591-25060-DPL MDOT Mt Pleasant TSC Roof Replacement_Bid_Permit Set.pdf
PDF 4 MB Posted
- Solicitation number
- RFQ 171 260000000278 2
- Issued by
- Ingham County, Michigan
About this file
Summary: MDOT Mt Pleasant TSC Roof Replacement Project
This document is a bid/permit set of architectural drawings for a roof replacement project prepared by Colliers Engineering & Design for the State of Michigan Department of Technology, Management and Budget (DTMB) Facilities and Business Services Administration. The project involves the complete replacement of the roofing system at the MDOT Mt Pleasant Transportation Service Center located at 1212 Corporate Drive, Mt. Pleasant, Michigan 48858. The work encompasses both a high roof area of 21,926 square feet and a low roof area of 8,900 square feet, for a total roof area of 30,826 square feet. The scope includes removal of existing single-ply membrane roofing, insulation, flashing, and associated accessories down to the structural roof deck, followed by installation of new 90 mil Elevate Rubbergard EPDM roofing (or equal) on tapered insulation providing 1/4-inch per foot roof slope to achieve R-30 continuous insulation in accordance with ASHRAE 90.1-2022 energy code requirements. The project design complies with the 2021 Michigan Building Code, 2021 Michigan Rehabilitation Code for Existing Buildings, 2021 Michigan Mechanical and Plumbing Codes, and 2023 National Electrical Code with Part 8 State Amendments. The drawings were issued for bidding and permitting on April 17, 2026, and include detailed specifications for edge systems, roof walks, drain replacements, flashing details, and coordination of existing roof penetrations and equipment that will remain in place.
The project documents specify that the contractor must visit the site and verify all existing roof conditions prior to demolition and report discrepancies to the architect before proceeding. New roofing materials specified include Elevate Rubbergard EPDM membrane, Elevate Isogard 6-inch tapered insulation, Advantedge metal edge systems, and O'Keefe's Inc 503A access ladders. Existing structural roof decking, roof drains, overflow drains, roof hatches, exhaust fans, vents, and vent stacks are to be retained and verified during demolition, with damaged areas requiring repair or replacement at contractor expense. The building is fully sprinkled per fire protection requirements. Temporary protection measures are required to maintain ongoing building operations, protect exiting paths, control dust, and ensure occupant safety. The contractor is responsible for all coordination, scheduling, site cleanup, protective measures, equipment startup and testing, and provision of closeout documentation including certificates of release, insurance for continuing coverage, warranties, and operational manuals.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROTECT YOURSELF
ALL STATES REQUIRE NOTIFICATION OF
EXCAVATORS, DESIGNERS, OR ANY PERSON
PREPARING TO DISTURB THE EARTH'S
SURFACE ANYWHERE IN ANY STATE
FOR STATE SPECIFIC DIRECT PHONE NUMBERS
VISIT: WWW.CALL811.COM
Know what's below.
Call before you dig.
www.colliersengineering.com
LANSING
7050 West Saginaw Hwy Suite 200 // Lansing, MI 48917
Phone: 517.272.9835
Colliers Engineering & Design
A
1/
0.
D
PL
M D
O T
M T
P
LE
A S
A N
T
TS
C R
O O
F R
E P
LA
C
E M
E N
T Y2
DA
TE
SH
EE
T
ID
EN
TI
FIC
AT
IO
N
NO
IS
SU
ED
F
OR
C
O P
O R
A T
E D
R
M T
P
L E
A S
A N
T
M I
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
, M A
N A
G E
M E
N T
A N
D B
U D
G E
T
S T
A T
E O
F M
IC
H
IG
A
N
K Y
L E
G U
E R
R A
N T
, A C
T
IN
G D
IR
E
C T
O R
FA
C
IL
IT
IE
S
A N
D B
U S
IN
E
S S
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
S
IG
N A
N D
C O
N
ST
R U
C T
IO
N
D
IV
IS
IO
N
FI
LE
N
O.
B
ID
S/
PE
RM
IT
S
AR
C
HI
TE
C T
PR
OJ
EC
T
NO
IN
DE
X N O.
FI
N A L
RE
C
OR
D
C O N
ST
RU
C
TI
O N
DR
AW
N
DE
SI
GN
ED
AP
PR
OV
ED
C
HE
C
KE
D
P.
A.
K
D.
P.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
Copyright © 2025. Colliers Engineering & Design All Rights Reserved. This drawing and all the information contained herein is authorized for use only by the party for whom the services were contracted or to whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied upon for any other purpose without the express written consent of
Colliers Engineering & Design.
