This document provides details for a federal construction contract opportunity issued by the Department of Veterans Affairs. The solicitation seeks proposals for a fixed-price construction contract to replace and upgrade water mains at the Miami VA Healthcare System. The project scope includes replacing water mains installed in 1967 that are in poor condition, comprised of transite piping that is difficult to work with and requires special handling for disposal. Some water mains run underneath buildings and have developed leaks requiring extensive demolition and construction to repair. Proposals are due by January 6, 2022 at 10:00 AM EST. The purpose of Amendment 0001 as indicated is to add numerous supplemental documents to the solicitation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24822R0026 0001.pdf | ||
| 3 BDoc Structural Draw.pdf | ||
| 1 BDoc Civil Drawings pgs 11-15.pdf | ||
| 4 BDocs Architectural .pdf | ||
| 0 BDocs General Drawings.pdf | ||
| 2 BDoc Abatement Drawi.pdf | ||
| 1 BDoc Civil Drawings pgs 1-10.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCKING NUT
HANGER ROD
HEAVY DUTY
CLEVIS HANGER
SUPPORT NUT
INSULATION
PIPE SIZE
MAXIMUM PIPE SUPPORT SPACING
1" 1 1/4" 1 1/2" AND LARGER
6 FT 10 FT
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST PIPE
ON
TRAPEZE.
COPPER PIPING
PIPE SIZE
5 FT. (10 FT WHERE 10 FOOT LENGTH
OF PIPE ARE USED)CAST IRON PIPING
PIPE SIZE
12 FTSTEEL PIPING
ALL PIPE SIZES
ALL PIPE SIZES
HORIZONTAL VERTICAL
ALL PIPE
SIZES
ALL PIPE
SIZES
ALL PIPE
SIZES
10 FT
15 FT
15 FT
PROVIDE AN
INSULATION
SHIELD.
VALVE IN RISER
BALL VALVE
BALANCING VALVE
CHECK VALVE
STRAINER
BUTTERFLY VALVE
WATER PRESSURE REGULATOR
SHOCK ABSORBER
HOT WATER RETURNHWR
HOT WATER HW
COLD WATERCW
SANITARY VENTV
SANITARY SEWERSAN
ROOF DRAINAGERD
FLOW ARROW
SYMBOL DESCRIPTION
PLUMBING LEGEND
INVERT ELEVATION
UTILITY RISER IDENTIFICATION
8" PIPE SIZE
PIPE SYSTEM ABBREVIATION
RISER DESIGNATION
RD
#7
OVERFLOW ROOF DRAINAGEORD
EXISTING ITEM TO REMAIN (DEMO PLANS)
FLOW ARROW
RISEDROP DROP OR RISE
NEW TO EXISTING PIPE CONNECTION
ITEM TO BE DEMOLISHED (DEMO PLANS)
REMOVE TO POINT INDICATED
NEW ITEM TO BE INSTALLED (NEW WORK PLANS)
SHUT-OFF INDICATED ON THE AS-BUILT DRAWINGS
BALANCING VALVE INDICATED ON THE AS-BUILT DRAWINGS
COLD WATER RETURNCWR
REMOVE GATE VALVE
REMOVE PIPING TO
POINTS INDICATED
INSTALL PRESS-FIT
UNIONS TO EXISTING
PIPING AT POINTS
INDICATED
NEW BALL VALVE
REMOVE GATE VALVE
REMOVE PIPING TO
POINTS INDICATED
NEW FLANGED
BALL VALVE
INSTALL PRESS-FIT
COUPLINGS TO
EXISTING PIPING AT
POINTS INDICATED
REMOVE BALANCING VALVE
REMOVE PIPING TO
POINTS INDICATED
INSTALL PRESS-FIT
UNIONS TO EXISTING
PIPING AT POINTS
INDICATED
NEW BALANCING VALVEGRADE
PIPE
LINK SEAL
BACKING MATERIAL
INTERIOR OF WALL
EXTERIOR OF WALL
SEAL ANNULAR OPENING
WITH WATER TIGHT
MASTIC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
P001
BID DOCUMENTS
PLUMBING SCHEDULES, LEGEND AND
DETAILS
NO SCALE
CLEVIS HANGER DETAIL
PLUMBING GENERAL NOTES
wt DESCRIPTION
1 NO BURIED PIPING UNDER THE SLAB SHALL BE INSTALLED WITHIN THE FOOTING BEARING.
2 CUTTING OF OPENINGS IN EXISTING CONSTRUCTION ASSOCIATED WITH THE PIPING SYSTEMS
SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR.
3 ALL BURIED PRESSURE PIPING INSTALLED SHALL BE A MINIMUM OF 36" BELOW FINISHED
GRADE TO TOP OF PIPE.
4 THE ISOMETRIC IS SCHEMATIC IN NATURE AND PROVIDED FOR GENERAL ROUTING AND
CLARIFICATION THE ISOMETRIC SHALL NOT BE USED FOR A SPECIFIC ESTIMATE TAKE-OFF OF
PIPE LENGTHS AND FITTINGS.
5 THE PLUMBING CONTRACTOR'S WORK SHALL BE COORDINATED IN SUCH A MANNER AS TO
NEVER BLOCK SERVICE PATHWAYS TO AND FROM ANY BUILDING AND TO MINIMIZE
INTERFERENCE WITH SITE ACCESSIBLITY.
