392 Patton Jr High School Mech Schedules.pdf

PDF 3 MB Posted

Attached to
Amendment 01 Fire Alarm Repairs & Replacement Bldg. 392 Ft Leavenworth Federal contract opportunity
Solicitation number
W91QF4-25-B-A005
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort Eustis

About this file

This document is a detailed Mechanical Schedules file for Patton Junior High School, containing comprehensive technical specifications for HVAC, ventilation, rooftop units, registers, grilles, diffusers, ductwork insulation, and other mechanical systems. The schedules provide exhaustive technical details including equipment manufacturers (Lennox, McQuay, Greenheck, Krueger), model numbers, performance specifications, airflow rates, cooling/heating capacities, electrical requirements, and installation notes for various mechanical components across different building zones such as classrooms, offices, kitchen, and mechanical rooms.

The schedules include specific technical requirements like vibration isolation, microprocessor controllers, refrigeration circuits, air handling specifications, and compliance with various technical standards. Equipment types covered include rooftop HVAC units, split system units, exhaust fans, kitchen hood systems, unit heaters, domestic hot water heaters, and circulation pumps. Each equipment entry includes detailed specifications such as airflow (CFM), temperature conditions, electrical ratings, manufacturer model numbers, and specific installation remarks, providing a comprehensive technical blueprint for the mechanical systems of the school facility.

View the file

Other files for this federal contract opportunity

Other files attached to Amendment 01 Fire Alarm Repairs & Replacement Bldg. 392 Ft Leavenworth, newest first.
File Type Posted
Q As W91QF4-25-B-A005 Fire Alarm_DPW Answers.pdf PDF
SOW_Bldg 392 and 339 Fire Alarm Repair.pdf PDF
Wage Determintation_Building_KS20250053_20250516.pdf PDF
2840__Abase1RCP_Fire Alarm devices-Layout1.pdf PDF
Comm Room Pic 2.jpg JPG image
Comm Room Pic 1.jpg JPG image
Old Patton Floor Plan - Sprinkled vs Non Areas.pdf PDF
Solicitation - W91QF425BA005_B392_B339 Fire Alarms.pdf PDF
Old Patton Floor Plan - Sprinkled vs Non Areas - Ceiling Heights.pdf PDF
B339 Remodel for WIT July 2008.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPLACEMENT ROOFTOP HVAC UNIT SCHEDULE

MARK SERVES

TOTAL hN~ t IOU~~ CAP. MBH IL£A'IING AIR > CAP. MBH~ EXISTING MFG. & MANUFACTURER &

CFM TOTAL SENSIBLE DB (1') 1\B ("F) INPUT OUTPUT I MODEL NO. MODEL NO.

OFFlCE A107 2490 0.9 240 87.7 60.4 57.4 55.5 N/A N/A 26.1 5(~01 ' 1,2,3,5

SEC. A115 1200 0.6 240 36.3 26.9 59.1 57.2 N/A N/A 9.2 '

1.2.3,5

CLASSROOM 8100 1350 0.6 375 46.9 32.9 57.3 55.6 N/A N/A 12.9 • ,,£tJ:ci~~004 LENNOX 1,2,3,5

LCA04BH28

I '"s1o7· 1200 0.7 375 46.9 32.9 57.3 55.6 N/A N/A 12.9 I 1,2,3,5

I 's\oi 1350 N/A N/A I 0.6 375 46.9 32.9 57.3 55.6 12.9 48LDT ' 1,2.3,5 jRru-m I -.iii?' 1350 0.6 375 46.9 N/A N/A I 32.9 57.3 55.6 12.9 48LDT, ' 1,2,3,5

CLASSROOM 8112 1350 0.6 375 46.9 32.9 57.3 55.6 N/A N/A 12.9 48,£tJ:ci~~004 LENNOX 1,2.3,5

LCA04BH28

CLASSROOM 8111 1350 0.6 375 46.9 32.9 57.3 55.6 N/A N/A 12.9 48,£fJ:ci~~oo• 1,2,3,5

CLASSROOM 8113 1350 0.6 375 46 .9 32.9 57.3 55.6 N/A N/A 12.9 48LDT

I

1,2,3,5

,,_,, CLASSROOM 8115 1350 0.6 375 46.9 32.9 57.3 55.6 N/A N/A 12.9

I

1.2,3,5

CLASSROOM C102 1350 0.6 375 46.9 32.9 57.3 55.6 N/A N/A 12.9 48,£fJ:ci~~oo4 1,2,3,5

CLASSROOM C103 1350 0.6 375 46.9 32.9 57.3 55.6 N/A N/A 12.9 48LDT,

I 1,2,3.5

COORIDOR 8101 2000 0.6 375 61.5 46.1 58.5 57.1 125.0 100.0 14.7 I 1,2,3,5

STAGE 8117 1800 0.6 375 60.6 43.6 57.4 56.0 78.0 62.4 15.9 I

1,2,3,5

CLASSROOM 8145 1350 0.5 375 48.8 33.4 56.9 55.1 N/A N/A 14.7 YORK

1,2,3,5

CLASSROOM 8142 1400 0.5 375 47.2 33.4 57.7 56.0 125.0 100.0 12.4 I LENNOX 1,2,3,5

LGA04BH28

CLASSROOM 8142 1400 05 375 47.2 33.4 57.7 56.0 125.0 100.0 12.4 I 1,2,3,5

CLASSROOM 8132 1350 0.5 375 46.8 32.6 55.6 54.2 125.0 100.0 14.4 ~10 "

1,2,3,5

CLASSROOM 8141 1400 0.5 375 47.2 33.4 57.7 56.0 125.0 100.0 12.4 '

