504-22-115 Drawings.pdf
PDF 26 MB Posted
- Attached to
- Y1DA--INSTALL A CHILLER FOR USP 797 Federal contract opportunity
- Solicitation number
- 36C25723B0060
About this file
This document provides details on a federal contract opportunity from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. The solicitation seeks to install a chiller at USP 797 under solicitation number 36C25723B0060. The opportunity type is listed as a solicitation. The related file is 504-22-115 Drawings.pdf, which contains drawings and specifications for the chiller installation project. The summary provides key information on the products and services required, awarding agency, and opportunity details.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25723B0060 0001.docx | DOCX document | |
| Sign In Sheet for Install Chiller 797.pdf | ||
| 504-22-115 Specifications.pdf | ||
| 36C25723B0060_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N or th
AREA OF WORK
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_A
R C
H _R
_d jo hn so nQ
P A
E 4.
rv t
/1
8/
0:
:1
A M
GI001
COVER INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
11/18/2022 DJ CR
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11
THOMAS E. CREEK VAMC
6010 W AMARILLO BLVD, AMARILLO, TX 79106
VAMC PROJECT #: 504-22-115
INSTALL CHILLER FOR USP
SHEET NUMBER SHEET NAME
GENERAL
GI001 COVER
GI002 GENERAL ABBREVIATIONS, NOTES, & SYMBOLS
GI111 LIFE SAFETY PLAN - BLDG 01 & 28 1ST FLOOR
ARCHITECTURAL
AD111 DEMOLITION PLAN - ROOF
AE111 ROOF PLAN
AE531 DETAILS - ROOF
PLUMBING
P-001 PLUMBING ABBREVIATIONS, SYMBOLS, & LEGENDS
PP111 DOMESTIC WATER PLAN & FIXTURE SCHEDULE
MECHANICAL
M-001 MECHANICAL ABBREVIATIONS & NOTES
M-002 MECHANICAL SYMBOLS
MQ601 EQUIPMENT SCHEDULES
MP111 PIPING PLAN
MI111 INSTRUMENTATION AND CONTROLS PLANS
MI601 CONTROLS & INSTRUMENTATION DETAILS
MK501 TYPICAL DETAILS
MK502 TYPICAL DETAILS
ELECTRICAL
E-001 ELECTRICAL ABBREVIATIONS AND GENERAL NOTES
E-002 ELECTRICAL SYMBOLS
EP111 POWER PLAN - 1ST FLOOR
EP411 ENLARGED POWER PLANS
EP601 ELECTRICAL SCHEDULES
EP602 BUILDING 28 POWER ONE-LINE DIAGRAM
EK501 TYPICAL DETAILS
EK502 LIGHTNING PROTECTION DETAILS
SHEET INDEXAREA OF WORK
0 100% CONSTRUCTION DOCUMENTS 11/18/22
DeLisa Johnson 11/18/2022
A. CONTRACTORS AND THEIR SUPERVISORY PERSONNEL SHALL REVIEW THE GENERAL AND SUPPLEMENTARY
CONDITIONS TO THE CONTRACT.
B. WORK SHALL CONFORM WITH PROJECT SPECIFICATIONS.
C. CONTRACTOR SHALL BECOME FULLY ACQUAINTED WITH CONDITIONS RELATED TO THE WORK. QUESTIONS
WILL BE DIRECTED TO VHA COR.
D. CONTRACTOR WILL BE SOLELY RESPONSIBLE FOR THE MEANS, METHODS, AND SEQUENCES OF
CONSTRUCTION AND THE SAFETY OF CONSTRUCTION PERSONNEL AND VISITORS.
E. DRAWINGS CONTAINED IN THIS SET SHALL NOT BE REPRODUCED FOR SHOP DRAWINGS. COPIES OF THESE DRAWINGS SUBMITTED AS SHOP DRAWINGS WILL BE REJECTED AND RETURNED TO THE CONTRACTOR.
REFER TO SPECIFICATION SECTION 01 33 23.
F. EACH CONTRACTOR AND SUBCONTRACTOR SHALL EXAMINE SUBSTRATE AND/OR CONDITIONS UNDER WHICH THE WORK WILL BE INSTALLED AND REPORT TO THE VHA COR OR GENERAL CONTRACTOR, IN WRITING, CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY EXECUTION OF THEIR WORK. DO NOT PROCEED
UNTIL UNSATISFACTORY CONDITIONS ARE CORRECTED. COMMENCING WITH INSTALLATION WILL
CONSTITUTE ACCEPTANCE OF THE SUBSTRATE AND/OR CONDITIONS.
G. DO NOT SCALE DRAWINGS: FOLLOW WRITTEN DIMENSIONS AND NOTES. CONTACT VHA COR FOR
CLARIFICATIONS, IF REQUIRED.
H. "TYPICAL", AS USED IN THESE DOCUMENTS, MEANS THAT THE CONDITION OR DIMENSION IS
REPRESENTATIVE OF, OR THE SAME, FOR SIMILAR CONDITIONS THROUGHOUT.
I. DISCREPANCIES SHALL BE REPORTED TO THE VHA COR IN WRITING FOR RESOLUTION, PRIOR TO PROCEEDING WITH THE WORK. NO CHANGE ORDERS OR EXTENSIONS OF TIME WILL BE ALLOWED OR ACCEPTED FOR PROCEEDING WITH THE WORK WITHOUT THE CONTRACTING OFFICER'S WRITTEN DIRECTION AND APPROVAL. ALSO, CONTRACTOR SHALL REMOVE, REPAIR, AND/OR REPLACE UNAUTHORIZED WORK, AS
INDICATED BY THE VHA COR, AT NO ADDITIONAL COST TO THE VHA.
J. POSSIBLE DISCREPANCIES IN PROJECT MAY INCLUDE BETWEEN SMALL SCALE AND LARGE SCALE DRAWINGS (PLAN, SECTION, & DETAIL DRAWINGS, ETC.), BETWEEN THE DRAWINGS AND ACTUAL CONDITIONS, AND BETWEEN THE DRAWINGS AND THE SPECIFICATIONS. DISCREPANCIES SHALL BE REPORTED TO THE VHA COR, IN WRITING, FOR RESOLUTION PRIOR TO PROCEEDING WITH THE WORK. SPECIFICATIONS SHALL GOVERN IN CASE OF DISCREPANCIES, WITH INPUT FROM THE A/E AND THE FINAL DETERMINATION BEING
MADE BY THE VHA COR.
K. DISSIMILAR METAL MATERIALS SHALL BE ISOLATED WITH AN APPROVED NONMETAL ISOLATION MATERIAL IN
ACCORDANCE WITH SPECIFICATIONS.
L. EXTERIOR EXPOSED STEEL SHALL BE PAINTED PER SPECIFICATION SECTION 09 91 00.
M. CONTRACTOR SHALL COORDINATE SIZE, LOCATIONS, AND NUMBER OF ROOF OPENINGS AND ROOF
ACCESSORIES WITH OTHER TRADES. REFER TO THE ARCHITECTURAL, STRUCTURAL, PLUMBING,
MECHANICAL AND ELECTRICAL DRAWINGS FOR REFERENCE AND SPECIFICATIONS FOR REQUIREMENTS.
