This is a Limited Pre-Renovation Survey Report prepared by RMEC Environmental, LLC for the State of Utah Division of Facilities Construction and Management (DFCM) regarding the Salt Lake City Division of Workforce Services facility located at 720 S. 200 East, Salt Lake City, Utah. The survey was conducted on July 28, 2026, to identify regulated asbestos-containing materials (RACM), lead-containing paint (LCP), and other hazardous materials prior to planned renovation activities involving the replacement of rooftop units (RTU), variable air volume (VAV) boxes, boilers, and pumps. The survey included a comprehensive visual assessment and physical evaluation of accessible suspect asbestos-containing building materials, with 27 bulk samples collected from 12 homogeneous areas and analyzed using Polarized Light Microscopy (PLM) methodology. Lead-containing paint was evaluated using X-Ray Fluorescence (XRF) technology with nine readings taken throughout the project area. The report was prepared by certified asbestos inspectors Mackenzie Hobbs (ASB-7699) and Benjamin Lambert (ASB-9061) and was finalized with revisions on August 26, 2026.
The survey findings determined that no asbestos-containing materials (ACM) or regulated asbestos-containing materials (RACM) were identified in the project area, and no sampled areas contained significant levels of lead-containing paint, although detectable amounts were found in one maintenance storage room location with readings ranging from 0.00 to 0.06 mg/cm². The survey identified two types of hazardous materials requiring proper disposal: approximately 225 fluorescent light bulbs and approximately 75 fluorescent lamp ballasts throughout the project area. The report recommends that OSHA requirements be followed for any disturbance of detected lead-containing paint surfaces, including dust suppression activities and best management practices. The document must be retained on-site during all demolition or renovation activities and kept on file for at least five years following completion of work.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Limited Pre-Renovation Survey Report and Hazardous Materials Survey
Salt Lake City Division of Workforce Services (5633) 720 S. 200 East
Salt Lake City, Utah 84111
RMEC PJ26A-5735
August 21, 2026
Prepared For:
State of Utah Division of Facilities Construction and Management 4315 South 2700 West, 3rd Floor
Taylorsville, Utah 84129-218
Utah DFCM
RTU & Boiler Renovation (Salt Lake City, Utah)
PJ26A-5735 Page I
DOCUMENT CONTROL
LIMITED PRE-RENOVATION SURVEY REPORT AND HAZARDOUS MATERIALS
SURVEY
SALT LAKEC CITY DIVISION OF WORKFORCE SERVICES (5633) – RTU AND BOILER
RENOVATION
PROJECT NUMBER: PJ26A-5648
PREPARED FOR:
State of Utah Division of Facilities Construction and Management 4315 South 2700 West, 3rd Floor Taylorsville, Utah 84129-2128
ATT: Mike Mirabella
PREPARED BY:
RMEC Environmental, LLC.
476 W. 325 South Bountiful, Utah 84010 t: (801) 467-3661 e: general@rmec.net
AUTHOR(S):
Mackenzie Hobbs Environmental Scientist RMEC Environmental, LLC.
8/21/2026 Signature Date
REVIEWER(S):
Daniel E. Nye, MSPH, CIH Senior Industrial Hygienist RMEC Environmental, LLC.
8/21/2026 Signature Date
REVISION HISTORY:
Revision Number Date Issued Reason/Comments:
00 August 21, 2026 INITIAL ISSUE
01 August 26, 2026
CLARIFIED
RECOMMENDED LEAD
PAINT ACTIONS
PJ26A-5735 Page II
APPENDICES
APPENDIX A – RMEC Inspection Summary Table(s)
APPENDIX B – Analytical Results Report(s)
APPENDIX C – Site Photographs and Sample Location Diagram
APPENDIX D – Copy of Certifications
TABLE OF CONTENTS
EXECUTIVE SUMMARY
1.0 INTRODUCTION
1.1 Site Information
1.2 Scope of Services
1.3 Limitations and Warranty of Work
1.4 Reliance
2.0 INSPECTION ACTIVITIES
2.1 Credentials
2.2 Field Activities
2.2.1 Visual Assessment
2.2.2 Suspect ACBM Physical Assessment
2.2.3 Suspect ACBM Sample Collection
2.2.4 Coatings Sample Collection to Identify Lead Containing Paint
2.3 Sample Analysis
2.4 Regulatory Overview
3.0 RESULTS/DISCUSSION
3.1 Asbestos Findings
3.1.1 Inaccessible Areas or Unsampled Materials
3.2 LCP Findings
4.0 RECOMMENDATIONS
PJ26A-5735 Page III
EXECUTIVE SUMMARY
RMEC Environmental, LLC. (RMEC) was retained by the State of Utah Division of Facilities Construction and Management (DFCM) to conduct a limited asbestos, lead, and hazardous materials pre-renovation survey for the Salt Lake City Division of Workforce Services (DWS) facility, located at 720 S. 200 East in Salt Lake City, Utah. This work was requested by DFCM in preparation for renovation work on the rooftop (RTU) unit, boilers, pumps, and variable air volume (VAV) boxes. Renovation activities were expected to impact mounts, piping, and features related to these units.
This Executive Summary only provides a brief overview of the findings from this survey—please read the report in its entirety for a more thorough presentation of all findings.
The site walkthrough and associated on-site sampling was conducted on July 28, 2026, by Mackenzie Hobbs and Benjamin Lambert, RMEC employees certified by the State of Utah as Asbestos Inspectors (ASB-7699 and ASB-9061, respectively). The purpose of the survey was to identify any regulated asbestos containing materials (RACM), in accordance with Utah Administrative Code (UAC) R307-801, that would require abatement, removal, and/or other safety precautions prior to the planned renovation activities.
RMEC was also tasked with identifying whether lead-containing paint (LCP), as defined by the U.S.
Occupational Safety and Health Administration (OSHA), was present in the structure and would likely be disturbed during renovation activities. Lastly, RMEC was asked to identify other hazardous materials that might be impacted during the planned renovation activities.
Asbestos Findings
As noted in Table A in Appendix A, no asbestos-containing materials (ACM) were identified as part of this survey.
Lead Findings
As noted in Table C in Appendix A, no sampled areas were identified as containing significant levels of LCP, although detectable amounts were found.
Hazardous Materials Findings
RMEC searched for other hazardous materials that could potentially be affected by activities within the scope of the project and noted the following (quantities are also noted):
• Fluorescent Light Bulbs (~225 total throughout the project area that may be affected)
• Fluorescent Lamp Ballasts (~75 total throughout the project area that may be affected)
As needed, all hazardous materials should be properly handled and disposed of according to local, regional, state, and/or national regulations before demolition or renovation occurs.
PJ26A-5735 Page 1
1.0 INTRODUCTION
RMEC Environmental, LLC. (RMEC), a State of Utah-Certified Asbestos Company (#ASBC-325), was retained by the State of Utah Division of Facilities Construction and Management (DFCM) to conduct a limited pre-renovation and hazardous materials survey of the project area described below.
In accordance with Utah Administrative Code (UAC) R307-801-9, the purpose of this limited survey was to identify and document any regulated asbestos containing materials (RACM) that would require removal or other potential actions prior to the planned renovation activities. Painted/Coated surfaces were also evaluated for lead, and an inventory of other potential hazardous materials was also determined.
1.1 Site Information
This section provides basic information that could be readily obtained about the project site/area and its associated structure(s).
Location/Address 720 S. 200 East, Salt Lake City, Utah Owner STATE BUILDING OWNERSHIP AUTHORITY Site Description The Salt Lake City Division of Workforce Services facility is a two-story commercial structure made of brick construction. The building was constructed in 1998 according to Salt Lake City Assessor records. Per DFCM, the planned renovation work was to include the replacement of an RTU unit, indoor VAV boxes across both floors, and two boilers and pumps in the mechanical space. Building materials expected to be impacted as part of this assessment included the RTU unit mount, piping near VAV boxes, and materials associated with the boilers and pumps.
1.2 Scope of Services
The scope of work for the asbestos survey included a limited on-site inspection for asbestos-containing materials (ACM), specifically with the intent to identify RACM (as defined in Section 2.4 of this report) in planned renovation areas. Accessible suspect asbestos-containing building materials (ACBM) were categorized into homogeneous areas for bulk sample collection and analysis, and then representative bulk samples of each identified homogeneous area throughout the project area were collected in accordance with 40 CFR 763.86. For each suspect ACBM identified during this work, RMEC’s intent was to provide accurate details regarding material type, location, condition, and approximate quantity throughout the project area (including any targeted building exteriors).
The scope of work for an evaluation of lead-containing paint (LCP) included evaluating all suspect painted/coated surfaces in the planned renovation areas. The intent was to identify all paint types, components, substrates, locations, conditions, and approximate quantities, and then note which ones contained any detectable level of lead.
The scope of work for the hazardous materials inventory included identifying other hazardous materials or products in the project area that could be disturbed during renovation activities.
Specific inspection and sampling methodologies are described in Section 2.0 of this report.
PJ26A-5735 Page 2
1.3 Limitations and Warranty of Work
RMEC warrants that the findings contained in this report have been prepared in general accordance with accepted professional practices at the time of its preparation as applied by similar professionals in the community. The field and laboratory results reported herein (only if bulk samples were collected) are considered sufficient in detail and scope to determine the presence of accessible and/or exposed suspect ACM, LCP, or hazardous materials at the defined project area. The results, findings, conclusions, and recommendations expressed in this report are based on the conditions observed during the site visit(s).
Changes in the state of the art or in applicable regulations cannot be anticipated and have not been incorporated into this report. RMEC does not warrant the work of regulatory agencies, laboratories, or other third parties, even if they provided information that may have been used in the preparation of this report.
Certain survey and analytical methods have been used to provide the client with information regarding the presence of accessible and/or exposed ACM or LCP present in the project area at the time of the survey.
Test results are valid only for materials tested. There is a distinct possibility that conditions or materials may exist—for suspect ACBM, LCP, and hazardous materials—which could not be reasonably identified within the scope of the survey, or which were not apparent during the site visit. The survey is also limited to the information available from the client at the time the survey was conducted.
Please note that the survey covered only accessible suspect materials and/or surfaces found within the planned renovation area—all relevant inaccessible areas are noted and explained in Section 3.0 of this report.
Estimations regarding total quantity for each suspect ACBM, LCP, or hazardous material are based only on a cursory visual evaluation. Noted hazardous materials were individually tallied. Actual quantities may vary significantly, especially if certain areas were not accessible. RMEC shall not be held liable for differences in actual versus estimated quantities.
1.4 Reliance
This report has been prepared for the sole use of the person(s) or entity(ies) listed below and only represents conditions within the project area that were present at the time this survey was completed.
• Utah Division of Facilities Construction and Management (DFCM)
This report may not be relied upon by any other person(s) or entity(ies) without the express written consent of RMEC Environmental, LLC. and the above-listed parties. Any use of the contents of this report by any other third party is at the sole risk of that party. Further, contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation, as necessary.
PJ26A-5735 Page 3
2.0 INSPECTION ACTIVITIES
2.1 Credentials
This survey was completed by the following qualified RMEC personnel:
Name Credential Information
Mackenzie Hobbs State of Utah Asbestos Certification – Inspector Certification #: ASB-7699 (expires 04/09/2027)
Benjamin Lambert State of Utah Asbestos Certification – Inspector Certification #: ASB-9061 (expires 06/10/2027)
In addition to the personal certification listed above, it should be noted that RMEC Environmental, LLC. is a Certified Asbestos Company (ASBC-325) with the Utah Department of Environmental Quality – Division of Air Quality (UDEQ-DAQ).
2.2 Field Activities
The asbestos portion of this limited pre-renovation survey was conducted in general accordance with the sampling and collection protocols established in the Asbestos Hazard Emergency Response Act (AHERA) standard (located at 40 CFR 763.86) for asbestos sampling.
The hazardous materials inventory includes items that, in addition to ACM and lead, would contribute to regulated debris or emissions during the renovation process. Those materials could also be regulated by state-level or federal regulations as hazardous wastes under certain circumstances if removed.
RMEC completed the on-site survey and walkthrough of the project area on the following dates:
• July 28, 2026
Site photographs of suspect ACBM samples or other relevant features are included in Appendix C of this report.
2.2.1 Visual Assessment
RMEC commenced the survey by conducting a visual assessment for suspect ACBM and potential LCP. Homogeneous areas consisting of similar building materials (including texture and color) with similar histories were identified and recorded for the sampling of suspect ACBM.
All other hazardous materials were visually inventoried only. A summary of those inventoried materials is presented in Table B in Appendix A of this report.
2.2.2 Suspect ACBM Physical Assessment
All homogeneous areas of suspect ACBM were assessed to determine whether they were friable or significantly damaged. “Friable” is defined as being able to be crumbled, pulverized, or reduced to powder by hand pressure when dry. A determination of friability is done by physically touching the suspect material.
PJ26A-5735 Page 4
2.2.3 Suspect ACBM Sample Collection
Based on the visual and physical assessments discussed previously in Sections 2.2.1 and 2.2.2, RMEC collected bulk samples of suspect ACBM. Where possible, sample locations were selected at random and intended to be representative of the entire applicable material.
Once homogeneous areas were identified, bulk samples were collected to confirm the presence or absence of asbestos in suspect materials. During sample collection, RMEC attempted to minimize the potential for the release of asbestos fibers, including using wet methods, where necessary.
Frequency of sampling was based on observations at the site (i.e., friability and total quantity) and assumptions made regarding whether observed materials were homogeneous.
Specific details about each of the collected bulk samples are listed in Table A of Appendix A.
2.2.4 Coatings Sample Collection to Identify Lead Containing Paint
To determine the presence of lead-containing paint (LCP), RMEC identified each painted/coated surface in the project area that were suspected of having differing painting histories.
RMEC utilized a hand-held SciAps Inc. Model X550Pb X-Ray Fluorescence (XRF) device to sample all suspect painted/coated surfaces in the project area. An XRF provides immediate results for each sampled material using non-destructive testing methods and allows for all unique components and substrates to be sampled. Surfaces were measured according to component type, substrate, and the presence of a potential source of LCP.
Specific details and results for each XRF reading are listed in Table C of Appendix A.
2.3 Sample Analysis
Asbestos samples were submitted under chain of custody to Eurofins Reservoirs Environmental, Inc.
Denver (Eurofins) of Arvada, Colorado for laboratory analysis. Eurofins is accredited by the American Industrial Hygiene Association (AIHA) and the National Institute of Standards and Technology (NIST) under the National Voluntary Laboratory Accreditation Program (NVLAP). Details about Eurofin’s accreditations are included in the analytical report attached in Appendix B of this report.
Samples were analyzed by Polarized Light Microscopy (PLM) visual estimation methodology, using the method specified in Appendix E, Subpart E of 40 CFR 763. For samples with a limited detection of asbestos—including those that meet the regulatory definition of a “wall system”—a point count methodology was requested to determine whether that material should be considered ACM (see Section
2.4 of this report). All bulk samples and their associated analytical results are summarized in Table A of Appendix A.
2.4 Regulatory Overview
The information provided below is a summary and not intended to be inclusive of all potentially pertinent regulatory information. Please note that the standards discussed hereafter should be reviewed and verified separately prior to demolition and renovation activities.
There are separate definitions for the various types of ACM, as classified by the U.S. Environmental Protection Agency (EPA). Asbestos is included in the National Emission Standards for Hazardous Air
PJ26A-5735 Page 5
Pollutants (NESHAP) standard—located in 40 CFR Part 61, Subpart M—under the Clean Air Act (CAA).
NESHAP regulates asbestos fiber emissions and asbestos waste disposal practices. The NESHAP regulation also requires determinations regarding friability of existing ACM prior to demolition or renovation activities. ACM is defined as any building material containing more than 1% asbestos (as determined by PLM or other approved analytical methods).
As mentioned previously, all ACM is physically evaluated to determine whether it is “friable.” Non-friable ACM is any material that contains more than 1% asbestos (again, as determined by an approved analytical method) that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure. There are two different categories for non-friable ACM:
Category I Non-Friable ACM means asbestos-containing packings, gaskets, resilient floor covering (commonly known as vinyl asbestos tile [VAT]) and asphalt roofing products, as determined by PLM.
Asbestos-containing mastic is also considered Category I non-friable ACM. These materials rarely become friable and are assumed to remain non-friable if demolition or renovation is performed using “normal” methods, but will become friable if severely weathered, sanded, or abraded. Category I materials which are not in poor condition and not friable prior to demolition or renovation do not have to be removed, except where demolition will be by intentional burning.
Category II Non-Friable ACM means any other “non-friable” material that does not meet the Category I non-friable ACM category described above. Category II materials may not need to be removed depending upon the quantity and probability of that material becoming friable during demolition or renovation.
On the other hand, friable ACM is always considered to be a regulated ACM (or RACM). All materials that are deemed to be RACM must be removed prior to demolition or renovation. In addition to friable ACM, RACM is defined in the NESHAP standard to include:
• Category I non-friable ACM that has become friable.
• Category I non-friable ACM that will be or has been subject to sanding, cutting, or abrading.
• Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation activities.
In Utah, asbestos regulations are defined in Utah Administrative Code (UAC) R307-801, Utah Asbestos Rule. This rule, as well as the associated state-level NESHAP program, is managed by the Utah Department of Environmental Quality (UDEQ) Division of Air Quality (DAQ). Of note, the federal NESHAP program, found at 40 CFR 61 Subpart M, is adopted by reference in UAC R307-214-1. Per the Asbestos NESHAP regulation, only friable ACM is required to be abated prior to demolition or renovation activities.
It should also be noted that the U.S. Occupational Safety and Health Administration (OSHA) has a construction standard (29 CFR 1926.1101) that regulates workplace exposures to asbestos. That standard requires that employee exposures to airborne asbestos not exceed 0.1 fibers per cubic centimeter of air (0.1 f/cc) as an eight-hour time-weighted average (TWA). In addition, worker exposures to airborne asbestos is not to exceed 1.0 f/cc over a 30-minute time period—this is known as an excursion limit (EL). Both the TWA and EL are considered to be permissible exposure limits (PELs) under the OSHA standard. Other specific work practices and precautions that must be followed during construction and maintenance activities—specifically, those that could disturb ACM—are defined in the OSHA standard relative to each class of regulated work.
PJ26A-5735 Page 6
Additionally, lead is regulated by both U.S. Environmental Protection Agency (EPA) and OSHA, and certain detectable quantities of lead may constitute a hazardous waste by EPA or a lead dust hazard during demolition or renovation (e.g., construction) activities by OSHA.
The EPA has the authority to regulate the waste status of demolition or renovation debris, including lead-containing materials. Specific requirements that must be addressed include potential notification and testing prior to transporting, treatment, storing, or disposal. For example, debris is hazardous if a Toxicity Characteristic Leachate Procedure (TCLP) analytical result is above 5.0 parts per million (ppm) for lead.
Of note, the aggregate of construction debris, which would include both the paint itself as well as any debris (such as drywall and other building materials) would typically render the overall lead quantity to fall well below the 5.0-ppm hazardous waste threshold using TCLP. Therefore, LCP is rarely considered for waste disposal when done in bulk. Conversely, LCP separated from its substrate may be considered hazardous waste.
According to OSHA, a lead dust hazard must be evaluated prior to demolition or renovation activities that would disturb LCP of any detectable concentration. Per OSHA regulations (see 29 CFR 1926.62), if lead is detected above the laboratory analytical detection limit in any amount, efforts must be made to minimize employee exposures. The OSHA standards also stipulate how painted components or other building surfaces with detectable lead quantities should be safely handled. Ultimately, employers must ensure that no employee is exposed to lead concentrations above 50 micrograms per cubic meter of air (μg/m3) over an eight-hour period without adequate protection. There is also an action level of 30 μg/m3 that, if exceeded, triggers medical monitoring requirements.
3.0 RESULTS/DISCUSSION
The following sub-sections detail the findings from RMEC’s limited on-site pre-renovation survey.
3.1 Asbestos Findings
Table A in Appendix A provides a summary of all bulk samples collected as part of this limited pre-renovation survey. A summary of the bulk samples collected is provided below in Table 3.1.
Table 3.1 – Summary of RMEC Bulk Samples
Total Number of Suspect ACBM Bulk Samples Collected: 27
Total Number of Homogeneous Areas (HA) Represented: 12
Total Number of Suspect ACBM Confirmed to be ACM: 0
Total Number of ACM Confirmed to be RACM: 0
Please refer to Section 4.0 of this report for any recommendations related to materials containing asbestos.
PJ26A-5735 Page 7
3.1.1 Inaccessible Areas or Unsampled Materials
There were no notable inaccessible rooms encountered during this inspection. Many asbestos containing materials are located in concealed areas such as wall cavities, below ground level and other hidden spaces. Since RMEC has been contracted to conduct a limited asbestos survey, it is understood that RMEC will minimize its impact during the investigation. As such, if there are concerns with locating any of these hidden materials, RMEC and DFCM would need to agree on the level of destruction necessary to correctly identify or rule out the presence of these hidden materials. This survey was conducted in an occupied area; therefore, minimally destructive methods were used to identify potential asbestos containing materials.
If any other suspect building materials are encountered during demolition or renovation activities and are found to be different than those that were already sampled (see Table A in Appendix A), they should be immediately sampled for asbestos by a qualified inspector.
3.2 LCP Findings
RMEC took a total of nine (9) XRF readings from within the project area. Table C in Appendix A provides a summary of all the collected XRF readings and their results.
To summarize, XRF readings ranged from 0.00 to 0.06 mg/cm2 within the maintenance storage room.
Because this paint was determined to have detectable levels of lead, this meets the OSHA definition of
LCP.
Of note, 1.0 mg/cm2 (used to define “lead-based paint” under EPA regulations) is presented in Table C in Appendix A as a benchmark reference point for comparing observed results with a known standard;
however, that threshold does not apply to this property—further, as discussed in Section 2.4, there is no minimum allowable lead content under OSHA.
PJ26A-5735 Page 8
4.0 RECOMMENDATIONS
Asbestos Recommendations
Based on the work completed as part of this limited survey, RMEC has determined that there are no ACM (including RACM) present in the anticipated project area.
If further demolition or renovation activities are planned for the property—specifically, outside the area inspected as part of this limited pre-renovation asbestos survey—RMEC recommends that a separate asbestos inspection be completed for those applicable areas or structures.
Lead Recommendations
For surfaces where lead has been detected in any amount, OSHA requirements (see 29 CFR 1926.62) and best management practices (BMPs) should be followed to prevent lead exposures to workers during renovation or salvaging (if applicable) activities.
In the event that DFCM employees use manual renovation practices around LCP, RMEC recommends the following additional provisions:
• Utilize dust suppression activities such as wetting surfaces prior to disturbance, or dust collection at the point of generation.
• Certain BMPs should be undertaken and can be found at the EPA’s Lead Renovation, Repair and Painting Program, found at https://www.epa.gov/lead/renovation-repair-and-painting-program-contractors.
• Should lead containing paint control activities not be undertaken, OSHA would require that employers perform an assessment to determine employee exposures to lead during activities that disturb any significant amount of lead (see 29 CFR 1926.62).
Hazardous Materials Recommendations
As listed in Table B in Appendix A, two (2) types of hazardous materials were noted in the planned renovation area. As needed, all identified hazardous materials should be properly handled (removed) and disposed of according to local, regional, state, and/or national regulations before commencing any activities that might disturb them. Also, the local health department with jurisdiction over the property may require proof of proper disposal of hazardous materials prior to demolition activities.
Other Recommendations
Finally, please note that this report is required to be kept on-site during any and all demolition or renovation activities associated with the project area and shall also be made available to all persons who have access to the site during those activities.
RMEC also recommends that this report be kept on file for at least five (5) years after those activities are completed and can be made available to any regulatory agency. For asbestos samples collected as part of this survey, if demolition/renovation work on those associated building materials is not completed in the project area within three (3) years, this report should be updated by a certified asbestos inspector if any subsequent work will need to rely on the results herein.
https://www.epa.gov/lead/renovation-repair-and-painting-program-contractors https://www.epa.gov/lead/renovation-repair-and-painting-program-contractors
APPENDIX A
RMEC INSPECTION SUMMARY TABLE(S)
Table B: Hazardous Materials Inventory
Material Type Quantity Area Approx.
Location Comments
Regulated by EPA as Universal Waste
Fluorescent Light Tubes & Bulbs ~225 Throughout
Project Area
Ceiling Light Fixtures and Mechanical
Room Storage
Fluorescent bulbs were noted near VAV boxes and stored in the mechanical room. All appeared to be intact and in good shape.
Fluorescent Lamp Ballasts ~75 Throughout
Project Area
Ceiling Light Fixtures and Mechanical
Room Storage
NOTE: Lamp Ballasts that were inspected did not contain PCBs.
Batteries None
Mercury Thermostat None
Equipment Containing Chlorofluorocarbons (CFCs)
Refrigerators (refrigerants) None
Drinking Fountains (refrigerants) None
Air Conditioners (refrigerants) None
Other Potential Hazardous Materials
None
Table A: RMEC Suspect ACBM Bulk Samples Analysis Summary
HA No. Sample Number Material Description Sample Location
HA
Estimated Quantity
(ft2)
Asbestos Analytical
Result
RM01
RM01-01 White Roofing Material RTU Stand 20 None Detected
RM01-02 White Roofing Material RTU Stand 20 None Detected
CK01
CK01-01 White Caulk RTU Piping 2 None Detected
CK01-02 White Caulk RTU Piping 2 None Detected
CN01
CN01-01 Gray Concrete Pump Mount 15 None Detected
CN01-02 Gray Concrete B-2 Boiler Mount 15 None Detected
MP01
MP01-01 White Mud Packing Pump Piping 5 None Detected
MP01-02 White Mud Packing B-2 Boiler Piping 5 None Detected
MP01-03 White Mud Packing B-1 Boiler Piping 5 None Detected
DC01
DC01-01 White Ducting Material B-1 Boiler 10 LF None Detected
DC01-02 White Ducting Material B-1 Boiler 10 LF None Detected
IN01
IN01-01 White Paper Wrap on Fiberglass Insulation B-1 Boiler Piping 50 LF None
Detected
IN01-02 White Paper Wrap on Fiberglass Insulation Pump Piping 50 LF None
Detected
IN01-03 White Paper Wrap on Fiberglass Insulation Near FD6 VAV Box 50 LF None
Detected
IN02
IN02-01 White Fabric Wrap on Fiberglass Insulation B-1 Boiler 5 LF None
Detected
IN02-02 White Fabric Wrap on Fiberglass Insulation B-2 Boiler 5 LF None
Detected
GK01 GK01-01 Black/Orange Gasket Pump Gasket 2 None Detected
HA No. Sample Number Material Description Sample Location
HA
Estimated Quantity
(ft2)
Asbestos Analytical
Result
GK01-02 Black/Orange Gasket Pump Gasket 2 None Detected
GK02
GK02-01 Black Gasket B-2 Boiler 2 None Detected
GK02-02 Black Gasket B-1 Boiler 2 None Detected
CT01
CT01-01 White 2’ x 2’ Ceiling Tile with Pinholes 1st Floor near VV1 VAV Box 100 None
Detected
CT01-02 White 2’ x 2’ Ceiling Tile with Pinholes 2nd Floor near FD6 VAV Box 100 None
Detected
DS01
DS01-01 Gray Duct Sealant 1st Floor near VV1 VAV Box 50 LF None Detected
DS01-02 Gray Duct Sealant 2nd Floor near FD6 VAV Box 50 LF None Detected
W01
W01-01 Textured Drywall with Mud & Tape
Mechanical Room – Near Entrance 250 None
Detected
W01-02 Textured Drywall with Mud & Tape
Mechanical Room – Near Water Heater 250 None
Detected
W01-03 Textured Drywall with Mud & Tape
Mechanical Room – Above Entrance 250 None
Detected
HA = Homogeneous Area LF = Linear Feet a Quantity is presented in relation to the planned project area Values in Italics contain detectable amounts of asbestos, but are not regulated by the EPA.
Values in bold are considered to be ACM.
Values in red are considered to be RACM based on their composition, classification, and physical conditions.
APPENDIX B
ANALYTICAL RESULTS REPORT(S)
August 03, 2026
Sincerely, Jeanne Spencer President
Subcontractor Number:
Laboratory Report: RES 772181-1
Project #/P.O. #: PJ26A-5735
Project Description: DFCM, DWS Boiler Replacement
Mackenzie Hobbs Rmec Environmental, LLC 476 W 325 S Bountiful, UT 84010-7134
Dear Mackenzie, Eurofins Reservoirs is an analytical laboratory accredited for the analysis of Industrial Hygiene and Environmental matrices by the National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896-0 for Transmission Electron Microscopy (TEM) and Polarized Light Microscopy (PLM) analysis and the American Industrial Hygiene Association (AIHA LAP), Lab ID 101533 for Phase Contrast Microscopy (PCM) analysis. This laboratory is currently proficient in both Proficiency Testing and PAT programs respectively.
Eurofins Reservoirs has analyzed the following samples for asbestos content as per your request. The analysis has been completed in general accordance with the appropriate methodology as stated in the attached analysis table. The results have been submitted to your office.
RES 772181-1 is the job number assigned to this study. This report is considered highly confidential and the sole property of the customer. Eurofins Reservoirs will not discuss any part of this study with personnel other than those of the client. The results described in this report only apply to the samples analyzed, as received and with the information provided by the customer (i.e. sample volumes and areas). This report must not be used to claim endorsement of products or analytical results by NVLAP or any agency of the U.S. Government. This report shall not be reproduced except in full, without written approval from Eurofins Reservoirs. Samples will be disposed of after sixty days unless longer storage is requested. If you have any questions about this report, please feel free to call 303-964-1986.
by Camryn Baumgartner
08/03/202608/03/202608/03/202608/03/2026
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
4955 Yarrow St, Suite 100, Arvada, CO 80002
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non- AAAA SubSubSubSub AsbestosAsbestosAsbestosAsbestos FibrousFibrousFibrousFibrous YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%) 772181 -772181 -772181 -772181 - RM01-01RM01-01RM01-01RM01-01 A Tan adhesive 3 NDNDNDND 0 100.0 B White/gray resinous material w/ white fibrous woven material
97 NDNDNDND 12 88.0
772181 -772181 -772181 -772181 - RM01-02RM01-02RM01-02RM01-02 A White/gray resinous material w/ white fibrous woven material
100 NDNDNDND 8 92.0
772181 -772181 -772181 -772181 - CK01-01CK01-01CK01-01CK01-01 A White/gray caulk 100 NDNDNDND 0 100.0 772181 -772181 -772181 -772181 - CK01-02CK01-02CK01-02CK01-02 A White caulk 100 NDNDNDND 0 100.0 772181 -772181 -772181 -772181 - CN01-01CN01-01CN01-01CN01-01 A Gray granular cementitious material 100 NDNDNDND 0 100.0 772181 -772181 -772181 -772181 - CN01-02CN01-02CN01-02CN01-02 A Gray granular cementitious material 100 NDNDNDND 0 100.0 772181 -772181 -772181 -772181 - MP01-01MP01-01MP01-01MP01-01 A White sealant 15 NDNDNDND 0 100.0 B Yellow insulation 85 NDNDNDND 90 10.0 772181 -772181 -772181 -772181 - MP01-02MP01-02MP01-02MP01-02 A White sealant 10 NDNDNDND 0 100.0 B Yellow insulation 90 NDNDNDND 90 10.0 772181 -772181 -772181 -772181 - MP01-03MP01-03MP01-03MP01-03 A White sealant 12 NDNDNDND 0 100.0 B Yellow insulation w/ white/silver wrap 88 NDNDNDND 85 15.0 772181 -772181 -772181 -772181 - DC01-01DC01-01DC01-01DC01-01 A Tan/gray insulation w/ white wrap & white coating 100 NDNDNDND 25 75.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
772181-1 Rmec Environmental, LLC
PJ26A-5735
DFCM, DWS Boiler Replacement 5633 July 29, 2026 EPA 600/R-93/116 - Short Report, Bulk Standard August 03, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%) 772181 -772181 -772181 -772181 - DC01-02DC01-02DC01-02DC01-02 A Tan/gray insulation w/ white wrap & white coating 100 NDNDNDND 25 75.0 772181 -772181 -772181 -772181 - IN02-01IN02-01IN02-01IN02-01 A White sealant 5 NDNDNDND 0 100.0 B Yellow insulation w/ white/silver wrap 95 NDNDNDND 80 20.0 772181 -772181 -772181 -772181 - IN02-02IN02-02IN02-02IN02-02 A White sealant 7 NDNDNDND 0 100.0 B Yellow insulation w/ white/silver wrap 93 NDNDNDND 80 20.0 772181 -772181 -772181 -772181 - GK01-01GK01-01GK01-01GK01-01 A Red gasket 45 NDNDNDND 0 100.0 B Black gasket 55 NDNDNDND 0 100.0 772181 -772181 -772181 -772181 - GK01-02GK01-02GK01-02GK01-02 A Red gasket w/ black debris 100 NDNDNDND 0 100.0 772181 -772181 -772181 -772181 - GK02-01GK02-01GK02-01GK02-01 A Black/silver gasket 100 NDNDNDND 5 95.0 772181 -772181 -772181 -772181 - GK02-02GK02-02GK02-02GK02-02 A Black/silver gasket 100 NDNDNDND 5 95.0 772181 -772181 -772181 -772181 - CT01-01CT01-01CT01-01CT01-01 A White/tan ceiling tile 100 NDNDNDND 60 40.0 772181 -772181 -772181 -772181 - CT01-02CT01-02CT01-02CT01-02 A White/tan ceiling tile 100 NDNDNDND 60 40.0 772181 -772181 -772181 -772181 - DS01-01DS01-01DS01-01DS01-01 A Gray/silver sealant 100 NDNDNDND 0 100.0 772181 -772181 -772181 -772181 - DS01-02DS01-02DS01-02DS01-02 A Gray/silver sealant 100 NDNDNDND 0 100.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
772181-1 Rmec Environmental, LLC
PJ26A-5735
DFCM, DWS Boiler Replacement 5633 July 29, 2026 EPA 600/R-93/116 - Short Report, Bulk Standard August 03, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%)
772181 -772181 -772181 -772181 - W01-01W01-01W01-01W01-01 A Cream tape 5 NDNDNDND 95 5.0 B White texture w/ gray paint 8 NDNDNDND 0 100.0 C White joint compound 10 NDNDNDND 0 100.0 D Tan/pink drywall 77 NDNDNDND 10 90.0 772181 -772181 -772181 -772181 - W01-02W01-02W01-02W01-02 A Cream tape 7 NDNDNDND 95 5.0 B White texture w/ gray paint 10 NDNDNDND 0 100.0 C White joint compound 13 NDNDNDND 0 100.0 D Tan/pink drywall 70 NDNDNDND 15 85.0 772181 -772181 -772181 -772181 - W01-03W01-03W01-03W01-03 A Cream tape 6 NDNDNDND 95 5.0 B White joint compound 10 NDNDNDND 0 100.0 C White texture w/ gray paint 12 NDNDNDND 0 100.0 D Tan/pink drywall 72 NDNDNDND 15 85.0 772181 -772181 -772181 -772181 - IN01-01IN01-01IN01-01IN01-01 A Yellow insulation w/ off-white/multi-colored wrap 100 NDNDNDND 85 15.0 772181 -772181 -772181 -772181 - IN01-02IN01-02IN01-02IN01-02 A Yellow insulation w/ off-white/multi-colored wrap 100 NDNDNDND 85 15.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
772181-1 Rmec Environmental, LLC
PJ26A-5735
DFCM, DWS Boiler Replacement 5633 July 29, 2026 EPA 600/R-93/116 - Short Report, Bulk Standard August 03, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%)
772181 -772181 -772181 -772181 - IN01-03IN01-03IN01-03IN01-03 A White sealant 3 NDNDNDND 0 100.0 B Yellow insulation 97 NDNDNDND 90 10.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Liu Wenlong Analyst
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
772181-1 Rmec Environmental, LLC
PJ26A-5735
DFCM, DWS Boiler Replacement 5633 July 29, 2026 EPA 600/R-93/116 - Short Report, Bulk Standard August 03, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
SUBMITTED BY INVOICE TO
Client Sample ID Number
RES Job #: 772181
CONTACT INFORMATION SERIES
ASBESTOS LABORATORY REQUESTED ANALYSIS VALID MATRIX CODES LAB NOTES
CHEMISTRY LABORATORY
MICROBIOLOGY LABORATORY
**Turnaround times establish a laboratory priority, subject to laboratory volume and are not guaranteed. Additional fees apply for afterhours, weekends and holidays.**
Laboratory Analysis Instructions
(Sample ID's must be unique)
Company: Rmec Environmental, LLC Company: Rmec Environmental, LLC
Address: 476 W 325 S Address: 476 W 325 S
Bountiful, UT 84010-7134 Bountiful, UT 84010-7134
Project Number and/or P.O. #: PJ26A-5735 Project Zip Code: 84111
Project Description/Location: DFCM, DWS Boiler Replacement 5633
Contact: Mackenzie Hobbs -1 PLM Standard Phone: (801) 467-3661
Fax:
Cell: (801) 712-7182
Final Data Deliverable Email Address:
admin@rmec.net (+ 1 ADDNL. CONTACTS)
PLM / PCM / TEM / NYS DTL RUSH PRIORITY STANDARD Air = A Bulk = B
Dust = D Food = F
Paint = P Soil = S
Dust RUSH PRIORITY STANDARD
*PRIOR NOTICE REQUIRED FOR SAME DAY TAT
Surface = SU Swab = SW
Tape = T Wipe = W
Metals RUSH PRIORITY STANDARD Drinking Water = DW
Waste Water = WW
Organics* SAME DAY RUSH PRIORITY STANDARD **ASTM E1792 approved wipe media only**
Viable Analysis** PRIORITY STANDARD
**TAT DEPENDENT ON SPEED OF MICROBIAL GROWTH
Medical Device Analysis RUSH STANDARD
Mold Analysis RUSH PRIORITY STANDARD
Special Instructions:
PC anything above trace, less than 5%. Positive Stop.
ASBESTOS CHEMISTRY MICROBIOLOGY ICO
1 RM01-01 X B
2 RM01-02 X B
3 CK01-01 X B
4 CK01-02 X B
5 CN01-01 X B
6 CN01-02 X B
7 MP01-01 X B
8 MP01-02 X B
9 MP01-03 X B
10 DC01-01 X B
11 DC01-02 X B
12 IN02-01 X B
13 IN02-02 X B
P L
M
P L
M S h o rt R ep o rt (E
PA
/6
/R
-9 3/
6)
T E
M
P C
M
N Y
S
D U
S T
M E
TA
L
S
O R
G A
N
IC
S
V
IA
B L
E S
M E
D
IC
A L
M O
L D
S am pl e
V ol um e
(L
A re a
S am pl e
Te m pe ra tu re
C
Le ng th (o r A liq uo ts
) x W id th
(o r A re a/
A liq uo t)
M at rix C od e of
C on ta in er s
D at e C ol le ct ed m m
/d d/ yy
T im e C ol le ct ed hh :m m
Eurofins Reservoirs Environmental, Inc establishes a unique Lab Sample ID, for each sample, by preceding each unique Client Sample ID with the laboratory RES Job Number.
Eurofins Reservoirs Environmental, Inc will analyze incoming samples based on information received and will not be responsible for errors or omissions in calculations resulting from the inaccuracy of original data. By signing, client/company representative agrees that submission of the following samples for requested analysis as indicated on this Chain of Custody shall consitute an analytical services agreement with payment terms of COD. Failure to comply with payment terms may result in a 18% APR finance charge.
Relinquished By:
Mackenzie Hobbs Date/Time: 07/28/2026 15:40:52 Sample Condition: Acceptable
Received By:
Kennedy White Date/Time: 07/29/2026 11:04:16 Carrier: Fed-Ex
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Client Sample ID Number
REQUESTED ANALYSIS VALID MATRIX CODES LAB NOTES
Laboratory Analysis Instructions
(Sample ID's must be unique)
Air = A Bulk = B
Dust = D Food = F
Paint = P Soil = S
Surface = SU Swab = SW
Tape = T Wipe = W
Drinking Water = DW
Waste Water = WW
**ASTM E1792 approved wipe media only**
RES Job #: 772181
Submitted By: Rmec Environmental, LLC
ASBESTOS CHEMISTRY MICROBIOLOGY ICO
14 GK01-01 X B
15 GK01-02 X B
16 GK02-01 X B
17 GK02-02 X B
18 CT01-01 X B
19 CT01-02 X B
20 DS01-01 X B
21 DS01-02 X B
22 W01-01 X B
23 W01-02 X B
24 W01-03 X B
25 IN01-01 X B
26 IN01-02 X B
27 IN01-03 X B
P L
M
P L
M S h o rt R ep o rt (E
PA
/6
/R
-9 3/
6)
T E
M
P C
M
N Y
S
D U
S T
M E
TA
L
S
O R
G A
N
IC
S
V
IA
B L
E S
M E
D
IC
A L
M O
L D
S am pl e
V ol um e
(L
A re a
S am pl e
Te m pe ra tu re
C
Le ng th (o r A liq uo ts
) x W id th
(o r A re a/
A liq uo t)
M at rix C od e of
C on ta in er s
D at e C ol le ct ed m m
/d d/ yy
T im e C ol le ct ed hh :m m
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Client Sample ID Sample Note Quantity Sampler(s)
RM01-01 White Roofing Material
RM01-02 White Roofing Material
CK01-01 White Caulk
CK01-02 White Caulk
CN01-01 Gray Concrete
CN01-02 Gray Concrete
MP01-01 White Mud Packing
MP01-02 White Mud Packing
MP01-03 White Mud Packing
DC01-01 White Ducting
DC01-02 White Ducting
IN02-01 White Fabric Wrap on Fiberglass Insulation
IN02-02 White Fabric Wrap on Fiberglass Insulation
GK01-01 Orange/Black Gasket
GK01-02 Orange/Black Gaskets
GK02-01 Black Gasket
GK02-02 Black Gasket
CT01-01 White 2x2 Ceiling Tile with Pinholes
CT01-02 White 2x2 Ceiling Tile with Pinholes
DS01-01 Gray Duct Sealant
DS01-02 Gray Duct Sealant
W01-01 Textured Drywall w/ Mud & Tape
W01-02 Textured Drywall w/ Mud & Tape
W01-03 Textured Drywall w/ Mud & Tape
IN01-01 White Paper Wrap on Fiberglass Insulation
IN01-02 White Paper Wrap on Fiberglass Insulation
Rmec Environmental, LLC Sample Notes
RES #: 772181
Project Number and/or P.O. #: PJ26A-5735
IN01-03 White Paper Wrap on Fiberglass Insulation
Rmec Environmental, LLC Sample Notes
RES #: 772181
Project Number and/or P.O. #: PJ26A-5735
APPENDIX C
SITE PHOTOGRAPHS
PRE-RENO SURVEY PHOTO LOG Inspection Date: July 28, 2026 Site Address: 720 S. 200 East, Salt Lake City, Utah 84111 Salt Lake City DWS 5633
RMEC Environmental, LLC. PJ26A-5735
Sample ID: RM01-01
Sample Description: White Roofing Material
Sample Location: RTU Stand
Note: This bag was relabeled as “RM01-01” before sample submittal
Sample ID: RM01-02
Sample Description: White Roofing Material
Sample Location: RTU Stand
Note: This bag was relabeled as “RM01-02”
Sample ID: CK01-01
Sample Description: White Caulk
Sample Location: RTU Piping
Sample ID: CK01-02
Sample Description: White Caulk
Sample Location: RTU Piping
Sample ID: CN01-01
Sample Description: Gray Concrete
Sample Location: Pump Mount
Sample ID: CN01-02
Sample Description: Gray Concrete
Sample Location: B-2 Boiler Mount
Sample ID: MP01-01
Sample Description: White Mud Packing
Sample Location: Pump Piping
Sample ID: MP01-02
Sample Location: B-2 Boiler Piping
Sample ID: MP01-03
Sample Location: B-1 Boiler Piping
Sample ID: DC01-01
Sample Description: White Ducting Material
Sample Location: B-1 Boiler
Note: This bag was relabeled as “DC01-01”
Sample ID: DC01-02
Sample Description: White Ducting Material
Sample Location: B-1 Boiler
Note: This bag was relabeled as “DC01-02”
Sample ID: IN01-01
Sample Description: White Paper Wrap on Fiberglass Insulation
Sample Location: B-1 Boiler Piping
Sample ID: IN01-02
Sample Location: Pump Piping
Sample ID: IN01-03
Sample Location: Near FD6 VAV Box
Sample ID: IN02-01
Sample Description: White Fabric Wrap on
Sample Location: B-1 Boiler
Sample ID: IN02-02
Sample Description: White Fabric Wrap on
Sample Location: B-2 Boiler
Sample ID: GK01-01
Sample Description: Black/Orange Gasket
Sample Location: Pump Gasket
Sample ID: GK01-02
Sample Description: Black/Orange Gasket
Sample Location: Pump Gasket
Sample ID: GK02-01
Sample Description: Black Gasket
Sample Location: B-2 Boiler Gasket
Sample ID: GK02-02
Sample Description: Black Gasket
Sample Location: B-1 Boiler Gasket
Sample ID: CT01-01
Sample Description: White 2’ x 2’ Ceiling Tile with Pinholes
Sample Location: 1st Floor near VV1 VAV Box
Sample ID: CT01-02
Sample Description: White 2’ x 2’ Ceiling Tile with Pinholes
Sample Location: 2nd Floor near FD6 VAV Box
Sample ID: DS01-01
Sample Description: Gray Duct Sealant
Sample Location: 1st Floor near VV1 VAV Box
Sample ID: DS01-02
Sample Description: Gray Duct Sealant
Sample Location: 2nd Floor near FD6 VAV Box
Sample ID: W01-01
Sample Description: Textured Drywall with Mud & Tape
Sample Location: Mechanical Room – Near Entrance
Sample ID: W01-02
& Tape
Sample Location: Mechanical Room – Near Water Heater
Sample ID: W01-03
& Tape
Sample Location: Mechanical Room – Above Entrance
M
M
P
T
S
PS
IBT
T
TT
F&T
F
MECHANICAL LEGEND
SYMBOL ABR, DESCRIPTION
GENERAL TERMINOLOGY
A
ME101
SECTION LETTER DESIGNATION
SECTION DRAWN ON THIS SHEET
A2
AH
DETAIL NUMBER DESIGNATION
CORRESPONDING WITH GRID
LOCATION
MECHANICAL EQUIPMENT DESIGNATION
EQUIPMENT ITEM DESIGNATION
REGISTER,…