504-21-110 Construction_Documents.pdf

PDF 21 MB Posted

Attached to
Y1DZ--504-21-110; Renovate Eye Clinic & Ambulatory Care Service Primary Care (Construction)
Solicitation number
36C25723B0016
Issued by

About this file

This document provides details on a federal contract solicitation for construction services. Solicitation number 36C25723B0016 from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17 seeks proposals to renovate the Eye Clinic and Ambulatory Care Service Primary Care at an unspecified location. Contractors should respond with proposals to complete renovations to modernize and improve facilities for eye and primary care services. The solicitation does not specify pricing terms, set asides, incumbent contractors, or response and award dates.

View the file

Other files

File Type Posted
36C25723B0016 0001.docx DOCX document
RFI_04_IN-401.pdf PDF
Bldg. 1 Asbestos Inspection Report Final 12-24-18.pdf PDF
RFI_16_A-401 - EQUIPMENT PLAN.pdf PDF
504-21-110 Specifications.pdf PDF
36C25723B0016.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

212 N. CRAWFORD AVE.

NORMAN, OK. 73069

VETERANS

HEALTH

ADMINISTRATION

U.S. Department of Veterans Affairs

F U E L

T A N K S

E N G

IN

E E R

IN

G

OI&T

SHOPS

BOILER

WARE-

HOUSE

G N D S

WAREHOUSE

HBPC

HAS

WAREHOUSE

FISCAL/

CHILLER

LOT E

LOT I

LOT J LO

T J

AREA 1

LOT I

LOT G

LOT H

LOT K

LOT L

LOT M

LOT N

LOT A

LO

T B

LOT C

LOT D

SWITCH

SERVICES

CLC

ME

DI

CA

L

AR

TS

LO

DGE

Tank

H A Z

PR

IM

AR

Y

CA

RE

FU

TU

RE

RE

HA

B

PR

OS

TH

ET

ICS

CLC

SP

EC

IAL

TY

C

LIN

IC

CE

NT

ER

f or

RE

CO

VE

RY

a nd

TH

ER

AP

Y

HO

SP

IT

AL

OR

IG

Ma in H os pi ta l

(S 3° '0 6" W

.9 1'

S 89°47'OO" E 1947.94'

L 8.

S °1 7' W

4.

(N

°2 '5

.4

R

.6 7'

(N 44°16'13" W 496.56')

(N44°17'57" W 1000.33')

N

°1 '2

.2

N 44°15'49" W 496.50'

N44°15'49" W 1000.00'

S.W. 9TH AVENUE

U .S H

IG

H W

AY

H

ER

N

DO

N

E. W

ALK

ER

N. EDM

AN

W

ED

M

AN

W . W

A

LK

ER

S.

ED

M

AN

(A M

AR

IL

LO

BL

VD

14 3

AREA OF WORK

PROJECT LOCATION

Thomas E. Creek VA Medical Center

6010 W AMARILLO BLVD.

AMARILLO, TX. 79106

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

2/10/2022

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

SubmissionARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

BI

M

R en ov at e Ey e C lin ic

A

C S

Pr im ar y

C ar e/ R en ov at e

Ey e

C lin ic

A C

S Pr im ar y C ar e_ de ta ch ed

.rv t

2/

/2

:0 7:

A

M

G-001

COVER SHEET AND SHEET INDEX

PRIME ARCHITECTS

212 N. CRAWFORD AVE

NORMAN, OK. 73069

(866) 226-8071

GENE LAVASTIDA

RENOVATE EYE CLINIC AND ACS

PRIMARY CARE

6010 AMARILLO BLVD. WEST, AMARILLO TX 79106

504-21-110

SCOTT HOBBS COR

02/09/2022 CM DT

Thomas E.

Creek VA

Medical Center

100% FINAL BID

DOCUMENTS

SHEET INDEX

SHEET NO. SHEET NAME

MECHANICAL

M-001 MECHANICAL NOTES, LEGENDS, & ABBREVIATIONS

M-101 MECHANICAL DUCTWORK DEMOLITION PLAN - FIRST FLOOR

M-102 MECANICAL PIPING DEMOLITION PLAN - FIRST FLOOR

M-201 MECHANICAL DUCTWORK PLAN - FIRST FLOOR

M-202 MECHANICAL PIPING PLAN - FIRST FLOOR

M-301 MECHANICAL DETAILS

M-401 MECHANICAL SCHEDULES

M-402 MECHANICAL CONTROLS

M-403 MECHANICAL AIR BALANCE

ELECTRICAL

E-001 NOTES AND LEGENDS

E-100 ELECTRICAL DEMOLITION PLAN - FIRST FLOOR

E-101 ELECTRICAL LIGHTING FIRST FLOOR PLAN

E-102 ELECTRICAL FIRST FLOOR PLAN

E-103 ELECTRICAL CONNECTIONS FLOOR PLAN

E-201 ELECTRICAL DETAILS

TECHNOLOGY

T-001 TECHNOLOGY NOTES, LEGENDS AND SCHEDULES

T-100 TECHNOLOGY DEMOLITION PLAN - FIRST FLOOR

T-101 TECHNOLOGY OVERALL

T-201 TECHNOLOGY FIRST FLOOR PLAN

T-301 TECHNOLOGY ENLARGED PLAN

T-401 TECHNOLOGY SCS DETAILS

T-402 TECHNOLOGY SCS DETAILS

T-403 TECHNOLOGY VSS DETAILS

SHEET INDEX

SHEET NO. SHEET NAME

GENERAL

G-001 COVER SHEET AND SHEET INDEX

G-002 FIRST FLOOR LIFE SAFETY ANALYSIS

G-003 PARTITION TYPES

ARCHITECTURAL

A-001 ARCHITECTURAL ABBREVIATIONS, SYMBOLS, LEGENDS

AD-101 FIRST FLOOR DEMO PLAN

AD-102 FIRST FLOOR DEMO RCP

A-100 PHASING PLAN AND INFECTION CONTROL

A-101 FIRST FLOOR PLAN

A-102 FIRST FLOOR RCP

A-201 INTERIOR ELEVATIONS

A-401 EQUIPMENT PLAN

A-402 EQUIPMENT PLAN

A-403 EQUIPMENT PLAN

A-404 ENLARGED PLAN

A-501 DOOR SCHEDULE / DOOR & WINDOW DETAILS

A-502 DETAILS

A-601 SIGNAGE

INTERIORS

IN-501 ROOM FINISH & MATERIALS LEGEND

IN-502 FLOOR PATTERN PLAN

PLUMBING

P-101 PLUMBING FIRST FLOOR PLAN

P-201 PLUMBING RISERS

P-202 PLUMBING RISERS

P-301 PLUMBING DETAILS

P-401 PLUMBING SCHEDULES

ADD ALTERNATES

1. ROOM 115 AIR HANDLING UNIT.

2. ROOMS 131, 132, 133 COMPLETE RENOVATION.

3. ROOMS 134, 135, AND 136 FINISHES.

4. STAIR #2 140, AND STAIR #3 141 FLOORING MATERIAL.

5. ROOMS 142, 143, AND 144 FINISHES.

Revisions: Date:

143' - 3"

EXIT

22 OCC

3.3"

EXIT

22 OCC

3.3"

EXIT

EXIT

EXIT

TOTAL FIRST FLOOR AREA

BUSINESS USE GROUP 21,497 S.F.

RENOVATED EYE CLINIC AND ACS PRIMARY CARE

BUSINESS USE GROUP PROJECT AREA 6,851 S.F.

EXIT

505 SF

5428 SF

534 SF

130 SF 218 SF

EXISTING

1 HOUR

FIRE

SMOKE

BARRIER

NEW 1 HOUR FIRE

SMOKE BARRIER

EXISTING 1 HOUR

FIRE BARRIER

EXISTING SMOKE

PARTITION AND

HAZARDOUS AREA

EXISTING 2 HOUR

FIRE BARRIER

EXISTING 2 HOUR

FIRE BARRIER

EXISTING 2 HOUR

FIRE BARRIER

EXISTING 2 HOUR

FIRE BARRIER

TEMPORARY MEANS

OF EGRESS DURING

CONSTRUCTION

TEMPORARY

BARRIER DURING

CONSTRUCTION

PHOTOGRAPHY

VISUAL FIELDS

SPECIALTY TESTING

LASER

MULTIPURPOSE ROOM

OPTOMETRY STAFF

OPHTHALMOLOGY

STAFF

TOMOGRAPHY

ULTRASOUND - MINOR

PROCEDURE

AIR HANDLING UNIT

WAITING

EXAM

PRE-TESTING

ACS CHIROPRACTOR

ACS MASSEUSE

ACS ACUPUNCTURE

FILES/SEC/RECEP

DENTIST OFFICE

CHIEFS OFFICE

WOMENS RESTROOM

ACS SHARED OFFICE

MENS RESTROOM

RECEPTION

112 OPTICAL FITTING

MEDICAL STORAGE

CHECK IN

110HAC

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

FIRE

WHEELCHAIR

LINEN

CORRIDOR

CORRIDOR

CORRIDOR

CLEAN

FIRE

STAIR #3

141 STAIR #2

CORRIDOR

CORRIDOR

CORRIDOR

LOCKSMITH

BREAKROOM

ANTE

ROOM

FIRE BARRIER AND SMOKE

PARTITION LEGEND

SMOKE PARTITIONS FIRE BARRIER

SMOKE

1 HR

2 HR

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

2/10/2022

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

SubmissionARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

BI

M

R en ov at e Ey e C lin ic

A

C S

Pr im ar y

C ar e/ R en ov at e

Ey e

C lin ic

A C

S Pr im ar y C ar e_ de ta ch ed

.rv t

2/

/2

:0 7:

A

M

G-002

FIRST FLOOR LIFE SAFETY

ANALYSISPRIME ARCHITECTS

212 N. CRAWFORD AVE

NORMAN, OK. 73069

(866) 226-8071

GENE LAVASTIDA

RENOVATE EYE CLINIC AND ACS

PRIMARY CARE

6010 AMARILLO BLVD. WEST, AMARILLO TX 79106

504-21-110

SCOTT HOBBS COR

02/09/2022 CM DT

Thomas E.

Creek VA

Medical Center

100% FINAL BID

DOCUMENTS

1/16" = 1'-0"1 FIRST FLOOR - LIFE SAFETY PLAN

FEC

FEC

FEC

PARTITION TYPES:

HEAD

NOTES:

SILL

PLAN

WHERE

NOTED

TO BE

FIRE RATED -

EXTEND GWB

FULL HT.

TO DECK AND

SEAL

CONTRACTOR TO PROVIDE SOLID,

CONTINUOUS,

FIRE RATED WOOD BLOCKING FOR ALL

MILLWORK, TOILET ACCESSORIES AND

OTHER

MISCELLANEOUS ASSEMBLIES REQUIRING

BLOCKING

L/240

L/240 L/240

3 5/8"

16"O.C.

16"O.C.

16"O.C.

