ENGINEERING ANNEX ROOF - addendum 2
Solicitation number
50013-BTB2858
Issued by
Orleans Parish, New Orleans City, Louisiana

About this file

This document is an Addendum (Addendum 02) issued by Holly & Smith Architects for the Engineering Annex Roof Replacement project at the University of New Orleans, associated with the State of Louisiana Facility Planning Control. The addendum, dated 4.24.2025, modifies original project specifications and drawings, specifically replacing three sheets: A001 (Demolition Plan), A901 (Roof Plan), and A912 (Roof Details). The project involves a comprehensive roof replacement for the Engineering Annex building, with detailed modifications to existing roof systems, including demolition of current roofing, installation of new roofing materials, and specific technical requirements for roof components.

The addendum provides comprehensive technical guidance for contractors, including specific instructions for roof system replacement, such as installing a cold-applied SBS modified bitumen roof system with tapered polyiso insulation, a 1/2" cover board, and associated flashings. The project includes multiple bid alternates (Base Bid: Main Roof, Add Alt. #1: High Roof, Add Alt. #2: Building Connector Roof), with precise specifications for roof deck elevations, insulation requirements, and integration with existing building structures. The document emphasizes detailed technical requirements, including provisions for lightning protection, mechanical penetrations, sealant applications, and specific metal flashing and coping details, indicating a highly technical and precise approach to the roof replacement project.

View the file

Other files

File Type Posted
50013-BTB2858-1.pdf PDF
50013-BTB2858.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HOLLY & SMITH ARCHITECTS, APAC 208 NORTH CATE ST. / HAMMOND, LA 70401

2302 MAGAZINE ST. / NEW ORLEANS, LA 70130

HOLLYANDSMITH.COM 100 E. VERMILION ST. , SUITE 406 / LAFAYETTE, LA 70501

ENGINEERING ANNEX

ROOF REPLACEMENT

UNIVERSITY OF NEW ORLEANS

Addendum 02

State of Louisiana Facility Planning Control

State Project No.: 01-107-24-05, F.01004598

UNO Purchasing Bid #: BTB 2858

UNO Project #: SP5286

H/S Project: 24054

Addendum: 02

Date: 4.24.2025

This Addendum forms a part of the Contract Documents and modifies the original specifications and drawings issued for bidding to the extent noted hereinafter. All other provisions of the Bid Documents shall remain unchanged.

Careful note of this Addendum will be taken by all parties of interest so that proper allowances are made in all computations, estimates and contracts and so that all trades affected are fully advised in the performance of the work that will be required of them. Acknowledge receipt of this Addendum on the Bid Form.

Modifications to the Drawings

Sheet A001

1.02 Delete Sheet A001 – DEMOLITION PLAN in its entirety. In lieu thereof, substitute revised Sheet A001 –

DEMOLITION PLAN, included herein as part of this Addendum.

Sheet A901

1.03 Delete Sheet A901 – ROOF PLAN in its entirety. In lieu thereof, substitute revised Sheet A901 – ROOF

PLAN, included herein as part of this Addendum.

Sheet A901

1.04 Delete Sheet A912 – ROOF DETAILS in its entirety. In lieu thereof, substitute revised Sheet A912 – ROOF

DETAILS, included herein as part of this Addendum.

END OF ADDENDUM.

1. EXISTING ROOF: BUILT UP ROOF WITH BROADCAST AGGREGATE

ON TAPERED PERLITE WITH APPROXIMATELY 3" THICK AT EDGE

OF ROOF DRAINS AND 9-1/2" THICK AT ROOF PERIMETER. PERLITE

APPEARS TO BE SET IN PITCH DIRECTLY ON CAST IN PLACE

CONCRETE DECK.

2. CLEAN EXISTING CONCRETE DECK SUFFICIENTLY TO PROVIDE A

SURFACE SUITABLE FOR ADHESIVE ATTACHMENT OF THE NEW

RIGID INSULATION. PROVIDE ONE SQUARE SAMPLE AREA FOR

CONFIRMATION WITH ROOFING MEMBRANE MANUFACTURER.

3. DIMENSIONS, ROOF THICKNESSES, LOCATIONS, SIZES AND

ORIENTATIONS OF ALL ROOF AREAS AND ROOF MOUNTED ITEMS

ARE ALL APPROXIMATE. FIELD VERIFY ALL CONDITIONS

THROUGHOUT.

4. UNLESS NOTED OTHERWISE, DASHED LINES INDICATE WORK TO

BE DEMOLISHED AND REMOVED.

5. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW EVERY ITEM

TO BE DEMOLISHED; WHETHER LISTED OR NOT, REMOVE ALL

COMPONENTS NEEDED FOR NEW WORK.

6. PROTECT ALL WORK THAT IS SCHEDULED TO REMAIN FROM

DAMAGE.

7. PRIOR TO EXECUTING WORK, NOTIFY THE ARCHITECT IF

CONDITIONS DEVIATE FROM WHAT IS SHOWN.

8. DEMOLISH ALL LIGHTNING PROTECTION SYSTEM COMPONENTS

THROUGHOUT WITH THE EXCEPTION OF ALUMINUM THREADED

GROUND RODS ATTACHED TO ROOF DECK.

9. SALVAGE ALL STAINLESS STEEL FLASHING AND COPING FOR

DELIVERY TO METAL RECYCLING COMPANY. OWNER WILL

COLLECT VALUE OF RECYCLED MATERIAL.

