The document is a specification sheet for a switchboard enclosure with detailed technical requirements. The switchboard is constructed of stainless steel, NEMA 3R Flatroof type, composed of two 36" wide x 30" deep x 90" high sections - one for utility wire-pull and another for bus bars and breakers. Specific technical specifications include a 1200A adjustable 3-phase main breaker with a 65kA interrupt rating, copper bus bars and ground bus, six 225A 3-phase breakers, and a required voltage of 208Y/120V, 3-phase, 4-wire configuration. The specification sheet includes a schematic diagram illustrating the switchboard's front view, power flow, and floor pull details, providing a comprehensive technical overview of the required electrical equipment.

View the file

Other files

File Type Posted
QandA 47QSSC2Q0169.pdf PDF
Attachment 2 - Quote Sheet.xlsx XLSX spreadsheet

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS FOR ONE (1) Switchboard Enclosure

Minimum Characteristics are as follows:

Switchboard material: Stainless Steel

Type: NEMA 3R Flatroof

Switchboard to be composed of two (2) sections. Each section to be 36” Wide x 30” Deep x 90” High.

1st section is the utility, wire-pull section.

2nd section is to contain the buss bars and breakers.

Main breaker = 1200A Adj, 3 Phase.

Minimum Interrupt Rating = 65kA

Buss bar material: Copper

Ground Bus Material: Copper Ground Bus Bolted To Frame, (1) #6-350 kcmil Ground Lug

Need six (6) breakers = 225A, 3 Phase, Mechanical (1) #4-4/0, Thermal Mag Trip – Standard

Voltage Required = 208Y/120V, 3 Phase, 4-Wire