4-Attachment A - Drawings 23X119.00 CEILING CLOUD 2024-11-13.pdf

PDF 1 MB Posted

Attached to
iRFB ENHANCED STRUCTURAL SUPPORT FOR INDOOR HANGING SIGN
Solicitation number
25-06291
Issued by
San Bernardino County, California

About this file

These are structural engineering drawings for the Inland Empire Health Plan (IEHP) Reception Desk & Hanging Cloud project located at 10801 Sixth St. in Rancho Cucamonga, California. The documents detail a construction project involving the installation of a curved cloud ceiling and supporting framing system within an existing building. The scope of work includes precise structural modifications, including attaching a 96-inch wide by 193-inch long curved cloud ceiling weighing approximately 1,100 pounds, utilizing existing steel trusses, roof deck, and structural elements. The drawings are prepared by IDS Group and are marked as a "Progress Set - Not for Construction", indicating they are preliminary design documents.

The structural design conforms to the 2022 California Building Code and includes detailed specifications for steel welding, installation techniques, and seismic considerations. The project involves complex mounting details using aircraft cables, threaded rods, and specialized attachments from manufacturers like B-Line. Structural requirements include specific load calculations (roof dead load of 15 PSF, live load of 20 PSF), seismic design category D, and risk occupancy category III. The drawings provide extensive technical guidance for contractors, including precise installation methods, material specifications, and safety requirements for modifying the existing structural system.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SCOPE OF WORK

1. REFER TO PROJECT SPECIFICATIONS FOR PROJECT REQUIREMENTS.

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF WORK AREA DURING CONSTRUCTION PERIOD. THE CONTRACTOR SHALL PROTECT ADJACENT PROPERTY AND UTILITIES IN ACCORDANCE WITH ALL NATIONAL, STATE, AND

LOCAL SAFETY ORDINANCES.

3. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED

SUBJECT TO PRIOR REVIEW BY THE SEOR.

4. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK, AND SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES. THE SUPPORTING SERVICES BY THE SEOR, WHETHER PERFORMED PRIOR TO, DURING, OR AFTER CONSTRUCTION, ARE PERFORMED SOLELY FOR THE PURPOSE OF ASSISTING IN QUALITY CONTROL AND IN ACHIEVING CONFORMANCE WITH CONTRACT DRAWINGS AND PROJECT SPECIFICATIONS; BUT THEY DO NOT GUARANTEE THE CONTRACTOR'S PERFORMANCE AND SHALL NOT BE CONSIDERED AS

SUPERVISION OF CONSTRUCTION.

5. SHOP DRAWINGS REQUIRED BY THE PROJECT SPECIFICATIONS SHALL BE SUBMITTED TO THE SEOR FOR REVIEW PRIOR TO FABRICATION. DRAWINGS ARE REVIEWED BY THE SEOR FOR GENERAL CONFORMANCE TO THE DESIGN. REGARDLESS OF THE SEOR'S REVIEW, THE CONTRACTOR IS FULLY AND SOLELY RESPONSIBLE FOR COMPLETE AND SATISFACTORY SUBMITTAL AND CONFORMANCE TO THE CONTRACT DOCUMENTS. SHOP DRAWINGS WILL BE REJECTED FOR INCOMPLETENESS, LACK OF CALCULATIONS (IF REQUIRED) OR CHANGES WITHOUT PRE-APPROVAL. ALL STRUCTURAL CALCULATIONS AND DRAWINGS AS PART OF THE SHOP DRAWINGS SUBMITTAL SHALL BE SIGNED AND STAMPED BY A

CALIFORNIA REGISTERED STRUCTURAL ENGINEER.

6. ANY PARTS OF WORK AREA WHICH ARE TO BE BARRICADED OR SEALED TO NON-CONSTRUCTION INDIVIDUALS MUST BE

COORDINATED WITH AND APPROVED BY THE OWNER BEFORE PROCEEDING WITH THE WORK.

7. THE CONTRACTOR SHALL EXERT EVERY EFFORT TO PREVENT DUST AND CONSTRUCTION DEBRIS FROM CONTAMINATING THE WORK AREA. THESE EFFORTS SHALL INCLUDE BUT NOT BE LIMITED TO PROVIDING A DAILY CLEANUP OF THE CONSTRUCTION AREA. THE CONTRACTOR SHALL REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

8. THE CONTRACTOR SHALL EXERT EVERY EFFORT TO MINIMIZE THE CONSTRUCTION NOISE AND DISTURBANCE DURING

CONSTRUCTION.

9. THE CONTRACTOR SHALL BE RESPONSIBLE TO SECURE THE CONSTRUCTION SITE.

10. CUTTING, BORING, SAW-CUTTING OR DRILLING THROUGH NEW STRUCTURAL MEMBERS OTHER THAN THOSE DETAILED ON

STRUCTURAL DRAWINGS SHALL NOT BE DONE WITHOUT THE SEOR'S APPROVAL.

11. THE CONTRACTOR SHALL:

A. CHECK ALL DIMENSIONS.

B. BE RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES.

ALL DISCREPANCIES SHALL BE CALLED TO THE ATTENTION OF THE SEOR AND SHALL BE RESOLVED BEFORE

PROCEEDING WITH THE WORK.

12. ALL MATERIALS, FEATURES OR CONDITIONS NOT IDENTIFIED AS (E) WHICH MEANS "EXISTING," SHALL BE CONSIDERED AS

NEW AND PART OF THE PROJECT SCOPE OF WORK.

13. THE CONTRACTOR IS FULLY AND SOLELY RESPONSIBLE FOR ALL SHORING REQUIRED IN ORDER TO SAFELY ACHIEVE THE FINAL CONSTRUCTION SHOWN ON THE DRAWINGS. THIS INCLUDES, BUT IS NOT LIMITED TO, ANY TYPES OF SHORING REQUIRED FOR SOILS EXCAVATION AND BACKFILL WORK; SUPPORT OF STRUCTURAL ELEMENTS UNTIL THEY HAVE ACHIEVED THE NECESSARY STRENGTH TO PERFORM IN THE FINAL POSITION AND MANNER SHOWN ON THE DRAWINGS; AND SUPPORT OF STRUCTURAL ELEMENTS THAT ARE MODIFIED AND THEREBY REDUCED IN STRENGTH IN ANY WAY DURING CONSTRUCTION AS REQUIRED TO ACHIEVE THE FINAL CONSTRUCTION AS SHOWN ON THE DRAWINGS. ALL SHORING CALCULATIONS AND DRAWINGS SHALL BE STAMPED BY A CALIFORNIA REGISTERED STRUCTURAL ENGINEER AND SUBMITTED

FOR REVIEW PRIOR TO PERFORMING THE WORK.

14. WHERE NOT INDICATED OTHERWISE, THE LATEST EDITION OF ALL CITED DOCUMENTS SHALL GOVERN.

15. THE TERM CBC IN THESE DRAWINGS MEANS 2022 CALIFORNIA BUILDING CODE, CALIFORNIA CODE OF REGULATIONS, TITLE 24, ALL PARTS AND VOLUMES.

16. ALL CONSTRUCTION AND WORKMANSHIP, INCLUDING MATERIALS, SHALL CONFORM TO THESE DRAWINGS, PROJECT

SPECIFICATIONS, AND THE CBC.

17. PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE AND ADJACENT STRUCTURE, AND THEIR FINISHES AND

UTILITIES, DURING CONSTRUCTION.

18. THE CONTRACTOR SHALL COORDINATE ALL UTILITY LOCATIONS WITH OTHER DRAWINGS AND SHALL CONDUCT A DETAILED SURVEY OF EXISTING UTILITIES TO IDENTIFY INTERFERENCES WITH THE NEW CONSTRUCTION. PROMPTLY NOTIFY THE

ARCHITECT OF ANY INTERFERENCES PRIOR TO PERFORMING THE WORK.