26'-1"

17'-11" 19'-2"

THE G.C. IS TO PROVIDE AND INSTALL METAL

STUDS OF A DEPTH AND GAUGE AS SHOWN

ON THE PLANS. REFER TO STUD GAUGE

CHART

SHOWN BELOW FOR GAUGES NOT

INDICATED ON PLANS (CONFORMANCE TO

MANUFACTURER'S STANDARDS REMAINS

THE G.C. RESPONSIBILITY):

SIM. TO 1:

1 LAYER OF 5/8" TYPE "X" GWB BOTH

SIDES FULL HEIGHT TO DECK WITH

ACOUSTICAL BATTS AT TENANT OFFICE

PARTITIONS

VARIES

VARIES

NOTE: ALL WALL FRAMING SHALL BE 20

GAUGE

STUDS MINIMUM AND ALL GWB UNLESS

OTHERWISE NOTED SHALL BE 5/8" TYPE X

IN

ALL LOCATIONS. MOISTURE RESISTANT AT

PLUMBING WALLS. HOLD INTERIOR GWB UP

ABOVE FINISHED SLAB MINIMUM 1/2"

GENERAL NOTE:

THE CONSTRUCTION DOCUMENTS MAY

NOTE SEVERAL ITEMS BY

MANUFACTURER.

ALL ITEMS ARE SUBJECT TO ALTERNATE

MANUFACTURER BUT MUST MEET OR

EXCEED THE PROPERTIES OF THE

MATERIAL OR PRODUCT NOTED OR

SPECIFIED AND MAY BE ACCEPTED

PENDING REVIEW AND APPROVAL BY

ARCHITECT, CONSULTANT, AND OWNER.

ADDITIONAL INFORMATION OR

DOCUMENTATION MAY BE REQUIRED TO

SUBSTANTIATE MATERIAL

/MANUFACTURER'S QUALIFICATIONS AND

ALL SUCH INFORMATION WILL BE

PROVIDED AT NO COST TO THE

ARCHITECT, CONSULTANT, AND OWNER.

20 GA.

STUD

SPACING ALLOW-

ABLE

DEFLECTION

PARTITION W/

ONE LAYER

GWB EACH

SIDE

BRACE TO

BOTTOM OF

STRUCTURE

ALLOW FOR

DEFLECTION

CEILING

REFER PLANS

PAINT FINISH

REFER FINISH

SCHEDULE

0'

6"

0' - 4 7/8"

0' - 4 7/8"

3 5/8" METAL

STUDS @

16" O.C.

5/8" TYPE X

GWB BOTH

SIDES

3 5/8" METAL

STUDS @ 16"

O.C.

5/8" TYPE X

GWB BOTH

SIDES ACOUSTICAL

BATT

INSULATION

REFER NOTES

BELOW

WALL BASE

VARIES

REFER FINISH

SCHEDULE

INTERIOR PARTITION:

3 5/8" METAL STUDS AT 16" O.C. WITH TYPE X

5/8" GWB EACH SIDE. INSULATE WALL FOR

SOUND. ALLOW FOR DEFLECTION AT HEAD.

FIRE RATED PARTITION:

3 5/8" METAL STUDS AT 16" O.C. WITH 5/8"

GWB EA. SIDE - INSULATE WALL FOR

SOUND - ALLOW FOR DEFLECTION AT

HEAD - 1 HOUR FIRE RATED - SEAL

TO DECK AND CONFORM TO UL 465

1A

1B

1C

1D

SIM. TO 1:

SIM TO 1. WITH FULL HT STUDS AND GWB

ONE SIDE - NO ACOUSTICAL INSULATION

SIM TO 1A:

2 LAYERS OF 5/8" TYPE "X" GWB BOTH SIDES,

NO ACOUSTIC INSULATION - SET RUNNERS

IN ACOUSTIC SEALANT. 2 HOUR FIRE RATED.

SEAL TO DECK.

MECH. CHASES

REFER PARTITION HEAD DETAILS FOR

ADDITIONAL INFORMATION

3 TYPICAL PLUMBING WALL:

ONE LAYER OF M.R. 5/8" TYPE "X" GWB

ON 3 5/8" METAL STUDS AT 16" O.C. -

PROVIDE F.R. WOOD BLOCKING AS

REQUIRED FOR ACCESSORIES -

PROVIDE SOUND INSULATION BATTS

INSTALL 1/2" REINFORCED CEMENT

UNDERLAYMENT BOARD BEHIND ALL

TILE ON WALLS IN LIEU OF 5/8" M.R.

GWB - REFER PLANS FOR LOCATIONS

TOILET PLUMBING WALLS

REFER PARTITION HEAD DETAILS FOR

ADDITIONAL INFORMATION

4 6" METAL STUD WALL:

5/8" TYPE "X" GWB FULL HEIGHT EITHER

SIDE OF 6" METAL STUDS AT 16" O.C. -

PROVIDE ACOUSTIC BATT INSULATION

4A 6" METAL STUD WALL:

(2) LAYERS 5/8" TYPE "X" GWB EACH

SIDE OF 6" METAL STUDS AT 16" O.C. -

PROVIDE ACOUSTIC BATT INSULATION

2 HOUR FIRE RATED - SEAL TO DECK

AND CONFORM TO UL 411

REFER PARTITION HEAD DETAILS FOR

ADDITIONAL INFORMATION

CEILING

RE: PLANS

PAINT

FINISH RE:

FINISH

SCHEDULE

BRACE TO

BOTTOM

OF

STRUCTURE

ALLOW FOR

DEFLECTION

EXTEND

GWB

FULL HT.

TO DECK

AND

SEAL

HEAD

3 5/8" STUD

@ 16" O.C.

M.R. 5/8"

GWB TYPE

X ONE SIDE

ONLY

SILL

3 5/8" STUD

@ 16" O.C.

M.R. 5 /8" GWB

TYPE X ONE

SIDE ONLY

ACOUSTICAL

BATT

INSULATION

*REFER NOTES BELOW

VARIES

PLAN

0' - 4 7/8"

0' - 4 7/32"

0' - 4 3/16"

0' - 4 1/4"

HEAD

SILL

PLAN

VARIES

VARIES

BRACE TO

BOTTOM OF

STRUCTURE

ALLOW FOR

DEFLECTION

CEILING

REFER

PLANS

PAINT FINISH

REFER

FINISH

SCHEDULE

0' - 7 1/4"

0' - 7 1/4"

6" METAL

STUDS @ 16"

O.C.

5/8" TYPE X

GWB BOTH

SIDES

6" METAL

STUDS @ 16"

O.C.

5/8" TYPE

X GWB

BOTH

SIDES

ACOUSTICAL

BATT

INSULATION

REFER

NOTES

BELOW

VARIES

0' - 7 1/4"

5 FURRING PARTITION:

3 5/8" METAL STUDS AT 16" O.C. WITH 5/8"

TYPE "X" GWB ONE SIDE.

ALLOW FOR DEFLECTION AT HEAD

ALLOW 1/4" SPACE BETWEEN STUDS AND

POURED-IN-PLACE CONCRETE WALLS -

REFER ENLARGED DETAILS

REFER PARTITION HEAD DETAILS FOR

ADDITIONAL INFORMATION

7 EXTERIOR WALL W/ MASONRY CLADDING:

MASONRY VENEER WITH 2" AIR SPACE

WITH 2 PIECE BRICK TIES AT 16" O.C.E.W.

AND STAGGERED OVER FLUID-APPLIED

AIR AND WATER BARRIER SYSTEM OVER

FIBERGLASS MAT GYPSUM ON 6"

STRUCTURAL GAUGE METAL STUDS WITH

R19 BATT INSULATION WITH FOIL FACED

VAPOR BARRIER AT INTERIOR FACE. ALL

PRODUCTS TO BE INSTALLED IN STRICT

CONFORMANCE TO ALL MFG.

RECOMMENDATIONS. WEEPS TO BE

INSTALLED AT 24" O.C.

EXTERIOR WALL AT MASONRY

REFER PARTITION HEAD DETAILS FOR

ADDITIONAL INFORMATION

SECTION 6" METAL STUDS

@ 16" O.C.

5/8" TYPE X GWB

6 EXTERIOR WALL W/ ACM CLADDING:

ACM TO BE INSTALLED OVER FLUID-

APPLIED AIR AND WATER BARRIER

SYSTEM OVER 1/2" FIBERGLASS MAT

GYPSUM ON 6" STRUCTURAL GAUGE

METAL STUDS WITH R19 BATT

INSULATION WITH FOIL FACED

VAPOR BARRIER AT INTERIOR FACE.

PROVIDE SAME MFG. MASTIC FOR

ALL THROUGH WALL FLASHING

CONDITIONS. ALL PRODUCTS TO BE

INSTALLED IN STRICT

CONFORMANCE TO ALL MFG.

RECOMMENDATIONS. PAINT FINISH

AT INTERIOR GWB FACE.

EXTERIOR WALL AT ACM

REFER PARTITION HEAD DETAILS FOR

ADDITIONAL INFORMATION

SECTION 6" METAL

STUDS @ 16"

O.C.

5/8" TYPE X

GWB

ACM PANEL

BRICK

MASONRY

VENEER

4" 6"

INSTALL M.R. GWB AT ALL LOCATIONS

FOR PLUMBING AND TOILET ROOM

WALLS - INSTALL 1/2" REINFORCED

CEMENT UNDERLAYMENT BOARD BEHIND

ALL TILE ON WALLS - REFER PLANS FOR

LOCATIONS

WRAP ALL ELECTRICAL OUTLET BOXES AT

ALL FIRE RATED WALLS WITH MOLDABLE

FIRESTOP MATERIAL - MAINTAIN FIRE

RATINGS

ALL PENETRATIONS THRU FIRE RATED

WALL ASSEMBLIES MUST BE

FIRESTOPPED TO MAINTAIN FIRE RATING

IN ACCORDANCE TO UL REQUIRMENTS

RUNNERS TO BE SET IN BED OF

ACOUSTIC SEALANT AT ALL RUNNERS

PROVIDE ACOUSTICAL INSULATION AT ALL

LOCATIONS IN BUILDING CORE.

HOLD BOTTOM OF INTERIOR 5/8" TYPE "X"

GWB UP 1/2" MAX. ABOVE CONCRETE.

1' - 0 21/32"

R-19 FOIL FACED

INSULATION

2" AIR SPACE

1/2" FIBERGLASS

MAT GYPSUM

SHEATHING

0' - 3 5/8"

0' - 1 15/16" HOLD 0' - 7 3/32"

WATER-

PROOFING

MEMBRANE

SHOWN DASHED

WATER-

PROOFING

MEMBRANE

SHOWN

DASHED

1/2"

FIBERGLASS

MAT GYPSUM

SHEATHING

7A EXTERIOR WALL W/ MASONRY CLADDING:

MASONRY VENEER WITH 1" AIR SPACE

WITH 2 PIECE BRICK TIES AT 16" O.C.E.W.

AND STAGGERED OVER FLUID-APPLIED

AIR AND WATER BARRIER SYSTEM OVER

1" RIGID INSULATION OVER 8" POURED-IN-

PLACE CONCRETE WALL. INTERIOR

FURRING AND INSULATION PER PLANS.

