589A7-23-314-Drawings SitePrepForGamma-CD.pdf
PDF 10 MB Posted
- Solicitation number
- 36C25525R0067
About this file
These are architectural and engineering construction documents for a site preparation project for a Gamma Camera at the Robert J. Dole VA Medical Center in Wichita, Kansas. The project involves renovating and preparing approximately 1,000 square feet of existing medical space to accommodate a new GE Healthcare NM/CT 850 Nuclear Medicine/CT imaging system.
The comprehensive drawing set includes detailed plans for architectural modifications, electrical systems, mechanical systems, fire suppression, and structural considerations. Key elements include installing a new ceiling, modifying walls, adding specialized radiation shielding, updating electrical infrastructure with dedicated power distribution, installing new HVAC equipment, and preparing floor anchoring for the heavy medical imaging equipment. The drawings specify precise technical requirements such as floor load specifications, radiation protection guidelines, temperature and humidity parameters, and interconnection details for the medical imaging system. The project is fully sprinklered and designed to meet VA medical facility standards, with a planned construction document date of March 4, 2025.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 5897-23-314 1.pdf | ||
| 36C25525R0067 0002.docx | DOCX document | |
| 5897-23-314 2.pdf | ||
| 36C25525R0067 0001.docx | DOCX document | |
| 589A7-23-314 CD SPECIFICATIONS 20250415 002.pdf | ||
| 36C25525R0067_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:3
P
M
GI001
COVER SHEET
ROBERT J. DOLE VA MEDICAL CENTER
S
IT
E P
R E
P F
O R
G A
M M
A C
A M
E R
A
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
5-
-0
SITE PREP FOR GAMMA CAMERA
5500 E. KELLOGG, WICHITA, 67218
Mark Revisions: Date:
imurphree Snapshot
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:3
P
M
GI002
INDEX OF DRAWINGS
Index of Drawings
E-501 ELECTRICAL DETAILS
ED101 ELECTRICAL DEMOLITION PLAN
EG101 ELECTRICAL SYMBOLS LEGEND AND GENERAL NOTES
EL101 FIRST FLOOR - LIGHTING PLAN
EP101 FIRST FLOOR - POWER AND SPECIAL SYSTEMS PLAN
GENERAL INFORMATION
GI001 COVER SHEET
GI002 INDEX OF DRAWINGS
LIFE SAFETY
GI101 FIRST FLOOR - LIFE SAFETY PLAN
STRUCTURAL
SE101 STRUCTURAL PLAN
ARCHITECTURAL
AG001 ARCHITECTURAL ABBREVIATIONS, LEGENDS AND NOTES
AD101 FIRST FLOOR - DEMOLITION PLAN
AE101 FIRST FLOOR - FLOOR PLAN
AC101 FIRST FLOOR - REFLECTED CEILING PLAN
AE401 WALL SECTIONS
AE701 DOOR AND FRAME TYPES, DETAILS AND DOOR SCHEDULE
AE801 PARTITION TYPES
AE802 PARTITION DETAILS
AE905 INTERIOR ELEVATIONS
INTERIOR DESIGN
IN101 FIRST FLOOR - INTERIOR FLOOR FINISH PLAN
IN601 ROOM FINISH SCHEDULE
EQUIPMENT
QH101 FIRST FLOOR - EQUIPMENT PLAN
FD101 FIRST FLOOR FIRE SUPPRESSION DEMOLITION PLAN
FG101 FIRE SUPPRESSION SYMBOLS LEGEND AND GENERAL NOTES
FP101 FIRST FLOOR FIRE SUPPRESSION PLAN
M-601 MECHANICAL DETAILS
M-701 MECHANICAL SCHEDULES
MECHANICAL
ELECTRICAL
FIRE PROTECTION
APPENDIX A GE HEALTHCARE NM/CT 850- NM/CT860 FINAL STUDY
MD101 FIRST FLOOR MECHANICAL DEMOLITION PLAN
MG101 MECHANICAL SYMBOLS LEGEND AND GENERAL NOTES
MH101 FIRST FLOOR MECHANICAL PLAN
PD101 FIRST FLOOR PLUMBING DEMOLITON PLAN
PG101 PLUMBING SYMBOLS LEGEND AND GENERAL NOTES
PL101 FIRST FLOOR PLUMBING PLAN
APPENDICES
Mark Revisions: Date:
imurphree Rectangle imurphree Snapshot imurphree Snapshot imurphree Rectangle imurphree Rectangle imurphree Snapshot imurphree Snapshot imurphree Snapshot imurphree Snapshot imurphree Rectangle imurphree Snapshot imurphree Snapshot imurphree Snapshot imurphree Snapshot
SMOKE PARTITION
SYMBOL
FIRE WALL LEGEND
DESCRIPTION
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
1-HOUR FIRE / SMOKE
BARRIER
2-HOUR FIRE / SMOKE
BARRIER
30-MINUTE FIRE / SMOKE
BARRIER
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SUITESTE STE STE STE STE
HAZARDOUS AREAHZ HZ HZ HZ HZ
HEALTHCARE CORRIDOR
GAMMA
CAMERA
TREADMILL
CLEAN
SUPPLY
LINEN
ROOM
IMAGING
ROOM
TOILET
HOT LAB
RECEPTION
MECHANICAL
WAITING
VESTIBULE
STAIR
STAIR
CORRIDOR
1-CORR-A
DENTAL
PROGRAM
DENTAL
PROGRAM
DENTAL
PROGRAM
DENTAL
DENTAL
PROGRAM
DENTAL
PROGRAM
117A
ULTRASOUND
NUCLEAR
MEDICINE
VIEW ROOM
NUCLEAR
MEDICINE
112A
CLINICAL
SPACE
ELEVATOR
1-ELEV
MECH
WAITING
CORRIDOR
1-CORR-B
GAMMA
CAMERA
CONTROL
92' - 7"
21 sec
PLAN
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:3
P
M
GI101
FIRST FLOOR - LIFE SAFETY PLAN
LIFE SAFETY NOTES
1. EXISTING FIRE-RATED WALL - VERIFY RATING.
1/8" = 1'-0"1
FIRST FLOOR - LIFE SAFETY PLAN
Mark Revisions: Date:
W
ID
E X
D E
E P
C O
N C
R E
T E
R
IB
S S
P A
C E
D A
T
O .C
E X
IS
T
IN
G
C O
N C
R E
T E
R
IB
B E
D F
L O
O R
S T
Y S
T E
M W
C O
N C
S
L A
B
PROVIDE ANCHORAGE PER DETAIL A/SE101.
COORDINATE ANCHOR LOCATIONS WITH
EQUIPMENT SUPPLIER.
EQUIPMENT WEIGHTS:
EXISTING SIEMENS SYMBIA S GAMMA CAMERA = 9,597 LBS.
NEW GE NM/CT 850
GAMMA CAMERA = 10,006 LBS.
NEW EQUIPMENT IS 4.2% HEAVIER THAN EXISTING
EQUIPMENT. PER SECTION 805.2 OF THE EXISTING
BUILDING CODE (2024 EDITION), EXISTING STRUCTURAL
FRAMING IS NOT REQUIRED TO BE ALTERED OR
REPLACED IF NEW SUPERIMPOSED LOAD IS LESS THAN
5% GREATER THAN EXISTING SUPERIMPOSED LOAD.
NEW GAMMA CAMERA
PROVIDE 5/8"Ø THRU BOLT ATTACHMENT W/
WASHER AND NUT EACH SIDE OF SLAB WHERE
EQUIPMENT ANCHORAGE POINT IS LOCATED
ABOVE THE CONCRETE SLAB
PROVIDE 5/8"Ø HILTI HY200 ANCHOR W/ 5"
MINIMUM CONCRETE EMBED. WHERE
EQUIPMENT ANCHORAGE POINT IS LOCATED
ABOVE EXISTING CONCRETE RIB BEAM
EXISTING CONCRETE
FLOOR SLAB
EXISTING CONCRETE
FLOOR SLAB
1/4"Ø THREADED ROD AT CASSETTE
SUPPORT POINTS. EMBED INTO EXISTING
CONCRETE SLAB AND/OR RIB BEAM W/
HILTI HY200 X 2 3/8" MINIMUM CONCRETE
EMBED.
CEILING MOUNTED
CASSETTE, COORDINATE
WITH MEP
PLAN
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREPERATION FOR
GAMMA CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 CNS CMS
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
MKEC Project No.