19. CORING, TRENCHING & EXCAVATIONS

PRIOR TO CORING, TRENCHING, AND EXCAVATIONS, THE CONTRACTOR IS RESPONSIBLE FOR AND IS REQUIRED TO USE AN INDEPENDENT UTILITY LOCATING SERVICE TO LOCATION ALL UTILITIES WITHIN THE IMPACTED AREA(S). THE INDEPENDENT UTILITY LOCATING SERVICE SHALL PROVIDE CERTIFICATION THAT IT HAS LOCATED ALL UTILITIES IN THE IMPACTED AREA(S) AND THE CONTRACTOR MUST DEPICT ALL DISCOVERED UTILITIES ACCURATELY ON REDLINES/AS-BUILT PLANS FOR SUBMISSION TO THE CITY FOR REVIEW AND APPROVAL PRIOR TO COMMENCEMENT OF CORING, TRENCHING, OR EXCAVATIONS. IN ADDITION, FOR UTILITIES REQUIRING EXTERNAL AGENCY NOTIFICATION, COORDINATION, AND APPROVALS, THE CONTRACTOR MUST PROVIDE PROOF OF NOTIFICATION, COORDINATION, AND REVIEWS BY EXTERNAL AGENCIES.

20. ALL SPECIAL/DEPUTY INSPECTION REPORTS AND TESTS SHALL INCLUDE: JOB NAME AND JOB NUMBER, SITE LOCATION, PLAN

PAGE AND DETAILS, ANY RFI , AND CODE REFERENCES.

GENERAL

DESIGN CRITERIA

DESIGN CONFORMS TO THE 2022 CALIFORNIA BUILDING CODE .

1. DEAD LOADS:

ROOF 15 PSF

FIRE SPRINKLER SYSTEM: 1.5 PSF (ASSUMED)

2. LIVE LOADS:

ROOF 20 PSF (REDUCIBLE)

3. SEISMIC ANALYSIS: EQUIVALENT LATERAL FORCE PROCEDURE

· SITE CLASS = D (DEFAULT)

· SEISMIC DESIGN CATEGORY = D

· RISK OCCUPANCY CATEGORY = III

· Ie = 1.0

· Ss = 1.66 g

· S1 = 0.60 g

· Fa = 1.2

· Fv = 1.7

· SDS = 1.107 g

· SD1 = 0.680 g

S-001 GENERAL NOTES

S-201 FRAMING PLAN AND SECTIONS

S-501 DETAILS

DRAWING INDEX

1. PERMITTED TOLERANCE SHALL BE ACCORDING TO THE CBC.

TOLERANCE

1. CONTRACTOR MUST FULLY MEASURE THE (E) STRUCTURE BEFORE FABRICATING/CUTTING ANY NEW STEEL OR WOOD

MEMBERS TO BE INSTALLED INTO THE STRUCTURE PER THESE DRAWINGS.

2. ALL NEW STEEL AND WOOD MEMBERS MUST BE FABRICATED/CUT TO THE ACTUAL AS-BUILT STRUCTURE DIMENSION IN ORDER TO ASSURE PROPER FIT-UP AND INSTALLATION AS SHOWN IN THE CONNECTION, SUPPORT AND OTHER DETAILS AS

SHOWN ON THE DRAWINGS.

3. MODIFICATION OF THE DESIGN OR DETAILS SHOWN ON THE DRAWINGS IN ORDER TO ACCOMMODATE IMPROPER FIT-UP DUE TO LACK OF AS-BUILT MEASUREMENTS AND/OR FABRICATION ERRORS WILL NOT BE ALLOWED AND WILL BE A BASIS FOR

REJECTION OF THE INSTALLATION.

4. CONDITIONS SHOWN OR NOTES AS EXISTING ARE BASED ON THE BEST INFORMATION AVAILABLE AT THE TIME OF THE PREPARATION OF THESE DRAWINGS. NO WARRANTY IS IMPLIED AS TO THE ACCURACY OF EXISTING CONDITIONS. THE CONTRACTOR SHALL REFER TO THE ORIGINAL CONSTRUCTION DOCUMENTS (IF ANY) FOR INFORMATION REGARDING EXISTING CONSTRUCTION AND SHALL FIELD VERIFY ALL CONDITIONS. IF CONDITIONS BECOME APPARENT WHICH DIFFER FROM THE CONDITIONS SHOWN HEREIN, THEY SHALL BE BROUGHT TO THE ATTENTIONS OF THE STRUCTURAL ENGINEER.

DIMENSIONS TAKE PRECEDENCE OVER SCALE OR DRAWINGS, HOWEVER, SIGNIFICANT CONFLICTS SHALL BE RESOLVED AS

NOTED.

AS-BUILT CONDITIONS

STRUCTURAL STEEL WELDING

1. THE CONTRACTOR SHALL SUBMIT ALL STRUCTURAL STEEL AND MISCELLANEOUS STEEL SHOP DRAWINGS TO THE ENGINEER

FOR REVIEW PRIOR TO FABRICATION.

2. MATERIAL TEST OR REPORTS FOR HOT-ROLLED STRUCTURAL SHAPES, PLATES, AND BARS SHALL BE MADE IN ACCORDANCE WITH ASTM A6. FOR SHEET MATERIAL, TEST SHALL BE MADE IN ACCORDANCE WITH ASTM A568. FOR TUBING AND PIPE, SUCH TEST SHALL BE MADE IN ACCORDANCE WITH REQUIREMENTS OF THE APPLICABLE ASTM STANDARDS.

3. STEEL MATERIALS SHALL CONFORM TO THE FOLLOWING, UNLESS OTHERWISE NOTED:

A. ANGLES, PLATES AND BARS: ASTM A36 (Fy=36ksi, Fu=58ksi) B. RECTANGULAR AND SQUARE HSS: ASTM A500, GRADE B (Fy=46ksi, Fu=65ksi) C. PIPES: ASTM A53, GRADE B (Fy=35ksi, Fu=60ksi) D. BOLTS AT STEEL-TO-STEEL CONNECTIONS: ASTM A325 ST (SNUG-TIGHTENED), TYPE 1; 7 8"Ø TYP. U.O.N.

E. BOLTS AT OTHER APPLICATIONS: ASTM A307

F. NUTS: ASTM A563

G. WASHERS: ASTM F436

H. THREADED ROD: ASTM F1554, GRADE 36 U.N.O.

5. HEAVY-HEX STRUCTURAL BOLT AND NUT DIMENSIONS SHALL MEET REQUIREMENTS OF ANSI/ASME B18.2.6. ALL BOLTS

SHALL HAVE A 3 THREAD ENGAGEMENT MINIMUM.

6. DIAMETER OF BOLT HOLE SHALL BE 116" LARGER THAN THE BOLT'S DIAMETER UNLESS OTHERWISE NOTED.

7. IF DRILLING HOLES AT STEEL MEMBERS TO ACCOMMODATE THE CONCRETE ANCHORS IS REQUIRED, THE DRILLING MUST BE DONE AFTER THE ANCHORS HAVE BEEN INSTALLED. THE HOLES AT STEEL MEMBERS SHALL MATCH THE LOCATION OF

INSTALLED ANCHORS.

8. PROVIDE BEVELED WASHERS ON SLOPING SURFACE OF CONNECTIONS FOR FULL BEARING.

9. MINIMUM BOLT SPACING FROM CENTER OF STANDARD AISC HOLE AS FOLLOWS, U.N.O.:

CENTER-TO-CENTER = 3 BOLT DIAMETER

CENTER-TO-EDGE = VARIES PER AISC 360-16 TABLE J3.4

10. THE NATURAL CAMBER IN BEAMS SHALL BE ORIENTED UP, UNLESS NOTED OTHERWISE. AT CANTILEVERS, THE NATURAL CAMBER SHALL BE ORIENTED SO THAT THE FREE END IS ABOVE THE CONNECTED END. THE TOP OF ALL MEMBERS SHALL BE CLEARLY IDENTIFIED. ALL BEAM CAMBERS SHOWN ON THE PLANS SHALL INCLUDE NATURAL CAMBER.