N. LOCATIONS AND SIZES OF CONCRETE MECHANICAL AND ELECTRICAL EQUIPMENT PADS SHALL BE COORDINATED BY THE MECHANICAL AND ELECTRICAL CONTRACTORS WITH THE SELECTED EQUIPMENT MANUFACTURER AND/OR SUPPLIER. LOCATIONS ARE TO BE APPROVED BY THE VHA COR PRIOR TO
PROCEEDING WITH THE WORK.
O. CONTRACTOR TO INSTALL WOOD BLOCKING AND PLYWOOD AS REQUIRED FOR THE MOUNTING OF MEP
ITEMS. REFER TO SPECIFICATIONS.
P. REFER TO SPECIFICATION SECTION 01 45 29 FOR REQUIRED TESTING AND INSPECTIONS.
Q. DIMENSIONS SHOWN ON THE FLOOR PLAN ARE TO THE FACE OF GYPSUM WALL BOARD (FOG), FACE OF EXPOSED MASONRY (FOM), FACE OF CONCRETE WALLS (FOC) AND COLUMN GRID LINES, UNLESS OTHERWISE
NOTED OR INDICATED.
R. OPEN EXTERIOR JOINTS AT PENETRATIONS THROUGH THE BUILDING ENVELOPE, ETC, SHALL BE SEALED, CAULKED, FLASHED, OR WEATHER-STRIPPED AS REQUIRED BY SPECIFICATION SECTION 07 92 00.
GENERAL NOTES
ROOM NAME
VIEW TITLE EXAMPLE
ELEVATION CALLOUT EXAMPLE
ENLARGED CALLOUT EXAMPLE
SECTION CALLOUT EXAMPLE
SECTION OR DETAIL SYMBOL IDENTIFIERS
DETAIL NAME
DRAWING NUMBER
DESIGNATOR ON SHEET
DRAWING SEQUENCE
NUMBER INDICATES
WHERE DRAWING IS
LOCATED
TWO CHARACTER
DISCIPLINE DESIGNATOR
AE101
DOOR
NUMBER TAG
WALL
TYPE TAG
WINDOW
TYPE TAG
CENTER LINE
COLUMN
BUBBLE
ROOM TAG
MATCH LINE
DETAIL NUMBER
ON SHEET
SHEET NUMBER
DETAIL NUMBER
ON SHEET
SHEET NUMBER
NEW LINE TYPE
EXISTING LINE TYPE
DEMOLITION LINE TYPE
AREA OF DEMOLITION
VIEW NAME
1/8" = 1'-0"
AE101
AE101
AS101
FLOOR PLAN SYMBOLS LEGEND
AE101
EXTERIOR
INTERIOR
## SHEET KEYNOTE
REVISION TAG
DRAWING SCALE
REFERENCE
KEYNOTE
DETAIL NUMBER
ON SHEET
SHEET NUMBER
W3
######-A
A
A2
1-HR FIRE
2-HR FIRE
3-HR FIRE
4-HR FIRE
1-HR FIRE/SMOKE
2-HR FIRE/SMOKE
3-HR FIRE/SMOKE
4-HR FIRE/SMOKE
0-HR SMOKE
0.5-HR SMOKE
GENERAL ABBREVIATIONS
ABBREVIATIONS LISTED BELOW ARE GENERAL ABBREVIATIONS ACROSS ALL DISCIPLINES. DISCIPLINE SPECIFIC ABBREVIATIONS MAY SUPERSEDE GENERAL ABBREVIATIONS. REFER TO DISCIPLINE SPECIFIC ABBREVIATIONS SHEETS.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_A
R C
H _R
_d jo hn so nQ
P A
E 4.
rv t
/1
8/
0:
:1
A M
GI002
GENERAL ABBREVIATIONS, NOTES,
& SYMBOLS
INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
11/18/2022 TW DJ
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11
A
ABA ARCHITECTURAL BARRIERS ACT
AC AIR CONDITIONING
AD AREA DRAIN
ADJ ADJUSTABLE / ADJACENT
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECT / ARCHITECTURAL
ATTEN ATTENUATION
AUTO AUTOMATIC
AV AUDIO / VISUAL
AVG AVERAGE
B
BD BOARD
BLDG BUILDING
BM BENCH MARK / BEAM
BO BOTTOM OF
BOC BACK OF CURB
BOT BOTTOM
BRG BEARING
BRK BRICK
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BVL BEVELED
C
CAP CAPACITY
CB CATCH BASIN
CCTV CLOSED CIRCUIT TV
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CIP CAST-IN-PLACE
CL CENTER LINE
CLG CEILING
CLR CLEAR / CLEARANCE
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONN CONNECTION / CONNECT
CONST CONSTRUCT / CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CORR CORRIDOR / CORRUGATED
CP CONCRETE PIPE
CS COUNTERSINK
CU CUBIC
CW COLD WATER
D
DBL DOUBLE
DEMO DEMOLISH / DEMOLITION
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DN DOWN
DR DOOR
DTL DETAIL
DWG DRAWING
E
E EAST
EA EACH
EF EXHAUST FAN
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXT EXTERIOR
F
FA FIRE ALARM
FB FACE BRICK
FBO FURNISHED BY OWNER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FF FINISH FLOOR
FF&E FIXTURES, FURNITURE & EQUIPMENT
FFE FINISH FLOOR ELEVATION
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RATED
FRMG FRAMING
FS FLOOR SINK
FT FOOT/ FEET
FTG FOOTING
FUT FUTURE
G
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GOVT GOVERNMENT
GPM GALLON PER MINUTE
H
H HIGH
HB HOSE BIBB
HC HOLLOW CORE
HORIZ HORIZONTAL
HR HOUR
HS HIGH STRENGTH
HT HEIGHT
HTG HEATING
HTR HEATER
HVAC HEATING / VENTILATING / AIR
CONDITIONING
HW HOT WATER
HYD HYDRANT
I
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IN INCH
INCL INCLUDE (D), (ING)
INFO INFORMATION
INST INSTALL / INSTALLATION
INSUL INSULATE / INSULATION
INT INTERIOR
INV INVERT
J
JAN JANITOR
JB JUNCTION BOX
JST JOIST
JT JOINT
K
KIT KITCHEN
KO KNOCKOUT
L
L LONG / LENGTH
LAB LABORATORY
LAV LAVATORY
LBS POUNDS
LF LINEAR FOOT (FEET)
LH LEFT HAND
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LPT LOW POINT
LRG LARGE
LT LIGHT
LTG LIGHTING
LVR LOUVER
LWC LIGHTWEIGHT CONCRETE
M
MAS MASONRY
MAX MAXIMUM
MBR MEMBER
MECH MECHANICAL
MED MEDIUM
MFG MANUFACTURING
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MOD MODULAR
MTD MOUNTED
MTG MOUNTING
MTL METAL
N
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NSF NET SQUARE FEET
NTS NOT TO SCALE
O
