472_25278.RWG Ionia IT Room Expansion - Bid Drawings-min.pdf
PDF 12 MB Posted
- Attached to
- 472/25278. RWG; Ionia C. F. - IT Room Expansion
- Solicitation number
- RFQ 171 270000000032 1
- Issued by
- Michigan
About this file
Summary of Ionia Correctional Facility IT Room Expansion Bid Drawings
This document is a comprehensive set of bid drawings for the Ionia Correctional Facility IT Room Expansion project prepared by the State of Michigan Department of Technology, Management and Budget, Facilities and Business Services Administration, Design and Construction Division. The project (File No. 472/25278.RWG) involves the expansion and renovation of the IT room at the Ionia Correctional Facility located at 1576 Bluewater Highway, Ionia, Michigan 48846. The scope of work encompasses architectural modifications including construction of new 8"x8"x16" concrete masonry unit (CMU) block walls, installation of insulated 1.5-hour fire-rated metal doors with dry suppression seals, electrical system upgrades including new lighting fixtures and power distribution panels, mechanical systems including a new air conditioning unit with roof-mounted condensing unit, and telecommunications infrastructure including new cable trays, fiber optic panels, and data cabling. The project includes the installation of four new server racks with cable management systems and rack-mounted equipment. The drawings were issued for bid on October 19, 2026, and include detailed plans from architects Straub Pettitt Mann Architecture, mechanical engineers Matrix Consulting Engineers, Inc., and technology designer Commtech Design.
The project requires coordination among multiple trades including electrical, mechanical, plumbing, and fire protection contractors. Key specifications include installation of a new Novec 1230 clean agent dry chemical fire suppression system compliant with NFPA standards, a new 40 kVA UPS system with 45 kVA and 30 kVA transformers and associated panels, and comprehensive data and telecommunications cabling with CAT-6 and fiber optic cables. All work must comply with the 2023 Michigan Electrical Code, Michigan Mechanical Code, and MDOC standards. The project requires that all electrical outages not exceed two hours, and any outages exceeding this duration require portable generator backup. Contractors must maintain an escort through the facility during work and coordinate a minimum of two weeks in advance for any hot work requiring fire alarm disabling. Specific security requirements include the use of tamperproof screws in areas exposed to inmates and compliance with MDOC maintenance and approval protocols for all work modifications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECHNOLOGY DESIGNER
COMMTECH DESIGN
6585 BELDING RD. NE, SUITE B
ROCKFORD, MI 49341
(616) 863-8132
IONIA CORRECTIONAL FACILITY
IT ROOM EXPANSION
ACTG TEMPLATE: 472ELECTRONICCOMM
FILE NUMBER: 472/25278.RWG
1576 BLUEWATER HWY, IONIA, MI 48846
DRAWING LIST:
IONIA CORRECTIONAL FACILITY
IT ROOM EXPANSION
STATE OF MICHIGAN
ELECTRICAL DRAWING INDEX
ELECTRICAL/MECHANICAL ENGINEER
MATRIX CONSULTING ENGINEERS, INC.
544 CHERBOURG DRIVE
LANSING, MI 48917
(517) 487-2511
ARCHITECTURE ENGINEER
STRAUB PETTITT MANN ARCHITECTURE
850 NORTH CROOKS, SUITE 200
CLAQSON, MI 48017-11311
(248) 658-7777
DRAWING LIST: DRAWING LIST:
TECHNOLOGY DESIGNER DRAWING INDEX ARCHITECT DRAWING INDEX
MECHANICAL DRAWING INDEX
DRAWING LIST:
COVER
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
L A
TC
H
, R A
, N C
A R
B , D
IR
EC
TO
R
FA
C
IL
IT
IE
S
A N
D B
U
SI
N
ES
S
SE
R V
IC
ES
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
C om m te ch
D es ig n
B
EL
D
IN
G R
O
AD
N E.
, S U
IT
E
B R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
AutoCAD SHX Text TC701 CABLING LEGENDS AND DETAILS TC702 CABLING DETAILS TC703 RACK LAYOUT/FIBER AND CABLING DETAILS TC704 IONIA ADMIN RACK LAYOUTS TC705 IONIA ADMIN FIBER CONNECTIVITY CURRENT TO NEW TC706 IONIA EXISTING AND NEW FIBER BACKBONE TC707 IONIA ADMIN RACK LAYOUTS RELOCATION SEQUENCE TC800 IONIA ADMINISTRATION SECOND FLOOR EXISTING AND NEW COMM ROOM LAYOUT
AutoCAD SHX Text E-100 ELECTRICAL NOTES, ABBREV. & SYMBOLS E-300 ADMIN SECOND FLOORPLAN - DEMOLITION E-400 ADMIN SECOND FLOORPLAN - LIGHTING E-500 ADMIN SECOND FLOORPLAN - POWER
AutoCAD SHX Text M-100 MECHANICAL NOTES, SYMBOLS, ABBREV. & SCHEDULES M-400 ADMINISTRATION BUILDING MECHANICAL NEW FLOORPLAN & MECHANICAL DEMOLITION FLOORPLAN
AutoCAD SHX Text A100 ADMIN FLOORPLAN/DOORS AND WALL DETAILS A101 ADMIN FLOORPLAN WITH RACK ELEVATION AND TURTLE SHELL DETAIL
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text file no.
AutoCAD SHX Text checked by
AutoCAD SHX Text drawn by
AutoCAD SHX Text consultant
AutoCAD SHX Text issue date
AutoCAD SHX Text index no.
AutoCAD SHX Text contract order no.
AutoCAD SHX Text consultant job no.
AutoCAD SHX Text sheet title
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text
IT ROOM EXPANSION
AutoCAD SHX Text
IONIA CORRECTIONAL FACILITY
AutoCAD SHX Text
IONIA, MICHIGAN
AutoCAD SHX Text 472ElectronicComm
AutoCAD SHX Text 1065_43
AutoCAD SHX Text Y17084
AutoCAD SHX Text
472/25278.RWG
AutoCAD SHX Text 10/19/26
AutoCAD SHX Text
ISSUE FOR BID
INSTALL NEW SPECIAL
SEALED DOOR
FOR DRY SUPPRESSION
EXISTING DUCT CHASE
EXISTING 1HR FIRE
RATED WALLS
DOOR TO BE REMOVED AND REPLACED WITH
NEW INSULATED 1 1/2" HR RATED METAL DOOR
AND SPECIAL SEALED FOR DRY SUPPRESSION
'-1
1 2
'-4
REMOVE VCT AND CLEAN
CONCRETE FLOOR SURFACE
REMOVE EXISTING 8"X8"X16"
CMU WALL, FULL HEIGHT
CLEAN EXCESS, ADD BLOCK
FILLER AND PAINT TO MATCH
EXISTING.
2'-7 1 2" ±
8"3'-6 1 2" 5'-3"
'-9
7 8
'-2
1-
1-209 1-210
1-218b
1-b
23'-6"±
20'-2"±
5'-4" 8" 8'-0" 8" 8'-10"
'-0
1'-5"
10"
'-1
1 2
2'-10"3'-0"2'-2"±3'-0"
3'-4"3 '-0
'-4
'-7
" V .I.
F
'-3
V
.I.
F
'-8
'-8
1 2
NEW 8"X8"X16" CMU BLOCK
NEW 1 1/2 HR RATED METAL DOOR
3'-0" X 7'-0"
3 12" X 3 12" X 5 16"
ANGLES BACK TO
BACK
REMOVE ACOUSTIC
LAYIN CEILING
PAINT METAL DECK TO
MATCH EXISTING IN
ELECTRIC ROOM
3'-6 7 16"
2'-10 1 2"8" 8"
EXISTING CMU
WALL
ELECTRICAL UNIT
EXISTING CONDUITS
FOAM AND SEALANT
AROUND CONDUITS
SAWCUT EXISTING DOOR
FRAME. INSTALL NEW DOOR
FRAME USING POST
INSTILLATION ANCHORS
INTO EXISTING CMU WALL
INSULATED 1 1/2" HR RATED METAL
DOOR
AND SPECIAL SEALED FOR DRY
SUPPRESSION
BACKER
ROD AND
SEALANT
TYP.
