Fire Alarm Drawings 02-14-22.pdf

PDF 2 MB Posted

Attached to
70159 GSA Fire Alarm Upgrade Federal contract opportunity
Solicitation number
47PH0623R0011
Issued by
General Services Administration Public Buildings Service Region 7

About this file

This document outlines a federal contract opportunity for a fire alarm system upgrade. The General Services Administration seeks to replace the existing fire alarm system at the Gallup Federal Building in Gallup, New Mexico with a new intelligent, addressable, and emergency voice/alarm communication system. The scope of work includes upgrading detectors, manual stations, voice and visual notification appliances, network node panels, remote power supplies, HVAC, elevator, security, and door interfacing. Offerors must provide a minimum sound level of 70dBA and intelligibility scale rating of 0.7 throughout all areas. The solicitation will be issued on December 6th, 2022 with proposals due January 10th, 2023 and award anticipated by March 6th, 2023. This procurement is set aside for small businesses with a size standard of $16.5 million. The period of performance is 225 days from notice to proceed. The contract will be awarded based on technical capability then price evaluation to the technically acceptable offeror with the lowest price.

View the file

Other files for this federal contract opportunity

Other files attached to 70159 GSA Fire Alarm Upgrade, newest first.
File Type Posted
Amendment 1.pdf PDF
Bid Schedule Template.xlsx XLSX spreadsheet
Past Performance Questionnaire.pdf PDF
Vendor Fitness Determination Training Manual.pdf PDF
SF1442 Gallup Fire Alarm 47PH0623R0011.pdf PDF
GSA 527.pdf PDF
Fire Alarm Specifications 11-03-2022.pdf PDF
Wage Determination NM20220024 dated 02-25-2022.pdf PDF
SOW GSA Fire Alarm Upgrade 11-15-2022.pdf PDF
Waste Mgmt Plan Reporting Template.xlsx XLSX spreadsheet

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM SYSTEM

SEQUENCE OF OPERATIONS MATRIX

GENERAL NOTES:

ALL WIRING ON TO BE INSTALLED IN 3/4" CONDUIT UNLESS

40% FOR 3 OR MORE CABLES,OR EXCEED 31% FOR TWO CABLES

ALL WIRING SHALL BE 14 AWG FPLP 2 CONDUCTOR CABLE

ALL SLC /NAC WIRING SHALL BE INSTALLED CLASS A WITH A MINIMUM SEPARATION OF 4 FOOT ON A HORIZONTAL PLANE OR

1 FOOT ON A VERTICAL PLANE.

VOICE INTELLIGIBILITY WILL BE FIELD VERIFIED.

ALL SPEAKER DEVICES SHALL BE TAPPED AT 1/4 WATT UNLESS OTHERWISE NOTED.