11. GALVANIZE ALL STEEL EXPOSED TO WEATHER, UNLESS OTHERWISE NOTED. REPAIR GALVANIZING AT FIELD WELDS WITH

CARBOLINE CARBOMASTIC 15 REPAIR PAINT (10 MILS), TYPICAL.

12. UNDER NO CIRCUMSTANCES SHALL DRAWINGS BE SCALED OR REFERENCE ELECTRONIC BUILDING INFORMATION BE USED

TO DETERMINE ELEVATIONS OR DIMENSIONS.

13. THE CONTRACTOR SHALL ESTABLISH A MASTER SET OF TOP-OF-STEEL DRAWINGS FOR ALL AREAS OF THE BUILDING OR STRUCTURE FOR APPROVAL BY THE ARCHITECT BEFORE BEGINNING FABRICATION OF STRUCTURAL STEEL. THE CONTRACTOR'S MASTER SET OF TOP-OF-STEEL DRAWINGS SHALL BE SUBMITTED AT THE BEGINNING OF THE SHOP DRAWING SUBMITTAL PROCESS. THIS SET OF DRAWINGS SHALL SHOW ALL TOP-OF-STEEL ELEVATIONS, ALL EDGE OF STEEL INFORMATION FOR FLOOR AND ROOF LEVELS, AND ALL STEEL FRAMING DIMENSIONS AT FLOOR AND WALL OPENINGS.

STRUCTURAL STEEL

1. ALL WELDING SHALL BE IN CONFORMANCE WITH THE AWS D1.1 AND AWS D1.8.

2. ALL WELDING MUST BE APPROVED BY AN AWS CERTIFIED INSPECTOR.

3. ALL WELDING OF STEEL SHALL CONFORM TO AWS D1.1 AND AWS D1.8 AND SHALL BE PERFORMED BY AWS CERTIFIED WELDERS USING E-70XX LOW HYDROGEN MOISTURE RESISTING ELECTRODES UNLESS OTHERWISE NOTED.

4. ALL WELDS USED IN MEMBERS AND CONNECTIONS IN THE SEISMIC LOAD RESISTING SYSTEM (SLRS) SHALL BE MADE WITH FILLER METALS MEETING THE REQUIREMENTS SPECIFIED IN AWS D1.8 CLAUSE 6.3. ALL WELDING ELECTRODES AND ELECTRODE-FLUX COMBINATIONS SHALL MEET DIFFUSIBLE HYDROGEN TESTING REQUIREMENTS OF TABLE 6.3 OF AWS D1.8.

WELDS DESIGNATED AS DEMAND 'CRITICAL WELDS' SHALL BE MADE WITH FILLER METALS MEETING THE REQUIREMENTS

SPECIFIED IN AWS D1.8 CLAUSES 6.3.5, 6.3.6, 6.3.7 AND 6.3.8.

5. ALL WELDS USED IN MEMBERS AND CONNECTIONS IN THE SLRS SHALL BE MADE WITH A FILLER METAL THAT CAN PRODUCE WELDS THAT HAVE A MINIMUM CHARPY V-NOTCH TOUGNESS OF 20 FT-LB AT 0 °F, AS DETERMINED BY THE APPROPRIATE

AWS A5 CLASSIFICATION OR MANUFACTURER CERTIFICATION.

6. USE THE MINIMUM SIZE OF WELDING IN ACCORDANCE WITH AISC 360-16 SECTION J2 AT STEEL-TO-STEEL JOINTS UNLESS A

LARGER WELDING SIZE IS SPECIFIED ON THE PLANS.

7. WHERE LENGTH OF WELDING IS NOT SHOWN, IT SHALL BE FULL LENGTH OF JOINT. ALL BUTT WELDS SHALL BE COMPLETE

PENETRATION WELDS UNLESS OTHERWISE NOTED.

8. THE CONTRACTOR SHALL PROVIDE WELDING PROCEDURE SPECIFICATION (WPS) AND DETAILED SEQUENCE OF WELDING SKETCH FOR REVIEW PRIOR TO STARTING FABRICATION. THE SEQUENCE OF WELDING SHALL BE PLANNED TO MINIMIZE LOCKED IN STRESSES AND DISTORTION. EACH WPS SHALL BE STAMPED WITH AN AWS INSPECTOR'S STAMP INDICATING THAT INSPECTOR'S CERTIFICATION THAT THE WPS CONFORMS TO AWS D1.1 AND D1.8, AND ALL REQUIREMENTS SET FORTH IN THE DRAWINGS AND SPECIFICATIONS. EACH WPS SHALL BE FORMATTED TO FIT ON LETTER SIZED PAPER BUT SHALL BE SUBMITTED ON THE UPPER PORTION OF LEGAL SIZED PAPER ALLOWING FOR AWS INSPECTOR, CONTRACTOR REVIEW, AND DESIGNER REVIEW STAMPS TO BE PLACED ON THE BLANK BOTTOM PORTION OF EACH LEGAL SIZED SHEET.

9. COMPLETE PENETRATION GROOVE WELDS SHALL HAVE A FILLER METAL WITH CHARPY V-NOTCH TOUGHNESS OF 20 FT-LBS AVERAGE AT -20 DEGREES FAHRENHEIT. FOR DEMAND CRITICAL WELDS OF THE SEISMIC LOAD RESISTING SYSTEM SUBJECTED TO SERVICE TEMPERATURES BELOW +50 °F, THE MINIMUM CHARPY V-NOTCH OF 40 FT-LBS SHALL BE PROVIDED AT A SERVICE TEMPERATURE NOT MORE THAN 20 °F ABOVE THE LOWEST ANTICIPATED SERVICE TEMPERATURE.

10. FACES OF FILLET WELDS NOT EXPOSED TO VIEW SHALL HAVE AS-WELDED SURFACES THAT ARE REASONABLY SMOOTH AND UNIFORM. NO FINISHING OR GRINDING SHALL BE REQUIRED EXCEPT WHERE CLEARANCES OR FIT OF OTHER ITEMS MAY SO

NECESSITATE.

11. ALL COMPLETE AND PARTIAL PENETRATION WELDS WHICH ARE EXPOSED TO VIEW SHALL BE GROUND SMOOTH AND FLUSH WITH FINISH SURFACE OF STEEL. HOLES SHALL BE FILLED WITH WELD METAL AND SMOOTHED BY GRINDING OR FILING.

12. FINISH GROOVE PREPARATION THERMAL CUTS BY GRINDING.

13. WELDS SHALL BE TERMINATED AT THE END OF A JOINT IN A MANNER THAT WILL ENSURE SOUND WELDS. THIS SHALL BE

DONE BY USE OF EXTENSION BARS AND RUN OFF TABS IF NECESSARY.

14. TO ASSURE THE PROPER AMPERAGE AND VOLTAGE OF THE WELDING PROCESS, A HAND HELD CALIBRATED AMP AND VOLT METER SHALL BE USED. AMPERAGE AND VOLTAGE SHALL BE MEASURED AT THE ARC WITH THIS EQUIPMENT. TRAVEL SPEED AND ELECTRODE STICK OUT SHALL BE VERIFIED TO BE IN COMPLIANCE WITH THE ELECTRODE MANUFACTURER'S

RECOMMENDATIONS AND WITH THE APPROVED WELDING PROCEDURE SPECIFICATION.

1. STRUCTURAL TESTS AND INSPECTIONS SHALL BE ACCORDING TO 2022 CALIFORNIA BUILDING CODE AND PROJECT

SPECIFICATIONS.

2. THE CONTRACTOR SHALL COORDINATE THE WORK AND SCHEDULE WITH THE OWNERS INSPECTOR TO ASSURE THAT ADEQUATE NOTICE IS GIVEN FOR INSPECTION TO OCCUR WHILE MAINTAINING PROJECT SCHEDULE.