PARTIAL FLOOR PLAN
1/4" = 1' - 0"A100
A100
1 ADMIN BUILDING SECOND FLOOR PLAN
1/8" = 1' - 0"
SECTION
1/4" = 1' - 0"A100
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
L A
TC
H
, R A
, N C
A R
B , D
IR
EC
TO
R
FA
C
IL
IT
IE
S
A N
D B
U
SI
N
ES
S
SE
R V
IC
ES
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
C om m te ch
D es ig n
B
EL
D
IN
G R
O
AD
N E.
, S U
IT
E
B R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
PLAN DETAILS
1 1/2" = 1' - 0"A100
S t r a u b
P e t t i t t M a n n
0 N
. C ro ok s R oa d, Su ite
Cl aw so n, Mi ch iga n 4
8 -
8 -
GROUT SOLID
NEW 1 1/2" HR RATED
METAL DOOR
NEW 1 HR RATED
8"X8"X16" CMU
WALL.
NEW 1 HR RATED
8"X8"X16" CMU
WALL.
INSTALL DOOR SEALS FOR
DRY SUPPRESSION
OPEN OFFICE
FLOOR: CARPET PATCH
BASE: MATCH EXISTING
WALLS: PAINT TO MATCH EXISTING
CEILING: NO WORK
SERVER ROOM 1-211
FLOOR: CONCRETE
BASE: NONE
WALLS: PAINT
CEILING: PAINT
DOORS: PAINT
ELECTRICAL ROOM
FLOOR: NO WORK
BASE: NONE
WALLS: PAINT TO MATCH EXISTING
CEILING: PAINT
DOORS: PAINT
FINISH SCHEDULE
WALL DETAIL AT CONDUITS
1 1/2" = 1' - 0"A100
PLAN DETAILS
1 1/2" = 1' - 0"A100
A100
GROUT SOLID
SEAL CONCRETE FLOOR
SEAL CONCRETE FLOOR
PORTION OF
EXISTING CMU WALL
TO REMAIN
8"X8"X16" CMU FINISH ON TWO
SIDES TOOTH INTO EXISTING
BLOCK PAINT TO MATCH
EXISTING
FOAM AND
SEALANT IN 2" ±
SPACE
8"X8"X16" CMU
FINISH ON TWO
SIDES
BACKER ROD AND
SEALANT TYP.
NOTE:
NEW DOORS HARDWARE SET 1:
Door Bottom: Zero 355AA Semi Mortised Automatic Door Bottom with Neoprene Seal.
Perimeter Gasketing: Zero 870AA Adjustable Perimeter Gasketing Acoustic Door Seal Set.
EXISTING CORRIDOR DOOR 1-209 HARDWARE SET 2:
Door Bottom: Zero 361AA Heavy-Duty Surface Mounted Automatic Door Bottom
Perimeter Gasketing: Zero 870AA Adjustable Perimeter Gasketing Acoustic Door Seal Set
AutoCAD SHX Text 1-218
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 1-207
AutoCAD SHX Text
HUMAN
AutoCAD SHX Text
RESOURCES
AutoCAD SHX Text 1-205
AutoCAD SHX Text
HUMAN
AutoCAD SHX Text
RESOURCE
AutoCAD SHX Text
RECORDS ROOM
AutoCAD SHX Text 1-204
AutoCAD SHX Text
HUMAN
AutoCAD SHX Text
RESOURCES
AutoCAD SHX Text 1-203
AutoCAD SHX Text H.R.
AutoCAD SHX Text
SUPERVISOR
AutoCAD SHX Text 1-202
AutoCAD SHX Text
FACILITY
AutoCAD SHX Text
MANAGER
AutoCAD SHX Text
XXXX
AutoCAD SHX Text
ELEV.
AutoCAD SHX Text 1-201
AutoCAD SHX Text
FACILITY
AutoCAD SHX Text
MANAGER
AutoCAD SHX Text
SECRETARY
AutoCAD SHX Text 1-A
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 1-B
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 1-216
AutoCAD SHX Text
MEN
AutoCAD SHX Text 1-215
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text 1-213
AutoCAD SHX Text J.C.
AutoCAD SHX Text 1-212
AutoCAD SHX Text
LOUNGE
AutoCAD SHX Text 1-211
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text 1-209
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 1-208
AutoCAD SHX Text
CORR.
AutoCAD SHX Text 1-217
AutoCAD SHX Text
EMPLOYEE
AutoCAD SHX Text
COMP
AutoCAD SHX Text
TRAINING AREA
AutoCAD SHX Text 1-218
AutoCAD SHX Text
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 1-221
AutoCAD SHX Text
STAFF
AutoCAD SHX Text
TRAINING
AutoCAD SHX Text
AREA
AutoCAD SHX Text 1-222
AutoCAD SHX Text
HRD
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 1-223
AutoCAD SHX Text
HRD
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 1-206
AutoCAD SHX Text
CORR.
AutoCAD SHX Text 1-219
AutoCAD SHX Text
CORR.
AutoCAD SHX Text 1-220
AutoCAD SHX Text
CORR.
AutoCAD SHX Text 1-214
AutoCAD SHX Text
CORR.
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
DROP CEILING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A100
AutoCAD SHX Text
AutoCAD SHX Text 1-210
AutoCAD SHX Text
TELEPHONE/DATA
AutoCAD SHX Text A100
AutoCAD SHX Text
AutoCAD SHX Text A100
AutoCAD SHX Text
AutoCAD SHX Text A101
AutoCAD SHX Text
AutoCAD SHX Text A101
AutoCAD SHX Text
AutoCAD SHX Text 1-211
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text 1-209
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 1-208
AutoCAD SHX Text
CORR.
AutoCAD SHX Text 1-210
AutoCAD SHX Text
TELEPHONE/DATA
AutoCAD SHX Text A100
AutoCAD SHX Text
AutoCAD SHX Text A100
AutoCAD SHX Text
AutoCAD SHX Text A100
AutoCAD SHX Text
AutoCAD SHX Text 1-209b
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text file no.
AutoCAD SHX Text checked by
AutoCAD SHX Text drawn by
AutoCAD SHX Text consultant
AutoCAD SHX Text issue date
AutoCAD SHX Text index no.
AutoCAD SHX Text contract order no.
AutoCAD SHX Text consultant job no.
AutoCAD SHX Text sheet title
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text
IONIA IT ROOM EXPANSION
AutoCAD SHX Text
IONIA CORRECTIONAL FACILITY
AutoCAD SHX Text
IONIA, MICHIGAN
AutoCAD SHX Text 472ElectronicComm
AutoCAD SHX Text 1065_43
AutoCAD SHX Text Y17084
AutoCAD SHX Text
472/25278.RWG
AutoCAD SHX Text
DOOR SCHEDULE
AutoCAD SHX Text
DOOR NUMBERS
AutoCAD SHX Text
DOOR SIZE
AutoCAD SHX Text
DOOR TYPE
AutoCAD SHX Text
DOOR MAT'L
AutoCAD SHX Text
FRAME TYPE
AutoCAD SHX Text
FRAME MAT'L
AutoCAD SHX Text
FRAME DETAILS
AutoCAD SHX Text
HARDWARE SET
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
SET 1
AutoCAD SHX Text 1-211
AutoCAD SHX Text 3'-0" x 7'-0"
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
EXISTING HOLLOW METAL
AutoCAD SHX Text
SET 2
AutoCAD SHX Text 3'-0" x 6'-10"
AutoCAD SHX Text
EXISTING HOLLOW METAL
AutoCAD SHX Text
SET 1
AutoCAD SHX Text
NEW HOLLOW METAL
AutoCAD SHX Text 1-209
AutoCAD SHX Text 1-210
AutoCAD SHX Text
INSULATED 1 1/2" HR RATED METAL DOOR PAINT DOOR AND FRAME
AutoCAD SHX Text
INSULATED 1 1/2" HR RATED METAL DOOR WITH DRY SUPPRESSION PAINT DOOR AND FRAME
AutoCAD SHX Text 3'-0" x 6'-10"
AutoCAD SHX Text 3'-0" x 6'-10"
AutoCAD SHX Text
PAINT DOOR AND FRAME
AutoCAD SHX Text
PAINT DOOR AND FRAME
AutoCAD SHX Text
NEW HOLLOW METAL
AutoCAD SHX Text
EXISTING HOLLOW METAL
AutoCAD SHX Text
EXISTING HOLLOW METAL
AutoCAD SHX Text
NEW HOLLOW METAL
AutoCAD SHX Text
NEW HOLLOW METAL
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text 10/19/26
ISSUED FOR BIDS
2'-7 1 2" ±
8"3'-6 1 2" 5'-3"
'-9
11 16
'-2
1-
1-209 1-210
1-218b
1-b
23'-6"±
20'-2"±
5'-4" 8" 8'-0" 8" 8'-10"
'-0
1'-5"
10"
'-1
1 2
2'-10"3'-0"2'-2"±3'-0"
3'-4"3 '-0
C
ABLE M
AN
AG
EM
EN
T
R
AC
KS
ALIGN NEW WALL COURSING TO EXISTING BRICK
7' -6
'-4
4'-6"
EXISTING PIPES
VERIFY IN FIELD
'-7
" V .I.
