4-Drawings.pdf
PDF 5 MB Posted
- Attached to
- Ellis Building Interior Renovation
- Solicitation number
- RFP-653
- Issued by
- Monroe County, Florida
About this file
This document is a comprehensive set of architectural and engineering drawings and specifications for the Ellis Building Interior Renovation project located at the Plantation Key Government Center campus in Monroe County, Florida. The project, designed by William P. Horn Architect, P.A., with MEP engineering by FAE Consulting, Inc., encompasses interior renovations to the second floor including revised room layouts, new wall construction, suspended ceiling and lighting systems, new flooring installation, ADA-compliant breakrooms, a new lobby counter, interior doors, and associated electrical, plumbing, and mechanical work. The scope requires the contractor to furnish all labor and materials necessary to provide a complete, habitable, weatherproof, safe, and secure finished building suitable for human occupancy in accordance with Florida Building Code 2023, applicable coastal zone protection requirements, and local ordinances. The contractor is required to field verify all existing conditions prior to bidding and coordinate with the architect and engineer regarding any discrepancies between the documents and actual site conditions. The project documents emphasize that no changes shall be made without prior approval from the engineer of record and note that the permit set date is 03/16/26, with the documents marked as "NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED."
The specifications include detailed requirements across all construction divisions, with particular emphasis on compliance with coastal salt water environment standards, including salt-resistant materials for exterior and non-air-conditioned areas. Key specifications address lead paint safety protocols for pre-1978 buildings, asbestos testing requirements, termite control soil treatment, waterproofing and vapor barrier installation, fire-rated construction sealing, and mold prevention measures. Paint specifications require Benjamin Moore or equal products with specific VOC content limits compliant with Green Seal and SCAQMD standards, with interior wood finishing using 100% Acrylic Fast Sand Primer and Regal Select semi-gloss finish. The HVAC system includes two air handling units (AHU/CU-1 and AHU/CU-2) providing 180 and 270 CFM respectively, with calculated outdoor air requirements of 450 CFM total. Mechanical, electrical, and plumbing contractors must coordinate all work to avoid conflicts, with the contractor bearing full responsibility for reviewing complete drawing sets across all disciplines and ensuring all subcontractors include comprehensive scope. The documents are digitally signed by licensed professionals including William P. Horn, RA, LEED AP; Ursula Iafrate, P.E.; Derek A. Evans, P.E.; and Stephen F. Rollin, P.E., with FAE Consulting's contact information provided at 300 Lock Road, Suite 302, Deerfield Beach, FL 33442.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-Notice to Publish-Ellis Bldg Interior Renovation.docx | DOCX document | |
| 1-RFP - Ellis Building Renovation FINAL.pdf | ||
| 3-Addendum 1 Ellis Bldg Reno.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELLIS BUILDING RENOVATION
ARCHITECT:
WILLIAM P. HORN ARCHITECT, P.A.
WILLIAM P. HORN, RA, LEED AP
OWNER:
MONROE COUNTY
MEP ENGINEERING:
FAE CONSULTING, INC.
Digitally signed by William Horn Date:
2026.07.09 12:01:19-04'00'
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 7'-11"
CLG: 8'-1"
CLG: 7'-11"
CLG: 8'-0"
CLGHT.: 8'-0"
CLGHT.: 8'-0"
CLGHT.: 8'-0"
William Horn Date:
12:01:35-04'00'
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 7'-11"
CLG: 8'-1"
CLG: 7'-11"
CLG: 8'-0"
CLGHT.: 8'-0"
CLGHT.: 8'-0"
William Horn Date:
12:01:47-04'00'
TAG: IMAGE: SPECIFICATION: PROVIDED
BY:NOTES: INSTALLED
BY:
DISTRIBUTOR /
VENDOR INFO:WEBSITE:
TAG: IMAGE: SPECIFICATION: PROVIDED
BY:NOTES: INSTALLED
BY:
DISTRIBUTOR /
VENDOR INFO:WEBSITE:
TAG: IMAGE: SPECIFICATION: PROVIDED
BY:NOTES: INSTALLED
BY:
DISTRIBUTOR /
VENDOR
INFORMATION:
WEBSITE:
Digitally signed by William Horn Date:
12:02:00-04'00'
01800 - GENERAL REQUIREMENTS
Project Description The Contractor shall furnish all labor and materials required and necessary to provide a complete habitable, weatherproof, safe and secure finish building, suitable for human occupancy in accordance with Specifications, Drawing and Project Documents.
The Florida Building Code 2023 Edition, as amended by Governing Local Ordinances and requirements of the State of Florida "Coastal Zone Protection Act", together with applicable requirements of governing public agencies and the following listed codes shall apply to this project.
Florida Existing Building Code, 2023 Edition Florida Building Code-Accessibility, 2023 Edition Florida Building Code-Energy Conservation, 2023 Edition National Electrical Code Latest Edition Florida Plumbing Code, 2023 Edition Florida Mechanical Code, 2023 Edition FEMA- Coordinate all building items required to be above flood elevation for project and other FEMA regulations that apply to the project.