DRAWING INDEXPROJECT CONTACT LIST
PROJECT LOCATION MAP
OWNER:
STATE OF MICHIGAN, DTMB
3111 W ST JOSEPH ST, LANSING, MI
48917
CONTACT: DAVID LENZ, AIA
PHONE: 517-614-5450
LENZD@MICHIGAN.GOV
ARCHITECT:
COLLIERS ENGINEERING & DESIGN
7050 W SAGINAW HIGHWAY, SUITE
200, LANSING, MI 48917
CONTACT: DAVID MOSS, AIA
PHONE: 517-898-1604
DAVID.MOSS@COLLIERSENG.COM
CONTRACTOR:
TBD
CODE INFORMATION
APPLICABLE BUILDING CODES:
2021 MICHIGAN BUILDING CODE
2021 MICHIGAN REHABILITATION CODE FOR EXISTING BUILDINGS
2021 MICHIGAN MECHANICAL CODE
2021 MICHIGAN PLUMBING CODE
2023 NATIONAL ELECTRICAL CODE (NEC) WITH PART 8 STATE AMENDMENTS
ROOF AREA: HIGH ROOF - 21,926 SF
LOW ROOF - 8,900 SF
TOTAL - 30,826 SF
FIRE PROTECTION:
BUILDING IS FULLY SPRINKLED
ENERGY CONSERVATION CODE SUMMARY
ENERGY SUBCODE: ASHRAE 90.1 - 2022
ELEMENT: REQUIRED: NEW ROOF ASSEMBLY:
ROOFS: R-30 C.I. R-30 C.I. (NOT INCLUDING TAPERED INSULATION)
ENERGY CODE NOTES: TABLE 5.5-5 (ZONE 5A FOR ISABELLA COUNTY)
G000
/1
7/
04/17/2026
MDOT Mt Pleasant Transportation Service Center Roof Replacement
1212 Corporate Dr., Mt. Pleasant, MI
48858
State of Michigan
DRAWING INDEX - WITH SCHEDULED RELEASES
/2
7/
IS
S
U E
D F
O R
P H
A S
E
R
E V
IE
W
00 - GENERAL
G000 COVER SHEET X
04 - ARCHITECTURAL
A001 GENERAL NOTES AND LEGENDS (WITH PROJECT MANUAL) X
A004 EXISTING ROOF PLAN X
AD103 ROOF DEMOLITION PLAN X
A103 ROOF PLAN X
A321 SECTION DETAILS X
A322 SECTION DETAILS X
A501 DETAILS X
CORPORATE DR
N M
IS
S
IO
N
S T
PACKARD ST
P A
C K
A R
D R
D
PROJECT LOCATION
REV DATE DESCRIPTION
1 04/17/2026 ISSUED FOR BIDDING/PERMIT
GENERAL NOTE WITH A PROJECT MANUAL
8' - 0"
XX
CEILING HEIGHT
ELEVATION NOTATION
EQUIPMENT TAG
KEYNOTE (REMOVALS)
KEYNOTE
CAST STONE
GRAVEL OR CRUSHED STONE
CONCRETE
CONCRETE MASONRY UNIT
UNDISTURBED EARTH
BRICK
RIGID INSULATION
PLYWOOD
SAND OR GYPSUM BOARD
STEEL
WOOD FRAMING (CONTINUOUS) BATT INSULATION
WOOD BLOCKING (DISCONTIN.)
EXISTING FINISH WOOD
GENERAL ARCHITECTURAL SYMBOLS
MATERIAL INDICATORS
A101
A101
XXX
XXX
A101
SIM
1Ref
DETAIL CALLOUT
ELEVATION MARKER
DRAWING #
ELEVATION #
BREAK MARKER
NORTH ARROW
(SHOWN IN KEYPLAN)
NEW COLUMN ID
DETAIL #
DRAWING #
EXISTING COLUMN ID
A101
1Ref
R ef
R ef
1Ref A000
VIEW TITLE
DETAIL #
SECTION MARKER
SECTION #
DRAWING #
DETAIL SECTION
DRAWING #
ACCESSORY MARKER
DETAIL #
XX
EXISTING DOOR
SCHEDULED DOOR
ROOM TAG
WINDOW TYPE MARKER
DOOR MARKER
Room name
WALL STYLES
EXISTING BRICK WALL
EXISTING CMU WALL
EXISTING STUD WALL STUD WALL
CMU WALL
BRICK WALL
EXISTING WALL REMOVAL
ABBREVIATIONS
1/8" = 1'-0"
VIEW NAME
ALL GENERAL NOTES PERTAIN TO ALL ARCHITECTURAL (A-SERIES) DRAWINGS IN THIS SET
GENERAL
1. DEFINITIONS: “PROVIDE” MEANS FURNISH AND INSTALL. SUPPLY LABOR AND MATERIALS
TO RESULT IN A FINISHED AND/OR OPERABLE SYSTEM.
2. CONTRACTOR RESPONSIBILITIES:
A. MATERIALS, CONSTRUCTION METHODS INCLUDING BUT NOT LIMITED TO LAYOUT,
COORDINATION, SCHEDULE AND CONSTRUCTION SITE ACCESS AND WORK.
B. DAILY CLEANING: KEEP SITE FREE FROM WASTE, RUBBISH, AND DEBRIS, ALL OF
WHICH SHALL BE REMOVED AND DISPOSED OF PROPERLY DAILY.
C. FINAL CLEANING: PRIOR TO PUNCHLIST INSPECTION, BROOM CLEAN ALL HARD
SURFACE FLOORS; VACUUM ALL CARPETING; AND WIPE DOWN ALL HORIZONTAL
AND GLASS SURFACES, THEREBY PROVIDING DUST FREE SURFACES.
D. TEMPORARY PROTECTION IS REQUIRED TO MAINTAIN ONGOING BUILDING
OPERATIONS, EXITING PATHS, DUST CONTROL AND OCCUPANT SAFETY. IDENTIFY
THE REQUIREMENTS FOR TEMPORARY PROTECTION AND PROJECT PHASING.
COORDINATE WITH OWNER FOR OTHER REQUIREMENTS.
E. COORDINATE STARTUP AND ADJUSTING OF EQUIPMENT AND OPERATING
COMPONENTS. START EQUIPMENT AND OPERATING COMPONENTS AND TEST TO
CONFIRM PROPER OPERATION AND CONTROL. REMOVE MALFUNCTIONING UNITS,
REPLACE WITH NEW UNITS, AND RETEST.
F. CLOSEOUT DOCUMENTS, CERTIFICATE OF RELEASE FROM THE AUTHORITY OF
JURISDICTION AND INSURANCE FOR CONTINUING COVERAGE, WARRANTIES, TEST &
INSPECTION RESULTS AND OPERATION, EMERGENCY & MAINTENANCE MANUALS.