6 THE PLUMBING CONTRACTOR IS REQUIRED TO PROVIDE 3" MINIMUM DURABLE PRINTED
PLASTIC WARNING TAPE FOR EXTERIOR METALLIC PIPING WITHIN THE SCOPE OF HIS
CONTRACT. THE WARNING TAPE SHALL BE IDENTIFIED FOR THE SPECIFIC UTILITY
7 THE PLUMBING CONTRACTOR IS REQUIRED TO PROVIDE 2" MINIMUM DETECTABLE TRACER
WIRE FOR EXTERIOR NON-METALLIC PIPING DISTRIBUTION WITHIN THE SCOPE OF HIS
CONTRACT. THE TRACER WIRE SHALL BE IDENTIFIED FOR THE SPECIFIC UTILITY.
8 ALL DEMOLISHED MATERIALS SHALL BE REMOVED AND DISPOSED OFF-SITE.
9 THE CONTRACTOR SHALL PROVIDE DAILY CLEAN-UP OF DEBRIS ASSOCIATED WITH THIS
SCOPE OF WORK.
10 THE PLUMBING CONTRACTOR'S WORK SHALL BE COORDINATED IN SUCH A MANNER AS TO
NEVER BLOCK SERVICE PATHWAYS TO AND FROM THIS BUILDING.
11 EXISTING PIPE SIZES ARE BASED ON LIMITED AS-BUILT DRAWINGS AND NON-DESTRUCTIVE
FIELD INVESTIGATIONS. THE CONTRACTOR SHALL VERIFY THE EXISTING PIPE SIZES AND
MATCH NEW PIPE SIZES ACCORDINGLY.
12 THE ISOMETRIC IS SCHEMATIC IN NATURE AND PROVIDED FOR GENERAL ROUTING AND
CLARIFICATION THE ISOMETRIC SHALL NOT BE USED FOR A SPECIFIC ESTIMATE TAKE-OFF OF
PIPE LENGTHS AND FITTINGS.
13 COORDINATE VERTICAL PIPING WITH ARCHITECTURAL PLANS FOR EXACT LOCATION OF RISER.
14 SLEEVES FOR PIPING PASSING THROUGH BELOW SLAB FOUNDATION WALLS SHALL BE
COORDINATED AND PROVIDED BY THE PLUMBING CONTRACTOR.
15 PIPE HANGERS AND CONCRETE INSERTS UTILIZED FOR THIS PROJECT SHALL BE PROVIDED BY
THE PLUMBING CONTRACTOR. THIS INCLUDES ALL SUPPLEMENTAL STEEL, ETC.
16 THE VA MIAMI IS UNDERGOING A SIGNIFICANT WATER SYSTEM CHANGE TO CONVERT WATER
SUPPLY ON FLOORS FROM VERTICAL TO HORIZONTAL. 10TH A/B, 10TH C/D, 11TH A/B, 12TH A/B
AND 12 C/D AND FLOORS SIX THROUGH NINE ARE CURRENTLY SUPPLIED BY THE ORIGINAL
COLD, HOT AND HOT WATER RETURN PIPING THAT IS “VERTICALLY” SUPPLIED BY MULTIPLE
VERTICAL RISERS IN WALLS. 11TH C/D IS ALREADY “HORIZONTAL” CONVERTED.
17 THE CONTRACTOR SHALL ANTICIPATE AND EXPECT THAT THE ORIGINAL “VERTICAL” SYSTEM
AND THE NEW “HORIZONTAL” SYSTEM WILL OPERATE IN PARALLEL WHILE IN CONSTRUCTION
AND FOR THE FUTURE UNTIL THE ENTIRE SYSTEM HAS BEEN CONVERTED TO “HORIZONTAL”.
ONCE TOTALLY CONVERTED IN THE FUTURE THE “VERTICAL SYSTEM” CAN BE REMOVED OR
ABANDONED.
18 ON ANY FLOOR OR WING, THE NEW HORIZONTAL SYSTEM SHALL BE INSTALLED WITH FIXTURE
BRANCHES TO BRANCH VALVES, TESTED AND DISINFECTED PRIOR TO “ONE BY ONE” OR
“FIXTURE BY FIXTURE” SWAP-OVERS FROM OLD “VERTICAL” SYSTEM SUPPLY TO NEW
“HORIZONTAL” SYSTEM SUPPLY. FIXTURE BRANCHES FROM OLD RISER SYSTEM SHALL BE
CAPPED IN WALLS WHERE NEW FIXTURE STUB-OUTS FROM NEW SYSTEM IS INSTALLED.
19 PIPE ROUTING OF MAINS SHOWN IS DIAGRAMATIC AND INTENDED TO MINIMIZE FIXTURE
BRANCH LENGTHS IN ACCORDANCE WITH VA PLUMBING GUIDE. CONTRACTOR SHALL OFF-SET
AND REROUTE PIPING AS REQUIRED TO AVOID OBSTACLES AND INTERFERENCE WITH
EXISTING SYSTEMS WHILE MAINTAINING MINIMUM FIXTURE BRANCH EXTENSIONS.
3/8"
NO SCALE
NPS 2 AND SMALLER VALVE REPLACEMENT
NO SCALE
NPS 2 1/2 TO NPS 6 VALVE REPLACEMENT
NO SCALE
VALVE REPLACEMENT DETAILS
NO SCALE
BALANCING VALVE REPLACEMENT
EXISTING VALVE REPLACEMENT: REFERENCED TO THE FIRST, SECOND, THIRD AND ELEVENTH
FLOORS:
1. A VALVE REPLACEMENT PHASING PLAN SHALL BE PROVIDED TO THE OWNER TWO WEEKS IN
ADVANCE TO SCHEDULE ALL REQUIRED SHUTDOWNS AND ADJUSTMENTS TO THE HOSPITAL
OPERATIONS.