3. CONTINUOUS OR PERIODIC INSPECTION BY THE PROJECT OR SPECIAL INSPECTOR HIRED BY THE OWNER ARE REQUIRED

FOR THE FOLLOWING TYPES OF WORK WHERE OCCURS:

A. CONCRETE

B. REINFORCING STEEL

C. BOLTS INSTALLED IN CONCRETE

D. POST INSTALLED ANCHORS

4. THE TESTING TORQUES FOR POST-INSTALLED ANCHORS SHALL BE BASED ON THE MANUFACTURER'S RECOMMENDED INSTALLATION TORQUE AS APPROVED IN AN ICC-ES EVALUATION REPORT UNLESS OTHERWISE NOTED. (CONFORM TO

REQUIREMENTS OF CBC 2022, SECTION 1901.3.4.4).

5. THE TESTING FORCES FOR POST-INSTALLED ADHESIVE ANCHORS SHALL BE BASED ON ONE AND A QUARTER (1¼) TIMES THE MAXIMUM DESIGN STRENGTH OF ANCHORS AS PROVIDED IN AN APPROVED TEST REPORT USING CRITERIA ADOPTED IN THIS CODE OR DETERMINED IN ACCORDANCE WITH APPENDIX D OF ACI 318. TENSION TEST LOAD NEED NOT EXCEED 80 PERCENT OF THE NOMINAL YIELD STRENGTH OF THE ANCHOR ELEMENT (=0.8Asefya). (CONFORM TO REQUIREMENTS OF CBC

2022, SECTION 1901.3.4.4)

6. ACCEPTANCE CRITERIA FOR POST INSTALLED ANCHORS SHALL BE BASED ON ICC-ESR OR MANUFACTURER'S WRITTEN INSTRUCTION. FIELD TEST SHALL SATISFY THE MINIMUM REQUIREMENTS PER CBC 2022, SECTION 1901.3.4.3 & 1901.3.4.5

7. ALL SPECIAL/DEPUTY INSPECTION REPORTS AND TESTS SHALL INCLUDE: JOB NAME AND JOB NUMBER, SITE LOCATION, PLAN PAGE AND DETAILS, ANY RFI , AND CODE REFERENCES.

STRUCTURAL TEST AND INSPECTIONS

1. STRUCTURAL OBSERVATION IS REQUIRED FOR THE STRUCTURAL SYSTEM IN ACCORDANCE WITH THE CBC 2022, SECTION

1704.6. STRUCTURAL OBSERVATION IS THE VISUAL OBSERVATION AT THE CONSTRUCTION SITE OF THE ELEMENTS AND CONNECTIONS OF THE STRUCTURAL SYSTEM AT SIGNIFICANT CONSTRUCTION STAGES, AND THE COMPLETE STRUCTURE FOR GENERAL CONFORMANCE TO THE APPROVED PLANS AND SPECIFICATIONS. STRUCTURAL OBSERVATION DOES NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS IN SECTION 110 OR THE SPECIAL INSPECTIONS IN 1705 OR OTHER

SECTIONS OF THIS CODE.

2. THE OWNER OR OWNER"S AUTHORIZED AGENT SHALL EMPLOY A STATE OF CALIFORNIA REGISTERED CIVIL OR STRUCTURAL

ENGINEER OR LICENSED ARCHITECT TO PERFORM THE STRUCTURAL OBSERVATION.

NAME OF SE: SAID HILMY

3. THE OWNER OR OWNER'S REPRESENTATIVE SHALL COORDINATE AND CALL FOR A MEETING BETWEEN THE ENGINEER OR ARCHITECT RESPONSIBLE FOR THE STRUCTURAL DESIGN, STRUCTURAL OBSERVER, CONTRACTOR, AFFECTED SUBCONTRACTORS AND DEPUTY INSPECTORS. THE PURPOSE OF THE MEETING SHALL BE TO IDENTIFY THE MAJOR STRUCTURAL ELEMENTS AND CONNECTIONS THAT AFFECT THE VERTICAL AND LATERAL LOAD SYSTEMS OF THE STRUCTURE AND TO REVIEW SCHEDULING OF THE REQUIRED OBSERVATIONS. A RECORD OF THE MEETING SHALL BE INCLUDED IN THE

FIRST OBSERVATION REPORT SUBMITTED TO THE BUILDING INSPECTOR.

4. THE STRUCTURAL OBSERVER SHALL PERFORM SITE VISITS AT THOSE STEPS IN THE PROGRESS OF THE WORK THAT ALLOW FOR CORRECTION OF DEFICIENCIES WITHOUT SUBSTANTIAL EFFORT OR UNCOVERING OF THE WORK INVOLVED. AT A MINIMUM, THE LISTED SIGNIFICANT CONSTRUCTION STAGES ON THE "STRUCTURAL OBSERVATION/SIGNIFICANT CONSTRUCTION STAGES" FORM REQUIRE A SITE VISIT AND AN OBSERVATION REPORT FROM THE STRUCTURAL OBSERVER.

5. THE STRUCTURAL OBSERVER SHALL PREPARE A REPORT OF THE "STRUCTURAL OBSERVATION REPORT FORM" FOR EACH SIGNIFICANT STAGE OF CONSTRUCTION OBSERVED. THE ORIGINAL OF THE STRUCTURAL OBSERVATION REPORT SHALL BE SENT TO THE BUILDING INSPECTOR'S OFFICE AND SHALL BE SIGNED AND SEALED (WET STAMP) BY THE RESPONSIBLE STRUCTURAL OBSERVER OF RECORD. ONE COPY OF THE OBSERVATION REPORT SHALL BE ATTACHED TO THE APPROVED PLANS. THE COPY ATTACHED TO THE PLANS SHALL BE SIGNED AND SEALED (WET STAMP) BY THE RESPONSIBLE STRUCTURAL OBSERVER OR THEIR DESIGNEE. COPIES OF THE REPORT SHALL ALSO BE GIVEN TO THE OWNER, CONTRACTOR, AND DEPUTY INSPECTOR. ANY DEFICIENCY NOTED ON THE OBSERVATION REPORT WILL BECOME THE RESPONSIBILITY OF THE STRUCTURAL ENGINEER OR ARCHITECT OF RECORD TO VERIFY ITS COMPLETION BY THE STRUCTURAL OBSERVER.

CONSTRUCTION STAGE ELEMENT / CONNECTIONS TO BE OBSERVED:

A. TRUSS STRENGTHENING MEMBERS AND CONNECTIONS

7. A FINAL OBSERVATION REPORT MUST BE SUBMITTED WHICH SHOWS THAT ALL OBSERVED DEFICIENCIES WERE RESOLVED AND

STRUCTURAL SYSTEM GENERALLY CONFORMS WITH THE APPROVED PLANS AND SPECIFICATIONS.

8. THE STRUCTURAL OBSERVER OF RECORD SHALL PROVIDE THE ORIGINAL STAMPED AND SIGNED "STRUCTURAL OBSERVATION REPORT FORM" TO THE CITY OF RANCHO CUCAMONGA DEPARTMENT OF BUILDING AND SAFETY BUILDING INSPECTOR.

9. THE ENGINEER OR ARCHITECT OF RECORD SHALL DEVELOP ALL CHANGES RELATING TO THE STRUCTURAL SYSTEMS. THE BUILDING DEPARTMENT SHALL REVIEW AND APPROVE ALL CHANGES TO THE APPROVED PLANS AND APPROVE ALL CHANGES

TO THE APPROVED PLANS AND SPECIFICATIONS.

10. AT THE CONCLUSION OF THE WORK INCLUDED IN THE PERMIT, THE STRUCTURAL OBSERVER OF RECORD SHALL SUBMIT TO THE BUILDING OFFICIAL A WRITTEN STATEMENT THAT THE SITE VISITS HAVE BEEN MADE AND IDENTIFY ANY REPORTED DEFICIENCIES THAT, TO THE BEST OF THE STRUCTURAL OBSERVER'S KNOWLEDGE HAVE NOT BEEN RESOLVED.