E F

F E

C T

S

CAUSE

MANUAL FIRE ALARM PULL STATION

SMOKE DETECTOR

ELEV. LOBBY SMOKE DET 1ST FLOOR

ELEV LOBBY SMOKE DET OTHER FLOOR

ELEVATOR MACH. RM. SMOKE DETECTOR

FLOW SWITCH

ACTIVATE ALARM SILENCE SWITCH

ACTIVATE GENERAL ALL CALL PAGE

ACTIVATE SELECT PAGE TO FLOOR

SMOKE DETECTOR IN HVAC UNIT

VALVE TAMPER

T R

A N

S M

IT

A

L A

R M

C O

N D

IT

IO

N O

F F

S

IT

E

T R

A N

S M

IT

T

R O

U B

L E

C O

N D

IT

IO

N O

F F

S

IT

E

T R

A N

S M

IT

S

U P

E R

V

IS

O R

Y C

O N

D

IT

IO

N

O F

F S

T

A N

S M

IT

A U

T O

S P

R

IN

K L E

R F

L O

W

S

A C

T

IV

A T

E A

L L S

T R

O B

E S

I N

B U

IL

D

IN

G

A C

T

IV

A T

E A

L L S

P E

A K

E R

S I N

B U

IL

D

IN

G

C

A L L E

L E

V O

P E

N T

O A

F F

E C

T E

D F

L O

O B

IE

S

T O

N

D F

L

R E

C A

L L E

L E

V O

P E

N T

O A

F F

E C

T E

D L

O B

B

IE

S T

O

S T

F L

A C

T

IV

A T

E I N

C A

R M

A C

H

IN

E R

O O

M S

D N

O T

IF

IC

A T

IO

N

L E

A S

E D

O O

R S

H E

L D

O P

E N

B Y

M A

G N

E T

IC

H O

L D

O P

E N

D E

V

IC

E S

S H

U T

D O

W N

A F

F E

C T

E D

H V

A C

U N

IT

S

S

IL

E N

C E

A L L A

C T

IV

E

A U

D

IB

L E

V

IS

IB

L E

A L A

R M

S

NOTES:A

C

T

IV

A T

E S

P E

A K

E R

S P

E R

F L O

O R

ALL REMOTE POWER SUPPLIES TO BE EQUIPPED WITH 12AH BATTERIES.

PROVIDE AC POWER SWITCH FOR EACH FACP FOR LOAD TESTING. DISCONNECT TO BE LOCATED NEXT TO CORRESPONDING FACP.

ALL CONTROL MODULES MUST BE LOCATED WITHIN 3' OF CORRESPONDING REMOTE POWER SUPPLIES.

PROVIDE A MINIMUM OF 1 CLASS 'A' SLC, 2 SPEAKER CIRCUITS, AND 2 STROBE CIRCUITS.

AREAWAY

DN

R A

M P

U P

R A

M P

U P

L A

N D

S C

A P

IN

G

PLANTER

P L A

N T

E R

P L A

N T

E R

P L A

N T

E R

PLANTERPLANTERPLANTERPLANTERPLANTERPLANTERPLANTER

P L A

N T

E R

S

ID

E W

A L K

S

ID

E W

A L K

SIDEWALKSIDEWALK

S

ID

E W

A L K

S

ID

E W

A L K

SIDEWALKSIDEWALK

S

ID

E W

A L K

SIDEWALK

SIDEWALK

S

ID

E W

A L K

FLAG POLE

S T

H

IR

D S

T

W. MESA AVE.

T O

P A

R K

IN

G

G A

R A

G E

B E

L O

W

BALLARD

GATE

FENCE

FENCE

FENCE

FENCE

Site Plan

GALLUP FEDERAL BUILDING

SOILS LABORATORY BUILDING

TIGHT FLEXIBLE CONDUIT MUST BE PROPERLY SUPPORTED BETWEEN BOX AND TAMPER/FLOW SWITCHES.

MONITOR MODULES SHALL BE MOUNTED ON WALL WITH LIQUID TIGHT FLEX CONNECTION TO TAMPER AND FLOW SWITCHES. LIQUID

THE MANUAL PULL STATION SHALL BE INSTALLED IN SAME LOCATION AS THE EXISTING MANUAL PULL STATION.

PROVIDE MR-201 OR APPROVED EQUAL.

UNLOCKING, DOOR HOLDERS, AND AHU CONTROLS. RELAYS SHALL BE HEAVY DUTY TYPE AND RATED A MINIMUM OF 10 AMPS.

AUXILIARY SLAVE RELAYS SHALL BE PROVIDED FOR INTERFACING TO ELEVATOR RECALL, SMOKE CONTROL SYSTEMS, HVAC, DOOR

FOOT WHERE THE CABLES ARE INSTALLED VERTICALLY.1ANDHORIZONTALLYINSTALLEDARECABLESTHE

A MINIMUM OF 4 FEET APART WHEREBEMUSTCONDUITSXCLASSORACLASSRETURNINGANDOUTGOINGOFPENETRATIONS

BE USED.WILLDRILLSCORETHATVERIFYACCEPTABLE.NOT

DRILL. HAMMER OR IMPACT DRILLS ARE COREABYPROVIDEDBESHALLFLOORSANDWALLSMASONRYOFPENETRATIONSALL

FMC OR MC CABLE.