ALL PRODUCTS TO BE INSTALLED IN

STRICT CONFORMANCE TO ALL MFG.

RECOMMENDATIONS. WEEPS TO BE

INSTALLED AT 24" O.C.

PLAN

CEILING

RE: PLANS

PAINT

FINISH RE:

FINISH

SCHEDULE

BRACE TO

BOTTOM

OF

STRUCTURE

ALLOW FOR

DEFLECTION

EXTEND GWB

FULL HT.

TO DECK

AND

SEAL

HEAD

1"

SHAFT

LINER

SHAFT

SIDE

1 1/2" STUD

@ 16" O.C.

2 LAYERS

5/8" GWB

TYPE X

PUBLIC

SIDE

SILL

1 1/2" STUD

@ 16" O.C.

2 LAYERS

5/8" GWB

TYPE X

PUBLIC

SIDE

ACOUSTICAL

BATT

INSULATION

*REFER NOTES BELOW

VARIES

2 TYPICAL CHASE WALL:

1" X 24" TYPE "X" GWB ON 1 1/2" FLOOR AND

CEILING J RUNNERS WITH TAB FLANGE 1

1/2" STEEL I STUDS BETWEEN PANELS -

PUBLIC FACE TWO LAYERS OF 5/8" TYPE "X"

GWB - PROVIDE SOUND INSULATION

BATTS - CONFORMS TO UL498 - TWO HOUR

RATED SHAFT WALL CONSTRUCTION.

1"

SHAFT

LINER

SHAFT

SIDE

1"

SHAFT

LINER

SHAFT

SIDE

2 LAYERS 5/8"

GWB TYPE X

PUBLIC SIDE

0' - 3 3/4"

4B 6" METAL STUD WALL:

(1) LAYER 5/8" TYPE "X" GWB AT ROOM

SIDE OF 6" METAL STUDS AT 16" O.C. -

PROVIDE ACOUSTIC BATT INSULATION

6A INTERIOR WALL W/ ACM CLADDING:

ACM INSTALLED OVER 1/2"

FIBERGLASS MAT GYPSUM ON 3 5/8"

STRUCTURAL GAUGE METAL STUDS

WITH R19 BATT INSULATION . ALL

PRODUCTS TO BE INSTALLED IN

STRICT CONFORMANCE TO ALL MFG.

RECOMMENDATIONS. PAINT FINISH AT

GWB FACE.

SIM TO 5:

AT CURTAIN WALL SPANDREL PANELS.

GWB ON ROOM SIDE ONLY WITH BATT

INSULATION AND SOLID SURFACE SILL -

SET RUNNERS IN ACOUSTIC SEALANT

6B SIM TO 6:

ACM INSTALLED OVER 1/2"

FIBERGLASS MAT GYPSUM ON 6"

STRUCTURAL GAUGE METAL STUDS.

5/8" TYPE X GWB INSTALLED ON 2 1/2"

METAL STUDS AT INTERIOR FACE.

F.O. STUD TO GRID TYP.

0' - 10 1/2" F.O. STUD TO GRID TYP.

0' - 10 1/2"

0' - 9 3/16"

CEILING

RE: PLANS

PAINT FINISH

RE:

FINISH

SCHEDULE

BRACE TO

BOTTOM

OF STRUCTURE

ALLOW FOR

DEFLECTION

EXTEND GWB 6"

ABOVE FIN. CLG.

HEAD

3 5/8" STUD @

16" O.C.

5/8" GWB TYPE

X ONE SIDE

ONLY

SILL

3 5/8" STUD

@ 16" O.C. 5 /8" GWB TYPE

X ONE SIDE

ONLY

ACOUSTICAL

BATT

INSULATION

REFER FINISH

SCHED.

PLAN

0' - 4 7/32"

0' - 4 3/16"

0'

6"

5A FURRING PARTITION:

7/8" FURRING CHANNELS AT 16" O.C. WITH

5/8" TYPE "X" GWB ONE SIDE.

5B

SIM. TO 1:

1 LAYER OF 5/8" TYPE "X" GWB BOTH

SIDES TERMINATING 6" ABOVE FINISHED

CEILING, WITH ACOUSTICAL INSULATION

1E

NOTE: ALL PARTITION TYPES TO HAVE ALTERNATING STUD KICKERS

FOR LATERAL BRACING EXTENDING TO STRUCTURE AT 48" O.C.

4C 6" METAL STUD WALL:

(1) LAYER 5/8" TYPE "X" GWB SEALED

TO DECK AT CORRIDOR SIDE OF 6"

METAL STUDS AT 16" O.C. - NO

ACOUSTIC BATT INSULATION

TENANT IMPROVEMENT:

1 LAYER OF 5/8" TYPE "X" GWB

INSTALLED TO DECK WITH ACOUSTICAL

BATTS ON TENANT SIDE OF EXISTING

WALL FRAMING

1F

4D TENANT IMPROVEMENT:

(1) LAYER OF 5/8" TYPE "X" GWB INSTALLED

TO DECK WITH ACOUSTICAL BATTS ON

TENANT SIDE OF EXISTING WALL FRAMING

4E 6" METAL STUD WALL - SOUND PARTITION:

5/8" TYPE "X" GWB FULL HEIGHT ON 1/2"

RESILIENT FURRING CHANNELS BOTH SIDES

OF 6" METAL STUDS AT 16" O.C. - PROVIDE

ACOUSTIC BATT INSULATION

SIM. TO 1:

2 LAYERS OF 5/8" TYPE "X" GWB EACH

SIDE OF STUDS INSTALLED TO DECK

WITH ACOUSTICAL BATTS - NOT FIRE

RATED

1G 5C FURRING PARTITION:

1 5/8" METAL STUDS AT 16" O.C. WITH 5/8"

TYPE "X" GWB ONE SIDE.

ALLOW FOR DEFLECTION AT HEAD

0' - 4 3/16"

ANCHOR TO UNDERSIDE OF

STRUCTURE WITH 3" NO. 3

TAPCON OR EQUAL AT 20"

O.C.

PROVIDE CONTINUOUS TYPE

II SILICONE AT PLYWOOD

FINISH FLOOR INTERSECT

1/ 2"

R-13 BATT

INSULATION WITH

FOIL SCRIM TO

OCCUPANT SIDE.

FUNCTION FIT ALL

JOINTS TAPED WITH

3M UL39 TAPE

20 GA. COLD

FORMED METAL

FRAMING AT 16"

O.C.

1/ 2"

6' - 0"

CLIP CEILING TO NEW

FRAMING AS REQUIRED

INCLUDING SUSPENDED

CEILING TO TRACK

EXISTING

CLIP CEILING TO NEW

FRAMING AS REQUIRED

INCLUDING SUSPENDED

CEILING TO TRACK

EXISTING

3/4" ASTM E84

FRT PLYWOOD

CONSTRUCT 3'-0"x 7'-0"

DOOR IN TEMPORARY

PARTITION. INCLUDE

PANIC DEVICE FOR

EMERGENCY EGRESS

ONLY

3/4" ASTM E84

FRT PLYWOOD

CONSTRUCT 3'-0"x 7'-0"

DOOR IN TEMPORARY

PARTITION. INCLUDE

PANIC DEVICE FOR

EMERGENCY EGRESS

ONLY

HEAVY DUTY

WALK-OFF MAT

HEAVY DUTY

WALK-OFF MAT

NOTE: CONTRACTOR TO ISOLATE AREA

OF CONSTRUCTION BY PROVIDING A

TEMPORARY PARTITION TO PRECLUDE

DUST, FUMES AND ODORS FROM

ENTERING OCCUPIED AREAS.

RELOCATE EXISTING EXIT

SIGN TO INSIDE TEMPORARY

PARTITION OCCUPANT SIDE-

CONTINUED ILLUMINATION AS

REQUIRED

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

2/10/2022

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

SubmissionARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

BI

M

R en ov at e Ey e C lin ic

A

C S

Pr im ar y

C ar e/ R en ov at e

Ey e

C lin ic

A C

S Pr im ar y C ar e_ de ta ch ed

.rv t

2/

/2

:0 7:

A

M

G-003

PARTITION TYPES

PRIME ARCHITECTS

212 N. CRAWFORD AVE

NORMAN, OK. 73069

(866) 226-8071

GENE LAVASTIDA

RENOVATE EYE CLINIC AND ACS

PRIMARY CARE

6010 AMARILLO BLVD. WEST, AMARILLO TX 79106

504-21-110

SCOTT HOBBS COR

02/09/2022 CM DT

Thomas E.

Creek VA

Medical Center

100% FINAL BID

DOCUMENTS

SCALE: 1/2" = 1'-0"

2 TEMPORARY PARTITION

A LABEL CLASS A DOOR

A/C AIR CONDITION

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAMA AMERICAN ARCHITECTURAL

MANUFACTURERS ASSOCIATION

AB ANCHOR BOLT

ABC AGGREGATE BASE COURSE

AC ASBESTOS CEMENT OR

ASPHALTIC CONCRETE

ACI AMERICAN CONCRETE INSTITUTE

ACS DR ACCESS DOOR

ACS FLR ACCESS FLOOR

ACS PNL ACCESS PANEL

ACST ACOUSTIC

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES

ADB AUTOMATIC DOOR BOTTOM

ADC AUTOMATIC DOOR CLOSER

ADDL ADDITIONAL

ADDN ADDITION

ADH ADHESIVE

ADJ ADJACENT, ADJOINING, OR

ADJUSTABLE

ADMIN ADMINISTRATION

ADO AUTOMATIC DOOR OPERATOR

AF ACCESS FLOORING

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFS ABOVE FINISHED SLAB

AGA AMERICAN GAS ASSOCIATION

AGC ASSOCIATED GENERAL

CONTRACTORS

AGGR AGGREGATE

AHJ AUTHORITY HAVING JURISDICTION

AHR ANCHOR

AHU AIR HANDLING UNIT

AIA AMERICAN INSTITUTE OF

ARCHITECTS

AISC AMERICAN INSTITUTE OF STEEL

CONSTRUCTION

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

ALUM ALUMINUM

AMP AMPERE

AMT AMOUNT

ANOD ANODIZE

ANSI AMERICAN NATIONAL STANDARDS

INSTITUTE

ANT ANTENNA

APA AMERICAN PLYWOOD

ASSOCIATION

APPD APPROVED

APPROX APPROXIMATE

APT APARTMENT

AR AS REQUIRED

ARCH ARCHITECT

ASB ASBESTOS

ASI ARCHITECT'S SUPPLEMENTAL

INSTRUCTION

ASKLR AUTOMATIC SPRINKLER

ASPH ASPHALT

ASSN ASSOCIATION

ASTM AMERICAN SOCIETY FOR TESTING

AND MATERIALS

AT (SP) ACOUSTICAL CEILING

(WITH SPRAYED PLASTIC FINISH)

ATCH ATTACHMENT

ATM AUTOMATIC TELLER MACHINE

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AVE AVENUE

AVG AVERAGE

AW ACID WASTE

AWI ARCHITECTURAL WOODWORKING

INSTITUTE

AWPA AMERICAN WOOD PRESERVERS'