2. ALL EXISTING VALVES SHALL BE CONSIDERED INSTALLED IN TIGHT SEMI-ACCESSIBLE CEILING
CAVITIES.
3. EXISTING VALVES SHALL BE ACCESSIBLE THROUGH THE LAY-IN CEILING.
4. ALL REMOVED DAMAGE COMPONENTS SHALL BE REPLACED WITH NEW COMPONENTS PAINTED
TO MATCH THE EXISTING WHERE APPLICABLE.
5. VALVE ACCESS MAY REQUIRE REMOVAL AND REPLACEMENT OF SELECTIVE BUILDING
COMPONENTS BY LICENSED TRADES BUT NOT LIMITED TO THE BELOW:
A. CEILING TILE
B. CEILING TILE SUPPORT GRID
C. LIGHTS
D. SMOKE DETECTORS
E. FIRE ALARM DEVICES
F. ELECTRICAL CONDUIT
G. COMMUNICATION CABLE
H. DUCTWORK
I. MISCELLANEOUS PIPING SYSTEMS
CRAWLSPACE PIPING PHASING PLAN
PHASING:
1. THE CONTRACTOR SHALL PROVIDE A MASTER PHASING PLAN FOR REVIEW BY THE
VA PRIOR TO COMMENCING WORK.
2. THE PROPOSED PHASING SHALL INCLUDE BUT IS NOT LIMITED TO THE FOLLOWING:
A. INSTALL NEW FULL LINE SIZE PIPING TEES WITH THREE NEW VALVES AT EACH TEE
FITTING PORT ON THE EXISTING COLD WATER BRANCH PIPING.
B. THE NEW TEE FITTING AND VALVES WILL ALLOW:
• ISOLATION OF THE NEW TO EXISTING CONNECTION TO BE ABANDONED
• ISOLATION OF THE EXISTING RISER
• CONNECTION POINT FOR THE NEW PIPING TO THE NEW 8” WATER MAIN
NO SCALE
BELOW GRADE PIPE PENETRATION
C W
C W
C W
CW
C W
CW
C W
C W
3"
CW
#2
3"
3"
3"
3"
3"
3"
3"
3"
3"
CW
#1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD101
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0"
0 5' 10' 15' 30' KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
SYSTEM. ALL SYSTEM COMPONENTS REQUIRED FOR THE COMPLETE
SYSTEM FUNCTION SHALL BE PROVIDED BY THE CONTRACTOR.
CW
C W
C W
C W
CW
C W
CW
CW
C W
C W
C W
C W
CWCW
C
W C
W
2"
CW
#6
2"
CW
#4
5"
CW
#5
4"
CW
#3
2"
5"
2"
5"
6"
5"
2"
5"
2"
2"
2"
2" 2"
2"
6"
5"
6"
5"
4"
3"
4"
3"
4"
4"
3"
3"
3"3"
3"
THE PIPING TO THE OUT
BUILDING SHALL REMAIN.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD102
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0" 0 5' 10' 15' 30'
KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
C W
C W
C W
C W
CWCWCWCW CWCW
4"
4"
4"
8"
6"
8" 8" 8"
6"
8"8"8" 8"8"
6"
8"
6"
LOCATION OF THE WATER QUALITY
MONITORING STATION
1. THE MONITORING STATION TO REMAIN
FOR RECONNECTION UNDER THE NEW
WORK SCOPE.
2. REMOVE THE EXISTING 3/4"
MONITORING STATION PIPING.
THE INTERIOR 8" WATER MAIN LOCATED
BELOW THE CRAWLSPACE DIRT/GRAVEL
FLOOR SHALL BE ABANDONED IN-PLACE AS
NOTED WITHIN THE DEMOLITION NOTES.
THE EXTERIOR 8" WATER MAIN LOCATED
BELOW THE PLAZA SLAB SHALL BE
ABANDONED IN-PLACE AS NOTED
WITHIN THE DEMOLITION NOTES.
THE INTERIOR 8" WATER MAIN LOCATED
BELOW THE CRAWLSPACE DIRT/GRAVEL
FLOOR SHALL BE ABANDONED IN-PLACE AS
NOTED WITHIN THE DEMOLITION NOTES.
4"
CW
#7
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD103
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"1
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0" 0 5' 10' 15' 30'
KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
C W
C W
2"
2"
2"
2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD104
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"1
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0"
0 5' 10' 15' 30' KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
C W
CW CW CW
C W
C W
CW
CW
CWCW
2"
CW
#11
2"
CW
#10
2"
CW
#9
2"
2"
2"
2" 2"2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD105
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0" 0 5' 10' 15' 30'
KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
CWCW
W
CWCWCWCW
C W
C W
CW
CWCWCWCW
8" 8" 8"
6"
8" 8"
6"
6"
6"
6"
4"
4"
4"
2"
4"
4"
4"
2"
THE EXTERIOR 8" WATER MAIN LOCATED
BELOW THE LOADING DOCK AREA SLAB
SHALL BE ABANDONED IN-PLACE AS
NOTED WITHIN THE DEMOLITION NOTES.
THE INTERIOR 8" WATER MAIN LOCATED
BELOW THE CRAWLSPACE DIRT/GRAVEL
FLOOR SHALL BE ABANDONED IN-PLACE
AS NOTED WITHIN THE DEMOLITION
NOTES.
6"
LOCATION OF THE WATER QUALITY MONITORING STATION
1. THE MONITORING STATION TO REMAIN AND IS NOT
WITHIN THIS SCOPE OF WORK.