3. CONTRACT DOCUMENTS:
A. PLANS, ELEVATIONS, SECTIONS, DETAILS AND SCHEDULES ARE COMPLEMENTARY.
PLAN DRAWINGS WILL TAKE PRECEDENCE OVER ELEVATION, SECTION AND
DETAILS DRAWINGS IN ANY CONFLICTS OF HORIZONTAL DIMENSIONS. DETAIL PLAN
DRAWINGS WILL TAKE PRECEDENCE OVER LARGER SCALE PLANS IN ANY
CONFLICTS WITH HORIZONTAL DIMENSIONS. WALL AND BUILDING SECTIONS WILL
TAKE PRECEDENCE OVER PLAN DRAWING AND DETAILS IN ANY CONFLICTS WITH
VERTICAL DIMENSIONS. DETAILS AND WALL SECTIONS WILL TAKE PRECEDENCE
OVER ELEVATION AND PLAN DRAWINGS IN ANY CONFLICTS WITH MATERIAL
DESCRIPTION. SCHEDULES WILL TAKE PRECEDENCE OVER OTHER
ARCHITECTURAL DRAWINGS IN AND CONFLICTS WITH WALL, FLOOR AND CEILING
FINISHES AND DOOR, DOOR HARDWARE AND FENESTRATION INFORMATION.
B. DRAWINGS AND SPECIFICATIONS PREPARED BY THE ARCHITECT ARE
INSTRUMENTS OF THE ARCHITECT'S SERVICE FOR USE SOLELY WITH RESPECT TO
THIS PROJECT AND, UNLESS OTHERWISE PROVIDED, BERGMANN SHALL BE
DEEMED THE AUTHOR OF THESE DOCUMENTS AND RETAIN ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT.
C. WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS,
SUCH STANDARDS SHALL BE THE LATEST EDITION AND/OR ADDENDUM.
FINISHES
1. GENERAL: FINISHED FLOORS EXTEND INTO TOE SPACES, CLOSETS, DOOR REVEALS
AND SIMILAR OPENINGS.
2. PRODUCTS:
A. PAINT DESIGNATIONS INDICATE COLOR ONLY, REFER TO SPECIFICATION FOR
FINISH TYPE.
B. PROVIDE SELF LEVELING TROWELABLE UNDERLAYMENT WHERE REQUIRED TO
OBTAIN FINISH MANUFACTURER'S REQUIRED SUBFLOOR CONDITION.
C. PROVIDE THE REQUIRED TRANSITIONS BASED ON TYPES IDENTIFIED ON DRAWINGS
AT EACH FINISH TRANSITION LOCATION.
ENERGY CODE STATEMENT:
TO THE BEST OF THE REGISTERED DESIGN PROFESSIONAL’S KNOWLEDGE, BELIEF AND
PROFESSIONAL JUDGEMENT, THESE PLANS AND/OR SPECIFICATIONS ARE IN COMPLIANCE
WITH THE APPLICABLE CODES.
UNIFORM CODE STATEMENT:
TO THE BEST OF THE REGISTERED DESIGN PROFESSIONAL’S KNOWLEDGE, BELIEF AND
PROFESSIONAL JUDGEMENT, THESE PLANS AND/OR SPECIFICATIONS ARE IN COMPLIANCE
WITH THE APPLICABLE CODES.
A
1/
0.
D
PL
Y2
DA
TE
SH
EE
T
ID
EN
TI
FIC
AT
IO
N
NO
IS
SU
ED
F
OR
M D
O T
M T.
P
LE
AS
AN
T
TS
C R
O O
F R
E P
LA
C
E M
E N
T
C
O P
O R
A T
E D
R
M T
P
L E
A S
A N
T
M I
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
, M A
N A
G E
M E
N T
A N
D B
U D
G E
T
S T
A T
E O
F M
IC
H
IG
A
N
K Y
L E
G U
E R
R A
N T
, A C
T
IN
G D
IR
E
C T
O R
FA
C
IL
IT
IE
S
A N
D B
U S
IN
E
S S
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
S
IG
N A
N D
C O
N
ST
R U
C T
IO
N
D
IV
IS
IO
N
FI
LE
N
O.
B
ID
S/
PE
RM
IT
S
AR
C
HI
TE
C T
PR
OJ
EC
T
NO
IN
DE
X N O.
FI
N A L
RE
C
OR
D
C O N
ST
RU
C
TI
O N
DR
AW
N
DE
SI
GN
ED
AP
PR
OV
ED
C
HE
C
KE
D
P.
A.
K
D.
P.
L./
R.