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD / OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
OZ OUNCE
P
PA PUBLIC ADDRESS
PB PUSH BUTTON
PC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PERF PERFORATE (D)
PERM PERMANENT
PERP PERPENDICULAR
PL PLATE / PROPERTY LINE
PLUMB PLUMBING
PNL PANEL
PR PAIR
PREFAB PREFABRICATE (D)
PREFIN PREFINISHED
PRELIM PRELIMINARY
PREP PREPARE (D)
PROJ PROJECT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
PVG PAVING
Q
QTY QUANTITY
R
R RISER / RADIUS
RA RETURN AIR
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REINF REINFORCE (D), (ING)
REQD REQUIRED
REV REVISED/ REVISION
RH RIGHT HAND
RM ROOM
ROW RIGHT OF WAY
RR RESTROOM
RTU ROOF TOP UNIT
S
S SOUTH
SAN SANITARY SEWER
SCH SCHEDULE
SCRN SCREEN
SECT SECTION
SF SQUARE FOOT (SQFT)
SHT SHEET
SIM SIMILAR
SOG SLAB ON GRADE
SPEC SPECIFICATION (S)
SPKLR SPRINKLE
SPKR SPEAKER
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURE / STRUCTURAL
SUSP SUSPENDED
SY SQUARE YARD (SQ YD)
SYM SYMMETRICAL / SYMBOL
SYS SYSTEM
T
TEL TELEPHONE
TEMP TEMPORARY / TEMPERED
THK THICK (NESS)
THRU THROUGH
TO TOP OF
TOC TOP OF CURB / CONCRETE
TOD TOP OF DECK
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOR TOP OF ROOF
TOS TOP OF STEEL
TOW TOP OF WALL
TRANSF TRANSFORMER
TV TELEVISION
TYP TYPICAL
U
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V
VERT VERTICAL
VEST VESTIBULE
VHA VETERANS HEALTH ADMINISTRATION
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
W
W WEST, WIDTH, WIDE
W/ WITH
W/IN WITHIN
W/O WITHOUT
WC WATER CLOSET
WH WALL HYDRANT / WATER HEATER
WT WEIGHT
X, Y, Z, MISC
& AND
@ AT
YD YARD
CHILLER FOR USP PROJECT LOCATION
A. GI100 SERIES LIFE SAFETY PLANS HEREIN INDICATE EXISTING FIRE-
RESISTANCE RATED WALLS AND AREA DATA AS PROVIDED BY THE VHA.
REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING PLANS FOR SCOPE OF
WORK. REFER TO SPECIFICATIONS FOR REQUIREMENTS OF WORK THAT
AFFECTS FIRE-RESISTIVE RATED CONSTRUCTION.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_A
R C
H _R
_d jo hn so nQ
P A
E 4.
rv t
/1
8/
0:
:2
A M
GI111
LIFE SAFETY PLAN - BLDG 01 & 28
1ST FLOOR
INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
11/18/2022 DJ MP
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11
NTS
LIFE SAFETY PLAN - BLDG 01 & 28 1ST FLOOR1
F1
A. REFER TO SHEET GI002 FOR ADDITIONAL APPLICABLE GENERAL NOTES,
SYMBOLS, AND ABBREVIATIONS.
B. REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
C. DEMOLITION SHALL ONLY OCCUR IN AREAS AND AT COMPONENTS THAT ARE
DIRECTLY RELATED TO INSTALLATION OF THE STAND-ALONE CHILLER
PROCESSING UNIT. VIF.
D. CONTRACTOR SHALL COORDINATE WITH CONCOMITANT PROJECTS
OCCURRING IN THE SAME AREA. IN PARTICULAR, PROJECT FOR SITE PREP
BUILD USP 797 (QLEANAIR PHARMACY SITE PREP).
A
S L O P E
SLOPE
LEGEND
AREA OF BUILDING
COMPONENT DEMOLITION
APPROXIMATE AREA OF
ROOFING AFFECTED BY
PROJECT; ONLY
REPLACE AS REQUIRED
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
PHARMACY
& AREA OF
WORK
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_A
R C
H _R
_d jo hn so nQ
P A
E 4.
rv t
/1
8/
0:
:2
A M
AD111
DEMOLITION PLAN - ROOF INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
11/18/2022 TW DJ
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11
1. 12"X18" OPENING IN CONCRETE SLAB FOR PIPING (VIF). RE: MECHANICAL.
2. REMOVE EXISTING TPO MEMBRANE LOW SLOPE ROOF SYSTEM AS
REQUIRED FOR INSTALLATION OF MECHANICAL EQUIPMENT (VIF).
1/2" = 1'-0"
DEMOLITION PLAN - ROOF
F6
A. REFER TO SHEET GI002 FOR ADDITIONAL APPLICABLE GENERAL NOTES,
SYMBOLS, AND ABBREVIATIONS.
B. REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE WITH CONCOMITANT PROJECTS
OCCURRING IN THE SAME AREA. IN PARTICULAR, PROJECT FOR SITE PREP
BUILD USP 797 (QLEANAIR PHARMACY SITE PREP).
D. MECHANICAL EQUIPMENT SHALL HAVE A TPO MEMBRANE CURB BUILT AND
FLASHED PER MANUFACTURER'S STANDARD DETAILS, INCLUDING
REQUIRED CRICKETS FOR DRAINAGE.
E. REFER TO MECHANICAL SHEET MK501 FOR MECHANICAL EQUIPMENT
SUPPORT DETAILS.
A
1'
1' - 0"
SLOPE
S L O P E
F5
AE531
TYP BOTH
SIDES OF
AHU
D5
AE531
FACE OF EQMT
6" TYP FROM
F3
AE531
LEGEND
APPROXIMATE AREA OF
ROOFING AFFECTED BY
PROJECT; ONLY
REPLACE AS REQUIRED
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
PHARMACY
& AREA OF
WORK
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_A
R C
H _R
_d jo hn so nQ
P A
E 4.
rv t
/1
8/
0:
:2
A M
AE111
ROOF PLAN INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
11/18/2022 TW DJ
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11
1. PATCH AND REPAIR EXISTING MEMBRANE LOW SLOPE ROOF AS REQUIRED
AFTER INSTALLATION OF MECHANICAL EQUIPMENT (VIF).
2. MECHANICAL OR ELECTRICAL EQUIPMENT. REFER TO MECHANICAL,
PLUMBING, AND ELECTRICAL DRAWINGS.