F
'-3
V
.I.
F
'-8
'-8
1 2
EXISTING HVAC
DUCT TO ROOF
VERIFY IN FIELD
REMOVE
ACOUSTIC
LAYIN CEILING
PAINT METAL
DECK TO
MATCH
EXISTING IN
ELECTRIC ROOM
NEW 8"X8"X16"
CMU BLOCK
NEW 1 1/2 HR RATED METAL DOOR
3'-0" X 7'-0"
2'-7 1 2" ±
8"3'-6 1 2" 5'-3"
'-9
7 8
'-2
1-
1-209 1-210
1-218b
1-b
23'-6"±
20'-2"±
5'-4" 8" 8'-0" 8" 8'-10"
'-0
1'-5"
10"
'-1
1 2
2'-10"3'-0"2'-2"±3'-0"
3'-4"3 '-0
"SERVER RACKS
NEW RACKS4
'-6
LADDERPERPENDICULAR LADDER
C
ABLE M
AN
AG
EM
EN
T
R
AC
KS 7'
-5
3 4
'-3
7 8
9"
2'-6"
2'-4"9"
7' -0
FRONT OF THE
RACK
WATER STOP
UNISTRUT
3"1'-11"7"1'-11"7"1'-11"107 8"1'-11"
R A
C K
R A
C K
R A
C K
R A
C K
8"1'-11"
R A
C K
7"
8'-83 4"
7'-1" 7'-1"
7' -0
C A
B
LE
M G
T
C A
B
LE
M G
T
C A
B
LE
M G
T
C A
B
LE
M G
T
NEW SHELL OVER RACK NEW SHELL FLUSH TO
EXISTING WALL WITH WALL
MOUNTING FLANGE
INSTALL NEW LADDER RACK
13'-43 4"
7'-1"
'-0
1'-2"
'-4
8"
RIVETS EVERY 8"
2" WATER STOP ON THE BACK
PARTIAL FLOOR PLAN
1/4" = 1' - 0"A101
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
L A
TC
H
, R A
, N C
A R
B , D
IR
EC
TO
R
FA
C
IL
IT
IE
S
A N
D B
U
SI
N
ES
S
SE
R V
IC
ES
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
C om m te ch
D es ig n
B
EL
D
IN
G R
O
AD
N E.
, S U
IT
E
B R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
S t r a u b
P e t t i t t M a n n
0 N
. C ro ok s R oa d, Su ite
Cl aw so n, Mi ch iga n 4
8 -
8 -
A101A101
4 SECTION WITH RACKS
3/4" = 1' - 0"
PARTIAL FLOOR PLAN WITH RACKS AT 7'-0"
1/4" = 1' - 0"A101
DETAIL SECTION OF RACK
1/2" = 1' - 0"A101
FRONT ELEVATION OF RACKS
1/4" = 1' - 0"A101
DETAIL OF SHELL
1/2" = 1' - 0"A101
7'-1"
AutoCAD SHX Text 1-209
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 1-208
AutoCAD SHX Text
CORR.
AutoCAD SHX Text A101
AutoCAD SHX Text
AutoCAD SHX Text 1-210
AutoCAD SHX Text
TELEPHONE/DATA
AutoCAD SHX Text A101
AutoCAD SHX Text
AutoCAD SHX Text 1-211
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text 1-209
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 1-208
AutoCAD SHX Text
CORR.
AutoCAD SHX Text 1-210
AutoCAD SHX Text
TELEPHONE/DATA
AutoCAD SHX Text A101
AutoCAD SHX Text
AutoCAD SHX Text A101
AutoCAD SHX Text
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text file no.
AutoCAD SHX Text checked by
AutoCAD SHX Text drawn by
AutoCAD SHX Text consultant
AutoCAD SHX Text issue date
AutoCAD SHX Text index no.
AutoCAD SHX Text contract order no.
AutoCAD SHX Text consultant job no.
AutoCAD SHX Text sheet title
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text
IONIA IT ROOM EXPANSION
AutoCAD SHX Text
IONIA CORRECTIONAL FACILITY
AutoCAD SHX Text
IONIA, MICHIGAN
AutoCAD SHX Text 472ElectronicComm
AutoCAD SHX Text 1065_43
AutoCAD SHX Text Y17084
AutoCAD SHX Text
472/25278.RWG
AutoCAD SHX Text A101
AutoCAD SHX Text
AutoCAD SHX Text 10/19/26
ISSUED FOR BIDS
GENERAL HVAC NOTES
1. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER
MANUFACTURERS WRITTEN INSTRUCTIONS.
3. ALL EXISTING SYSTEMS (AIR HANDLING UNITS) THAT SERVES
AREAS BEING RENOVATED SHALL BE REBALANCED AS
REQUIRED.
4. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION
THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.
5. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY
CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS
NEEDED.
6. LOCATIONS OF THE THERMOSTATS TO BE VERIFIED IN FIELD.
7. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
8. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.
9. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS
THAT MAY AFFECT THE WORK.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
11. ALL WORK SHALL BE PERFORMED BY LICENSED
CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY
LAW.
12. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.
13. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA
AIR GAP.
14. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR
SPECIFICATIONS THE MORE STRINGENT AND GREATER COST
ITEM SHALL BE USED.
15. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.
IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL
NECESSARY OFFSETS. INSTALL WORK IN MANNER TO
CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
DO NOT SCALE FROM DRAWINGS.
16. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,
REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE
STATUTES, ORDINANCES, CODES OR REGULATIONS OF
FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING
JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
17. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY
OSHA, UNDERWRITERS, LABORATORIES, AMERICAN CODES,
ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION
BODY, NFPA OR OTHERS, THESE STANDARDS SHALL BE
FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING
AND SPECIFICATIONS.
18. COORDINATE WITH ARCHITECTURAL AND STRUCTURAL
DRAWINGS FOR EXACT LOCATION OF EQUIPMENT.
19. DUCT/PIPING LAYOUT IS SCHEMATIC. EXACT LOCATION OF
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH
BUILDING STRUCTURE, EQUIPMENT FURNISHED,
ARCHITECTURAL DRAWINGS, AND ALL OTHER TRADES PRIOR
TO INSTALLATION. ANY CONTRACTOR INSTALLING WORK
WITHOUT PRIOR COORDINATION SHALL RELOCATE HIS WORK
AT HIS EXPENSE TO ALLOW PROPER INSTALLATION OF ANY
AND ALL TRADES WORK.
20. UNLESS OTHERWISE NOTED, ALL PIPING SHALL BE
CONCEALED WHEREVER POSSIBLE. PROVIDE CHROME
ESCUTCHEON OR ALUMINUM DUCT COLLAR AT EACH
PENETRATION OF A FINISHED SURFACE.
21. PIPING SHALL NOT BE RUN ABOVE ELECTRICAL GEAR IN THE
SERVICE SPACE REQUIRED BY THE NATIONAL ELECTRICAL
CODE.