10. CONFIRM IF CONDUIT OR PIPE PENETRATIONS ARE STILL IN

SERVICE. WHERE NO LONGER IN USE AND/OR CAPPED ABOVE

ROOF, REMOVE LINE TO BELOW ROOF DECK AND CAP. WHERE

STILL IN USE, REMOVE ALL PITCH POCKETS, MASTIC, LEAD

FLASHING AND PREPARE FOR LIQUID FLASHING.

11. CUT BACK TREE BRANCHES FROM EXTERIOR FACE OF ROOF

PARAPET 24" CLEAR MIN. THERE SHALL BE NO TREE BRANCHES

ABOVE THE ROOF OR PARAPET.

GENERAL NOTES

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

013401340134

/A

1/ A

3/ A

4/A011

6/A011

/A

8/A011

/A

12/A

13/A011

14/A011

/A

19/A011

/A

3/ A01

2/A012

1/A012

0137 0137

0137 0137

EXISTING

ROOF TO

REMAIN -

N.I.C.

EXISTING

ROOF TO

REMAIN -

N.I.C.

EXISTING TOWER ROOF

TO REMAIN - N.I.C.

32'-3"

'-0

/2

'-1

/2

'-4

/2

48'-6 1/2" 59'-5 1/2" 23'-11"

'-6

'-1

'-0

'-4

/2

42'-11" 185'-5" 59'-9"

94'-7" 43'-5"

(OPEN TO

COURTYARD

BELOW)

/A

5/ A

/A

8/ A

/A

/A

10/A012

11/A012

12/A

16/A012

4/A012 16 /A

9/A011

/A

TYP

TYP

29'-7"

WEATHERPROOF DAILY: CONTRACTOR SHALL SEAL THE ROOF ON

THE SAME DAY AS ANY DEMO/INSTALLATION. IN ADDITION, THE

CONTRACTOR SHOULD NOT REMOVE MORE ROOF THAN CAN BE

REPLACED IN THE SAME DAY, KEEPING WATCH ON HOURLY LOCAL

RAIN FORECASTS.

ADD ALT. # 1:

HIGH ROOF

ADD ALT. # 2:

BUILDING

CONNECTOR

ROOF

PLUMBING VENT STACK

DEMOLITION LEGEND

ROOF DRAIN

REMOVE EXISTING ROOF SYSTEM

AND ALL FLASHING DOWN TO TOP

OF EXISTING ROOF DECK

4 / A011

REFERENCE FOR PHOTOGRAPH OF

EXISTING CONDITION

EXHAUST FAN ASSEMBLY

ON CURB

DUCT PENETRATION AND AIR

HANDLING ASSEMBLY ON CURBS

/8 A013

/1 A013

/5 A013

/9 A013

/3 A013

/7 A013

/10 A013

/6 A013

/4 A013

BASE BID: MAIN ROOF

TOP OF CONC. DECK =

15'-0" +/- V.I.F.

ADD ALT. # 1: HIGH ROOF

TOP OF CONC. DECK =

22'-0" +/- V.I.F.

ADD ALT. # 2:

BUILDING

CONNECTOR ROOF

TOP OF CONC.

DECK = 10'-8" +/-

V.I.F.

N.I.C.

N.I.C.

KEY PLAN

PROJECT NO.

DATE

This drawing, as an instrument of service, is and shall remain the property of the Architect and shall not be reproduced, published, or used in any way without the permission of the Architect.

© Holly & Smith Architects, APAC

PROJECT MANAGER

PHASE

QUALITY CONTROL

DESCRIPTION DATENO.

1"

0" 1"½"

½"

The graphic scale at the bottom left corner of this drawing must measure 1"x1" otherwise all listed scales are null and void.

HOLLY & SMITH

ARCHITECTS

HAMMOND

T 9 8 5 . 3 4 5 . 5 2 1 0 www.hollyandsmith.com

NEW ORLEANS

T 5 0 4 . 5 8 5 . 1 3 1 5

LAFAYETTE

T 3 3 7 . 2 7 9 . 2 0 1 0

S T

A T

E P

R O

JE

C

T N

O -1

-2

-0

F

.0

S T

A T

E I

D S

IT

E C

O D

E -3

-0

U .N

.O P

R O

JE

C

T

S

P

U .N

.O P

U R

C H

A S

IN

G B

ID

B

T B

C R e v it M o d e ls

\2

U

N O

E n g in e e ri n g A n n e x R o o f R e p la c e m e n t_ ra y h o lly a n d s m it h .c o m

.r v t

/2

/2

:5

:3

A

M

A001

DEMOLITION PLAN

24054

02/07/25

RK

CD

AV

BID

DOCUMENTS

L A

K E

S H

O R

E D

R

IV

E , N

E W

O R

L E

A N

S , L

A

U N

IV

E

R S

IT

Y O

F N

E W

O R

L E

A N

S

E N

G

IN

E E

R

IN

G A

N N

E X

R O

O F

R E

P L

A C

E M

E N

T

KEYNOTE LEGEND

0130 DEMOLITION ROOF HATCH ASSEMBLY AND WOOD BLOCKING DOWN

TO TOP OF CONCRETE ROOF DECK. SEE DETAIL -

0131 DEMOLISH ALL OF ROOF SYSTEM DOWN TO TOP OF CONCRETE

ROOF DECK WITHIN THE HATCHED AREA ENCLOSED BY BOLD

DASHED LINE. THIS INCLUDES ALL STAINLESS STEEL COUNTER

FLASHING AT CAST STONE PANEL REGLETS, FLASHING, SEALANT,

AGGREGATE, MEMBRANES, INSULATION, CANTS AND PITCH

POCKETS.