3. RAIL MOUNT. REFER TO MECHANICAL.
4. BREAKMETAL COVER AT PIPING.
5. OPENING IN CONCRETE ROOF SLAB BELOW.
6. PROVIDE CRICKETS AS REQUIRED (VIF).
1/2" = 1'-0"
ROOF PLAN
F6
EXIST CONC ROOF SLAB
EXIST TAPERED INSULATION
EXIST ROOFING MEMBRANE
BUILT-UP TREATED 2X6 WOOD CURB TO
HEIGHT OF (E) TAPERED INSULATION (VIF)
SELF-ADHERED ROOFING MEMBRANE; LAP UP
& OVER CURB ASSEMBLY
REPLACE RIGID INSULATION AS REQUIRED
SHEET MTL CAP FLASHING
SEALANT, EA SIDE
6" COLD-FORMED METAL FRAMED MECHANICAL
CURB; LAG SCREW TO WOOD CURB
CONC 3/8" WEDGE ANCHOR
TO (E) CONC SLAB;
MINIMUM 3" PENETRATION
5/8" GYP EXTERIOR SHEATHING;
EACH SIDE
SPLICE & LAP NEW SELF-ADHERED ROOFING
MEMBRANE OVER EXISTING ROOF MEMBRANE
NOTE: COORDINATE WITH
MECHANICAL ROOF PLAN FOR
LOCATIONS AND DETAIL D2/MK501
FOR BIDDING PURPOSES.
COORDINATE WITH APPROVED
MECHANICAL SHOP DRAWINGS FOR
CURB LENGTH AND PLACEMENT
DURING CONSTRUCTION.
1' -0
M
IN
IM
U M
NOTES:
1. THIS DETAIL ILLUSTRATES A METHOD OF ELIMINATING PITCH POCKETS AND A METHOD OF GROUPING PIPING THAT
MUST COME ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE. SPECIFICS ABOUT THESE
PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURER'S SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET-METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3 INCHES, THE REMOVABLE SHEET-METAL
COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE ARCHITECTURAL METAL FLASHING SECTION OF THE NRCA ROOFING MANUAL: ARCHITECTURAL METAL FLASHING, CONDENSATION AND AIR LEAKAGE CONTROL, AND REROOFING FOR DESIGN, JOINERY AND SECUREMENT OPTIONS FOR
COUNTERFLASHINGS.
SHEET METAL ENCLOSURE
WITH REMOVABLE TOP -
CROSSBREAK OR SLOPE
FOR DRAINAGE.
INSULATE VOID (NOT
SHOWN FOR CLARITY).
SHEET METAL OR
FLEX-TUBE COLLAR.
PIPING. REFER TO
MECHANICAL.
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING -
SEE NOTE 3.
PREFABRICATED
CORNER FLASHING PIECE
AT EACH CORNER.
ADHERED MEMBRANE
FLASHING.
SEALANT (IF REQUIRED FOR
THE SPECIFIC SYSTEM).
HOT AIR WELDED SEAM.
GASKETED FASTENERS -
MIN TWO PER SIDE.
BONDING ADHESIVE.
SEAM PLATES AND
FASTENERS - SEE NOTE 4.
2 X 6 MIN WOOD NAILER
ATTACHED TO SUBSTRATE -
OVERALL THICKNESS TO
MATCH INSULATION.
SHEET METAL
FLASHING RECEIVER.
MIN 4" CLEARANCE
FROM PIPE TO TOP
OF CURB - MIN 2"
BETWEEN PIPES.
SLOPE
8" M
IN
IM
U M
FL
A
S H
IN
G
H
E
IG
H T
A. REFER TO SHEET GI002 FOR ADDITIONAL APPLICABLE GENERAL NOTES,
SYMBOLS, AND ABBREVIATIONS.
B. REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE WITH CONCOMITANT PROJECTS
OCCURRING IN THE SAME AREA. IN PARTICULAR, PROJECT FOR SITE PREP
BUILD USP 797 (QLEANAIR PHARMACY SITE PREP).
D. REFER TO MECHANICAL SHEET MK501 FOR MECHANICAL EQUIPMENT
SUPPORT DETAILS.
STAINLESS STEEL
CLAMPING RING
CONTINUOUS BEAD
OF SEALANT
PRE-MOLDED TPO LARGE
PIPE FLASHING
ROUND PENETRATION
(ACCESSIBLE FROM TOP)
WELDED SEAM
APPROVED PLATES
FASTENED WITH
APPROPRIATE
EXIST CONC ROOF SLAB
EXIST TAPERED INSULATION
EXIST ROOFING
MEMBRANE 2"
BUILT-UP TREATED 2X4 WOOD
CURB TO HEIGHT OF (E)
TAPERED INSULATION (VIF)
CONC 3/8" WEDGE ANCHOR
TO (E) CONC SLAB;
MINIMUM 3" PENETRATION
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
PHARMACY
& AREA OF
WORK
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_A
R C
H _R
_d jo hn so nQ
P A
E 4.
rv t
/1
8/
0:
:2
A M
AE531
DETAILS - ROOF INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
11/18/2022 TW DJ
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11
1 1/2" = 1'-0"
DETAIL - ROOF CURB
F5
NTS
FLASHING DETAIL AT PIPING THROUGH ROOF
D5
1 1/2" = 1'-0"
DETAIL - PIPE FLASHING
F3
GENERAL PLUMBING SYMBOLS
DIRECTION OF PIPE PITCH (DOWN)
DIRECTION OF FLOW
GUIDE
ANCHOR
REDUCER OR INCREASER
ECCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
CAPPED OUTLET
RISE OR DROP IN PIPE
UNION
PIPE UP
PIPE DOWN
POINT OF CONNECTION BETWEEN NEW
AND EXISTING WORK
LIMIT OF DEMOLITION
INVERTED BUCKET TRAP SET INCLUDING
PIPING ACCESSORIES
FLOAT & THERMOSTATIC TRAP SET
INCLUDING PIPING ACCESSORIES
STRAINER
THERMOMETER
PRESSURE GAGE
FLOW ELEMENT
WALL CLEAN OUT
CLEAN OUT
HOSE BIBB, FAUCET HEAD, SHOWER HEAD
WATER HAMMER ARRESTOR (PLAN VIEW)
FE
CO
MA
MV
LA
LV
OA
IA
D
SS
SD
SD
TWR
DWS
DWR
TWS
SS
SCW
FCW
NO
O
N
NG
NG
FOD
FOS
FOR
FOV
PLUMBING PIPING SYMBOLS
DOMESTIC COLD WATER, COLD WATER
DOMESTIC HOT WATER, HOT WATER
DOMESTIC HOT WATER RETURN
MEDICAL AIR
MEDICAL VACUUM
LABORATORY AIR
LABORATORY VACUUM
ORAL EVACUATION
INDUSTRIAL AIR
DRAIN
VENT (SANITARY)
SOIL, WASTE, OR SANITARY SEWER
SANITARY SEWER, BELOW GRADE
STORM WATER
STORM WATER, BELOW GRADE
SOFTEN COLD WATER
FILTERED COLD WATER
DRINKING WATER SUPPLY
DRINKING WATER RETURN
TEMPERED WATER RETURN
TEMPERED WATER SUPPLY
NITROUS OXIDE
OXYGEN
NITROGEN
NATURAL GAS
NATURAL GAS, BELOW GRADE
FUEL OIL DISCHARGE
FUEL OIL SUPPLY
FUEL OIL VENT
FUEL OIL RETURN
REAGENT WATER
REAGENT WATER RETURN
CORROSION RESISTANT SANITARY SEWER
CORROSION RESISTANT VENT (SANITARY)
GREASE WASTE
NEW PIPING
EXISTING PIPING
PIPE TO BE DEMOLISHED
FIXTURE OR EQUIPMENT TO BE DEMOLISHED
AV
PLUMBING VALVE SYMBOLS
GENERIC VALVE (REF SPEC FOR TYPE)
GENERIC VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
CONTROL VALVE
THREE-WAY CONTROL VALVE
PRESSURE REGULATING VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
THERMOSTATIC MIXING VALVE
RWR
RW
V CRP
SS CRP
GW
P-###
H4
H7
A
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL FIXTURE NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING SYMBOLS
NEW FIXTURE/EQUIPMENT (SHAPE VARIES, REF: SYMBOLS,
TAGS, & NOTES. SCHEDULED ITEMS ARE NEW UNO)
(E) EXISTING COMPONENT
(X) DEMOLISHED COMPONENT
26-SF 3
TYPICAL EQUIPMENT NUMBER
## GENERAL EQUIPMENT FURNISHED BY OTHERS; REF PQ
SHEET SERIES FOR CONNECTION SCHEDULE
PLUMBING GENERAL NOTES
A. PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED
CHASE OR ABOVE THE CEILING. REF SPECIFICATION 22 05 11.
B. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING TYPES IN EACH
SPACE. MINIMUM 18"X18" ACCESS PANELS ARE REQUIRED IN HARD CEILINGS
FOR VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, AND SO FORTH.
COORDINATE FINAL LOCATIONS IN THE FIELD FOR BEST ACCESS. REF
SPECIFICATION 08 31 13.
C. PROVIDE ACOUSTICAL SEALANT PER SPECIFICATION 07 92 00 AT PIPE
PENETRATIONS THROUGH SOUND RATED PARTITIONS.
D. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS
FOR NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME
AREAS. DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING
UNTIL COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED. REF
SPECIFICATION 01 33 23 AND 22 05 11.
E. PROVIDE LINE SIZE SERVICE VALVES AT POINTS OF CONNECTION TO
EXISTING PRESSURIZED PLUMBING PIPING.
PLUMBING ASCE 7-16 NONSTRUCTURAL SEISMIC
RESTRAINT AND ANCHORAGE NOTES
PROVIDE AND DESIGN SEISMIC BRACING FOR PLUMBING EQUIPMENT, PIPING
AND DUCTWORK IN ACCORDANCE WITH SPECIFICATION SECTION 13 05 41
SEISMIC RESTRAINT REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS.
GENERAL NOTES
A. PROVIDE TEMPORARY CONSTRUCTION PARTITIONS AND INFECTION
CONTROL BARRIERS AS APPLICABLE AROUND THE PROJECT AREA
CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY
THE VHA. REFER TO SPECIFICATION 01 35 26.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
/1
7/
:3 2:
P
M
P-001
PLUMBING ABBREVIATIONS,
SYMBOLS, & LEGENDS
INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
MB JD
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11 11/18/22
A
A/E ARCHITECT/ENGINEER
AD AREA DRAIN/ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AG AIR GAP
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION,
AND AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANCIAL ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
AV ACID VENT
AW ACID WASTE
B
BAS BUILDING AUTOMATION SYSTEM
BFP REDUCED PRESSURE BACKFLOW PREVENTER
BHP BREAK HORSEPOWER
BOD BASIS OF DESIGN
BSP BLACK STEEL PIPE
BT BATHTUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
CA COMPRESSED AIR
CFM CUBIC FEET PER MINUTE
CGA COMPRESSED GAS ASSOCATION
CI CAST IRON
CO CLEANOUT
CRP CORROSION RESISTANT PIPE
CS CLINICAL SINK
CV CONTROL VALVE
D
DCW DOMESTIC COLD WATER
DEMO DEMOLISH
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DI DEIONIZED WATER
DIV DIVISION
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
E
EL ELEVATION
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
EPA ENVIRONMENTAL PROTECTION AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWS EYE WASH STATION
EWS/SH EYE WASH/DRENCH SHOWER
EX EXISTING
F
F FARENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE) CONNECTION
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FS FLOW SWITCH
FU FIXTURE UNITS
G
GAL GALLON
GCO GRADE CLEANOUT
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GT GREASE TRAP
GVTR GAS VENT THROUGH ROOF
GWB GYPSUM WALL BOARD
GWH GAS FIRED WATER HEATER
PLUMBING ABBREVIATIONS
H
HB HOSE BIB
HD HUB DRAIN
HP HORSEPOWER
HR HR
HS HAND SINK
HST HOT WATER STORAGE TANK (DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HX HEAT EXCHANGER
HYD HYDRANT
I
ICW INDUSTRIAL COLD WATER
ID INSIDE DIAMETER
IE INVERT ELEVATION
IHW INDUSTRIAL HOT WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
K
KW KILOWATT
KWH KILOWATT-HOUR
L
LA LABORATORY AIR
LAV LAVATORY
LB POUND
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LV LABORATORY VACUUM
LW LOW WATER
M
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MFR MANUFACTURER
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N
N2 NITROGEN
N2O NITROUS OXIDE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NPS NOMINAL PIPE SIZE
NPW NON POTABLE WATER
NTS NOT TO SCALE
O
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OH OVER HEAD
OR OPERATING ROOM
OVFL OVERFLOW
P
P&ID PROCESS & INSTRUMENTATION DIAGRAM
PB PUSH BUTTON
PD PRESSURE DROP OR DIFFERENCE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAUGE
PH PHASE
PLBG PLUMBING
PLUM PLUMBING
PP PLUMBING PUMP
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAGE
PTRV PRESSURE TEMPERATURE RELIEF VALVE
PW POTABLE WATER
R
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
REF REFERENCE OR REFER TO
RH ROOF HYDRANT
RL ROOF LEADER
RO REVERSE OSMOSIS WATER
RP RECIRCULATION PUMP
RPZA REDUCED PRESSURE BACKFLOW PREVENTION
ASSEMBLY
RW REAGENT WATER
RWL RAIN WATER LEADER
RWR REAGENT WATER RETURN
S
SAN SANITARY SEWER
SCFM STANDARD CUBIC FEET PER MINUTE
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SIM SIMILAR
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCATION
SMH SANITARY MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SQFT/SF SQUARE FEET
SS SANITARY SEWER
SST STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
T
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
U
UF UNDER FLOOR
UNO UNLESS NOTED OTHERWISE
UR URINAL
V
V VENT
VAC VACUUM OR VOLTAGE (AC)
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VSD VARIABLE SPEED DRIVE
VTR VENT THROUGH ROOF
W
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNITS
X
XP EXPLOSION PROOF
Y
YCO YARD CLEANOUT
YH YARD HYDRANT
0 CONSTRUCTION DOCUMENTS 100% 11/18/22
11/17/2022
B
133712
BUFFER RM
MECH RM
13371
ANTEROOM
133711
BUFFER RM
2 3
C
BFP
4"ø DCW
3" ø
D C
W
2 1/2"ø DCW2 1/2"ø DCW
MECHANICAL
NUCLEAR MEDICINE
LAB
28-3
STAIR 33/
4" ø D
C W
3/4"ø DCW
3/ 4" ø D
C W
PHARMACY
A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
E. REFER TO SPECIFICATIONS FOR PROJECT PHASING PLAN AND NARRATIVE.
F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
G. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
B
A
P-805
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTIONS 22 40 00.