1,2,3,5

CLASSROOM 8137 1200 0.5 375 47.2 33.4 57.7 56.0 125.0 100.0 12.4 CARRIER 1,2,3,5

48HD005 310

CLASSROOM 8151 1350 0.5 375 46.8 33.4 56.9 55.1 N/A N/A 14.7 YORK 1,2,3,5

I CENTER C16 1990 0.5 270 61.5 46.0 58.5 57.0 125.0 100.0 15.3 :;;20 '

1,2,3,5

STORAGE C160 1990 0.5 270 61.5 46.0 58.5 57.0 125.0 100.0 15.3 1i2o ' 1,2,3,5

MUSIC C150 1990 0.5 270 61.5 46.0 58.5 57.0 125.0 100.0 15.3 LENNOX LENNOX 1, 4, 5

GCS16 652 LGA060H28

MUSIC C150 1990 0.5 270 61 .5 46.0 58.5 57.0 125.0 100.0 15.3 ccsis:.-652 1, 4, 5

CENTER C16• 1960 0.5 240 61.5 46.0 58.5 57.0 125.0 100.0 15.3 ~ '

1,2,3,5

I CENTER C160 1440 0.5 240 47.4 33.9 58.1 56.3 78.0 62.4 12.4 '

1,2,3,5

1. SEE MECHANICAL/ELECTRICAL COORDINATlON SCHEDULE FOR ELECTRICAL DATA.

2. FURNISH PRE-FABRICATED, INSULATED ADAPTER CURB TO MOUNT NEW UNIT ON EXISTING ROOF CURB.

3. COOLING AND DEHUMIDIFICATlON PERFORMANCE DATA BASED ON 105'F AMBIENT AIR TEMPERATURE, 80'f DB/67'f WB ENTERING AIR CONOITlONS.

4. PROVIDE PRE-FABRICATED, INSULATED ROOF CURB.

5. UNIT TO HAVE FACTORY INSTALLED LONMARK COMPLIANT MICROPROCESSOR CONTROLLER AND HOT GAS REHEAT DEHUMIDIFICATION CONTROL.

SEE SECTIONS 15782 AND 15985 FOR ADDITlONAL REQUIREMENTS.

MARK

UH 1,

UH-3

UH-4

CUH 1,

• 3.

REMARKS.

FAN AND HOOD SCHEDULE

MARK SERVICE TYPE CFM S.P. FAN DRIVE MAX. VARIABLE MANUFACTURER & REMARKS

RPM SONES CON'TROL MODEL NO.

EF-1 THRU 7 RESTROOMS

CEILING

75 0.25 700 DIRECT 3.0 GREENHECK

MOUNTED

SP 890

EF-8 GIRLS LOCKER ROOF MOUNTED

1455 1.0 1324 BELT 10.5

GREENHECK

ROOM CENTRIFUGAL

GB- 141

EF-9 BOYS LOCKER ROOF MOUNTED

1540 1.0 1344 BELT 11.0 GREENHECK

ROOM CENTRIFUGAL

GB 141

EF-10 KH-1 ROOF MOUNTED 2150 1.0 927 BELT

CAPTIVE AIR£

CENTRIFUGAL

NCA16FA

EF-11 KH-2 ROOF MOUNTED 2150 1.0 927 BELT

CAPTIVE AIR£

CENTRIFUGAL

NCA16FA

EF-12 DISH WASH ROOF MOUNTED 1340 1.0 1194 IREC

CAPTIVE AIR£

A129 CENTRIFUGAL

DU85HFA

EF- 13 FUME HOOO ROOF MOUNTED

1000 .75 1611 BELT 10.0

GREENHECK

A176 UPBLAST

CUBE 101

EF-14 FUME HOOO ROOF MOUNTED

1000 .75 1611 BELT 10.0

GREENHECK

A177 UPBLAST

CUBE 101

EF-15 & 16 CLOSET

CEILING 75 0.25 700 DIRECT 3.0 GREENHECK

MOUhUED

SP-B90

SF-1 BOILER IN LINE 1100 0.50 995 BELT 6.8 GREENHECK

ROOM CABINET FAN

BCF 108

KV-1 KILN KILN VENT 500 - 3450 IREC - - VENT-A-KILN

1.

A162 MODEL 1544, 44H~

IH-1 & 2 BOILER INTAKE HOOD - - - - GREENHECK

ROOM

FHI 36x18

REMARKS.

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. PROVIDE P!TCHED ROOF CURB 1'-0~ HEIGHT. VERIFY ROOF SLOPE W11H ARCHITECTURAL DRAWINGS.

3. THROAT SIZE TO BE 18" X 36~. PROVIDE 24H HIGH ROOF CURB. HOOD TO HAVE TI--lREE SQUARE FEET

MIN IMUM FREE AREA

4. INFORMATION REGARDING HOOD CAN BE OBTAINED FROM AIR-SIDE COMPONENTS IN OMAHA OR

VENT-A-KILN CORPORATION IN BUFFALO, NY. (716) 876-2023.

1. 2

1' 2

1. 5

1' 5

1' 5

1' 2

1. 2

4, 6

5. FANS AND CURBS PROVIDED BY FOOD SERVICE EQUIPMENT SUPPLIER (FSES), INSTALLED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR. INFORMATION GIVEN FOR COORDINATION PURPOSES ONLY- VERIFY MODEL

NUMBERS WITH (FSES).

6. PROVIDE GREENHECK GRS-12 ROOF CAP OR EQUAL

GAS FIRED MAKE-UP AIR UNIT SCHEDUlE (FURNISHED BY FOOD SERVICE EQUIPMENT SUPPUER)

MARK UNIT TYPE INPUT/ CFM TOTAL EXT. MANUFACTIJRER & REMARKS OUlPUT MBH S.P. S.P. MODEL NO.