0132 DEMOLISH ALL STAINLESS STEEL COPING, FASTENERS, CLEATS

AND WOOD BLOCKING AT TOP OF PARAPET TYPICAL. SEE DETAIL -

0133 DEMOLISH MEMBRANE FLASHING AND CANT STRIP AT BASE OF

EXHAUST FAN CURB. EXISTING CURB AND COUNTERFLASHING TO

REMAIN. SEE DETAIL -

0134 DEMOLISH ROOF DRAIN DOME, COLLAR, BOLTS AND ANY ROOF

MEMBRANE OR MASTIC ATTACHED TO THE DRAIN BASIN. EXISTING

DRAIN BASIN TO REMAIN. SEE DETAIL -

0135 REMOVE BASE FLASHING ON GALVANIZED STEEL SUPPORT POSTS

AT CONDUITS RUNS. CONDUIT AND SUPPORT POSTS ARE EXISTING

TO REMAIN AND SHALL REMAIN IN OPERATION THROUGHOUT

RENOVATION.

0136 EXISTING GALVANIZED STEEL LADDER TO REMAIN.

0137 DEMOLISH STAINLESS STEEL THROUGH WALL SCUPPER

ENCLOSURE, WOOD BLOCKING, CAN STRIP, MEMBRANE FLASHING

AND MASTIC. EXISTING CAST STONE PANEL ROUGH OPENING TO

REMAIN. SEE DETAIL -

0138 DEMOLISH ALL SEALANT AND BACKER ROD FROM VERTICAL JOINTS

IN EXTERIOR FACE OF CAST STONE PANELS ALONG THIS WALL,

FROM TOP OF CONCRETE DECK TO TOP OF PARAPET ABOVE.

PREPARE JOINT FOR NEW SEALANT INSTALLATION.

0139 DEMOLISH ALL SEALANT AND BACKER ROD FROM VERTICAL JOINTS

IN EXTERIOR FACE OF CAST STONE PANELS ALONG THIS WALL,

FROM TOP OF CONCRETE DECK TO HORIZONTAL JOINT

APPROXIMATELY 12'-0" ABOVE TOP OF ROOF DECK. PREPARE JOINT

FOR NEW SEALANT INSTALLATION.

0147 DEMOLISH METAL JACK VENT ASSEMBLY AND WOOD BLOCKING

DOWN TO TOP OF CONCRETE ROOF DECK.

3/32" = 1'-0"1 ROOF PLAN - DEMOLITION

N

TRUE

NORTH

KEYNOTE LEGEND

0148 DEMOLISH METAL GOOSE NECK VENT ASSEMBLY, METAL FLASHING,

WOOD BLOCKING AND/OR CURB DOWN TO TOP OF CONCRETE ROOF

DECK. SEE DETAIL -

0149 DEMOLISH ALL LEAD FLASHING, MEMBRANE, MASTIC AND SEALANT

ON VENT PIPE DOWN TO TOP OF CONCRETE ROOF DECK. SEE

DETAIL -

0150 DISCONNECT EXHAUST FAN ASSEMBLY, REMOVE FROM SUPPORT

CURB AND SET ASIDE FOR RE-INSTALLATION ON NEW CURB.

DEMOLISH EXISTING SUPPORT CURB ASSEMBLY AND BLOCKING

DOWN TO TOP OF CONCRETE ROOF DECK. SEE DETAIL -

0161 PULL BACK LIGHTNING PROTECTION ATTACHED TO THIS PARAPET

AND ACCESS LADDER AND SECURE TO N.I.C. ROOF UNTIL

RENOVATION WORK IS COMPLETE AND REINSTALL.

0162 DISCONNECT POWER TO PARAPET MOUNTED LIGHT FIXTURE, PULL

BACK WIRING TO AN INTERIOR LOCATION AND DEMOLISH (2) 1"

DIAMETER GALV. METAL CONDUITS, FITTINGS, JUCTION BOXES AND

SUPPORT CURBS WITHIN THE DEMOLISHED ROOF AREA. LIGHT

FIXTURE IS EXISTING TO REMAIN.

0166 DEMOLISH ALL METAL FLASHING, MEMBRANE, CANTS, MASTIC AND

BLOCKING AT CONCRETE SUPPORT BASE. TEMPORARILY

DISCONNECT AND REMOVE AIR HANDLER ASSEMBLY, SHOCK

ABSORBER BASE, AND STEEL BEAM DUNNAGE FROM TOP OF

CONCRETE SUPPORT BASE. SEE DETAIL -

0167 DEMOLISH MEMBRANE FLASHING AND CANT STRIPS. PREP FACE OF

CURB AND DUCT TRANSITION FOR NEW LIQUID FLASHING SYSTEM

AT BASE.

0168 DEMOLISH EXHAUST FAN ASSEMBLY, ELECTRICAL SERVICE,

SUPPORT CURB AND FLASHING DOWN TO TOP OF CONCRETE ROOF

DECK. TERMINATE ELECTRICAL BELOW ROOF DECK AND CAP.