A u to d e s k D o c s /1
A
-2
-3
S it e
P re p f o r G a m m a C a m e ra
/2
G a m m a
C a m e ra
S tr u c tu ra l_ v
.r v t
/2
/2
:2
:3
P
M
SE101
STRUCTURAL PLAN
2401080611
4'2' 8'0' 1'
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN
N
STRUCTURAL GENERAL NOTES:
1. CODE: INTERNATIONAL BUILDING CODE, 2024 EDITION.
2. FLOOR LIVE LOAD: 60 PSF
3. WIND: ULTIMATE WIND SPEE - 122 MPH (3 SECOND GUST)
EXPOSURE C, RISK CATEGORY IV
4. SEISMIC: DESIGN CATEGORY - C, SITE CLASS - D
5. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS AND REPORT
ANY DISCREPANCIES TO THE ARCHITECT AND ENGINEER IMMEDIATELY.
6. IF CONDITIONS DIFFER, CONTACT THE ARCHITECT OR ENGINEER.
0' 1' 2' 3'
SCALE: 1 1/2" = 1'-0"
SE101
A
SECTION AT FLOOR MOUNTED EQUIPMENT
0' 1' 2' 3'
SCALE: 1 1/2" = 1'-0"
SE101
B
CEILING HUNG CASSETTE SUPPORT
Mark Revisions: Date:
1. THE CONTRACTOR SHALL INSPECT THE SITE, STUDY EXISTING CONDITIONS, REVIEW DRAWINGS AND SPECIFICATIONS.
CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT.
2. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR THE WORK AND BE RESPONSIBLE FOR SAME. COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED AND MAKE ANY NECESSARY OFFSETS TO CONCEAL PIPING AND DUCTWORK AND TO CLEAR EQUIPMENT, STRUCTURAL MEMBERS AND OTHER OBSTRUCTIONS.
3. ALL UTILITIES AND SERVICES SHALL BE KEPT IN CONTINUOUS OPERATION UNLESS WRITTEN PERMISSION IS OTHERWISE GRANTED BY THE GOVERNMENT CONTRACTOR MUST
CONTACT VA'S COR PRIOR TO ANY SHUTDOWNS.
4. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, OF THE BEST QUALITY AND FREE FROM DEFECTS.
5. MANUFACTURER AND MODEL NUMBERS SPECIFIED ESTABLISH THE TYPE AND QUALITY REQUIRED, UNLESS OTHERWISE NOTED.
6. ALL WORK SHALL COMPLY WITH APPLICABLE REGULATIONS, CODES AND ORDINANCES.
7. THE CONTRACTOR SHALL PERFORM ALL TESTS AS SPECIFIED OR AS NECESSARY TO DEMONSTRATE A COMPLETE AND SATISFACTORY INSTALLATION.
8. INSTALL THE SPECIFIED FIRE STOPPING (SLEEVES, WRAP, CONDUIT, ETC.) AT RATED CONSTRUCTION (NEW OR EXISTING) OR SMOKE PARTITIONS:
A. REPLACE FIRE STOP AT ALL PENETRATIONS WHERE NEW DEVICES/LINES USE EXISTING PENETRATIONS OF RATED BARRIERS.
B. REPLACE FIRE STOP AT ALL EXISTING PENETRATIONS OF RATED BARRIERS WHERE EXISTING LINES HAVE BEEN MODIFIED OR RELOCATED.
C. FIRE STOP ALL NEWLY CREATED PENETRATIONS WHERE NEW DEVICES/LINES PENETRATE EXISTING FLOORS, CEILINGS AND OTHER RATED BARRIERS.
D. FIRE STOP ALL NEW PENETRATIONS WHERE NEW DEVICES/LINES PENETRATE THROUGH NEWLY CONSTRUCTED RATED BARRIERS OR SMOKE PARTITIONS.
E. USE ONLY APPROVED FIRE CAULKING AND FIRE STOPS (SEE SPECIFICATIONS).
9. ALL METAL STUD AND GYPSUM WALLBOARD PARTITIONS ARE DIMENSIONED TO THE OUTSIDE FINISH FACE OF WALL AND TO THE COLUMN GRID UNLESS OTHERWISE NOTED.
10. ALL GYPSUM BOARD SHALL BE TYPE 'X' FIRE CODE GYPSUM BOARD AND SHALL BE MOLD AND MOISTURE RESISTANT.
11. PROVIDE WOOD BLOCKING OR 16 GA. SHEET METAL BACKING PLATES IN ALL WALLS TO RECEIVE WALL HUNG ACCESSORIES, SUCH AS EQUIPMENT, GRAB BARS, MILLWORK, COAT HOOKS, AND DOOR STOPS, ETC. IF WOOD BLOCKING IS USED, PROVIDE AS FIRE-RESISTANT.
12. THE CONTRACTOR SHALL WORK WITH THE CONDITIONS AS THEY EXIST AT THE SITE. ALL ABOVE CEILING CONDITIONS SHALL BE REVIEWED, AND MODIFICATIONS IDENTIFIED, COORDINATED, AND INCORPORATED INTO THE SHOP DRAWING PROCESS. COORDINATE ALL ABOVE CEILING WORK TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM AT NO ADDITIONAL COST TO THE GOVERNMENT COORDINATION SHALL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:
A. THE GOVERNMENT'S EQUIPMENT REQUIREMENTS.
B. THE CEILING SUPPORT SYSTEM.
C. THE MECHANICAL DUCTWORK SYSTEM.
D. THE LIGHTING FIXTURES.
E. ELECTRICAL WIRING AND CONDUIT SYSTEMS.
F. THE PLUMBING AND PIPING SYSTEMS.
G. FIRE PROTECTION SYSTEMS
H. THE COMMUNICATIONS AND SPECIAL SYSTEMS.
13. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED
EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
14. ALL NEW STUD WALLS AND GYPSUM BOARD SHALL EXTEND TO STRUCTURE UNLESS NOTED OTHERWISE.
15. WHEN WALL PARTITIONS OF DIFFERENT FIRE RATING INTERSECT, THE HIGHEST RATED PARTITION TAKES PRECEDENCE. MAINTAIN RATING BEHIND RECESSED AREAS IN WALLS.
16. ALL CORRIDOR WALLS ARE REQUIRED TO BE SMOKE TIGHT, WHETHER THEY ARE FIRE RATED OR NOT. REPAIR AND EXTEND AT LEAST THE CORRIDOR SIDE OF NON-RATED
CORRIDOR WALLS TO STRUCTURE, UNLESS NOTED OTHERWISE, SEE WALL TYPES.
17. COORDINATE CONSTRUCTION REQUIREMENTS WITH CIVIL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, PLUMBING AND ELECTRICAL DRAWINGS.
18. FURNITURE SHOWN IS N.I.C., UNLESS NOTED OTHERWISE.
19. EQUIPMENT SHALL BE PROVIDED BY THE GOVERNMENT AND INSTALLED BY THE CONTRACTOR AS SCHEDULED, UNLESS NOTED OTHERWISE.
GENERAL ARCHITECTURAL NOTES
SEE SECTION 01 00 00 - GENERAL REQUIREMENTS FOR FULL
DESCRIPTION OF DEDUCT ALTERNATES. REFER TO DRAWINGS FOR
ADDITIONAL NOTES AND DIRECTIONS RELATED TO DEDUCT
ALTERNATES.
LIST OF BID DEDUCT ALTERNATES
1. REMOVAL OF DOOR BETWEEN CORRIDOR AND WAITING FROM
SCOPE.
2. REMOVAL OF DEMOLITION OF DOOR 108 TO GAMMA CAMERA
FROM SCOPE.
3. REMOVAL OF DEMOLITION OF DOOR BETWEEN GAMMA CAMERA
AND TREADMILL FROM SCOPE.
4. DELETION OF SKYFACTORY LIGHT IN GAMMA CAMERA ROOM.
BID ITEMS & DEDUCT ALTERNATES
FRONT APPROACH, PULL SIDE FRONT APPROACH, PUSH SIDE
NOTE: X=12" MINIMUM IF DOOR HAS
BOTH A CLOSER AND LATCH
HINGE SIDE APPROACHES - SWINGING DOORS
LATCH SIDE APPROACHES - SWINGING DOORS
NOTE:
1. ALL DOORS IN ALCOVES SHALL COMPLY WITH CLEARANCES FOR FRONT APPROACHES.
HINGE APPROACH, PULL SIDE HINGE APPROACH, PUSH SIDE
LATCH APPROACH, PULL SIDE LATCH APPROACH, PUSH SIDE
NOTE: X=36" MINIMUM IF Y=60"; X=42"
MINIMUM IF Y=54".