STRUCTURAL OBSERVATION

CBC 2022 SPECIAL INSPECTIONS & TEST TABLE

@ AT

& AND

A.B. ANCHOR BOLT

ABV. ABOVE

ADD'L. (ADDL.) ADDITIONAL

ADJ. ADJACENT

ALT. ALTERNATE

ALUM. ALUMINUM

APPRX. (APPROX.) APPROXIMATE(LY)

ARCH. ARCHITECT(URAL)

BLDG. BUILDING

BLKG. BLOCKING

BLW. BELOW

BM. BEAM

B.N. BOUNDARY NAILING

BNDRY. BOUNDARY

B.O.C. BOTTOM OF CONCRETE

B.O.F. BOTTOM OF FOOTING

BOT. (B) BOTTOM

BRCG. BRACING

BRDG. BRIDGE (ING)

BRG. BEARING

BTWN. BETWEEN

CAMB. (C) CAMBER(ED)

CANT. CANTILEVER(ED)

C.F. CUBIC FEET (FOOT)

C.I.P. CAST-IN-PLACE

C.I.D.H. CAST-IN-DRILLED HOLE

C.J. CONTROL JOINT;

CONSTRUCTION JOINT

C.L. ( ℄ ) CENTER LINE

CLG. CEILING

CLR. CLEAR

COL. COLUMN

CONC. CONCRETE

CONN. CONNECTION

CONST. CONSTRUCTION

CONT. CONTINUOUS

C.P. COMPLETE-PENETRATION

CTSK. COUNTERSINK

CTR. CENTER(ED)

C.Y. CUBIC YARD

d d PENNY NAIL

DBA DEFORMED BAR ANCHOR

DBL. DOUBLE

DEPT. DEPARTMENT

D.F. DOUGLAS FIR

DIA. ( Ø ) DIAMETER

DIAG. DIAGONAL

DIAPH. DIAPHRAGM

DIM. DIMENSION

DN. DOWN

DO DITTO (REPEAT)

DWG. (DWGS.) DRAWING(S)

DWL. DOWEL

EA. EACH

E.F. EACH FACE

E.J. EXPANSION JOINT

EL. ELEVATION

ELEC. ELECTRICAL

ELEV. ELEVATOR

EMB. EMBED(MENT)

E.N. EDGE NAIL

ENG. ENGINEER

EQ. EQUAL

EQPT. EQUIPMENT

EQUIV. EQUIVALENT

EXP. EXPANSION

EXIST. (E) EXISTING

EXT. EXTERIOR

FDN. FOUNDATION

FIN. FINISH(ED)

FLR. FLOOR

F.N. FIELD NAIL; FACE NAIL

F.O.C. FACE OF CONCRETE

F.O.M. FACE OF MASONRY

F.O.S. FACE OF STUD

F.O.W. FACE OF WALL

F.P. FULL (COMPLETE) PENETRATION

FRP FIBER REINFORCED POLYMER

F.S. FAR SIDE

FT. (') FOOT (FEET)

FTG. FOOTING

GA. GAUGE

GALV. GALVANIZE(D)

GLB. GLUED LAMINATED BEAM

GRD. GRADE

GRND. GROUND

GYP. GYPSUM

HD. HOLDOWN; HAND

HDR. HEADER

HGR. HANGER

HORIZ. (H) HORIZONTAL

H.S. HEADED STUD

H.S.B. HIGH STRENGTH BOLT

HT. HEIGHT

I.D. INSIDE DIAMETER

IN. (") INCH(ES)

INFO. INFORMATION

JST. JOIST

JT. JOINT

K KIPS; 1000

K.P. KING POST

LAT. LATERAL

L.B. LAG BOLT

LB (#) POUND

L.F. LINEAL FEET (FOOT)

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LT. WT. LIGHT WEIGHT

MAX. MAXIMUM

M.B. MACHINE BOLT

MECH. MECHANICAL

M.E.P. MECHANICAL, ELECTRICAL

AND PLUMBING

MEZZ. MEZZANINE

MFR. MANUFACTURER

MIN. MINIMUM

MISC. MISCELLANEOUS

MTL. METAL

(N) NEW

NO. (#) NUMBER

N.S. NEAR SIDE

N.T.S. NOT TO SCALE

O/C (O.C.) ON CENTER

O.D. OUTSIDE DIAMETER

O.H. OPPOSITE HAND

OPNG. OPENING

OPP. OPPOSITE

ORTHO. ORTHOGONAL

O.W.J. OPEN WEB JOIST

PL. PLATE

P.P. PARTIAL-PENETRATION

P.S.F. POUNDS PER SQUARE FOOT

P.S.I. POUNDS PER SQUARE INCH

PT PRETENSIONED

QTY. QUANTITY

RAD. (R) RADIUS

REF. REFERENCE

REINF. REINFORCEMENT (ING)

REQ'D. (REQD.) REQUIRED

RF. ROOF

R.O. ROUGH OPENING

S.A.D. SEE ARCHITECTURAL DRAWINGS

SC SLIP-CRITICAL

S.C.D. SEE CIVIL DRAWINGS

SCH. SCHEDULE

SEP. SEPARATION

SHT. SHEET

SIM. SIMILAR

SKW. SKEW(ED)

S.O.G. SLAB-ON-GRADE

S.M.S. SHEET METAL SCREW

SPEC. SPECIFICATION

SQ. SQUARE

ST SNUG-TIGHTENED

STD. STANDARD

STAGG. STAGGER(ED)

STIFF. STIFFENER

STIR. STIRRUP

STL. STEEL

STRUC(T). STRUCTURAL

SUSP. SUSPENDED

SYMM. SYMMETRICAL

T&B TOP AND BOTTOM

TEMP. TEMPORARY

THK. THICK(NESS)

T.O. TOP OF

T.O.C. TOP OF CONCRETE

T.O.S. TOP OF STEEL;

T.O.W. TOP OF WALL

TRANS. TRANSVERSE

T.S.G. TAPERED STEEL GIRDER

TYP. TYPICAL

U.O.N. (U.N.O.) UNLESS OTHERWISE NOTED

UTIL. UTILITY

VERT. (V) VERTICAL

W/ WITH

(W) WIDE; WIDTH

WD. WOOD

W.P. WORK POINT

WT. WEIGHT

W.W.F. WELDED WIRE FABRIC

X-STG EXTRA STRONG

XX-STG DOUBLE EXTRA STRONG

N.I.C. NOT IN CONTRACT

DC DEMAND CRITICAL

SFRS SEISMIC FORCE RESISTING SYSTEM

LGR. LEDGER

1. COMPLETE AND PARTIAL JOINT PENETRATION GROOVE WELDS

5. INSPECTION OF WELDING:

a. STRUCTURAL STEEL AND COLD-FORMED STEEL DECK:

X

- X

AWS D1.3,

SDI QA/QC

1705A.2.1, 1750A.2.5

b. REINFORCING STEEL:

1. VERIFY WELDABILITY OF REINFORCING STEEL OTHER THAN

ASTM A706. - X

3. INSPECT ALL OTHER WELDS.

6. INSPECTION OF STEEL FRAME JOINT DETAILS FOR COMPLIANCE:

AWS D1.4

ACI 318: 18.2.8,

25.5.7.4, 26.6.6.4, 26.13.1.4, 26.13.3.2, 26.13.3.3

a. DETAILS SUCH AS BRACING AND STIFFENING. - X

b. MEMBER LOCATIONS.

c. APPLICATION OF JOINT DETAILS AT EACH CONNECTION.

1705A.2.1

TYPE

CONTINUOUS

SPECIAL

INSPECTION

PERIODIC

SPECIAL

INSPECTION

REFERENCED

STANDARD

CBC

REFERENCEa

1. MATERIAL IDENTIFICATION AND TESTING OF HIGH-STRENGTH BOLTS, NUTS AND WASHERS:

a. IDENTIFICATION MARKINGS TO CONFORM TO ASTM STANDARDS

SPECIFIED IN THE APPROVED CONSTRUCTION DOCUMENTS.