ASSOCIATION

AWS AMERICAN WELDING SOCIETY

AWT ACOUSTICAL WALL TREATMENT

B LABEL CLASS B DOOR

B PL BASE PLATE

BALC BALCONY

BAT BATTEN

BB BULLETIN BOARD

BD BOARD

BD FT BOARD FEET (FOOT)

BEV BEVEL

BHMA BUILDER'S HARDWARE

MANUFACTURER'S ASSOCIATION

BI FLD DR BIFOLDING DOORS

BIM BUILDING INFORMATION MODEL

BITUM BITUMINOUS

BK BRICK

BKG BACKING

BLD BUILD

BLDG BUILDING

BLKT BLANKET

BLVD BOULEVARD

BM BEAM OR BENCHMARK

BOT BOTTOM

BR BEDROOM

BRCG BRACING

BRDG BRIDGING

BRDG JST BRIDGING JOIST

BRG BEARING

BRG PL BEARING PLATE

BRKT BRACKET

BRZ BRONZE

BSMT BASEMENT

BTWN BETWEEN

BU BUSHEL

BUR BUILT-UP ROOFING

C CELSIUS OR CHANNEL

C CONC CAST CONCRETE

C LABEL CLASS C DOOR

C TO C CENTER TO CENTER

CAB CABINET

CAC CEILING ATTENUATION CLASS

CB CATCH BASIN OR CORNER BEAD

CBB CEMENTITIOUS (BACKER) BOARD

CC CUBIC CENTIMETER

CCTV CLOSED CIRCUIT TELEVISION

CCW COUNTERCLOCKWISE

CD CONSTRUCTION DOCUMENTS OR

CONTRACT DOCUMENTS

CEM CEMENT

CEM PLAS CEMENT PLASTER

CER CERAMIC

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR

FURNISHED/CONTRACTOR

INSTALLED

CF/OI CONTRACTOR

FURNISHED/OWNER INSTALLED

CFLG COUNTERFLASHING

CFM CUBIC FEET PER MINUTE

CFMF COLD-FORMED METAL FRAMING

CFS CUBIC FEET PER SECOND

CG CENTER OF GRAVITY OR CORNER

GUARD

CGSFU CERAMIC GLAZED STRUCTURAL

FACING UNITS

CH BD CHALKBOARD

CHEM CHEMICAL

CHFR CHAMFER

CHK CHECK

CI CAST IRON

CIP CAST-IN-PLACE

CIR CIRCLE

CIRC CIRCULAR

CJ CONSTRUCTION JOINT OR

CONTROL JOINT

CL CENTER LINE

CLDG CLADDING

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CM² SQUARE CENTIMETER

CM³ CUBIC CENTIMETER

CM CONSTRUCTION MANAGEMENT

CMU CONCRETE MASONRY UNIT

CNR CORNER

CNTR COUNTER

CO CARBON MONOXIDE,

CERTIFICATE OF OCCUPANCY,

CLEANOUT, OR COMPANY

CO₂ CARBON DIOXIDE

COL COLUMN

COM COMMON

COMB COMBINATION, COMBINED

COMM COMMUNICATION

COMP COMPONENT

CONC CONCRETE

CONC FLR CONCRETE FLOOR

COND CONDENSER OR CONDITION

CONF CONFERENCE

CONN CONNECT

CONSTR CONSTRUCTION

CONT CONTINUE OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

CORR CORRIDOR

CP CARPET (WITHOUT CUSHION

BROADLOOM)

CPM CRITICAL PATH METHOD

CPRS COMPRESSIBLE

CPT CARPET TILE

CRS COLD ROLLED STEEL

CRSI CONCRETE REINFORCING STEEL

INSTITUTE

CSB CONCRETE SPLASH BLOCK

CSG CASING

CSI CONSTRUCTION SPECIFICATIONS

INSTITUTE

CSK COUNTER SINK

CSMT CASEMENT

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTF CERAMIC TILE FLOOR

CTG COATING

CTR CENTER OR CONTOUR

CTRL CONTROL

CTV CABLE TELEVISION

CU COPPER C

CU FT CUBIC FEET

CU IN CUBIC INCHES

CU YD CUBIC YARD

CURT CURTAIN

CYL CYLINDER

CYL L CYLINDER LOCK

D DEPTH OR PENNY (NAIL)

D LABEL CLASS D DOOR

DAT DATUM

DB DECIBEL

DBL DOUBLE

DBL GLZ DOUBLE GLAZE

DC DIRECT CURRENT

DEG DEGREE

DEL DELETE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL OR DIAGRAM

DIFF DIFFERENCE OR DIFFUSER

DIM DIMENSION

DIR DIRECTION

DISP DISPENSER

DIST DISTANCE

DIV DIVIDE OR DIVISION

DL DEAD LOAD

DN DOWN

DOC DOCUMENT

DOUG FIR DOUGLAS FIR

DOZ DOZEN

DR DOOR, DRAIN, DRESSING ROOM,

OR DRIVE

DR CL DOOR CLOSER

DR FR DOOR FRAME

DR OPNG DOOR OPENING

DS DOWNSPOUT

DSGN DESIGN

DW DISHWASHER

DWG DRAWING

DWTR DUMBWAITER

E EAST

E LABEL CLASS E DOOR

EA EACH

EFF EFFICIENCY

EFS EXTERIOR FINISH SYSTEM

EFTR EXISTING FINISH TO REMAIN

EIFS EXTERIOR INSULATION AND

FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELAST ELASTOMERIC

ELEC ELECTRIC

ELEC DR OP ELECTRIC DOOR OPENER

ELEV ELEVATOR

EMER EMERGENCY

EMER SHR EMERGENCY SHOWER

ENCL ENCLOSURE

ENGR ENGINEER

ENVIR ENVIRONMENT

EPA ENVIRONMENTAL PROTECTION

AGENCY

EPDM ETHYLENE PROPYLENE DIENE

MONOMER

EPO EMERGENCY POWER OFF

EPS EXPANDED POLYSTYRENE BOARD

(INSULATION)

EPY EPOXY FLOORING

EQ EQUAL

EQL SP EQUALLY SPACED

EQUIP EQUIPMENT

EQUIV EQUIVALENT

ERD EXISTING ROOF DRAIN

ESC ESCAPE OR ESCUTCHEON

ESCAL ESCALATOR

ESMT EASEMENT

ESP ESPECIALLY

EST ESTIMATE

ETC AND SO FORTH OR ET CETERA

EW EACH WAY

EWC ELECTRIC WATER COOLER

EWS EYE WASH STATION

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION OR EXPOSED

EXP BT EXPANSION BOLT

EXST GR EXISTING GRADE

EXT EXTERIOR, EXTERNAL, OR

EXTINGUISHER

EXT GR EXTERIOR GRADE

F FAHRENHEIT OR FEMALE

FA FIRE ALARM

FAB FABRIC

FAC FACTOR

FACIL FACILITY

FAS FASCIA

FAS BD FASCIA BOARD

FCO FLOOR CLEANOUT

FCTY FACTORY

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDIM FINISH DIMENSION

FDTN FOUNDATION

FDVB FIRE DEPARTMENT VALVE BOX

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FF&E FURNITURE, FIXTURE, AND

EQUIPMENT

FH FLAT HEAD OR FLAT HEAD

SCREWS

FHC FIRE HOSE CABINET

FHMS FLAT HEAD MACHINE SCREW

FIG FIGURE

FIL FILLET

FIN FINISH OR FINISHED

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIN WD FINISH WOOD

FIXT FIXTURE

FL FLOORLINE

FLASH FLASHING

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLR FLOOR

FLR FIN FLOOR FINISH

FLR SK FLOOR SINK

FLUOR FLUORESCENT

FLUOR FIX FLUORESCENT FIXTURE

FM FACTORY MUTUAL

FM-G FACTORY MUTUAL GLOBAL

FO FINISH OPENING

FOC FACE OF CONCRETE OR FACE OF

CURB

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF SLAB OR FACE OF STUD

FOUNT FOUNTAIN

FOW FACE OF WALL

FP FIRE PROTECTION OR FIREPROOF

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FIRE RATING, FIRE RESISTANT, OR

FRAME

FR SNK FLUSHING RIM SINK

FREQ FREQUENCY

FRMG FRAMING

FRP FIBER REINFORCED POLYESTER

OR FIBERGLASS REINFORCED

PLASTIC

FRZ FREEZER

FS FEDERAL SPECIFICATION

FSTNR FASTENER

FT FEET OR FOOT

FTG FOOTING

FURG FURRING

FURN FURNISH OR FURNITURE

FUT FUTURE

FWC FABRIC WALLCOVERING

GA GAUGE OR GYPSUM ASSOCIATION

GAL GALLON

GALV GALVANIC OR GALVANIZED

GALV STL GALVANIZED STEEL

GB GRAB BAR

GC GENERAL CONTRACTOR

GD GUARD

GDR GUARD RAIL

GEN GENERAL OR GENERATOR

GFRC GLASS-FIBER-REINFORCED

CONCRETE

GFRG GLASS-FIBER-REINFORCED

GYPSUM

GFRP GLASS-FIBER-REINFORCED

PLASTIC

GI GALVANIZED IRON

GL GLASS (GLAZING)

GL BLK GLASS BLOCK

GLU LAM GLUED LAMINATED WOOD

GR FL GROUND FLOOR

GRAN GRANITE

GRTG GRATING

GSB GYPSUM SHEATHING BOARD

GSM GALVANIZED SHEET METAL

GSU GLAZED STRUCTURAL UNIT

GT GROUT

GUAR GUARANTEE

GUT GUTTER

GWB GYPSUM WALLBOARD SYSTEMS

GYP GYPSUM

GYP BD GYPSUM BOARD

GYP PLAS GYPSUM PLASTER

H HIGH

H PLAM HIGH PRESSURE PLASTIC

LAMINATE

HAZ MAT HAZARDOUS MATERIALS

HB HOSE BIBB

HC HOLLOW CORE

HCWD HOLLOW CORE WOOD DOOR

HDBD HARDBOARD

HDNR HARDENER

HDO HIGH DENSITY OVERLAY

HDR HEADER

HDW HARDWARE

HDWD HARDWOOD

HEPA HIGH EFFICIENCY PARTICULATE

AIR (FILTER)

HEX HEXAGON

HF HIGH FREQUENCY

HGR HANGER

HM HECTOMETER OR HOLLOW METAL

HMD HOLLOW METAL DOOR

HMDF HOLLOW METAL DOOR AND

FRAME

HMF HOLLOW METAL FRAME

HNDRL HANDRAIL

HO HOLD OPEN

HORIZ HORIZONTAL

HOSP HOSPITAL

HP HIGH PRESSURE OR

HORSEPOWER

HQ HEADQUARTERS

HS HEAT-STRENGTHENED (GLASS)

