4 Generator 14RESA.pdf
PDF 225 KB Posted
- Attached to
- Hume Lake SCADA Installation
- Solicitation number
- 127EAW24R0051
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a product specification for a Kohler 14RESA multi-fuel emergency generator set. It provides detailed information on the generator's features, ratings, alternator, engine, fuel system, controller, sound levels, dimensions, and available options.
The key details include: the generator set is rated for 12 kW standby power and can run on natural gas or LPG; it has a Kohler Command PRO engine, a digital RDC2 controller, and a corrosion-proof polymer enclosure; it is certified to EPA emissions regulations and available in 50 Hz and 60 Hz models with various voltage configurations; it comes with a 5-year/2000 hour warranty for standby use; and a number of additional options are available such as automatic transfer switches, load management, and maintenance kits. This generator set appears to be targeted for residential, commercial, and light industrial standby power applications.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Models: 14RESA Multi-Fuel
LPG/Natural Gas
Standard Features D RDC2 Controller d One digital controller manages both the generator set and transfer switch functions (with optional Model RXT).
d Designed for today’s most sophisticated electronics.
d Electronic speed control responds quickly to varying demand.
d Digital voltage regulation protects your sensitive electronics from harmonic distortion and unstable power quality.
D Kohler Command PRO Engine Features d Kohler Command PROr OHV engine with hydraulic valve lifters for reliable performance without routine valve adjustment or lengthy break-in requirements.
d Powerful, reliable air-cooled performance.
d Simple field conversion between natural gas and LPG fuels while maintaining emission certification.
D Designed for Easy Installation d Polymer base eliminates the need for a concrete mounting pad, reducing installation time and cost.
d Fuel and electrical connections through the enclosure wall eliminate the need for stub-ups through the bottom.
d Load connection terminal block allows easy field wiring.
d Designed for outdoor installation only.
D Certifications d Meets emission regulations for U.S. Environmental Protection Agency (EPA) with both natural gas and LPG.
Note: CARB does not regulate emergency standby generators with outputs less than 50 HP.
d UL 2200/cUL listed (60 Hz model).
d CSA certification available (60 Hz model).
d GOST certified (Russia).
d Accepted by the Massachusetts Board of Registration of Plumbers and Gas Fitters
D Warranty d 5-year /2000 hour limited warranty for on-grid (standby) applications in locations served by a reliable utility source.
d 18 month/1000 hour limited warranty for off-grid (non-standby) applications.
The Kohlerr Advantage D High Quality Power Kohler home generators provide advanced voltage and frequency regulation along with ultra-low levels of harmonic distortion for excellent generator power quality to protect your valuable electronics.
D Extraordinary Reliability Kohler is known for extraordinary reliability and performance and backs that up with a premium 5-year or 2000 hour limited warranty.
D Powerful Performance Exclusive Powerboostt technology provides excellent starting power. The Kohler 14 kW generator can easily start and run a 5 ton air conditioner.*
D Corrosion-Proof Enclosure The bold new Kohler design is completely corrosion proof, even in harsh seaside environments, and is impact-resistant even at --34_ C (--30_ F).
D Fast Response Kohler generators restore power to your home quickly and reliably.
* Check the appliance manufacturer’s specifications for actual power requirements. Consult a Kohlerr Power Systems professional to calculate your exact residential power system requirements.
G4-245 (14RESA) 10/15a
Generator Ratings Standby Ratings Line Circuit
BreakerNatural Gas LPG Alternator Voltage Phase Hz kW/kVA Amps kW/kVA Amps Amps Poles
2F5
120 * 1 60 12/12 100 13/13 108 125 1 110/220 1 60 12/12 54 14/14 63 100 2 120/240 * 1 60 12/12 50 14/14 58 70 2 115/230 1 50 10/10 43 11/11 47 70 2
220[ 1 50 10/10 45 11/11 50 50 1 230 1 50 10/10 43 11/11 47 50 1
240[ 1 50 10/10 41 11/11 45 50 1
2G5
120/208 * 3 60 12/15 41 13/16 45 50 3 120/240 * 3 60 12/15 36 13/16 39 50 3 220/380 3 60 12/15 22 13/16 24 32 4 277/480 3 60 12/15 18 13/16 20 25 3
220/380] 3 50 10/12 18 11/13 20 25 4 230/400 3 50 10/12 18 11/13 19 25 4 240/416] 3 50 10/12 17 11/13 19 25 4
* UL listed.
