED. SEE MP-101 FOR CONTINUATION.

1/2" HWR

3/4" HWS

3/4" CWS

1 1/2" SAN

4" SAN

G028

NORTH

CORRIDOR

1 1/2" CWS

1 1/4" HWS

3/4" HWR

IN CRAWLSPACE

1/2" HWS

1/2" CWS

G018

1/2" CWS

1/2" HWS

1/2" HWR

1/2" CWS

1/2" HWS

1/2" HWR

CO

CO

1 1/4" V

1 1/2" V

4" V

1 1/4" V

1 1/4" D

1 1/2" SAN

PET/CT

G013

IT CLOSET

G034

ELEC ROOM

G009

PATIENT

CORRIDOR

G031

SCANNER

EQUIPMENT

G011

CONTROL

ROOM

G012

TOILET

G010

DOSING

G022

HOT LAB

G023

THYROID

UPTAKE

G025

TOILET

G026

WAITING

ROOM

G002

DEXASCAN

G021

STRESS LAB

G020

NM SUITE

CORRIDOR

G018

CLOSET

G018A

CAMERA

G014

CONTROL

ROOM

G014A

CAMERA

G015

TOILET

G016

NM TECH

OFFICE

G017

CLOSET

G017A

STAIR

G030

WATER

SERVICE

ENTRY

G019

PLAN KEYNOTES::

1 PROVIDE 1 1/2" SANITARY PIPING AND P-TRAP TO SINK IN G013. PROVIDE TEE

Y CONNECTION AND TIE INTO EXISTING SANITARY LINE.

2 PROVIDE 1/2" HWR, 3/4" HWS, AND 3/4" CWS UP TO SINK. PROVIDE

THERMOSTATIC MIXING VALVE AS PER ASSE 1017. CONNECT TO EXISTING

MAIN PIPING IN CRAWL SPACE BELOW AND PROVIDE BALL VALVES AFTER

TEE CONNECTIONS AS SHOWN.

3 PROVIDE 1 1/2" V PIPING DOWN TO SINK . AFTER SHUT OFF VALVES.

RECONNECT EXISTING HWS, HWR, AND CWS LINES.

4 PROVIDE 1 1/4" DRAIN PIPING BETWEEN PET/CT SCANNER CONDENSATE

WATER DRAIN (PROVIDED BY SEIMENS) AND EXISTING SANITARY LINE.

5 RECONNECT HWS, HWR, AND CWS CONNECTION.

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

3610 LAWSON ROAD « JAMESTOWN, NY 14701

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

BID SET

NTS

NOTES:

1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF

INLET

2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO

ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0".

3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10

FEET (3 METERS). FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT

TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100'.

4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO

DIFFUSER, SHALL NOT EXCEED 5'-0". USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°. SUPPORT FLEXIBLE DUCT WITH INTERMEDIATE SUPPORT AT MIDPOINT FOR LENGTHS

GREATER THAN 3'-0".

5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR

BARRIER FOR CONNECTING DUCT SECTIONS.

6. PROVIDE INTEGRAL FLOW RING TUPE AIR FLOW MEASUREMENT SENSOR ON VAV INLET.

AIR TERMINAL

UNIT (VAV)

REHEAT

COIL

SOUND

ATTENUATOR

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL

DIFFUSER (TYP.)

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

SEE NOTE 5

SE

E

N O

TE

SEE NOTE 3

SEE NOTE 2

SEE NOTE 1

NTS NTS NTS

NOTES:

1. REFRIGERANT LINES SHALL BE SIZED AND ROUTED AS PER MANUFACTURER'S RECOMMENDATIONS.

2. MULTIPLE REFRIGERANT CIRCUITS SHALL BE TYPICAL TO SINGLE CIRCUIT SHOWN.

DIRECT

EXPANSION

COIL

INDOOR UNIT

THERMAL EXPANSION VALVE

SOLENOID VALVE

ISOLATION VALVES CONDENSER UNIT

RECEIVER

COMPRESSOR

CONDENSER

CONDENSER FAN

FILTER/DRIER WITH

CHANGING PART

OIL TRAP

SIGHT GLASS AND

LIQUID INDICATOR

ISOLATION VALVES

RS

RLRS

TO DRAIN

D

RS

HEATING

COIL

TEST PLUG (TYP.)

REDUCER, IF REQUIRED

WATER RETURN

MANUAL AIR VENT

UNION CONNECTIONS

(TYP.)