OR HIGH STRENGTH OR

HORIZONTAL IN SPLASH

HSE HOUSE

HSKPG HOUSEKEEPING

HST HOIST

HT HEIGHT

HVAC HEATING, VENTILATING, AND AIR

CONDITIONING

HVY HEAVY

HW HOT WATER

HYD HYDRANT

HYDR HYDRAULIC

I INTERSTATE (HIGHWAY) OR

MOMENT OF INERTIA

IAQ INDOOR AIR QUALITY

IBC INTERNATIONAL BUILDING CODE

ICU INTENSIVE CARE UNIT

ID IDENTIFICATION, INSIDE

DIAMETER, OR INTERIOR DESIGN

ID NO IDENTIFICATION NUMBER

ILLUM ILLUMINATION

INCL INCLUDED

IND INDEPENDENT OR INDUSTRIAL

INFO INFORMATION

INSUL INSULATION

INT INTERIOR

INTERCOM INTERCOMMUNICATION

INTL INTERNATIONAL

IRMA INVERTED ROOF MEMBRANE

ASSEMBLY

ITC INSTALLED THIS CONTRACT

IWH INSTANTANEOUS WATER HEATER

J JANITOR

J-BOX JUNCTION BOX

KD KILN DRIED OR KNOCKED DOWN

KIT KITCHEN

KO KNOCKOUT

KPL KICKPLATE

KS KNEE SPACE

L ANGLE

LAB LABORATORY

LAD LADDER

LAM LAMINATE

LAM GL LAMINATED GLASS

LAU LAUNDRY

LAV LAVATORY

LBR LUMBER

LBS POUND

LD BRG LOAD-BEARING

LDR LEADER

LED LIGHT EMITTING DIODE

LH LEFT HAND

LHR LEFT HAND REVERSE OR LATENT

HEAT RATIO

LIB LIBRARY

LIN LINEAR

LINO LINOLEUM

LIQ LIQUID

LKR LOCKER

LKR RM LOCKER ROOM

LKWASH LOCKWASHER

LL LEAD LINED

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LMST LIMESTONE

LNDSCP LANDSCAPE

LR LIVING ROOM

LRG LARGE

LRV LOUVERED ROOF VENT

LS LUMP SUM

LT LIGHT

LT GA LIGHT GAGE

LT WT LIGHTWEIGHT

LTG LIGHTING

LTNG LIGHTNING

LVD LOUVERED

LVR LOUVER

LWC LIGHTWEIGHT CONCRETE

LWIC LIGHTWEIGHT INSULATING

CONCRETE

LYR LAYER

MACH MACHINE

MACH RM MACHINE ROOM

MAINT MAINTENANCE

MAN MANUAL

MATL MATERIAL

MATV MASTER ANTENNA TELEVISION

SYSTEM

MAX MAXIMUM

MB MACHINE BOLT

MCB METAL CORNER BEAD

MD DECK

ME MECHANICAL ENGINEER

MEAS MEASURE

MECH MECHANICAL

MECH RM MECHANICAL ROOM

MED MEDICAL OR MEDIUM

MEK METHYL ETHYL KETONE

MEL MELAMINE

MEMB MEMBRANE

MEMO MEMORANDUM

MEZZ MEZZANINE

MF MILL FINISH

MFD MANUFACTURED

MFG MANUFACTURING

MFR MANUFACTURER

MFR REC MANUFACTURER'S

RECOMMENDATION

MGT MANAGEMENT

MH MANHOLE

MIC MICROPHONE

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM OR MINUTE

MIRR MIRROR

MISC MISCELLANEOUS

MIT MITER

MKR MARKER

ML METAL LATH

MLDG MOLDING (MOULDING)

MLWK MILLWORK

MM MILLIMETER

MO MASONRY OPENING OR

MOTOR OPERATED

MOD MODEL, MODIFY, OR MODULE

MOD BIT MODIFIED BITUMEN

MON MONITOR

MOPR MOP RACK

MR MOISTURE RESISTANT

MS MACHINE SCREW OR MOP SINK

MTD MOUNTED

MTG MOUNTING

MTL METAL

MULL MULLION

MW MICROWAVE

MWP MEMBRANE WATERPROOFING

N NORTH

NA NOT APPLICABLE

NAAMM NATIONAL ASSOCIATION OF

ARCHITECTURAL METAL

MANUFACTURERS

NAT NATURAL

NATL NATIONAL

NC NOISE CRITERIA

NCOMBL NONCOMBUSTIBLE

NEC NATIONAL ELECTRICAL CODE

NEG NEGATIVE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUT NEUTRAL

NFC NATIONAL FIRE CODE

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NR NOISE REDUCTION

NRC NOISE REDUCTION COEFFICIENT

NRCA NATIONAL ROOFING

CONTRACTORS ASSOCIATION

NRP NON-REMOVABLE

NS NARROW STILE

NTS NOT TO SCALE

NUM NUMERAL

O/O OUT TO OUT

O OXYGEN

OA OUTSIDE AIR OR OVERALL

OC ON CENTER

OCC OCCUPY

OCT OCTAGON

OD OUTSIDE DIAMETER OR OUTSIDE

DIMENSION

OF/CI OWNER FURNISHED/

CONTRACTOR INSTALLED

OFD OVERFLOW DRAIN

OFF OFFICE

OF/OI OWNER FURNISHED/ OWNER

INSTALLED

OH OVERHANG

OH DR OVERHEAD (COILING) DOOR

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

OPT OPTIONAL

OR OPERATING ROOM OR OUTSIDE

RADIUS

ORD ORDINANCE OR OVERFLOW ROOF

DRAIN

ORG ORGANIC

ORIG ORIGINAL

ORN ORNAMENTAL

OSHA OCCUPATIONAL SAFETY AND

HEALTH ADMINISTRATION

OUT OUTLET

OZ OUNCE

PAR PARALLEL OR PARAPET

PARA PARAGRAPH

PART PARTIAL

PAT PATTERN

PB PUSHBUTTON

PBD PARTICLEBOARD

PC PIECE, POLYCARBONATE OR

PORTLAND CEMENT

PCA PORTLAND CEMENT ASSOCIATION

PCC PRECAST CONCRETE

PCCP CONCRETE PAVEMENT

PCD PAPER CUP DISPENSER

PCF POUNDS PER CUBIC FOOT

PCP PORTLAND CEMENT PLASTER

PD PLAN DIMENSION

PED PEDESTAL

PEN PENETRATE

PEND PENDANT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PGBD PEGBOARD

PHAR PHARMACY

PHOTO PHOTOGRAPH

PHS PHILLIPS HEAD SCREW

PKG PACKAGE

PL PROPERTY LINE

PL GL PLATE GLASS

PLAM PLASTIC LAMINATE

PLAS PLASTER OR PLASTIC

PLBG PLUMBING

PLYWD PLYWOOD

PMTL PAINTED METAL

PNEU PNEUMATIC

PNL PANEL

PO POST OFFICE OR PURCHASE

ORDER

POLY POLYETHYLENE (PLASTIC)

PORCT PORCELAIN TILE

PR PAIR

PRB PROFILE BASE

PRCST PRECAST

PREFAB PREFABRICATE

PREFIN PREFINISH

PRELIM PRELIMINARY

PREP PREPARATION

PRESS PRESSURE

PREV PREVIOUS

PRKG PARKING

PRMLD PREMOLDED

PROJ PROJECT

PROP PROPERTY

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT, PNEUMATIC TUBE, OR

PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PVC POLYVINYL CHLORIDE (PLASTIC)

PVG PAVING

PWR POWER

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QRY QUARRY

QT QUARRY TILE

QTB QUARRY TILE BASE

QTF QUARRY TILE FLOOR

QTR QUARTER

QTY QUANTITY

QUAD QUADRANT

QUAL QUALITY

R RADIUS OR RISER

RA RETURN AIR

RAD RADIATOR

RAF RESILIENT ATHLETIC FLOORING

RB RESILIENT BASE (RUBBER OR

VINYL WITH FACTORY FORMED

INSIDE AND OUTSIDE CORNERS)

RB HK ROBE HOOK

RBM REINFORCED BRICK MASONRY

RBR RUBBER

RCP REFLECTED CEILING PLAN

RCVR RECEIVER

RD ROAD OR ROOF DRAIN

REC RECESSED

RECD RECEIVED

RECPT RECEPTACLE

RECT RECTANGLE

REF REFERENCE OR REFRIGERATOR

REFR REFRACTORY OR REFRIGERATION

REG REGISTER

REINF REINFORCE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RES RESINOUS FLOORING

RES-W RESINOUS/EPOXY WALL/CEILING

RESIL RESILIENT

RET RETURN

REV REVISE OR REVISION

RF RADIO FREQUENCY OR RUBBER

FLOORING

RFG ROOFING

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

RH RIGHT HAND

RHMS ROUND HEAD MACHINE SCREW

RHR RIGHT HAND REVERSE

RHWS ROUND HEAD WOOD SCREW

RL ROOF LEADER

RLG RAILING

RM ROOM

RND ROUND

RO ROUGH OPENING

ROW RIGHT OF WAY

RPM REVOLUTIONS PER MINUTE

RS ROUGH SAWN

RSF RESILIENT SHEET FLOORING

(CHEMICALLY WELDED SEAMS)

RT RIGHT

RV ROOF VENT

RVS REVERSE

RWD REDWOOD

RWL RAIN WATER LEADER

S SOLID SURFACE

SA SUPPLY AIR

SALV SALVAGE

SAMP SAMPLE

SAN SANITARY

SAT SUSPENDED ACOUSTICAL TILE

SATC SUSPENDED ACOUSTICAL TILE

CEILING

SB SPLASH BLOCK

SBS STYRENE BUTADIEN STYRENE

SBSTR SUBSTRATE

SC SHADING COEFFICIENT OR SOLID

CORE OR HIGH BUILD GLAZED

COATING (SPECIAL COATING)

SCH SCHOOL

SCHED SCHEDULE

SCHEM SCHEMATIC

SCP SCUPPER

SCRN SCREEN

SCT STRUCTURAL CLAY TILE

SCWD SOLID CORE WOOD DOOR

SD SHOP DRAWINGS, SMOKE

DETECTOR OR SOAP DISPENSER

OR STATIC DISSIPATIVE

SDG SIDING

SECT SECTION

SEG SEGMENT

SEL SELECT

SEP SEPARATE

SF SQUARE FOOT (FEET)

SFTWD SOFTWOOD

SGD SLIDING GLASS DOOR

SGL SINGLE

SHR SHOWER

SHR HD SHOWER HEAD

SHRD SHOWER DRAIN

SHT SHEET

SHT MTL FLASH SHEET METAL FLASHING

SHTHG SHEATHING

SHV SHELVING

SIM SIMILAR

SJ SCORED JOINT

SJI STEEL JOIST INSTITUTE

SK SKETCH

SKLT SKYLIGHT

SLD WDW HORIZONTAL SLIDING WINDOW

SLDG SLIDING

SLNT SEALANT

SM SHEET METAL

SMK SMOKE

SND SANITARY NAPKIN DISPENSER

SND INS SOUND INSULATION

SNDU SANITARY NAPKIN DISPOSAL UNIT

SP SPECIAL FACED

SPEC SPECIFICATION

SPKLR SPRINKLER

SPKR SPEAKER

SPLY SUPPLY

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SANITARY SEWER OR SERVICE

SINK

SST STAINLESS STEEL

ST STAIRS OR STREET OR STONE

(CAST)