E.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
A001
/1
7/
" INCHES
# NUMBER, POUNDS
& AND
' FEET
(E), EXST EXISTING TO REMAIN
(ER) EXISTING TO BE RELOCATED
(N) NEW WORK
(R) REMOVE
(RE) RELOCATED EXISTING
@ AT
Ø, DIA DIAMETER
A
A/C AIR CONDITIONING
ACP ACOUSTICAL CEILING PANELS
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
AOR ARCHITECT OF RECORD
APPROX APPROXIMATE, APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
ATTN ATTENTION
B
B/, BO BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BTWN BETWEEN
C
CANT CANTILEVER
CG CORNER GUARD
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR
CM CONSTRUCTION MANAGER
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CT CERAMIC TILE
CTB CERAMIC TILE BASE
D
D DEEP
DF DRINKING FOUNTAIN
DIA, Ø DIAMETER
DIM DIMENSION
DWG,
DWGS
DRAWING, DRAWINGS
E
EA EACH
EIFS EXTERIOR INSULATION FINISH
SYSTEM
EL ELEVATION
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EXF EPOXY FLOORING
EXP EXPANSION
EXP BT EXPANSION BOLT
EXT EXTERIOR
F
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFE FINISH FLOOR ELEVATION
FLG FLOORING
FLR FLOOR
FPR FIBER REINFORCED PLASTIC
FR FIRE RATED
FRT FIRE RETARDANT TREATED
FT FLOOR TILE
FT FIRE TREATED
FTG FOOTING
G
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GRC GLASS-REINFORCED CONCRETE
GRG GLASS-REINFORCED GYPSUM
GWB GYPSUM BOARD
H
HB HOSE BIBB
HC HOLLOW CORE
HDR HEADER
HM HOLLOW METAL
HORIZ HORIZONTAL
HPC HIGH PERFORMANCE COATING
HW HOT WATER
HWD HARDWARE
HWT HOT WATER TANK
I
ID INSIDE DIAMETER
IN WG INCH OF WATER GAUGE
INSUL INSULATION
INT INTERIOR
INV INVERT
J
JAN CL JANITORS CLOSET
JT JOINT
L
LAM LAMINATE
LAV LAVATORY
LBS POUNDS
LF LINEAR FEET
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LMC LINEAR METAL CEILING
LT LIGHT
LTL LINTEL
LVR LOUVER
LVT LUXURY VINYL TILE
M
MAX MAXIMUM
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
N
NIC NOT IN CONTRACT
NTS NOT TO SCALE
O
OC ON CENTER
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
P
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLM PLASTIC LAMINATE
PLYWD PLYWOOD
PMEJ PRE MOLDED EXPANSION JOINT
PMF PRE MOLDED FILLER
PP PLASTIC PANELING
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PORCELAIN TILE
PTD PAINTED
PTWD (PRESSURE)
PRESERVATIVE-TREATED WOOD
Q
QT QUARRY TILE
QTY QUANTITY
R
R RISER
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REBAR REINFORCING BAR
REINF REINFORCED, REINFORCING,
REINFORCEMENT
REQD REQUIRED
REQMTS REQUIREMENTS
RESIL RESILIENT
RF RESILIENT FLOORING
RM ROOM
RO ROUGH OPENING
RTU ROOF TOP UNIT
S
SC SEALED CONCRETE
SCHED SCHEDULE
SCL STRUCTURAL COMPOSITE LUMBER
SF, SQFT SQUARE FEET
SIM SIMILAR
SMS SHEET METAL SCREW
SOG SLAB ON GRADE / GROUND
SPCS SPACES
SPEC SPECIFICATION
SS SOLID SURFACE
SSL SHORT SLOTTED
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STRUCT STRUCTURAL, STRUCTURE
SYS SYSTEM
T
T TREAD
T&G TONGUE AND GROOVE
TEMP TEMPORARY
TH THRESHOLD
TL TWIST LOCK
TR TRANSITION
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
UPH UPHOLSTERY
UR URINAL
V
VAR VARIES
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W
W WIDE, WIDTH
W/ WITH
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET
WCV WALL COVERING
WD WOOD
WDT WINDOW TREATMENT
WF WOOD FLOORING
WOM WALKOFF MAT
WP WATERPROOF
WT WALL TILE
EXISTING SINGLE PLY MEMBRANE
ON TAPERED INSULATION
EXISTING CONTROL JOINT
EXISTING ROOF HATCH
EXISTING SINGLE PLY MEMBRANE
ON TAPERED INSULATION
EXISTING SINGLE PLY MEMBRANE
ON TAPERED INSULATION
EXISTING SINGLE PLY MEMBRANE
ON TAPERED INSULATION
EXISTING SINGLE PLY MEMBRANE
ON TAPERED INSULATION
EXISTING OVERFLOW
EXISTING OVERFLOW
NOTE:
EXISTING ROOF PLAN SHOWN
FOR REFERENCE ONLY
SHADED AREA INDICATES AREA
OF SLOPED STRUCTURE.
A
1/
0.
D
PL
Y2
DA
TE
SH
EE
T
ID
EN
TI
FIC
AT
IO
N
NO
IS
SU
ED
F
OR
M D
O T
M T.
P
LE
AS
AN
T
TS
C R
O O
F R
E P
LA
C
E M
E N
T
C
O P
O R
A T
E D
R
M T
P
L E
A S
A N
T
M I
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
, M A
N A
G E
M E
N T
A N
D B
U D
G E
T
S T
A T
E O
F M
IC
H
IG
A
N
K Y
L E
G U
E R
R A
N T
, A C
T
IN
G D
IR
E
C T
O R
FA
C
IL
IT
IE
S
A N
D B
U S
IN
E
S S
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
S
IG
N A
N D
C O
N
ST
R U
C T
IO
N
D
IV
IS
IO
N
FI
LE
N
O.
B
ID
S/
PE
RM
IT
S
AR
C
HI
TE
C T
PR
OJ
EC
T
NO
IN
DE
X N O.
FI
N A L
RE
C
OR
D
C O N
ST
RU
C
TI
O N
DR
AW
N
DE
SI
GN
ED
AP
PR
OV
ED
C
HE
C
KE
D
P.
A.
K
D.
P.
L./
R.
E.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
A004
/1
7/
1" = 10'-0"
1 EXISTING ROOF PLAN
PLAN
NORTH
A. CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING ROOF
CONDITIONS PRIOR TO DEMOLITION. REPORT ALL DISCREPANCIES
TO THE ARCHITECT BEFORE PROCEEDING.
B. DEMOLITION SHALL BE SELECTIVE. REMOVE ONLY ITEMS INDICATED
ON THE DRAWINGS OR REQUIRED FOR NEW CONSTRUCTION.
C. REMOVE EXISTING ROOFING MEMBRANE, INSULATION, FLASHING,
BALLAST (IF PRESENT), AND ASSOCIATED ACCESSORIES DOWN TO
THE STRUCTURAL ROOF DECK UNLESS NOTED OTHERWISE.
D. REMOVE DEMOLITION DEBRIS PROMPTLY AND DISPOSE OF OFF-SITE
IN ACCORDANCE WITH LOCAL REGULATIONS.