[ 50 Hz single-phase models are factory-connected as 230 volts. Field-adjustable to 220 or 240 volts by an authorized service technician.
] 50 Hz 3-phase models are factory-connected as 230/400 volts. Field-adjustable to 220/380 or 240/416 volts by an authorized service technician.
Note: The line circuit breaker is automatically selected based on the generator set model and voltage configuration.
RATINGS: Standby ratings apply to installations served by a reliable utility source. All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. The standby rating is applicable to variable loadswith an average load factor of 80% for the duration of the power outage. No overload capacity is specified at this rating. Ratings are in accordancewith ISO--3046/1, BS5514, AS2789, and DIN 6271. GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 4% per 305 m (1000 ft.) elevation above 153 m (500 ft.). TEMPERATURE: Derate 2% per 5.5_C (10_F) temperature increase above16_C (60_F). Availability is subject to changewithoutnotice. Thegenerator setmanufacturer reserves the right to change thedesign or specificationswithoutnotice and without any obligation or liability whatsoever. Contact your local Kohler Co. generator distributor for availability.
Alternator Specifications Alternator Specifications Specifications Alternator
Manufacturer Kohler
Type 2-Pole, Rotating Field
Leads, quantity
2F5 4
2G5 12
Voltage regulator Digital
Insulation: NEMA MG1-1.66
Material Class H
Temperature rise 130_C Standby
Bearing: quantity, type 1, Sealed
Coupling Direct
Amortisseur windings Full
Voltage regulation, no-load to full-load
RMS ±1.0%
One-step load acceptance 100% of Rating
Peak motor starting kVA: (35% dip for voltages below)
240V, 1 ph 2F5 (4 lead) 33 (60 Hz)
230 V, 1 ph 2F5 (4 lead) 26 (50 Hz)
240 or 480 V, 3 ph 2G5 (12 lead) 54 (60 Hz)
208 V or 416 V, 3 ph 2G5 (12 lead) 38 (50 Hz)
Alternator Features
D Compliance with NEMA, IEEE, and ANSI standards for temperature rise.
D Self-ventilated and dripproof construction.
D Windings are vacuum-impregnated with epoxy varnish for dependability and long life.
D Superior voltage waveform and minimum harmonic distortion from skewed alternator construction.
D Digital voltage regulator with 1.0% no-load to full-load RMS regulation.
D Rotating-field alternator with static exciter for excellent load response.
D Total harmonic distortion (THD) from no load to full load with a linear load is less than 5%.
Application Data Engine Engine Specifications Manufacturer Kohler
Engine: model, type CH740 4-Cycle
Cylinder arrangement V-2
Displacement, cm3 (cu. in.) 725 (44)
Bore and stroke, mm (in.) 83 x 67 (3.27 x 2.64)
Compression ratio 9:1
Main bearings: quantity, type 2, Parent Material
Rated RPM
60 Hz 3600
50 Hz 3000
Max. engine power at rated rpm, kW (HP)
LPG, 60 Hz 17.6 (23.6)
LPG, 50 Hz 15.8 (21.2)
Natural gas, 60 Hz 15.3 (20.5)
Natural gas, 50 Hz 13.8 (18.5)
Cylinder head material Aluminum
Valve material Steel/Stelliter
Piston type and material Aluminum Alloy
Crankshaft material Heat Treated, Ductile Iron
Governor: type Electronic
Frequency regulation, no load to full load Isochronous
Frequency regulation, steady state 0.5%
Air cleaner type Dry
Engine Electrical Engine Electrical System Ignition system Electronic, Capacitive Discharge
Starter motor rated voltage (DC) 12
Battery (purchased separately):
Ground Negative
Volts (DC) 12
Battery quantity 1
Recommended cold cranking amps:
(CCA) rating for --18_C (0_F) 500
Group size 51
Exhaust Exhaust System Exhaust temperature exiting the enclosure at rated kW, dry, _C (_F) 260 (500)
Lubrication Lubricating System Type Full Pressure
Oil capacity (with filter), L (qt.) 1.8 (1.9)
Oil filter: quantity, type 1, Cartridge
Oil cooler Integral
Fuel Pipe Size Minimum Gas Pipe Size Recommendation, in. NPT
Pipe Length, m (ft.)
