Revised Fire Protection Template.xlsx

XLSX spreadsheet 224 KB Posted

Attached to
Fire Protection and Safety & Health Risk MGMT Surveys - 36 Leased Locations
Solicitation number
47PF0024Q0112
Issued by

About this file

This document appears to be a Risk Management Survey and Fire Protection Survey for a government-leased building called the Orland Office Center II in Orland Park, Illinois. The survey covers various fire protection systems and elements, including means of egress, fire alarm and emergency communication systems, automatic sprinkler systems, smoke management systems, interior finish, passive fire protection, vertical transportation systems, preventative maintenance records, emergency preparedness records, and other special systems or areas. The survey provides a detailed assessment of the building's compliance with applicable codes, standards, and regulations, and includes risk assessments and recommended corrective actions. This survey seems to be part of a larger federal contract opportunity for conducting similar risk management and fire protection surveys at 36 leased locations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RAC Summary

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Fire Protection Survey

RAC Summary
8523EDITABLEN
Means of Egress System
Fire Alarm & Emerg. Comm Sys
Automatic Sprinkler Systems
Non-Water-Based Fire Ext. Sys.
Smoke Management Systems
Interior Finish
Passive Fire Protection Systems
Vertical Transportation Systems
Preventative Maint. Records
Emergency Preparedness Records
Special Systems or Areas
Significant Fuel Loads & HazMat
Other Categories

Overall RAC

IRIS Building Profile

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Questions Response Findings/Observations (Location Description: Floor, Room #, Stair #, etc.)

IRIS Building Profile
Region51328652327553921
GSA Building NumberIL2514ZZ1328652427553931
GSA Building NameORLAND OFFICE CENTER II1328652527553941
Building Street Address15321 S 94th Ave1328652627553951
Date of Building Construction1328651727553861
Building CityORLAND PARK1328652127553901
Building StateIL1328652227553911
Building Size (RSF)132865161
Building Size (GSF)153001328651827553871
Total Number of Floors Above Grade01328651927553881
Total Number of Floors Below Grade01328652027553891
8523N1328

Building Information

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Building Information

Questions Response Findings/Observations (Location Description: Floor, Room #, Stair #, etc.)