E. CONTRACTOR SHALL PROTECT EXISTING CONSTRUCTION AND
EQUIPMENT NOTED TO REMAIN FROM DAMAGE RESULTING FROM
DEMOLITION ACTIVITIES. ANY DAMAGE TO EXISTING PROPERTY
RESULTING FROM DEMOLITION SHALL BE REPAIRED IMMEDIATELY AT
THE CONTRACTOR'S EXPENSE.
F. CONTRACTOR SHALL PROTECT ADJACENT SURFACES IN
PREPARATION OF SAW CUTTING REQUIRED FOR DEMOLITION
ACTIVITIES.
G. DEMOLITION WORK SHALL BE COORDINATED WITH NEW ROOF
INSTALLATION TO MINIMIZE BUILDING EXPOSURE.
GENERAL NOTES
2 2 2 2
2 2
3 3
79' - 11" - V.I.F. 185' - 6" - V.I.F.
1/
2"
V .I.
F.
/2
V .I.
F.
3'
-3
- V .I.
F.
153' - 2" - V.I.F. 32' - 4" - V.I.F.
6'
-0
V .I.
F.
33' - 11" - V.I.F. 23' - 10" - V.I.F. 151'-11" - V.I.F.
1'-3" - V.I.F.
2'
9"
V .I.
F.
V
.I.
F.
'-1
- V
.I.
F.
8' - 9" 71' - 2"
V
.I.
F.
'-8
- V
.I.
F.
'-9
- V
.I.
F.
1"
V
.I.
F.
8' - 9" - V.I.F. 14'-8" - V.I.F.
6 6
6 6
UPPER ROOF
LOWER ROOF
UPPER ROOF
ROOF AREAS:
LOW ROOF - 8,900 SF
HIGH ROOF - 21,926 SF
TOTAL - 30,826 SF
69' - 3" - V.I.F. 10' - 8" - V.I.F.
A
1/
0.
D
PL
Y2
DA
TE
SH
EE
T
ID
EN
TI
FIC
AT
IO
N
NO
IS
SU
ED
F
OR
M D
O T
M T.
P
LE
AS
AN
T
TS
C R
O O
F R
E P
LA
C
E M
E N
T
C
O P
O R
A T
E D
R
M T
P
L E
A S
A N
T
M I
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
, M A
N A
G E
M E
N T
A N
D B
U D
G E
T
S T
A T
E O
F M
IC
H
IG
A
N
K Y
L E
G U
E R
R A
N T
, A C
T
IN
G D
IR
E
C T
O R
FA
C
IL
IT
IE
S
A N
D B
U S
IN
E
S S
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
S
IG
N A
N D
C O
N
ST
R U
C T
IO
N
D
IV
IS
IO
N
FI
LE
N
O.
B
ID
S/
PE
RM
IT
S
AR
C
HI
TE
C T
PR
OJ
EC
T
NO
IN
DE
X N O.
FI
N A L
RE
C
OR
D
C O N
ST
RU
C
TI
O N
DR
AW
N
DE
SI
GN
ED
AP
PR
OV
ED
C
HE
C
KE
D
P.
A.
K
D.
P.
L./
R.
E.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
AD103
/1
7/
1" = 10'-0"
1 DEMOLITION ROOF PLAN
PLAN
NORTH
1 EXISTING MEMBRANE ROOFING AND TAPERED INSULATION TO BE
REMOVED. POST MEMBRANE REMOVAL AND INSULATION REMOVAL,
INSPECT DECKING; REPLACE/REPAIR AS REQUIRED.
2 EXISTING COPING/GRAVEL STOP TO BE REMOVED. POST COPING REMOVAL,
INSPECT CONTINUOS NAILER AND REMOVE/REPLACE ANY DAMAGED AREAS
AS REQUIRED.
3 EXISTING ROOF DRAINS TO REMAIN. INSPECT EXISTING COVER(S) AND
REPLACE AS REQUIRED.
4 EXISTING ROOF HATCH TO REMAIN. CONTRACTOR TO CHECK FOR PROPER
OPERATION AND REPAIR/SERVICE AS REQUIRED.
5 EXISTING EXHAUST FAN TO REMAIN. CONTRACTOR TO VERIFY LOCATION
AND QUANTITY DURING DEMOLITION.
6 EXISTING VENT TO REMAIN. CONTRACTOR TO VERIFY LOCATION(S) DURING
DEMOLITION.
7 EXISTING WEATHERHEAD TO REMAIN.
8 EXISTING VENT STACKS TO REMAIN; VERIFY QUANTITY IN FIELD.
COORDINATE WITH OWNER SPECIFIC VENT STACKS THAT ARE TO BE
REMOVED DURING DEMOLITION.
9 EXISTING SKYLIGHT AND INTERIOR LIGHT WELL TO BE REMOVED.
10 EXISTING OVERFLOW.
KEYNOTES #
A. REFER TO A002 FOR WALL TYPES, DETAILS, AND ADDITIONAL
INFORMATION.
B. REFER TO A120 SERIES DRAWINGS FOR REFLECTED CEILING PLANS
AND DETAILS.
C. REFER TO A140 SERIES DRAWINGS FOR FINISH PLANS, SCHEDULES,
AND DETAILS.
D. REFER TO A160 SERIES DRAWINGS FOR FURNITURE AND EQUIPMENT
PLANS AND SCHEDULES.
E. REFER TO A600 SERIES DRAWINGS FOR DOOR SCHEDULE, WINDOW
SCHEDULE, DETAILS, AND BASIS OF DESIGN.
F. ALL DOORS TO BE LOCATED 4" FROM DRYWALL ADJACENT WALL
UNLESS OTHERWISE NOTED.
G. ALIGN FACES OF MASONRY AND STUD WALLS INDICATED IN THE
SAME PLANE ON PLANS, U.O.N.