22. ANY ADDITIONAL LOW VOLTAGE CONTROL WIRING THAT IS
REQUIRED SHALL BE PROVIDED BY THE HVAC CONTRACTOR.
CONTROL WIRING SHALL BE RUN IN CONDUIT IF REQUIRED BY
LOCAL CODES OR THE SPECIFICATIONS. POWER SHALL BE
PROVIDED BY THE ELECTRICAL CONTRACTOR.
23. PROVIDE TRAP FOR CONDENSATION DRAIN LINES.
24. PROVIDE VIBRATION ISOLATION AT EACH CONNECTION TO A
MOTORIZED PIECE OF EQUIPMENT BY THE HVAC
CONTRACTOR.
25. MOUNT THERMOSTAT/SENSORS AT 48" AFF UNLESS NOTED
OTHERWISE.
26. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO
OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED
THROUGHOUT THE PROJECT.
27. CONTRACTOR WILL HAVE 1 ESCORT TO WORK WITH THROUGH
AT THE PROJECT.
28. CONTRACTOR TO PATCH AND PAINT EXISTING WALLS AS
NEEDED TO MATCH EXISTING WHERE DEMOLITION AND/OR
NEW WORK IS COMPLETED.
29. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN
ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO
DISABLE THE FIRE ALARM.
30. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL
USE TAMPERPROOF SCREWS.
31. ALL ROOF PENETRATIONS SHALL BE SEALED WATER TIGHT
AND SHALL MAINTAIN ALL EXISTING WARRANTIES.
32. ALL HOT WORK WILL REQUIRE THE COMPLETION OF A CAJ-516
FORM AND THE PULLING OF A HOT WORK PERMIT FROM THE
MDOC MAINTENANCE STAFF.
33. DETAILED PLANS FOR THE FIRE SUPPRESSION LAYOUT AND
FLOW CALCULATIONS TO BE SUBMITTED SEPARATELY BY THE
CONTRACTOR TO LARA PLAN REVIEW AND MDOC (AHJ) FOR
REVIEW AND APPROVAL.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLS
HVAC PIPING
HVAC DUCTWORK
F/S F/S s s
TEMPERATURE CONTROL SYMBOLS
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
FLOAT & THERMOSTATIC STEAM TRAP
INVERTED BUCKET STEAM TRAP
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
TURNING VANES
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
90° TEE W/45° APPROACH
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
EXISTING VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
EXISTING HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
BT
FT
SD-1 250
8"ø ---
P
H
S
T
T P
T N
M
M
SD
1. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
2. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING
STRUCTURE, EQUIPMENT FURNISHED, ARCHITECTURAL DRAWINGS AND ALL
OTHER TRADES PRIOR TO DEMOLITION.
3. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,
AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,
CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES
HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
4. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,
UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,
STATE FIRE INSURANCE REGULATION BODY, NFPA OR OTHERS. THESE
STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE
DRAWING AND SPECIFICATIONS.
5. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.
6. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY
KEYNOTE. ALL OTHER EXISTING SYSTEMS SHOWN FOR REFERENCE ONLY.
7. PATCH AND REPAIR ALL WALL SURFACES LEFT DAMAGED OR INCOMPLETE
FROM REMOVAL OF EXISTING EQUIPMENT WITH MATERIALS TO MATCH
EXISTING, AS ACCEPTABLE TO THE ARCHITECT.
8. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL
ATTENTION TO DEMOLITION WHICH IS REQUIRED. HOWEVER, THESE
DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE
REMOVED. CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR
RESPECTIVE TRADES AS REQUIRED TO PERMIT THE CONSTRUCTION OF THE
NEW WORK AS SHOWN.
9. THE GENERAL CONTRACTOR SHALL COORDINATE THE EXTENT OF THE
REQUIRED DEMOLITION OF THE EXISTING BUILDING AS REQUIRED TO
FACILITATE THE CONSTRUCTION OF THE PROJECT AS SHOWN AS PART OF
THIS WORK.
10. ALL DEMOLITION SHALL BE APPROVED BY THE OWNER/TENANT PRIOR TO
COMMENCEMENT AND SHALL BE PERFORMED UNDER REQUIREMENTS AND
APPROVAL OF THE LOCAL CODE JURISDICTIONS.
11. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN
APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.
12. RUBBISH AND DEBRIS RESULTING FROM THE WORK SHALL BE REMOVED
IMMEDIATELY FROM THE SITE IN A SAFE AND LEGAL MANNER BY THE
CONTRACTOR.
13. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING
REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE
DOCUMENTS OR SHOWN NOT MATCHING FIELD CONDITIONS.
GENERAL DEMOLITION NOTES PLUMBING ABBREVIATIONS
AD AREA DRAIN
ASR AUTOMATIC SPRINKLER RISER
BFS BELOW FLOOR SLAB
BWV BACK WATER VALVE
CB CATCH BASIN
CI CAST IRON
CO CLEAN OUT
CV CONTROL VALVE
DF DRINKING FOUNTAIN
DIA DIAMETER
DN DOWN
DWH DOMESTIC WATER HEATER
E.T.C. ELECTRICAL TRADES CONTRACTOR
EWC ELECTRIC WATER COOLER
EXIST EXISTING
FD FLOOR DRAIN
FC FINAL CONNECTIONS
FDC FIRE DEPT. CONNECTION
FF FINISH FLOOR
FHV FIRE HOSE VALVE
FT FEET
GAL GALLON
GD GARBAGE DISPOSAL
GI GREASE INTERCEPTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HB HOSE BIB
HD HEAD (FT)
HP HORSE POWER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
LAV LAVATORY
LT LAUNDRY TRAY
MA MEDICAL AIR
MAX MAXIMUM
MGC MEDICAL GAS CONSOLE
MH MAN HOLE
MIN MINIMUM
MS MOP SINK
M.T.C. MECHANICAL TRADES CONTRACTOR
NTS NOT TO SCALE
ORD OVERFLOW ROOF DRAIN
OXY OXYGEN
P PUMP
PD PRESSURE DROP
PVC POLY-VINYL-CHLORIDE
RC RAIN CONDUCTOR
RD ROOF DRAIN
RI ROUGH-IN
REQ'D REQUIRED
SAN SANITARY
SHWR SHOWER
SK SINK
SP STAND PIPE
SQ. FT. SQUARE FEET
SS SERVICE SINK
ST STORM
S&W STOP & WASTE
STR STRAINER
SV STACKED VENT
TYP. TYPICAL
UR URINAL
VB VACUUM BREAKER
VS VENT STACK
V.F.D VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
W WASTE
WB WET BULB
WC WATER CLOSET
WH WALL HYDRANT
WS WASTE STACK
W&V WASTE AND VENT
X-CW EXIST. CW PIPING
ITEM
EXISTING
FIRE PROTECTION SYMBOLS LEGEND
PLUMBING PIPING PLUMBING EQUIPMENT
MISCELLANEOUS NOTES
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
FIRE PROTECTION FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
INLINE CLEANOUT
CONNECTION
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
FLOOR DRAIN & FLOOR SINK
BACK FLOW PREVENTER
FLANGE END CONNECTION
PIPE CAP
PIPE BREAK
WATER METER
PRESSURE GAUGE
FIRE HYDRANT
SPRINKLER HEAD (PENDANT)
SPRINKLER HEAD (UPRIGHT)
SPRINKLER HEAD (SIDEWALL)
FIRE DEPARTMENT CONNECTION
FLOW SWITCH
PRESSURE SWITCH
SUPERVISORY SWITCH INVERTED
X
X
XX
XXXX
XX
XXXX
FP
M
P
FS
PS
SS
FIRE PROTECTION DESIGN DATA
1. FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN AND
PAY FOR REQUIRED PERMITS AND APPROVAL FEES ASSOCIATED WITH
THIS PROJECT FOR HIS PORTION OF THE WORK.
GENERAL CONDITIONS
1. FIRE PROTECTION DESIGN, PIPING, CALCULATIONS, AND DRAWINGS SHALL BE COMPLETED BY
CERTIFIED FIRE PROTECTION CONTRACTOR.