Lead paint safety requirements: The contractor is required to use lead safe work practices for buildings built before 1978. All lead paint shall be removed or covered as per EPA and other code requirements. Contractor to coordinate with owner for investigative methods, removal solutions and costs.
Asbestos Testing in Existing Buildings: Prior to demolishing items and or buildings in an existing building the contractor shall coordinate with the owner and obtain any asbestos reports required by Code.
Contractor shall visit the site to become familiar with existing conditions and requirements of construction prior to bidding.
Contractor shall complete new work in conformance with these drawings. Notify Architect if conflicts appear or are uncovered during the progress of the work prior to any field modifications or construction. Deviations from permitted drawings without Architects prior written approval shall be at the Contractors responsibility. Contractor is to verify all dimensions of project prior to proceeding with construction. Notify architect of any conflicts or problems so solutions can be achieved prior to construction. In event of conflict between drawings and specifications the most stringent requirements shall apply. Verification shall include, but not limited to, coordination of site work, existing conditions, buildings and utilities. Notify architect of any conflicts so solution can be worked out prior to construction.
Contractor shall provide all subcontractors complete set of drawings, including drawings from other disciplines. Change orders will not be allowed because a subcontractor only looked at drawings for his discipline and not other disciplines. Contractor must review all drawings and notify Architect of any conflicts. If a conflict arises assume worst case scenario for bidding and or Construction (or notify Architect for clarification prior to bidding). General Contractor is responsible for reviewing the complete set of drawings and specifications and assuring that his and his subcontractors bids include complete work and systems (free of conflict with other contractors and subcontractors).
Contractor and subcontractor shall follow industry standards for each discipline. Drawings do not show every condition, fastener, etc. . If something is not detailed, follow industry standards. Provide complete functioning systems.
Contractor shall coordinate all final floor finishes and thicknesses and adjust floor levels as required to maintain desired or required level changes (if any). This shall be done prior to building the floor. Coordinate with Architect and Owner as required.
Contractor needs to coordinate final color selections with owner and architect prior to ordering items. Factory finished items such as roofing, windows and doors need color and finish selections verified in writing by owner and architect prior to ordering.
Allowance items, if any shall be listed in writing by the Owner/Architect prior to bidding.
General Notes:
A. Engineer's approval must be secured for all structural substitutions.
B. Verify all openings through floors, roof and walls with mechanical and electrical contractors. Verification of locations, sizes, lintel and required connections are contractor's complete responsibility.
C. The MEP plans and drawings are diagrammatic of the work to be performed and may not show every item and/or detail.
Some components may be shown outside the work area for clarity. The work shall be executed in a manner to avoid conflicts with other trades and other elements of construction. All deviations from the plans shall be approved by the owner and/or owner's representative before being installed. The contractor shall not willfully install any aspect of the mechanical, electrical, or plumbing systems as shown on the plans and drawings when it is obvious in the field that obstructions or discrepancies exist that might not have been known during the design of the systems. in the event that notification of the conflict is not approved by the owner's representative, the contractor will assume full responsibility for all revisions.
D. Prior to installation of mechanical and electrical equipment or other items to be attached to the structure, engineer's approval of connections and supports shall be obtained. Unless specifically detailed on architectural and structural drawings, respective sub-contractor shall furnish all hangers, connections, etc., required for installation of his items.
E. Provide all embedded items in structure as noted on architectural, mechanical, electrical as well as structural drawings.
Miscellaneous embedded items and anchor bolts shall be furnished by steel supplier and installed by concrete contractor.
F. Contractor to verify all dimensions before proceeding with any new work, including layout of the entire project on site for verification of setbacks, elevations and location of existing trees.
G. Provide temporary bracing and precautions necessary to withstand all construction and/or wind loads until all field connections are completed and shear walls and decks are in place. All shoring is the responsibility of the contractor including use of a specialty engineer if required.
H. Submit shop and erection drawings for all items required by the drawing or elsewhere in the specifications for written approval. The manufacture or fabrication of any items prior to written approval of shop drawings will be entirely at the risk of the contractor.
All references to standards to be of the latest issue applicable.
I. This project is in a coastal salt water environment. Contractor shall consider this in selections of materials used in the exterior and non-air conditioned areas. All materials shall be salt resistant.
J. Manufactured assemblies; such as roofing, soffits, panels, storefront, doors, windows and other external assemblies incorporated into the project shall require detailed shop drawing submittals. Miami Dade N.O.A'S or Florida product approvals providing tested assembly installation details and windload compliance are required. Manufacturers recommendations and requirements (including warranty requirements) shall be incorporated along with the latest industry standards and best practices. All final color selections or finishes shall be coordinated and verified with the owner and architect prior to ordering (typical).
K. Waterproofing, vapor barriers, waterstop, air seals,, etc. shall be as indicated in the Specifications and as per manufacturer and industry standards.