2. INSPECTI0N OF HIGH-STRENGTH BOLTING:

- X

b. MANUFACTURER'S CERTIFICATE OF COMPLIANCE REQUIRED.

a. SNUG-TIGHT JOINTS.

b. PRETENSIONED AND SLIP-CRITICAL JOINTS USING TURN-OF-NUT

WITH MATCHMARKING, TWIST-OFF BOLT OR DIRECT TENSION

INDICATOR METHODS OF INSTALLATION.

3. MATERIAL IDENTIFICATION AND TESTING OF STRUCTURAL STEEL AND COLD-FORMED STEEL DECK:

a. FOR STRUCTURAL STEEL, IDENTIFICATION MARKINGS TO CONFORM

TO AISC 360.

b. FOR OTHER STEEL, IDENTIFICATION MARKINGS TO CONFORM TO

ASTM STANDARDS SPECIFIED IN THE APPROVED CONSTRUCTION

DOCUMENTS.

4. MATERIAL IDENTIFICATION OF WELDING CONSUMABLES AND TESTING OF WELDED ELEMENTS:

RCSC: 1.5,

AISC 360: A3.3, J3.1 &

APPLICABLE ASTM

MATERIAL STANDARDS

2202A.1

AISC 360: A3.1

APPLICABLE ASTM

MATERIAL STANDARDS

c. MANUFACTURER'S CERTIFIED TEST REPORTS. -

a. IDENTIFICATION MARKINGS TO CONFORM TO AWS SPECIFICATION

IN THE APPROVED CONSTRUCTION DOCUMENTS. -

AISC 360: A3.5 & N3.2

AND APPLICABLE AWS

A5 DOCUMENTS

b. MANUFACTURER'S CERTIFICATE OF COMPLIANCE REQUIRED. -

CBC 2022 TABLE 1705A.2.1: REQUIRED SPECIAL INSPECTIONS AND TESTS OF STEEL CONSTRUCTION

3. SINGLE-PASS FILLET WELDS > 5 16"

2. MULTIPASS FILLET WELDS.

4. PLUG AND SLOT WELDS

X

6. FLOOR AND ROOF DECK WELDS.

5. SINGLE-PASS FILLET WELDS < 5 16"

2. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5 16"; NOT

DEFINED IN b.4 or b.5

X -

X

X

X

X

X

X

X

X

X

RCSC: 1.5, & 2.1;

AISC 360: A3.3 & N3.2 -

c. TESTING OF HIGH-STRENGTH BOLTS, NUTS AND WASHERS. - -

RCSC: 7.2, APPLICABLE

ASTM MATERIAL

STANDARDS

2213A.1

c. PRETENSIONED AND SLIP-CRITICAL JOINTS USING TURN-OF-NUT

WITHOUT MATCHMARKING OR CALIBRATED WRENCH METHODS OF

OF INSTALLATION.

RCSC: 7-9,

AISC 360: J3.1, J3.2,

M2.5, & N5.6

1705A.2.6, 2204A.2

X -

2202A.1

2202A.1

AISC 360: A3.1 & N3.2

d. TESTING OF UNIDENTIFIED STEEL. - - 2202A.1APPLICABLE ASTM

MATERIAL STANDARDS

c. NONDESTRUCTIVE TESTING OF WELDED JOINTS. - -

AISC 360: N3.2

AISC 360: N5.5

X

X

AISC 360:

J2, M2.4 & M4.5

AWS D1.1

AWS D1.8

1705A.2.1, 1750A.2.2, 1750A.2.5

- X7. END-WELDED STUDS. AWS D1.1 1705A.2.5,

2213A.2

- X8. WELDED SHEET STEEL FOR COLD-FORMED FRAMING MEMBERS AWS D1.3 1705A.2.5,

1750A.2.4.1

5. SHEAR REINFORCEMENT.

1705A.3.1, 1903A.8

X

X

AISC 360:

N5.8

4. REINFORCING STEEL RESISTING FLEXURAL AND AXIAL FORCE

INTERMEDIATE AND SPECIAL MOMENT FRAMES , AND

BOUNDARY ELEMENTS AND COUPLING BEAMS OF SPECIAL

STRUCTURAL WALLS OF CONCRETE AND SHEAR

REINFORCEMENT.

X

X -

X -

a. WHERE APPLICABLE, SEE ALSO CBC SECTION 1705A.13, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.

INSTALL "IEHP" CLOUD CEILING AND SUPPORT FRAMING

ABBREVIATION

NGI

ALONSI

HI E

RP O EF

I.T

RE

DE

S

EER

Y

IA

ORFIAL

LRAUT N

SGER

I

TE OF

CRTS

US

AT

C

No. 3680

S NMLAID

SHEET NO. OF

DATEDESCRIPTIONREV.

1 PETERS CANYON ROAD, SUITE 130

IRVINE, CA. 92606

TEL: 949-387-8500, FAX: 949-387-0800

IDS

IDS GROUP

ISSUE

STAMP

STAMP

ENGINEER/ARCHITECT

PROJECT NAME

CLIENT

IDS PROJECT NO.

DRAWN BY

CHECKED BY

23X119.06

SHEET TITLE

SHEET NUMBER

APPROVAL

APPROVED BY

ID

S

G R

O U

P

- F

IL

E

LO

C

AT

IO

N : S

:\P R

O

JE

C

TS

\2

3\

SH

AR

ED

\2 3X

9.

IE

H P

R

EC

EP

TI

O N

D

ES

K

H

AN

G

IN

G C

LO

U

D \0

C

AD

\0

ST

R U

C \S

-0

_G

EN

ER

AL

N O

TE

S

P

LO

T D

AT

E:

1/

/2

1:

:5

PM

U

SE

R

: C K.

M

AK

XXXXXX

PROJECT IDENTIFICATION

THIS DRAWING WAS CREATED IN AUTODESK AUTOCAD V. 2021

UNLESS OTHERWISE NOTED.

THE ORIGINAL SIZE OF THIS SHEET IS 30" X 42"

THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY AND

COPYRIGHT OF IDS GROUP AND SHALL NOT BE USED ON ANY

OTHER PROJECT OR LOCATIONS EXCEPT AS DESCRIBED ON THE

DRAWINGS, WITHOUT THE WRITTEN AGREEMENT WITH IDS GROUP.

IEHP Reception Desk & Hanging Cloud

Inland Empire Health Plan 10801 Sixth St.

Rancho Cucamonga, CA 91730

PR

O

G R

ES

S

SE

T

- N O

T

FO

R C

O N

ST

R

U C

TI

O

N

Inland Empire Health Plan 10801 Sixth St.

Rancho Cucamonga, CA 91730

EL

CK, VM

SH

GENERAL NOTES

S-001

1 2

A

B

B

±17'-8" F.V. ±21'-0" F.V. ±17'-8" F.V. ±3'-4"±3'-4"

±56'-5" F.V.

5' -0

±2

0' -0

" F .V

4@

±8 '-8

'-8

" F .V

(E) HSS 4x4x1 4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V.

(E) HSS 4x4x1 4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V.

(E) HSS 4x4x1 4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V.

(E) HSS 4x4x1 4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V.

(E) HSS 4x4x1 4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V. (E) HSS 4x4x1

4" CURVE F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

HSS 8x8x1 4" POST F.V. HSS 8x8x1

4" POST F.V. HSS 8x8x1 4" POST F.V. HSS 8x8x1

4" POST F.V.

(E) WF. COLUMN TYP.

20'-0" F.V. 20'-0" F.V.

11/8"=1'-0"PARTIAL ROOF PLAN

96"Wx193"L "IEHP" CURVE

CLOUD CEILING BELOW

MAX. WT = 1,100 LBS

(E) 1 12"X20 GA HSB

ROOF DECK F.V.