CW
C W
C W
4"
CW
#15
2"
CW
#14
2"
CW
#16
DEMOLISH THE PIPING TO
A POINT 24" FROM THE
CRAWLSPACE WALL.
8"
CW
#17
C W
CW
CW
CWCW
DEMOLISH THE PIPING TO THE
EXISTING 2" BACKFLOW
PREVENTER INLET. THE BACKFLOW
PREVENTER, VALVES AND PIPING
DOWNSTREAM OF THE BACKFLOW
PREVENTER TO REMAIN.
C W
EXISTING
BACKFLOW
PREVENTER
EXISTING
PRESSURE
REDUCING
VALVE
2" 2"
THE EXISTING PIPING TO REMAIN AND
IS NOT WITHIN THIS SCOPE OF WORK.
THE EXISTING PIPING TO REMAIN AND
IS NOT WITHIN THIS SCOPE OF WORK.
THE EXISTING PIPING TO REMAIN AND
IS NOT WITHIN THIS SCOPE OF WORK.
3/4"
3/4"3/4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD106
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"1
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0" 0 5' 10' 15' 30'
KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD107
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0" 0 5' 10' 15' 30'
KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
THIS EXISTING WATER PIPING IS
NOT WITHIN THE SCOPE OF WORK.
8"
CW
#12
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD108
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0" 0 5' 10' 15' 30'
KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
C W
C W
CW CWCW
6"
4"
6"
4"
6"
6"
4" 4"
6"
CW
#13
DEMOLISH THE PIPING TO THE
UPSTREAM SIZE OF THE GATE
VALVE INCLUDING THE GATE
VALVE AND CHECK VALVE.
THE EXISTING PIPING TO REMAIN AND
IS NOT WITHIN THIS SCOPE OF WORK.
DEMOLISH THE PIPING TO THE
UPSTREAM SIDE OF THE FIRST
HORIZONTAL 90 DEGREE FITTING
AND CAP FOR RECONNECTION
UNDER THE NEW SCOPE OF WORK.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PD109
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING DEMOLITION
1/8" = 1'-0"1
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING DEMOLITION
1/8" = 1' - 0" 0 5' 10' 15' 30'
KEY PLAN
PD109 PD106
PD103
PD108 PD105 PD102
PD107 PD104 PD101
DEMOLITION NOTES:
PIPING:
1. ALL EXISTING EXPOSED COLD WATER PIPING SHALL BE REMOVED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. ALL PIPING MATERIALS SHALL BE DISPOSED
OFF SITE.
2. ALL EXISTING PIPING CONNECTIONS TO THE EXISTING BELOW GRADE 8”
WATER MAIN SHALL BE REMOVED TO THE 8” WATER MAIN TEE FITTING. THE
REMAINING FITTING SHALL BE CAPPED AND ABANDONED.
3. ALL ASSOCIATED EXISTING HANGERS AND SUPPORTS SHALL BE REMOVED
AND DISPOSED OFF-SITE.
4. ALL EXISTING VALVES ASSOCIATED WITH THE PIPING DEMOLITION SHALL
BE CLEANED AND RETURNED TO THE OWNER.
5. ALL 8” COLD WATER MAIN PIPING LOCATED WITHIN THE BUILDING
FOOTPRINT IS ROUTED BELOW THE CRAWL SPACE DIRT/GRAVEL FLOOR.
THIS PIPING SHALL BE ABANDONED IN-PLACE UNDER THE OUTSIDE UTILITY
SCOPE OF WORK. REFER TO DRAWINGS D-1, D-2 AND D-3 FOR NOTES
REFERENCING ABANDONING AND FILLING THE 8" WATER MAIN PIPE.
WATER QUALITY MONITORING STATIONS:
1. THE CONTRACTOR SHALL AS-BUILT AND DOCUMENT THE CONDITION OF
THE EXISTING MONITORING STATIONS.
2. EXISTING WATER QUALITY MONITORING STATIONS SHALL REMAIN FOR
RECONNECTION TO THE NEW COLD WATER PIPING SYSTEM. THE
MONITORING SYSTEMS SHALL BE PROTECTED DURING DEMOLITION. ALL
DAMAGE TO THESE SYSTEMS SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR.
3. THE CONTRACTOR SHALL REINSTALL THE MONITORING STATIONS.
4. A WATER QUALITY MONITORING TECHNICIAN APPROVED BY THE OWNER
AND ENGINEER SHALL COMMISSION THE MONITORING STATIONS TO A LIKE
NEW CONDITION.
5. REMOTE MONITORING SHALL BE PROVIDED TO THE BUILDING AUTOMATION
PD102
PD101
PD108
PD107
PD103
PD104
PD105
PD106
PD109
PP209
PP202
PP201
PP208
PP207
PP203
PP204
PP205
PP206
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PP100
BID DOCUMENTS
OVERALL PLUMBING PLAN -
CRAWLSPACE - PIPING REPLACEMENT
1" = 30'-0"
OVERALL PLUMBING PLAN - CRAWLSPACE
1" = 30' 0 30' 120'60'
KEY PLAN
PP209 PP206
PP203
PP208 PP205 PP202
PP207 PP204 PP201
0.1 0.8 1 2 3 4 5 6 7 8 9 9.3 10 10.3 10.40.7
AA
A
A.8
B
B.1
B.3
B.6
C
C.2
C.9 D
C.2
C
B.3
B.1
A.6
A.2
AA
D.1
B.4
B.5
B
A
A.3
C
A
TELEPHONE
101A
TOILET
STORAGE
101B
TELEPHONE EQUIPMENT
101C
BATTERY ROOM
M1 11 1
MEA-25
OPERATORS
47.2 sq.ft.
