The document is an Attachment A detailing Salient Characteristics for a specific air conditioning unit manufactured by Thermal Zone, model RGEDZT120ACG222AAAA0. The detailed specifications include a 12-ton, 208/230V (3-phase) unit with a two-stage compressor, convertible airflow options, MicroChannel evaporator and condenser coil, Variable Frequency Drive (VFD) blower, and advanced diagnostic features like a dual 7-segment LED display and smart logic protection.
The related federal contract opportunity (Solicitation Number 47QSSC-25-Q-0160) is a one-time small business set-aside procurement for this air conditioning unit, managed by the GSA Federal Acquisition Service. The solicitation requires a brand name or equal unit that matches existing ductwork, with specific technical requirements including Trade Act Agreement compliance. The award will be made using a lowest price technically acceptable (LPTA) method, with a 30-calendar day delivery window after receipt of order to a San Diego, CA location. Vendors must submit quotes for all line items and comply with specific documentation and shipping requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment C - Instructions Military Standard 129 Compliance.pdf | ||
| Attachment B - Quote Submittal Worksheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Thermal Zone model RGEDZT120ACG222AAAA0
· Equal configurations will be considered, provided they meet or exceed the salient characteristics outlined herein. Additionally, they must match the ductwork.
· 12 ton 208/230V (3 phase)
· Two stage compressor
· Convertible airflow – vertical downflow or horizontal side flow
· Forkable base rails for easy handling and lifting
· MicroChannel evaporator and condenser coil
· Overflow condensate sensor
· Diagnostics with Dual 7-Segment LED display to meet code compliance
· One-Piece top cover and base pan with drawn supply and return opening
· Two-piece control door
· ¼ Turn fasteners on filter access door
· Color-coded and labeled wiring
· External lockable gauge ports
· TXV refrigerant metering system
· Solid-core liquid line filter drier
· High pressure and low pressure / loss of charge protection with built-in Smart Logic
· Variable Frequency Drive (VFD) blower
· The sheet metal cabinet uses 18-gauge material for structural components with an underlying coat of G90
· Fuse 60 AMP 250V class RK5 (3 ea)
· 60 Amp 240-Volt 3-pole, 3-phase Fused Outdoor General Duty Safety Switch (1 ea)
· Coil coating w/clear finish
· Ensure ductwork match
File details come from the government source that posted it. Updated .