2. PROVIDE LABOR, MATERIAL, AND EQUIPMENT NECESSARY TO FURNISH AND INSTALL FIRE PROTECTION
WORK. WORK SHALL CONFORM WITH THE BUILDING AND FIRE CODES AND NFPA CRITERIA.
3. WORK SHALL BE COORDINATED WITH OWNER AND WITH OTHER TRADES TO AVOID INTERFERENCES.
GENERAL NOTES FOR FIRE PROTECTION
DESIGN:
DRY CHEMICAL CALCULATIONS SHALL BE BASED ON NFPA 13, NFPA 2001,
AND SHALL COMPLY WITH THE RESPECTIVE REQUIREMENTS AND THE
REQUIREMENTS OF THE LOCAL FIRE MARSHALL, CODES, AND
AUTHORITY HAVING JURISDICTION. WHICHEVER IS MOST STRINGENT.
DESIGN DATA:
NOVEC 1230 DRY CHEMICAL FIRE SUPPRESSION SYSTEM.
INSPECTION:
PLANS OF THE SPRINKLER SYSTEMS SHALL BE SUBMITTED TO THE
LOCAL FIRE MARSHALL AND AUTHORITY HAVING JURISDICTION FOR
PLAN REVIEW.
NOTES:
1. UNLESS OTHERWISE NOTED, COORDINATE HEAD LOCATIONS WITH
GENERAL MECHANICAL, ELECTRICAL, AND PLUMBING CONTRACTORS
AND EXISTING EQUIPMENT PRIOR TO INSTALLATION TO AVOID ANY
CONFLICTS.
1. FIRE PROTECTION SYSTEM SHALL BE DESIGNED IN COMPLIANCE WITH THE
LATEST EDITION OF NFPA 13, NFPA 2001, AND LOCAL FIRE CODE
REQUIREMENTS.
2. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,
REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUES,
ORDINANCES, CODES OF REGULATIONS OF FEDERAL, STATE, AND LOCAL
AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE
RECEIVED.
3. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,
UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI,
NEC, STATE FIRE INSURANCE REGULATION BODY, NFPA, OR OTHERS.
THESE STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED
ON THE DRAWING AND SPECIFICATIONS.
4. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER
MANUFACTURERS WRITTEN INSTRUCTIONS.
5. ALL PIPE SIZES SHOWN ARE SERVICE SIZE. SIZE SLEEVES FOR 1" CLEAR
SPACE BETWEEN PIPE AND SLEEVE FOR INSTALLATION OF MECHANICAL
SEAL.
6. FIRE SUPPRESSION DESIGN & PIPING SHALL BE COMPLETED BY CERTIFIED
FIRE SUPPRESSION CONTRACTOR.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE
INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW" CONDITION
DURING CONSTRUCTION.
8. ALL WORK SHALL BE PERFORMED BY LICENSED CONTRACTORS AND
SUBCONTRACTORS AS REQUIRED BY LAW.
9. DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE CODES
AND REGULATIONS ENFORCED BY LOCAL BUILDING OFFICIALS.
10. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF
PIPES AND SUGGESTED ROUTES. IT IS NOT INTENTION OF DRAWINGS TO
INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO
CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE HEADROOM
AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM
DRAWINGS.
11. FIRE SUPPRESSION PLANS ARE BASED ON A PERFORMANCE
SPECIFICATION AND IDENTIFY AREAS FOR FIRE SUPPRESSION. DETAILED
PLANS FOR THE FIRE SUPPRESSION LAYOUT AND FLOW CALCULATIONS
TO BE SUBMITTED SEPARATELY BY THE CONTRACTOR TO PLAN REVIEW
FOR APPROVAL WITH THEIR HYDRAULIC CALCULATIONS.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING ALL REQUIRED
HYDRAULIC CALCULATIONS.
13. PROVIDE AND INSTALL ADDITIONAL AUTOMATIC SPRINKLERS UNDER ALL
OBSTRUCTIONS IN EXPOSED AREAS PER NFPA 13 AND NFPA 2001. THIS
SHOULD INCLUDE ADDITIONAL SPRINKLERS BELOW DUCTS AND
MEZZANINES WHICH ARE 48 INCHES WIDE OR WIDER. ALL SPRINKLERS
UNDER OBSTRUCTIONS SHALL BE EQUIPPED WITH CAGE GUARDS.
14. WHERE REQUIRED BY CODE OR DIRECTED BY LOCAL AUTHORITIES ,
CONTRACTOR SHALL PROVIDE SEISMIC HANGING & CONSTRAINTS ON ALL
PIPING IN COMPLETE ACCORDANCE WITH THE LATEST ISSUE OF THE
STATE MECHANICAL BUILDING CODE, LOCAL CODES, AND NFPA.
15. FIRE PROTECTION CONTRACTOR OR ANY OF THEIR SUB-CONTRACTORS
SHALL BE RESPONSIBLE FOR DAMAGE TO OWNER'S PROPERTY AND
SHALL REPAIR EQUIPMENT OR UTILITIES DAMAGED BY HIS EMPLOYEES
WHILE PERFORMING WORK. REPAIRS SHALL BE PERFORMED ONLY BY
CERTIFIED TRADE PERSONNEL. COSTS INVOLVED WITH THIS REPAIR
SHALL BE THE RESPONSIBILITY OF THE FIRE PROTECTION CONTRACTOR
AS ASSESSED BY THE PROJECT MANAGER.
16. ALL EQUIPMENT AND MATERIAL BEING UTILIZED SHALL BE UNDERWRITERS
LABORATORIES LISTED-(UL) APPROVED AND LISTED IN THE CURRENT
EDITION OF APPROVAL GUIDES.
17. ANY PENETRATION THROUGH THE EXTERIOR WALLS OR FLOORS SHALL BE
SEALED TO MAKE WATER TIGHT AND MAINTAIN CURRENT FIRE RATINGS.
18. ALL PIPE, FITTINGS, AND HANGERS SHALL BE AS PERMITTED BY NFPA 13,
CURRENT EDITION AND ATTACHED TO STRUCTURAL MEMBERS.
19. MATERIALS AND WORKMANSHIP FOR FIRE PROTECTION CONTRACTORS
WORK SHALL HAVE A MINIMUM OF A ONE-(1) YEAR GUARANTEE FROM THE
TIME THE SYSTEM IS ACCEPTED AND APPROVED BY THE OWNER.
20. FIRE PROTECTION CONTRACTOR SHALL BE CERTIFIED BY THE STATE OF
MICHIGAN, TO PERFORM THIS WORK.
21. AT THE COMPLETION OF THE PROJECT THE FIRE PROTECTION
CONTRACTOR SHALL FURNISH TO THE OWNER AN OPERATION AND
MAINTENANCE MANUAL COMPLETE WITH: CATALOG CUTS ON ALL MAJOR
PIECES FOR EQUIPMENT, COPY OF HYDRAULIC CALCULATIONS, COPY OF
DRAWINGS IN AUTO-CAD FORMAT, CURRENT EDITION, RECOMMENDED
SPARE PARTS LIST, WIRING DIAGRAMS, AND OWNER'S MANUAL.
22. FIRE PROTECTION CONTRACTOR SHALL FURNISH THE OWNER WITH
THREE (3) COPIES OF THE MATERIAL AND TEST CERTIFICATES AT THE
COMPLETION OF THE PROJECT.
23. PROVIDE A SPARE SPRINKLER HEAD CABINET WITH A MINIMUM OF
THREE-(3) SPRINKLERS OF EACH TYPE UTILIZED.
24. ALL SMOKE DETECTORS, PULL STATIONS, AND OTHER FIRE SUPPRESSION
DETECTION DEVICES SHALL BE TIED INTO THE MAIN FIRE ALARM PANEL.
25. ALL SPRINKLERS IN ELECTRICAL ROOMS SHALL BE 286°F COMPLETE WITH
CAGE GUARDS.
26. ALL SPRINKLERS SHALL BE INSTALLED IN THE CENTER OF TILE WITH A 1"
VARIANCE IN EITHER DIRECTION. QUARTER POINTS ARE NOT ALLOWED.