L. Contractor to provide all required fire blocking as required by Code.
M. Unless otherwise noted, provide framing @ 24” o.c. for roofing and 16” o.c. for walls and floors.
N. Contractor to take all precautions to prevent mold from growing in or on the building. Do not use materials that have mold on them for construction, close up building each night to keep water out, do not install A/C ducts until building is dried in and take all other possible efforts to prevent mold from growing.
O. All penetrations of fire rated construction shall be treated with dampers, seals, collars, etc., see section 09260 and 15100.
P. When working within occupied or partially occupied buildings it is the contractors responsibility to provide safe access and to maintain in operation all features of existing life safety systems including alarms, detectors, lighting and exit ways throughout the course of construction.
Q. If in the event of conflicting, or overlapping requirements in any area of the proposed documents, technical specifications, or drawings, the most stringent condition shall be proposed and constructed.
DIVISION 2 - SITE AND CIVIL WORK
02250 - Demolition shall include the removal of all items as indicated on the drawings, as well as incidental items necessary for new work to progress. All work shall be done in a workman like manner with minimal disturbance to existing to remain; see structural specifications for temporary shoring and bracing. All unwanted material to be removed from the site and properly disposed of. Unless noted otherwise, patch all areas to remain to match existing in areas damaged by demolition.
02361 - Termite Control: Provide soil treatment for termite control at slabs on grade including foundations and slab penetrations, if any. Formulate and apply termicides, and label with a federal registration number, to comply with EPA regulations and authorities having jurisdiction. Use only soil treatment solutions not harmful to plants. Apply at label volume and rate per EPA-registered label with application by a licensed pest control operator. Provide a soil treatment application report for owners record and use.
02855 - Underground Utilities - Contractor shall include in his work all underground (and above) utility work for all systems to make a complete system from buildings to street hook-ups as required to complete the job.
DIVISION 3 - CONCRETE (NOT USED)
DIVISION 4 - MASONRY (NOT USED)
09900 - Painting - This section includes surface preparation, painting, and finishing of exposed interior and exterior items and surfaces. Surface preparation, priming, and finish coats specified in this section are in addition to shop priming and surface treatment specified under other sections.
A. Paint exposed surfaces whether or not colors are designated in "schedules", except where a surface or material is specifically indicated not to be painted or is to remain natural. Where an item or surface is not specifically mentioned, paint the same as similar adjacent materials or surfaces. If color or finish is not designated, the architect will select from standard colors or finishes available.
1. Painting includes field painting exposed bare and covered pipes and ducts (including color coding), hangers, exposed steel and iron work, and primed metal surfaces of mechanical and electrical equipment.
2. Painting is not required on prefinished items, finished metal surfaces, concealed surfaces, operating parts, and labels.
3. Labels: do not paint over Underwriter's Laboratories, Factory Mutual or other code-required labels or equipment name, identification, performance rating, or nomenclature plates.
B. Submit Data: Manufacturer's technical information, label analysis, and application instructions for each material proposed for use.
1. List each material and cross-reference the specific coating and finish system and application.
Identify each material by the manufacturer's catalog number and general classification.
2. Samples for initial color selection in the form of manufacturer's color charts. The exterior will have four colors minimum, one being special order color. The interior will have three colors minimum, one being a special order color.
C. Provide samples of each color and materials to be applied, with texture to simulate actual conditions, or representative samples of actual substrate. Define each separate coat, including block fillers and primers. Use representative colors when preparing samples for review. Resubmit until required sheen, color, and texture are achieved.
1. Provide a list of material and application for each coat of each sample. Label each sample as to location and application.
D. Paints and coating used on the interior of the building (i.e., inside of the weather proofing system and applied on - site ) shall comply with the following criteria:
1. Architectural paints, coating and primers applied to interior walls and ceilings:
Do not exceed the VOC content limits established in the Green Seal Standard GS-11, Paints, First Edition, May 20, 1993. Primers must meet the VOC limit for non-flat paint.
Flats: 50 g/L Non-Flats: 100 g/L
2. Anti-corrosive and anti-rust paints applied to interior ferrous substrates: Do not exceed the VOC content limit of 250 g/L established in Green Seal Standard GS-03, Anti-corrosive Paints, Second Edition, January 7, 1997.
3. Clear wood finishes, floor coatings, stains, primers, and shellacs applied to interior elements must no exceed the VOC content limits established in South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004.