STC SOUND TRANSMISSION CLASS

STD STANDARD

STIF STIFFENER

STL JST STEEL JOIST

STL LNTL STEEL LINTEL

STL PL STEEL PLATE

STL RF DK STEEL ROOF DECK

STL TB STEEL TUBE

STL TR STEEL TRUSS

STNLS STAINLESS

STOR STORAGE

STR STRINGERS

STRUCT STRUCTURAL

STRUCT STL STRUCTURAL STEEL

SUB SUBSTITUTE

SURF SURFACE

SUSP SUSPEND

SUSP CLG SUSPENDED CEILING

SV SHEET VINYL

SVT SOLID VINYL FLOOR TILE (LUXURY

VINYL TILE)

SW SWITCH

SWDR SWING DOOR

SYM SYMBOL

SYNTH SYNTHETIC

SYS SYSTEM

T TREAD

T&G TONGUE AND GROOVE

T&M TIME AND MATERIALS

TB THROUGH BOLT OR TOWEL BAR

TCA TILE COUNCIL OF AMERICA

TCP TELEPHONE CONTROL PANEL

TEMPERATURE OR TRAFFIC

CONTROL PLAN

TD TOWEL DISPENSER

TECH TECHNICAL

TEL TELEPHONE

TEMP TEMPERATURE OR TEMPORARY

TER TERRAZZO, POURED

THD THREAD

THERM THERMAL

THK THICKNESS

THRES THRESHOLD

THRU THROUGH

THRUOUT THROUGHOUT

TK BD TACKBOARD

TMPD TEMPERED

TMPD GL TEMPERED GLASS

TN TRUE NORTH

TO OF ____

TO FDN TOP OF FOUNDATION

TOB TOP OF BEAM

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOS TOP OF STEEL

TOW TOP OF WALL

TPD TOILET PAPER DISPENSER

TPH TOILET PAPER HOLDER

TR TOWEL RACK

TRANS TRANSOM

TRANS WD FIN TRANSPARENT WOOD FINISH

TRTD TREATED

TS TENSILE STRENGTH OR TUBE

STEEL

TSTAT THERMOSTAT

TT TERRAZZO TILE (PLASTIC MATRIX)

TV TELEVISION

TYP TYPICAL

U HEAT TRANSFER COEFFICIENT

UC UNDERCUT

UCD NDERCUT DOOR

UCR UNDER COUNTER REFRIGERATOR

UCT UNDER COUNTER

UGND UNDERGROUND

UL UNDERWRITERS LABORATORIES

ULT ULTIMATE

UNFIN UNFINISH

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER

SUPPLY

UR URINAL

UTIL UTILITY

UV ULTRAVIOLET

V VOLT

VAC VACUUM

VAR VARIES

VCT VINYL COMPOSITE TILE OR

VITRIFIED CLAY TILE

VEH VEHICLE

VENT VENTILATION

VERT VERTICAL

VEST VESTIBULE

VFAT VINYL FACED ACOUSTICAL TILE

VIC VICINITY

VID VIDEO

VIF VERIFY IN FIELD

VNR VENEER

VOC VOLATILE ORGANIC COMPOUND

VOL VOLUME

VOLT VOLTAGE

VP VENEER PLASTER

VR VAPOR RETARDER

VTR VENT THROUGH ROOF

VWC VINYL WALL COVERING

VWF VINYL WALL FABRIC

W WIDE OR WEST

W/ WITH

W/O WITHOUT

WARR WARRANTY

WBL WOOD BLOCKING

WC WALL COVERING OR WATER

CLOSET

WC WL HNG WATER CLOSET, WALL HUNG

WCHR WATER CHILLER

WCL WL MTD WATER COOLER, WALL HUNG

WD WOOD

WDW WINDOW

WF WIDE FLANGE

WFAB WALL FABRIC

WFR WOOD FRAME

WFS WOOD FURRING STRIPS

WH WATER HEATER

WHSE WAREHOUSE

WLD WELDED

WM WIRE MESH

WP WATERPROOFING

WPD WATER PRESSURE DROP

WPM WATERPROOF MEMBRANE

WR WEATHER RESISTANT

WS WEATHERSTRIP

WSCT WAINSCOT

WSF WELDED SEAM SHEET FLOORING

(HEAT WELDED WITH ROD)

WT WEIGHT

WWF WELDED WIRE FABRIC

X BRACE CROSS BRACE

XPS EXTRUDED POLYSTYRENE

BOARD (INSULATION)

YD YARD

YR YEAR

ARCHITECTURAL ABBREVIATIONS

GROUND FLOOR PLAN

SCALE:1/8"=1'-0"

A401

AE 101

DRAWING TYPES LEGEND

0- GENERAL INFORMATION

1 - PLANS (HORIZONTAL VIEWS)

2 - ELEVATIONS (VERTICAL VIEWS)

3 - SECTIONS (SECTIONAL VIEWS)

4 - ENLARGED VIEWS (PLANS, ELEVATIONS OR SECTIONS)

5 - DETAILS

6 - SCHEDULES & DIAGRAMS

DISCIPLINE TYPE (ARCHITECTURE SHOWN)

DRAWING TYPE (PLAN, ELEVATION, ETC.)

SERIES/ FLOOR DESIGNATION

DETAIL CALLOUT

ENLARGED PLAN OR DETAIL

ON SHEET INDICATED

A201

INTERIOR ELEVATION CALLOUT

ARROWS INDICATE INTERIOR

ELEVATION ON SHEET

INDICATED

STRUCTURAL GRIDS

AS INDICATED ON

DRAWINGS

BUILDING SECTION CALLOUT

ARROWS INDICATE BUILDING

SECTION ON SHEET INDICATED

A301

SECTION CALLOUT

ARROW INDICATE WALL SECTION ON

SHEET INDICATED

A302

ROOM NAME

ROOM NAME & NUMBER SYMBOL

REFER TO ROOM FINISH SCHEDULE

101.1

DOOR NUMBER SYMBOL

REFER TO DOOR SCHEDULE

DOOR NUMBER WITH *

INDICATES ACCESS CONTROL

HARDWARE

PARTITION TYPE SYMBOL

REFER TO PARTITION TYPES

GLAZING TYPE SYMBOL

REFER TO GLAZING TYPES

A

AL1

REVISION SYMBOL

REFER TO SHEET BORDER FOR

REVISION HISTORY

ELEVATION DATUM SYMBOL

INDICATES DATUM ELEVATION AS

INDICATED

Bottom Text Top Text

DISCIPLINE MODIFIER (ELEMENTS SHOWN)

ARCHITECTURAL SYMBOLS LEGEND

DRAWING TITLE 0 4' 8' 16'

1/8" = 1'-0"

NORTH ARROW AND SCALE

A301

EXTERIOR ELEVATION CALLOUT

ARROW INDICATE ELEVATION ON

SHEET INDICATED

A201

N

KEYNOTE SYMBOL

INDICATES INFORMATION FOUND IN

KEYNOTES ON PLAN

LOCATED IN THE

BOTTOM RIGHT

SHEET CORNER

0 2' 4' 8'

1/4" = 1'-0"

A

INTERIOR SECTION CALLOUT

ARROW INDICATES SECTION ON

SHEET INDICATED

1 / A302

0 1' 2' 4'

1/2" = 1'-0"

6" 1'-6"1'0

1 1/2" = 1'-0"

3' - 0" 6" MAX

2' - 0" 1' - 0"

1' - 6"

7"

3"

WATER CLOSET

GRAB BAR

SANITARY NAPKIN

DISPOSAL

TOILET TISSUE

DISPENSER

TOILET SEAT

COVER

DISPENSER

TYPICAL ACCESSIBLE

WATER CLOSET BACK WALL

TYPICAL ACCESSIBLE WATER CLOSET SIDE WALL

TO

S

PO

U

T

2'

1/

8"

TO

S

PO

U

T

3'

1/

2"

ELECTRIC

WATER

COOLERS

12" MAX 42" MIN

39" - 41"

1"

" M

IN

3"

FINISH FLOOR

DESCRIPTION MOUNTING HEIGHT

WATER CLOSET 15" AFF TO RIM

WATER CLOSET - ACCESSIBLE 17" AFF TO RIM

URINAL 24" AFF TO RIM

URINAL - ACCESSIBLE 17" AFF TO RIM

LAVATORY 34" AFF TO TOP

PAPER TOWEL DISPENSER 46" AFF TO BOTTOM/DISPENSER

SANITARY NAPKIN DISPOSAL 28" AFF TO TOP

TOILET PAPER DISPENSER 28" AFF TO TOP

GRAB BAR 34.5" AFF TO CENTER

ROBE HOOK/TOWEL BAR 60" AFF TO TOP

ROBE HOOK/TOWEL BAR -

ACCESSIBLE

48" AFF TO TOP

TOILET SEAT COVER DISPENSER 28" AFF TO TOP

TYPICAL ACCESSIBILITY, PLUMBING FIXTURE AND TOILET

ACCESSORY CLEARANCES, MOUNTING HEIGHTS AND DIMENSIONS

TOILET ACCESSORY MOUNTING HEIGHT SCHEDULE

EDGE OF WALL

FLUSH VALVE

1- 1/

2" M

IN

TYPICAL WATER COOLERS

ACCESSIBLE

STANDARD

4' - 9 1/2" MIN CLR

HAND DRYER

BABY CHANGING STATION 48" AFF TO TOP

15" AFF TO BOTTOM

COMBINATION TOWEL

/ RECEPTACLE

PAPER TOWEL

DISPENSER/DISPOSAL

NOTE: ALL TOILET ACCESSORIES LISTED ABOVE MAY NOT BE IN CONTRACT.

COAT HOOK 60" AFF TO TOP

COAT HOOK - ACCESSIBLE 48" AFF TO TOP

1/

2" M

IN

SPECIMEN PASS-THRU 48" AFF

6"

6"

1' - 4"

LAVATORY

SOAP DISPENSER

MIRROR (ALIGN W/

LAVATORY

CENTERLINE UNO)

WALL MOUNTED

LAVATORY

FINISH FLOOR

INSULATED PIPE

COVERING WHERE

EXPOSED

MIN

1' - 3"

MIN

1' - 3" PLUMBING FIXTURE

MINIMUM

CLEARANCES

2- 1 1/2" x #10

WASHER HEAD

TEK

SCREWS

2x8

FIRETREATED

WD BLOCKING,

TYP @ ALL

LOCATIONS

METAL STUDS

ELEVATION SECTION

NOTES:

1. PROVIDE BLOCKING @ ALL WALL MOUNTED DOOR STOPS,

REF DOOR HARDWARE

2. PROVIDE BLOCKING @ ALL WALL MOUNTED FIXTURES,

EQUIPMENT, HANDRAIL BRACKETS, CABINETS & GRAB BARS

3. BLOCKING TO BE FIRE TREATED

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

2/10/2022

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

SubmissionARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

BI

M

R en ov at e Ey e C lin ic

A

C S

Pr im ar y

C ar e/ R en ov at e

Ey e

C lin ic

A C

S Pr im ar y C ar e_ de ta ch ed

.rv t

2/

/2

:0 6:

A

M

A-001

ARCHITECTURAL ABBREVIATIONS,

SYMBOLS, LEGENDSPRIME ARCHITECTS

212 N. CRAWFORD AVE

NORMAN, OK. 73069

(866) 226-8071

GENE LAVASTIDA

RENOVATE EYE CLINIC AND ACS

PRIMARY CARE

6010 AMARILLO BLVD. WEST, AMARILLO TX 79106

504-21-110

SCOTT HOBBS COR

02/09/2022 CM DT

Thomas E.