2. FIXTURES SHALL BE ACCESSIBLE
UNO. REFER TO GENERAL AND
ARCH PLANS FOR REQUIREMENTS.
3. PROVIDE WATER HAMMER
ARRESTOR. ALSO REFER TO
SPECIFICATION 22 11 00.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
L K
E R
B
LV
D
W A
L K
E R
B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
PHARMACY
& AREA OF
WORK
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
6/
/2
9:
:0
A
M
PP111
DOMESTIC WATER PLAN &
FIXTURE SCHEDULE
INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
MB JD
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11 11/18/22
1/4" = 1'-0"
DOMESTIC PLAN - LEVEL 1
F5
1. CONNECT TO CHW MAKEUP ASSEMBLY. REF MP SHEET SERIES.
2. UP TO ROOF HYDRANT ON 1ST FLOOR ROOF.
3. ROUTE 3/4" INDIRECT DRAIN FROM ROOF HYDRANT TO FLOOR DRAIN IN
MECH RM.
4. COORDINATE PLUMBING TO AVOID NEW ELECTRICAL PANELS.
5. PERFORM TIE-IN ON WEEKEND DURING SHUTDOWN OF FLOOR ZONE
COORDINATED WITH THE VA 2 WEEKS IN ADVANCE.
6. CONNECT FULL SIZE INDIRECT DRAIN TO BFP AND ROUTE TO FLOOR DRAIN
IN MECH RM.
7. WORK IN THE PHARMACY DEPARTMENT REQUIRES SUPERVISION BY
HOSPITAL PHARMACY STAFF. COORDINATE WITH VHA COR. PROVIDE
CLASS IV INFECTION CONTROL FOR WORK IN PHARMACY DEPARTMENT IN
ACCORDANCE WITH SPECIFICATION 01 35 26.
1/4" = 1'-0"
DOMESTIC PLAN - LEVEL 2 & ROOF
F1
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION
DCW
CONNECTION
(NPS)
DHW
CONNECTION
(NPS)
SS
CONNECTION
(NPS)
VENT
CONNECTION
(NPS)
BASIS OF
DESIGN
REMARKS
P-805 ROOF HYDRANT, FREEZELESS 3/4 - - -
WOODFORD
RHY1-MS
1,2,3
06/26/2023
HVAC GENERAL NOTES
A. PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED
IN A FURRED CHASE OR ABOVE THE SUSPENDED CEILING. REF
SPECIFICATION 23 05 11.
B. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN
OR INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS IN INCHES UNO.
REF SPECIFICATION 23 31 00.
C. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING TYPES IN EACH
SPACE. MINIMUM 18"X18" ACCESS PANELS ARE REQUIRED IN HARD CEILINGS
FOR VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, AND SO FORTH.
COORDINATE FINAL LOCATIONS IN THE FIELD FOR BEST ACCESS. REF
SPECIFICATION 08 31 13.
D. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT
SYSTEM, TERMINAL UNITS, FILTERS, COILS, AND SO FORTH.
E. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT,
SEE EQUIPMENT DETAILS AND RESPECTIVE SPECIFICATIONS.
F. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE
MADE TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
G. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE
INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE FINISHED
FLOOR.
H. PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE.
I. CONTROL SYSTEM EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING
BUILDING MANAGEMENT SYSTEM CONTROLS. EXTEND EXISTING CONTROL
SYSTEM TO INCLUDE CONTROLS AND SEQUENCES SHOWN. REF
SPECIFICATION 23 09 23.
J. COORDINATE EXISTING FIRE SPRINKLER HEADS AND LIGHTS WITH DUCTS
AND DIFFUSERS.
K. FOR RETURN AIR AND EXHAUST AIR, AND FOR SUPPLY AIR IN THE
FOLLOWING SPACES OR WHERE EXPOSED TO VIEW, THE USE OF FLEXIBLE
AIR DUCT IS PROHIBITED:
a. PATIENT ROOMS
b. OPERATING ROOM SUITES AND SPACES
c. SPS PROCESSING SPACES
d. PHARMACY COMPOUNDING SPACES
e. ISOLATION ROOMS
f. CLEAN ROOMS
g. BIO-CONTAINMENT LABORATORIES
h. RESEARCH LABORATORIES
i. CLINICAL LABORATORIES
L. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS
FOR NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME
AREAS. DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING
UNTIL COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED. REF
SPECIFICATION 01 33 23 AND 22 05 11.
M. PROVIDE LINE SIZE SERVICE VALVES AT POINTS OF CONNECTION TO
EXISTING MECHANICAL PIPING.
GENERAL NOTES
A. PROVIDE TEMPORARY CONSTRUCTION PARTITIONS AND INFECTION
CONTROL BARRIERS AS APPLICABLE AROUND THE PROJECT AREA
CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY
THE VHA. REFER TO SPECIFICATION 01 35 26.