Survey Information
Date(s) of Onsite Survey133065271
Name of Surveyor133065281
Surveyor Company Name and Contact Information133065291
Type of Survey133065453
Facility Type133065463
General Building Information
GSA Facility Manager / Lease Administration Manager & Contact Information138067921
Building occupancy classification per latest edition of IBC138067933
Building construction type per latest edition of IBC138067943
Automatic Sprinkler Coverage (None/Partial/Full-Total)138067953
For Federally Owned & Leased surveys, identify the specific floors the Federal Government occupies.138067961
For Federally Owned & Leased surveys, identify the different type of occupancies on each floor the Federal Government occupies.138067971
Height from lowest level of fire department vehicle access to the highest Federally occupied floor of the building (in feet)138067981
Height from the lowest level of fire department vehicle access to the roof of the building (in feet)138067991
High-rise Building138068004
Historic Building138068013
Identify and describe the location of the nearest fire department and the approximate distance (e.g. Blocks, Miles, etc.) from the building.138068021
For Federally Owned & Leased surveys, identify by location and describe significant fuel load areas that when ignited would produce significant adverse effects to the space occupied by the Federal Government.138068031
Identify by location and describe any High Risk Operations, e.g., High Risk Laboratories, Firing Ranges, Shoot Houses, Storage of Explosive Materials.138068041
For Federally Owned & Leased surveys, describe the fire exposures on the north, south, east, and west sides of the building, including the distance from the building.138068051
Identify any Unique Space Type(s). If "other" is chosen, please describe the "other" unique space in the Findings/Observations Column.138074203
Identify any Unique Space Type #2.138074213
Identify any Unique Space Type #3.138074223
Identify any Unique Space Type #4.138074233
Child Care Center Information
Is there a Child Care Center in this building?138168063
Child Care Center Name138168071
Child Care Center Director Name and Contact Information138168081
Describe location of the Child Care Center and associated Child Care Center spaces (Floor(s)).138168091
Describe approximate GSF of each Child Care Center Space.138168101
Identify the number of children in the Child Care Center by age group (e.g., infants, young toddlers, older toddlers, 3 year olds, 4 year olds, and 5 year olds+).138168111
Identify the number of Child Care Center staff.138168121
Is the Child Care Center protected by an automatic sprinkler system (Yes/No)?138168133
Identify the different type of occupancies on each floor the Child Care Center occupies.138168141
Identify by location and describe significant fuel load areas within the Child Care Center.138168151
Describe the fire exposures on the north, south, east, and west sides of the building, including the distance from the Child Care Center.138168161
Means of Egress System Information
Identify and describe the number of means of egress from each floor of Federal occupancy. (e.g., stair width, tread length, riser height, and handrail specifics, etc.).136867131
Identify and describe the location of where each exit discharges and terminates.136867141
Identify and describe if the building has a fire escape(s).136867151
Identify and describe if the building has a scissor stair(s).136867161
Describe the calculated occupant load and exit capacity for each floor of Federal occupancy.136867171
Describe the Illumination of means of egress system (includes emergency lighting) for Federal occupants.136867191
Describe the marking means of egress (e.g., exit signage, path markings, signage, evacuation route signage) for Federal occupants.136867201
Identify and describe the number of means of egress from the GSA Child Care Center.136867211
Identify and describe the arrangement of means of egress from each floor of the Child Care Center (e.g., travel distance, common path of travel, exit remoteness, etc.).136867221
Identify and describe the location of where each exit discharges and terminates from each floor of the Child Care Center.136867231
Describe the Illumination of means of egress system (includes emergency lighting) for the Child Care Center.136867241
Describe the marking means of egress (e.g., exit signage, path markings, signage, evacuation route signage) for the Child Care Center.136867251
Automatic Sprinkler System(s) Information
If applicable, for Federally Owned surveys, describe the water supply (e.g., public, tanks, etc.) for the facility.136967281
If applicable, for Federally Owned & Leased surveys, identify the type(s) and describe the location of automatic sprinkler system(s) on each floor of Federal occupancy (e.g., wet, dry, pre-action, etc.).136967291
If applicable, for Federally Owned & Leased surveys, identify the type(s) of sprinklers (e.g., manufacturer, model, date of manufacturer for each type of sprinkler) in the sprinkler cabinet.136967301
Identify the type and describe the location of the automatic sprinkler system for the Child Care Center (e.g., wet, dry, etc.).136967311
For a Child Care Center, identify the type(s) of sprinklers (e.g., manufacturer, model, date of manufacturer for each type of sprinkler) in the sprinkler cabinet.136967321
Standpipe System Information
If applicable, for Federally Owned and Leased surveys, identify by location and describe the type(s) of standpipe systems.137067331
Fire Department Connection Information
If applicable, identify by location and describe the fire department connections.138268171
Sprinkler Piping Information
If applicable, for Federally Owned surveys identify if pressure reducing valves are present.138368181
Fire Pump Information
If applicable, for Federally Owned and Leased surveys, identify (e.g., type, manufacturer, model) and the location of fire pump.137167341
If applicable, for Federally Owned and Leased surveys, identify the size of fire pump (__ gpm at __ psi).137167351
If applicable, for Federally Owned and Leased surveys, identify (e.g., manufacturer, model) and the location of jockey pump.137167361
Non-Water Based Fire Extinguishing Systems
If applicable, for Federally Owned and Leased surveys, identify by location and describe the clean agent extinguishing system on the floor(s) of Federal occupancy.137267381
If applicable, for Federally Owned and Leased surveys, identify by location and describe the types of portable fire extinguishers on the floor(s) of Federal occupancy.137267391
If applicable, for Federally Owned and Leased surveys, identify by location the wet chemical system on the floor(s) of Federal occupancy.137267401
If applicable, identify by location and describe the type of portable fire extinguishers within the Child Care Center.137267411
If applicable, identify by location the wet chemical system within the Child Care Center.137267421
Fire Alarm & Emergency Communication System Information
If applicable, for Federally Owned and Leased surveys, describe the fire alarm and emergency communication system for the facility.137367431