NOTE: Y=48" MINIMUM IF DOOR HAS
BOTH A LATCH AND CLOSER.
NOTE: Y=54" MINIMUM IF DOOR HAS
CLOSER.
NOTE: Y=48" MINIMUM IF DOOR HAS
CLOSER.
FRONT APPROACHES - SWINGING DOORS
MIN.
1'-6"
M
IN
M
IN
X
54" MIN.
M
IN
5' -0
X
MIN.
2'-0"
M
IN
M
IN
MIN.
2'-0" X X
Y
Y
Y
PULL SIDE PUSH SIDE
POCKET OR HINGE APPROACH - SLIDING BARN DOORS
POCKET OR HINGE APPROACH STOP OR LATCH APPROACH
FRONT AND SIDE APPROACHES - NO DOORS
M
IN
M
IN
2'-0"42
M
IN
22" MIN. 42
M
IN
GENERAL SYMBOLS
A101
SIM
A101
SIM
1i
A101
SIM
D
SCALE:1 View Name 1/8" = 1'-0"
A
NTRUE
NORTH
A
B
EARTH
EARTH GRAVEL
CONCRETE
METALS
BRICK
CMU
TILE
STONE
WOOD
GYPSUM
GLASS
INSULATION
REGULAR
STEEL ALUMINUM
FACE COMMON
CMU
CERAMIC
MARBLE LIMESTONE
FINISH BLOCKING
PLASTER OR GWB
LARGE SCALE SMALL SCALE
BATT OR LOOSE RIGID
SURFACE
ACTUAL SQ. FT.
PROGRAMMED SQ. FT.
ROOM NUMBER
DOOR NUMBER
KEYNOTE
WALL TYPE
REVISION NUMBER
ELEVATION INDICATION
COLUMN GRID
IDENTIFICATION
NORTH ARROW
XXX WINDOW NUMBER
DETAIL TITLE
BUILDING SECTION
WALL SECTION
EXTERIOR/INTERIOR
ELEVATION
INTERIOR MULTI-VIEW
ELEVATION
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
MATERIALS REFERENCE
Room Name
150 PSF / 150 SF
PROPERTY CORNER
PROPERTY LINE
4" UNDERGROUND COMMUNICATION
(NO. INDICATES NO. OF DUCTS)
4" UNDERGROUND DUCT
(NO. INDICATES NO. OF DUCTS)
TELEPHONE LINE OH
UNDERGROUND ELECTRICAL
CONDUIT
OVERHEAD POWER LINE
ELECTRICAL MANHOLE
P/T = POWER & TELEPHONE
W/ STREET LIGHT
W/ DOWN GUY (NO. INDICATES LENGTH, CLASS
GUY & ANCHOR STRENGTH)
POWER POLE (NO. INDICATES LENGTH &
CLASS)
REMOVE OR ABANDON LINE
VALVE
GAS LINE
IRRIGATION WATER MAIN
FIRE WATER LINE
WATER LINE
STORM SEWER
SANITARY SEWER FORCE MAIN
SANITARY SEWER
CURB LINE
STREET CENTER LINE
BUILDING
EXISTING NEW
SITE
EXISTING NEW
S
MH CO
SFM
SS SS
MH
CLAL
Y.D.
F.H.
W
F
IRM
G
4M
P T
P T
P
UG
T
2-T
P
UG
T
2-T
POLE
4M
45-2
45-2
G
IRM
F
Y.D.
F.H.
W
AL
SS SS
MH
SFM
S
MH CO
GRID COORDINATES
SECTION LINE
CONTOURS
SPOT ELEVATIONS
DRAINAGE DITCH OR SWALE
CONCRETE PAVEMENT (SECTION)
BITUMINOUS PAVEMENT (SECTION)
CONTRACTION JOINT FOR PAVEMENT
BORINGS, TEXT
TREES, DECIDUOUS - WITH
DIAMETER
EVERGREEN - WITH HEIGHT
SHRUBS
CHAIN-LINK FENCE
BARBED WIRE FENCE
SECURITY FENCE XX XX
XX
XX XX
XX
12"
10'
HIGH
12" (TO BE REMOVED)
10' (TO BE REMOVED)
HOLE #3
90 X 10W 90 X 10 W (TOP OF WALL)
90 X 10C 90 X 10 C (TOP OF CURB)
90 X 10P 90 X 10 P (TOP OF PAVEMENT)
90 X 10 90 X 10
SEC 24
SEC 25
290 N
90 W
A101
SIM
DETAIL SECTION
AE201
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:3
P
M
AG001
ARCHITECTURAL ABBREVIATIONS,
LEGENDS AND NOTES
A
A/C AIR CONDITIONING
AB ANCHOR BOLT / AIR BLENDER
ABS ACRYLONITRILE-BUTADIENE-STYRENE
AC ALTERNATING CURRENT / AIR COMPRESSOR
ACP ASBESTOS CEMENT PIPE
ACU AIR CONDITIONING UNIT
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJACENT / ADJUSTABLE
ADR ACCESS DOOR
AFF ABOVE FINISH FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
APPROX APPROXIMATELY
APT APARTMENT
ARCH ARCHITECT(URAL)
ASPH ASPHALT
AT ACOUSTICAL PANEL CEILING
ATB AIR TERMINAL BOX
ATD AIR TRANSFER DUCT
ATU AIR TERMINAL UNIT
AUX AUXILIARY
AVG AVERAGE
AWC ACOUSTICAL WALLCOVERING
AZ AZIMUTH
B
BB BALLED AND BURLAPPED
BD BOARD
BDD BACK DRAFT DAMPER
BE BOTTOM ELEVATION
BL BUILDING LINE
BLDG BUILDING
BLKG BLOCKING
BM BENCH MARK / BEAM
BR BARE ROOT
BRG BEARING
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
C/C CENTER TO CENTER
CAB CABINET
CB CIRCUIT BREAKER / CATCH BASIN
CC COOLING UNIT
CE COVER ELEVATION
CEM CEMENT
CFM CUBIC FEET PER MINUTE
CFS CONCRETE FLOOR SEALER
CG CORNER GUARD
CH CHILLER
CI CURB INLET / CAST IRON
CIP CAST IRON PIPE
CJ CONTROL JOINT OR CONTRACTION JOINT
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CM CENTIMETER
CMH CUBIC METER PER HOUR
CMP CORRUGATED METAL PIPE
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CO CLEANOUT / CARBON MONOXIDE
CO2 CARBON DIOXIDE
COL COLUMN
COMB COMBINATION / COMBINE
COMP COMPRESSIBLE
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS / CONTINUATION
CONTR CONTRACTOR
CORR CORRIDOR
CP CEMENT PIPE
CPT CARPET
CSF CUBIC FEET PER SECOND
CT CERAMIC TILE / COOLING TOWER
CTR CENTER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CUYD CUBIC YARD
CW COLD WATER
D
D DRAIN / DIFFUSER
DA DENTAL AIR
DBL DOUBLE
DEPR DEPRESSED
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFUSER
DIP DUCTILE IRON PIPE
DISC DISCONNECT
DISP DISPENSER
DIST DISTRIBUTION
DK DECK
DL DEAD LOAD
DN DOWN
DO DITTO
DPR DAMPER
DR DOOR
DS DOWNSPOUT
DV DENTAL VACUUM
DWG DRAWING
DWL DOWEL
ABBREVIATIONS
JT JOINT
K
KC MIL THOUSAND CIRCULAR MILS
KCJ KEYED CONSTRUCTION JOINT
KIT KITCHEN
KPA KILOPASCALS
KS KITCHEN SINK
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATTS
L
L LITER
LA LABORATORY AIR
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUNDS
LF LINEAR FEET
LIN LINEAR
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LMU LIGHTWEIGHT MASONRY UNITS
LONG LONGITUDINAL
LPM LITERS PER MINUTE
LT LIGHT
LT WT LIGHT WEIGHT
LTG LIGHTING
LV LABORATORY VACUUM
LVL LEVEL
LVT LUXURY VINYL TILE
M
M METER
M2 SQUARE METER
M3 CUBIC METER
MA MEDICAL AIR
MAINT MAINTENANCE
MAR MARBLE
MAS MASONRY
MAT MATERIAL / ENTRY CARPET
MAX MAXIMUM
MBH 1000 BTUH
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MET METAL
MFR MANUFACTURER
MG MOTOR GENERATOR / MEDICAL GAS
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MM MILLIMETER
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING
MULL MULLION
MV MEDICAL VACUUM
N
N NITROGEN
N2O NITROUS OXIDE
NEC NATIONAL ELECTRICAL CODE