Natural Gas 193,000 Btu/hr.
LPG
203,000 Btu/hr.
8 (25) 3/4 3/4
15 (50) 1 3/4
30 (100) 1 1
46 (150) 1 1/4 1
61 (200) 1 1/4 1
Fuel Requirements Fuel System
Fuel types Natural Gas or LPG Fuel supply inlet 1/2 NPT Fuel supply pressure, kPa (in. H2O):
Natural gas 1.2--2.7 (5-11)
LP 1.7--2.7 (7-11)
Fuel Composition Limits * Nat. Gas LPG Methane, % by volume (minimum) 90 min. — Ethane, % by volume (maximum) 4.0 max. — Propane, % by volume 1.0 max. 85 min.
Propene, % by volume (maximum) 0.1 max. 5.0 max.
C4 and higher, % by volume 0.3 max. 2.5 max.
Sulfur, ppm mass (maximum) 25 max.
Lower heating value, MJ/m3 (Btu/ft3), (minimum) 33.2 (890) 84.2 (2260)
* Contact your local distributor for suitability and rating derates based on fuel compositions outside these limits.
Operation Requirements Fuel Consumption
Model Fuel Type % Load
Fuel Consumption, m3/hr. (cfh) 60 Hz 50 Hz
14RESA
Natural Gas
100 5.4 (193) 4.9 (175) 75 4.7 (163) 4.2 (148) 50 3.5 (124) 3.1 (108) 25 2.6 (93) 2.4 (84)
Exercise 1.7 (60) 1.7 (60)
LPG
100 2.3 (81) 2.1 (74) 75 2.1 (75) 1.9 (68) 50 1.8 (60) 1.5 (53) 25 1.2 (45) 1.1 (40)
Exercise 0.8 (30) 0.8 (30)
Nominal fuel rating: Natural gas: 37 MJ/m3 (1000 Btu/ft.3) LPG: 93 MJ/m3 (2500 Btu/ft.3)
LPG conversion factors: 8.58 ft.3 = 1 lb.
0.535 m3 = 1 kg
36.39 ft.3 = 1 gal.
RDC2 Controller
Voltage: 240 V Freq: 60.0 Hz
The RDC2 controller provides integrated control for the generator set, Kohlerr Model RXT transfer switch, programmable interface module (PIM), and load shed kit.
The RDC2 controller’s 2-line LCD screen displays status messages and system settings that are clear and easy to read, even in direct sunlight or low light.
RDC2 Controller Features D Membrane keypad:
d OFF, AUTO, and RUN pushbuttons d Select and arrow buttons for access to system configuration and adjustment menus
D LED indicators for OFF, AUTO, and RUN modes D LED indicators for utility power and generator set source availability and ATS position (Model RXT transfer switch required)
D LCD display:
d Two lines x 16 characters per line d Backlit display with adjustable contrast for excellent visibility in all lighting conditions
D Scrolling system status display:
d Generator set status d Voltage and frequency d Engine temperature d Oil pressure d Battery voltage d Engine runtime hours
D Date and time displays D Smart engine cooldown senses engine temperature D Digital isochronous governor to maintain steady-state speed at all loads
D Digital voltage regulation:±1.0% RMS no-load to full-load D Automatic start with programmed cranking cycle D Programmable exerciser can be set to start automatically on any future day and time, and run every week or every two weeks
D Exercise modes:
d Unloaded weekly exercise with complete system diagnostics d Unloaded full-speed exercise d Loaded full-speed exercise (Model RXT ATS required)
D Front-access mini USB connector for SiteTecht or USB Utility connection
D Integral Ethernet connector for Kohlerr OnCuer Plus D Built-in 2.5 amp battery charger D Remote two-wire start/stop capability for optional connection of a Model RDT transfer switch
Additional RDC2 Controller Features D Diagnostic messages:
d Displays diagnostic messages for the engine, generator, Model RXT transfer switch, programmable interface module (PIM), and load management device.