MECHANICAL ASCE 7-16 NONSTRUCTURAL SEISMIC
RESTRAINT AND ANCHORAGE NOTES
PROVIDE AND DESIGN SEISMIC BRACING FOR MECHANICAL EQUIPMENT, PIPING
AND DUCTWORK IN ACCORDANCE WITH SPECIFICATION SECTIONS 13 05 41
SEISMIC RESTRAINT REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS AND
23 05 41 NOISE AND VIBRATION CONTROL.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
/1
7/
:3 2:
P
M
M-001
MECHANICAL ABBREVIATIONS &
NOTES
INSTALL CHILLER FOR USP
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-22-115
MB JD
CONSTRUCTION
DOCUMENTS 100%
VEG 22.11 11/18/22
A
A/E ARCHITECT / ENGINEER
AAV AUTOMATIC AIR VENT
ACCH AIR COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER, MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER, TWO POSITION
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AHU AIR HANDLING UNIT
AMP AMPERE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARCH ARCHITECTURE
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND
AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
B
B BOILER
BAS BUILDING AUTOMATION SYSTEM
BASC BUILDING AUTOMATION SYSTEM CONTRACTOR
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BLDG BUILDING
BOD BASIS OF DESIGN
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
C
CAP CAPACITY
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CONDENSATE DRAIN
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMP
CFT CUBIC FEET
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CKT CIRCUIT
CLG COOLING
CM CARBON MONOXIDE
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CTRL CONTROL
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CUP CENTRAL UTILITY PLANT
CV CONSTANT VOLUME
CV CONTROL VALVE
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO COOLING TOWER)
CWS CONDENSER WATER SUPPLY (FROM COOLING TOWER)
D
D DAMPER
DB DECIBEL
DBT DRY BULB TEMPERATURE
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG DEGREES
DEMO DEMOLISH
DF DIFFUSER
MECHANICAL ABBREVIATIONS
DI DEIONIZED WATER
DIA DIAMETER
DN DOWN
DP DEW POINT TEMPERATURE
DP DIFFERENTIAL PRESSURE
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
E
E EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EAT-DB ENTERING AIR TEMPERATURE DRY BULB
EC ELECTRONICALLY COMMUTATED
ECC ENGINEERING CONTROL CENTER
ECM ELECTRONICALLY COMMUTATED MOTOR
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ERW ENERGY RECOVERY WHEEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
F
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/S FIRE SMOKE DAMPER
FA FIRE ALARM
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FD FLOOR DRAIN
FD FIRE DAMPER
FF FILTER FEEDER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOHX FUEL OIL HEAT EXCHANGER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT WG FEET WATER GAUGE
FT-LB FOOT-POUND
FTR FINNED TUBE RADIATION
FV FACE VELOCITY
G
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GH GRAVITY HOOD
GHW GLYCOL HEATING WATER
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
GWB GYPSUM WALL BOARD
H
H HUMIDIFIER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HR HOUR
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTG HEATING
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVD HOISTWAY VENT DAMPER
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING WATER PUMP
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCHES OF WATER COLUMN
IN WG INCHES OF WATER, GAUGE
IN-LB INCH-POUND
IOM INSTALLATION AND OPERATION MANUAL
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
K
KEA KITCHEN EXHAUST AIR
KW KILOWATT
KWH KILOWATT HOURS
L
LAT LEAVING AIR TEMPERATURE
LAT-DB LEAVING AIR TEMPERATURE DRY BULB
LB POUND
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPG LIQUID PROPANE GAS
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPS LOW PRESSURE STEAM
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKEUP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM CIRCUIT AMPACITY
MEP MECHANICAL ELECTRICAL PLUMBING
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MOCP MAXIMUM OVERCURRENT PROTECTION
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING UNIT
MTD MEAN TEMPERATURE DIFFERENCE
MUA MAKEUP AIR
MV MECHANICAL VENT
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
N
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOW METER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPS NOMINAL PIPE SIZE
NPSH NET POSITIVE SUCTION HEAD
NPSHA NPSH AVAILABLE
NTS NOT TO SCALE
O
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OAL OUTSIDE AIR LOUVER
OD OUTER DIAMETER
OFM OIL FLOWMETER
OH OVER HEAD
OR OPERATING ROOM
P
P PUMP
P&ID PROCESS & INSTRUMENTATION DIAGRAM
P/T PRESSURE/TEMPERATURE
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAUGE
PGW PROPYLENE GLYCOL-WATER SOLUTION
PH PHASE
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRESS PRESSURE
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH, ABSOLUTE
PSIG POUNDS PER SQUARE INCH, GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
Q
QTY QUANTITY
R
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCP RADIANT CEILING PANEL
RD REFRIGERANT DISCHARGE
REA RELIEF AIR
REF REFERENCE OR REFER TO
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
RV RELIEF VALVE
S
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SIM SIMILAR
SOO SEQUENCE OF OPERATION
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT
SQ IN SQUARE INCHES
SR SUPPLY AIR REGISTER
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
SST STAINLESS STEEL
ST STEAM TRAP
STRUCT STRUCTURAL
SUH STEAM UNIT HEATER
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
T
T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE
TAB TESTING, ADJUSTING, AND BALANCING
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
U
UC UNIT COOLER
UCT UNDERCUT
UF UNDER FLOOR
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
V
V VALVE
VAC VOLTAGE ALTERNATING CURRENT
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
W
W WASTE
WAG WASTE ANESTHESIA GAS
WB WET BULB
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCPU WATER COOLED HEAT PUMPS
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
X
XP EXPLOSION-PROOF
Y
YR YEAR
T
TT
M
MT
PT
TT
FT
IT
CT
SD
PDT
TSL
HS
M
LC
LT
PDS
TSH
EPT
AT
CO2
AT
CO
AT
OC
LTCP
VFD
PSH
PSL
26-SF 3
26-TU-1-1
H4
H7
A
BDD
FD
VD
N
1/24
F/S DPR
AV
MV
RH
SCH
SH
TH
PS
RC
WB
CSH
SS
VR
CTPS
CTPD
FWPS
FWPD
CF
FWS
BWS
CBD