0190 EXISTING TO REMAIN - N.I.C.

2 ADDENDUM 02 04/24/25

32'-3"

'-0

/2

'-1

/2

'-4

/2

(OPEN TO

COURTYARD

BELOW)

48'-6 1/2" 59'-5 1/2" 23'-11"

'-6

'-1

'-0

9.30"

8.28"

8.17"

10.78"

10.36"

'-4

/2

42'-11" 185'-5" 59'-9"

7.27"

7.27"

7.53" 8.16"

MAIN ROOF

10.36"

R I

D G

E

R I

D G

E

R I

D G

E

R I D G E

R I D G E

R I D G E

TYP

TYP

TYP

TYP

TYP

TYP

0762 0762

0762 0762

TYP

0722 0722 0722

0721 0721

0722 0722

TYP

TYP

TYP

TYP

TYP

TYP

0761 0762

94'-7" 43'-5"

3.75"

3.75" 3.75"

3.75" 3.75"

3.75"

3.75"

8.63"

3.75"

8.22"

3.75"

8.11"

3.75"

3.75"

9.40"

8.30"

6.84"

6.25"

3.75"

3.75"

7.25"

6.25"

7.50"

6.44"

3.75"

7.58"

3.75"

3.75"

9.00"

8.39"

8.31"

EXISTING

ROOF TO

REMAIN -

N.I.C.

EXISTING

ROOF TO

REMAIN -

N.I.C.

EXISTING ROOF TO

REMAIN - N.I.C.

(OPEN TO

COURTYARD

BELOW)

TYP

TYP

0730 0730

0782 0782

0782 0782

R I

D G

E

7.69"

29'-7"

A912

A912

Sim

A912

29'-7"

A912

ADD ALT. # 1:

HIGH ROOF

ADD ALT. # 2:

BUILDING

CONNECTOR

ROOF

GENERAL NOTES

1. TYPICAL ROOF SYSTEM: COLD APPLIED SBS MODIFIED BITUMEN ROOF SYSTEM ON 1/2" COVER

BOARD AND AN R-25 AVERAGE TAPERED POLYISO INSULATION VALUE ON EXISTING CAST

CONCRETE ROOF DECK. ENTIRE SYSTEM IS SET IN ADHESIVE ON EXISTING ROOF DECK IN

PATTERN ENGINEERED BY ROOF MEMBRANE MANUFACTURER TO RESIST UPLIFT. PROVIDE 3/16"

PER FOOT SLOPE TYPICAL UNLESS NOTED OTHERWISE. REFER TO DETAILS AND SPECIFICATIONS

FOR MORE INFORMATION.

2. LIGHTNING PROTECTION SYSTEM: PROVIDE LIGHTNING PROTECTION SYSTEM THROUGHOUT

AREAS WHERE ROOF IS REPLACED UNLESS NOTED OTHERWISE. RE-USE EXISTING ALUMINUM

THREADED GROUND RODS ATTACHED TO ROOF DECK WHERE POSSIBLE. SEE DETAIL -

3. METAL FLASHING: ALL METAL FLASHING, COUNTER FLASHING, EDGE METAL AND COPING NOTED IN THE DRAWINGS SHALL BE 24 G.A. STAINLESS STEEL TO MATCH THE EXISTING 9 STORY ROOF.

4. SEE SHEET A911 FOR ROOFING DETAILS. WHERE DETAILS ARE NOT SHOWN, PROVIDE STANDARD

DETAILS AS RECOMMENDED BY THE ROOFING MANUFACTURER AND NRCA. REPORT ANY

DISCREPANCIES BETWEEN DETAILS, MANUFACTURER’S RECOMMENDATIONS, AND FIELD

CONDITIONS TO THE ARCHITECT.

5. THE WORK SHALL INCLUDE THE INSTALLATION OF 18 SQUARES OF MODIFIED BITUMEN CAP SHEET PLIES ONLY AS DETERMINED BY ARCHITECT TO ELIMINATE PONDING OBSERVED DURING PONDING WATER INSPECTION. FOR ANY QUANTITY REQUIRED BEYOND THIS AMOUNT, REFER TO UNIT PRICE

SPECIFICATION.

6. WHERE DETAILS ARE NOT SHOWN, PROVIDE STANDARD DETAILS AS RECOMMENDED BY THE

ROOFING MANUFACTURER AND NRCA. REPORT ANY DISCREPANCIES BETWEEN DETAILS,

MANUFACTURER’S RECOMMENDATIONS, AND FIELD CONDITIONS TO THE ARCHITECT. COMPLY

WITH MANUFACTURER'S RECOMMENDATIONS FOR ROOF PENETRATIONS, FLASHINGS, ETC.

7. DIMENSIONS, ROOF THICKNESSES, LOCATIONS, SIZES AND ORIENTATIONS OF ALL ROOF AREAS

AND ROOF MOUNTED ITEMS ARE ALL APPROXIMATE. FIELD VERIFY ALL CONDITIONS

THROUGHOUT.

8. ALL ELECTRICAL, MECHANICAL AND/OR PLUMBING WORK REQUIRED TO BE DISCONNECTED,

RECONFIGURED, EXTENDED, RELOCATED AND/OR TO HAVE EXISTING LINES REPOSITIONED SHALL

MEET ALL APPLICABLE CODE REQUIREMENTS AND REGULATIONS.

9. PROVIDE REINFORCED LIQUID FLASHING AT ALL PIPE AND CONDUIT PENETRATIONS THROUGH ROOF ASSEMBLY, WHETHER SHOWN ON PLAN OR NOT, UNLESS DETERMINED TO NO LONGER BE IN

SERVICE. IF NO LONGER IN SERVICE CAP LINE BELOW ROOF DECK.