NFPA NATIONAL FIRE PROTECTION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O
O/S OFFSET
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
OX OXYGEN
OZ OUNCE
P
P PAINT / PUMP / PENDANT
PA PASCAL
PART PARTITION
PAVT PAVEMENT
PC POINT OF CURVATURE
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PERP PERPENDICULAR
PHC PREHEAT COIL
PHVAC PLUMBING, HEATING, VENTILATING AND AIR
CONDITIONING
PI POINT OF INTERSECTION
PIV POST INDICATOR VALVE
PKG PARKING
PL PLASTIC LAMINATE / PROPERTY LINE / PLATE
PLAS PLASTER
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
PR PAIR
PROJ PROJECTION
PRV PRESSURE REGULATING VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT OF TANGENCY / PORCELAIN TILE
PTVC POINT OF VERTICAL CURVATURE
PVC POLYVINYL CHLORIDE
PVI POINT OF VERTICAL INTERSECTION
PVT POINT OF VERTICAL TANGENCY
DWP DOMESTIC WATER PUMP
E
E EPOXY
EA EACH / EXHAUST AIR
EF EACH FACE / EXHAUST FAN
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMBED EMBEDMENT
EMD ESTIMATED MAXIMUM DEMAND
EMT ELECTRICAL METAL TUBING
EQ EQUAL
EQUIP EQUIPMENT
ET EXPANSION TANK
EVAC MEDICAL GAS EVACUATION
EW EACH WAY
EWC ELECTRICAL WATER COOLER
EWH ELECTRICAL WATER HEATER
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXPN EXPANSION
EXT EXTERIOR
F
F FIRE MAIN
FA FIRE ALARM
FCU FAN COIL UNIT
FD FLOOR DRAIN / FIRE DAMPER
FD / SD COMBINATION FIRE AND SMOKE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FDR FEEDER
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIN FINISH
FIX FIXTURE
FL FLOOR
FM FORCE MAIN / FACTORY MUTUAL
FP FIREPROOFING / FIRE PUMP
FPM FEET PER MINUTE
FR FIRE RATED
FRP FIBERGLASS REINFORCED PLASTIC
FS FLOW SWITCH
FT FEET
FTG FOOTING
FVC FIRE VALVE CABINET
G
G GAS / GRILLE
GA GAGE
GALV GALVANIZED
GB GRAB BAR
GBD GRAVITY BACKDRAFT DAMPER
GEN GENERATOR
GFRC GLASS FIBER REINFORCED CONCRETE
GI GALVANIZED IRON
GL GLASS
GLB GLASS BLOCK
GP GLAZED PAINT
GPM GALLONS PER MINUTE
GR GRADE
GRV GRAVITY ROOF VENTILATOR
GWB GYPSUM WALLBOARD
GYP GYPSUM
H
HB HOSE BIBB
HC HEATING COIL
HDNR HARDENER
HDW HARDWARE
HDWD HARDWOOD
HK1E HOOK ONE END
HK2E HOOK TWO ENDS
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSEPOWER
HPT HIGH POINT
HR HOUR
HS HIGH STRENGTH
HT HEIGHT
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HW HOT WATER
HWC HOT WATER CIRCULATING
HZ HERTZ
I
IA INSTRUMENT AIR
IC INTERCOM
ICB INTEGRAL COVE BASE
ID INSIDE DIAMETER
IE INVERT ELEVATION
IF INSIDE FACE
IN INCH
INSUL INSULATION
INT INTERIOR
J
JAN JANITOR
JB JUNCTION BOX
JP JOCKEY PUMP
JST JOIST
Q
QT QUARRY TILE
R
R RADIUS / REGISTER
RA RETURN AIR
RB RESILIENT BASE
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REF REFERENCE
REFL REFLECTED
REG REGISTER
REINF REINFORCED
REQD REQUIRED
REV REVERSE / REVISION
RF RETURN FAN
RGS RIGID GALVANIZED STEEL
RH ROOF HOOD / RELATIVE HUMIDITY / REHEAT
RHC REHEAT COIL
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RT RESILIENT TILE
RWC RIGID WALLCOVERING
S
S STAIR / STAIN / SURFACE / SANITARY
SA SUPPLY AIR / SOUND ATTENUATOR
SAN SANITARY
SCH SCHEDULE
SD SMOKE DAMPER / SUB DRAIN
SECT SECTION
SF SUPPLY FAN
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SP SUMP PUMP
SPEC SPECIFICATIONS
SPF SPRAY POLYURETHANE FOAM
SQ SQUARE
SS SERVICE SINK / STORM SEWER
SSO STORM SEWER OVERFLOW
SSTL STAINLESS STEEL
ST STAIR TREAD
STA STATION
STD STANDARD
STE STANDARD TAPERED END
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STOR STORAGE
STR STRUCTURAL
SUSP SUSPENDED
SW SWITCH
SWGR SWITCHGEAR
SYM SYMMETRICAL
T
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TC TOP OF CURB
TE TOP ELEVATION
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TLT TOILET
TOPO TOPOGRAPHY
TOS TOP OF STEEL
TOW TOP OF WALL
TP TOP OF PAVEMENT
TRANS TRANSVERSE
TYP TYPICAL
U
UC UNDERCUT
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UR URINAL
UV UNIT VENTILATOR
V
V VOLT
VAV VARIABLE AIR VOLUME
VB VINYL BASE
VC VERTICAL CURVE
VCP VITRIFIED CLAY PIPE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W
W WATT / WATER
W/ WITH
W/O WITHOUT
WAGD WASTE ANESTHESIA GAS DISPOSAL
WC WATER CLOSET
WD WOOD
WDW WINDOW
WH WATER HEATER / WALL HYDRANT
WP WEATHERPROOF
WPFG WATERPROOFING
WS WATER STOP
WT WEIGHT
WWF WELDED WIRE FABRIC
X
XFMR TRANSFORMER
Y
YD YARD
YH YARD HYDRANT
HAZARDOUS MATERIALS
1. IF THE CONTRACTOR ENCOUNTERS MATERIAL THAT COULD BE HAZARDOUS, THE CONTRACTOR SHALL STOP WORK AND NOTIFY THE GOVERNMENT
IMMEDIATELY FOR DIRECTION.
1/4" = 1'-0"1
GUIDE FOR CLEARANCES AT DOORS
Mark Revisions: Date:
WAITING
VESTIBULE
MECHANICAL
RECEPTION
HOT LAB
TOILET
IMAGING
ROOM
CLEAN
SUPPLY
LINEN
ROOM
TREADMILL
GAMMA
CAMERA
GAMMA
CAMERA
CONTROL
WAITING
ELEVATOR
1-ELEV
CLINICAL
SPACE
MECH
VIEW ROOM
NUCLEAR
MEDICINE
STORAGE
CORRIDOR
1-CORR-A
STAIR
STAIR
DENTAL
PROGRAM
DENTAL
PROGRAM
CORRIDOR
1-CORR
ULTRASOUND
DENTAL
PROGRAM
117A
DENTAL
PROGRAM
DENTAL
DENTAL
PROGRAM
B
J
A
L
GAMMA
CAMERA
WAITING
CORRIDOR
1-CORR-B
TREADMILL
HEART
ROOM
B
B
A
J
L
P
P
TREADMILL
IMAGING
HEART
STATION
IMAGING
ROOM
CLEAN
SUPPLY
LINEN
ROOM
TOILET
CORRIDOR
1-CORR
WAITING
CORRIDOR
1-CORR
WAITING
RECEPTION
HOT LAB
CLINICAL
SPACE
ELEVATOR
1-ELEV
MECHANICAL
VESTIBULE
VIEW ROOM
NUCLEAR
MEDICINE
112A
NUCLEAR
MEDICINE
HVAC
STORAGE
DENTAL
PROGRAM
DENTAL
PROGRAM
ULTRASOUND
DENTAL
PROGRAM
DENTAL
PROGRAM
117A
DENTAL
PROGRAM
DENTAL
E
D
C
DEMOLITION PLAN LEGEND:
FULL HEIGHT TEMPORARY PARTITION
ELEMENT TO BE REMOVED, TYP.
INDICATES AREA TO BE REMOVED, TYP
EXISITING CONSTRUCTION TO REMAIN UNO.