108.3 sq.ft.
822.1 sq.ft.
225.6 sq.ft.
497.1 sq.ft.
GENERAL
PP219
PP212
PP211
PP218
PP217
PP213
PP214
PP215
PP216
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PP101
BID DOCUMENTS
OVERALL PLUMBING PLAN - FIRST
FLOOR VALVE REPLACEMENT
1" = 30'-0"
OVERALL PLUMBING PLAN - FIRST FLOOR
1" = 30' 0 30' 120'60'
KEY PLAN
PP219 PP216
PP213
PP218 PP215 PP212
PP217 PP214 PP211
ROOF
PP221
PP222
PP221
PP221
PP221
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PP102
BID DOCUMENTS
OVERALL PLUMBING PLAN - SECOND
FLOOR VALVE REPLACEMENT
1" = 30' 0 30' 120'60'
KEY PLAN
PP221
PP221
PP221
PP222
PP221
1" = 30'-0"1
OVERALL SECOND FLOOR PLAN
STAIR
#12
#3
#2
200 V
PYXIS
326 324
317319321
324A 320
318 316
C3 1-7
313 312 309 308 E3 1
C3-5-7
300301
344342341
311 310
314315
337336334
331 329
333332 S3 2
S3 1
C3 1-7
C3 3-7
C3 2-7
C3 6-7
C3 1-7
R.D.
ROOF
CHASE
MECHANICAL
ELEVATOR
ANIMAL
FREEZER
ELEVATOR
SERVICE
GENERAL HISTOPATHOLOGY LAB.
OFFICEOFFICEPHYSIOLOGICAL LAB.
DARK ROOM
FREEZER
OFFICE PHYSIOLOGICAL
BIOCHEMICAL LAB. BIOCHEMICAL LAB.
CORRIDOR
BIOCHEMICAL LAB. BIOCHEMICAL LAB.
F.E.C.
PHYSIOLOGICAL LAB. PHYSIOLOGICAL LAB.
F.E.C.
ELECT. RM. & DUCT SPACE
REFRIGERATOR
OFFICE
COMPUTER
LOUNGE
TISSUE CULTURE
R.D.
EQUIPMENT
OFFICE
LOBBY
WOMEN'SMEN'S
E.W.C.
ELEV.ELEV.
UP
DN.
BIOCHEMICAL LAB.
F.E.C.
BIOCHEMICAL LAB.MOLECULAR BIOLOGY
GENERAL LAB. BIOCHEMICAL LAB.
F.E.C.
BIOCHEMICAL LAB.
PHYSIOLOGICAL LAB.BIOCHEMICAL LAB.
BIOCHEMICAL LAB.
F.E.C.
BIOCHEMICAL
BIOCHEMICAL LAB.
BIO-LAB.
MEN'S
E.W.C.
UP
DN.
BIOCHEMICAL LAB.
COMMON INSTRUMENTS WOMEN'S
HOUSEKEEPING
BIOCHEMICAL LAB.GLASS WASH
STAIR
STAIR STORAGE
STORAGE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CLOSET
ROOM
LAB.
REFRIGERATOR
RESTROOM
RESTROOM
LAB.
BIOCHEMICAL
LAB.
BIOCHEMICAL
LAB.
LAB.
RESTROOM RESTROOM
ROOM
M3 1 7
MEA-16
BIOCHEMICAL LAB.
PP234
PP233
1PP231
PP232
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PP103
BID DOCUMENTS
OVERALL PLUMBING PLAN - THIRD
FLOOR VALVE REPLACEMENT
1" = 30'-0"
OVERALL THIRD FLOOR PLAN
1" = 30' 0 30' 120'60'
KEY PLAN
PP232
PP234
PP231 PP233
PP241
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PP104
BID DOCUMENTS
OVERALL FLOOR PLAN - TENTH FLOOR
PLUMBING PLAN
1/16" = 1'-0"1
OVERALL PLUMBING PLAN - TENTH FLOOR - HORIZONTAL CONVERSION
1/16" = 1' - 0" 0 5' 10' 20' 30' 60'
KEY PLAN
PP241
PP242
C
D
A
B
10TH FLOOR C/D PLUMBING FIXTURE SCHEDULE
FIXTURE DESCRIPTION CW HW
CW
FU
HW
FU
FIXTURE
COUNT NOTES
P-103 WATER CLOSET 1" 170 0 17
P-418 LAVATORY 19.9 18.5 17
P-701 SHOWER 1/2" 1/2" 16 12 4
Grand total 205.9 30.5
PLUMBING FIXTURE SCHEDULE NOTES:
1. ALL WATER CLOSET TOILET SEATS AND FLUSH VALVES/BED PAN WASHERS SHALL BE REPLACED. REFER TOT HE
SPECIFICATIONS.
2. ALL LAVATORY FAUCETS, STOP VALVES, STOP VALVE RISERS, P-TRAPS AND ESCUTCHEONS SHALL BE REPLACED.
REFER TO THE SPECIFICATIONS.
3. ALL SHOWER SUPPLY VALVES SHALL BE REPLACED. REFER TO THE SPECIFICATIONS.
GENERAL:
A. ALL EXISTING CHINA FIXTURES TO REMAIN.
B. ANY PHYSICAL DAMAGE ON THE CHINA FIXTURES PRIOR TO STARTING THE NEW WORK SHALL BE PHOTOGRAPHED, DOCUMENTED PER ROOM AND THE INFORMATION FORWARDED TO THE ARCHITECT.