10. PATCH CHIPPED OR SPALLED PORTIONS OF CAST STONE WALL PANELS AT SEALANT JOINTS

AND/OR FLASHING CONDITIONS WITH CEMENTITIOUS MORTAR.

11. AVOID INSTALLING FASTENERS IN CONCRETE SUBSTRATE WITHIN 2" OF CONCRETE EDGE OR

CORNER. FOLLOW ACI GUIDELINES TYPICAL.

ROOF LEGEND

EXISTING PLUMBING VENT STACK

TO REMAIN IN PLACE WITH NEW

BASE FLASHING

EXISTING ROOF DRAIN

LOCATION - SEE KEYNOTE FOR

RENOVATION EXTENT

TYP. ROOF SYSTEM: SEE GENERAL

NOTES

T Y

P

'-0

3"

TOTAL THICKNESS OF INSULATION

AND COVER BOARD ABOVE

CONCRETE ROOF DECK

CRICKETS AND ROOF DRAIN SUMP:

SBS MODIFIED BITUMEN ROOF

MEMBRANE OVER TAPERED ROOF

INSULATION AT CRICKETS AND ROOF

DRAIN SUMP (1/2":1'-0" MIN. SLOPE)

EXISTING EXHAUST FAN

ASSEMBLY ON CURB

EXISTING AIR HANDLING

ASSEMBLY AND DUCT

PENETRATION ON CURB/

DUNNAGE

NEW GOOSE NECK VENT

ASSEMBLY ON CURB

/4 A912

/1 A911

/6 A911

/10 A912

/5 A911

/2 A911

/4 A911

/8 A911

/10 A911

/3 A911

/11 A911

/6 A912

/7 A911 /1 A911

ROOF DRAIN SUMP - 1/2" : 1'-0"

SLOPE

/3 A912

/3 A912

/2 A911

/11 A912

BASE BID: MAIN ROOF

TOP OF CONC. DECK =

15'-0" +/- V.I.F.

ADD ALT. # 1: HIGH ROOF

TOP OF CONC. DECK =

22'-0" +/- V.I.F.

ADD ALT. # 2:

BUILDING

CONNECTOR ROOF

TOP OF CONC.

DECK = 10'-8" +/-

V.I.F.

N.I.C.

N.I.C.

KEY PLAN

PROJECT NO.

DATE

This drawing, as an instrument of service, is and shall remain the property of the Architect and shall not be reproduced, published, or used in any way without the permission of the Architect.

© Holly & Smith Architects, APAC

PROJECT MANAGER

PHASE

QUALITY CONTROL

DESCRIPTION DATENO.

1"

0" 1"½"

½"

The graphic scale at the bottom left corner of this drawing must measure 1"x1" otherwise all listed scales are null and void.

HOLLY & SMITH

ARCHITECTS

HAMMOND

T 9 8 5 . 3 4 5 . 5 2 1 0 www.hollyandsmith.com

NEW ORLEANS

T 5 0 4 . 5 8 5 . 1 3 1 5

LAFAYETTE

T 3 3 7 . 2 7 9 . 2 0 1 0

S T

A T

E P

R O

JE

C

T N

O -1

-2

-0

F

.0

A T

E I

D S

E C

O D

E -3

-0

U .N

.O P

R O

JE

C

T

S

P

.O P

U R

C H

A S

IN

G B

ID

B

T B

R e v it M o d e ls

\2

U

N O

E n g in e e ri n g A n n e x R o o f R e p la c e m e n t_ ra y h o lly a n d s m it h .c o m

.r v t

/2

/2

:5

:3

A

M

A901

ROOF PLAN

24054

02/07/25

RK

CD

AV

BID

DOCUMENTS

L A

K E

S H

O R

E D

R

IV

E , N

E W

O R

L E

A N

S , L

A

U N

IV

E

R S

IT

Y O

F N

E W

O R

L E

A N

S

E N

G

IN

E E

R

IN

G A

N N

E X

R O

O F

R E

P L

A C

E M

E N

T

N

TRUE

NORTH

3/32" = 1'-0"1 ROOF PLAN

KEYNOTE LEGEND

0560 PREP, PRIME AND PAINT EXISTING STEEL ACCESS

LADDER WITH GALVANIZING PAINT. THIS WORK

SHALL BE PART OF THE BASE BID. SEE DETAIL -

0710 FLASH NEW ROOF SYSTEM INTO EXISTING EXHAUST

FAN SUPPORT CURB. SEE DETAIL -

0713 FLASH NEW ROOF SYSTEM INTO EXISTING CURB

ENCLOSED DUCT PENETRATION. SEE DETAIL -

0721 PROVIDE TAPERED INSULATION CRICKET AS SHOWN

WITH 1/2" PER 1'-0" SLOPE TO GUIDE STORM WATER

TOWARDS DRAINS.

0722 INSTALL NEW CAST IRON DOME, COLLAR AND

EXTENSION AT EXISTING DRAIN BASIN. COORDINATE

INSTALLATION WITH TAPERED INSULATION SUMP.