PLAN
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:3
P
M
AD101
FIRST FLOOR - DEMOLITION PLAN
KEYNOTE LEGEND
KEY KEYNOTE
A REMOVE GWB AND STUD WALL SYSTEM.
B REMOVE DOOR, FRAME AND INDICATED PORTION OF ADJOINING WALL REQUIRED FOR DOOR AND
FRAME INSTALLATION.
C REMOVAL OF DEMOLITION OF CORRIDOR DOOR FROM SCOPE.
D REMOVAL OF DEMOLITION OF DOOR 108 FROM SCOPE.
E REMOVAL OF DEMOLITION OF TREADMILL DOOR FROM SCOPE.
J REMOVE GWB AND STUDD WALL SYSTEM FOR WINDOW INSTALLATION.
L PATIENT LIFT TO BE REMOVED ALONG WITH FRAME AND TURNED OVER TO OWNER FOR STORAGE OR
REUSE.
P REMOVE FLOOR FINISHES AND BASE, SUCH AS CARPET, VAT, TILE OR OTHER SIMILAR MATERIALS IN INDICATED AREA. PATCH OR MATCH FLOOR FINISH MATERIAL WHERE NEW FINISH IS NOT INDICATED, VERIFY COLOR SELECTION WITH ARCHITECT.
GENERAL DEMOLITION NOTES
1 DASHED BOLD LINES INDICATE EXTENT OF DEMOLITION INCLUDING THE FOLLOWING:
* INTERIOR PARTITIONS (REMOVED TO STRUCTURE)
* CEILINGS, INCLUDING CEILING SUSPENSION SYSTEM, MISC. STEEL SUPPORTS FOR SUSPENDED
EQUIPMENT, SUSPENDED EQUIPMENT, LIGHT FIXTURES, DIFFUSERS AND GRILLES ETC.
* FLOOR FINISHES (TO CONCRETE) INCLUDING CARPET, RVT, SHEET VINYL, CERAMIC TILE, QUARRY
TILE, BRICK PAVERS, ETC.
* DOORS AND FRAMES UNLESS NOTED OTHERWISE IN DOOR SCHEDULE
* WINDOW GLAZING AND FRAMES UNLESS NOTED OTHERWISE
* BRICK AND BACK-UP WALL SYSTEM
* CABINETWORK, SHELVING, BASES
* TOILET PARTITIONS AND ACCESSORIES
* TACK BOARDS, MARKER BOARDS, PEGBOARDS, DISPLAY BOARDS
* EQUIPMENT ITEMS
* PLUMBING FIXTURES
2 DASHED BOLD LINES INDICATE EXTENT OF DEMOLITION INCLUDING THE FOLLOWING:
3 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS.
4 ALL LIGHT OR HALFTONE LINES INDICATE EXISTING TO REMAIN.
5 SEE SPECIFICATIONS SECTIONS FOR CUTTING AND PATCHING 01 40 50.
6 SEE ROOM FINISH SCHEDULE, MECHANICAL PLANS, AND ELECTRICAL PLANS FOR EXTENT OF NEW
CEILING CONSTRUCTION OR CEILING PATCHING IN EXISTING AREAS.
7 SEE ROOM FINISH SCHEDULE FOR EXTENT OF NEW FLOORING MATERIAL IN EXISTING AREAS.
8 SEE ROOM FINISH SCHEDULE FOR EXTENT OF NEW WALL COVERING MATERIAL IN EXISTING AREAS.
WHERE NEW FINISHES ARE REQUIRED REMOVE EXISTING WALL FINISHES, (TEXTURED PLASTIC COATING, VINYL WALL COVERING, PANELING, BASE, ETC.).
9 CONTRACTOR TO VERIFY ALL WALL CONSTRUCTION & FINISHES NOTED FOR REMOVAL. TAKE INTO
ACCOUNT ANY DISCREPANCY AND MAKE PROPER ADJUSTMENT TO ACCOMPLISH REQUIRED
CONSTRUCTION & FINISHES. IF STRUCTURAL INTEGRITY IS VIOLATED, CONTACT ARCHITECT.
COORDINATE PHASING WITH OWNER
10 COORDINATE REMOVEL OF FURNITURE AND EXISTING EQUIPMENT WITH OWNER.
11 REFER TO EQUIPMENT SCHEDULE 11700S FOR NEW LOCATIONS OF EXISTING EQUIPMENT, ETC.
12 SAW CUT EDGES OF EXISTING FLOOR SLAB FOR REMOVAL AND INSTALLATION OF UTILITIES. REFER TO
MECHANICAL AND ELECTRICAL DRAWINGS.
13 REMOVE FURRING OR GWB ONLY WHERE REQUIRED TO COMPLETE CONSTRUCTION. PATCH AND MATCH WALLS AS REQUIRED TO COMPLETE AND MATCH EXISTING CONDITIONS, UNLESS AN ALTERNATIVE
MATERIAL AND FINISH IS INDICATED.
14 REMOVE CEILINGS ONLY AS REQUIRED FOR NEW CONSTRUCTION. REINSTALL, REPLACE OR PATCH AS
REQUIRED.
15 CONSTRUCTION BARRIER RATING AND SPRINKLER PROTECTION DURING CONSTRUCTION TO BE
DETERMINED BY CONTRACTOR AS REQUIRED.
16 WHERE CEILING TILES ARE REMOVED OUTSIDE OF THE RATED CONSTRUCTION BARRIER THEY MUST BE REPLACED AT THE END OF EACH SHIFT. WHERE TILES CANNOT BE REPLACED THE SPRINKLER SYSTEM MAY BE CONSIDERED OUT OF SERVICE IN THESE AREAS AND A 1-HOUR FIRE RATED SEPARATION WILL BE
REQUIRED BETWEEN THE CONSTRUCTION AND OCCUPIED PORTIONS OF THE BUILDING.
17 CONTRACTOR TO DETERMINE IF TEMPORARY CONSTRUCTION BARRIER MAY NOT BE RATED WHERE SPRINKLER HEAD MAINTENANCE HAS BEEN PERFORMED TO RAISE THE SPRINKLER HEADS TO THE
STRUCTURAL DECK WHERE THE CEILING HAS BEEN REMOVED. WHERE FIRE RATED BARRIER IS
REQUIRED CONTRACTOR IS TO CONFIRM THE EXISTING NON-RATED WALLS EXTEND TO THE STRUCTURAL
DECK AND ARE PROPERLY FIRE STOPPED AT ALL PENETRATIONS.
1/8" = 1'-0"1
FIRST FLOOR - DEMOLITION PLAN
1/4" = 1'-0"3
FIRST FLOOR - DEMOLITION PLAN ENLARGED
1/8" = 1'-0"2
FIRST FLOOR - DEMOLITION PLAN DEDUCT 1, 2, & 3
Mark Revisions: Date:
WAITING
STAIR
STAIR
DENTAL
PROGRAM
DENTAL
PROGRAM
DENTAL
PROGRAM
DENTAL
DENTAL
PROGRAM
DENTAL
PROGRAM
117A
ULTRASOUND
NUCLEAR
MEDICINE
VIEW ROOM
STORAGE
113 NUCLEAR
MEDICINE
112A
CLINICAL
SPACE
ELEVATOR
1-ELEV
HVAC
WAITING
GAMMA
CAMERA
CONTROL
GAMMA
CAMERA
TREADMILL
CLEAN
SUPPLY
LINEN
ROOM
IMAGING
ROOM
TOILET
HOT LAB
RECEPTION
132MECHANICAL
VESTIBULE
CORRIDOR
1-CORR-B
CORRIDOR
1-CORR-A
CORRIDOR
1-CORR
MECH
A
GAMMA
CAMERA
GAMMA
CAMERA
CONTROL
CORRIDOR
1-CORR-B
WAITING
TREADMILL
AE9058
AE905
B
F
F
R
RR
R
AE401
AE401
W1
14'-10 3/4"
'-2
/4
AE905 9
N
R
M
11 1/4"
/4
/4
1'-2"
6'-11"
10 3/4"
1'-3 3/4"
2' -1
1"
9' -0
11 E
D
PLAN
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:3
P
M
AE101
FIRST FLOOR - FLOOR PLAN
1/8" = 1'-0"1
FIRST FLOOR - FLOOR PLAN
1/2" = 1'-0"2
FIRST FLOOR - FLOOR PLAN ENLARGED
KEYNOTE LEGEND
KEY KEYNOTE
D REMOVAL OF DEMOLITION OF DOOR 108 FROM SCOPE.
E REMOVAL OF DEMOLITION OF TREADMILL DOOR FROM SCOPE.