C. ALL CHINA FIXTURES DAMAGED AFTER THE START OF NEW WORK SHALL BE REPLACED BY THE CONTRACTOR.
1/2" 1/2"
10TH FLOOR C/D 2/12" LOOPED COLD WATER MAIN - COLD WATER = 92 GPM
10TH FLOOR C/D 1-1/4" LOOPED COLD WATER MAIN - HOT WATER = 19 GPM
DEMOLITION SCOPE OF WORK AT EACH PLUMBING FIXTURE:
1. THE EXISTING PLUMBING FIXTURE SHALL REMAIN.
2. THE CONTRACTOR SHALL INCLUDE REMOVING AND REPLACING THE EXISTING PLUMBING FIXTURE TO ALLOW
ACCESS TO THE EXISTING PIPING.
3. THE EXISTING PIPING SERVING THE EXISTING PLUMBING FIXTURE SHALL BE REMOVED BACK TO AN ACTIVE MAIN
AND CAPPED.
4. REFER TO THE ARCHITECTURAL DRAWINGS ALL BUILDING COMPONENT DEMOLITION.
PP235
PP236
PP244
PP243
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PP105
BID DOCUMENTS
OVERALL FLOOR PLAN - ELEVENTH
FLOOR PLUMBING PLAN
1" = 30'-0"
OVERALL PLUMBING PLAN - ELEVENTH FLOOR- VALVE REPLACEMENT
1" = 30' 0 30' 120'60'
KEY PLAN
PP244
PP243
C
D
A
B
1" = 30'-0"
OVERALL PLUMBING PLAN - ELEVENTH FLOOR - HORIZONTAL CONVERSION
PLUMBING FIXTURE SCHEDULE NOTES:
1. ALL WATER CLOSET TOILET SEATS AND FLUSH VALVES/BED PAN WASHERS SHALL BE REPLACED. REFER TOT HE
SPECIFICATIONS.
2. ALL LAVATORY FAUCETS, STOP VALVES, STOP VALVE RISERS, P-TRAPS AND ESCUTCHEONS SHALL BE REPLACED.
REFER TO THE SPECIFICATIONS.
3. ALL SHOWER SUPPLY VALVES SHALL BE REPLACED. REFER TO THE SPECIFICATIONS.
GENERAL:
A. ALL EXISTING CHINA FIXTURES TO REMAIN.
B. ANY PHYSICAL DAMAGE ON THE CHINA FIXTURES PRIOR TO STARTING THE NEW WORK SHALL BE PHOTOGRAPHED, DOCUMENTED PER ROOM AND THE INFORMATION FORWARDED TO THE ARCHITECT.
C. ALL CHINA FIXTURES DAMAGED AFTER THE START OF NEW WORK SHALL BE REPLACED BY THE CONTRACTOR.
31/2" 1/2"
2/12" LOOPED COLD WATER MAIN - COLD WATER = 122 GPM
1-1/4" LOOPED COLD WATER MAIN - HOT WATER = 24 GPM
11TH FLOOR PLUMBING FIXTURE SCHEDULE
FIXTURE DESCRIPTION CW HW
CW
FU
HW
FU
FIXTURE
COUNT NOTES
P-103 WATER CLOSET 1" 320 0 32
P-418 LAVATORY 1/2" 1/2" 28 20 37
P-701 SHOWER 24 18 30
Grand total 372 38
DEMOLITION SCOPE OF WORK AT EACH PLUMBING FIXTURE:
1. THE EXISTING PLUMBING FIXTURE SHALL REMAIN.
2. THE CONTRACTOR SHALL INCLUDE REMOVING AND REPLACING THE EXISTING PLUMBING FIXTURE TO ALLOW
ACCESS TO THE EXISTING PIPING.
3. THE EXISTING PIPING SERVING THE EXISTING PLUMBING FIXTURE SHALL BE REMOVED BACK TO AN ACTIVE MAIN
TEL
#9
#10
DUCT
SPACE
#4
#5#2
#3
#7
#8
E.W.C.
DUCT
SPACE
FHC
F.H.C.
C
EN
TR
AL
ST
AT
IO
N
FHC
ROOF
TERRACE
F.E.C.
PNEUMATIC
TUBE
DUCT
SPACE
B1230
CONFERENCE
B1230A
B1231
OFFICE
B1231A
B1231B
B12324 BEDS
ROOM
B1232B
B1232A
B1228
OFFICE
B1228B
B11228A
B1227A
B1227
OFFICE
B1227B
B1226C
OFFICE
B1226D
B1226B
OFFICE
B1226A
B1226
RESPIRATORY B1234
H O U S E K E E P
IN
G
B1233SPD SUPPLY
RM
B A
G E N E R A L
B1235
E Q U
IP
M E N T
S T O R A G E
B1236
OFFICE
F.H.C.
B12251 BED
ROOM
B1225A
B1224
OFFICE
B1224A
B1217
STAFF
TOILET
B1216
MEDROOM
B1215
GENERAL
STORAGE
B1214A
OFFICE
B1214
NURSE
STATION
B1213WAITING
ROOM
A1206A
A12061 BED
ROOM
A1207B
TREATMENT
A1207B
A1207A
A1208B2 BEDS
ROOM
A1208A
A1208D
A1208C2 BEDS
ROOM
A1209B2 BEDS
ROOM
A1209A
A1209C2 BEDS
ROOM
A1209D
A1210EXAM.
ROOM
A1210A
A1211CONSULT
ROOM
B1222A
B1223B
OFFICE
B1223
VEST.