Creek VA

Medical Center

100% FINAL BID

DOCUMENTS

SCALE: 1 1/2" = 1'-0"

2 WOOD BLOCKING DETAIL

UP

UP

STAIR #1STAIR #2STAIR #3

9' - 8" 9' - 8"

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

A

B

C

D

E

G

H

I

J

30' - 0"

03 03 03

03 03

10 10

040404

03 03

4' - 9 1/2"

ADD ALT ADD ALT ADD ALT

12 12

13 13

13 13

0404 04

14 14

1. THIS DEMOLITION PLAN SHOWS GRAPHIC AND WRITTEN INFORMATION CONCERNING THE

EXISTING SPACE. THIS IS INCLUDED AS "INFORMATION ONLY" REPRESENTING AVAILABLE

RECORD INFORMATION OF THE ORIGINAL LEASE DRAWINGS PLUS FIELD NOTATIONS. SOME

MODIFICATIONS MAY HAVE BEEN MADE AND NOT SHOWN. THIS INFORMATION IS FOR THE

CONTRACTOR’S USE AS THEY SEE FIT. NEITHER THE OWNER NOR THE ARCHITECT ACCEPT

ANY RESPONSIBILITY FOR THE ACCURACY OF THIS INFORMATION OR THE CONTRACTOR’S

INTERPRETATION OF IT. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

DETERMINE THE SCOPE OF WORK REQUIRED. THE CONTRACTOR SHALL EXAMINE THE

EXISTING BUILDING AND WORK SHOWN BY ALL CONTRACT DOCUMENTS TO DETERMINE THE

SCOPE OF DEMOLITION REQUIRED WHETHER SPECIFICALLY SHOWN OR NOT.

2. REFER TO MECHANICAL & ELECTRICAL DEMOLITION NOTES AND MEP DOCUMENTS FOR

EXTENT OF DEMOLITION OF THOSE SYSTEMS

3. PROTECT ALL EXISTING STRUCTURE, SYSTEMS, FINISHES AND GENERAL CONSTRUCTION

THAT ARE TO REMAIN THROUGHOUT THE COURSE OF THE WORK TO PREVENT DAMAGE OR

LOSS. ANY SUCH DAMAGE CAUSED DURING THE COURSE OF THIS WORK WILL BE REPAIRED

AT THE CONTRACTOR’S EXPENSE BEFORE THIS WORK IS CONCLUDED

4. OPERATING SYSTEMS, UTILITIES AND SERVICES SERVING THE EXISTING SITE SHALL BE

MAINTAINED IN OPERATION TO SERVE THE NEEDS OF PORTIONS OF THE BUILDING AND SITE

NOT INVOLVED IN THE WORK UNDER THIS CONTRACT AT ALL TIMES DURING THE PROGRESS

OF THE WORK UNDER THIS CONTRACT, EXCEPT FOR SUCH SHORT PERIODS AS ARE

ABSOLUTELY NECESSARY TO PERFORM THE WORK. SUCH OPERATING SYSTEMS, UTILITIES

AND SERVICES INCLUDE BUT ARE NOT LIMITED TO WATER, ELECTRICITY, HVAC, SANITARY,

SEWER, FIRE ALARM, TELEPHONE AND SECURITY

5. PRIOR TO INTERRUPTING OR OTHERWISE AFFECTING ANY SUCH OPERATING SYSTEM,

UTILITY OR SERVICE, CONTRACTOR SHALL CONSULT WITH OWNER’S REPRESENTATIVE TO

ESTABLISH A MUTUALLY SATISFACTORY SCHEDULE FOR CUT OVER, CUT OFF DISRUPTION OR

OTHER CHANGE IN THE OPERATION OF THE AFFECTED SYSTEM, UTILITY OR SERVICE.

6. DEMOLITION CONTRACTOR IS TO ARRANGE FOR SHUT OFF OF EXISTING UTILITIES.

CONTRACTOR SHALL ARRANGE ALL TEMPORARY POWER.

7. NOISE AND DUST IS NOT TO BE DISRUPTIVE TO THE OCCUPIED AREA OF THE BUILDING.

PROVIDE TEMPORARY PARTITIONS AS REQUIRED PER DEMOLITION SPECIFICATION.

8. CONTRACTOR IS RESPONSIBLE FOR VERIFYING WITH THE VA THAT EACH COMPONENT

REMOVED IS ACCEPTABLE FOR DISCARDING OR RECYCLING.

9. CONTRACTOR IS RESPONSIBLE FOR DEMOLISHING AND REMOVING ALL MATERIALS FROM

PREMISES IN ORDER TO ACCOMPLISH THE SCOPE OF THE NEW WORK.

10. CONTRACTOR TO SALVAGE PATIENT LIFTS AND TV UNIT ASSEMBLIES FOR OWNER'S USE.

11. CONTRACTOR TO REMOVE, STORE AND REINSTALL ALL WALL MOUNTED ITEMS IN THE LOBBY, CORRIDOR, AND ELEVATOR LOBBY

12. GENERAL CONTRACTOR TO MAKE A CONTINGENCY FOR ADDITIONAL DEMOLITION WORK NOT

SHOWN ON THESE DRAWINGS. AFTER ALL CEILING ELEMENTS HAVE BEEN REMOVED AND

AFTER ANY SELECTIVE DEMOLITION WORK HAS BEEN COMPLETED, BUT PRIOR TO ANY

MAJOR DEMOLITION WORK OF ELECTRICAL LINES, PLUMBING LINES, STEAM LINES, AND

MEDICAL GAS LINES, THE GENERAL CONTRACTOR SHALL ALLOW FOR TWO WEEKS OF DOWN

TIME FOR THE VA TO CONFIRM WHICH ITEMS ARE TO BE DEMOLISHED AND REMOVED, AND

WHICH ITEMS ARE TO REMAIN IN PLACE. GENERAL CONTRACTOR TO COORDINATE THE

EXACT TIME AND DATE WITH THE VA, AND GIVE THE VA TWO WEEKS ADVANCE NOTICE OF

THE DOWN TIME.

13. DURING THE DOWN TIME FOR THE VA TO REVIEW DEMOLITION ITEMS THAT MAY NOT BE

SHOWN ON THIS PLAN THE CONTRACTOR IS TO REMOVE THE FURRING AROUND ALL

INTERIOR COLUMNS IN PROJECT AREA AND CONFIRM DIMENSIONS OF COLUMN

GRID/CENTER LINES OF COLUMNS TO INTERIOR FACE OF EXTERIOR WALLS, AND FROM

BOTTOM OF BEAMS TO FINISH FLOOR OF EXISTING SLAB. GENERAL CONTRACTOR MUST

NOTIFY ARCHITECT IMMEDIATELY AND PRIOR TO THE END OF THE TWO WEEK DOWN TIME OF

ANY DISCREPENCIES.

GENERAL DEMOLITION NOTES

DEMOLITION LEGEND

DEMOLISH PARTITION WALL

DEMOLISH DOOR AND DOOR FRAME

DEMOLISH MILLWORK

DIMENSION TO DEMOLISH ELEMENT

4' - 0"

EXISTING PARTITION WALL

X

X

REFERS TO ENTIRE ROOM OR AREA

REFERS TO SPECIFIC ELEMENT

DEMOLITION PLAN KEYNOTES

1. DEMOLISH AND REMOVE 4" CMU INFILL WALL. VA AND GENERAL CONTRACTOR TO VERIFY IT

IS NOT A LOAD BEARING WALL.

2. CONTRACTOR TO REMOVE TV MONITOR AND RETURN TO VA. TV MONITOR WILL NOT BE

REMOUNTED.

3. DEMOLISH AND REMOVE EXISTING DOOR AND DOOR FRAME AND ALL ASSOCIATED

COMPONENTS. INCLUDING BUT NOT LIMITED TO FRAME ANCHORS, TRANSOMS, SIDE LIGHTS,

ELECTRICAL COMPONENTS, AND ALL HARDWARE; FLOOR, WALL, AND CEILING MOUNTED.

4. DEMOLISH AND REMOVE EXISTING FLOORING MATERIAL DOWN TO SLAB. INCLUDING BUT NOT LIMITED TO FLOOR TILE, CARPET TILE, MASTIC, THIN SET GROUT, AND TRANSITION STRIPS.

5. DEMOLISH AND REMOVE HORIZONTAL PORTION OF HANDRAIL THAT WILL INTERFERE WITH

NEW WALL.

6. DEMOLISH AND REMOVE EXISTING WALL FINISH MATERIAL. INCLUDING BUT NOT LIMITED TO

WALL MOUNTED EQUIPMENT, SIGNAGE, HAND RAILS, WALL TILE, AND WALL BASE.

7. DEMOLISH AND REMOVE EXISTING WALL PARTITION AND ASSOCIATED FINISH MATERIAL.

INCLUDING BUT NOT LIMITED TO HAND RAILS, STUDS, GYPSUM WALL BOARD, WALL TILE,

BACKER BOARD, WALL BASE, TOP AND BOTTOM STUD TRACKS.

8. EXISTING TO REMAIN AND PROTECT DURING DEMOLITION AND CONSTRUCTION.

9. DEMOLISH AND REMOVE EXISTING TOILET PARTITIONS, AND ACCESSORIES. INCLUDING BUT

NOT LIMITED TO ASSOCIATED WALL ANCHORS, FLOOR ANCHORS, AND CEILING ANCHORS,

GRAB BARS, SOAP DISPENSERS, PAPER TOWEL DISPENSERS, COAT HOOKS, CLIP BOARD

HOLDERS, COAT HOOKS, AND MIRRORS.

10. DEMOLISH AND REMOVE EXISTING PLUMBING FIXTURE. INCLUDING BUT NOT LIMITED TO

ELECTRICAL SENSORS, DRAIN LINES, PROTECTIVE COVERINGS, FLOOR ANCHORS, AND WALL

ANCHORS. REFER TO PLUMBING DEMOLITION FOR COMPLETE REMOVAL INSTRUCTIONS.

11. EXISTING ELECTRICAL CONDUIT TO REMAIN.

12. SMOKE DOOR AND WALL TO REMAIN AND PROTECTED FROM DAMAGE.

13. DEMOLISH AND REMOVE EXISTING DRYWALL ON INTERIOR FACE OF EXTERIOR WALLS.

DEMOLITION AND REMOVAL OF ANYTHING INSIDE EXTERIOR WALLS MUST BE INSPECTED AND

APPROVED PRIOR BY THE VA. DO NOT DAMAGE ANY FIBER OPTICS CABLING, HYDRONIC

PIPING, AND ELECTRICAL CONDUIT IN EXTERIOR WALLS BEFORE VA APPROVAL AND

INSPECTION.