GENERAL NOTES
A321
A321
A321
A321
A321
A321
A321
A321
SIM
A321
SIM1
A321
SIM1
A322
A322
A322
79' - 11" - V.I.F. 185' - 6" - V.I.F.
1/
2"
V .I.
F.
/2
V .I.
F.
3'
-3
- V .I.
F.
153' - 2" - V.I.F. 32' - 4" - V.I.F.
6'
-0
V .I.
F.
33' - 11" - V.I.F. 23' - 10" - V.I.F. 151'-11" - V.I.F.
1'-3" - V.I.F.
2'
9"
V .I.
F.
V .I.
F.
'-1
- V .I.
F.
8' - 9" 71' - 2"
V
.I.
F.
'-8
- V
.I.
F.
'-9
- V
.I.
F.
1"
V
.I.
F.
8' - 9" - V.I.F. 14'-8" - V.I.F.
ROOF AREAS:
LOW ROOF - 8,900 SF
HIGH ROOF - 21,926 SF
TOTAL - 30,826 SF
69' - 3" - V.I.F. 10' - 8" - V.I.F.
A322
A322
A322
A322
A322
A322
4 4
4 4
SHADED AREA INDICATES AREA
OF SLOPED STRUCTURE.
SHADED AREA INDICATES AREA
OF SLOPED STRUCTURE.
RIDGE RIDGE
RIDGE
R
ID
G E
R
ID
G E
RIDGE
RIDGE
A
1/
0.
D
PL
Y2
DA
TE
SH
EE
T
ID
EN
TI
FIC
AT
IO
N
NO
IS
SU
ED
F
OR
M D
O T
M T.
P
LE
AS
AN
T
TS
C R
O O
F R
E P
LA
C
E M
E N
T
C
O P
O R
A T
E D
R
M T
P
L E
A S
A N
T
M I
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
, M A
N A
G E
M E
N T
A N
D B
U D
G E
T
S T
A T
E O
F M
IC
H
IG
A
N
K Y
L E
G U
E R
R A
N T
, A C
T
IN
G D
IR
E
C T
O R
FA
C
IL
IT
IE
S
A N
D B
U S
IN
E
S S
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
S
IG
N A
N D
C O
N
ST
R U
C T
IO
N
D
IV
IS
IO
N
FI
LE
N
O.
B
ID
S/
PE
RM
IT
S
AR
C
HI
TE
C T
PR
OJ
EC
T
NO
IN
DE
X N O.
FI
N A L
RE
C
OR
D
C O N
ST
RU
C
TI
O N
DR
AW
N
DE
SI
GN
ED
AP
PR
OV
ED
C
HE
C
KE
D
P.
A.
K
D.
P.
L./
R.
E.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
A103
/1
7/
KEYNOTES #
1 90 MIL ELEVATE RUBBERGARD EPDM ROOFING (OR EQUAL) ON
TAPERED INSULATION. PROVIDE TAPERED INSULATION TO PROVIDE
1/4" PER FOOT ROOF SLOPE.
2 FIELD VERIFY EXISTING VENT STACKS.
3 LOCATION OF REMOVED EXISTING SKYLIGHTS. PROVIDE NEW
DECKING AND FRAMING INFILL TO MATCH EXISTING AND SECURE
ACCORDINGLY. PROVIDE CEILING TILES AND TRACK (INTERIOR) TO
MATCH EXISTING ONCE EXISTING LIGHT WELL HAS BEEN REMOVED.
4 EXISTING MECHANICAL EXHUAST FANS AND VENTS TO REMAIN.
VERIFY IN FIELD AS REQUIRED.
5 EXISTING ROOF HATCH TO REMAIN.
6 O'KEEFE'S INC 503A ACCESS LADDER (OR EQUAL). SEE
MANUFACTURER'S RECOMMENDATIONS FOR ATTACHMENT TO
EXISTING WALL.
7 EXISTING ROOF DRAIN TO REMAIN AND RE-USED. INSPECT, CLEAN,
AND/OR REPLACE IF REQUIRED.
8 EXISTING OVERFLOW DRAIN TO REMAIN AND RE-USED. CLEAN,
INSPECT, AND/OR REPLACE IF REQUIRED.
9 32" W ROOF WALK-OFF MAT, 165 LF, V.I.F., SEE SPECIFICATIONS.
1" = 10'-0"
1 NEW ROOF PLAN
PLAN
NORTH
T.O. MASONRY (HIGH)
19' - 4"
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) - BASIS OF DESIGN
EXISTING CMU - V.I.F. AS
REQUIRED.
EXISTING OVERHEAD
DOOR
ELEVATE ADVANTEDGE
METAL EDGE SYSTEM (OR
EQUAL) - BASIS OF DESIGN.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
2X NAILER(S) TO MATCH EXISTING.
NAILER MUST BE INSTALLED TO
ADHERE TO APPLICABLE BUILDING
CODES OR 200 LB PER LINEAR
FOOT MIN IN ANY DIRECTION.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
COVER BOARD
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) - BASIS OF DESIGN
PROVIDE TREATED
BLOCKING AS REQUIRED AT
RIDGE.
EXISTING ROOF STRUCTURE -
V.I.F. AS REQUIRED
EXISTING CMU - V.I.F. AS
REQUIRED.
EXISTING ROOF
STRUCTURE - V.I.F. AS
REQUIRED
COVER BOARD
T.O. MASONRY (HIGH)
19' - 4"
EXISTING 1 1/2" METAL ROOF
DECKING TO REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6" TAPERED
INSULATION (OR EQUAL) ON COVER
BOARD - BASIS OF DESIGN
EXISTING CMU - V.I.F. AS
REQUIRED.
ELEVATE ADVANTEDGE
METAL EDGE SYSTEM (OR
EQUAL) - BASIS OF DESIGN.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
2X NAILER(S) TO MATCH EXISTING.