B1223A
B1223C
OFFICE
B1223D
OFFICE
B1222B
B1222
OFFICE
B1221
OFFICE
B1221A T
1T E L E P H O N E
R O O M
B1218
OFFICE
B1219
EQUIPMENT
E12
ELECTRIC
ROOM
A1204
DERMATOLOGY
A1205ADOCTOR
OFFICE
A1205ASSIST.
CHIEFSKIN
CANCER
A1203
DERMATOLOGY
B1211
SOILED
LINEN
C H
UTE
B1210
DERMATOLOGYEXAM
ROOM
B1212
SURGICAL
B1209
LOUNGE
B1208
MEDICAL
B1205
HUB
CLO.
B1206
OFFICE
B1206A
0FFICE
B1204
TOILET
B1237
LOCKER
B1237A
ELEVATOR
LOBBY
B1201
TOILET
ELEVATOR
LOBBY
A1201
CHIEF
B1240
EMS
B1230B
A1209
A1208
B1229
E .W .C
ISOLATION
RESPIRATORY
ISOLATION
RESPIRATORY
ISOLATION
RESPIRATORY
ISOLATION
EXAM
ROOM CUTANEOUS
SURGERY
COORDINATOR
STORAGE
STORAGE
DERMATOLOGY
#6#1
D1209
OFFICE
D1208
OFFICE
D1207A2
BEDS
ROOM
D1207
D1207A1
D1206A2
BEDS
ROOMD1206
D1206A1
D1205A2
BEDS
ROOM
D1205
D1205A1
D1204A2
BEDS
ROOM
D1204A1
D1204
D1203A D1203
D1203A1
D1202A
C1222AC1222
D1202
D1202A1
C1221A
PATIENT
BED
C1221
C1220CLEAN
STORAGE
WHEEL
CHAIR
ALCOVE
C1218
CLEAN
UTIL
C1217A1
BED
ROOM
C1216A1
BED
ROOM
C1215A1
BED
ROOM
C1217
C1216 C1215
C1217A1 C1216A1 C1215A1 C1214A1
C1214
C1214A1
BED
ROOM
C1213
C1213A1
BED
ROOM
C1213A1
C1211A1
BED
ROOM
C1212A1
BED
ROOM
C1209A1
BED
ROOM
C1210A1
BED
ROOM
C1210 C1211 C1212
C1208A1
BED
ROOM
C1209
C1208A1 C1209A1 C1210A1 C1211A1
C1208
C1207A1
BED
ROOM
C1206A1
BED
ROOM
C1207C1206
C1207A1C1206A1
C1204B
COMPUTER
ROOM
C1204
C1204A C1205
NOURISHMENT
STATION
C1201A
MEDICATION
C1202
SOILED
UTILITY
C1203
REPORTS
C A
H O U S E K E E P
IN
G
C1201B
NURSE
MANAGER
C1201
NURSES
STATION
C1201C
PHYSICIAN'S
ASSIST.
D1201
LOUNGE STRETCHER
ALCOVE
D1201A
LOCKERS
D1216A2
BEDS
ROOM
D1216
D1216A1
D1217
CLEAN
LINEN
D1215A2
BEDS
ROOM
D1214A2
BEDS
ROOM
D1215
D1214
D1215A1
D1214A1
D1213A2
BEDS
ROOM
D1212B
SURGICAL
SUPPLY
D1211
PHARMACY
D1210TELEMETRY
RM
D1213
D1212
D1212A
D1213A1
F.H.C.
E.W.C.
D1201A2
D1201A1
F.H.C.
C1212A1
F.H.C.
T12
TELEPHONE
ROOM
E12
ELECTRIC
ROOM
S12
STAIR
S12
STAIR
S12
STAIR
S12
STAIR
S12
STAIR
B1206B
OFFICE
C12 2
CORRIDOR
C12 3
CORRIDOR
C12 6
CORRIDOR
C12 1
CORRIDOR
C12 8
CORRIDOR
B1238B
OFFICE
B1238C
OFFICE
B1239A
CLINICAL
B1239B
RESEARCH
B1238A
GENERAL
B1238 B1239
SECRETARY
B1239C
SPECIAL
BEDS
ROOM
OFFICE
IMMUNOLOGY
UNIT
DIRECTORDIRECTOR
SPECIAL
IMMUNOLOGY
UNIT
E12 2A
ELECTRIC
ROOM
E12 1A
ELECTRIC
ROOM
RESTROOM
RESTROOM
RESTROOM
GENERAL
STORAGE
STORAGE
SHOWER
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOM
STORAGE
SUPPLY
B1203
A1202
RESTROOM
RESTROOM
RESTROOM
SHOWER
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOM RESTROOM
RESTROOM
RESTROOM
RESTROOM RESTROOM RESTROOM RESTROOM RESTROOM RESTROOM
RESTROOMRESTROOMRESTROOMRESTROOMRESTROOM
GENERAL
STORAGE
GENERAL
STORAGE
GENERAL
STORAGE
RESTROOM
GENERAL
STORAGE
GENERAL
STORAGE
RESTROOM
RESTROOM
GENERAL
STORAGE
RESTROOM
RESTROOM
EMS
STORAGE
S T O R A G E
PATIENT
BED
PATIENT
BED
L
L L
L L
L L
L L
L L
L L
L L
L L
L L
L L
L
L
L L L L
L
D3 E2 E8 F6
DCB
G H J KJ.9 LK.8 M.3M N P Q R
10.8
10.5
10.2
9.5
8.9
8.8
7.4
7.2
5.8
5.1
4.1
E F
PP246
PP245
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PP106
BID DOCUMENTS
OVERALL FLOOR PLAN - TWELFTH
FLOOR PLUMBING PLAN
1/16" = 1'-0"1
OVERALL PLUMBING PLAN - TWELFTH FLOOR - HORIZONTAL CONVERSION
1/16" = 1' - 0" 0 5' 10' 20' 30' 60'
KEY PLAN
PP246
PP245
C
D
A
B
12TH FLOOR PLUMBING FIXTURE SCHEDULE
FIXTURE DESCRIPTION CW HW
CW
FU
HW
FU
FIXTURE
COUNT NOTES
P-103 WATER CLOSET 1" 440 0 44
P-418 LAVATORY 77.5 63.5 89
P-701 SHOWER 1/2" 1/2" 140 105 35
Grand total 657.5 168.5
PLUMBING FIXTURE SCHEDULE NOTES:
1. ALL WATER CLOSET TOILET SEATS AND FLUSH VALVES/BED PAN WASHERS SHALL BE REPLACED. REFER TOT HE
SPECIFICATIONS.