SEE DETAIL -

0725 INSULATED ROOF HATCH ASSEMBLY ON TREATED

BLOCKING. SEE DETAIL -

0730 FLASH ROOF SYSTEM INTO EXISTING VENT STACK.

SEE DETAIL -

0740 24 GA S.S. GOOSE NECK VENT ON INSULATED CURB

MATCHING SIZE, FUNCTION AND CONFIGURATION OF

DEMOLISHED ASSEMBLY. COORDINATE

INSTALLATION WITH CONNECTION TO EXISTING

DUCT. SEE DETAIL -

0741 ALUMINUM EXHAUST VENT MATCHING SIZE,

FUNCTION AND CONFIGURATION OF DEMOLISHED

ASSEMBLY. SEE DETAIL -

0742 RECONNECT AND MOUNT EXISTING AIR HANDLING

UNIT WITH SHOCK ABSORBERS AND STEEL

DUNNAGE TO CONCRETE BASE IN SAME

CONFIGURATION AS ORIGINAL INSTALLATION. PREP,

PRIME AND PAINT STEEL DUNNAGE WITH

GALVANIZING PAINT. REPLACE EXISTING NUTS AT

ANCHOR BOLTS AS NEEDED.

0761 24 GA S.S. METAL COPING W/ DRIP EDGE. SEE

DETAIL -

0762 FLASH 24 GA S.S. METAL THROUGH WALL SCUPPER

INTO EXISTING OPENING IN CAST STONE PARAPET.

SEE DETAIL -

KEYNOTE LEGEND

0775 INSTALL SILICONE SEALANT AND BACKER ROD IN

EXISTING VERTICAL AND HORIZONTAL JOINTS IN

CAST STONE PANELS FROM ROOF DECK UP TO TOP

OF PARAPET ABOVE AT EXTERIOR SIDE OF FACADE.

SEE TYPICAL DETAIL -

0776 INSTALL SILICONE SEALANT AND BACKER ROD IN

EXISTING JOINTS IN CAST STONE PANELS FROM

ROOF DECK UP TO NEAREST HORIZONTAL JOINT AT

APPROXIMATELY 12'-0" ABOVE ROOF. WHERE CAST

STONE PANELS SLOPE INTO INSET WINDOWS,

CONTINUE SEALANT ASSEMBLY ON SLOPED JOINTS

UP TO BOTTOM OF SILL FLASHING AT BASE OF

WINDOW. SEE TYPICAL DETAIL -

0780 FLASH BASE OF EXISTING GALVANIZED STEEL PIPE

SUPPORTS AT EXISTING ELECTRICAL CONDUITS.

MAINTAIN OPERATION OF CONDUITS THROUGHOUT

RENOVATION. SEE DETAIL -

0781 INSTALL NEW INSULATED CURB AT PERIMETER OF

EXISTING CONCRETE BASE AND COVER WITH LIQUID

FLASHING AND 24 GA S.S. METAL CAP FLASHING. SEE

DETAIL -

0782 PROVIDE 24 GA S.S. METAL SADDLE FLASHING FOR

COPING WHERE PARAPET TERMINATES INTO

PERPENDICULAR WALL. SEE DETAIL -

0783 REPLACE DEMOLISHED CONDUITS WITH (2) 1"

DIAMETER GALV. METAL CONDUITS ON RUBBER

CURBS AT 48" O.C. AND RE-FEED EXISTING PARAPET

MOUNTED LIGHT FIXTURE. PROVIDE NEW GALV.

METAL JUNCTION BOXES, FITTINGS AND MEET N.E.C.

REQUIREMENTS FOR ALL MATERIALS AND

INSTALLATION.

0785 FLASH NEW ROOF SYSTEM INTO NEW INSULATED

SUPPORT CURB AND REINSTALL EXISTING EXHAUST

FAN ON TOP. SEE DETAIL -

0786 INFILL EXISTING EXHAUST FAN OPENING WITH

GALVANIZED METAL DECK AND PERIMETER

SUPPORT ANGLES. SEE DETAIL -

1 ADDENDUM 01 04/22/25

2 ADDENDUM 02 04/24/25

GALV. STL. FRAME

& CAP FLSHG.

EXISTING CONCRETE

ROOF DECK TO REMAIN

TAPERED RIGID

INSULATION

1/2" THICK COVER

BOARD WITH

STAGGERED JOINTS

CANT STRIP

EXISTING STEEL

SHIP'S LADDER TO

REMAIN

1" FIBERBOARD INSULATED

ROOF HATCH ASSEMBLY

ON TREATED WOOD

BLOCKING. SECURE TO

BLOCKING WITH NO. 10 -

2.5" GALV. CONSTRUCTION

SCREWS AT 8" O.C.

TREATED 2X6 WOOD

BLOCKING

1/2" DIAMETER HOT

DIPPED GALV.

EXPANSION ANCHOR AT

24" O.C. MAX.

TORCH APPLIED BASE

FLASHING

BASE PLY

V .I .F

'-0

M

IN

TERMINATION BAR

ASSEMBLY, CONTINUOUS

SEALANT

'-0

(U

P P

E R

R O

O F

T O

M A

IN

R

O O

F

'-4

V

.I .F

'-8

V

.I .F

'-0

M A

IN

R

O O

F T

O L

O W

E R

R O

O F

PREP, PRIME AND

PAINT EXISTING

STEEL ACCESS

LADDER WITH

GALVANIZING

PAINT. THIS WORK

SHALL BE PART OF

THE BASE BID. SEE

DETAIL -

A911

Sim

A911

Sim

SEAL ALL WALL

FASTENERS

THOROUGHLY

SEAL ALL WALL

FASTENERS

THOROUGHLY

FLASHING CAP SHEET ON

FLASHING BASE PLY ON CAST

STONE SURFACE.

