This document is a Welding, Cutting, and Brazing Policy developed by IEHP (Inland Empire Health Plan) to provide comprehensive safety requirements for welding operations in accordance with OSHA (Occupational Safety and Health Administration) standards under 29 CFR 1910.252. The policy applies to all employees and contractors performing welding, cutting, or brazing activities at IEHP facilities, establishing detailed guidelines for safe work practices, personal protective equipment (PPE), designated work areas, and hot work permit procedures.
The policy outlines extensive safety protocols including pre-work hazard assessments, fire watch requirements, equipment inspections, and specific protective measures for different types of welding operations. Key safety provisions include removing flammable materials within 35 feet of work areas, using appropriate fire-resistant materials like welding blankets and curtains, maintaining proper ventilation, and ensuring workers use comprehensive PPE including flame-resistant clothing, eye protection, and heat-resistant gloves. The document also addresses fall protection challenges specific to welding, emphasizing the need for heat-resistant harnesses and frequent equipment inspections to meet OSHA requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Welding, Cutting, & Brazing Policy
1 | P a g e
Purpose
The purpose of this policy is to provide safety requirements for welding, cutting and brazing in accordance with OSHA under 29 CFR 1910.252 requirements.
Scope and Applicability
This policy applies to anyone working at any IEHP facility who may perform welding, cutting, or brazing in their job functions.
Abbreviations and Definitions
Abbreviations
OSHA: Occupational Safety and Health Administration
PPE: Personal Protective Equipment
Definitions
Brazing: Applies heat to the metal, usually from an oxy-acetylene gas flame. The metal does not reach its melting point. Instead, filler material and flux from a welding rod melt to form the weld.
Designated Area: An area where welding, cutting, and or brazing is authorized.
Fire Watch: Trained personnel who are in attendance during the entire cutting and welding operation and are immediately available to extinguish a fire or take other effective action if necessary.
Gas Cutting: Creates a molten pool of metal using heat from a gas torch. A jet of oxygen is injected into the pool to accelerate the oxidation of the material.
Gas Welding: Typically uses an oxy-acetylene gas flame as a source of heat. Some types of gas welding, such as soldering, using propane or other fuel gases.
Hot Work: Any temporary operation involving open flames or producing heat and/or sparks.
This includes, but is not limited to, grinding, cutting, brazing, soldering, torching, and welding.
Hot Work Permit: A special permit issued by the Supervisor or EHS which authorizes specific welding, cutting, and/or brazing activities at a specific location and time.
Hot Work Operator: Employee who is qualified and authorized to perform hot work, such as welding, brazing, soldering, and other associated work tasks.
Rev. 07082025
Permit: Authorized Individual: employee who is trained and is authorized to issue a hot work permit.
Soldering: Like brazing, is accomplished without melting the metal parts that will be joined.
Welder/Welder Operator: Any operator of electric or gas welding and cutting equipment.
Roles and Responsibilities
Those who conduct welding, cutting or brazing shall:
• Ensure that all directly supervised employees and contractors utilize appropriate welding, cutting and brazing procedures.
• Ensure that the conditions of designated hot work areas have not changed prior to authorizing hot work.
• Ensure that all welding and cutting equipment is maintained in a safe operating condition.
• Ensure that employees are trained in the operation of the equipment and safe use of the process.
• Ensure hot work permits for work under their supervision.
• Determine the combustible materials and hazardous areas present or are likely to be present in the work area.
• Determine that fire protection and fire extinguishing equipment are properly located at the site.
• When fire watches are required, make sure they are available at the site.
• Review and approve locations proposed for Hot Work areas.
• Periodically inspect designated areas to be sure that conditions have not become unsafe for welding or cutting.
• Suspend welding, cutting and brazing work if conditions become unsafe for the work being performed.
• Provide training for the fire watches and ensure that the proper firefighting equipment is in working condition and is available to standby personnel.
• Advise contractors about flammable materials or hazardous conditions of which they may not be aware.
• Communicate all hazards associated with the potentially hazardous materials employed in fluxes, coatings, coverings and filler materials, complying with the OSHA HAZCOM standard. Ensure employees have access to labels on containers and safety data sheets and are trained in accordance with HAZCOM regulations.
• Ensure proper engineering and administrative controls are established to protect everyone from welding hazards; provide personal protective equipment to workers when necessary.
