50-M0061-24-CP332_Aquionics.pdf.PDF
PDF 903 KB Posted
- Attached to
- LESS LETHAL MUNITIONS
- Solicitation number
- 50-M0061-24-CP333
- Issued by
- Valencia County, New Mexico
About this file
This document is a sole source letter from Aquionics UV to the Village of Los Lunas, New Mexico regarding the replacement of their existing Aquionics UV disinfection equipment. The letter confirms that the existing equipment is compliant with regulations and will be upgraded to enhance operational reliability and performance. To maintain compliance, the UV components and services must be sole sourced from Aquionics UV. Aquionics UV's main place of business is in Charlotte, NC, and they have a factory authorized municipal service technician for Los Lunas.
The pricing and terms for the replacement project are provided in quote number 8-9-24AH109. The project involves a water evaluation for a 4 MGD peak with 70 TSS. No other details about pricing, set asides, incumbents, funding requirements, or sources are provided in the document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 50-M0061-24-CP333_Portfolio1.pdf.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Monday, August 12, 2024
Mr. Craig Byers Village of Los Lunas Los Lunas, NM byersc@loslunasnm.gov
505-353-6902
RE: Sole Source Aquionics UV Equipment Replacement for Los Lunas
Dear Mr. Byers
This letter confirms that the existing Aquionics UV disinfection equipment is compliant with VA DEQ regulations and will be upgraded to enhance operational reliability and performance on the site. To maintain ongoing compliance, the UV components and services offered within the project quote number 8-9-24AH109 must be sole sourced from Aquionics UV. Aquionics UV’s main place of business is in Charlotte NC, and our factory authorized municipal service technician for Los Lunas NM, will locally assist.
We thank you for being an existing Aquionics customer and look forward to working with you and future projects requiring UV treatment.
Sincerely, Amber Hudson Regional Manager, Municipal & Industrial 4215 Stuart Andrew Blvd, Suite 3 Charlotte, NC 28217 USA P: 980.256.5700 M: 980.219.2954 amber.hudson@nuvonicuv.com cc: Dan Bertschman Goble Sampson Phone: 610.406.2309 dbertschman@goblesampson.com mailto:mirekesk@loslunasnm.gov mailto:amber.hudson@nuvonicuv.com mailto:dbertschman@goblesampson.com
Quote No: 8-9-24AH109 Company: Goble Sampson Date: August 12, 2024
Attention:
From:
Project:
Water Evaluation: 70
4 MGD peak
TSS: <6 mg/l
E-Coli: 3 log
Average Dose: 30 mJ/cm2
Redundancy: Yes
Unit: ProLine WW IL 4500 Quantity: 2 Configuration: Parallel Each Unit Treats: 4 MGD
Lamp Type: B4035E+
Horizontal and perpendicular to flow
- Each unit comes complete with an automatic quartz cleaning system, UV sensor, temperature sensor, access hatch and automatic lamp variable power control via electronic ballasts (35-100% output) Spare Parts: 6 Lamps, 6 Sleeves, 12 O-Rings, 6 Wiper Rings On-Site Services: Commissioning Start-up, Operator Training, Functional Testing 2 trips/5 days each
- Standard power and controls are housed in 1 epoxy coated steel cabinet per chamber. Cabinets are NEMA 12 rated, suitable for indoor installation.
480 V 3- phase 60 Hz
(includes freight to site).
Terms: -Quote valid for 60 days.
-Freight is ocean with CPT (Carriage Paid to) Terms
Dan Bertschman
Amber Hudson - Municipal Sales Manager
Los Lunas Upgrade NM
Parameters:
% transmittance in a 1cm light path at 253.7nm
" ANSI flanges
Flowrate:
I duty + 1 standby
Equipment Selection & Design:
Medium Pressure No. Lamps per Unit:
Lamp Configuration:
Budget Price: $198,928.00
-Aquionics standard terms and conditions apply (available upon request).
-Delivery approx. 10-14 weeks.