SITE MAP

AREA SCOPE

OF WORK

(E)20"Dx42"W

DUCT BELOW

(E)20"Dx42"W

DUCT BELOW

(E) SKYLIGHT

S-501

CABLE BRACE PER

TYP.

CABLE BRACE PER TYP.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E) 44" DEPTH "LH" STEEL

TRUSS F.V.

(E ) W

F.

G

IR

D

ER

(E ) W

F.

G

IR

D

ER

(E) ELEVATOR BELOW

(E) SOFFIT BELOW

21/2"=1'-0"SECTION VIEW

"IEHP" CURVED CLOUD

CEILING PER PLAN

2" WIDE LAMINATED

BACKING BY MANUF. EA.

END

4"

B-LINE B22 UNISTRUT

8"Ø THREADED ROD W/

B-LINE 22 STIFFENER PER

(E) MECHANICAL

DUCT PER PLAN

B-LINE B-22A

TYP.

16"Ø AIR CRAFT CABLE IN

LONGITUDINAL DIRECTION

PER

30°-60°

TYP.

(E) ROOF DECK

PER PLAN

B-LINE B-22A TYP.

2L1 1 4 x1 1

4 x 1 8 "

L2 x2 x3 16 "L2x2x 3

16 "(E )L2 x2 x3 16

"(E)L2x2x 3 16 "

(E )L2 x2 x3 16

S-501

S-501

S-501

S-501

SIM. TYP.

S-500TYP.

S-501

±20'-0" F.V. ±20'-0" F.V.

(E)L2x2x 3 16 " (E

)L2 x2 x3 16

±44" ±55" ±45" ±48" ±48" ±48" ±48" ±49"±55"±45"±48"±48"±48"±48"

±92" F.V.

(E) WF GIRDER

TYP F.V.

2L1 1 4 x1 1

4 x 1 8 "

L2 x2 x3

2L

1 4x

1 4x 1 8"

L2x2x 3 16 "

L2 x2 x3 16

L1

4" x1

4" x1 8"

(E)L2x2x 3 16 " (E

)L2 x2 x3 16

(E)L2x2x 3 16 "

(E )L2 x2 x3 16

(E)L2x2x 3 16 "

2L

1 4x

1 4x 1 8"

L2 x2 x3

S-501

±4 4"

6" MAX. END OF BENDED

LEGS TYP. F.V.

(E)2L2x2x3

16" BOTTOM

CHORD

(E)2L2 12x2 12x3 16"

TOP CHORD

L1

4" x1

4" x1 8"

L1

4" x1

4" x1 8"

L1

4" x1

4" x1 8"

L1

4" x1

4" x1 8"

6" MAX. END OF BENDED

LEGS TYP. F.V.

S-501

96" MAX.

NOTE:

1. CONTRACTOR TO VERIFY ALL DIMENSION PRIOR TO ANY CONSTRUCTION

±92" F.V.3

16"Ø PRE-STRETCHED

7x19 STRAND CORE GALV.

AIRCRAFT CABLE

2'-0"

1' -0

(E) 24"Ø HANGING LIGHT WHERE OCCURS. F.V.

2'-0"

1' -0

(E) 24"Ø HANGING LIGHT WHERE OCCURS. F.V.

33/8"=1'-0"SECTION VIEW

ROOF DECK

PER PLAN

16" AIR CRAFT CABLE

IN TRANSVERSE

DIRECTION PER

44" DEPTH STEEL

TRUSS @ ±8'-8" O.C.

PER

TYP.

B-LINE B22A TYP.

16" AIRCRAFT CABLE

IN TRANSVERSE

DIRECTION PER

8" TREADED ROD W/

B-LINE B22 STIFFENER

TYP. PER 9

S-500

4B

S-500

TYP.

16" AIRCRAFT CABLE IN

TRANSVERSE

DIRECTION PER

TYP.

4A

S-500

TYP.

S-500

" M

AX

8" M

IN

" M

AX

. F

.V

S-500 TYP.

TYP.

NOTE:

1. CONTRACTOR TO VERIFY ALL DIMENSION PRIOR TO ANY CONSTRUCTION

16"Ø PRE-STRETCHED

7x19 STRAND CORE

GALV. AIRCRAFT CABLE

60°

(E) SKYLIGHT

(E) SOFFIT TO REMAIN

NGI

ALONSI

HI E

RP O EF

I.T

RE

DE

S

EER

Y

IA

ORFIAL

LRAUT N

SGER

I

TE OF

CRTS

US

AT

C

No. 3680

S NMLAID

SHEET NO. OF

DATEDESCRIPTIONREV.

1 PETERS CANYON ROAD, SUITE 130

IRVINE, CA. 92606

TEL: 949-387-8500, FAX: 949-387-0800

IDS

IDS GROUP

ISSUE

STAMP

STAMP

ENGINEER/ARCHITECT

PROJECT NAME

CLIENT

IDS PROJECT NO.

DRAWN BY

CHECKED BY

23X119.06

SHEET TITLE

SHEET NUMBER

APPROVAL

APPROVED BY

ID

S

G R

O U

P

- F

IL

E

LO

C

AT

IO

N : S

:\P R

O

JE

C

TS

\2

3\

SH

AR

ED

\2 3X

9.

IE

H P

R

EC

EP

TI

O N

D

ES

K

H

AN

G

IN

G C

LO

U

D \0

C

AD

\0

ST

R U

C \S

-2

_F R

AM

IN

G P

LA

N

P

LO

T D

AT

E:

1/

/2

1:

:5

PM

U

SE

R

: C K.

M

AK

XXXXXX

PROJECT IDENTIFICATION

THIS DRAWING WAS CREATED IN AUTODESK AUTOCAD V. 2021

UNLESS OTHERWISE NOTED.

THE ORIGINAL SIZE OF THIS SHEET IS 30" X 42"

THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY AND

COPYRIGHT OF IDS GROUP AND SHALL NOT BE USED ON ANY

OTHER PROJECT OR LOCATIONS EXCEPT AS DESCRIBED ON THE

DRAWINGS, WITHOUT THE WRITTEN AGREEMENT WITH IDS GROUP.

IEHP Reception Desk & Hanging Cloud

Inland Empire Health Plan 10801 Sixth St.

Rancho Cucamonga, CA 91730

PR

O

G R

ES

S

SE

T

- N O

T

FO

R C

O N

ST

R

U C

TI

O

N

Inland Empire Health Plan 10801 Sixth St.

Rancho Cucamonga, CA 91730

EL

CK, VM

SH

FRAMING PLAN AND

SECTIONS

S-201

(E) WEB MEMBER

L2x2x3

16"

1/8

3" MIN. EA.

END, TYP.2-12

L2x2x3

16" (TRIM BOTH

LEGS FOR WELD)

(E) WEB MEMBER

2L11

4x11 4x1

8"

3" MIN. EA.

END, TYP.2-12

(E) 14" STITCH PL

AT MID WHERE

OCCUR

16" THK x 3" LONG

STITCH PL. AT MID SPAN

2L11 4x11

4x1

8" (TRIM

BOTH LEGS FOR WELD)

WELD ANGLES, (SEE

TRUSS ELEVATION)

1/8

13"=1'-0"(E) STEEL JOIST WEB STRENGTHENING

23"=1'-0"(E) STEEL JOIST WEB STRENGTHENING

1 1/2"

33"=1'-0"TYPICAL ANGLE STIFFENER DETAIL

63"=1'-0"FRAMING CHANNEL TO TOP CHORD

(E) 2-L2 12"x2 12"x1 4"

TOP CHOR

(E) ROOF DECK

PER PLAN

3" MIN.

2"Ø HEX HEAD BOLT W/

N300 SERIES SPRING

NUT. INSTALL TORQUE

50 LBS-FT

TYP.