BY THE GSA FIRE PROTECTION ENGINEER, CIRCUITS MAY BE RUN IN 3/4" MINIMUM ALLOWEDWHEREANDCEILINGSHARDABOVE

MECHANICAL PROTECTION. WHERE CIRCUITS ARE FORCONDUITMETALRIGIDORIMC,EMT,INRUNBESHALLCIRCUITS

GALLUP FEDERAL BUILDING

3rd and HILL STREETS GALLUP

BUILDING # NM0038ZZ

87301NM

FIRE ALARM REPLACEMENT

S U

P E

R V

IS

O

R Y

S

IG

N A

L O

N F

A C

P

OTHERWISE NOTED. MAXIMUM FILL RATIO SHALL NOT EXCEED

ALL NETWORK CABLE SHALL BE INSTALLED CLASS X WITH A MINIMUM SEPARATION OF 4 FOOT ON A HORIZONTAL PLANE OR

1 FOOT ON A VERTICAL PLANE.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

WF

S

MM

FACP

ANN

H

R

CM

SMOKE DETECTOR

HEAT DETECTOR

CONTROL MODULE

MONITOR MODULE

24 VOLT CONTROL RELAY - MR201

NAC

REMOTE ANNUNCIATOR

FIRE ALARM NOTIFICATION APPLIANCE POWER SUPPLY

FIRE ALARM CONTROL PANEL

SPRINKLER VALVE TAMPER SWITCH MONITOR MODULE

SPRINKLER WATER FLOW SWITCH MONITOR MODULE

STROBE ONLY NOTIFICATION APPLIANCE - WALL MOUNT

SPEAKER ONLY NOTIFICATION APPLIANCE - WALL MOUNT

COMBINATION SPEAKER & STROBE NOTIFICATION APPLIANCE - WALL MOUNT

FIRE ALARM SYSTEM DEVICE LEGEND

MANUAL PULL STATION F

TS

# DENOTES CANDELA

# DENOTES CANDELA

# DENOTES CANDELACOMBINATION SPEAKER & STROBE NOTIFICATION APPLIANCE - CEILING MOUNT

SPEAKER ONLY NOTIFICATION APPLIANCE - CEILING MOUNT

STROBE ONLY NOTIFICATION APPLIANCE - CEILING MOUNT # DENOTES CANDELA

S

AHU

SMOKE DETECTOR INSIDE AIR HANDLING UNIT

FLOOR NODE PANEL WITH AMPLIFIERSNODE

ONE ZONE, 2 SPEAKER CIRCUITS FOR STAIRS5.

ONE ZONE, 2 SPEAKER AND 2 STROBE CIRCUITS FOR THIRD FLOOR4.

ONE ZONE, 2 SPEAKER AND 2 STROBE CIRCUITS FOR SECOND FLOOR3.

ONE ZONE, 2 SPEAKER AND 2 STROBE CIRCUITS FOR FIRST FLOOR2.

ONE ZONE, 2 SPEAKER AND 2 STROBE CIRCUITS FOR SOILS BLDG1.

NOTIFICATION ZONES:

UP

UP

TELE.

TELE.

CUST.

ELEC.

ELEV.

MEN

WOMEN

CUST.

ELEC.

AIR SHAFT

ELEC.

G1

144A

164B

164A

G

176184

109-A

G2

ELEV.

TELE.

DN

DN DN DN

F

F

F

F

F

ANN

F A C P

F A C P

EXISTING FIRE ALARM PANEL

110 110

F

F WF

TS

S

AHU

S

AHU

S

AHU

S

AHU

S

AHU

S

AHU

WF

TS

TS

S

S

151515

30 30

15 15

16'8' 12'4'0

GRAPHIC SCALE

4'

NAC

NAC

S

S

PROVIDE AIR TIGHT SEAL

AROUND CONDUIT

PENETRATION

CONDUIT

4x4x2

BACK BOX

CROUSE-HINDS EYS SEALED WITH

CHICO X-FIBER AND SPEED SEAL

COMPOUND

INTELLIGENT ADDRESSABLE

PHOTOELECTRIC SMOKE DETECTOR

PROVIDE AIR TIGHT SEAL AROUND

CONDUIT PENETRATION

CONDUIT

4x4x2

BACK BOX

INTELLIGENT ADDRESSABLE

PHOTOELECTRIC SMOKE DETECTOR

NOTE:

LOCATE SMOKE DETECTOR ANYWHERE IN TOP OR SIDE OF SUPPLY AIR PLENUM OF HVAC

UNIT

NOTE:

LOCATE SMOKE DETECTOR ANYWHERE IN TOP OR SIDE OF SUPPLY AIR PLENUM OF HVAC

UNIT

CROUSE-HINDS EYS SEALED WITH

CHICO X-FIBER AND SPEED SEAL

COMPOUND

HVAC SUPPLY AIR PLENUM HVAC SUPPLY AIR PLENUM

"LB" CONDULET

"LB" CONDULET

SCHEME 1 SCHEME 2

MEN WOMEN

RAMP

FEC

FEC

S19S18

S-10A

S13A

S14A S11A

S

S -5

S -6

248-B

E

207D

UP

UP

CUST.