Those performing Hot Work shall:
• Read and understand the IEHP welding, cutting and brazing policy.
• Submit evidence of completion of hot work training.
• Ensure that PPE is worn properly for the specific hazard involved and that all equipment is in good working condition.
• Conduct welding, cutting, brazing and/or hot work activities in accordance with all safety guidelines and procedures.
• Protect nearby personnel and materials against heat, sparks, etc. when working in occupied workplaces.
• Inform their supervisors of any hazards that they feel are not adequately addressed in the workplace and of any concerns they have regarding the program.
Contractors shall:
• Follow Welding, Cutting and Brazing Policy and follow all OSHA requirements.
• Provide personal protective equipment and other engineering and administrative means to protect against harmful exposures during welding.
The following safety guidelines should be followed when performing various welding operations:
Electric Welding and Cutting:
• Perform Safety Check on all equipment
• Ensure fire extinguisher is charged and available.
• Perform Safety Check on all equipment
• Ensure electrical cords, electrode holders and cables are free from defects (no cable splices are allowed within 10 feet of the electrode holder.
• Ensure PPE (welding hood, gloves, rubber boots/soled shoes, aprons) are available and have no defects.
• Ensure the welding unit is properly grounded.
• Examine equipment frequently to determine that all electrical connections and insulation on holders and cables are in good condition. Loose cable connections may overheat, or arc cause a fire.
• Keep welding cables dry, grease and oil-free, and protected from sparks or hot metal.
• Store welding rods in the container on the welding machine; do not throw them on floors or staging.
Gas Welding and Cutting
• Perform Safety Check on all equipment
• Ensure tanks have gas and fittings are tight.
• Ensure fire extinguisher is charged and available.
• Ensure hoses have no defects.
• Ensure PPE (welding hood, gloves, rubber boots/soled shoes, aprons) are available and have no defects.
• All defective equipment must be repaired or replaced before use.
• Remove flammables and combustibles
• Remove all nearby flammable or combustible materials before striking an arc or lighting a flame.
• Remove all flammable and readily combustible materials from your pockets, such as matches and cigarette lighters.
• Place welding screen or suitable barricade around the work area to provide a fire safety zone and prevent injuries to passersby.
Welding Operators Protection
Before beginning a welding job, it is very important to identify the hazards for that specific welding operation. Welders should understand the hazards they are working with. A Safety Data
Sheet (SDS) should be provided to identify the hazardous materials used in the welding operation. Less hazardous materials can be substituted for some welding chemicals, such as cadmium –free solders and asbestos-free electrodes, gloves and hot pads.
Welding surfaces should be cleaned of any coatings that could potentially create toxic exposure, such as paint and solvent residue.
Workers should position themselves to avoid breathing welding fumes and gases. For example, welders should stay upwind when welding in open or outdoor environments.
Welders need to be protected against heat, sparks, ultraviolet rays, hot slag, fumes and toxic gases. Make sure workers are outfitted with the following personal protective equipment (PPE):
Personal Protective Equipment:
Body Protection:
• Clothing should provide sufficient coverage, and be made of suitable materials, to minimize skin burns caused by sparks, splatter, or radiation.
• Keep clothing dry and change when needed to reduce the risk of electric shock.
• Keep clothing clean (free of grease, oil and solvents, which can catch fire and burn easily).
• Do not wear synthetic fabrics, wear cotton or wool.
• Protective clothing and equipment shall be suitable for the type of work to be performed, kept in good condition, and kept free of oil and grease.
• Sleeves shall be kept buttoned at the wrist.
• Collars shall be kept buttoned.
• Fire-resistant gloves and aprons shall be worn during welding, flame cutting and brazing processes.
• Safety shoes should be worn to protect the operator from spark hazard.
Eye and Face Protection
• Safety glasses, goggles, face shields, helmets, or other suitable eye protection having the proper shade lens for the work being done shall be worn during all welding, cutting, and brazing operations.
• Fire Watch personnel shall wear eye and face protection as appropriate.
• Wear flame resistant gloves (such as leather welder’s) that are dry, hole-free and insulated.
• Goggles shall be ventilated to prevent fogging of the lenses as much as practicable.
• Goggles, helmets, and face shields shall be checked frequently.
Head protection
• Head protection made of a flame-resistant material shall be worn.
