38DJA51405_01_A01.pdf
PDF 285 KB Posted
- Attached to
- Remove and Install Rev-1(FO) No. 5 A/C Chilled Water Pump Motor/ Rewind - No. 5 A/C Chilled Water Pump Motor
- Solicitation number
- N6264926Q0458
About this file
This is a Job Specification document for naval maintenance work on the USS TRIPOLI (LHA-7). The document details the removal, disassembly, rewind, and reinstallation of the No.5 Air Conditioning Chilled Water Pump Motor, a 200 horsepower electric motor manufactured by Hansome Energy Systems (Model A-507-331, Frame 507, 3600 RPM, 440 VAC, 3-phase, 220 amps) currently located in Auxiliary Machinery Room No. 2.
The work scope requires accomplishing standard motor maintenance procedures including disassembly and inspection (009-033), cleaning and preservation of motor housing and components (009-032), and balancing of rotating assemblies (009-015). The motor must be delivered to SRF Production Shop S51 for core loss testing with submission of measurement data per the enclosed form (Enclosure B). A critical requirement involves fabricating and installing a new information plate stating "Future Rewind With Sealed Insulation" per NSTM Chapter 300 Rev.11. The motor will be rewound using Class F conventional insulation rather than the original Sealed Insulation System (SIS) due to schedule urgency and facility limitations, authorized by Design Branch Code S241 per ESR LHA7-0089. The anticipated award date is July 24, 2026, with a production completion date of October 30, 2026. Work period runs from August 17, 2026 to November 30, 2026, with the operation to be performed at Sasebo. Government-furnished materials include six specific gaskets, washers, deflectors, and nuts identified by part numbers and stock numbers. The document emphasizes that subsequent rewinds must use SIS and recommends future procurement of a replacement SIS motor or engagement of a NAVSEA-certified facility for SIS rewind capability.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation - N6264926Q0458.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ship/HULL NO. Ship/HULL NAME JoN. ICN: Rev: Key Op:
LHA-7 USS TRIPOLI 380JA51405 01 AOl
TITLE: No.5 A/C Chilled Water Pump Motor; remove and install
Rev-1(FO)- No.5 A/C Chilled Water Pump Motor; rewind
JOB SPECIFICATION
Anticipated Award Date: Production Completion Date: PREPARING ACTIVITY:
SASEBOPOP Start Date: POP End Date:
PREPARED BY:
J.SAKURAI
CODE
E_SJ
DATE
3/26/2026
APPROVED BY: c
S.MURAKAMI LVV '
CODE
S225
CONCURRED BY: A A_-..
A.OKA
CODE
S233
ASSIST PLANNER'S NAME: CODE
ASSIST PLANNER'S NAME: CODE
ASSIST PLANNER'S NAME: CODE
DESCRIPTION:
JSN(S): EAO5-1343 CASREP# 26031, C-2 DTG: 150359ZFEB26
S/F CONTACT: PALANCA MM2 / THOMAS MMC CWP # CCNS #
D. PERKINS
ar
Approved by S300/S900 Date: AVL: 6M-
LWC:
Work Completed
S/Force: Rate: Date:
Ship Supt: Date: SRF CONTROL NO.:_________________________
WORK CERTIFICATION SIGNATURES
COMPLETION OF WORK REVIEW: BADGE NO.: SHOP/CODE: PRONE: DATE:
A
Sakura.Yamaguchi.ja Typewritten Text 8/17/2026
Sakura.Yamaguchi.ja Typewritten Text 10/30/2026
Sakura.Yamaguchi.ja Typewritten Text 11/30/2026
Sakura.Yamaguchi.ja Typewritten Text 7/24/2026
Sakura.Yamaguchi.ja Typewritten Text 1301390378
Ship/HULL NO. ShipIHULL NAME ICN: Rev: KeyOp:
LHA -7 USS TRIPOLI JON. 38DJA51405 01 AOl
TITLE: No.5 AIC Chilled Water Pump Motor; remove and install
Rev-1(FO)-- No.5 A/C Chilled Water Pump Motor; rewind
1. SCOPE:
1.1 Title: No.5 A/C Chilled Water Pump Motor; remove and install Rev-l(FO) No.5 A/C Chilled Water Pump Motor; rewind
1.2 Location of Work:
1.2.1 Ship to Shop
1.3 Identification:
1.3.1 Quantity (One HA), Electric Motor for No.5 Air Conditioning (A/C) Chilled Water Pump Located in Auxiliary Machinery Room No.2 (4- 121-0-E), MFR Hansome Energy Systems, MFR DWG A-507-331, Frame 507, Speed 3600 RPM, Horsepower 200 HP, ½mps 220 A, Volts 440 VAC, Frequency 60 HZ, Phase 3, INS CLASS F (Sealed Insulation System), Duty Continuous, Weight 2750 LBS, APL 17A150038
2. REFERENCES:
2.1 Standard Items (FY26)
2.2 56226-1R-MMA-010 Rev 2, Pump, Air Conditioning Chilled Water Centrifugal, Model 8 X 8 X l3NC2, Part 998 -64GK-A-001
2.3 MFR DWG A-507-331 Rev 2, A.C. Motor
3. REQUIREMENTS:
3.1 Pick up the electric motor listed in 1.3.1 from designated location via SHIPSUPT.
3.2 Accomplish the requirements of 009-033 of 2.1 for the electric motor listed in 1.3.1, using 2.2, 2.3, and ENCLOSURE (A) for guidance.