Provide paint as shown with all materials by Benjamin Moore or equal. Colors and finish shall be selected by owner:
Interior wood:
Primer:.............100% Acrylic Fast Sand Primer #507 VOC = 29.7 g/L. (1 Coat ) Finish:..............Regal Select semi- gloss finish #N551 VOC = 96 g/L (2 Coats )
Galvanized metal and Aluminum (Non Ferrous Metal) Clean surfaces with Super Spec HP oil and grease emulsifier (P83) to remove contaminants Primer:.............One coat Super Spec HP D.T.M. Acrylic Semi-Gloss #HP29 VOC = 148 g/L Finish:…………One coat Super Spec HP D.T.M. Acrylic Semi-Gloss #HP29 VOC = 148 g/L
Gypsum Board:
Primer:.............Fresh start 100 % Acrylic Superior Primer #046 VOC = 44 G/l.(1coat) Finish:..............2 coats Regal. Select Matte Finish #N548 or Flat #N547, VOC = 48g/L Ceilings……….Waterborne Ceiling Paint #508, VOC = 50 g/L (2 coats )
Structural Steel and Iron: (Ferrous Metal) Primer and Finish…2 Coats Super Spec HP D.T.M. Acrylic Semi-Gloss #HP29, VOC = 45 g/L
Natural-Finish Woodwork:
Primer………..Benwood stays clear Acrylic Polyurethane High Gloss #W422, VOC = 250 g/L (1 coat) Finish………... Benwood stays clear Acrylic Polyurethane High Gloss #W422, VOC = 250 g/L (2 coats)
09940 - Existing wood preparation: Contractor to remove and replace all rotted or damaged wood to match existing (use pressure treated wood). Splice in new boards as inconspicuously as possible and stagger joints as required. Scrape all loose paint of existing wood surfaces, sand smooth prior to prime coat paint. (see paint specification). After prime coat, caulk all seams, joints and holes as required prior to finish coats (see sealant specifications).
DIVISION 10 - SPECIALTIES
10522 - Fire extinguishers: Provide fire extinguisher and cabinet or wall mounting bracket, as manufactured by Larsen's Manufacturing Co. or equal, for each location and mounting condition indicated on the drawings.
A. Cabinet to be semi-recessed, fabricated in one piece w/one piece combination trim and perimeter door frame overlapping surrounding wall surface. Shop drawing submittals are required for approval, prior to any fabrication or delivery of materials.
B. Extinguisher to be multipurpose dry chemical type: UL rated 4-A: 60-BC, 10-LB. nominal capacity, in enameled steel container.
C. To comply with ADA wall projection guidelines, the cabinet must be mounted with its bottom (leading edge) at or bellow 27” from the finished floor.
DIVISION 11 - EQUIPMENT
11400 - Contractor to coordinate with owner and or equipment supplier prior to bidding to determine in writing what will be supplied by owner, equipment supplier, or contractor, and to determine what will be coordinated or installed by contractor.
DIVISION 12, 13 & 14 - NOT USED
DIVISION 15 - MECHANICAL (SEE MECHANICAL DRAWINGS)
DIVISION 16 - ELECTRICAL (SEE ELECTRICAL DRAWINGS)
DIVISION 5 - METALS
05300 - Miscellaneous Metals: anchor bolts, nuts and washers shall be minimum 5/8 in. galvanized steel embedded minimum 7 in. into concrete and spaced maximum 2 feet o.c.
Provide miscellaneous galvanized steel anchors, straps and hangers as required.
05320 -Manufactured Anchors and Straps shall be heavy duty galvanized metal G90, as manufactured by Simpson Strong Tie or equal. Item numbers shall be as identified on the drawings. In no event shall pier, sill, joist, plate, rafter or truss connections be made without anchorage devises for hurricane protection, unless specifically noted and address by other means. All truss anchors shall be designed, specified and supplied by Truss Fabricator.
05400 - Light-Gage Metal framing:
A. Light-gage metal framing shall be galvanized according to ASTM A924 and of size and gage shown on the drawings. If not shown on drawings or specifications provide size and gage as per industry standards.
B. Framing rolled from steel shall conform to ASTM A653, grade 33, with a minimum yield stress of 33,000 PSI.
C. Metal framing to be installed per Aisi North American specifications and typical standards.
D. Non structural metal framing members to be installed per ASTM C645 standard specifications.
E. Provide “Sliptrack” on top track of walls under structure that has possibility of moving (typical).
F. Add Galvanized metal clips as required at 4' O.C. for any wall framing offset off of masonry wall, (typical).
G. Metal framing members to receive screw-attached gypsum panel products shall be installed and specified per
ASTM C745 standard specification.
H. Contractor shall provide complete framing systems as per drawings, specifications or industry standards (if not shown on drawings or specifications) I. If soffits, drop ceilings or other items are not detailed, provide as per industry standards.
DIVISION 6 - WOOD AND PLASTICS
06100 - Rough Carpentry all framing (and truss) lumber shall be dry southern pine, 19% MC, No. 2 or better, (Fb = 975 PSI Minimum). Member sizes noted on drawings are nominal.
Provide 1"x4" cross bridging not over 8 feet o.c. for all wood joist and 2 x solid blocking between joist at all supports. Provide 1x4 furring at 16"o.c. for all trusses that will have a finished ceiling below unless clearly written not to have furring in drawings.
06130 Pressure Treated: All wood indicated shall be pressured-treated with chemicals to protect from decay and insects. Dry after treatment. All metal connectors to be by Simpson Strong-Tie Company or equal approved in writing by the engineer and to be stainless steel finish, unless otherwise noted.