Foot and Leg Protection
• Wear leather, steel-toed, high top boots in good condition
• In heavy spark and slag areas, used fire-resistant foot protectors or leather spats strapped around pant legs and boot tops.
• Do not tuck pant legs into boots.
Designated Hot Work Areas
• All hot work shall be performed in a Designated Hot Work Area, if possible.
• Where welding, cutting and brazing are done near walls, partitions, ceilings, or a roof of combustible construction, fire-resistant shields or guards shall be provided to prevent ignition.
• Protective dividers such as welding curtains or non-combustible walls will be provided to contain sparks and slag to the combustible free area.
• Flammable and combustible liquids and material will be kept 35 feet from work area.
• Floors shall be swept and clean of combustibles within 35 feet of work area.
• A fire extinguisher shall be within access to the 35 feet of work area and shall be maintained in a state of readiness for instant use.
Hot Work Procedures
• All hot work permits shall be returned to the issuing ABM supervisors when the hot work has been completed.
• Supervisors and contractors are responsible for identifying and controlling workplace hazards before hot work is performed.
• Hot Work Permit (for non-designated hot work area) will be issued for a period covering the duration of hot work.
Prior to Hot Work
• Inspect the hot work area to identify any fire hazards.
• Remove all flammable or combustible materials within a thirty-five (35) foot radius of the hot work.
• Sweep floor of all loose combustible debris.
• Combustible floors shall be covered with fire resistant flooring protection mats during the hot work.
• Place non-combustible or flame-resistant screens to protect personnel in adjacent work areas from heat, flames, radiant energy and welding splatter.
• Cover sprinkler heads directly above the hot work area with wet rags or other non-combustible materials so they will not be triggered during the work if the hot work area has any.
• Cover smoke detectors located in proximity to the work area or notify the ABM
Supervisor to deactivate smoke detectors in the hot work area.
• Notify anyone nearby who may be affected by the work.
• Make provisions for proper ventilation.
During Hot Work
• Store acetylene and other fuel cylinders in a secure and upright position.
• Place hoses so that they will not be crushed or damaged.
After Hot Work
• Remove any covers from sprinkler heads immediately upon completion of the hot work if the hot work area has any.
• Remove covers from any smoke detectors immediately upon completion of the hot work or notify ABM to reactivate them if they have been deactivated.
• Clean up any slag, debris or used electrodes resulting from the work.
• Restore ventilation to its original condition.
Hot Work in areas not designated as Hot Work Areas.
When welding, cutting, or brazing work is to be done outside of a Designated Hot Work Area, it is necessary to meet the following requirements:
• A Hot Work Permit is required for all Hot Work. Contact ABM supervisor for a Hot
Work Permit.
Permit Authorization—The hot work permit should contain the following information:
• Name of employee or contractor authorized to perform the hot work
• Location of hot work area
• Nature of work to be performed
• Issue date and expiration date of permit
• Signature of authorizing supervisor
Most organizations develop a hot work permit that can be used by both employees and contractors. Additional supervision should be provided whenever contractors are performing hot work, as they are less familiar with the hazards of the facility.
Permit Posting— Hot work permits should be printed on a highly visible color of paper (e.g., hot pink, bright orange) and posted in a prominent location in the work area. This lets other employees and contractors know that hot work is being conducted in the area.
Precautions and Safeguards—The precautions and safeguards that should be taken when performing hot work will vary in each situation. The supervisor authorizing the permit should verify that all hazards have been controlled in the hot work area before any work begins.
Evaluate the following hot work precautions and safeguards prior to authorization:
• Sprinklers, hoses and fire extinguishers are in good working order
• Hot work equipment is in good condition (hoses, compressed gas cylinders, electrical cords, etc.)
• Within 35 feet of the work area:
o Remove flammable liquids, dust, lint and oil deposits o Eliminate explosive atmosphere in the work area o Sweep all floors o Wet down combustible floors and protect with sand or fire-resistant blankets o Remove combustibles or protect with fire-resistant blankets or metal covers o Cover all floor or wall openings o Close all doors and fire doors
• If working on walls or ceilings, ensure that:
o Construction is noncombustible and there are no combustible coverings or insulation o All combustibles on the other side of the wall or ceiling are moved away
• If working on enclosed equipment, ensure that:
o Equipment is cleaned of flammable liquids, combustible dusts and residues o Equipment is purged of flammable vapors
Hot work should not be authorized until hazardous conditions have been eliminated. Never take a shortcut, even if the hot work will only be performed for a few minutes.