NAILER MUST BE INSTALLED TO
ADHERE TO APPLICABLE BUILDING
CODES OR 200 LB PER LINEAR
FOOT MIN IN ANY DIRECTION.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
EXISTING ROOF
STRUCTURE - V.I.F. AS
REQUIRED
T.O. MASONRY (HIGH)
19' - 4"
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) - BASIS OF DESIGN
EXISTING CMU - V.I.F. AS
REQUIRED.
EXISTING ROOF
STRUCTURE - V.I.F.
AS REQUIRED
ELEVATE ADVANTEDGE
METAL EDGE SYSTEM (OR
EQUAL) - BASIS OF DESIGN.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
2X NAILER(S) TO MATCH EXISTING.
NAILER MUST BE INSTALLED TO
ADHERE TO APPLICABLE BUILDING
CODES OR 200 LB PER LINEAR
FOOT MIN IN ANY DIRECTION.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
COVER BOARD
T.O. MASONRY (HIGH)
19' - 4"
ELEVATE ADVANTEDGE
METAL EDGE SYSTEM (OR
EQUAL) - BASIS OF DESIGN.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
2X NAILER(S) TO MATCH EXISTING.
NAILER MUST BE INSTALLED TO
ADHERE TO APPLICABLE BUILDING
CODES OR 200 LB PER LINEAR
FOOT MIN IN ANY DIRECTION.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
EXISTING 1 1/2" METAL ROOF
DECKING TO REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6" TAPERED
INSULATION (OR EQUAL) ON COVER
BOARD - BASIS OF DESIGN
EXISTING CMU - V.I.F. AS
REQUIRED.
EXISTING ROOF
STRUCTURE - V.I.F. AS
REQUIRED
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) ON COVER BOARD -
BASIS OF DESIGN
EXISTING ROOF STRUCTURE -
V.I.F. AS REQUIRED
EXISTING CMU - V.I.F. AS
REQUIRED.
PROVIDE TREATED
BLOCKING AS REQUIRED AT
RIDGE.
EXISTING ROOF
STRUCTURE - V.I.F. AS
REQUIRED
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
T.O. MASONRY (HIGH)
19' - 4"
T.O. MASONRY (LOW)
14' - 0"
M
IN8"
O'KEEFFE'S INC 503A ACCESS LADDER
(OR EQUAL). SEE MANUFACTURER'S
RECOMMENDATIONS FOR ATTACHMENT
TO EXISTING WALL.
5'
4"
V .I.
F.
S
E E
M A
N U
FA
C
TU
R
E R
'S S
P E
C
IF
IC
A
TI
O
N S
ELEVATE ADVANTEDGE
METAL EDGE SYSTEM (OR
EQUAL) - BASIS OF DESIGN.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
2X NAILER(S) TO MATCH EXISTING.
NAILER MUST BE INSTALLED TO
ADHERE TO APPLICABLE BUILDING
CODES OR 200 LB PER LINEAR
FOOT MIN IN ANY DIRECTION.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) ON COVER BOARD -
BASIS OF DESIGN
EXISTING ROOF
STRUCTURE - V.I.F. AS
REQUIRED
EXISTING CMU - V.I.F. AS
REQUIRED.
EXISTING ROOF
STRUCTURE - V.I.F. AS
REQUIRED
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) ON COVER BOARD -
BASIS OF DESIGN
A321
T.O. MASONRY (LOW)
14' - 0"
8" M
IN
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) ON COVER BOARD -
BASIS OF DESIGN
3/4" TREATED PLYWOOD
BACKING ATTACHED TO
EXISTING MASONRY.
V .I.
F.
O'KEEFFE'S INC 503A ACCESS
LADDER (OR EQUAL). SEE
MANUFACTURER'S
RECOMMENDATIONS FOR
ATTACHMENT TO EXISTING WALL.
EXISTING CMU - V.I.F. AS
REQUIRED.
REMOVABLE METAL
COUNTER FLASHING.
TERMINATION BAR.
SLOPED FOR POSITIVE
DRAINAGE METAL FLASHING.
A
1/
0.
D
PL
Y2
DA
TE
SH
EE
T
ID
EN
TI
FIC
AT
IO
N
NO
IS
SU
ED
F
OR
M D
O T
M T.
P
LE
AS
AN
T
TS
C R
O O
F R
E P
LA
C
E M
E N
T
C
O P
O R
A T
E D
R
M T
P
L E
A S
A N
T
M I
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
, M A
N A
G E
M E
N T
A N
D B
U D
G E
T
S T
A T
E O
F M
IC
H
IG
A
N
K Y
L E
G U
E R
R A
N T
, A C
T
IN
G D
IR
E
C T
O R
FA
C
IL
IT
IE
S
A N
D B
U S
IN
E
S S
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
S
IG
N A
N D
C O
N
ST
R U
C T
IO
N
D
IV
IS
IO
N
FI
LE
N
O.
B
ID
S/
PE
RM
IT
S
AR
C
HI
TE
C T
PR
OJ
EC
T
NO
IN
DE
X N O.
FI
N A L
RE
C
OR
D
C O N
ST
RU
C
TI
O N
DR
AW
N
DE
SI
GN
ED
AP
PR
OV
ED
C
HE
C
KE
D
P.
A.
K
D.
P.
L./
R.
E.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
A321
/1
7/
3/4" = 1'-0"
1 SECTION DETAIL
3/4" = 1'-0"
2 SECTION DETAIL
3/4" = 1'-0"
3 SECTION DETAIL
3/4" = 1'-0"
4 SECTION DETAIL
3/4" = 1'-0"
5 SECTION DETAIL
3/4" = 1'-0"
6 SECTION DETAIL
3/4" = 1'-0"
7 SECTION DETAIL
1 1/2" = 1'-0"
8 ENLARGED FLASHING DETAIL
T.O. MASONRY (LOW)
14' - 0"
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) ON COVER BOARD-
BASIS OF DESIGN
EXISTING CMU - V.I.F. AS
REQUIRED.