F WALL REPAIR TO BE PERFORMED WHERE NECESSARY.
M PATIENT LIFT TO BE REINSTALLED BY PROVIDER
1/2" = 1'-0"3
FIRST FLOOR - DEDUCT ALTERNATE 2 & 3 FLOOR PLAN
GENERAL NOTES
1 ALL NEW CONSTRUCTION IS INDICATED BOLD OR FULL TONE.
2 ALL INTERIOR WALLS WILL BE TYPE "A" UNLESS OTHERWISE INDICATED. REFER TO SHEET
A-801.
3 ALL METAL STUD AND WALLBOARD PARTITIONS ARE DIMENSIONED TO THE OUTSIDE FACE AND
TO COLUMN GRID UNLESS OTHERWISE NOTED.
4 WHEN WALL PARTITIONS OF DIFFERENT FIRE INTERSECT, THE HIGHEST RATED PARTITION
TAKES PRECEDENT. MAINTAIN RATING BEHIND FIRE EXTINGUISHER CABINETS, ETC.
5 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION.
6 REFER TO A-300 SERIES FOR LARGE SCALE PLANS AND TOILET ACCESSORIES. ALSO, REFER
TO SPECIFICATION SECTION 10800 FOR ADDITIONAL TOILET ACCESSORIES LOCATIONS AND
MOUNTING HEIGHTS.
7 REFER TO THE Q SERIES FOR ARCHITECTURAL CABINETWORK AND EQUIPMENT NUMBERS.
8 REFER TO SHEET A-802 FOR TYPICAL BACKING DETAIL WITHIN INTERIOR WALL PARTITION, HANDRAILS, CUBICAL CURTAIN TRACKS, CORNER GUARDS ETC.
9 ALL EXISTING TO REMAIN CEILING AND WALL GRILLES, DIFFUSERS AND LIGHTS ETC. TO BE
CLEANED.
10 VERIFY THAT THE EXISTING REQUIRING FIRE RATING ARE MAINTAINED, REPAIRED AND
EXTENDED TO STRUCTURE.
11 ALL CORRIDOR WALLS ARE REQUIRED TO BE SMOKE TIGHT, WHETHER THEY ARE FIRE RATED
OR NOT. REPAIR AND EXTEND AT LEAST THE CORRIDOR SIDE OF NON-FIRE RATED CORRIDOR
WALLS TO STRUCTURE, UNLESS NOTED OTHERWISE NOTED. SEE PARTITION TYPES SHEET.
12 REFER TO LIFE SAFETY PLANS FOR LOCATION OF REQUIRED FIRE WALLS.
13 REFER TO SPECIFICATION SECTIONS 05800 & 07600 FOR EXPANSION JOINT ASSEMBLIES.
PROVIDE FIRE RATED EXPANSION JOINTS IN RATED FIRE RATED WALLS, REFER TO LIFE
SAFETY SERIES FOR FIRE RATINGS.
14 ALL FURNITURE SHOWN HALF TONE WILL BE OWNER FURNISHED AND OWNER INSTALLED.
Mark Revisions: Date:
R R
RR
RR
R R
RR
RR
EXISTING GYPSUM WALL BOARD CEILING
EXISTING SUSPENDED ACOUSTICAL REMAIN
EXISTING SUPPLY AIR GRILLE - SEE MECHANICAL
EXISTING RETURN AIR GRILLE - SEE MECHANICAL
EXISTING RECESSED 2X2 LIGHT FIXTURE - SEE ELECTRICAL
EXISTING RECESSED 2X4 LIGHT FIXTURE - SEE ELECTRICAL
STRIP LIGHTING
CAN LIGHT
EXIT LIGHT
WIRELESS ACCESS POINT
SPEAKER
SMOKE DETECTOR
OCCUPANCY SENSOR
VIDEO SURVEILLANCE CAMERA
REFLECTED CEILING LEGEND
GYPSUM WALL BOARD CEILING
SUSPENDED ACOUSTICAL CEILING
SUPPLY AIR GRILLE - SEE MECHANICAL
RETURN AIR GRILLE TO - SEE MECHANICAL
RECESSED 2X2 LIGHT FIXTURE - SEE ELECTRICAL
RECESSED 2X4 LIGHT FIXTURE - SEE ELECTRICAL
STRIP LIGHTING
CAN LIGHT
EXIT LIGHT
WIRELESS ACCESS POINT
SPEAKER
SMOKE DETECTOR
OCCUPANCY SENSOR
VIDEO SURVEILLANCE CAMERA
SS
SDOS
OSOS
WAPWAP
CCTVCCTV
CORRIDOR
1-CORR-B
GAMMA
CAMERA
GAMMA
CAMERA
CONTROL
TREADMILL
IMAGING
ROOM
CLEAN
SUPPLY
LINEN
ROOM
TOILET
WAITING
HOT LAB
RECEPTION
MECHANICAL
102 ELEVATOR
1-ELEV
CLINICAL
SPACE
CORRIDOR
1-CORR-A
WAITING
STAIR
STAIR
STORAGE
113 VIEW ROOM
NUCLEAR
MEDICINE
112A
VESTIBULE
DENTAL
PROGRAM
DENTAL
PROGRAM
120 CORRIDOR
1-CORR
NUCLEAR
MEDICINE
ULTRASOUND
DENTAL
PROGRAM
117A
DENTAL
PROGRAM
DENTAL
DENTAL
PROGRAM
AE401
AE401
CEILING AT 8'
CEILING AT 8'
PATIENT LIFT
SKYFACTORY LIGHT
GAMMA
CAMERA
CONTROL
GAMMA
CAMERA
CORRIDOR
1-CORR-B
TREADMILL
'-2
/4
9'
-0
14'-10 3/4"
PLAN
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:3
P
M
AC101
FIRST FLOOR - REFLECTED CEILING
PLAN
GENERAL REFLECTED CEILING NOTES
1 PROVIDE GYPSUM WALL BOARD AND METAL STUD BULK HEADS WHERE CEILINGS OF DIFFERENT HEIGHTS
ABUT. DO NOT BUILD BULKHEADS OF ACOUSTICAL CEILING MATERIALS UNLESS SPECIFICALLY DETAILED.
2 REFER TO MECHANICAL DRAWINGS (M SERIES) FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST GRILLES. SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
3 REFER TO ELECTRICAL DRAWINGS (E SERIES) FOR QUANTITY AND TYPE OF LIGHTS, SPEAKERS, DETECTORS, POWER OUTLETS, ETC. SCRIBE CEILING MATERIALS CAREFULLY. WHERE NO DEVICES ARE SHOWN ON PLANS, FIELD VERIFY LOCATION & QUANTITY OF DEVICES IN EXISTING CEILING. THESE
DEVICES WILL BE RELOCATED TO THE NEW CEILING.
4 ALTHOUGH NOT SPECIFICALLY SHOWN, THE ENTIRE PROJECT HAS FIRE SPRINKLER HEADS IN CEILING.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
5 ACOUSTIC TILE CEILING TO BE AT-1 UNLESS NOTED OTHERWISE.
6 REFER TO DETAIL X/X-XXX FOR GWB SOFFITS ABOVE BUILT-IN CASEWORK.
7 REFER TO ROOM FINISH SCHEDULE FOR CEILING HEIGHTS AND MATERIAL LOCATIONS.
8 REFER TO ROOM FINISH SCHEDULE FOR THE EXTENT OF GRID SYSTEM. REFLECTED CEILING PLANS
SHOW TILE PATTERNS.
9 CONTRACTOR TO FIELD VERIFY EXTENT OF CEILING REPLACEMENT. CONTRACTOR TO COORDINATE WITH
ALL TRADES.