• Flammable materials that cannot be removed from the area must be adequately covered or guarded before hot work is started.
• All floor openings and cracks shall be closed, sealed and/or covered to ensure that sparks cannot drop into the openings and come into contact with combustible materials.
• Guards, shields, and or fire-blankets shall be used to confine the heat, sparks and/or slag from coming into contact with any combustible material with 35 feet of the hot work
• Portable welding curtains or shields must be used to protect other workers in the welding area.
• Airflow away from the welder and others present must be established and maintained.
• Plastic materials must be covered with welding tarps during welding procedures.
• Suitable fire extinguishing equipment shall be always maintained in a state of readiness for instant use. This may include fire extinguishers, water hoses or buckets of sand, depending on the nature of the combustible material exposed
Fire Watch:
Fire Watchers shall be required whenever these activities are performed in locations where other than a minor fire might develop. The Fire Watcher:
• Shall be present to ensure that sparks, slag and heat generated by the hot work do not start a fire while the welder is working.
• Shall not be assigned any other duty during fire watch period.
• Shall remain at the work location for at least thirty (30) minutes after the hot work has been completed to ensure that no sparks or slag are smoldering and that the heat generated by the hot work did not cause other materials to smolder thus creating a potential fire hazard.
• Shall be trained in the proper use of fire extinguishing equipment and be prepared to use it.
• Shall be familiar with facilities for sounding an alarm in the event of a fire or other emergency situations.
• Shall also be trained to react to other potential hazards associated with the work activity such as exposure to welding fumes, welding flash and any other potential hazards unique to the area in which the work is being performed.
• The person performing hot work and the Fire Watch shall be required to read the Hot
Work Permit and sign the permit acknowledging the fact that they understand the potential hazards and will follow the requirements of the permit.
• If feasible, floors shall be wet, or covered with a fire blanket, fire pad, or other flame-resistant material prior to start of hot work to prevent ignition.
APPROVED FIRE-RESISTANT MATERIALS FOR HOT WORK AREAS:
Welding Blanket: A welding blanket is a heat-resistant fabric designed to be placed in the vicinity of a hot work operation. Intended for use in horizontal applications with light to moderate exposures such as that resulting from chipping, grinding, heat treating, sand blasting, and light horizontal welding. They are designed to protect machinery and prevent ignition of combustibles such as wood that are located under the blanket. They are made from different materials such as fiberglass, silica, and other fire-resistant materials.
Welding Pads: A welding pad is heat-resistant fabric designed to be placed directly under a hot work operation such as welding or cutting. Welding pads are intended for use horizontal applications with severe exposures such as that resulting from molten substances of heavy horizontal welding.
Welding Curtain: A welding curtain is a heat-resistant fabric designed to be placed in the vicinity of a hot work operation. It is intended for use in vertical application with light to moderate exposures such as that resulting from chipping, grinding, heat treating, and light horizontal welding. It’s designed to prevent sparks from escaping a confined area.
*Welding blankets and curtains are required to be listed, approved, or the equivalent for such use. One such approval includes ANSI/FM 4950, American National Standard for Evaluating
Welding Pads, Welding Blankets and Welding Curtains for Hot Work Operations.
Fall Protection and Hot Work:
Fall protection used in welding operations presents special challenges, since the hot slag generated from hot work can damage harnesses and other fall protection equipment. Full body harnesses made of heat-resistant material should be used to protect equipment from heat and UV exposure. All fall protection equipment must be inspected before each use and meet OSHA requirements.
References
OSHA: 29 CFR 1910.133 Eye and Face Protection
OSHA: 29 CFR 1910 Subpart Q: Welding, Cutting, and Brazing
OSHA 29 CFR 1910 Subpart J: Welding and Cutting
OSHA 29 CFR 1915 subpart D: Welding, Cutting and Heating
OSHA: 29 CFR 1926.350 Gas, Welding, and Cutting
OSHA 29 CFR 1910.146: Permit Required Confined Spaces
OSHA 29 CFR 1910.1200: Hazard Communication
OSHA 29 CFR 1910.134: Respiratory Protection https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=9778 https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=10133 https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=10121 https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=12929 https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=10696 https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=9797 https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=standards&p_id=10099 https://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=standards&p_id=12716