14. DEMOLISH AND REMOVE EXTERIOR WINDOW AND FRAME.

X

DEMOLISH WALL LAYER

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

2/10/2022

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

SubmissionARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

BI

M

R en ov at e Ey e C lin ic

A

C S

Pr im ar y

C ar e/ R en ov at e

Ey e

C lin ic

A C

S Pr im ar y C ar e_ de ta ch ed

.rv t

2/

/2

:0 7:

A

M

AD-101

FIRST FLOOR DEMO PLAN

PRIME ARCHITECTS

212 N. CRAWFORD AVE

NORMAN, OK. 73069

(866) 226-8071

GENE LAVASTIDA

RENOVATE EYE CLINIC AND ACS

PRIMARY CARE

6010 AMARILLO BLVD. WEST, AMARILLO TX 79106

504-21-110

SCOTT HOBBS COR

02/09/2022 CM DT

Thomas E.

Creek VA

Medical Center

100% FINAL BID

DOCUMENTS

SCALE: 1/8" = 1'-0"

1 FIRST FLOOR - EAST WING

0 4' 8' 16'

1/8" = 1'-0"

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

A

B

C

D

E

G

H

I

J

ADD ALT ADD ALT ADD ALT

LINEN CHUTE

TO REMAIN

NIC

21 21 21

212121

21 21

1. THIS DEMOLITION PLAN SHOWS GRAPHIC AND WRITTEN INFORMATION CONCERNING THE

EXISTING SPACE. THIS IS INCLUDED AS "INFORMATION ONLY" REPRESENTING AVAILABLE

RECORD INFORMATION OF THE ORIGINAL LEASE DRAWINGS PLUS FIELD NOTATIONS. SOME

MODIFICATIONS MAY HAVE BEEN MADE AND NOT SHOWN. THIS INFORMATION IS FOR THE

CONTRACTOR’S USE AS THEY SEE FIT. NEITHER THE OWNER NOR THE ARCHITECT ACCEPT

ANY RESPONSIBILITY FOR THE ACCURACY OF THIS INFORMATION OR THE CONTRACTOR’S

INTERPRETATION OF IT. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

DETERMINE THE SCOPE OF WORK REQUIRED. THE CONTRACTOR SHALL EXAMINE THE

EXISTING BUILDING AND WORK SHOWN BY ALL CONTRACT DOCUMENTS TO DETERMINE THE

SCOPE OF DEMOLITION REQUIRED WHETHER SPECIFICALLY SHOWN OR NOT.

2. REFER TO MECHANICAL & ELECTRICAL DEMOLITION NOTES AND MEP DOCUMENTS FOR

EXTENT OF DEMOLITION OF THOSE SYSTEMS

3. PROTECT ALL EXISTING STRUCTURE, SYSTEMS, FINISHES AND GENERAL CONSTRUCTION

THAT ARE TO REMAIN THROUGHOUT THE COURSE OF THE WORK TO PREVENT DAMAGE OR

LOSS. ANY SUCH DAMAGE CAUSED DURING THE COURSE OF THIS WORK WILL BE REPAIRED

AT THE CONTRACTOR’S EXPENSE BEFORE THIS WORK IS CONCLUDED

4. OPERATING SYSTEMS, UTILITIES AND SERVICES SERVING THE EXISTING SITE SHALL BE

MAINTAINED IN OPERATION TO SERVE THE NEEDS OF PORTIONS OF THE BUILDING AND SITE

NOT INVOLVED IN THE WORK UNDER THIS CONTRACT AT ALL TIMES DURING THE PROGRESS

OF THE WORK UNDER THIS CONTRACT, EXCEPT FOR SUCH SHORT PERIODS AS ARE

ABSOLUTELY NECESSARY TO PERFORM THE WORK. SUCH OPERATING SYSTEMS, UTILITIES

AND SERVICES INCLUDE BUT ARE NOT LIMITED TO WATER, ELECTRICITY, HVAC, SANITARY,

SEWER, FIRE ALARM, TELEPHONE AND SECURITY

5. PRIOR TO INTERRUPTING OR OTHERWISE AFFECTING ANY SUCH OPERATING SYSTEM,

UTILITY OR SERVICE, CONTRACTOR SHALL CONSULT WITH OWNER’S REPRESENTATIVE TO

ESTABLISH A MUTUALLY SATISFACTORY SCHEDULE FOR CUT OVER, CUT OFF DISRUPTION OR

OTHER CHANGE IN THE OPERATION OF THE AFFECTED SYSTEM, UTILITY OR SERVICE.

6. DEMOLITION CONTRACTOR IS TO ARRANGE FOR SHUT OFF OF EXISTING UTILITIES.

CONTRACTOR SHALL ARRANGE ALL TEMPORARY POWER.

7. NOISE AND DUST IS NOT TO BE DISRUPTIVE TO THE OCCUPIED AREA OF THE BUILDING.

PROVIDE TEMPORARY PARTITIONS AS REQUIRED PER DEMOLITION SPECIFICATION.

8. CONTRACTOR IS RESPONSIBLE FOR VERIFYING WITH THE VA THAT EACH COMPONENT

REMOVED IS ACCEPTABLE FOR DISCARDING OR RECYCLING.

9. CONTRACTOR IS RESPONSIBLE FOR DEMOLISHING AND REMOVING ALL MATERIALS FROM

PREMISES IN ORDER TO ACCOMPLISH THE SCOPE OF THE NEW WORK.

10. CONTRACTOR TO SALVAGE PATIENT LIFTS AND TV UNIT ASSEMBLIES FOR OWNER'S USE.

11. CONTRACTOR TO REMOVE, STORE AND REINSTALL ALL WALL MOUNTED ITEMS IN THE LOBBY, CORRIDOR, AND ELEVATOR LOBBY

12. GENERAL CONTRACTOR TO MAKE A CONTINGENCY FOR ADDITIONAL DEMOLITION WORK NOT

SHOWN ON THESE DRAWINGS. AFTER ALL CEILING ELEMENTS HAVE BEEN REMOVED AND

AFTER ANY SELECTIVE DEMOLITION WORK HAS BEEN COMPLETED, BUT PRIOR TO ANY

MAJOR DEMOLITION WORK OF ELECTRICAL LINES, PLUMBING LINES, STEAM LINES, AND

MEDICAL GAS LINES, THE GENERAL CONTRACTOR SHALL ALLOW FOR TWO WEEKS OF DOWN

TIME FOR THE VA TO CONFIRM WHICH ITEMS ARE TO BE DEMOLISHED AND REMOVED, AND

WHICH ITEMS ARE TO REMAIN IN PLACE. GENERAL CONTRACTOR TO COORDINATE THE

EXACT TIME AND DATE WITH THE VA, AND GIVE THE VA TWO WEEKS ADVANCE NOTICE OF

THE DOWN TIME.

13. DURING THE DOWN TIME FOR THE VA TO REVIEW DEMOLITION ITEMS THAT MAY NOT BE

SHOWN ON THIS PLAN THE CONTRACTOR IS TO REMOVE THE FURRING AROUND ALL

INTERIOR COLUMNS IN PROJECT AREA AND CONFIRM DIMENSIONS OF COLUMN

GRID/CENTER LINES OF COLUMNS TO INTERIOR FACE OF EXTERIOR WALLS, AND FROM

BOTTOM OF BEAMS TO FINISH FLOOR OF EXISTING SLAB. GENERAL CONTRACTOR MUST

NOTIFY ARCHITECT IMMEDIATELY AND PRIOR TO THE END OF THE TWO WEEK DOWN TIME OF

ANY DISCREPENCIES.

GENERAL DEMOLITION NOTES

DEMOLITION LEGEND - RCP

DEMOLISH SUPPLY REGISTER

DEMOLISH TROFFER LIGHT

DEMOLISH RETURN REGISTER

DEMOLISH CEILING GRID

EXISTING ELEMENT TO REMAIN

XDEMOLITION RCP KEYNOTES

1. DEMOLISH AND REMOVE SUSPENDED CEILING SYSTEM AND ALL

ASSOCIATED COMPONENTS. INCLUDING BUT NOT LIMITED TO

CEILING TILES, PERIMETER TRACKS, MAIN TS, CROSS TS,

HANGAR WIRES, AND WALL ANCHORS.

2. DEMOLISH AND REMOVE EXISTING LIGHT FIXTURE AND ALL

ASSOCIATED COMPONENTS. INCLUDING BUT NOT LIMITED TO

ATTACHED AND/OR REMOTE BALLASTS, J BOXES, AND CONDUIT

LINES. REFER ELECTRICAL DEMOLITION FOR COMPLETE

REMOVAL INSTRUCTIONS.

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

2/10/2022

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

SubmissionARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

BI

M

R en ov at e Ey e C lin ic

A

C S

Pr im ar y

C ar e/ R en ov at e

Ey e

C lin ic

A C

S Pr im ar y C ar e_ de ta ch ed

.rv t

2/

/2

:0 7:

A

M

AD-102

FIRST FLOOR DEMO RCP

PRIME ARCHITECTS

212 N. CRAWFORD AVE

NORMAN, OK. 73069

(866) 226-8071

GENE LAVASTIDA

RENOVATE EYE CLINIC AND ACS

PRIMARY CARE

6010 AMARILLO BLVD. WEST, AMARILLO TX 79106

504-21-110

SCOTT HOBBS COR

02/09/2022 CM DT

Thomas E.

Creek VA

Medical Center

100% FINAL BID

DOCUMENTS

0 4' 8' 16'

1/8" = 1'-0"

EYE CLINIC RENOVATION

PHASING PLAN LEGEND

WHOLE HEALTH (ACS) RENOVATION

WHOLE HEALTH (ACS) RENOVATION

G

EN

E

LAVASTID

A

AT

T S

XETE FO

SA

R

EG

IS

TE

RED ARCHITEC

T

24186

2/10/2022

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

SubmissionARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

BI

M

R en ov at e Ey e C lin ic

A

C S

Pr im ar y

C ar e/ R en ov at e

Ey e

C lin ic

A C

S Pr im ar y C ar e_ de ta ch ed

.rv t

2/

/2

:0 6:

A

M

A-100

PHASING PLAN AND INFECTION

CONTROLPRIME ARCHITECTS

212 N. CRAWFORD AVE

NORMAN, OK. 73069

(866) 226-8071

GENE LAVASTIDA

RENOVATE EYE CLINIC AND ACS

PRIMARY CARE

6010 AMARILLO BLVD. WEST, AMARILLO TX 79106

504-21-110

SCOTT HOBBS COR

02/09/2022 CM DT

Thomas E.

Creek VA

Medical Center

100% FINAL BID

DOCUMENTS

SCALE: 3/32" = 1'-0"

1 PHASING PLAN

INFECTION…

This is the start of the file's text. The full file is on GovTribe.