ELEVATE ADVANTEDGE
METAL EDGE SYSTEM (OR
EQUAL) - BASIS OF DESIGN.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
2X NAILER(S) TO MATCH EXISTING.
NAILER MUST BE INSTALLED TO
ADHERE TO APPLICABLE BUILDING
CODES OR 200 LB PER LINEAR
FOOT MIN IN ANY DIRECTION.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
EXISTING STEEL BEAM -
V.I.F. AS REQUIRED
NOTE:
ALIGN BLOCKING W/ TOP OF
TAPERED INSULATION, TYP.
T.O. MASONRY (LOW)
14' - 0"
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) ON COVER BOARD -
BASIS OF DESIGN
EXISTING CMU - V.I.F. AS
REQUIRED.
ELEVATE ADVANTEDGE
METAL EDGE SYSTEM (OR
EQUAL) - BASIS OF DESIGN.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
2X NAILER(S) TO MATCH EXISTING.
NAILER MUST BE INSTALLED TO
ADHERE TO APPLICABLE BUILDING
CODES OR 200 LB PER LINEAR
FOOT MIN IN ANY DIRECTION.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
EXISTING STEEL BEAM -
V.I.F. AS REQUIRED
NOTE:
ALIGN BLOCKING W/ TOP OF
TAPERED INSULATION, TYP.
T.O. MASONRY (LOW)
14' - 0"
EXISTING 1 1/2" METAL
ROOF DECKING TO
REMAIN
ELEVATE RUBBERGARD
EPDM ROOFING (OR
EQUAL) - BASIS OF DESIGN.
ELEVATE ISOGARD 6"
TAPERED INSULATION (OR
EQUAL) ON COVER BOARD -
BASIS OF DESIGN
EXISTING CMU - V.I.F. AS
REQUIRED.
ELEVATE ADVANTEDGE
METAL EDGE SYSTEM (OR
EQUAL) - BASIS OF DESIGN.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
2X NAILER(S) TO MATCH EXISTING.
NAILER MUST BE INSTALLED TO
ADHERE TO APPLICABLE BUILDING
CODES OR 200 LB PER LINEAR
FOOT MIN IN ANY DIRECTION.
1 1/4" HOT DIPPED
GALVANIZED ROOF NAILS AT
12" O.C.
EXISTING STEEL BEAM -
V.I.F. AS REQUIRED
NOTE:
ALIGN BLOCKING W/ TOP OF
TAPERED INSULATION, TYP.
A
1/
0.
D
PL
Y2
DA
TE
SH
EE
T
ID
EN
TI
FIC
AT
IO
N
NO
IS
SU
ED
F
OR
M D
O T
M T.
P
LE
AS
NA
T
TS
C R
O O
F R
E P
LA
C
E M
E N
T
C
O P
O R
A T
E D
R
M T
P
L E
A S
A N
T
M I
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
, M A
N A
G E
M E
N T
A N
D B
U D
G E
T
S T
A T
E O
F M
IC
H
IG
A
N
K Y
L E
G U
E R
R A
N T
, A C
T
IN
G D
IR
E
C T
O R
FA
C
IL
IT
IE
S
A N
D B
U S
IN
E
S S
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
S
IG
N A
N D
C O
N
ST
R U
C T
IO
N
D
IV
IS
IO
N
FI
LE
N
O.
B
ID
S/
PE
RM
IT
S
AR
C
HI
TE
C T
PR
OJ
EC
T
NO
IN
DE
X N O.
FI
N A L
RE
C
OR
D
C O N
ST
RU
C
TI
O N
DR
AW
N
DE
SI
GN
ED
AP
PR
OV
ED
C
HE
C
KE
D
P.
A.
K
D.
P.
L./
R.
E.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
A322
/1
7/
3/4" = 1'-0"
1 SECTION DETAIL
3/4" = 1'-0"
2 SECTION DETAIL
3/4" = 1'-0"
3 SECTION DETAIL
A
1/
0.
D
PL
M D
O T
M T.
P
LE
AS
AN
T
TS
C R
O O
F R
E P
LA
C
E M
E N
T Y2
DA
TE
SH
EE
T
ID
EN
TI
FIC
AT
IO
N
NO
IS
SU
ED
F
OR
C
O P
O R
A T
E D
R
M T
P
L E
A S
A N
T
M I
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
, M A
N A
G E
M E
N T
A N
D B
U D
G E
T
S T
A T
E O
F M
IC
H
IG
A
N
K Y
L E
G U
E R
R A
N T
, A C
T
IN
G D
IR
E
C T
O R
FA
C
IL
IT
IE
S
A N
D B
U S
IN
E
S S
S E
R V
IC
E
S A
D M
IN
IS
T R
A T
IO
N
D E
SI
G
N A
N D
C O
N
ST
R U
C T
IO
N
D
IV
IS
IO
N
FI
LE
N
O.
B
ID
S/
PE
RM
IT
S
AR
C
HI
TE
C T
PR
OJ
EC
T
NO
IN
DE
X N O.
FI
N A L
RE
C
OR
D
C O N
ST
RU
C
TI
O N
DR
AW
N
DE
SI
GN
ED
AP
PR
OV
ED
C
HE
C
KE
D
P.
A.
K
D.
P.
L./
R.
E.
L./
R.
E.
G.
D.
P.
L./
R.
E.
G.
A501
/1
7/
NOTE:
EXISTING DRAINS/OVERFLOWS TO REMAIN.
REPLACE STRAINER BASKET IF APPLICABLE.
File details come from the government source that posted it. Updated .