10 ALL EXISTING TO REMAIN GRILLES, DIFFUSERS AND LIGHTS ETC. TO BE CLEANED
11 CONTRACTOR TO COORDINATE WITH ALL TRADES.
12 UNLESS NOTED OTHERWISE, TYPICAL CEILING HEIGHT TO BE 9'-0".
1/8" = 1'-0"1
FIRST FLOOR - REFLECTED CEILING PLAN
1/2" = 1'-0"2
FIRST FLOOR - REFLECTED CEILING PLAN
Mark Revisions: Date:
FIRST FLOOR
100' - 0"
SECOND FLOOR
112' - 0"
AE401
GAMMA
CAMERA
GAMMA
CAMERA
CONTROL
4' -0
8'
-0
4" 3'
-2
1' -6
3'
-0
2' -0
3'
-0
3' -0
37 108
AE701
6"
Z1020
SLOPPING TOP
CABINET
W1
C02C0
CABINET
PATIENT LIFT
Z1020
SLOPPING TOP
CABINET
C02C0
CABINET
NM AQUISITION STATIONXELERIS WORKSTATION
FIRST FLOOR
100' - 0"
SECOND FLOOR
112' - 0"
AE401
GAMMA
CAMERA
4' -0
8'
-0
'-0
3' -6
1'
-6
3' -0
Z1020
SLOPPING TOP
CABINET
C02C0
CABINET
COLLIMITER CART
PATIENT LIFT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:3
P
M
AE401
WALL SECTIONS
1/2" = 1'-0"1
N-S SECTION
1/2" = 1'-0"2
E-W SECTION
Mark Revisions: Date:
STEEL TELESCOPIC LEAD LINED WINDOW FRAMES
MATCH HOLLOW METAL DOOR FRAMES.
ADJUSTABLE TO WALL THICKNESS OF 4 1/4" TO 6".
LEADED GLAZING
ADJ. SILL AND JAMB DETAIL
LEAD LINED GYP. BD.
PANELS - EXTEND
LEAD INTO FRAME
REFER TO WALL TYPE
PLAN FOR DESCRIPTION
2' HOLLOW METAL FRAME
W/LEAD SHIELDING -
ATTACH PER MFR.
RECOMMENDATIONS -
GROUT SOLID
2" ON LEAD LINED SIDE
1 3/8" ON CONTROL ROOM SIDE
REMOVABLE GLAZING STRIPS
1/2" x 1/2"
LEADED GLASS-UNDERCUT
GLASS 1/8" ALL FOUR SIDES
DOUBLE SIDED FOAM TAPE
BETWEEN GLASS AND FRAME
F
FLUSH
2"
SCHEDULE
SEE DOOR 2"
HOSPITAL
STOPS @
INTERIOR
DOORS
ONLY
1H
HOLLOW METAL
2" S
E E
D O
O R
S C
H E
D U
LE
FRONT APPROACH, PULL SIDE FRONT APPROACH, PUSH SIDE
NOTE: X=12" MINIMUM IF DOOR HAS
BOTH A CLOSER AND LATCH
LATCH SIDE APPROACHES - SWINGING DOORS
NOTE:
1. ALL DOORS IN ALCOVES SHALL COMPLY WITH CLEARANCES FOR FRONT APPROACHES.
2. ENTRY DOORS TO HOSPITAL PATIENT ROOMS FOR IN-PATIENTS SHALL BE EXEMPTED
FROM REQUIREMENT FOR SPACE AT LATCH SIDE OF DOOR (SEE DIMENSION ”X”) IF DOOR
IS AT LEAST 44” WIDE.
LATCH APPROACH, PULL SIDE LATCH APPROACH, PUSH SIDE
NOTE: Y=54" MINIMUM IF DOOR HAS
CLOSER.
NOTE: Y=48" MINIMUM IF DOOR HAS
CLOSER.
FRONT APPROACHES - SWINGING DOORS
MIN.
1'-6"
M
IN
M
IN
X
MIN.
2'-0"
M
IN
M
IN
MIN.
2'-0" X X
Y
Y
PULL SIDE PUSH SIDE
POCKET OR HINGE APPROACH - SLIDING BARN DOORS
POCKET OR HINGE APPROACH STOP OR LATCH APPROACH
FRONT AND SIDE APPROACHES - NO DOORS
M
IN
M
IN
2'-0"42
M
IN
22" MIN. 42
M
IN
HINGE SIDE APPROACHES - SWINGING DOORS
HINGE APPROACH, PULL SIDE HINGE APPROACH, PUSH SIDE
NOTE: X=36" MINIMUM IF Y=60"; X=42"
MINIMUM IF Y=54".
NOTE: Y=48" MINIMUM IF DOOR HAS
BOTH A LATCH AND CLOSER.
54" MIN.
M
IN
5' -0
X Y
HOLLOW METAL FRAME
BOTTOM OF FRAME
4" MATCH EXISTING FRAMES
45°
TYP.
4"
HOLLOW METAL FRAME
WALL - SEE
PLAN FOR TYPE
WALL (WHERE OCCURS)
- SEE PLAN FOR TYPE
2" 6'-7" 2"
3' -0
2"
2' -8
2"
T.O. SLAB
W1
TYPE 11 V
A
R
IE
S
S E
E P
LA
N
1/ 2"
1/ 2"
2"
VARIES
SEE PLAN
1/2"1/2"
4"
WALL - SEE
PLAN FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND, TYP.
HOLLOW METAL
FRAME
ADJACENT WALL
WHERE OCCURS
SEALANT - EA. SIDE
& ALL AROUND, TYP.
HOLLOW
METAL
FRAME
A
HEAD JAMB
B3" = 1'-0" 3" = 1'-0"
WALL - SEE
PLAN FOR TYPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:4
P
M
AE701
DOOR AND FRAME TYPES, DETAILS
AND DOOR SCHEDULE
DOOR SCHEDULE
DOOR NUMBER ROOM NAME DOOR SIZE HARDWARE DOOR MATERIAL DOOR TYPE DOOR FINISH FRAME TYPE
FRAME
MATERIAL FRAME FINISH FIRE RATING REMARKS
108 GAMMA CAMERA PR 4'-0"/1'-6" x 7'-0"
SET 01 WD F STN-1 1H HM MT-1 NA SHEILDED
109B GAMMA CAMERA 3'-6" x 7'-0" SET 02 WD F STN-1 1H HM MT-1 NA SHEILDED
137 CORRIDOR PR 3'-6"/1'-6" x 7'-0"
SET 03 WD F STN-1 1H HM MT-1 NA
1/4" = 1'-0"1
DOOR TYPES - EXAMPLES
1/4" = 1'-0"2
FRAME TYPES - EXAMPLES
GLASS TYPE SCHEDULE
REF TYPE Description Thickness Remarks
1 TYPE 1 CLEAR FLOAT 6mm --
2 TYPE 2 CLEAR, TEMPERED TONGLESS FLOAT 6mm --
9 TYPE 9 CLEAR, FIRE RATED & SAFETY RATED GLASS CERAMIC 8mm --
11 TYPE 11 LEAD GLASS, RADIATION RESISTANT, CLEAR VARIES --
S19 TYPE S-19 SECURITY GLASS, GLASS CLAD POLYCARBONATE CLEAR 1 3/16" A
SGU1 TYPE SGU 1 SEALED GLASS UNITS W/ INTEGRAL OPERABLE LOUVER BLINDS 2 1/2" B
SGU2 TYPE SGU 2 SEALED GLASS UNITS W/ INTEGRAL OPERABLE LOUVER BLINDS 2 1/2" B,C
SGU3 TYPE SGU 3 SEALED GLASS UNITS W/ INTEGRAL OPERABLE LOUVER BLINDS 2 1/2" C,D
GLASS TYPE SCHEDULE NOTES:
A: COMPLY WITH UL LEVEL 3 PROTECTION LEVEL, SPSA - SUPER POWER SMALL ARMS
B: SEE SPECIFICATION SECTION 08 80 00, SEALED GLASS UNITS WITH OPERABLE LOUVERS
C: PLASTIC THUMBWHEEL OPERATOR, ACCESSIBLE FROM BOTH SIDES
D: DOOR UNIT ASSEMBLY, COORDINATE WITH DOOR & HARDWARE SCHEDULE
REMARKS:
1. SEE SPECIFICATIONS FOR DOOR & HARDWARE SCHEDULE
2. SEE SHEETS AE701 FOR DOOR AND WINDOW FRAME DETAILS
3. SEE SHEET AE701 FOR BULLET RESISTANT DOOR AND WINDOW FRAME TYPES
4. SEE SHEET AE701 FOR WON DOOR HORIZONTAL SLIDING FIRE DOOR, POCKET DOOR AND DOOR FRAME TYPE
1/4" = 1'-0"8
GUIDE FOR CLEARANCES AT DOORS
1 1/2" = 1'-0"7
HOSPITAL STOPS
1 1/2" = 1'-0"6
DOOR FRAME OFFSET
3/8" = 1'-0"3
WINDOW TYPES
3" = 1'-0"4
SHEILDED WINDOW DETAIL
3" = 1'-0"5
DOOR DETAILS A
Mark Revisions: Date:
imurphree Rectangle imurphree Snapshot