TOLCO FIG. 990 CABLE SWAY

BRACE ATTACHMENT. TIGHTEN

UNTIL BREAK-OFF NUTS COME

OFF. BOTH DIRECTION (EA. END

OF CABLE)

43"=1'-0"FRAMING CHANNEL BOTTOM CHORD ANGLE

8"Ø THREADED ROD

W/ B-LINE B22

STIFFENER PER 9

B-LINE HN SERIES HEX NUT,

LOCK WASHER AND B-LINE

B200 SERIES SQUARE

WASHER. T&B

B-LINE B22A1

4" STIFF. PL.

(E) 2L2x2x3

16" BOTTOM CHORD

B-761-22A SERIES

BEAM CLAMP

8"Ø THREADED ROD

W/ B-LINE B22

STIFFENER PER 9

B-LINE HN SERIES HEX NUT,

LOCK WASHER AND B-LINE

B200 SERIES SQUARE

WASHER. T&B

B-LINE B22A1

4" STIFF. PL.

(E) 2L2x2x3

16" BOTTOM CHORD

B760-22 SERIES

BEAM CLAMP

CASE B

(AT MIDDLE)

CASE A

(AT END)

B-LINE B-22A

16"Ø PRE-STRETCHED

7x19 STRAND CORE GALV.

AIRCRAFT CABLE

BOTH

ENDS

B-LINE B22 SOLID, PUNCHED OR

SLOTTED CHANNEL.

TOLCO FIG. 99 OR B-LINE ATR ALL

THREAD ROD.

4" M

AX

. D

IS

TA

N C

E

FR

O M

T O

P O

F H

AN

G

ER

T

O F

IR

ST

ST

IF

F.

1" MA

X.

MA

X.

C

LIP

S

PA

CI

NG

BE

TW

EE

N

FI

G

(S

EE

C

HA

RT

MA

X.

TOLCO FIG. 98 ROD

STIFFENER.

TORQUE 8 FT. LBS.

ROD SIZE

8" 18"

MAX. ROD

LENGTH

WITHOUT ROD

STIFFENER

2 "

8 "

4"

8"

25"

37"

43"

31"

MAX.

COMPRESSION

FORCE WITHOUT

STIFFENER

MAX. SPACING

BETWEEN

TOLCO FIG. 98

13"

18"

28"

33"

23"

MAX.

COMPRESSION

FORCE WITH

STIFFENER

B-LINE B22 SOLID,

PUNCHED OR SLOTTED

CHANNEL

M

AX

. R O

D L

EN

G

TH

W

IT

H

O U

T

ST

IF

FE

N

ER

(S

EE

T

AB

LE

NOTES:

1. ROD STIFFENERS ARE REQUIRED ONLY ON VERTICAL STRUT COMPONENT OF THE SEISMIC BRACE

SYSTEM ON HANGER AND TRAPEZE ASSEMBLIES THAT HAVE SEISMIC BRACING BRACING ATTACHED AT OR WITHIN 6" OF THE ROD. A MINIMUM OF TWO ROD STIFFENERS (TOLCO FIG. 98) MUST BE

INSTALLED.

2. DETAIL APPLIES TO ALL HUNG UTILITIES INCLUDING SINGLE HUNG UTILITIES, TRAPEZE HUNG

UTILITIES, AND HUNG EQUIPMENT.

3. AN EXCEPTION IS THE USE OF TWO OPPOSING RIGID BRACES AT THE SAME LOCATION. FOR INDIVIDUALLY HUNG PIPE THE TWO OPPOSING RIGID BRACES MUST BE AT THE SAME HANGER ROD;

TOTAL OF (2) FOR TRANSVERSE, OR TWO (2) LONGITUDINAL FOR A TRAPEZE HANGER THE TWO OPPOSING RIGID BRACES MUST BE AT SAME HANGER ROD; TOTAL OF TWO (2) FOR TRANVERSE , OR

FOUR (4) FOR LONGITUDINAL. THE TWO OPPSING BRACES MUST BE AT THE SAME ANGLE FROM

HORIZONTAL AND WITHIN 5 DEGREES OF 180 DEGRESS FROM EACH OTHER. IN THIS CASE NO

STIFFENING OF VERTICAL ROD IS NECESSARY.

4. MATERIAL SPECIFICATIONS FOR TOLCO FIG. 98, BODY: ASTM A-1011 CS TYPE B SAE; 1006 BOLT: HEX

BOLT GR5

5. THREADED ROD SHALL CONFORM TO ASTM A307

91 1/2"=1'-0"VERTICAL ROD STIFFINER (OPM-0052-13)

8"Ø THREADED ROD

W/ B-LINE B22

STIFFENER PER

16"Ø PRE-STRETCHED

7x19 STRAND CORE

GALV. AIRCRAFT CABLE

TOLCO FIG. 991 CABLE SWAY BRACE

ATTACHMENT. TIGHTEN UNTIL

BREAK-OFF NUTS COME OFF. BOTH

DIRECTION (EA. END OF CABLE)

B-LINE B22

L3x3x3 16"x2"

2"Ø THRU BOLT

2" WIDE LAMINATED

BACKING BY MANUF.

EA. END

"IEHP" CURVED CLOUD

CEILING PER PLAN (BY

OTHERS)

51 1/2"=1'-0"IEHP CLOUD CEILING TO STRUT

4" M

AX

. D

IS

TA

NC

E

F

RO

M

TO

P

OF

H

AN

GE

R

TO

F

IR

ST

S

TI

FF

13N.T.S.(E) ROOF CONDITION (FOR REF. ONLY)

HANGER BRACKET PER

MANUFACTURER

LOCK WASHER & NUT

DETAILS

NGI

ALONSI

HI E

RP O EF

I.T

RE

DE

S

EER

Y

IA

ORFIAL

LRAUT N

SGER

I

TE OF

CRTS

US

AT

C

No. 3680

S NMLAID

SHEET NO. OF

DATEDESCRIPTIONREV.

1 PETERS CANYON ROAD, SUITE 130

IRVINE, CA. 92606

TEL: 949-387-8500, FAX: 949-387-0800

IDS

IDS GROUP

ISSUE

STAMP

STAMP

ENGINEER/ARCHITECT

PROJECT NAME

CLIENT

IDS PROJECT NO.

DRAWN BY

CHECKED BY

23X119.06

SHEET TITLE

SHEET NUMBER

APPROVAL

APPROVED BY

ID

S

G R

O U

P

- F

IL

E

LO

C

AT

IO

N : S

:\P R

O

JE

C

TS

\2

3\

SH

AR

ED

\2 3X

9.

IE

H P

R

EC

EP

TI

O N

D

ES

K

H

AN

G

IN

G C

LO

U

D \0

C

AD

\0

ST

R U

C \S

-5

_S

EC

TI

O

N S

AN

D

D

ET

AI

LS

P

LO

T D

AT

E:

1/

/2

1:

:5

PM

U

SE

R

: C K.

M

AK

XXXXXX

PROJECT IDENTIFICATION

THIS DRAWING WAS CREATED IN AUTODESK AUTOCAD V. 2021

UNLESS OTHERWISE NOTED.

THE ORIGINAL SIZE OF THIS SHEET IS 30" X 42"

THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY AND

COPYRIGHT OF IDS GROUP AND SHALL NOT BE USED ON ANY

OTHER PROJECT OR LOCATIONS EXCEPT AS DESCRIBED ON THE

DRAWINGS, WITHOUT THE WRITTEN AGREEMENT WITH IDS GROUP.

IEHP Reception Desk & Hanging Cloud

Inland Empire Health Plan 10801 Sixth St.

Rancho Cucamonga, CA 91730

PR

O

G R

ES

S

SE

T

- N O

T

FO

R C

O N

ST

R

U C

TI

O

N

Inland Empire Health Plan 10801 Sixth St.

Rancho Cucamonga, CA 91730

EL

CK, VM

SH

S-501

Sheets and Views
S-001_GENERAL NOTES-S-001
S-201_FRAMING PLAN-S-201
S-501_SECTIONS AND DETAILS-S-501

File details come from the government source that posted it. Updated .