Included Features:
Power & Controls:
free standing
Electrical Data:
Connections:
* See sales drawings for dimensions
UV CHAMBER
Material: StSt 316L / 1.4404
Internal finish: < 0.8 µm Ra, welds ground out, electropolished and passivated
External finish: Brushed to K280, electropolished and passivated
Process (mating) connections: Flange ANSI 150
Drain connection: NPT
Air vent connection NPT
End plate: Removable end plate
Inspection hatch: Removable plate (except WW IL 100)
Degree of protection: IP54 equivalent to NEMA 12
Wiper: Automatic (electrically driven)
Lamps: Medium pressure
Quartz Sleeves: Pure quartz (F200)
Number of Lamps: See table above
Expected lamp life: 10,000 hours
Temperature sensor: Yes
UV sensor: Dry DVGW compliant UV sensor (one per UV chamber)
Working fluid temperature: 33.8°F to 140°F
Hydrostatically pressure tested: Yes
Chamber mounting: Flow horizontal or vertical (lamps horizontal only)
Operating pressure: 145 psi (positive pressure only)
Seals: EPDM, ADI free, EC 1935/2004, FDA 21 CFR
177.2600 approved
OPTIONS
Document Support Pack
Cabinet: Stainless steel 304
Cabinet: Stainless steel 304 with air conditioning (41°-122°F), NEMA 4X (IP66), relative humidity <95% non-condensing*
Cabinet: Stainless steel 316 with air conditioning with sloping roof (41°-122°F), NEMA 4X (IP66), relative humidity <95% non-condensing*
Operation and Maintenance manual and printed Installation and Commissioning manual in Chinese, English, French, German & Spanish
Flange options: PN16, JIS, Table ‘E’
Cable length: 65.6 and 95.1 ft
In-field UV reference sensor kit
Bleed: valve with BSP connection or NPT if ANSI flange
Water level sensor: Full water detection UV chamber
Water leak detection: Detects water leaks from quartz sleeve
OPTIONS (CONTINUED)
Quartz sleeve F240 (reduces performance)
Ultrawipe (for WW IL 250-18000)
UV TouchTM controller (AB850 plc & Touchscreen)
CABINET (CONTROLLER UVTOUCH - AB850 PLC & TOUCHSCREEN)
Material: Polyester coated carbon steel, RAL 7035
Degree of protection: NEMA 12 (IP54)
Supply voltages: IL 100 - 1250:
208V 3Ph 240V 1P+N
220V 1PH +N
277/480V 3P+N IL 4500 - 18000: 480V 3Ph
Operating temperature range: 41°F to 95°F
Relative humidity: <85% non-condensing
Cooling fans: Yes
Interconnecting cable: 32.8 ft
Variable power: Stepless variable power (70% reduction from maximum ballast power)
***CC: Control cabinet, PC: Power cabinet Attention: the optional cabinet with A/C is bigger. Ask for dimensions.
HMI/CONTROL
Display: Allen Bradley Panelview HMI, 7” Color Touch Screen
Operating menu: 3 levels (2 with password protection)
Fault finding: Event log
CUSTOMER OUTPUTS
4-20 mA passive output: UV dose, ballast power
VFC outputs: Standby in remote, system standby, system cooling down, any trip, any warning, UV dose failure, system ready, wiper failure, lamp failure, full water level detection water leak, water temperature warning, water and cabinet temperature alarm
CUSTOMER INPUTS
4-20 mA active or passive inputs:
Flow meter and transmittance meter
VFC inputs: Remote stop/start, remote clear message, remote wipe, remote set power high
CUSTOMER COMMUNICATIONS PORT
Ethernet
APPROVALS
CE marked, UL 508A
MODEL NUMBER MAX POWER (KW) NO OF LAMPS DIMENSIONS (INCHES) APPROX WEIGHT (LB)
Chamber Cab. Cabinet (fan cooled)a Chamber Cabinet
A B C DN No*** K* L M** Empty Fan cooled
ProLine WW IL 100 1.8 2 30.7 12.2 15.7 4 1 13.84 31.5 49.02 93 170
ProLine WW IL 250 5.6 2 30.7 12.2 21.3 6 1 13.84 39.37 56.89 121 286
ProLine WW IL 400 11 4 30.7 12.2 18.3 6 1 13.84 39.37 56.89 121 286
ProLine WW IL 1000 11 4 30.7 12.2 23.6 8 1 13.84 39.37 56.89 176 286
ProLine WW IL 1250 16.5 6 30.7 12.2 23.6 8 1 13.84 47.24 49.02 176 300
ProLine WW IL 4500 26 6 35.3 14.5 31.5 14 1 26.09 47.53 83.05 375 683
ProLine WW IL 5000 35 8 35.3 14.5 31.5 14 1 26.09 47.53 83.05 375 683
ProLine WW IL 7500 52 12 35.3 14.5 31.5 14 1 CC 26.09 31.77 78.98 375 396
1 PC 26.09 47.53 83.05 793
ProLine WW IL 14000 52 8 41.4 17.6 35.4 20 1 CC 26.09 31.77 78.98 573 396
1 PC 26.09 47.53 83.05 793
ProLine WW IL 15000 52 12 41.4 17.6 35.4 20 1 CC 26.09 31.77 78.98 573 396
1 PC 26.09 47.53 83.05 793
ProLine WW IL 16000 78 12 41.4 17.6 35.4 20 1 CC 26.09 31.77 78.98 573 396
2 PC 26.09 47.53 83.05 793
ProLine WW IL 18000 117 18 41.4 17.6 35.4 20 1 CC 26.09 31.77 78.98 595 396
3 PC 26.09 47.53 83.05 793
Amber.Hudson Highlight
| Aquionics UV Sole Source Ltr for Los Lunas NM2 |
| Revised Aquionics UV - Option 2 Quote 8-9-24AH109 Los Lunas NM Upgrade[4] |
| ProLine WW IL (Average Dose WW) |