Lift Station N6A Section 22 13 29 Page 1 Base Kodiak, Alaska
SECTION 22 13 29
SANITARY SEWERAGE PUMPS
02/11
PART 1 GENERAL
1.1 REFERENCES
AMERICAN BEARING MANUFACTURERS ASSOCIATION (ABMA)
ABMA 9 (2015) Load Ratings and Fatigue Life for Ball Bearings
ABMA 11 (2014) Load Ratings and Fatigue Life for Roller Bearings
ASME INTERNATIONAL (ASME)
ASME B40.100 (2013) Pressure Gauges and Gauge Attachments
ASTM INTERNATIONAL (ASTM)
ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA MG 1 (2016; SUPP 20162018) Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
1.2 SUBMITTALS
Submit the following information for each specified item:
SD-02 Shop Drawings
Equipment Installation;
SD-03 Product Data
Materials and Equipment Framed Instructions
Lift Station N6A Section 22 13 29 Page 2
Spare Parts
SD-10 Operation and Maintenance Data
Operating and Maintenance Manuals;
1.3 DELIVERY, STORAGE, AND HANDLING
Protect from the weather, excessive humidity and excessive temperature variation; and dirt, dust, or other contaminants all equipment delivered and placed in storage.
1.4 EXTRA MATERIALS
Submit spare parts data for each different item of material and equipment specified, after approval of the related submittals. Include in the data a complete list of parts and supplies, with current unit prices and source of supply
PART 2 - PRODUCTS
2.1 MATERIALS AND EQUIPMENT
Provide materials and equipment which are the standard products of a manufacturer regularly engaged in the manufacture of such products and that essentially duplicate items that have been in satisfactory use for at least 2 years prior to bid opening. Equipment shall be supported by a service organization that is, in the opinion of the Contracting Officer, reasonably convenient to the site. Pump casings shall be constructed of cast iron of uniform quality and free from blow-holes, porosity, hard spots, shrinkage defects, cracks, and other injurious defects. Impellers shall be cast iron.
2.1.1 Nameplates
Provide each major item of equipment with the manufacturer's name, address, type or style, model or serial number, and catalog number on a plate secured to the item of equipment.
2.1.2 Equipment Guards
Enclose or guard belts, pulleys, chains, gears, projecting setscrews, keys, and other rotating parts so located that any person may come in close proximity thereto.
2.1.3 Special Tools
Provide one set of special tools, calibration devices, and instruments required for operation, calibration, and maintenance of the equipment.
2.1.4 Electric Motors
The pump motors shall be vertical, solid shaft, NEMA P-base, squirrel-cage induction type, suitable for 3 phase, 60 cycle, 208 volt electric current.
Motor shall have a Class F insulation, suitable for temperatures up to 105 degrees Celsius. Insulation temperature shall, however, be maintained
Lift Station N6A Section 22 13 29 Page 3 below 80 degrees Celsius. The motors shall have a normal starting torque and low starting current, as specified by NEMA Design B characteristics.
They shall be open drip-proof design with forced air circulation by integral fan. Openings for ventilation shall be uniformly spaced around the motor frame. Leads shall terminate in cast connection box and clear identification markings.
The motors shall have a 1.15 service factor. The service factor shall be reserved for the owner’s protection. The motors shall not overload beyond their nameplate rating, at the design condition, nor at any head in the operating range as specified under Operating Conditions.
The motor-pump shaft shall center, in relation to the motor base, within .005”. The shaft shall equal or exceed the diameter specified under “Pumps”, at all points from immediately below the top bearing to the top of the impeller hub.
A bearing cap shall hold the bottom motor bearing in a fixed position.
Bearing housings shall have fittings for lubrication as well as purging old lubricant.
The motor shall be fitted with heavy lifting eyes or lugs, each capable of supporting the entire weight of the pump and motor.
The pump motors shall be Premium Efficiency type, per NEMA MG-1 table 12- 12, Inverter Ready per NEMA Part 31.4.4.2, with cast-iron frames, and be UL Recognized and CSA Approved. The motor windings shall be 200 C Inverter Spike-Resistant Magnet wire and the rotors shall have an epoxy coatings for corrosion protection.
2.1.6 Bolts, Nuts, Anchors, and Washers
Bolts, nuts, anchors, and washers shall be steel; galvanized in accordance with ASTM A153/A153M.
2.1.8.2 Auxiliary Equipment
Auxiliary equipment required to complete the system shall be as indicated and shall include the necessary piping, valves, pressure gauges, pressure regulators, pressure switches, solenoid valves, strainers, and accessories.
2.2 CENTRIFUGAL SOLIDS HANDLING PUMPS
The contractor shall furnish and install two (2) vertical, close-coupled, motor-driven, non-clog type pumps.
The pump shall be an 8” vertical, non-clog type of heavy cast iron construction, especially designed for the use of mechanical seals. In order to minimize seal wear caused by linear movement of the shaft, the shaft bearing nearest the pump impeller shall lock in place so that endplay is limited to the clearance within the bearing. Size the impeller to minimize seal wear as a result from shaft deflection caused by the radial thrust of the pump. Size shall be determined from the top of the impeller to the lower bearing supporting the impeller shall have a minimum diameter
Lift Station N6A Section 22 13 29 Page 4 of 1-7/8” for motor frame sizes 213 through 286; 2-1/8” for motor frame sizes 324 and 326; and 3” for frame 364 and larger. The dimension from the lowest bearing to the top of the impeller shall not exceed 6”.
Centrifugal solids handling pumps shall be of the non-clogging centrifugal type designed to pump solids up to 3 inches in diameter and which provide no internal interstices that catch solids and stringy materials to cause clogging.