STAIR

ELEC.

ELEV.

CUST.

TELE.

ELEC.

ELEV.

TELE.

DN

DN

DN

DN

DN

CUST.

15 15 15

15 15 15

F

F

F

F

F

15 15 15

15 15

F

F

16'8' 12'4'0

GRAPHIC SCALE

4'

S

NODE

NAC

S

S

NAC

WF

S

MM

FACP

ANN

H

R

CM

SMOKE DETECTOR

HEAT DETECTOR

CONTROL MODULE

MONITOR MODULE

24 VOLT CONTROL RELAY - MR201

NAC

REMOTE ANNUNCIATOR

FIRE ALARM NOTIFICATION APPLIANCE POWER SUPPLY

FIRE ALARM CONTROL PANEL

SPRINKLER VALVE TAMPER SWITCH MONITOR MODULE

SPRINKLER WATER FLOW SWITCH MONITOR MODULE

STROBE ONLY NOTIFICATION APPLIANCE - WALL MOUNT

SPEAKER ONLY NOTIFICATION APPLIANCE - WALL MOUNT

COMBINATION SPEAKER & STROBE NOTIFICATION APPLIANCE - WALL MOUNT

FIRE ALARM SYSTEM DEVICE LEGEND

MANUAL PULL STATION F

TS

# # DENOTES CANDELA

# DENOTES CANDELA

# DENOTES CANDELACOMBINATION SPEAKER & STROBE NOTIFICATION APPLIANCE - CEILING MOUNT

SPEAKER ONLY NOTIFICATION APPLIANCE - CEILING MOUNT

STROBE ONLY NOTIFICATION APPLIANCE - CEILING MOUNT # DENOTES CANDELA

S

AHU SMOKE DETECTOR INSIDE AIR HANDLING UNIT

FLOOR NODE PANEL WITH AMPLIFIERSNODE

S

FEC

FEC

346A

346B

-D

-C

-B

327-A

-A

-B

-C

311-A

324B

324A

CUST.

STAIR

ELEC.

ELEV.

WOMEN

STAIR

CUST.

TELE.

ELEC.

ELEV.

TELE.

UP

DN DN

15 15 15

15 15 15

75 75

75 75

F

F

16'8' 12'4'0

GRAPHIC SCALE

4'

MECH.

DN

F

S

S S

NODE

S

NAC

S

NAC

WF

S

MM

FACP

ANN

H

R

CM

SMOKE DETECTOR

HEAT DETECTOR

CONTROL MODULE

MONITOR MODULE

24 VOLT CONTROL RELAY - MR201

NAC

REMOTE ANNUNCIATOR

FIRE ALARM NOTIFICATION APPLIANCE POWER SUPPLY

FIRE ALARM CONTROL PANEL

SPRINKLER VALVE TAMPER SWITCH MONITOR MODULE

SPRINKLER WATER FLOW SWITCH MONITOR MODULE

STROBE ONLY NOTIFICATION APPLIANCE - WALL MOUNT

SPEAKER ONLY NOTIFICATION APPLIANCE - WALL MOUNT

COMBINATION SPEAKER & STROBE NOTIFICATION APPLIANCE - WALL MOUNT

FIRE ALARM SYSTEM DEVICE LEGEND

MANUAL PULL STATION F

TS

# # DENOTES CANDELA

# DENOTES CANDELA

# DENOTES CANDELACOMBINATION SPEAKER & STROBE NOTIFICATION APPLIANCE - CEILING MOUNT

SPEAKER ONLY NOTIFICATION APPLIANCE - CEILING MOUNT

STROBE ONLY NOTIFICATION APPLIANCE - CEILING MOUNT # DENOTES CANDELA

S

AHU

SMOKE DETECTOR INSIDE AIR HANDLING UNIT

FLOOR NODE PANEL WITH AMPLIFIERSNODE

S

H__Gallup_Cover
H__Gallup_1st Floor Fire Alarm
H__Gallup_2nd Floor Fire Alarm
H__Gallup_3rd Floor Fire Alarm (1)