MAU-1 DIRECT FIRED 222/204.3 3440 - .55 CAPTIVE AIR£

1, 2 NHMUA2.12

REMARKS.

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. MAKE-UP UNIT AND CURB FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER (FSES), INSTALLED BY

MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR INFORMATION GIVEN FOR COORDINATION

PURPOSES ONLY. VERIFY MODEL NUMBERS WITH (FSES).

CABINET AND UNIT HEATER SCHEDULE (HOT WATER)

TYPE ARRANGEMENT CFM HEATING GPM PO EXlERNAL FAN MANUFACTURER &

REM ARKS CAP. UBH FT. S.P. RPM MODEL NO.

UNIT HEATER HORIZONTAL 550 15.3 1.0 3.5 1550 McQUAY - 1. 2

UHH 02BB

UNIT HEATER HORIZONTAL 380 9.8 0.5 1.0 - 1550 McQUAY 1. 2

UHH 016B

UNIT HEATER VERTICAL 1730 48.2 4.0 1.0 - 1050 McQUAY 1. 2

UDH 090

CABINET CEIUNG FLUSH 300 17.4 1.0 1.0 1370 McQUAY

UNIT HEATER MOUNTED

- 1. 2

CHB 003

1. ' SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. CAPACITY BASED ON 180'F E.W.T. & 60'f E.A.T.

(CONTINUED) MECHANICAL/ELECTRICAL COORDINATION SCHEDULE

REFER TO SPEC! FICA TIONS FOR ADDITIONAL REQUIREMENTS.

RATING

DISCONNECT MOTOR STARTER

MARK DESCRIPTION FURNISH/ RA1NG FUSE FURNISH/ T'fl'E/ REMARKS

LON> v PH INSTAll TYPE (AIIPS) SIZE ENCL INSTALL NEMA ENCL

BY BY SIZE

SF-1 IN-LINE CABINET FAN 1/4 120 1 E/E SH 20 MR N1 - - -

HP

AC-1 EVAPORATOR (INDOOR) - - - E/E SH 20 MR N1 - - - 4

CU-1

CONDENSING UNIT 20 208 1 E/E ss 60 MR 3R 4

(OUlDOORS) FLA

AC-2 EVAPORATOR (INDOOR) - - - E/E SH 20 MR N1 - - - 4

CU-2

CONDENSING UNIT 12 120 1 E/E ss 30 MR 3R 4

(OUlDOORS)· FLA

UH-1-2 HORIZONTAL UNIT HEAlER 1/20 120 1 E/E SH 20 MR N1 M/M - -

HP

UH-3 HORIZON,TAL UNIT HEATER 1/60 120 1 E/E, 5H 20 MR N1 M/M - -

HP ' • • '

UH-4 HORIZONTAL UNIT HEATER 1/15 120 1 E/E 5H 20 MR N1 M/M - -

HP

CUH CEIUNG CABINET 1/12 120 1 E/E SH 20 MR N1 M/M 1-4 UNIT HEATER HP

KV-1 KILN VENT 1/3 120 1 E/E SH 20 MR N1 M/M - - 3

HP

KH-1 KITCHEN HOOD - - - - - - - - - - 2 -

KH-2 KITCHEN HOOD - - - - - - - - - - 2 -

I.IAU-1

GAS FIRED 2 208 3 E/E ss 30 MR 3R M/M 2

MAKE-UP AIR UNIT HP

01\H DOMESTIC 5.0 120 1 E/E SH 20 MR N1 M/M 1A WATER HEATER AMPS

01\H DOMESTIC 5.0 120 1 E/E SH 20 MR N1 M/M 18 WATER HEATER AMPS

PP-1 DOMESTIC HW (120' ) 1/12 120 1 E/E SH 20 MR N1 M/M - -

CIRCULATOR HP

PP-2 DOMESTIC HW (140') 1/12 120 1 E/E SH 20 MR N1 M/M - -

CIRCULATOR HP

PP- 3 DOMESTIC HW (140' ) 1/12 120 1 E/E 5H 20 MR N1 M/M - -

CIRCULATOR HP

PP-4 DOMESTIC HW (120' ) 1/12 120 1 E/E SH 20 MR N1 M/M - -

CIRCULATOR HP

CP-1 CONDENSATE 0.24 120 1 E/E 5H 20 MR N1

PUMP AMPS

ROOFTOP HVAC UNIT SCHEDULE

TOTAL COOUNG ~~U~I~ EXT. OUTDOOR COOUNG CAP. MBH HEAllNG CAP. MBH MANUFACTURER &

MARK SERVES CFM ENT. AIR IACAllON S.P. AIR, MODEL NO.

REMARKS

(08/ \\B) (lBS/HR ) IN. W.C. CFM TOTAL SENSIBLE INPUT OUlPUT

RlU-1A KITCHEN A 122 5000 81.1'f /65"F 20.2 1.0 400 147.5 126.2 169 135 LENNOX 1, 2, LGC156 9. 10

R1U-2A ART CLASSROOM 2250 78.4'F /64.8'F 22.9 1.6 375 83.7 59.8 180 144 LENNOX 1, 2, A161 LGA090 9. 10, 11

R1U-3A CLASSROOM A165 1475 80.5'f /67'f 18.4 0.75 375 58.8 39.5 125 100 LENNOX 1, 2, LGA060 9, 10

RlU-4A CLASSROOM A156 2250 77.5'F /64.1 'F 16.3 0.75 375 84.6 65.0 130 104 LENNOX 1, 3, LGC090 8, 9, 10

R1U-5A CLASSROOM A157 1120 81.5'F/67.4'F 13.6 0.50 375 46.2 32.0 78 62.4 LENNOX 1, 4, LGA048 B. 9, 10

RTU-6A CLASSROOM A169 1400 80.5'F /67'F 16.8 0.75 375 58.8 39.5 125 100 LENNOX 1, 2, LGA060 9, 10

R11J - 7A ART A153 1680 79.7'F /65.8'F 21.5 0.75 375 69.0 46.6 125 100 LENNOX 1, 2, LGC072 9. 10

RllJ-BA L.D. A152 1325 80.8'F /66.6'F 11.7 0.75 375 46.5 34.2 125 100 LENNOX 1, 5, LGA048 8, 9, 10

R1U-9A SCIENCE CLASSROOM 1400 80.5'f /67'f 16.8 0.75 375 58.8 39.5 125 100 LENNOX 1, 2, A176 LGA060 9, 10, 11

TU-10A SCIENCE CLASSROOM 1400 80.5'f /67'f 16.8 0.75 375 58.8 39.5 125 100 LENNOX 1, 2, A177 LGA060 9, 10, 11

R1U-11A STAFF A143 1325 77.5'F /64.1 'F 10.9 0.75 165 44.8 33.4 125 100 LENNOX 1, 2, LGA048 9, 10

RTU-12A DINING A120 7000 79.1'F/65.7'F 79.0 1.0 1470 276.1 193.7 260 208 LENNOX 1, 2, LGC300 9, 10

TU-13A WRITlNG LAB B144 2250 78.4'F /64.8'F 22.9 0.75 375 83.7 59.8 180 144 LENNOX 1, 6, 8, LGA090 9, 10, 11

TU-14A CLASSROOM B136 2000 78'F /64.8'F - 0.75 495 71.8 52.2 125 100 LENNOX 1, 7, LGA072 8, 9, 10

1U-15A

GIRLS

2380 82.8'F /68.9'F 1.25 765 101.3 64.9 130 104 LENNOX 1, 2, -

LOCKER ROOMS LGC102 9, 10

1U-16A

BOYS

1680 84.3'F /69.3'F 25.2 1.25 765 75.1 48.8 125 100 LENNOX 1, 2,

LOCKER ROOMS LGC072 9, 10

TU-17A STORAGE C200 5600 76.4'F /63.1'F 61.4 1.0 375 225.2 161.1 260 208 LENNOX 1, 2, LGA240 9, 10, 11

TU-19A VESnBULE C107 1050 81.6'F/68.1'F 11.0 0.75 100 32.5 26.0 78 62.4 LENNOX 1, 2, LGA036 9, 10

REMARKS.

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. FURNISH NEW INSULATED ROOF CURB. VERIFY ROOF TYPE W11H ARCHITECTURAL DRAWINGS.

3. FURNISH PREFABRICATED INSULATED ADAPTOR CURB TO MOUNT NEW UNIT ON EXISTING ROOF CURB. EXISnNG UNIT IS A CARRIER UNIT.

NO MODEL NUMBER AVAILABLE.

4. FURNISH PREFABRICATED INSULATED ADAPTOR CURB TO MOUNT NEW UNIT ON EXISTING ROOF CURB. EXISTING UNIT IS A SNYDER GENERAL PG11A060.

5. FURNISH PREFABRICATED INSULATED ADAPTOR CURB TO MOUNT NEW UNIT ON EXISTING ROOF CURB. EXISTING UNIT IS A TRANE TCC030F100AB.

6. FURNISH PREFABRICATED INSULATED ADAPTOR CURB TO MOUNT NEW UNIT ON EXISTING ROOF CURB. EXISTING UNIT IS A CARRIER 48HD006300.

7. FURNISH PREFABRICATED INSULATED ADAPTOR CURB TO MOUNT NEW UNIT ON EXISTING ROOF CURB. EXISTING UNIT IS A CARRlER 48HD006310.

8. CONTRACTOR TO FIELD VERIFY ROOF CURB DIMENSIONS PRIOR TO SHOP DRAWING SUBMITTAL

9. COOLING CAPACITY BASED ON 105' F AMBIENT AIR TEMPERATURE.

10. UNIT TO HA~ FACTORY INSTALLED LONMARK COMPLIANT MICROPROCESSOR CONTROLLER AND HOT GAS REHEAT DEHUMIDIFICATION CONTROL.

SEE SECTIONS 15782 AND 15985 FOR ADDITlONAL REQUIREMENTS.

11. PROVIDE VIBRATION ISOLATION RAIL ON TOP OF CURB. RAILS TO BE VIBRAllON MOUNTINGS AND CONTROLS MODEL AXR OR EQUAL.

CONTRACTOR RESPONSIBLE FOR TRANSITlON FROM ROOF CURB FRAMING PlECES TO ROOFTOP DISCHARGE.

KITCHEN HOOD SCHEDULE (FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER)

" ARK

. DATA

l::s~:P & PF

HOOD MANUFACTURER

I"""" ' CFM NO SIZE MATERIAL & MODEL NO.

KH 1 24" l<''."c': 430 s.s. _: AIRE

KH 2 24" 12150 .441 I (1) @ IE~·,g .145 ii?l_@. 430 S.S.

CAPTIVE AIR£

KH-3 - - 24" 11342 .333 IS!,,~· - - - - - - - 304 s.s.

CAPTIVE AIR£

REMARKS.

1. SEE MECHANICAL/ELECTRICAL COORD INATION SCHEDULE FOR ELECTRICAL DATA.

2. EQUIPMENT FURNISHED BY FOOD SERVICE EQUIPMENT SUPPUER (FSES), INSTALLED BY MECHANICAL CONTRACTOR AND

WIRED BY ELECTRICAL CONTRACTOR. INFORMATION GIVEN FOR COORDINATION PURPOSES ON LY. VERIFY CONNECTION SIZES AND OUANllTIES AND MODEL NUMBERS WITH (FSES).

SOUND ATTENUATOR SCHEDULE

SIZE (INCHES)

FACE PRESS.

INSERTION LOSS/SELF NOISE dB

MARK SERVICE CFM "'DlH VEL LOSS OCTAVE BAND CENTER FREQUENCY HZ MANUFACTURER & l.ENGJH X DIA. FPM IN. W.G. MODEL NO.

HElGHT 63 125 250 500 1000 2000 4000

SA-1 GYM C109 3800 60" 30. x20" - -912 56 13/ 18.4/ 32/ 42/ 44/ 37/ 24.5/ DYNASONICS RETURN 55.5 46 44 46.3 45.4 40.7 31.8 lF 99

SA-2 GYM C109

7100 72/72 64~x16" - -1000 .44 7/ 18/ 30/ 41/ 46/ 46/ 39/ DYNASONICS

RETURN 64.3 50.3 47.6 48.3 45.6 35.3 31 EBS-A

SA-3 RTU 2A

2225 36" 28-xtz• - 1000 .41 3.66/ 7/ 15.66/ 25.33/ 34/ 35.66/ 25.33/ DYNASONICS

SUPPLY 61 53.33 44.33 44.66 47.66 47.66 39 SF-95

SA-4 RTU 2A

2225 36" 28"x12" - -1000 .41 6/ 7.66/ 18.33/ 29.33/ 37.33/ 36.66/ 26/ DYNASONICS

RETURN 58.33 47.33 41 43 45.33 39 34.66 SF 95

REM ARKS

1. 2

1. 2

REMARKS

MECHANICAL/ELECTRICAL COORDINATION SCHEDULE

~LECTRiCAL CONTRACTOR HP HORSEPOWER 3R NEMA 3R 5H HP RATED SWITCH M MECHANICAL CONTRACTOR KW KILOWATTS 4X NEMA 4X ST Tl-IERMAL ELEM. SW.

c COMBINATION STARTER MR PER MANUFACTURER'S PH PHASE v VOLTAGE

& SAFETY SWITCH RECOMMENDATION RE REVERSING VFD VARIABLE FREQUENCY

CB CIRCUIT BREAKER NF NON-FUSED RV REDUCED VOLTAGE DRIVE

~ ~tt ~g~6A~~PS NR NON-REVERSING SF FUSEHOLDER WI1H SWITCH 2S TWO SPEED N1 NEMA 1 ss SAFETY SWITCH 35 THREE SPEED

REFERTO OAllONS~ I

~TOR

RAllNG

I MARK DESCRIPllON I= FUSE ENCL 1 7.:~:~ 'f~ REMARKS

TYPE ENCL

LON> v PH BY SIZE

ROOFTOP UNIT 1~1 460 3 E/E 5S 60 MR 3R M/M

ROOFTOP UNIT I~~ 460 3 E/E 5S 60 MR 3R M/M

ROOFTOP UNIT 14.8 460 3 E/E 5S 30 MR 3R M/M FLA

ROOFTOP UNIT ~~ 460 3 E/E 5S 60 MR 3R "1M -

ROOFTOP UNIT }i1 460 3 E/E 5S 30 MR 3R M/M

ROOFTOP UNIT }~ 460 3 E/E 55 30 MR 3R M/M

ROOFTOP UNIT }t: 460 3 E/E 55 30 MR 3R M/M

ROOFTOP UNIT }iX 460 3 E/E S5 30 MR 3R M/M

ROOFTOP UNIT }~ 460 3 E/E S5 30 MR 3R M/M

ROOFTOP UNIT 1ff 460 3 E/E S5 30 MR 3R M/M

ROOFTOP UNIT }t~ 460 3 E/E S5 30 MR 3R M/M

ROOFTOP UNIT 'iU 460 3 E/E 5S 100 MR 3R M/M

ROOFTOP UNIT ~~ 460 3 E/E 55 60 MR 3R M/M

ROOFTOP UNIT 1ff 460 3 E/E 55 30 MR 3R M/M

ROOFTOP UNIT I~} 460 3 E/E 55 60 MR 3R M/M

ROOFTOP UNIT

14.8 460 3 E/E 5S 30 MR 3R M/M FLA

"'V ROOFTOP UNIT I~: 460 3 E/E ss 100 MR 3R M/M - -

ROOFTOP UNIT I "FL:.; 460 3 E/E 5S 200 MR 3R M/M

ROOFTOP UNIT ii~ 460 3 E/E 55 30 MR 3R M/M

ROOFTOP UNIT 1~: 460 3 E/E 55 200 MR 3R M/M

ROOFTOP UNIT I 'Fi::.; 460 3 E/E ss 200 MR 3R M/M

' UNIT I ~~~ 460 3 E/E S5 60 MR 3R M/M

REPLACEMENT ii~ 460 3 E/E S5 30 MR 3R M/M ROOFTOP UNIT

UN I' ~ 460 3 E/E 5S 30 MR 3R M/M

UN I' I }iX 460 3 E/E 55 30 MR 3R M/M

REPLACEMENT :u 460 3 E/E 55 30 MR 3R M/M

ROOFTOP UNIT

REPL

UN I' }i1 460 3 E/E 55 30 MR 3R M/M

UN I' ~ 460 3 E/E 55 30 MR 3R M/M

· UNIT ~~ 460 3 E/E S5 30 MR 3R M/M

• UNIT }t~ 460 3 E/E 55 30 MR 3R M/M

REPL

UNIT }t~ 460 3 E/E S5 30 MR 3R M/M

REPLACEMENT ~ 460 3 E/E 5S 30 MR 3R M/M

ROOFTOP UNIT

UNIT :tx 460 3 E/E 5S 30 MR 3R M/M

REPL

UNIT :t: 460 3 E/E 55 30 MR 3R M/M

UNIT

·~ 460 3 E/E 55 30 MR 3R M/M

~ 12.9 460 3 E/E 55 30 MR 3R M/M UNIT FlA

·~~~~ ~; 460 3 E/E ss 30 MR 3R M/M

UNI }tl' 460 3 E/E 55 30 MR 3R M/M

UNI I Fci 460 3 E/E S5 30 MR 3R M/M

; UNIT :tx 460 3 E/E 5S 30 MR 3R M/M

REPL

UN I' :{1 460 3 E/E 55 30 MR 3R M/M

UN I'

-;.r; 460 3 E/E 5S 30 MR 3R M/M

' UNIT liJ1 460 3 E/E 55 30 MR 3R M/M

REPLACEMENT :t: 460 3 E/E 55 30 MR 3R M/M

ROOFTOP UNIT

REPL

UN I' }~ 460 3 E/E S5 30 MR 3R M/M

REPL

UN I'

~-~ 460 3 E/E 5S 30 MR 3R M/M

~ I Fi;: ' UNIT 460 3 E/E 5S 30 MR 3R M/M

· UNIT :u 460 3 E/E 55 30 MR 3R M/M lrr_

I -FAN

50 120 1 E/E 5H 20 MR N1

EF 8 R~vo.r MOU~l'.i' ::p4 120 1 E/E SH 20 MR 3R M/M 1

EF-9 R~v<;" 3T FAN f?: 120 1 E/E 5H 20 MR 3R M/M 1

EF- 10 DlR?_?!' MOUNTED 3,{p4 120 1 - 2

EXHAUST FAN

EF- 11 "ppr~~; _MUUO Ccu FAN 3,{p4 120 1 - - - - - - - - 2

EF 12 "PPr~~; MOUNTED FAN 3.;;; 120 1 2

EF- 13 ROOF

• FAN ',{i 120 1 ' 1

EF 14

ROOF MOUNTED \?! 120 1 1

lT EXHAUST FAN

EF 15

I

'"rAN

50 120 1 E/E 5H 20 MR N1

EF16 I

-FAN

50 120 1 E/E 5H 20 MR N1

GENERAL NOTES.

A. CONTRACTOR SHALl VERIFY/COORDINATE ALL RATINGS FOR EQUIPMENT SUPPLIED BY THE SELECTED MANUFACTURER. 'IJHERE

SUCH RATINGS ARE OTHER THAN AS INDICATED ON MECHANICAL/ELECTRICAL COORDINATION SCHEDULE, DISCONNECTS, MOTOR STARTERS, OVERCURRENT DEVICES AND RELATED REVISIONS SHALL BE PROVIDED ACCORDINGLY. lHE CONTRACTOR THAT FURNISHES EQUIPMENT \AII1H RATINGS OJHER THAN AS INDICATED SHALL BE RESPONSIBLE FOR ALL COORD INATION AND COSTS

FOR REVISIONS TO ACCOMMODATE SELECTED EQUIPMENT.

B. ALL FRACTIONAL HORSEPOWER MOTORS SHALL BE PROVIDED WITH INTEGRAL OVERLOAD PR01ECTION.

C. HORSEPOWER R~TED SWITCHES (SH): FOR 120 V MOTORS LESS THAN 1/2 HP, PROVIDE FUSEHOLDER WITH SWITCH, FUSED PER

MANUFACl1JRER S RECOMMENDATION AND NEC REQUIREMENTS. FOR 120 V MOTORS RATED 1/2 HP OR 3/4 HP, PROVIDE HP RATED TOGGLE S'MTCH ('IJHERE BRANCH CIRCUIT OVERCURRENT DEVICE MEETS NEC REQUIREMENTS FOR SHORT-CIRCUlT

PROTECTION) OR FUSED SAFETY SWITCH.

REMARKS:

1. EXHAUST FAN MOTOR SHALL BE FACTORY WIRED TO WEATHERPROOF JUNCTION BOX INTEGRAL WITH FAN . ELECTRICAL

CONTRACTOR TO PROVIDE WEATHERPROOF HORSEPOWER RATED SWITCH (SEE GENERAL NOTES ABOVE).

2. FURNISHED BY FOOD SERVICE EQUIPMENT SUPPLIER, INSTALLED BY MECHANICAL AND WIRED BY ELECTRICAL.

3. PROVIDE CORD AND PLUG AS REQUIRED, COORDINATE.

4. INDOOR EVAPORATOR POWERED FROM OUTDOOR CONDENS!NG UNIT.

SEMI-CUSTOM ROOFTOP UNIT SCHEDULE

MARK SUPPLY OUTSIDE EXHAUST EXT. S.P. IN. Vft-IEEL SUMMER AIR CONDITIONS v.Hm WINlER AIR CONDITIONS OX COIL CONDITIONS OX COIL CONDITIONS GAS HEAT CONOITlONS MANUFAClURER CF\1 AIR CFI.4 CF\1 S. F. E.F. O.A. EXHAUST LA. T O.A. EXHAUST LA.T E.A.T. LA.T TOTAL MBH SENSIBLE t.iBH INPUT MBH OUTPUT MBH & MODEL NO. REt.tARKS

RllJ-16A 8475 3270 2950 2" 1" 95/78 75/62 79.5/66.3 0" F 70.0/52.6 44.6/37.3 76.8/63.8 53.8/53.4 259.2 213.2 500 400 MCQUAY 1, 2.

RPR020C 3, 4, 5

,,,_,,. 6250 3115 2800 2" 1" 95/78 75/62 79.4/66.2 0' F 70.0/52.6 44.8/37.5 76.8/63.7 53.5/53.0 257.3 210 500 400

MCQUAY 1, 2.

RPR020C 3, 4, 5

RTU-21A 8250 3115 2800 2" 1" 95/78 75/62 79.4/66.2 0' F 70.0/52.6 44.8/37.5 76.8/63.7 53.5/53.0 257.3 210 500 400

MCQUAY 1, 2.

RPR020C 3, 4, 5

REMARKS.

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. PROVIDE INTERNAL VIBRATION ISOLATION ON UNIT INCLUDING 2" SPRING ISOLATORS ON SUPPLY AND EXHAUST FANS AND R-1-S ISOLATION ON SCROLL COMPRESSORS.

3. UNIT TO HAVE MINIMUM OF (2) REFRIGERATION CIRCUITS W/ HOT GAS BYPASS ON FIRST CIRCUIT, VARIABLE FREQUENCY DRIVES ON SUPPLY AND EXHAUST FANS, SUPPLY MINIMUM AIRFLOW SHALL BE 3700 CFM. SEE SECTIONS 15782 AND 15985 FOR ADDITIONAL REQUIREMENTS.

4. UNIT SHALL BE PROVIDED WITH A COMPLETE MICROPROCESSOR BASED TEMPERAlURE CONTROL SYSTEM WI TH THE ABILITY TO COMMUNICATE TO AN INDEPENDENT BUILDING AUTOMATION SYSTEM THROUGH A DIRECT

LONTALK COMMUNICATIONS CONNECTION. MICROPROCESSOR CONTROLS AND ALL REQUIRED SENSORS (INCLUDING DISCHARGE AIR, ECONOMIZER CONTROLS, FACTORY MOUNTED FREEZESTATS, AND SPACE STATIC PRESSURE, ETC.) TO BE SUPPLIED WITH ROOFTOP UNITS. TEMPERATURE CONTROL CONIRACTOR TO FIELD WIRE STATlC PRESSURE SENSORS TO ROOnOP UNIT CONTROLLER. UNIT CONTROL SYSTEM SHALL PERFORM ALL UNIT CONTROL FUNCTIONS INCLUDING SCHEDUUNG, TEMPERA lURE CONTROL AND SPACE STATIC PRESSURE CONTROL C02 SENSORS ARE TO BE PROVIDED AND INSTALLED BY TEMPERATURE CONTROL CONTRACTOR AND 'MRED TO UNIT CONTROLLER. SEE SECTION t 5985 FOR SEQUENCE OF OPERATIONS. •

5 . PROVIDE INSULATED ROOF CURB, PROVIDE VIBRATION ISOLATION RAIL ON TOP OF CURB. RAILS TO BE VIBRATION MOUNTINGS AND CONTROLS MODEL AXR OR EQUAL. CONTRACTOR RESPONSIBLE FOR

TRANSITION FROM ROOF CURB FRAMING PIECES TO ROOFTOP DISCHARGE.

SPLIT SYSTEM UNIT SCHEDULE

REMARKS

AC-1 CU-1 650

AC-2 CU-2 300 9.4 6.1 MW09C1E MR09C1E

REMARKS:

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

REGISTER-GRILLE-DIFFUSER SCHEDULE

MARK FUNCTION TYPE CFM MAX SIZE BORDER OR

I FINISH ACCESS. MANUFAClURER & REMARKS RANG!' N.C. FRAME I SlEEL MODEL NO.

A SUPPLY I SQUARE;~~ 1°70 <25 N';;lK &,<-;.:~ X l ~i'E SERIES 1400 1, 2 . • •

8 SUPPLY SQUARE FACE 170-

<25 N~~K 24x24 X STND. KRUEGER 1, 2 NOMINAL PNL 260 LAY-IN I>HilE

SERIES 1400

c SUPPLY ~ ~~.~~,~~ 1 2;~0 <25 .~9:~. &,".,X:~ X l~i'E ~ 1, 2 l·w.>~ 0 SUPPLY .";0 <25 -M<JUNr- X l~i'E O.B.O. 1, 2, 3 I'"'"" lllfF1ISER SE~2 E SUPPLY ~3o <25 ~~: ,:.~ -MouNT- X l ~i'E O.B.D. sE~11ES-RA~2 1, 2, 3 I R<XIND DIFFUSER

F SUPPLY SQUARE FACE 261 <25 ~~~~ 24~2~NT X STND. KRUEGER 1, 2, 5

NOMINAL PNL 350 I>HilE SERIES 1400

G SUPPLY DOUBLE 0 <25 6x6 SURFACE X STND. - KRUEGER 1, 2 DEFlECTION 145 MOUNT I>HilE SERIES 880 H

H SUPPLY

<25 10x6 MOUNT X l~i'E ~H

1, 2

I SUPPLY <25 14x6 MOONT- X l~i'E 1, 2 -,.0 ~H

J RETURN -PANEL .:'sa <20 ~~~~4 "~,;:' LAY IN X l~i'E SE~IES 6290 1, 2

K RETURN -;;,;-NEL I i~6-o <20 ~~:~~ N~~~ LAY IN X STND. KRUEGER 1, 2 I>HilE SERIES 6290

L RETURN o· BLADE 8250 <25 96X30 MOUNT X l~i'E ~H 1, 2

M 35' BLADE 1'i;o <25 6x6 ,~8!J~~c X l~i'E 1, 2 S[RI[S 5580 H

N 35' BLADE l 1:fi5 <25 12x6 -IA<JUNT- X l~i'E SERIES S580 H 1, 2

0 I~~~ ~~;;t,. 35" BLADE l 2f~o- <25 18X10 SURFACE X STND. KRUEGER 1, 2 MOUNT WHilE

SERIES 5580 H

p 1 ~c.'.~~:~~ 35" BLADE 13~0 <25 24x10 MOUNT X ~i'E ~H

1, 2

0 RETURN 0" BLADE

l 1goo <25 36x10 -MoUNT- X .~i'E 1, 2 SERIES S580 H

R RETURN . PANEL 1~60 <20 ~~~~ "~,;:' -.AouNT- X STND.

SER1Es-629o 1, 2

WHilE s ~~~~~~:~~ 35" BLADE l2f~o <25 12x12 SURFACE X ~i'E - SER~:~Es"raa H 1, 2. 5

MOUNT

T SUPPLY •.F~~ ~ <25 ~~;~ .2.~~2i· X ~i'E

1, 2 I u RETURN o· BLADE 1060 <25 32x16 -M<JUNr- X ~i'E 1, 2, 4 v SUPPLY si:or , 2~~5 <25 l <ffi1·~~~i -IAouNT- X ~i'E 1910 _SE;IES 1, 2 w RETIJRN o· BLADE 4240 <25 48x30 ·;;oc!Nr- X ~i'E ~H 1, 2

X SUPPLY VAV c;:~g 200 <25 1;~;2~~~~ MOUNT X I>HilE ll'FR HC 1, 2 y SUPPLY 3,i;o <25 18x6 X STND. 1, 2 MOUNT WHilE SERIES 880 H z SUPPLY FACE 351 <25 ~~~ 24x24 X ~i'E 1, 2 I PNL 430 LAY IN SERIES 1400

AA RETURN o· BLADE .?45 <25 18x10 X ~i'E ~H 1, 2

BB SUPPLY 23~0 <25 11~:~:~~ ~ ~<;.:~ X ~i'E 1, 2, 6 PANEl SERIES 6500

1. PROVIDE SPECIFIC NOISE CRITERIA (NC) DATA FOR EACH LINE ITEM 'NITH SHOP DRAWINGS.

2. VERIFY FRAME TYPES IN ALL ROOMS.

3. PROVIDE OPTIONAL SAFETY CHAIN.

4. PROVIDE PENCIL PROOF SPACING NON REMOVABLE CORE. FACE SCREW MOUNTING WITH NO SLEEVE.

5. SEE PLANS FOR DIFFUSERS AND GRILLES REQUIRING CEILING RADIATION DAMPERS.

6. OMIT DIRECTIONAL BLADES FROM DIFFUSER.

DUCTWORK INSULATION SCHEDULE

DUCT SYSlEM

ACOUSTICAL FLEXIBLE RIGID TI-iiCKNESS REMARKS UNER FIBERGLASS FIBERGLASS (INCHES)

ALL RECTANGULAR SUPPLY X - - 1" 1

AND RETURN DUCTWORK

ROUND DUCTWORK - X - 1 1/2" I

CONCEALED ABOVE CEIUNGS

ROUND EXPOSED DUCTWORK X - - 1" 1

INDICA lED TO BE LINED

EXHAUST DUCTWORK FROM FAN ON ROOF X - - 1" 1, 2

TO 20' 0» INSIDE BUILDING

KITCHEN HOOD EXHAUST DUCTWORK - - - 3" 1. 3

DUCT LAGGING ON SUPPLY AND RElURN - - - - 4 DUCTS AT ROOnOP UNITS

REMARKS:

1. SEE SPEC SECTION 15890 ~AIR DISTRIBUTIOW FOR ACOUSTICAL LINER SPECIFICATIONS &

SEE SECTION 15250 "MECHANICAL INSULATIOW FOR OTHER DUCT INSULATION SPECIFICATIONS.

2. DOES NOT INCLUDE KITCHEN HOOD & DISHWASHER EXHAUST.

3. DUCTS SHALL BE WRAPPED WITH TWO (2) LAYERS OF 1 1/2~ THICK (FOR A TOTAL OF 3 INCHES)

•FIREMASTER" FIRE RESISTIVE DUCT WRAP AS MANUFAClURED BY THERMAL CERAMICS OR EQUAL.

4. PROVIDE KINETICS KNM-100ALQ DUCT LAGGING. SEE DETAIL 2, SHEET M7.1.

DOMESTIC HOT WATER HEATER SCHEDULE (GAS)

MARK STORAGE RECO~Y IDIP RISE GAS INPUT DESIGN MANUFAClURER & REMARKS CN'. (G.OL) GPH " F (BTU/HR) PRESS. MODEL NO.

01'.>< 130 356 100 300,000 160 A.O. SMITH 1 1A PSI BTH-300

0\>H

130 356 100 300,000 160 A.O. SMITH 1 16 PSI BTH- 300

REMARKS:

1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

. PUMP SCHEDULE

"ARK TYPE SERVICE GP" HEAD RPM

MANUFAClURER & REMARKS

FT. MODEL NO.

PP-1 IN-UNE 120' HW 5.0 15.0 2750 GRUNDFOS 1, 2

CIRCULATION UP25-64

PP-2 IN-LINE 140' HW 3.0 12.0 2750 GRUNOFOS 1, 2

CIRCULATION UP25-64

PP-3 IN-LINE 140' HW 3.0 15.0 2750 GRUNDFOS 1, 2

CIRCULATION UP25-64

PP-4 IN-LINE 120' HW 5.0 15.0 2750 GRUNDFOS 1, 2 - CIRCULATION - UF:'25-64 -

CP-1 IN-LINE AC-2 4.0 7.5 - LITTLE GIANT 1

COt·JOENSA TE EC- 400

REMARKS.

1. SEE MECHANICAL/ELEC1RICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.

2. ALL BRONZE