Identify the location of the main fire alarm control unit (e.g., 1st floor fire command center, etc.).137367441
Identify the date the fire alarm system was installed.137367451
Identify the age of fire alarm system.137367461
Identify the control unit manufacturer.137367471
Identify the control unit model number.137367481
Identify the control unit date manufactured.137367491
If applicable, identify the software/firmware and revision number.137367501
If applicable, identify and describe the emergency responder radio communication system.137367511
Describe the fire alarm and emergency communication system for the Child Care Center; indicate if the Child Care Center is provided with a separate fire alarm control unit and if it is connected to the building’s fire alarm system.137367521
Identify and describe the location of smoke detectors within the Child Care Center.137367531
Smoke Management System Information
If applicable, for Federally Owned and Leased surveys, identify and describe vertical shaft pressurization systems (e.g., exit stairs and elevator hoistways).137467541
If applicable, for Federally Owned and Leased surveys, identify and describe the atrium smoke control system.137467551
If applicable, for Federally Owned and Leased surveys, identify and describe the floor pressurization system (zones).137467571
If applicable, for Federally Owned and Leased surveys, identify and describe the location of the fire fighters' smoke control panel.137467581
If applicable, for Federally Owned surveys, identify and describe if the BAS system is connected to any smoke control system noted.137467591
If applicable, for Federally Owned and Leased surveys, identify and describe the smoke removal systems.137467601
If applicable, for Federally Owned and Leased surveys, identify and describe the smoke purge systems.137467611
Passive Fire Protection Information
If applicable for Federally Owned and Leased surveys, Identify and describe protection of vertical and horizontal openings (include walls, floors, doors, fire dampers, smoke dampers, combination fire/smoke dampers, etc.) for floor(s) of Federal occupancy.137567621
If applicable for Federally Owned and Leased surveys, Identify and describe protection from hazards (e.g., flammable & combustible solids, liquids, corrosives; explosive materials; chemical laboratories; etc.) for floor(s) of Federal occupancy.137567631
Identify and describe the separation requirements for the Child Care Center.137567641
Interior Finishes
For Federally Owned and Leased surveys, identify and describe by location the different types of interior finish on floor(s) of Federal occupancy.137667711
Identify and describe by location the different types of interior finish within the Child Care Center137667721
Vertical Transportation System Information
If applicable, for Federally Owned and Leased surveys, identify and describe the location and number of escalators.137767731
If applicable, for Federally Owned and Leased surveys, identify the number of passenger elevators.137767741
If applicable, for Federally Owned and Leased surveys, identify the number of freight elevators.137767751
If applicable, for Federally Owned and Leased surveys, identify the number of service elevators.137767761
If applicable, for Federally Owned and Leased surveys, identify the number of fire service access elevators.137767771
If applicable, for Federally Owned and Leased surveys, identify the number of occupant evacuation elevators.137767781
If applicable, for Federally Owned and Leased surveys, identify and describe the fire fighters' emergency operation provided (Phase I emergency recall operation) for the elevators.137767791
If applicable, for Federally Owned and Leased surveys, identify and describe the fire fighters' emergency operation provided (Phase II emergency in-car operation) for the elevators.137767801
If applicable, for Federally Owned and Leased surveys, identify and describe the location of each elevator machine room (include if protected by automatic sprinklers, shunt trip, smoke detection, etc.).137767811
If applicable, for Federally Owned and Leased surveys, describe the standby power for each of the types of elevator.137767821
Emergency and Standby Power System Information
Identify and describe the source(s) of emergency and standby power for the building.137967881
Identify all systems connected to the emergency and standby power system.137967891
Identify and describe the source(s) of emergency and standby power for the GSA Child Care Center.137967901
Identify all systems within the GSA Child Care Center connected to the emergency and standby power system.137967911
Preventative Maintenance Record Information (Fire Protection Equipment and Systems)
List the fire protection equipment and systems preventative maintenance records reviewed (e.g., smoke management/control system, sprinklers, fire alarm, fire doors, fire pump, emergency lighting, exit signage, stand-by power, dampers, portable fire extinguishers, etc.).138768331
Emergency Preparedness Record Information
For Federally Owned and Leased surveys, describe the building's occupant emergency plan (OEP) reviewed. Include date of OEP; procedures to evacuate occupants and persons with mobility disabilities; procedures to evacuate occupants after-hours; etc. during an emergency.138868341
For Child Care Center surveys, describe the Child Care Center's occupant emergency plan (OEP) reviewed. Include date of OEP; procedures to evacuate the children during an emergency.138868351
Describe the fire and evacuation drill records reviewed (e.g., annual drill, monthly drill for Child Care Centers).138868361
Identify and describe if the local fire department has been invited into the facility to prepare a pre-fire plan for the facility.138868371
Special Systems/Areas Information
If applicable, for Federally Owned and Leased surveys, identify location and describe the energy storage system.138968381
If applicable, for Federally Owned and Leased surveys, identify location and describe the energy production system (including wind, solar, & geothermal).138968391
If applicable, for Federally Owned and Leased surveys, identify location and describe information technology equipment rooms.138968401
If applicable, for Federally Owned and Leased surveys, identify location and describe places of confinement (holding areas).138968411
If applicable, for Federally Owned surveys, identify location and describe the fire protection for the cooling towers.138968421
If applicable, for Federally Owned and Leased surveys, identify location and describe emergency power (generator, etc.).138968431
If applicable, for Federally Owned and Child Care surveys, identify location and describe the CO detection system.138968441
Fire Safety Evaluation System (FSES) Scoring
If applicable, for Federally Owned surveys - FSES Completion Date:137867831
If applicable, for Federally Owned surveys - Fire Control:137867841
If applicable, for Federally Owned surveys - Egress Provided:137867851
If applicable, for Federally Owned surveys - General Fire Safety:137867861
If applicable, for Federally Owned surveys - Building Fire Risk Index (BFRI)137867871
8523EDITABLEN1378

