This is a Questions & Answers document for RFQ 47QSWC26Q0021 that clarifies specifications for an automatic control box and power pigtail system for a Flygt pump installation.

The automatic control box must be a weatherproof enclosure that includes a 25-foot power pigtail wired to a control box disconnect switch, a 50-foot power cable extending from the control box to the pump, and two 40-foot floats for low-level and high-level detection. The control box must contain a run status light, hand/off/auto switch, power disconnect switch, and contactor reset button, with all components wired and installed to operate as a fully functional automatic control system. Reference images provided show the exterior control panel with safety labeling and the internal wiring and component configuration within the weatherproof enclosure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions & Answers- RFQ (47QSWC26Q0021)

Q1: “Would you be able to provide some clarification/detail on the “automatic control box” & “power pigtail”? These are separate items that would not be supplied with the pump from Flygt.”

A1: “Please see the attached pictures. We are looking for a 25’ power pigtail to be wired to the control box disconnect switch, a 50’ power cable to be wired from the control box to the pump, and 2 – 40’ floats (low level, high level). There should be a run status light, hand/O/auto switch, Power disconnect Switch, contactor reset button. All shall be wired and installed to operate as an “Automatic Control Box”. The box shall be weatherproof.”

File details come from the government source that posted it. Updated .