All connectors to be installed with all Manufacture specified fasteners before loading. All nails used in pressure treated shall be stainless steel. Alternate connector/fastener materials may be approved on submittal of manufacturers data indicating compatibility with specific pressure treatment chemicals used in this project.
Note: It is intended to limit the use of pressure treated wood to avoid need for specialized or stainless steel anchor devises and fasteners. However, pressure treated is to be used in all moist and or exposed locations such as sills on concrete, near grade installations, exposed decks and rails, exterior open stairs, etc. and as required by code. Coordinate any questionable areas with architect.
06300 - Finish Carpentry shall include trim, frames, paneling and cabinetry. Profiles and plastic laminate are to be as selected or noted on the drawings. Cabinets shall be of a custom or premium grades as noted or determined by the owner. Use of particle or press board shall be precluded. All cabinets to be formaldehyde free.
Select grade southern yellow pine shall be used as a quality standard for trim, frames and base unless noted otherwise. All work shall be by skilled finish carpenters.
A. Wood shelving where indicated shall be 3/4" plywood with edge banding, painted.
DIVISION 7 - THERMAL AND MOISTURE PROTECTION
07270- Air Barriers and Seals General Requirements. The thermal envelope of the building shall comply shall comply with FBC, 2017. A continuous air barrier shall be provided for the following components:
A. Shafts: Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed.
B. Narrow Cavities: Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity space.
C. Recessed Lighting: Recessed light fixtures installed in the building thermal envelope shall be air tight, IC rated, and sealed to the drywall.
D. Plumbing and wiring: Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring.
E. Electrical/ Phone Box on Exterior Walls: The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed.
F. HVAC Register Boots: HVAC register boots that penetrate building thermal envelope shall be sealed to the sub-floor or drywall.
DIVISION 8 - DOOR AND WINDOWS
08110 - Standard steel doors and frames:
A. Doors: seamless composite construction standard steel doors for interior and exterior locations (galvanized
G90). Doors to be provided in the types and styles indicated, and in accordance with ANSI/SDI-100, GRADE III, extra heavy duty, w/minimum 16 gauge galvanized steel faces. Comply with the applicable requirements of ANSI A115 Series specifications for door and frame, preparation for hardware.
B. Frames to be minimum 16 gage at interior locations and 14 gage at exterior locations, galvanized steel with mitered; welded construction, and concealed anchors to suite wall construction.
C. Doors and frames shall be factory primed for field painting.
D. Shop drawing submittal showing fabrication, installation, anchorage and Label Construction Certification of fire-rated assemblies, is required for approval prior to any fabrication or delivery of material.
08210 - Wood Doors shall be of sizes and types indicated with surfaces to accept paint finish unless noted otherwise. Exterior doors shall be solid core 1 3/4" thick exterior weatherproof type. Interior doors shall be 1 3/4" thick solid core implanted blanks type. Doors shall meet NWMA std. tolerance for their types.
08710 - Hardware: Furnish and install complete hardware for each condition as manufactured by Schlage; Yale or approved equal. ANSI grade 1 or better for heavy commercial use. Finish and style to be selected. All exterior installations to be salt resistant and suitable for use in a coastal salt water environment.
DIVISION 9 - FINISHES
09260 - Gypsum Drywall: provide gypsum drywall shown on drawing and as follows:
A. Steel furring channels: ASTM C 645, with flange edges bent back 90 deg. and doubled over to form 3/16 inch minimum lip, minimum thickness of base (uncoated) metal, galvanized finish-typical and minimum depth as follows; thickness is 0.0329 inch, depth is 1-5/8 inch.
B. Gypsum board: provide 5/8 inches thickness (unless otherwise indicated) to comply with ASTM C 840 and ASTM C 36. Use type X for fire-resistance-rated assembles. Provide tapered edges. Use water - resistant gypsum board ( ASTM C 630 ) where indicated and for all areas subject to moisture including all toilet and bathroom walls and ceilings, janitor room walls and ceilings and the wet wall of a kitchen. Provide galvanized metal trim accessories complying to ASTM C 1047. Provide tape and three coats spackle, screw gypsum board to metal framing.
C. At fire rated wall assemblies-required layers (type X) shall be installed continuous past any intersecting partitions. Sheet installation, layering, penetrations, treatment of recessed electrical boxes, and expandable fire caulk to decks above and below, etc. shall be in accordance with assembly guidelines.
D. Penetrations of fire rated wall and floor assemblies, by pipes or conducts, shall be sealed using products by 'Rector seal' or 'Hilti' or equal. At penetrations less than 2” nominal provide 'Biostop' or 'Firestop' caulking per manufacturer recommendation. At penetration larger than 2” nominal provide fire collars per manufactures recommendations. The angle of penetrations shall not exceed 45˚. Multiple lines shall not penetrate a single opening unless specially taped and sealed per manufacturers requirements. Fire seals assemblies shall be U.L. listed, or submitted by the manufacturer for specific site conditions as a “technical judgment” subject to review and approval.