2. ALL LAVATORY FAUCETS, STOP VALVES, STOP VALVE RISERS, P-TRAPS AND ESCUTCHEONS SHALL BE REPLACED.
REFER TO THE SPECIFICATIONS.
3. ALL SHOWER SUPPLY VALVES SHALL BE REPLACED. REFER TO THE SPECIFICATIONS.
GENERAL:
A. ALL EXISTING CHINA FIXTURES TO REMAIN.
B. ANY PHYSICAL DAMAGE ON THE CHINA FIXTURES PRIOR TO STARTING THE NEW WORK SHALL BE PHOTOGRAPHED, DOCUMENTED PER ROOM AND THE INFORMATION FORWARDED TO THE ARCHITECT.
C. ALL CHINA FIXTURES DAMAGED AFTER THE START OF NEW WORK SHALL BE REPLACED BY THE CONTRACTOR.
1/2" 1/2"
2/12" LOOPED COLD WATER MAIN - 12th FLOOR A/B - COLD WATER = 82 GPM
1-1/4" LOOPED COLD WATER MAIN - 12th FLOOR A/B - HOT WATER = 30 GPM
TWO 2" COLD WATER MAINS - 12th FLOOR C/D - COLD WATER = 82 GPM
TWO 1-1/4" HOT WATER MAINS - 12th FLOOR C/D - HOT WATER = 30 GPM
THE 12TH FLOOR C/D WATER SYSTEM IS SUPPLIED FROM THE EXISTING 11TH
FLOOR HORIZONTAL CONVERSION.
THE 12TH FLOOR A/B WATER SYSTEM IS SUPPLIED FROM THE NEW 11TH FLOOR
HORIZONTAL CONVERSION PIPING LOOP.
DEMOLITION SCOPE OF WORK AT EACH PLUMBING FIXTURE:
1. THE EXISTING PLUMBING FIXTURE SHALL REMAIN.
2. THE CONTRACTOR SHALL INCLUDE REMOVING AND REPLACING THE EXISTING PLUMBING FIXTURE TO ALLOW
ACCESS TO THE EXISTING PIPING.
3. THE EXISTING PIPING SERVING THE EXISTING PLUMBING FIXTURE SHALL BE REMOVED BACK TO AN ACTIVE MAIN
CW CW
W
CW
C W
C W
CW
C W
3"
CW
#2
3"
3"
3"
3"
3"
3"
CW
#1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
590 MEANS STREET NW
STE. 200
ATLANTA, GA 30318
F
440 Martin Luther King Jr. Blvd Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
I:
\P ro je c ts
\8
\8
-T
M M
M ia m i V
A M
C U p g ra d e W a te r M a in s \B
IM
-C
A D
\ C la ri ty
\R e v it \P
\8
T
M M
M ia m i V
A M
C c ra w ls p a c e s t-n d -3 r d -1 th f lo o rs o n ly
.r v t
UPGRADE WATER MAINS TO
BUILDING 1 FCA-D
MIAMI VAMC
07-08-2020 RWC AWB
546-19-102
PP201
BID DOCUMENTS
ENLARGED PLUMBING PLAN -
CRAWLSPACE - PIPING NEW WORK
1/8" = 1' - 0"
0 5' 10' 15' 30' KEY PLAN
PP209 PP206
PP203
PP208 PP205 PP202
PP207 PP204 PP201
1/8" = 1'-0"
ENLARGED PLUMBING PLAN - CRAWLSPACE - PIPING NEW WORK
NEW WORK:
1. ALL NEW EXPOSED COLD WATER PIPING SHALL BE CONNECTED TO THE
FIRST ELBOW AT THE EXISTING VERTICAL RISER SCHEDULED TO REMAIN,
UNLESS NOTED OTHERWISE. PROVIDE ALL PIPING MATERIALS TO
COMPLETE THE NEW TO EXISTING CONNECTION.
2. ALL NEW PIPING SHALL BE ROUTED AT APPROXIMATELY 4’-0” TO THE PIPE
CENTERLINE BELOW THE BOTTOM OF THE FIRST FLOOR SLAB. FIELD
VERIFY THE EXISTING CRAWL SPACE CONDITIONS. PIPING ELEVATIONS
SHALL BE ADJUSTED TO ACCOMMODATE EXISTING CONDITIONS AND
EQUIPMENT CLEARANCES.
3. NEW VALVES WITH VALVE TAGS SHALL BE PROVIDED AT EACH BRANCH
TAKE-OFF. VALVE TAGS SHALL BE REFERENCED…