Means of Egress System

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Means of Egress System

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Arrangement of Means of Egress
Is the Arrangement of Means of Egress in compliance?Not PossibleNo Impact134465984
Identified Risk Condition # 1Not PossibleNo Impact134466043
Identified Risk Condition # 2Not PossibleNo Impact134466053
Identified Risk Condition # 3Not PossibleNo Impact134466063
Capacity of Means of Egress
Is the Capacity of Means of Egress in compliance?Not PossibleNo Impact134666114
Identified Risk Condition # 1Not PossibleNo Impact134666123
Identified Risk Condition # 2Not PossibleNo Impact134666133
Identified Risk Condition # 3Not PossibleNo Impact134666143
Discharge from Exits
Is the Discharge from Exits in compliance?Not PossibleNo Impact134065784
Identified Risk Condition # 1Not PossibleNo Impact134065793
Identified Risk Condition # 2Not PossibleNo Impact134065803
Identified Risk Condition # 3Not PossibleNo Impact134065813
Doors
Are the Doors in compliance?Not PossibleNo Impact134265864
Identified Risk Condition # 1Not PossibleNo Impact134265883
Identified Risk Condition # 2Not PossibleNo Impact134265893
Identified Risk Condition # 3Not PossibleNo Impact134265903
Exit Stairs
Are the Exits Stairs in compliance?Not PossibleNo Impact134365914
Identified Risk Condition # 1Not PossibleNo Impact134365953
Identified Risk Condition # 2Not PossibleNo Impact134365963
Identified Risk Condition # 3Not PossibleNo Impact134365973
Horizontal Exits
Are the Horizontal Exits in compliance?Not PossibleNo Impact134165824
Identified Risk Condition # 1Not PossibleNo Impact134165833
Identified Risk Condition # 2Not PossibleNo Impact134165843
Identified Risk Condition # 3Not PossibleNo Impact134165853
Fire Escapes
Are the Fire Escapes in compliance?Not PossibleNo Impact134566074
Identified Risk Condition # 1Not PossibleNo Impact134566083
Identified Risk Condition # 2Not PossibleNo Impact134566093
Identified Risk Condition # 3Not PossibleNo Impact134566103
Illumination of Means of Egress
Is the Illumination of Means of Egress in compliance?Not PossibleNo Impact134766154
Identified Risk Condition # 1Not PossibleNo Impact134766173
Identified Risk Condition # 2Not PossibleNo Impact134766183
Identified Risk Condition # 3Not PossibleNo Impact134766193
Marking Means of Egress
Is the Marking Means of Egress in compliance?Not PossibleNo Impact138468204
Identified Risk Condition # 1Not PossibleNo Impact138468213
Identified Risk Condition # 2Not PossibleNo Impact138468223
Identified Risk Condition # 3Not PossibleNo Impact138468233
Means of Egress Reliability
Is the Means of Egress Reliability in compliance?Not PossibleNo Impact138568254
Identified Risk Condition # 1Not PossibleNo Impact138568263
Identified Risk Condition # 2Not PossibleNo Impact138568273
Identified Risk Condition # 3Not PossibleNo Impact138568283
Number of Means of Egress
Are the Number of Means of Egress in compliance?Not PossibleNo Impact138668294
Identified Risk Condition # 1Not PossibleNo Impact138668303
Identified Risk Condition # 2Not PossibleNo Impact138668313
Identified Risk Condition # 3Not PossibleNo Impact138668323
Other Findings
Other Findings 1Not PossibleNo Impact133965681
Other Findings 2Not PossibleNo Impact133965691
Other Findings 3Not PossibleNo Impact133965701
Other Findings 4Not PossibleNo Impact133965711
Other Findings 5Not PossibleNo Impact133965721
Other Findings 6Not PossibleNo Impact133965731
Other Findings 7Not PossibleNo Impact133965741
Other Findings 8Not PossibleNo Impact133965751
Other Findings 9Not PossibleNo Impact133965761
Other Findings 10Not PossibleNo Impact133965771
Overall RAC
Overall RAC133865655
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.133865666
Explanation of User Adjusted RAC133865671
8523EDITABLEN1338
N