EXPOSED FACE OF

CAST STONE PANEL

TYP. RECEIVER

FLASHING AND

REMOVABLE

COUNTER FLASHING

DETAIL

POLY-

URETHANE

SEALANT

AT REGLET

24 GA S.S.

COPING

ASSEMBLY

CANT STRIP

POLYURETHANE

SEALANT AT REGLET

AT TOP OF RECEIVER

ON SADDLE FLASHING

6"

6"

PARAPET

WIDTH

24 GA S.S. SADDLE

FLASHING. EXTEND

DRIP EDGE DOWN OVER

RECEIVER FLASHING AT

REGLET

4"

5"

EXPOSED FACE OF

CAST STONE PANEL

HIGH TEMP SELF

ADHERED FLASHING

MEMBRANE OVER

LIQUID FLASHING

6"

6"

PARAPET

WIDTH

REINFORCED

LIQUID FLASHING

SYSTEM ON STONE

PANEL AND OVER

CAP SHEET AT

PARPET. EXTEND

DOWN OVER

SELANT JOINT

4"

5"

/9 A911

POLY-

URETHANE

SEALANT

AT REGLET

EXISTING CAST STONE

PARAPET

FLASHING CAP SHEET ON

FLASHING BASE PLY ON CAST

STONE SURFACE.

TYP. RECEIVER

FLASHING AND

REMOVABLE

COUNTER FLASHING

DETAIL

CANT STRIP

EXISTING CAST

STONE PARAPET

/9 A911

'-8

V

.I .F

'-0

V

.I .F

6" 3/4" 1'-6"

'-0

/2

V

.I .F

S E

E P

L A

N

V A

R

IE

S

V .I .F

A912

Sim

1/2" THICK COVER BOARD

WITH STAGGERED JOINTS

TAPERED RIGID

INSULATION

CANT STRIP

TORCH APPLIED

BASE FLASHING

EXISTING CONCRETE ROOF

DECK TO REMAIN

24 GA S.S. CAP FLASHING WITH

DRIP EDGE AT PERIMETER.

EXISTING CAST CONCRETE

STRUCTURE

24 GA S.S. METAL COPING

ASSEMBLY

EXISTING CAST

STONE PANEL TO

REMAIN

6" 3/4" 1'-6"

V .I .F

24 GA S.S. CAP

FLASHING WITH DRIP

EDGE AT PERIMETER.

24 GA S.S. METAL COPING

ASSEMBLY

EXISTING CAST STONE

PANEL TO REMAIN

1/2" DIAMETER HOT DIPPED

GALV. EXPANSION ANCHOR

AT 24" O.C. MAX.

2X WOOD BLOCKING RIPPED TO

DIMENSIONS AND SHAPE SHOWN

CONTINUOUS 18 GA S.S.

CLEAT NAILED TO

BLOCKING AT 8" O.C.

ELASTOMERIC

SEALANT JOINT

FLASHING BASE PLY

HIGH DOMED GASKETED

FASTENER AT 16" O.C. MAX

LIQUID FLASHING SYSTEM

WITH FLEECE REINFORCING

FLASHING CAP SHEET

HIGH DOMED GASKETED

FASTENER AT 16" O.C. MAX

EXISTING CAST CONCRETE

STRUCTURE

5" +/- V.I.F.

24 GA S.S. RECEIVER

FLASHING SET IN EXISTING

REGLET WITH SPRING LOCK

LEG, SECURED WITH LEAD

WEDGES ATA 12" O.C.

COVERED WITH BACKER

ROD AND SEALANT.

24 GA S.S. METAL

COUNTER FLASHING

WITH DRIP EDGE

1/2" THICK COVER

BOARD WITH

STAGGERED JOINTS

PROVIDE LIQUID FLASHING

SYSTEM WITH FLEECE

REINFORCING OVER TOP OF

TERMINATION BAR

ASSEMBLY WHERE 8" MIN.

BASE FLASHING HEIGHT IS

UNACHIEVABLE

TERMINATION BAR

ASSEMBLY,

CONTINUOUS

SEALANT

TAPERED RIGID

INSULATION

'-5

/2

V

.I .F

PREP SURFACES AND

EXTEND LIQUID

FLASHING SYSTEM UP

ONTO METAL DUCT

TRANSITION

EXISTING CAST STONE

PANEL TO REMAIN

EXISTING DUCT

PENETRATION

EXISTING SUPPORT CURB

ASSEMBLY TO REMAIN.

EXISTING CONCRETE

ROOF DECK TO REMAIN

FLASHING BASE PLY

BASE PLY

SECTION

PLAN

.5 X

1/ 4"

X

.5X.5X

1/2" MIN.

SECONDARY

SEALANT JT.

BACKER

ROD

CAST STONE

PANEL

.5X.5X

1/2" MIN.

SECONDARY

SEALANT JT.

WEEP

PRIMARY

SEALANT JT.

PRIMARY

SEALANT JT.

SEE TYP.

DETAIL AT

REGLETS

BACKER

ROD

A912

'-0

'-6

'-3

E

X

IS

T

IN

G C

U R

B

V .I .F

PROVIDE TAPERED

INSULATION CRICKET AS

SHOWN WITH 1/2" PER

1'-0" SLOPE TO GUIDE

STORM WATER

TOWARDS DRAINS.