27. FIRE PROTECTION CONTRACTOR SHALL PAY CLOSE ATTENTION THAT THIS
IS A WORKING SITE. INSTALLATION MUST BE COORDINATED WITH THE
PROJECT MANAGER AND BUILDING COORDINATOR.
28. FIRE PROTECTION CONTRACTOR SHALL REVIEW AND COORDINATE ALL
WORK ACTIVITIES WITH OTHER TRADES TO ALLEVIATE POTENTIAL
CONFLICTS.
29. ALL SPRINKLER PIPING SHALL BE SUPPORTED FROM TOP CHORD OF
JOISTS. DO NOT SUSPEND ITEMS FROM BOTTOM CHORD WITHOUT
SPECIFIC APPROVAL.
30. INSTALL NEW NOVAC 1230 DRY FIRE SUPPRESSION SYSTEM AND ALL
ACCESSORIES PER NFPA 13 AS REQUIRED TO SERVE THE IT ROOM AS
INDICATED ON DRAWINGS. NEW DRY FIRE SUPPRESSION SYSTEM TO BE
INSTALLED BY CERTIFIED FIRE SUPPRESSION CONTRACTOR.
31. ALL NEW/RELOCATED DUCTWORK AND EQUIPMENT IS TO BE AT LEAST 36"
FROM SMOKE DETECTORS.
GENERAL FIRE SUPPRESSION NOTES
9"x15.25" POLYCARBONATE
ROOF MOUNTING PADS
12 GA. HOT DIPPED
GALVANIZED STRUT
12 GA. HOT DIPPED
GALVANIZED STRUT
NOTES:
1. ROOF MOUNTED EQUIPMENT STAND BASED ON
MIRO-HD OR APPROVED EQUIVALENT.
2. CONTRACTOR TO COORDINATE SIZE OF CONDENSING
UNIT PRIOR TO ORDERING EQUIPMENT STAND TO
ENSURE PROPER FITMENT.
3. CONTRACTOR TO MOUNT CONDENSING UNIT TO
ADJUSTABLE FRAME RAILS WITH CORROSION
RESISTANT HARDWARE.
4. CONTRACTOR TO ENSURE THE BOTTOM OF THE
CONDENSING UNIT IS AT LEAST 18" ABOVE THE ROOF.
1 ROOF MOUNTED CONDENSING UNIT STAND DETAIL
SCALE: NTS
M-100
MECHANICAL NOTES,
SYMBOLS, ABBREVIATIONS,
AND SCHEDULES
file no.
checked by drawn by consultant issue date index no.
contract order no.
consultant job no.
sheet title
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
L A
TC
H
, R A
, N C
A R
B , D
IR
EC
TO
R
FA
C
IL
IT
IE
S
A N
D B
U
SI
N
ES
S
SE
R V
IC
ES
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
C om m te ch
D es ig n
B
EL
D
IN
G R
O
AD
N E.
, S U
IT
E
B R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
472ElectronicComm
1065_43
Y17084
472/25278.RWG
10/19/26 ISSUE FOR BID
TAT
CAT
X-CU-1 (ON ROOF)
X-CD
X-ECARO-25
TANK
X-3/4"
X-24x24 OA
UP TO
INTAKE
HOOD
X-RELIEF AIR UP
TO X-RELIEF HOOD
X-UH-2
X-EF-11
X-12x12 OA
UP X-IH
X-36x20 RA
X-40x20 RA X-36x36 UP TO INTAKE HOOD X-20x20
DN
X-FD
X-
DX
X-
DX
X-
DX
X-
DX
X-CD
PUMP
X-36x20 RA
X-AC-1
X-FT
X-FIRE SUPPRESSION
CONTROL PANEL
X-HS/HR
X-3/4" HS AND HR
X-FT
X-3/4" HS AND HR
M-400
M-400
INSTALL NEW NOVEC 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEM,
PIPING, DISCHARGE HEADS, CONTROLS, CONTROL PANEL, ALARM DEVICES,
AND ALL ASSOCIATED ACCESSORIES PER NFPA REQUIREMENTS TO SERVE
ENTIRE IT ROOM AND PROVIDE ANY ADDITIONAL PIPING, HEADS, OR
ACCESSORIES AS NEEDED FOR A COMPLETE AND OPERABLE STANDALONE
SYSTEM PER NFPA. CONNECT NEW NOVEC 1230 CLEAN AGENT SYSTEM TO
EXISTING FIRE ALARM SYSTEM. RE-CERTIFY FIRE ALARM SYSTEM TO
COMPLY WITH NFPA AND ENSURE COMPLETE AND OPERABLE SYSTEM.
INSTALLED SALVAGED FIRE SUPPRESSION CONTROL PANEL AND ALL
ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN. CONTRACTOR TO
RE-CERTIFY MODIFIED FIRE SUPPRESSION SYSTEM/ALARM TO COMPLY WITH
NFPA AND ENSURE A COMPLETE AND OPERABLE SYSTEM
FIRE PROTECTION KEY NOTES
MECHANICAL KEY NOTES
INSTALL NEW CEILING MOUNTED AC UNIT, ROOF MOUNTED CONDENSING UNIT,
CONTROLS, CONTROL WIRING, THERMOSTAT, PIPING, VALVES, FITTINGS, AND ALL
ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS. INSTALL NEW CEILING MOUNTED AC UNIT AS HIGH
AS POSSIBLE IN THE SPACE. NEW CONDENSING UNIT IS TO BE INSTALLED ON NEW
CONTRACTOR PROVIDED ROOF EQUIPMENT MOUNTING STAND (BASED ON
MIRO-HD EQUIPMENT SUPPORT STAND OR APPROVED EQUIVALENT) WITH
BOTTOM OF CONDENSING UNIT TO BE 18" ABOVE ROOF. INSTALL
POLYPROPYLENE PADS BETWEEN CONDENSING UNIT STAND AND ROOF. CEILING
MOUNTED AC UNIT AND ROOF MOUNTED CONDENSING UNIT ARE TO BE
INSTALLED TO ACCOMMODATE ALL MANUFACTURER RECOMMENDED
CLEARANCES. CONTRACTOR TO PATCH ALL ROOF PENETRATIONS AS REQUIRED
TO MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF
WARRANTIES. CONNECT NEW AC UNIT AND ALL CONTROLS TO EXISTING TRANE
DDC CONTROL SYSTEM. CONTRACTOR TO PROVIDE ALL REQUIRED CONTROLS
EQUIPMENT TO INTEGRATE NEW AC UNIT ON THE BAS FRONT-END GRAPHICS.
INSTALL NEW CONDENSATE PUMP, CONDENSATE PIPING, DX PIPING, VALVES,
FITTINGS, HANGERS, AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION
SHOWN. ROUTE CONDENSATE PIPING AND DX PIPING THROUGH THE EXISTING
INTERIOR WALL IN LOCATION SHOWN. CONTRACTOR TO ROUTE NEW DX PIPING
THROUGH EXISTING PIPE CURB AND NEW ROOF BOOT IN THE LOCATIONS SHOWN.
CONTRACTOR TO PATCH, PRIME, AND PAINT INTERIOR WALL PENETRATIONS AS
REQUIRED TO MATCH EXISTING. CONTRACTOR TO PATCH ALL ROOF
PENETRATIONS AS REQUIRED TO MATCH EXISTING, SEAL WATER TIGHT, AND
MAINTAIN ANY EXISTING ROOF WARRANTIES. CONTRACTOR TO MODIFY EXISTING
CONDENSATE PIPING AS REQUIRED TO MAKE NEW CONNECTION IN THE LOCATION
SHOWN.
SUPPORT REFRIGERANT PIPING WITH MIRO 24-BASE STRUT OR APPROVED
EQUAL. SUPPORTS SHALL BE CAPABLE OF BEING FIELD ADJUSTED BY
CONTRACTOR TO SUPPORT DX PIPING WITH UP TO A 2% SLOPE. SPACING AND
QUANTITY OF PIPE SUPPORTS SHALL BE DETERMINED BY PIPE SUPPORT
MANUFACTURER, BUT NOT TO EXCEED 8' SPACING. STRUT AND ALL HARDWARE
FOR SUPPORTS SHALL BE GALVANIZED AND BASES SHALL BE POLYCARBONATE.