Fire Alarm & Emerg. Comm Sys

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Fire Alarm & Emerg. Comm Sys

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Annunciator(s)
Is the Annunciator in compliance?Not PossibleNo Impact136066804
Identified Risk Condition # 1Not PossibleNo Impact136066813
Identified Risk Condition # 2Not PossibleNo Impact136066823
Identified Risk Condition # 3Not PossibleNo Impact136066833
Fire Alarm Control Unit(s)
Is the Fire Control Unit in compliance?Not PossibleNo Impact135966704
Identified Risk Condition # 1Not PossibleNo Impact135966773
Identified Risk Condition # 2Not PossibleNo Impact135966783
Identified Risk Condition # 3Not PossibleNo Impact135966793
Fire Command Center
Is the Fire Command Center in compliance?Not PossibleNo Impact135866654
Identified Risk Condition # 1Not PossibleNo Impact135866673
Identified Risk Condition # 2Not PossibleNo Impact135866683
Identified Risk Condition # 3Not PossibleNo Impact135866693
Initiating Devices
Are the Initiating Devices in compliance?Not PossibleNo Impact139168494
Identified Risk Condition # 1Not PossibleNo Impact139168503
Identified Risk Condition # 2Not PossibleNo Impact139168513
Identified Risk Condition # 3Not PossibleNo Impact139168523
Notification Appliances
Are the Notification Appliances in compliance?Not PossibleNo Impact139068454
Identified Risk Condition # 1Not PossibleNo Impact139068463
Identified Risk Condition # 2Not PossibleNo Impact139068473
Identified Risk Condition # 3Not PossibleNo Impact139068483
Supervisory Station Monitoring Service
Is the Supervisory Station Monitoring Service in compliance?Not PossibleNo Impact139268534
Identified Risk Condition # 1Not PossibleNo Impact139268543
Identified Risk Condition # 2Not PossibleNo Impact139268553
Identified Risk Condition # 3Not PossibleNo Impact139268563
Other Findings
Other Findings 1Not PossibleNo Impact135766551
Other Findings 2Not PossibleNo Impact135766561
Other Findings 3Not PossibleNo Impact135766571
Other Findings 4Not PossibleNo Impact135766581
Other Findings 5Not PossibleNo Impact135766591
Other Findings 6Not PossibleNo Impact135766601
Other Findings 7Not PossibleNo Impact135766611
Other Findings 8Not PossibleNo Impact135766621
Other Findings 9Not PossibleNo Impact135766631
Other Findings 10Not PossibleNo Impact135766641
Overall RAC
Overall RAC135666525
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.135666536
Explanation of User Adjusted RAC135666541
8523EDITABLEN1356
N