William Horn Date:
12:02:13-04'00'
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"CLG: 8'-0"
CLG: 8'-0"
CLG: 8'-0"
CLG: 7'-11"
CLG: 8'-1"
CLG: 7'-11"
CLG: 8'-0"
CLGHT.: 8'-0"
CLGHT.: 8'-0"
William Horn Date:
12:02:26-04'00'
CLG: 8'-0"
0'-0"
8'-0"
K-T14415-3PURISTFAUCETSBRASS
BRASS
FAUCETSPURISTK-T14428-4
CLG: 8'-0"
8'-0"
William Horn Date:
12:02:39-04'00'
William Horn Date:
12:02:58-04'00'
William Horn Date:
12:03:10-04'00'
PRIOR TO SUBMITTING THE BID, THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND INFORM THE ARCHITECT AND THE ENGINEER OF ANY DISCREPANCY BETWEEN THESE DOCUMENTS AND THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
Stephen F. Rollin, P.E. License #36428
This item has been digitally signed and sealed on the date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
PLUMBING SHEET INDEXPLUMBING SPECIFICATIONS
MAXIMUM FLOW RATES AND CONSUMPTION
FOR PLUMBING FIXTURES AND FITTINGS
CONTRACTOR GENERAL CONDITIONS NOTES
SCOPE OF WORK
FLOOD ELEVATION
SCCR NOTE
FIRE-SAFETY FLORIDA STATUTES
ADA NOTE
DETAIL
NO. 2 CONDENSATE DRAIN TRAP
DETAIL
NO. 1 WALL CLEAN-OUT
PLUMBING FIXTURE UNIT CALCULATION
PLUMBING LEGEND
Digitally signed by Ursula P Iafrate Location: PE #73122 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
uiafrate@faeconsulting.com Date: 2026.07.09 11:21:40-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
NOT IN SCOPE
NOT IN SCOPE
208 207
EXISTING FIXTURES
TO REMAIN AS IS.
EXISTING FIXTURES
TO REMAIN AS IS.
PLUMBING KEY NOTES
Digitally signed by Ursula P Iafrate Location: PE #73122 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
uiafrate@faeconsulting.com
11:21:39-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
LIFE SAFETY NOTE
CONTRACTOR GENERAL CONDITIONS NOTES
HVAC GENERAL NOTES
SCOPE OF WORK
MECHANICAL SHEET INDEX
A
R
E
A
HVAC LEGEND
ADA NOTES
STRUCTURAL NOTES
FLORIDA BUILDING CODE 2023 CONFORMANCE
SCCR NOTE
Digitally signed by Ursula P Iafrate Location: PE #73122 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
uiafrate@faeconsulting.com
11:22:05-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
OUTDOOR AIR CALCULATIONS
AIR DEVICE SCHEDULE
OFFICE AIR BALANCE SCHEDULE
EXHAUST FAN SCHEDULE
SYSTEM SPACE NAME SPACE CATEGORY SPACE TYPE
AREA
(SQFT)
OCCUPANCY DENSITY
PER 1000 SQFT
OCCUPANCY
VENTILATION
RATE
CFM/PERSON
VENTILATION RATE
CFM/SQFT
MINIMUM OUTDOOR
AIR REQUIRED
(CFM)
OUTDOOR AIR
PROVIDED
(CFM)
TOTAL OUTDOOR AIR
PROVIDED
(CFM)
AHU/CU-1(E)
204 PROPERTY APPRAISE OFFICES OFFICE SPACES 147 5 1 5 0.06 14 15
205 SUPERVISOR OFFICE OFFICES OFFICE SPACES 108 5 1 5 0.06 12 15
206 OPEN WORKSPACE OFFICES OFFICE SPACES 703 5 4 5 0.06 63 65
207 STORAGE STORAGE UNOCCUPIABLE SPACE 40 - - - - - -
208 IT ROOM STORAGE UNOCCUPIABLE SPACE 40 - - - - - -
209 BREAK ROOM OFFICES RECEPTION AREAS 187 30 6 5 0.06 42 45
210 BREAK ROOM OFFICES RECEPTION AREAS 123 30 4 5 0.06 28 30
211 WOMEN PUBLIC SPACES TOILET ROOMS - PUBLIC (CONTINUOUS) 116 - - - - - -
CORRIDOR-1 PUBLIC SPACES CORRIDORS 113 - - - 0.06 7 10
AHU/CU-2(E)
201 LOBBY OFFICES MAIN ENTRY LOBBIES 312 10 4 5 0.06 39 40
202 CONFERENCE OFFICES CONFERENCE ROOMS 227 50 12 5 0.06 74 75
203 COPY WORKROOMS COPY, PRINTING ROOMS 99 4 1 5 0.06 11 15
212 MEN PUBLIC SPACES TOILET ROOMS - PUBLIC (CONTINUOUS) 101 - - - - - -
213 JAN. STORAGE UNOCCUPIABLE SPACE 22 - - - - - -
CONFERENCE OFFICES CONFERENCE ROOMS 150 50 8 5 0.06 49 50
COPY ROOM WORKROOMS COPY, PRINTING ROOMS 54 4 1 5 0.06 9 10