INSTALL NEW DUCTWORK, FITTINGS, SUPPORTS, DIFFUSER, AND ALL ASSOCIATED
ACCESSORIES IN THE LOCATION SHOWN. MODIFY EXISTING DUCTWORK AS
REQUIRED TO MAKE NEW CONNECTION. CONTRACTOR TO COORDINATE WITH ALL
TRADES IN INSTALL NEW DUCTWORK IN NEW BLOCK WALL. CONTRACTOR TO
INSTALL NEW DUCTWORK/DIFFUSER AS HIGH AS POSSIBLE.
CONTRACTOR TO ENSURE NEW CEILING MOUNTED AC UNIT, DX PIPING,
CONDENSATE PIPING AND ALL ASSOCIATED ACCESSORIES ARE NOT INSTALLED
ABOVE DATA RACKS. CONTRACTOR TO COORDINATE WITH DATA RACK
CONTRACTOR TO MINIMIZE THE CROSSING OF DX PIPING/CONDENSATE PIPING
WITH NEW/EXISTING CABLE TRAYS.
CONNECT EXISTING HEATING SUPPLY AND HEATING RETURN PIPING INSIDE
EXISTING FIN TUBE ENCLOSURE.
INSTALL NEW FLAT PLATE BAS TEMPERATURE SENSOR, CONTROL WIRING,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER
THE MANUFACTURERS INSTALLATION INSTRUCTIONS AS REQUIRED TO CONNECT
TO EXISTING DDC CONTROL PANEL AND BE INTEGRATED ON TO THE EXISTING BAS
FRONT END GRAPHICS. BAS TEMPERATURE SENSOR IS TO ALARM BAS IF
TEMPERATURE IS OVER 80 DEG F (ADJUSTABLE).
GENERAL MECHANICAL NOTES
1. INSTALL NEW AC UNIT, CONDENSING UNIT, DX PIPING, CONDENSATE PIPING,
THERMOSTAT, AND ALL ASSOCIATED ACCESSORIES PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS. ENSURE ALL MANUFACTURER REQUIRED
CLEARANCES ARE MET.
2. REFRIGERANT PIPING ROOF PENETRATIONS ARE TO BE ROUTED UP TO
ROOF THROUGH A EXISTING PIPE CURB WITH A NEW ROOF PIPE BOOT
INSTALLED ON TOP OF THE EXISTING CURB. SEAL NEW BOOT WATER TIGHT.
ALL ROOF PATCHING IS TO MATCH EXISTING, SEAL WATER TIGHT, AND
MAINTAIN ANY EXISTING ROOF WARRANTIES.
3. CONTRACTOR TO PATCH, PRIME, AND PAINT WALLS/CEILINGS AS REQUIRED
TO MATCH EXISTING AS REQUIRED AFTER ALL WORK IS COMPLETED.
4. INSTALL 0.020" THICK ALUMINUM, STUCCO EMBOSSED JACKET AROUND ALL
EXTERIOR ROUTED REFRIGERANT PIPING.
5. ALL NEW CONTROL WIRING TO BE CONCEALED WITHIN WALLS OR INSTALLED
IN THE ABOVE CEILING SPACE.
6. CONTRACTOR TO COORDINATE ROUTING OF NEW DX PIPING AND
CONDENSATE PIPING WITH NEW IT RACKS, DATA CABLING TRAYS,
ELECTRICAL GEAR, AND ALL ASSOCIATED ACCESSORIES.
GENERAL FIRE SUPPRESSION NOTES
1. MODIFY EXISTING FIRE PROTECTION AS NEEDED PER NFPA 13 FOR NEW ROOM LAYOUTS.
2. CONTRACTOR TO ENSURE STORAGE 1-211 IS AIR TIGHT FOR NEW DRY CHEMICAL FIRE
SUPPRESSION SYSTEM. CONTRACTOR TO PATCH ALL NEW/EXISTING PIPING/WIRING, AND ALL
OTHER PENETRATIONS AS REQUIRED TO MATCH WALL RATING AND SEAL AIR TIGHT.
DISCONNECT, REMOVE, AND DEMO, EXISTING FIRE PROTECTION SPRINKLER
HEAD(S), ALARMS, AND ALL ASSOCIATED ACCESSORIES AS REQUIRED TO
INSTALL NEW DRY CHEMICAL SUPPRESSION SYSTEM AS SHOWN ON NEW
DRAWINGS. CONTRACTOR TO DEMOLISH EXISTING SPRINKLER PIPING TO
OUTSIDE THE SPACE AND CAP. CONTRACTOR TO ENSURE FIRE
SUPPRESSION SYSTEM MODIFICATIONS ARE COMPLIANT WITH NFPA 13.
DISCONNECT, REMOVE, AND SALVAGE EXISTING FIRE SUPPRESSION
CONTROL PANEL AND ALL ASSOCIATED ACCESSORIES. CONTRACTOR TO
RELOCATE EXISTING CONTROL PANEL TO NEW LOCATION SHOWN ON NEW
DRAWINGS.
FIRE PROTECTION KEY NOTES
DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING FIN TUBE, PIPING, VALVES, FITTINGS,
AND ALL ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN. CONTRACTOR TO
DISCONNECT, REMOVE, AND DEMO EXISTING HEATING SUPPLY PIPING AND
HEATING RETURN PIPING TO EXTENTS SHOWN AND SOLDER TOGETHER TO
ENSURE THE OPERATION OF EXISTING MONOFLOW FIN TUBE. EXISTING HEATING
SUPPLY PIPING AND HEATING RETURN PIPING IS LOCATED WITHIN THE EXISTING
FIN TUBE ENCLOSURE. CONTRACTOR TO MODIFY EXISTING FIN TUBE ENCLOSURE,
HEATING SUPPLY PIPING, AND HEATING RETURN PIPING AS REQUIRED TO
COMPLETE THEIR WORK. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING
WALL AS REQUIRED TO MATCH EXISTING.
EXISTING UNIT HEATER TO REMAIN. CONTRACTOR TO
REMOVE/SALVAGE/REINSTALL EXISTING HEATING SUPPLY PIPING, HEATING
RETURN PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES AS
REQUIRED TO INSTALL NEW BLOCK WALL SHOWN ON ARCHITECTURAL DRAWINGS.
CONTRACTOR TO MODIFY PIPING, INSTALL NEW SLEEVES AND PATCH NEW WALL
AS REQUIRED TO MAINTAIN FIRE RATING AND SEAL AIR TIGHT. CONTRACTOR TO
COORDINATE WITH ALL TRADES TO MODIFY EXISTING PIPING AS REQUIRED
INSTALL NEW BLOCK WALL.
EXISTING FIN TUBE, PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED
ACCESSORIES TO REMAIN IN THEIR ENTIRETY.
GENERAL DEMOLITION NOTES
1. EXISTING MECHANICAL EQUIPMENT AND ALL ASSOCIATED ACCESSORIES TO
REMAIN UNLESS OTHERWISE NOTED.
2. MODIFY EXISTING WALLS/CEILINGS AS REQUIRED TO COMPLETE DEMO/NEW
WORK.
X-CU-1 (ON ROOF)
X-CD
X-ECARO-25
TANK
X-3/4"
X-24x24 OA
UP TO
INTAKE
HOOD
X-RELIEF AIR UP
TO X-RELIEF HOOD
X-UH-2
X-EF-11
X-12x12 OA
UP X-IH
X-36x20 RA
X-40x20 RA X-36x36 UP TO INTAKE HOOD X-20x20
DN
X-FD
X-
DX
X-
DX
X-
DX
X-
DX
X-CD
PUMP
X-36x20 RA
X-AC-1
X-HS/HR
X-FT
X-3/4" HS AND HR
CU-2 (ON ROOF)
AC-2
DX DX
PIPE SUPPORTS
(TYP.)