d Over 70 diagnostic messages can be displayed D Maintenance reminders D System settings:
d System voltage, frequency, and phase d Voltage adjustment d Measurement system, English or metric
D ATS status (Model RXT ATS required):
d Source availability d ATS position (normal/utility or emergency/generator) d Source voltage and frequency
D ATS control (Model RXT ATS required):
d Source voltage and frequency settings d Engine start time delay d Transfer time delays d Voltage calibration d Fixed pickup and dropout settings
D Programmable Interface Module (PIM) status displays:
d Input status (active/inactive) d Output status (active/inactive)
D Load control menus:
d Load status d Test function
Generator Set Sound Data Model 14RESA 8 point logarithmic average sound levels are 63 dB(A) during weekly engine exercise and 67 dB(A) during full-speed generator diagnostics and normal operation. For comparison to competitor ratings, the lowest sound levels are 58 dB(A) and 63 dB(A) respectively.*
All sound levels are measured at 7 meters with no load.
* Lowest of 8 points measured around the generator. Sound levels at other points around generator may vary depending on installation parameters.
2015 by Kohler Co. All rights reserved.
DISTRIBUTED BY:
Generator Set Dimensions and Weights Overall Size, L x W x H: 1216 x 665 x 733 mm
(48 x 26.2 x 29 in.)
Shipping Weight: 191 kg (420 lb.)
NOTE: Dimensions are provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information.
H
L
W
G4-245 (14RESA) 10/15a
Generator Set Standard Features D Battery cables D EPA certified fuel system D Corrosion-proof polymer sound enclosure D Critical silencer D Field-connection terminal block D Fuel solenoid valve and secondary regulator D Line circuit breaker D Multi-fuel system, LPG/natural gas, field-convertible D Oil drain extension with shutoff valve D Premium 5-year/2000 hour limited warranty for on-grid (standby) applications
D 18-month/1000 hour limited warranty for non-standby (off-grid) applications
D RDC2 generator set/ATS controller D Rodent-resistant construction D Sound-deadening, flame-retardant foam per UL 94, class HF-1
Available Options Approvals and Listings
- CSA approval
Communication Accessories
- OnCuer Plus Generator Management System
- OnCuer Plus Wireless Generator Management System
Concrete Mounting Pads
- Concrete mounting pad, 3 in. thick
- Concrete mounting pad, 4 in. thick
(recommended for storm-prone areas)
Electrical System
- Battery
- Battery heater, 120VAC
- Battery heater, 240VAC
- Emergency stop kit
- PowerSyncr Automatic Paralleling Module (APM)
(single phase only; parallels two 14RESA generators)
- Programmable interface module (PIM)
(provides 2 digital inputs and 6 relay outputs)
Available Options, Continued Fuel System
- Flexible fuel line
Literature
- General maintenance literature kit
- Overhaul literature kit
- Production literature kit
Maintenance
- Maintenance kit (includes air filter, oil, oil filter, and spark plugs)
Starting Aids
- Carburetor heater, 120 VAC
- Carburetor heater, 240 VAC
Carburetor heater is recommended for reliable starting at temperatures below 0_C (32_F )
Automatic Transfer Switches and Accessories
- Model RDT ATS
- Model RXT ATS
- Model RXT ATS with combined interface/ load management board
- Load shed kit for RXT or RDT
- Power relay modules (use up to 4 relay modules for each load management device)
- Other Kohlerr ATS
KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
File details come from the government source that posted it. Updated .