WATER SUPPLY

SHUT OFF VALVE

DRAIN WITH HOSE

CONNECTION

MV

MODULATION CONTROL VALVE

NTS

ROOM THERMOSTAT/SENSOR

WALL MOUNTED

48" AFF.

TU

HCHWS

HWR

V-1

HEATING

COIL

AIR

TERMINAL

UNIT

AIR

FLOW

TE

ATU

CONTROLLER

PC

TE

FE

VAV BOX CONTROL SEQUENCE

A. SET POINTS SHALL BE SET AS FOLLOWS: COOLING 75°F (ADJ) HEATING

70°F(ADJ) DEADBAND OF 5° F BETWEEN HEATING AND COOLING SET POINTS

WILL BE MAINTAINED.

B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL MODULATE TO

MINIMUM POSITION.

C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL MODULATE

TO MAINTAIN SET POINT + .5° F. THE ADJUSTABLE TOLERANCE OF + .5° F

HAS BEEN SELECTED TO PREVENT VALVE HUNTING

D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.

E. EXHAUST FAN FOR INTERACTION WITH VAV,

F. FLOW METER ON VAV AND EXHAUST FAN.\

G. BMS SYSTEM NEEDS TO READ SPEED OF EXHAUST TO MAINTAIN 5% OFFSET

IN EXHAUST AIRFLOW BELOW THE MEASURED SUPPLY RATE.

VOLUME

DAMPER

CRAWLSPACE

BELOW

SIEMENS SUPPLY/ RETURN

TEE ASSEMBLY SUPPLIED

BY SIEMENS

(2) 1" WATER HOSE SUPPLIED

BY SIEMENS, CONTRACTOR TO

INSTALL. MAX LENGTH 16'-0".

(2) 1" HIGH PRESSURE WATER HOSES

SUPPLIED BY SIEMENS. CONTRACTOR TO

INSTALL. MAX LENGTH 90'-0". ON SITE CHILLED

WATER REQUIREMENTS. THE COOLING

SYSTEM IS INTEGRATED WITHIN THE GANTRY.

THE ON SITE CHILLED WATER SUPPLY AND

RETURN ARE CONNECTED CWC CABINET.

CHILLED WATER HOSES:

SIEMENS SUPPLIES THE 1" WATER SUPPLY AND RETURN WITH 1/2" INSULATION FOR

THE BIOGRAPH VISION THAT TERMINATES INTO THE SUPPLY/RETURN MANIFOLDS THAT

ARE SUPPLIED AND INSTALLED BY SIEMENS. THE MAXIMUM LENGTH OF THE WATER

SUPPLY AND RETURN HOSES IS 90'-0" AND INSTALLED BY THE CONTRACT0R.

ACCEPTABLE BENDING RADIUS OF THE HOSES IS 9". THE OUTER DIAMETER OF THESE

HOSES WITH THE INSULATION IS 1 1/2". RECOMMENDED CONDUIT SIZE IS 3" FOR A

SINGLE WATER HOSE RUN PER CONDUIT. IF CONDUIT IS USED FOR THE

SUPPLY/RETURN HOSES, 90° ELBOWS MUST BE AVOIDED DUE TO THE HOSE BEND

RADIUS AND THE NUMBER OF HOSES PROVIDED FOR THE BIOGRAPH VISION.

ON SITE CHILLED WATER CONNECTION TO

HOSPITAL COOLING CIRCUIT.

CUSTOMER/CONTRACTOR TO SUPPLY 1 1/4"

SHUT OFF VALVES (1 SUPPLY, 1 RETURN).

FACILITY WATER CONNECTIONS PROVIDED

BY CUSTOMER/CONTRACTOR MUST BE

FEMALE 1 1/4" NPT/

ROOF RAIL SUPPORT

(TYP)

FC

AIR FLOW

MEASUREMENT

SENSOR

ADJUSTABLE CLEVIS HANGER

TYPE 1 - SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE

43 - SEE SPECIFICATIONS

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

NTS

PROVIDE INSULATION

SHIELD & INSERT FOR

ALL PIPING 8" MIN.)

BAND

1-5/8" 12 GAUGE

CHANNEL OR 2"X2"X1/4" ANGLE

1/2" DIA. HANGER RODS WITH

36" MAX. SPACING ON EACH

CHANNEL

NTS

DRAIN STANDPIPE - TO BE UTILIZED FOR

HIGH RATE OF DISCHARGE EQUIPMENT

SUCH AS WASHING MACHINES, OR TO

CREATE ADDED HEAD PRESSURE.

(OPTIONAL)

HUB DRAIN

4" P-TRAP

3' -0

4"

1" MIN.