2.2.1 Pump Characteristics
Provide two pumps; each shall be capable of delivering 410 GPM of raw water or wastewater against a total dynamic head of 37 feet. The minimum acceptable pump efficiency at this condition shall be 68%. Due to the energy-conservation requirements, manufacture shall meet the above minimum efficiency. The maximum allowable speed shall be 1170 RPM. The minimum rated horsepower of each pump motor shall be 10.
Pump Service Sewage
Design Operating Point 410 gpm flow, 37 feet head, 68 percent efficiency.
Impeller Type Cast-iron non-clog centrifugal
Operating Speed 1170 rpm
Electrical Characteristics 208 volts ac, 3 phase, 60 Hz
Size Within rated load driving pump at specified rpm
2.2.2 Pump Casing
Pump casing construction shall have tapped and plugged holes for venting and draining the pump. The casing shall be capable of withstanding pressures 50 percent greater than the maximum operating pressure. The volute shall have smooth passages. The casing shall be such that removal of the impeller can be without disturbing the suction and discharge connections. The casing shall have a hand-hole to permit inspection and cleaning of the pump interior. Pump shall have lifting eyes to facilitate handling of the pump.
2.2.3 Impeller
The impeller design shall be with smooth passages to prevent clogging and pass stringy or fibrous materials. The manufacture shall balance the impeller statically, dynamically, and hydraulically within the operating range and to the first critical speed at 150 percent of the maximum operating speed.
Lift Station N6A Section 22 13 29 Page 5
The manufacturer shall securely key the impeller to the shaft with a locking arrangement whereby the impeller cannot be loosen by torque from either forward or reverse direction.
The pump impeller shall be of the enclosed two-port type made of close-grained cast-iron. The eye of the impeller as well as the ports shall be large enough to permit the passage of a sphere 3” in diameter in accordance with nationally recognized codes.
The impeller shall have a machined keyway, with a stainless steel key, and secured to the motor shaft by a stainless steel cap screw equipped with a Nylock or other suitable self-locking device. The impeller shall not be screwed or pinned to the motor pump shaft and shall be readily removable without the use of special tools.
To prevent the buildup of stringy materials, grit and other foreign particles around the pump shaft, all impellers less than full diameter shall be trimmed inside the impeller shrouds. The shrouds shall remain full diameter to maintain that close minimum clearance from shrouds to volute. Both the end of the shaft and the bore of the impeller shall taper to permit easy removal of the impeller from the shaft.
2.2.4 Wearing Rings
Renewable wearing rings shall be provided on the impeller and casing and shall have wearing surfaces normal to the axis of rotation. Manufacture shall construct wearing rings of steel. Wearing rings design shall be for ease of maintenance and secured to prevent rotation. Contractor may use replaceable steel wear plates fastened to casing in lieu of wearing rings on casing and impeller.
2.2.5 Pump Shaft
The shaft shall be solid stainless steel through the mechanical seal to eliminate corrosion and abrasive rust particles. Removable shaft sleeves will not be acceptable if the shaft under the sleeve does not meet the specified minimum diameter. Pump shaft shall be of adequate size and strength to transmit the full driver horsepower with a liberal safety factor.
2.2.6 Pump Shaft Sleeve
The pump shaft shall protect from wear by a stainless steel, high-grade alloy steel or bronze shaft sleeve. The joint between the shaft and sleeve shall seal to prevent leakage.
2.2.7 Stuffing Box
The stuffing box shall be of the same material as the casing and shall be grease sealed. The stuffing box design shall be for a minimum of five rings of packing and shall have easily removable split type glands.
2.2.8 Mechanical Seals
Lift Station N6A Section 22 13 29 Page 6
Pump shall include double mechanical seals to seal the pump shaft against leakage. Each seal interface shall hold in contact by its own spring system, supplemented by external liquid pressures. The seal system construction shall be readily removable from the shaft.
2.2.9 Bearings
Pump bearings shall be ball or roller type designed to handle all thrust loads in either direction. Pumps depending only on hydraulic balance end thrust will not be acceptable. Bearings shall have an ABEMA L-10 life of 50,000 hours minimum, as specified in ABMA 9 or ABMA 11.
The bearing nearest the impeller shall be designed for the combined thrust and radial load. The upper bearing shall be free to move linearly with the thermal expansion of the shaft and carry only radial loads.
2.2.10 Lubrication
Bearings shall be grease lubricated. Provide a grease fitting on the pump for grease-lubricated bearings. The grease fitting shall be of the type that prevents over-lubrication and the building up of pressure injurious to the bearings. If the grease fitting is not easily accessible, provide grease tubing to a convenient location.
2.2.11 Pump Support
Vertical shaft centrifugal pumps shall have separate bases for the pump and motor. A heavy cast iron base with adequate legs that provide maximum rigidity and balance shall support the vertical dry pit centrifugal pump.
2.2.12 Coupling
Couplings shall be of the heavy-duty flexible type, keyed or locked to the shaft. Disconnecting of the coupling shall be possible without removing the driver half or the pump half of the coupling from the shaft. Couplings for extended shaft vertical centrifugal pumps may be of the universal type.
2.11 ELECTRICAL WORK
Provide electrical motor driven equipment specified complete with motors, motor starters, controls and wiring in accordance with latest code requirements. Electrical characteristics shall be as specified or indicated. Motor starters shall be complete with thermal overload protection and other appurtenances necessary for the motor control specified. Provide manual or automatic control and protective or signal devices required for the operation specified, and any control wiring required for controls and devices but not shown.
PART 3 EXECUTION
3.3 PAINTING
Thoroughly clean, prime, and give two finish coats of paint at the factory in accordance with the recommendations of the manufacturer for each pump and motor.
Lift Station N6A Section 22 13 29 Page 7
-- End of Section --