CORRIDOR-2 PUBLIC SPACES CORRIDORS 282 - - - 0.06 17 20
IN HOME SERVICE OFFICE OFFICES OFFICE SPACES 163 5 1 5 0.06 15 15
NON-DEDICATED OFFICE OFFICES OFFICE SPACES 106 5 1 5 0.06 12 15
OFFICE OFFICES OFFICE SPACES 90 5 1 5 0.06 11 15
TRANSPORTATION OFFICE OFFICES OFFICE SPACES 96 5 1 5 0.06 11 15
TOTALS 3,279 414 450 450
UNIT TAG MFGR & MODEL CFM RANGE FACE SIZE / MODULE NECK FRAME THROW
SA TITUS TMS-AA 0-85 10x10 / 12x12 4"∅ LAY-IN 2-4-7
SB TITUS TMS-AA 86-300 10x10 / 12x12 8"∅ LAY-IN 4-6-12
RA TITUS 350FL 0-540 10x10 / 12x12 SEE RETURN DUCT DETAILS LAY-IN -
TAG MANUFACTURER MODEL LOCATION CFM E.S.P. (IN W.C.) Voltage (V/PH/Hz) OPERATING POWER NOISE (SONES) DRIVE TYPE DUCT SIZE
EF-2 GREENHECK SP-A90 CEILING 70 0.3 115/1/60 15 W 0.5 DIRECT 6"∅
BUILDING AIR BALANCE
SYSTEM
OUTSIDE AIR FROM
UNIT (CFM)
EXHAUST AIR
(CFM)
RESULTING PRESSURE
AHU/CU-1(E) 180 - 180
AHU/CU-2(E) 270 - 270
EF-1(E) - -200 -200
EF-2 - -70 -70
TOTALS 450 -270 180
Digitally signed by Ursula P Iafrate Location: PE #73122 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
uiafrate@faeconsulting.com
11:22:04-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
A
R
A
R
A
R
A R
A R
A
R
A
R
A
R
NOT IN SCOPE
NOT IN SCOPE
NOT IN SCOPE
A
R
202 203
A
R
A
R
A
R
A
R
A
R
A R
A R
A
R
A
R
A
R
Digitally signed by Ursula P Iafrate Location: PE #73122 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
uiafrate@faeconsulting.com
11:22:03-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
METHODS OF HANGING
RIGID DUCT DETAIL
LOW PRESSURE DUCT VOLUME
DAMPER REQ. DETAIL
DETAIL
NO. 2
DUCTWORK CONNECTION TO RETURN/EXHAUST GRILL (FLEX DUCT) DETAILDETAIL
NO. 5
DUCTWORK CONNECTION TO SUPPLY DIFFUSER (FLEX DUCT) DETAILDETAIL
NO.3
DETAIL
NO. 1
CEILING MOUNTED FAN DETAILDETAIL
NO. 4
Digitally signed by Ursula P Iafrate Location: PE #73122 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
uiafrate@faeconsulting.com
11:22:03-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
Digitally signed by Ursula P Iafrate Location: PE #73122 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
uiafrate@faeconsulting.com
11:22:02-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
ELECTRICAL SYMBOL LEGEND GENERAL DEMOLITION NOTESGENERAL ELECTRICAL NOTES ELECTRICAL SHEET INDEX
COORDINATION NOTES
LIGHTING NOTES
SCOPE OF WORK
EQUIPMENT/FEEDER REMOVAL NOTES
FIRE RATING NOTE
AIR CONDITIONING EQUIPMENT AND CONTROLS SPECIFICATION
FLORIDA BUILDING CODE 2023 CONFORMANCE
VOLTAGE DROP NOTE
CONTRACTOR GENERAL CONDITIONS NOTES
SCCR AND POWER STUDY NOTE
SEALING NOTE
SPECIAL PURPOSE OUTLET NOTES
FBC NOTE
LOW VOLTAGE NOTES
CONTRACTOR BIDDING SUPPLEMENTAL NOTES:
WIFI
SP
CLEARANCE NOTE
UL LISTING AND NRTL CERTIFICATIONS NOTE
WIRING NOTES
CODE COMPLIANCE
CONTRACTOR CAUTION - POWER STUDY NOTE
Digitally signed by Stephen Rollin Location: PE #36428 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
srollin@faeconsulting.com
11:22:44-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
LIGHTING NOTES
LIGHTING CONTROLS - FBC 2023 NOTE
MANUAL LIGHTING CONTROLS - FBC 2023 NOTE
EMERGENCY LIGHTING NOTE
NOTE:
NFPA LIGHTING CONTROLS NOTE (TYPICAL FOR ENTIRE PROJECT)
LIGHTING CONTROL NOTES
ENERGY COMPLIANCE NOTE
LIGHTING CONTROL SYMBOL LEGEND
NOT TO
SCALE
DETAIL
NO. 2
NOT TO
SCALE
DETAIL
NO. 1
WALL SWITCH, 1 POLE, AUTO ON/OFF
OCCUPANCY SENSOR INTERFERENCE DETAIL
Digitally signed by Stephen Rollin Location: PE #36428 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