FIRE RATING - 1 HOUR
STC RATING - 45-49
TEST: U.L. Design No. U465
TEST: TL 99-103
RATING INFORMATION
SAME AS "A" WITH
NO SOUND INSULATION
SAME AS "A6" WITH
NO SOUND INSULATION
6" NON-LOAD BEARING WALL
FRAMING SYSTEM
3 5/8" NON-LOAD BEARING WALL
FRAMING SYSTEM
STC RATING - 40 TEST: TL 99-160
STRUCTURAL DECK
CEILING LINE
5/8" F.R. GWB BOTH SIDES
FIRESTOP BOTH SIDES
(FIRE AND/ OR SMOKE WALL)
FLOOR LINE
SECTION
SOUND INSULATION
A A6
A1 A7
A
A1
A6
A7
NO SCALE
WALL TYPE
A7A6A1A
AE802
FIRE RATING - NON-RATED
RATING INFORMATION
STRUCTURAL DECK
CEILING LINE
SKIM COAT OF PLASTER
5/8" GWB SYSTEM ADHESIVELY APPLIED
SEALANT
FLOOR LINE
M
IN6"
SECTION
N
N1
NO SCALE
WALL TYPE GWB ADHESIVELY APPLIED
N1N
LEAD SHEET BACKING THICKNESS:
SEE SCHEDULE
FIRE RATING - 1 HOUR
STC RATING - 45-49
TEST: U.L. Design No. U430 OR V439
TEST: TL 99-103
RATING INFORMATION
STC RATING - 40 TEST: TL 99-160
LEAD SHEET BACKING THICKNESS:
SEE SCHEDULE
SHIM TO MATCH LEAD THICKNESS
STRUCTURAL DECK
SAME AS "R" WITH
NO SOUND INSULATION
SAME AS "R6" WITH
NO SOUND
INSULATION
6" NON-LOAD BEARING WALL
FRAMING SYSTEM
3 5/8" NON-LOAD BEARING WALL
FRAMING SYSTEM
CEILING LINE
5/8" GWB BOTH SIDES
FIRESTOP BOTH SIDES
(FIRE AND/ OR SMOKE WALL)
FLOOR LINE
NOTE:
REFER TO 1D, 2D, 3D & 4D / A-802
FOR ADDITIONAL INFORMATION
SOUND INSULATION
R
R1
R6
R7
R R6
R1 R7
SECTION
NO SCALE
WALL TYPE
R7R6R1R
AE802
FIRE RATING - 1 HOUR TEST: U.L. Design No. U465
TEST: TL 99-103
RATING INFORMATION
3 5/8" NON-LOAD BEARING WALL
FRAMING SYSTEM
TEST: TL 99-160
STRUCTURAL DECK
CEILING LINE
5/8" F.R. GWB BOTH SIDES
FIRESTOP BOTH SIDES
FLOOR LINE
SECTION
NO SCALE
TEMPORARY WALL TYPE
T
AE802
FIRE RATING - 1 HOUR
STC RATING - 45-49
TEST: U.L. Design No. U430 OR V439
TEST: TL 99-103
RATING INFORMATION
STC RATING - 40 TEST: TL 99-160
LEAD SHEET BACKING THICKNESS:
SEE SCHEDULE BOTH SIDES
SHIM TO MATCH LEAD THICKNESS
STRUCTURAL DECK
SAME AS "R" WITH
NO SOUND INSULATION
SAME AS "R6" WITH
NO SOUND
INSULATION
6" NON-LOAD BEARING WALL
FRAMING SYSTEM
3 5/8" NON-LOAD BEARING WALL
FRAMING SYSTEM
CEILING LINE
5/8" GWB BOTH SIDES
FIRESTOP BOTH SIDES
(FIRE AND/ OR SMOKE WALL)
FLOOR LINE
NOTE:
REFER TO 1D, 2D, 3D & 4D / A-802
FOR ADDITIONAL INFORMATION
SOUND INSULATION
R
R1
R6
R7
R R6
R1 R7
SECTION
NO SCALE
WALL TYPE
RR7RR6RR1RR
AE802
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
BDH Engineering 440 Regency Parkway, Suit 135 Omaha, Nebraska 68114 Phone: (402) 981-5527
Farris Engineering 12700 W Dodge Rd, Omaha, NE 68154 Phone: (402) 330-5900
A on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
CONSTRUCTION
DOCUMENTS
SITE PREP FOR GAMMA
CAMERA
589A7-23-314
WICHITA, KS
A
B
C
D
E
F
04 MARCH 2025 RJO IJM
MKEC Engineering, Inc.
411 N. Webb Rd, Wichita, KS 67206 Phone: (316) 684-9600
A u to d e s k D o c s /1
A
-2
-3
S it e P re p f o r
G a m m a C a m e ra
/5
A
-2
-3
.B
.A rc h R
-S it e
P re p F o rG a m m a
.r v t
/2
/2
:4
:4
P
M
AE801
PARTITION TYPES
SHIELDING SCHEDULE
ROOM NUMBER ROOM NAME
MININUM THICKNESS OF LEAD SHIELDING
NORTH EAST SOUTH WEST
108 GAMMA CAMERA CURRENT
SHEILDIN
G
ACCEPTA
BLE
CURRENT
SHEILDIN
G
ACCEPTA
BLE
1/16" 1/16"
109 GAMMA CAMERA CONTROL 1/16"
NOTE: EXISTING WALLS SHALL RECEIVE WALL TYPE "N" IN ROOMS REQUIRING SHIELDING
INTERIOR PARTITION NOTES
1. UPGRADE GWB TO TILE BACKER (MR GWB) WHERE CALLED FOR BY SPEC. SECTION 09 22 16 AND
WHERE DRAWINGS CALL FOR ADHERED CSMU TILE VENEER.
2. EXTEND FIRE RATED WALL CONSTRUCTION BEHIND RECESSED OR BUILT-IN EQUIPMENT SUCH AS FIRE EXTINGUISHER CABINETS (FEC), ELECTRICAL WATER COOLERS (EWC), ELECTRIC PANELS, ETC., UNO.
3. PROVIDE AND INSTALL ALL STIFFENERS, BRACING, BACK-UP PLATES & SUPPORTING BRACKETS
REQUIRED FOR THE INSTALLATION OF ALL CASEWORK AND OF ALL FLOOR MOUNTED OR
SUSPENDED MECHANICAL, ELECTRICAL OR LABORATORY EQUIPMENT.
4. WHERE HVAC OR OTHER MECHANICAL, ELECTRICAL AND PLUMBING ITEMS PENETRATE
PARTITIONS, STUDS SHALL BE BRACED AND FRAMED TO STRUCTURE AS REQUIRED TO PROVIDE
ADEQUATE SUPPORT. ALL PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED TO
PROVIDE FIRE, SMOKE, AND/OR ACOUSTICAL ISOLATION OF SPACES WITH APPROPRIATE
FIRESTOP MATERIAL.
5. COORDINATE METAL STUD GAUGE WITH PRE-APPROVED EQUIPMENT ANCHORAGE. WHERE A
DISCREPANCY OCCURS, THE MORE STRINGENT REQUIREMENT SHALL GOVERN.
6. WHERE COLUMN FURRING STUDS EXCEED THE MANUFACTURER'S RECOMMENDED LIMITING
HEIGHTS, STUDS SHALL BE BRACED BACK TO THE STRUCTURE AS REQUIRED.
7. THERE SHALL BE NO BACK-TO-BACK ELECTRICAL, TELEPHONE, OR OTHER OUTLETS, EXCEPT
WHERE SPECIFICALLY SHOWN. AT ACOUSTICALLY SENSITIVE AREAS, SUCH AS EXAM ROOMS,
OFFICES, CLASSROOMS, ETC. OFFSET OUTLETS IN OPPOSITE SIDES OF THE WALL BY AT LEAST
TWO STUD CAVITIES.
8. WALL BASE NOT SHOWN ON WALL TYPES FOR CLARITY.
9. WHERE 'SEALANT' IS INDICATED ON WALL TYPES, PROVIDE ACOUSTIC (SOUND) SEALANT AT
NON-RATED WALLS AND FIRE-RATED SEALANT AT RATED WALLS AS REQUIRED BY FIRE RATING
TEST NUMBER.
10. PROVIDE SOUND INSULATION AS REQUIRED TO MEET STC RATING INDICATED ON WALL TYPE.
PROVIDE SOUND INSULATION IN WALLS AROUND THE FOLLOWING SPACES: CLASSROOMS,
CONFERENCE ROOMS, OFFICES,…