A911

1'-0" EXISTING CURB 1'-0"

EXISTING CAST STONE

PANEL TO REMAIN

LIQUID FLASHING

SYSTEM W/ FLEECE

REINFORCING SHOWN

HATCHED WITH

DASHED BOUNDARY.

EXTEND UP ONTO

CURBS AS SHOWN IN

DETAILS.

NOTE: EXISTING DUNNAGE

AND MECHANICAL EQUIPMENT

NOT SHOWN FOR CLARITY.

NO CANTS

INSTALLED

WITHIN THIS

AREA

6" 3/4"

V .I .F

24 GA S.S. CAP

FLASHING WITH

DRIP EDGE AT

PERIMETER.

24 GA S.S. METAL COPING

ASSEMBLY

EXISTING CAST STONE

PANEL TO REMAIN

1/2" DIAMETER HOT

DIPPED GALV.

EXPANSION ANCHOR AT

24" O.C. MAX.

2X WOOD BLOCKING RIPPED TO

DIMENSIONS AND SHAPE SHOWN

CONTINUOUS 18 GA S.S.

CLEAT NAILED TO

BLOCKING AT 8" O.C.

ELASTOMERIC

SEALANT JOINT

FLASHING BASE PLY

HIGH DOMED

GASKETED

FASTENER AT 16"

O.C. MAX

LIQUID FLASHING

SYSTEM WITH

FLEECE

REINFORCING

EXISTING CAST

CONCRETE

STRUCTURE

/8

EXISTING MEMBRANE

FLASHING TO REMAIN

ON THIS SIDE

24 GA S.S. PARAPET

METAL CAP / COPING

ASSEMBLY

HIGH DOMED GASKETED

FASTENER @ 16" O.C (MAX.)

3" MIN.

TURNDOWN

SEE SECTION

DETAILS

CONT. 18 GA.

PREFINISHED

METAL CLEAT

SEE SECTION DETAILS FOR

WALL COMPOSTION (TYP.)

TORCH APPLIED BASE FLASHING

SLOPE TO ROOF

STANDING SEAM

JOINT "J8" PER

SMACNA AT

COPING PANEL

JOINT TYP.

SEAL TYP.

1/2" THICK COVER

BOARD WITH

STAGGERED JOINTS

TAPERED RIGID

INSULATION

6'-0" X 6'-0" +/-

V.I.F. - EXISTING

ROOF ROUGH

OPENING

1/2" DIAMETER HOT

DIPPED GALV.

EXPANSION ANCHOR AT

24" O.C. MAX.

3B20-GA GALVANIZED METAL

ROOF DECK CONNECTED TO

ANGLE WITH 5/8" PUDDLE

WELDS IN A 36/5 PATTERN

EXISTING

CONCRETE

ROOF DECK TO

REMAIN

CONTINUOUS GALV.

L4X4X1/4 STEEL ANGLE

AT OPENING PERIMETER

CAP SHEET

BASE PLY

PROJECT NO.

DATE

This drawing, as an instrument of service, is and shall remain the property of the Architect and shall not be reproduced, published, or used in any way without the permission of the Architect.

© Holly & Smith Architects, APAC

PROJECT MANAGER

PHASE

QUALITY CONTROL

DESCRIPTION DATENO.

1"

0" 1"½"

½"

The graphic scale at the bottom left corner of this drawing must measure 1"x1" otherwise all listed scales are null and void.

HOLLY & SMITH

ARCHITECTS

HAMMOND

T 9 8 5 . 3 4 5 . 5 2 1 0 www.hollyandsmith.com

NEW ORLEANS

T 5 0 4 . 5 8 5 . 1 3 1 5

LAFAYETTE

T 3 3 7 . 2 7 9 . 2 0 1 0

S T

A T

E P

R O

JE

C

T N

O -1

-2

-0

F

.0

A T

E I

D S

E C

O D

E -3

-0

U .N

.O P

R O

JE

C

T

S

P

.O P

U R

C H

A S

IN

G B

ID

B

T B

R e v it M o d e ls

\2

U

N O

E n g in e e ri n g A n n e x R o o f R e p la c e m e n t_ ra y h o lly a n d s m it h .c o m

.r v t

/2

/2

:5

:3

A

M

A912

ROOF DETAILS

24054

02/07/25

RK

CD

AV

BID

DOCUMENTS

L A

K E

S H

O R

E D

R

IV

E , N

E W

O R

L E

A N

S , L

A

U N

IV

E

R S

IT

Y O

F N

E W

O R

L E

A N

S

E N

G

IN

E E

R

IN

G A

N N

E X

R O

O F

R E

P L

A C

E M

E N

T

3" = 1'-0"10 DETAIL - ROOF HATCH

3/4" = 1'-0"4 DETAIL - ROOF LADDER

1 1/2" = 1'-0"6 DETAIL - PARAPET TRANSITION

1 1/2" = 1'-0"7 DETAIL - COPING STEP

3" = 1'-0"8 DETAIL - ENLARGED COPING STEP

3" = 1'-0"2 DETAIL - DUCT PENETRATION FLASHING

6" = 1'-0"3 DETAIL - CAST STONE JOINT

1/2" = 1'-0"1 ENLARGED PLAN - STAIR PRESSURE FAN

3" = 1'-0"9 DETAIL - CANOPY TIE IN

1 1/2" = 1'-0"5 DETAIL @ METAL COPING STANDING SEAM

2 ADDENDUM 02 04/24/25

1 1/2" = 1'-0"11 DETAIL - ROOF INFILL