Automatic Sprinkler Systems

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Automatic Sprinkler Systems

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Fire Department Connections
Are the Fire Department Connections in compliance?Not PossibleNo Impact136466974
Identified Risk Condition # 1Not PossibleNo Impact136466983
Identified Risk Condition # 2Not PossibleNo Impact136466993
Identified Risk Condition # 3Not PossibleNo Impact136467003
Fire Pumps
Are the Fire Pumps in compliance?Not PossibleNo Impact136567014
Identified Risk Condition # 1Not PossibleNo Impact136567023
Identified Risk Condition # 2Not PossibleNo Impact136567033
Identified Risk Condition # 3Not PossibleNo Impact136567043
Sprinkler Piping
Is the Sprinkler Piping in compliance?Not PossibleNo Impact136667054
Identified Risk Condition # 1Not PossibleNo Impact136667063
Identified Risk Condition # 2Not PossibleNo Impact136667073
Identified Risk Condition # 3Not PossibleNo Impact136667083
Sprinklers
Are the Sprinklers in compliance?Not PossibleNo Impact136767094
Identified Risk Condition # 1Not PossibleNo Impact136767103
Identified Risk Condition # 2Not PossibleNo Impact136767113
Identified Risk Condition # 3Not PossibleNo Impact136767123
Standpipes
Are the Standpipes in compliance?Not PossibleNo Impact139468614
Identified Risk Condition # 1Not PossibleNo Impact139468623
Identified Risk Condition # 2Not PossibleNo Impact139468633
Identified Risk Condition # 3Not PossibleNo Impact139468643
Water Supply
Is the Water Supply in compliance?Not PossibleNo Impact139368574
Identified Risk Condition # 1Not PossibleNo Impact139368583
Identified Risk Condition # 2Not PossibleNo Impact139368593
Identified Risk Condition # 3Not PossibleNo Impact139368603
Other Findings
Other Findings 1Not PossibleNo Impact136366871
Other Findings 2Not PossibleNo Impact136366881
Other Findings 3Not PossibleNo Impact136366891
Other Findings 4Not PossibleNo Impact136366901
Other Findings 5Not PossibleNo Impact136366911
Other Findings 6Not PossibleNo Impact136366921
Other Findings 7Not PossibleNo Impact136366931
Other Findings 8Not PossibleNo Impact136366941
Other Findings 9Not PossibleNo Impact136366951
Other Findings 10Not PossibleNo Impact136366961
Overall RAC
Overall RAC136266845
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.136266856
Explanation of User Adjusted RAC136266861
8523EDITABLEN1362
N

Non-Water-Based Fire Ext. Sys.

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Non-Water-Based Fire Ext. Sys.

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Clean Agent Extinguishing System
Is the Clean Agent Extinguishing System in compliance?Not PossibleNo Impact133665614
Identified Risk Condition # 1Not PossibleNo Impact133665623
Identified Risk Condition # 2Not PossibleNo Impact133665633
Identified Risk Condition # 3Not PossibleNo Impact133665643
Portable Fire Extinguishers
Are the Portable Fire Extinguishers in compliance?Not PossibleNo Impact139668694
Identified Risk Condition # 1Not PossibleNo Impact139668703
Identified Risk Condition # 2Not PossibleNo Impact139668713
Identified Risk Condition # 3Not PossibleNo Impact139668723
Wet Chemical System
Is the Wet Chemical System in compliance?Not PossibleNo Impact139568654
Identified Risk Condition # 1Not PossibleNo Impact139568663
Identified Risk Condition # 2Not PossibleNo Impact139568673
Identified Risk Condition # 3Not PossibleNo Impact139568683
Other Findings
Other Findings 1Not PossibleNo Impact133565511
Other Findings 2Not PossibleNo Impact133565521
Other Findings 3Not PossibleNo Impact133565531
Other Findings 4Not PossibleNo Impact133565541
Other Findings 5Not PossibleNo Impact133565551
Other Findings 6Not PossibleNo Impact133565561
Other Findings 7Not PossibleNo Impact133565571
Other Findings 8Not PossibleNo Impact133565581
Other Findings 9Not PossibleNo Impact133565591
Other Findings 10Not PossibleNo Impact133565601
Overall RAC
Overall RAC133465485
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.133465496
Explanation of User Adjusted RAC133465501
8523EDITABLEN1334
N

Smoke Management Systems

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Smoke Management Systems

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Atrium
Is the Atrium in compliance?Not PossibleNo Impact135266374
Identified Risk Condition # 1Not PossibleNo Impact135266403
Identified Risk Condition # 2Not PossibleNo Impact135266413
Identified Risk Condition # 3Not PossibleNo Impact135266423
Floor Pressurization Zones
Are the Floor Pressurization Zones in compliance?Not PossibleNo Impact135366434
Identified Risk Condition # 1Not PossibleNo Impact135366453
Identified Risk Condition # 2Not PossibleNo Impact135366463
Identified Risk Condition # 3Not PossibleNo Impact135366473
Smoke Purge System
Is the Smoke Purge System in compliance?Not PossibleNo Impact135466484
Identified Risk Condition # 1Not PossibleNo Impact135466493
Identified Risk Condition # 2Not PossibleNo Impact135466503
Identified Risk Condition # 3Not PossibleNo Impact135466513
Smoke Removal System
Is the Smoke Removal System in compliance?Not PossibleNo Impact135166334
Identified Risk Condition # 1Not PossibleNo Impact135166343
Identified Risk Condition # 2Not PossibleNo Impact135166353
Identified Risk Condition # 3Not PossibleNo Impact135166363
Vertical Shaft Pressurization
Is the Vertical Shaft Pressurization in compliance?Not PossibleNo Impact139768734
Identified Risk Condition # 1Not PossibleNo Impact139768743
Identified Risk Condition # 2Not PossibleNo Impact139768753
Identified Risk Condition # 3Not PossibleNo Impact139768763
Other Findings
Other Findings 1Not PossibleNo Impact135066231
Other Findings 2Not PossibleNo Impact135066241
Other Findings 3Not PossibleNo Impact135066251
Other Findings 4Not PossibleNo Impact135066261
Other Findings 5Not PossibleNo Impact135066271
Other Findings 6Not PossibleNo Impact135066281
Other Findings 7Not PossibleNo Impact135066291
Other Findings 8Not PossibleNo Impact135066301
Other Findings 9Not PossibleNo Impact135066311
Other Findings 10Not PossibleNo Impact135066321
Overall RAC
Overall RAC134966205
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.134966216
Explanation of User Adjusted RAC134966221
8523EDITABLEN1349
N

Interior Finish

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Interior Finish

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Interior Finish
Is the Interior Finish in compliance?Not PossibleNo Impact140168904
Identified Risk Condition # 1Not PossibleNo Impact140168913
Identified Risk Condition # 2Not PossibleNo Impact140168923
Identified Risk Condition # 3Not PossibleNo Impact140168933
Other Findings
Other Findings 1Not PossibleNo Impact140068801
Other Findings 2Not PossibleNo Impact140068811
Other Findings 3Not PossibleNo Impact140068821
Other Findings 4Not PossibleNo Impact140068831
Other Findings 5Not PossibleNo Impact140068841
Other Findings 6Not PossibleNo Impact140068851
Other Findings 7Not PossibleNo Impact140068861
Other Findings 8Not PossibleNo Impact140068871
Other Findings 9Not PossibleNo Impact140068881
Other Findings 10Not PossibleNo Impact140068891
Overall RAC
Overall RAC139968775
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.139968786
Explanation of User Adjusted RAC139968791
8523EDITABLEN1399
N

Passive Fire Protection Systems

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Passive Fire Protection Systems

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Passive Protection for High Hazardous Contents
Is the Passive Protection for High Hazardous Contents in compliance?Not PossibleNo Impact140669114
Identified Risk Condition # 1Not PossibleNo Impact140669123
Identified Risk Condition # 2Not PossibleNo Impact140669133
Identified Risk Condition # 3Not PossibleNo Impact140669143
Passive Protection of Vertical and Horizontal Openings
Is the Passive Protection of Vertical and Horizontal Openings in compliance?Not PossibleNo Impact140569074
Identified Risk Condition # 1Not PossibleNo Impact140569083
Identified Risk Condition # 2Not PossibleNo Impact140569093
Identified Risk Condition # 3Not PossibleNo Impact140569103
Other Findings
Other Findings 1Not PossibleNo Impact140468971
Other Findings 2Not PossibleNo Impact140468981
Other Findings 3Not PossibleNo Impact140468991
Other Findings 4Not PossibleNo Impact140469001
Other Findings 5Not PossibleNo Impact140469011
Other Findings 6Not PossibleNo Impact140469021
Other Findings 7Not PossibleNo Impact140469031
Other Findings 8Not PossibleNo Impact140469041
Other Findings 9Not PossibleNo Impact140469051
Other Findings 10Not PossibleNo Impact140469061
Overall RAC
Overall RAC140368945
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.140368956
Explanation of User Adjusted RAC140368961
8523EDITABLEN1403
N

Vertical Transportation Systems

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Vertical Transportation Systems

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Elevator Machine Room(s)
Are the Elevator Machine Room(s) in compliance?Not PossibleNo Impact144970894
Identified Risk Condition # 1Not PossibleNo Impact144970903
Identified Risk Condition # 2Not PossibleNo Impact144970913
Identified Risk Condition # 3Not PossibleNo Impact144970923
Emergency Signage
Is the Emergency Signage in compliance?Not PossibleNo Impact144870854
Identified Risk Condition # 1Not PossibleNo Impact144870863
Identified Risk Condition # 2Not PossibleNo Impact144870873
Identified Risk Condition # 3Not PossibleNo Impact144870883
Escalator(s)
Are the Escalator(s) in compliance?Not PossibleNo Impact144770814
Identified Risk Condition # 1Not PossibleNo Impact144770823
Identified Risk Condition # 2Not PossibleNo Impact144770833
Identified Risk Condition # 3Not PossibleNo Impact144770843
Fire Service Access Elevator(s)
Are the Fire Service Access Elevator(s) in compliance?Not PossibleNo Impact144670774
Identified Risk Condition # 1Not PossibleNo Impact144670783
Identified Risk Condition # 2Not PossibleNo Impact144670793
Identified Risk Condition # 3Not PossibleNo Impact144670803
Firefighters Emergency Operation
Is the Firefighters Emergency Operation in compliance?Not PossibleNo Impact144570734
Identified Risk Condition # 1Not PossibleNo Impact144570743
Identified Risk Condition # 2Not PossibleNo Impact144570753
Identified Risk Condition # 3Not PossibleNo Impact144570763
Hoistway Enclosure(s)
Are the Hoistway Enclosure(s) in compliance?Not PossibleNo Impact144470694
Identified Risk Condition # 1Not PossibleNo Impact144470703
Identified Risk Condition # 2Not PossibleNo Impact144470713
Identified Risk Condition # 3Not PossibleNo Impact144470723
Occupant Evacuation Elevator(s)
Are the Occupant Evacuation Elevator(s) in compliance?Not PossibleNo Impact144370654
Identified Risk Condition # 1Not PossibleNo Impact144370663
Identified Risk Condition # 2Not PossibleNo Impact144370673
Identified Risk Condition # 3Not PossibleNo Impact144370683
Standby Power
Is the Standby Power in compliance?Not PossibleNo Impact144270614
Identified Risk Condition # 1Not PossibleNo Impact144270623
Identified Risk Condition # 2Not PossibleNo Impact144270633
Identified Risk Condition # 3Not PossibleNo Impact144270643
Other Findings
Other Findings 1Not PossibleNo Impact144170511
Other Findings 2Not PossibleNo Impact144170521
Other Findings 3Not PossibleNo Impact144170531
Other Findings 4Not PossibleNo Impact144170541
Other Findings 5Not PossibleNo Impact144170551
Other Findings 6Not PossibleNo Impact144170561
Other Findings 7Not PossibleNo Impact144170571
Other Findings 8Not PossibleNo Impact144170581
Other Findings 9Not PossibleNo Impact144170591
Other Findings 10Not PossibleNo Impact144170601
Overall RAC
Overall RAC144070485
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.144070496
Explanation of User Adjusted RAC144070501
8523EDITABLEN1440
N

Preventative Maint. Records

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Preventative Maint. Records

Compliance refers to adherence to applicable reference documents such as Federal laws (e.g., 41 CFR part 102-80), GSA Policies (e.g., PBS-P100), and national recognized codes and standards (e.g., ICC codes, NFPA codes & standards).
If the Response to the compliance question is "Yes," "N/A", or "Unknown," select "N/A" for the Response to each Identified Risk Condition. If the Response to a compliance question is "No," move to the Identified Risk Condition lines and for every one used select "Yes" for the Response & complete all other cells. For any unused Identified Risk Conditions lines, select "N/A" for the Response.
Risk Assessment Code (RAC)Recommended Corrective Actions
QuestionsResponseFindings/Observations (Location Description: Floor, Room #, Stair #, etc.)Applicable Reference Documents, Edition, & Section/ParagraphProbabilitySeverityRACIs there a recommended corrective action associated with this item?Responsible OfficeLocalized or Building WideRecommendation
Preventative Maintenance Records Review
Are the Preventative Maintenance Records in compliance?Not PossibleNo Impact141069284
Identified Risk Condition # 1Not PossibleNo Impact141069293
Identified Risk Condition # 2Not PossibleNo Impact141069303
Identified Risk Condition # 3Not PossibleNo Impact141069313
Other Findings
Other Findings 1Not PossibleNo Impact140969181
Other Findings 2Not PossibleNo Impact140969191
Other Findings 3Not PossibleNo Impact140969201
Other Findings 4Not PossibleNo Impact140969211
Other Findings 5Not PossibleNo Impact140969221
Other Findings 6Not PossibleNo Impact140969231
Other Findings 7Not PossibleNo Impact140969241
Other Findings 8Not PossibleNo Impact140969251
Other Findings 9Not PossibleNo Impact140969261
Other Findings 10Not PossibleNo Impact140969271
Overall RAC
Overall RAC140869155
User Adjusted RAC
: Once the surveyor has reviewed the findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.140869166
Explanation of User Adjusted RAC140869171
8523EDITABLEN1408
N

Emergency Preparedness Records

Downloaded on: 02/22/2023 09:35:40
GSARisk Management Survey

Emergency Preparedness Records