NTS

NOTE:

1. SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" CADMIUM PLATED LAG BOLTS

NOT OVER 12" ON CENTER.

2. SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS

(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).

3. RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER,

THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.

4. PROVIDE VFD IN NEMA ENCLOSURE.

GRAVITY BACKDRAFT DAMPER

RIGID CONDUIT TO

ACCOMMODATE

ELECTRICAL WIRES

SEE NOTE 2

PREFABRICATED

ROOF CURB

WOOD NAILING

STRIP

ELECTRICAL

CONDUIT GUIDE

MOTOR HOUSING

DUCT

TRANSITION DUCT TO

FULL SIZE OF DAMPER

SUPPLIED WITH ROOF

VENTILATOR

ROOF

SEE NOTE 2

SEE NOTE 1

CURB CAP

NTS

P-TRAP

EXISTING SINK

WALL

SANITARY LINE

VENT

HWS

CWS

THERMOSTATIC

MIXING VALVE

FLOOR

SHUT OFF VALVES

NTS

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

«««A/E:

GREENMAN-PEDERSEN, INC.

52 GLENMAURA NATIONAL BLVD.

SCRANTON, PA 18505

570-342-3700

JOHN D. MURPHY

52 Glenmaura National Blvd.

Suite 302, P.O. Box 5777

Scranton, PA 18505

Greenman-Pedersen, Inc.

Construction Management

Engineering

Design

Planning

GPINET.COM570.342.3700SUITE 302. P.O. BOX 5777

10/02/2020

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

«««A/E:

GREENMAN-PEDERSEN, INC.

52 GLENMAURA NATIONAL BLVD.

SCRANTON, PA 18505

570-342-3700

JOHN D. MURPHY

52 Glenmaura National Blvd.

Suite 302, P.O. Box 5777

Scranton, PA 18505

Greenman-Pedersen, Inc.

Construction Management

Engineering

Design

Planning

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

«««A/E:

GREENMAN-PEDERSEN, INC.

52 GLENMAURA NATIONAL BLVD.

SCRANTON, PA 18505

570-342-3700

JOHN D. MURPHY

52 Glenmaura National Blvd.

Suite 302, P.O. Box 5777

Scranton, PA 18505

Greenman-Pedersen, Inc.

Construction Management

Engineering

Design

Planning

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

«««A/E:

GREENMAN-PEDERSEN, INC.

52 GLENMAURA NATIONAL BLVD.

SCRANTON, PA 18505

570-342-3700

JOHN D. MURPHY

52 Glenmaura National Blvd.

Suite 302, P.O. Box 5777

Scranton, PA 18505

Greenman-Pedersen, Inc.

Construction Management

Engineering

Design

Planning

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

«««A/E:

GREENMAN-PEDERSEN, INC.

52 GLENMAURA NATIONAL BLVD.

SCRANTON, PA 18505

570-342-3700

JOHN D. MURPHY

52 Glenmaura National Blvd.

Suite 302, P.O. Box 5777

Scranton, PA 18505

Greenman-Pedersen, Inc.

Construction Management

Engineering

Design

Planning

(716) 484 - 1366 « (716) 484 - 1519 FAX

P TRIOT

DESIGN & CONSULTING

STILL SERVING

«««A/E:

GREENMAN-PEDERSEN, INC.

52 GLENMAURA NATIONAL BLVD.

SCRANTON, PA 18505

570-342-3700

JOHN D. MURPHY

52 Glenmaura National Blvd.

Suite 302, P.O. Box 5777

Scranton, PA 18505

Greenman-Pedersen, Inc.

Construction Management

Engineering

Design

Planning

M-001.pdf
Sheets and Views
M-001
FD-101.pdf
Sheets and Views
FD-101
MGD-101.pdf
Sheets and Views
MGD-101
MD-101.pdf
Sheets and Views
MD-101
MD-102.pdf
Sheets and Views
MD-102
PD-101.pdf
Sheets and Views
PD-101
FP-101.pdf
Sheets and Views
FP-101
MGP-101.pdf
Sheets and Views
MGP-101
MP-101.pdf
Sheets and Views
MP-101
MP-102.pdf
Sheets and Views
MP-102
PP-101.pdf
Sheets and Views
PP-101
M-500.pdf
Sheets and Views
M-500
2020-09-25_Bid Set Electrical_REV.pdf
Sheets and Views
E001-E001
ED100-ED100
EL100-EL100
EP100-EP100
EP100-EP101
ET100-ET100

File details come from the government source that posted it. Updated .