DX DX
DX DX
CD
NOVEC 1230
CONTROL PANEL
NOVEC 1230
TANK
1X-FIRE
SUPPRESSION
CONTROL
PANEL
SD-1 ---
12x12 ---
12x12
AC-3
CU-3 (ON ROOF)
CD
3/4"
CD PUMP
DX (TYP.4)
3/4"
CO
CO
CO
CD PUMP
3/4"
3/4"
CD
CO
CO
DX
DX
M-400
ADMINISTRATION BUILDING
- MECHANICAL
DEMOLITION/NEW
TAT
CAT
SCALE: 1/32" = 1'-0"
0 51 10 25
N ADMINISTRATION BUILDING KEY PLAN
1 ADMINISTRATION BUILDING - ENLARGED FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
2 ADMINISTRATION BUILDING - ENLARGED FLOOR PLAN - MECHANICAL NEW
SCALE: 1/4" = 1'-0"
file no.
checked by drawn by consultant issue date index no.
contract order no.
consultant job no.
sheet title
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
L A
TC
H
, R A
, N C
A R
B , D
IR
EC
TO
R
FA
C
IL
IT
IE
S
A N
D B
U
SI
N
ES
S
SE
R V
IC
ES
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
C om m te ch
D es ig n
B
EL
D
IN
G R
O
AD
N E.
, S U
IT
E
B R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
472ElectronicComm
1065_43
Y17084
472/25278.RWG
10/19/26 ISSUE FOR BID
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERRUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST./EX.
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERRUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
GENERAL ELECTRICAL NOTES
ALL WORK SHALL BE IN COMPLIANCE WITH THE 2023 MICHIGAN
ELECTRICAL CODE AND MDOC STANDARDS.
1. ALL NON-FIRE RATED WALLS ARE TO BE PATCHED WITH LIKE
MATERIAL TO MAINTAIN ORIGINAL RATING.
2. ALL WALL AND FLOOR PENETRATIONS THROUGH FIRE RATED WALLS
ARE TO BE SEALED WITH FIRE CAULK TO MAINTAIN ORIGINAL
RATING. EXISTING PENETRATIONS IN THE AREA OF WORK THAT ARE
NOT PROPERLY SEALED ARE TO BE SEALED TO MATCH THE RATING
OF THE WALL.
3. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING
AND STRUCTURAL STEEL. CONDUITS SHALL BE INSTALLED
STRAIGHT, LEVEL, AND PARALLEL OR PERPENDICULAR TO THE
BUILDING LINES.
4. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID
WALK THROUGH TO DETERMINE THE EXACT EXTENT OF THE WORK
REQUIRED BEFORE BIDDING THE PROJECT.
5. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE, AND
EQUIPMENT NOT TO BE RE-USED WHERE WORK IS BEING DONE
EXCEPT ITEMS NOTED OTHERWISE.
6. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF
OLD WORK, SURFACES SHALL BE PATCHED AND PAINTED TO MATCH
ADJACENT.
7. EXISTING WORK, WHICH IS PRESENTLY CONCEALED, WHICH WILL
REMAIN CONCEALED, AND DOES NOT INTERFERE WITH ANY NEW
WORK OF ANY TRADE NEED NOT BE REMOVED. HOWEVER, ALL
CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND THEN
PATCHED AND PAINTED TO MATCH, OR AS NOTED.
8. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE
MODIFIED OR ENLARGED TO SUIT THE NEW SYSTEMS AS REQUIRED.
PROVIDE ALL REQUIRED CUTTING AND PATCHING.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING
WALLS TO MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE
MOUNTED EQUIPMENT.
10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS
PRIOR TO INSTALLING SERVICE TO EQUIPMENT.
11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENTS AND
CASUAL FIELD OBSERVATION. REPORT ANY DISCREPANCIES TO
ENGINEER FOR CLARIFICATION.
12. CONDUITS AND BOXES:
12.1. 3/4" MINIMUM TRADE SIZE.
12.2. EMT TYPE CONDUIT IS APPROVED WITH COMPRESSION
FITTINGS.
12.3. NO PVC ALLOWED INSIDE OF BUILDINGS.
12.4. CONDUITS SHALL BE ATTACHED WITH TWO-HOLE STRAPS.
SINGLE HOLE STRAPS ARE NOT PERMITTED.
12.5. NO SET SCREWS ARE ALLOWED.
12.6. TAMPER-PROOF SCREWS REQUIRED FOR EXPOSED CONDUIT
AND BOXES MOUNTED BELOW TEN FEET.
12.7. DRIVE PIN ANCHORS USED ON MASONARY OR CONCRETE
WALLS/CEILINGS.
13. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. ALL FLEXIBLE CONDUIT
RACEWAYS SHALL BE LIQUID TITE, MAXIMUM 72" LENGTH AND MUST
BE APPROVED BY PSC AND MDOC PROJECT MANAGER. REFER TO
SPECIFICATION 260533 - RACEWAY AND BOXES FOR ELECTRICAL
SYSTEMS.
14. INSTALLATION OF ANY NEW OR REWORKED CONDUIT, FITTINGS, AND
STRAPS SHALL FOLLOW CURRENT NEC AND MDOC STANDARDS.
15. CONDUIT, CONDUIT INSTALLATION, AND BOXES BEING REUSED
SHALL BE BROUGHT UP TO CURRENT MDOC STANDARDS.
16. ALL CONDUIT AND BOXES ABOVE 10 FOOT OR IN
MECHANICAL/ELECTRICAL ROOMS, SHALL MEET THE FOLLOWING
REQUIREMENTS:
16.1. STRAP DISTANCE: 5 FEET.
16.2. FASTENERS: 2 HOLE.
16.3. CONDUIT” INTERIOR EMT, EXTERIOR EXPOSED/CONCEALED-
GRC.
16.4. FITTINGS: COMPRESSION.
16.5. BOXES: STANDARD BOXES FOR ENVIORNMENT INSTALLED TO
MEET N.E.C.
16.6. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND
ENCLOSURES.
17. ALL CONDUIT AND BOXES 10 FOOT AND BELOW SHALL MEET THE
FOLLOWING REQUIREMENTS:
17.1. STRAP DISTANCE: 3 FEET.
17.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
17.3. SECURITY HARDWARE:
17.3.1. TORX T-25 WITH CENTER REJECTION PIN.
17.3.2. HEX HEAD CONCRETE SCREWS WITH NO SCREWDRIVER
SLOT.
17.3.3. EXPANSION POUND-IN ANCHORSWITH NO SCREWDRIVER
SLOT THAT DO NOT REQUIRE TO BE EXPLOSIVELY DRIVEN.
17.3.4. PRE-APPROVED HARDWARE.
17.4. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED -
GRC.
17.5. FITTINGS: COMPRESSION
17.6. BOXES:
17.6.1. SURFACE MOUNTED:
17.6.1.1. BELL BOX: FS TYPE, WITH SQUARE HEAD KO SEAL.
17.6.1.2. NO KNOCKOUTS - DRILL AS REQUIRED.
17.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND
ENCLOSURES.
18. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE
WIRING ABOVE ACCESIBLE CEILINGS IS ACCEPTABLE.
18.1. ALL EXPOSED WIRING ABOVE CEILINGS SHALL BE INSTALLED
WITH J-HOOKS. DO NOT CONNECT TO EXISTING CEILING TIE
WIRES.
19. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE
CUT INTO WALL.
20. ALL LOCATIONS WHERE THE WALLS CAN NOT BE FISHED SHALL BE
SURFACE MOUNTED CONDUIT FOLLOWING NOTES 14 THROUGH 15
ABOVE.
21. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE
RNC/HDPE SCHEDULE 80. ALL EXTERIOR ABOVE GROUND CONDUIT
SHALL BE RGC UP TO 10 FEET ABOVE GRADE. PROVIDE UL LISTED
#12 COPPER TRACER WIRE TO ALL UNDERGROUND CONDUITS
INSTALLED FOR LOW VOLTAGE.
22. ALL ELECTRICAL OUTAGES SHALL…
This is the start of the file's text. The full file is on GovTribe.