3.2.1 Accomplish the requirements of 009-032 of 2.1 for cleaning and preservation of motor housing, fan, interior and exterior of each end bell and foundation.
3.2.2 Accomplish the requirements of 009-015 of 2.1 for balancing of each rotating assembly.
3.2.3 Deliver the electric motor to SRF Production Shop S51 via SHIPSUPT for core loss testing and pick them up after testing.
3.2.3.1 Submit one legible copy of a core measurement data of ENCLOSURE (B) to SRF Production Shop S51.
3.2.4 After completion of the Core Loss Test, pick it up.
Ship/HULL NO. Ship/HULL NAME ICN: Rev: Key Op:
LHA-7 USS TRIPOLI JON. 38DJA51405 01 AOl
TITLE: No.5 A/C Chilled Water Pump Motor; remove and install
Rev-1(FO)- No.5 A/C Chilled Water Pump Motor; rewind
3.2.5 Fabricate and install new SIS information plate out of ORES plate engraving, "Future Rewind With Sealed Insulation" in accordance with Paragraph 300-4.5.7.6-b(4) of NSTM Chapter 300 Rev.11.
3.3 Deliver the electric motor listed in 1.3.1 to the designated location via SHIPSUPT.
4. NOTES:
4.1 Initial Condition - (No.5 AC) During normal operations S/F discovered white smoke emitting from No.5 AC chilled water pump motor and electrically isolated the pump. Upon further investigation S/F determined the motor to be no longer operational. Request outside activity remove motor, disassemble, replace/repair broken/worn parts, rewind, reassemble and reinstall. Remove & reinstall by 551:38DJA51405 -H01. Rewind by FO:38DJA51405-AO1(Ship to Shop).
4.2 SRF Tool Room will issue each gauge and dial indicator when required.
4.3 Removal, installation, and operational test in the 009-033 of 2.1 will be performed by Production Shop under original JON 38DJA51405-HO1.
4.3.1 SRF Production Shop POC is S91OPS (Mr. H.OONO / 252-8242).
4.4 S241 concurred to rewind the electric motor listed in 1.3.1 using a Class F conventional insulation system by official response to ESR LHA7 -0089 on 3/26/2026.
5. GOVERNMENT FURNISHED MATERIAL (GFM):
5.1 Government Furnished Materials.
MATERIAL LIST
ITEM
NO.
PC
NO.
REF M
/ DESCRIPTION STOCK NUMBER I-IAZ DOC NO. QTY PARA
/UNIT NO.
001 11 2.3 M GASKET, P/N: I-IAN912-2 9B 5330 013734680 N 6075D500 1/EA 3.2
002 12 2.3 M GASKET, P/N: F-IAN912-1 9B 5330 011598412 N 6075D501 1/EA 3.2
003 23 2.3 M WASHER,SPRING TENSION,
9B 5310 013697938 N 6075D502 1/EA 3.2
P/N: ESBO12-26
004 46 2.3 M DEFLECTOR,DIRT AND LIQUID,
9B 4320 012995731 N
6075D503
1/EA
3.2
P/N: HAN2392-11
005 47 2.3 M DEFLECTOR,DIRT AND LIQUID,
9B 4320 015979423 N
6075D504
1/EA 3.2
PIN: HAN239-13B
56 2.3 C NUT, PLAIN, ROUND,
P/N: ESBOO9-10
9B 5310 013333808
N
6075D506
1/EA
3.2
Ship/HULL NO. Ship/HULL NAME ICN:
Rev: Key Op:
LHA-7 USS TRIPOLI JON. 38DJA51405 01 AOl
TITLE: No.5 A/C Chilled Water Pump Motor; remove and install
Rev-1(FO)-- No.5 AIC Chilled Water Pump Motor; rewind
S241 official email response to ESR LHA7 -0089.
BLUF: Rewind No. 5 AC Chilled water pump motor using Clas F conventional insulation system.
References:
(a) ESR LHA7 -0089, NO. 5 AC CHILLED WATER PUMP MOTOR; rewind
(b) MFR DWG A-507-331, Rev. 2, A. C. Motor, Hansome Energy Systems Inc.
(c) MIL-STD-2037, Procedure to Obtain Certification for Electric Motor Sealed Insulation Systems
(d) 59086-KC-STM-010/300 Rev 11, Naval Ships' Technical Manual Chapter 300 Electric Plant - General
(e) Ser S240/1236, Conventional Class F and Sealed Insulation System Motor Rewind Conducted by Non-certified NAVSEA Facility
Enclosures: None.
Background:
(1) Reference (a) requested SRF-JRMC Det. Sasebo Design Branch Code S24l to provide technical assistance to rewind No. 5 AC Chilled water pump motor with Class F conventional insulation (non-SIS) . This motor was originally equipped with a Sealed Insulation System (SIS)
(2) Per reference (b), the motor is specified to have SIS insulation. However, SRF-JRMC Det. