This document is an Exhibit B Tenant Space Configuration specification for the Illinois Department of Innovation and Technology (CMS) on behalf of the Department of Children and Family Services (DCFS) for a proposed office facility lease in Jacksonville, Morgan County, Illinois (Project Reference L6941). The RFI seeks 11,385 square feet of general office space to accommodate 44 employees across seven business units: Child Protection, Permanency, Licensing, Quality Assurance, Administrative Services, Clinical & Education, and Intact. The space configuration details specific requirements for 3,624 square feet of personnel space (including one medium office, seven standard offices, and 36 medium cubicles), 2,667 square feet of common office space (conference rooms, break room, reception area, and storage), 3,197 square feet of specialty spaces (file room, wiring closet, copy/mail room, wellness room, visitation and interview rooms, child placement area, restrooms, and guard desk), and 1,898 square feet of circulation, support, and flex space for mechanical, electrical, plumbing, and data infrastructure. The facility must be above-grade, preferably contiguous, with a minimum of six contiguous or proximate paved parking spaces including one ADA-accessible space.

The specification document establishes comprehensive performance and spatial guidelines incorporating Illinois Building Program Standards as the baseline for tenant improvements and construction quality. Data infrastructure requirements mandate Category 5e or Category 6 cabling in compliance with IEEE standards and Department of Innovation and Technology (DoIT) specifications, with minimum 2 data runs to each station and dedicated secure closets for network hardware. Specialty requirements include 50 foot-candle minimum lighting in office and public areas (20 foot-candle in storage and mechanical spaces), comprehensive electrical outlet provisions for each space type, ADA accessibility compliance throughout, HVAC zoning in the large conference room, soundproofing in visitation and observation rooms with one-way reflective glass, and a Hirsch keyless/access control system for secure areas including the child placement area and file room. The State reserves sole discretion to evaluate responses and determine whether proposed properties meet the guidelines, with exceptions requiring State approval. The specification was prepared by Space Planner D. Hernandez on October 28, 2025, and updated February 25, 2026.

View the file

Other files

File Type Posted
ipg-active-registered-disclosure-for-leasing-vendors-v.25.1~5.docx DOCX document
RFI Template Response~2.xlsx XLSX spreadsheet
Disclosure for Leasing Vendors v.27.1.docx DOCX document
Lease Document Template V2.2026.08.docx DOCX document
5 L6941 RFI Document DCFS Jacksonville~1.docx DOCX document
3 L6941 Exhibit A - DCFS Jacksonville.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Agency: DCFS

Location: Jacksonville

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

L6941

Date: 10/28/2025

Space Planner: D. Hernandez

The following descriptions of programmed spaces define the initial minimum standards to fulfill the Using Agency's needs. The requested interior space categories includes the following:

1. Personnel Space - Business Units

1.a. CHILD PROTECTION

1.b. PERMANENCY

1.c. LICENSING

1.d. QUALITY ASSURANCE

1.e. ADMINISTRATIVE SERVICES

1.f. CLINICAL & EDUCATION

1.g. INTACT

2. Common Office Space

3. Specialty Space Requests

4. Circulation/Support/Flex Space

5. Summary

All responses shall incorporate the standard defined below. Unless otherwise specifically noted herein, the [State and the] Using Agency prefers all occupiable tenant space be located within a contiguous space and above grade level, however [the State] the Using Agency may, in its sole discretion, may consider multiple floors or non-contiguous space(s) included in an offer if it is determined that the offer meets the client agency’s operational needs. Additionally, Building Program Standards (refer to link below) are defined to include exterior needs and provide a standard for performance and quality of materials required. All work defined and reasonably implied by programmatic information herein shall be incorporated into proposals for the initial tenant build-out.

Building Program Standards:

https://cms.illinois.gov/content/dam/soi/en/web/cms/agency/property/leasing/documents/buildingprogramstandards-after7-21.pdf In the event a response is submitted for consideration of property where these Tenant Space Configurations may be reasonably met without complete demolition and re-construction of the space, but may require some interior upgrades and alterations, the Tenant Space Configurations shall represent performance and spatial guidelines. Evaluation of such response will require a review of the site and concurrence by the state on the extent to which the property reasonably meets the performance and spatial guidelines or will meet the guidelines based upon proposed improvements detailed in the response. Unless specific exceptions to the performance and spatial guidelines are acceptable to the state as may be offered, this Tenant Space Configuration document will serve as the definitive improvement exhibit to the lease without regard to the scope of work required to deliver the space in accordance with all standards and requests noted herein. Determinations of meeting the performance and spatial guidelines set forth herein shall be made solely at the state's discretion to favor the interest of the state.

All responses shall also provide a minimum of 6 parking spaces, contiguous with the building or a parking structure or surface lot(s) in close proximity to the proposed property, including 1 ADA-accessible spaces on an accessible route to the main building entrance. Except for reasonable accomodation, parking provided is for Using Agency clients and state-owned vehicles only.

The parking lot(s) designated for the proposed building must be completely paved by asphaltic cement, concrete or approved equal, and shall be lighted and striped. Paving is to be done in a manner that will provide efficient drainage. Lighting shall provide at least minimum illumination of the parking area, building access routes and entrances.

Exhibit B Template - Revised 2/7/2022 Page 1 of 14 https://cms.illinois.gov/content/dam/soi/en/web/cms/agency/property/leasing/documents/buildingprogramstandards-after7-21.pdf

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Data wiring and racks shall be installed in accordance with the Department of Innovation and Technology (DoIT) requirements. Rack placement shall confirm to TIA-569 standard. Rack clearances shall be 7" minimum from walls at sides, rear clearance shall be minimum of 24" from walls (36" clearance preferred), front clearance shall be 36" minimum (48" clearance preferred). All data wiring is to be of Category 5e, Category 6 or better cabling and installed within IEEE and manufacturer specifications. Minimum 2 data wiring runs from wiring closets to each station jack. All connections are to be terminated in numerical sequence starting with "1". No gaps in numbering shall be allowed. For each wiring closet, all jacks shall be numbered consecutively with no breaks in numbering and labeled on. There shall never be more than one connection terminated in a wiring closet with the same number. Enough service loop shall be available to move panels anywhere within a rack. Data port locations shall be provided throughout selected leased space for wireless access point equipment provided by the Illinois Department of Innovation and Technology (DoIT). DoIT shall conduct a wifi study and provide locations once site is selected.

Due to data security regulations (i.e., HIPAA Section 164.310, PCI-DSS 9.1, etc.) requiring facility access controls and limiting physical access to network hardware, only authorized personnel shall have access to DoIT network closets. These closets shall be used for information technology purposes only. Sharing these spaces with outside entities or storage of customer items in these areas is prohibited.

Exhibit B Template - Revised 2/7/2022 Page 2 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Total Personnel Space

Total BU Square Feet

# Type of Space SF - Each SF - Total Divider Electrical Outlets Voice/Data Outlets Other

1 Medium Office 150 150 Enclosed Walls 4 duplex wall outlets 2 wall outlets Keyed Lockset

3 Standard Office 120 360 Enclosed Walls 4 duplex wall outlets 2 wall outlets Keyed Lockset

14 Medium Cubicle 48 672 60" High Panels 2 floor/partition/wall outlets 1 floor/partition/wall outlet

1 Open Space 394 394 Open Area Per local building code and using agency requirements

Per using agency requirements. Refer to the "Other" column

Data for any additional eqipment

(ie. Printers/scanners/phones)

Total BU Square Feet

# Type of Space SF - Each SF - Total Divider Electrical Outlets Voice/Data Outlets Other

2 Standard Office 120 240 Enclosed Walls 4 duplex wall outlets 2 wall outlets Keyed Lockset

11 Medium Cubicle 48 528 60" High Panels 2 floor/partition/wall outlets

1 floor/partition/wall outlet

1 Open Space 256 256 Open Area Per local building code and using agency requirements

Per using agency requirements. Refer to the "Other" column

Data for any additional eqipment

(ie. Printers/scanners/phones)

1.a. CHILD PROTECTION

1.b. PERMANENCY

1. Personnel Space - Business Units

Exhibit B Template - Revised 2/7/2022 Page 3 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Total BU Square Feet

# Type of Space SF - Each SF - Total Divider Electrical Outlets Voice/Data Outlets Other

1 Standard Office 120 120 Enclosed Walls 4 duplex wall outlets 2 wall outlets Keyed Lockset

5 Medium Cubicle 48 240 60" High Panels 2 floor/partition/wall outlets 1 floor/partition/wall outlet

1 Open Space 120 120 Open Area Per using agency and local code

Requirements

Per using agency requirements. Refer to the

"Other" column

Data for any additional eqipment

(ie. Printers/scanners/phones)

Total BU Square Feet

# Type of Space SF - Each SF - Total Divider Electrical Outlets Voice/Data Outlets Other

2 Medium Cubicle 48 96 60" High Panels 2 floor/partition/wall outlets 1 floor/partition/wall outlet

1 Open Space 32 32 Open Area Per local building code and using agency requirements

Per using agency requirements. Refer to the

"Other" column

Data for any additional eqipment

(ie. Printers/scanners/phones)

1.c. LICENSING

1.d. QUALITY ASSURANCE

Exhibit B Template - Revised 2/7/2022 Page 4 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Total BU Square Feet

# Type of Space SF - Each SF - Total Divider Electrical Outlets Voice/Data Outlets Other

1 Medium Cubicle 48 48 60" High Panels 2 floor/partition/wall outlets 1 floor/partition/wall outlet

1 Open Space 16 16 Open Area Per local building code and using agency requirements

Per using agency requirements. Refer to the

"Other" column

Data for any additional eqipment

(ie. Printers/scanners/phones)

Total BU Square Feet

# Type of Space SF - Each SF - Total Divider Electrical Outlets Voice/Data Outlets Other

2 Medium Cubicle 48 96 60" High Panels 2 floor/partition/wall outlets 1 floor/partition/wall outlet

1 Open Space 32 32 Open Area Per local building code and using agency requirements

Per using agency requirements. Refer to the

"Other" column

Data for any additional eqipment

(ie. Printers/scanners/phones)

1.e. ADMINISTRATIVE SERVICES

1.f. CLINICAL & EDUCATION

Exhibit B Template - Revised 2/7/2022 Page 5 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Total BU Square Feet

# Type of Space SF - Each SF - Total Divider Electrical Outlets Voice/Data Outlets Other

1 Standard Office 120 120 Enclosed Walls 4 duplex wall outlets 2 wall outlets Keyed Lockset

1 Medium Cubicle 48 48 60" High Panels 2 floor/partition/wall outlets

1 floor/partition/wall outlet

1 Open Space 56 56 Open Area

Per local building code and using agency requirements

Per using agency requirements. Refer to the "Other" column

Data for any additional eqipment

(ie. Printers/scanners/phones)

1.g. INTACT

Exhibit B Template - Revised 2/7/2022 Page 6 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Total Common

Space

# Type of Space SF - Each SF - Total Divider Lighting Electrical Outlets Voice/Data Outlets Other

1 Small Conference 165 165 Enclosed Walls 50 foot-candle minimum 4 duplex wall outlets 4 wall outlets

On Video Conference wall, Data/Electrical wall outlet at

60" and Data/Electrical wall outlet at 18" AFF.

1 Large Conference 750 750 Enclosed Walls 50 foot-candle minimum 8 duplex wall outlets 4 wall outlets

On Video Conference wall, Data/Electrical wall outlet at 60" and Data/Electrical wall outlet at

18" AFF. Physical support for agency provided projector as required. Lighting controls to provide dimming for presentations. Separate zoned thermostats to control temperature and humidity;

painted wood chair rail at 32" to top with washable wall covering below; privacy locksets.

1 Medium Break Room 250 250 Kitchenette 50 foot-candle minimum

2 duplex GFCI outlets above counter and 6 duplex wall outlets including dedicated wall outlet for refrigerator.

N/A

Include 10 LF of cabinets and counters with a stainless steel double compartment sink w/ hot & cold water; minimum clearance opening below sink of 30" width, 29" height & 19" depth for access by wheelchair users); Resilient floor finish;

gypsum wallboard ceiling; flush mounted ceiling fixtures.

2. Common Office Space

Exhibit B Template - Revised 2/7/2022 Page 7 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

1 Medium Reception 160 160 Open Area 50 foot-candle minimum 4 duplex wall outlets 4 wall outlets

Must be located at building entrance in non-secure area.

Public Restrooms, visitation/observation rooms and interview rooms must be visible from reception desk. Provide data and power outlet adjacent to entry for guard desk that will serve as client check-in station. Employee entrance must have adequate

24hr/7days per week lighting to accommodate operation of child care workers.

1 Medium Storage Room 250 250 Enclosed Walls 20 foot-candle minimum 4 duplex wall outlets

One (1) wall outlet located within five (5) feet and on same wall as entry door

Keyed Lockset

1 Large Storage Room 425 425 Enclosed Walls 20 foot-candle minimum 4 duplex wall outlets

One (1) wall outlet located within five (5) feet and on same wall as entry door

Keyed Lockset

1 Open Space 667 667 Per local building code and using agency requirements

Per using agency requirements. Refer to the "Other" column

Data for any additional eqipment

(ie. Printers/scanners/phones)

Exhibit B Template - Revised 2/7/2022 Page 8 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Total Specialty Space

Type of

Space SF - Each SF - Total Divider Lighting Electrical Outlets Voice/Data Outlets Other

1 File Room 300 300 Enclosed Walls 50 foot-candle minimum

Per local building code and using agency requirements

N/A Hirsch Access Control

Wiring Closet

(IDF)

100 100 Enclosed Walls

20 foot-candle minimum

4 - Dedicated 20A circuits with NEMA 5-

20r receptacles; 1 -dedicated 30A circuit with NEMA L5-30r locking receptacle for closets supporting more than 96 user devices.

2 - standard duplex outlets.

Minimum 1 per floor. Minimum

12 strands Single Mode or

Multimode Fiber between closets. Min. 8 ft ceiling ht. Hirsch keyless entry system.

Closet temperature will be maintained according to ASHRAE defined class A3 (41 to 100

Fahrenheit at 20% to 80% relative humidity).

Copy / Mail

Room 80 160 Enclosed Walls

50 foot-candle minimum

Per local building code and using agency requirements

4 wall outlets

Sufficient grounded electrical outlets

(30amp and 20amp outlets) to supply tenant equipment needs. Verify equipment list with Tenant

Staff

Wellness

Room

150 150 Enclosed Walls 50 foot-candle minimum

3. Specialty Space Requests

Exhibit B Template - Revised 2/7/2022 Page 9 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Visitation

Room 125 250 Enclosed Walls

50 foot-candle minimum

2 floor/partition/wall outlets 1 floor/partition/wall outlet

Located in close proximity to Public

(non-secured) Waiting Area, accessable to the Public Restrooms and within line of sight of Reception window. Rooms to be soundproof with Half-Glazed interior doors andresilent floor finish. Doors to be keyed on the exterior and panic device on the interior.

Observation

Room 80 80 Enclosed Walls

50 foot-candle minimum

2 floor/partition/wall outlets 1 floor/partition/wall outlet

Located between Visitation Rooms with private door (no glazing) and viewing window into each Visitation room. Window to be 36" wide x 48" high, ECLIPSE Reflective One-Way

Glass or equal. Install a 16"x24" plastic laminated shelve beneath window. Provide Intercom system to transmit and receive voice communication. Room to be soundproof with keyed lockset.

Interview

Room 100 200 Enclosed Walls

50 foot-candle minimum 4 duplex wall outlets 2 wall outlets

Child

Placement

Area

600 600 Enclosed Walls 50 foot-candle minimum

Per using agency requirements 1 floor/partition/wall outlet needs to be 3 rooms that are 80 square feet each with an open area that is approximately 150 sq ft, laundry area approximately 90 sq ft with washer/dryer hookups that match appliances on DCFS contract, and restroom with sink, toilet, and shower room that is approximately

120 sq ft with bathroom fixtures;

passage doors in bedrooms, bedroom doors need windows on top half of door, Hirsch controlled entry into Child Placement area, lock on bathroom door

Exhibit B Template - Revised 2/7/2022 Page 10 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

1 Janitor Closet 50 50 Enclosed Walls 20 foot-candle minimum

Per using agency and local code

Requirements

N/A Minimum 1 per floor. Mop sink and shelving/storage for janitorial supplies

Drinking

Fountains N/A

Provide at least two (2) electric water coolers/bottle fillers (one public, one employee) as required by the Illinois

Plumbing Code complying with standards of the Illinois Accessibility

Code and the ADA. Provide adjacent finishes similar to toilet room finishes

Men's

Employee

Restroom

(Small)

136 136 Enclosed Walls 20 foot-candle minimum

Minimum (2) duplex wall outlets including

(1) GFI outlet.

N/A

Accommodate 16-35 employees.

Minimum (1) water closet, (1) urinal

& (2) lavatories; comply with ADA accesibility regulations; privacy door hardware; all necessary toilet room accessories (e.g. soap dispensers, mirrors, waste receptacles, mounted electric hand dryer, etc.). Per Local

Building Code, minimum one per floor

Women's

Employee

Restroom

(Small)

136 136 Enclosed Walls 20 foot-candle minimum

Minimum (2) duplex wall outlets including

(1) GFI outlet.

N/A

Accommodate 16-35 employees.

Minimum (2) water closets, & (2) lavatories; comply with ADA accesibility regulations; privacy door hardware; all necessary toilet room accessories (e.g. soap dispensers, mirrors, waste receptacles, mounted electric hand dryer, etc.). Per Local

Building Code, minimum one per floor

Exhibit B Template - Revised 2/7/2022 Page 11 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Men's Public

Restroom 100 100 Enclosed Walls

50 foot-candle minimum

Minimum (2) duplex wall outlets including

(1) GFI outlet.

N/A

Minimum (1) water closet, (1) urinal

& (2) lavatories; comply with ADA accesibility regulations; privacy door hardware; all necessary toilet room accessories (e.g. soap dispensers, mirrors, waste receptacles, mounted electric hand dryer, etc.); provide (1) baby changing station and (1) child protection seat in stall to be fully retractable when not in use; signage indicating availability of unit at each location on access door or wall adjacent to access door.

Women's

Public

Restroom

100 100 Enclosed Walls 50 foot-candle minimum

Minimum (2) duplex wall outlets including

(1) GFI outlet.

N/A

Minimum (2) water closets, & (2) lavatories; comply with ADA accesibility regulations; privacy door hardware; all necessary toilet room accessories (e.g. soap dispensers, mirrors, waste receptacles, mounted electric hand dryer, etc.); provide (1) baby changing station and (1) child protection seat in stall to be fully retractable when not in use; signage indicating availability of unit at each location on access door or wall adjacent to access door.

1 Guard Desk 48 48 Open Area 50 foot-candle minimum 2 duplex wall outlets 1 floor/partition/wall outlet Short wall cubicle

1 Open Space 787 787 Open Area Per local building code and using agency requirements

Per using agency requirements.

Refer to the "Other" column

Data for any additional eqipment (ie.

Printers/scanners/phones)

Exhibit B Template - Revised 2/7/2022 Page 12 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Total Flex Space

# Type of Space SF - Each SF - Total Electrical Outlets Voice/Data Outlets Other

Circulation/Support/

Flex Space 1898 1898

Per local building code and using agency requirements

Per using agency requirements.

Refer to the "Other" column

Space for Mechanical/Electrical/

Plumbing, Data closets, circulation and flexibility in layout

4. Circulation/Support/Flex Space

Exhibit B Template - Revised 2/7/2022 Page 13 of 14

STATE OF ILLINOIS

EXHIBIT B - TENANT SPACE CONFIGURATION

DRAFT - L6941

Date: 10/28/2025

Space Planner: D. Hernandez

Square Footage Totals:

Personnel Space 3,624

Common Space 2,667

Specialty Space 3,197

Flex Space 1,898

Total SF 11,385

Headcount Totals:

Medium Office 1

Standard Office 7

Medium Cubicle 36

Total Headcount 44

Percentage Offices: 18%

5. SUMMARY