srollin@faeconsulting.com
11:22:43-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
NOT TO
SCALE
DETAIL
NO. 1
NOT TO
SCALE
DETAIL
NO. 3
NOT TO
SCALE
DETAIL
NO. 4
NOT TO
SCALE
DETAIL
NO. 2
ETS-20-DR EMERGENCY
SHUNT DETAIL
PP2O SINGLE CIRCUIT W/MULTIPLE
OCC SENSORS
CM SERIES, SPODMA D WITH ETS20 DR
BATTERY BACK UP - NO EM CIRCUIT)
CM SERIES, SPODMA D WITH ETS20 DR
Digitally signed by Stephen Rollin Location: PE #36428 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
srollin@faeconsulting.com
11:22:43-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
NOT IN SCOPE
212 211
E
E
E
E E E
E
E E
E
E
E E
E E E
EE
EE E
E
E
E E
E E
E
E
E
E
EEEE
E
(4) E
SEE ELECTRICAL NOTES & LEGEND
ON SHEET E0.1
POWER PLAN KEYNOTES
GENERAL NOTE
CONTRACTOR SHALL ENGAGE A
DELEGATED ENGINEER PE TO DESIGN ALL
FA AND INTERLOCKING SYSTEMS AND
RESPOND TO PERMIT COMMENTS
IT RACK CAUTION NOTE
CONTRACTOR TO PRESERVE EXISTING IT RACKS
IN PLACE. THESE CONNECTIONS MUST REMAIN
ACTIVE DURING DEMOLITION. CONTRACTOR
SHALL PROVIDE APPROPRIATE DUST AND
DEBRIS MITIGATION MEASURES TO PROTECT
ALL ACTIVE I.T. EQUIPMENT THROUGHOUT
CONSTRUCTION. COORDINATE WITH ARCHITECT
/ PROJECT MANAGER FOR ALL REQUIRED
PROTECTION MEASURES AND ANY POTENTIAL
SERVICE INTERRUPTIONS.
Digitally signed by Stephen Rollin Location: PE #36428 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
srollin@faeconsulting.com
11:22:42-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
NOT IN SCOPE
212 211
SEE LIGHTING NOTES & LEGEND ON
SHEET E0.2
LIGHTING PLAN KEYNOTES
PP
PP
PP
Digitally signed by Stephen Rollin Location: PE #36428 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
srollin@faeconsulting.com
11:22:41-04'00'
THE EXISTING CONDITIONS AND SHALL INCLUDE IN THE BID TO CORRECT THE SAME AS DIRECTED.
THE ENGINEER AND THE ARCHITECT, ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING
FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
NO CHANGES SHALL BE MADE TO THESE PLANS WITHOUT PRIOR APPROVAL FROM THE ENGINEER OF
RECORD. ALL CHANGES SHALL BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
NOT FOR BID UNTIL PERMIT HAS BEEN ISSUED.
PERMIT SET: 03/16/26
E-mail: info@faeconsulting.com
TEL: (561) 391-9292 FAX: (561) 391-9898
Certificate of authorization no. 28107
Ursula Iafrate, P.E. License #73122
Designed By: MAM/SV/AB PM: KS
C O N S U L T I N G 300 Lock Road, Suite #302 Deerfield Beach, FL 33442
P/N 24037
Derek A. Evans, P.E. License #93746FIRE SAFETY FLORIDA STATUTES: TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS
AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE
APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH F.B.C. 2023 SECTION 110.8.4.4 AND CHAPTER 633, FLORIDA STATUTES.
THE ELECTRICAL CONTRACTOR SHALL VERIFY THE LENGTH OF ALL
BRANCH CIRCUITS IN FIELD AND SHALL MAINTAIN LESS THAN 3% VOLTAGE
DROP FOR FEEDERS AND 2% VOLTAGE DROP FOR BRANCH CIRCUITS.
CONTRACTOR SHALL INCREASE WIRE SIZES AND CONDUIT AS REQUIRED
TO MEET NEC.
PANEL FEEDER NOTE
GCL2
PANEL SCHEDULE INDEX
N
NOT TO SCALEPROPOSED PARTIAL: POWER RISERRISER
NO. 1
CONDUCTOR SIZE KEY NOTESELECTRICAL SERVICE NOTE
LEGEND
EXISTING
PROVIDE ALL PANELS AND SYSTEMS AS FULLY RATED SELECTIVELY
COORDINATED EQUIPMENT.
TYPICAL FOR ENTIRE PROJECT SYSTEMS.
Digitally signed by Stephen Rollin Location: PE #36428 Reason: I agree to the terms defined by the placement of my signature on this document.
Contact Info:
srollin@faeconsulting.com
11:22:41-04'00'