BO
TC
A
OFL
HW
SW
CW
FOR
FOS
LPG(I)
NG(I)
NG
HPS
HPR
MPS
MPR
LPS
LPR
PC
HWS
HWR
GHS
GHR
V
SWS
SWR
CWR
CHR
GCR
RL
RS
RHG
CWS
CHS
GCS
MW
D
GRR
GRS
D
R
FC
10x8
M
DETAIL REFERENCE
DRAWING NUMBER WHERE SHOWN
SECTION REFERENCE
TYPICAL UNIT NUMBER
BUILDING NUMBER WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NUMBER 3 IN BUILDING NUMBER 26
EQUIPMENT ABBREVIATION (EG SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NUMBER 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NUMBER 1
DRAWING NUMBER WHERE DRAWN
BUILDING NUMBER WHERE EQUIPMENT IS LOCATED
* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY STANDARD PRACTICE SP-58
TEST PLUG (P/T PORT)
AUTOMATIC AIR VENT
MANUAL AIR VENT
QUICK-COUPLE HOSE CONNECTOR
CONNECT TO EXISTING
LIMIT OF DEMOLITION
AIR SEPARATOR
EXISTING DUCT TO BE REMOVED
LOUVER (REF SPECIFICATION 08 90 00)
FLEXIBLE DUCTWORK (INSULATED)
DUCT WITH SOUND LINING
MANUAL VOLUME DAMPER
FIRE DAMPER
BACK DRAFT DAMPER
COMBINATION FIRE/SMOKE DAMPER
AUTOMATIC CONTROL DAMPER
2'x2' RADIANT CEILING PANEL
2'x4' RADIANT CEILING PANEL
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
SQUARE 1-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SUPPLY REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING
REGISTER OR GRILLE
EXHAUST OR RETURN REGISTER
OR GRILLE (WALL TYPE)
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
(REF MK SHEET SERIES)
CONNECT NEW DUCT TO EXISTING DUCT
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
LIMIT OF DEMOLITION
FLEXIBLE CONNECTION, EQUIPMENT,
VIBRATION, OR SEISMIC
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS, INCHES):
WIDTH x DEPTH (RECTANGULAR)
WIDTH / DEPTH (FLAT OVAL)
DIAMETER Ø (ROUND)
EXISTING DUCT TO REMAIN
GENERIC VALVE (REF SPEC FOR TYPE)
GLOBE VALVE
3/4" HOSE ADAPTER
CHECK VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
FLEXIBLE PIPE CONNECTOR
ANGLE GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
CONTROL VALVE
CONTROL BUTTERFLY VALVE
THREE-WAY CONTROL VALVE
PRESSURE REGULATING (IE REDUCING) VALVE
PRESSURE SAFETY VALVE / RELIEF VALVE
WATER FLOW BALANCE VALVE
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
FLOW METER
ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT
ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER -
WALL MOUNT
TEMPERATURE TRANSMITTER
TEMPERATURE TRANSMITTER, AVERAGING ELEMENT
MOISTURE (HUMIDITY) TRANSMITTER
PRESSURE TRANSMITTER
FLOW TRANSMITTER
CURRENT TRANSMITTER
CONDUCTIVITY TRANSMITTER
SMOKE DETECTOR
PRESSURE DIFFERENTIAL TRANSMITTER
PRESSURE DIFFERENTIAL SWITCH
HAND SWITCH (HAND-OFF-AUTO SWITCH)
VALVE OR DAMPER ACTUATOR
TEMPERATURE SWITCH, LOW (FREEZESTAT)
TEMPERATURE SWITCH, HIGH
LEVEL CONTROLLER
LEVEL TRANSMITTER
PRESSURE SWITCH HIGH
PRESSURE SWITCH LOW
ELECTRONIC TO PNEUMATIC TRANSDUCER
CARBON DIOXIDE TRANSMITTER
CARBON MONOXIDE TRANSMITTER
OCCUPANCY SENSOR
LOCAL TEMPERATURE CONTROL PANEL
VARIABLE SPEED MOTOR CONTROLLER
CONTROLS SYMBOLS
GENERAL SYMBOLS AND TAGS
HVAC SYMBOLS PIPING SYMBOLSPIPING SYMBOLSHVAC SYMBOLS
FLOOR-SUPPORTED PIPE STAND
RISER CLAMP (TYPE 42)*
WALL BRACKET (TYPE 31, 32, 33)*
CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*
SLIDING SUPPORTS (TYPE 35)*
TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT
TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)
HOT WATER
ROLLER-TYPE HANGER
VARIABLE SPRING-TYPE HANGER (TYPE 51)*
SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*
CLEVIS-TYPE HANGER
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HIGH PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
LOW PRESSURE STEAM CONDENSATE RETURN
CONDENSATE PUMP DISCHARGE
HEATING WATER SUPPLY
HEATING WATER RETURN
GLYCOL-WATER HEATING SUPPLY
GLYCOL-WATER HEATING RETURN
SOLAR WATER SUPPLY
SOLAR WATER RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
CONDENSER WATER SUPPLY (FROM TOWER)
CONDENSER WATER RETURN (TO TOWER)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
GLYCOL-WATER CHILLED SUPPLY
GLYCOL-WATER CHILLED RETURN
MAKE-UP WATER
DRAIN LINE
VENT LINE
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURN
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
CONDENSATE TRANSFER PUMP DISCHARGE
CONDENSATE TRANSFER PUMP SUCTION
VACUUM CONDENSATE RETURN
TUBE CLEANER WATER SUPPLY
BOILER BLOWOFF
CONTINUOUS BLOWDOWN
BOILER WATER SAMPLE
FEEDWATER SAMPLE (FROM DEAERATOR)
CHEMICAL FEED
OVERFLOW
COMPRESSED AIR
NATURAL GAS MAIN FUEL
NATURAL GAS IGNITER FUEL
LIQUEFIED PETROLEUM GAS IGNITER FUEL
FUEL OIL SUPPLY
FUEL OIL RETURN
COLD WATER (CITY WATER)
SOFTENED WATER
THERMOMETER
PRESSURE GAGE
FLOW ELEMENT
SIGHT GLASS
THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
FLOAT & THERMOSTATIC TRAP SET
INCLUDING PIPING ACCESSORIES SEE DETAIL
INVERTED BUCKET TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
DIRECTION OF PIPE PITCH (DOWN)
DIRECTION OF FLOW
ANCHOR
REDUCER OR INCREASER
ECCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
CAPPED OUTLET
RISE OR DROP IN PIPE
UNION
PIPE UP
PIPE DOWN
POINT OF CHANGE IN DUCT CONSTRUCTION BY STATIC
PRESSURE CLASS. THE NUMBER ASSIGNS PRESSURE
CLASS (IN OF WATER) WHICH WILL ACCOMMODATE
MAXIMUM OPERATING PRESSURE IN THE DUCT
SUBSECTION. THE SYMBOL CONTINUES THE
ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
FE
DEMOLISHED EQUIPMENT (SHAPE VARIES, REF:
SYMBOLS, TAGS, & NOTES)
(E) EXISTING COMPONENT
(X) DEMOLISHED COMPONENT
PIPE TO BE DEMOLISHED
MS MOISTURE (HUMIDITY) SWITCH
FSH FLOW SWITCH HYDRONIC
DS DOOR SWITCH
PR PILOT RELAY
MOTOR STARTER
WELDED STAINLESS STEEL DUCT
PROVIDE FLEXIBLE SHAFT WRAP A MINIMUM OF 10 FT ON
BOTH SIDES OF FIRE BARRIER PENETRATIONS. THE FIRE
RESISTIVE RATING OF THE WRAP SHALL BE EQUIVALENT TO
THAT OF THE BARRIER PENETRATED. WRAP ENTIRETY OF
RISERS WITHIN SHAFTS SHARED WITH ENVIRONMENTAL AIR
DUCTS.
AIR DEVICE MARK
AIR DEVICE CFM1,200
SD-1
GUIDE
WM WATER FLOW METER
SENSOR WELL / O-LET
NEW PIPING
EXISTING PIPING
MV MECHANICAL VENT LINE
CD CONDENSATE DRAIN LINE
AFMD AIR FLOW MEASUREMENT DEVICE
PUMP TRAP SET INCLUDING PIPING
ACCESSORIES SEE DETAIL
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
DUCT-MOUNTED COIL (HOT WATER
OR STEAM COIL)
DUCT-MOUNTED COIL (ELECTRIC)
SDPR
SMOKE DAMPER
## GENERAL EQUIPMENT FURNISHED BY OTHERS; REF MQ
SHEET SERIES FOR CONNECTION SCHEDULE
DOUBLE-LINED VALVE
(REFER TO SPECS FOR TYPE)
# MI7##
DETAIL
SHEET
EQUIPMENT APPLICABLE P&ID, SOO, &
POINT LIST REFERENCE
NEW EQUIPMENT…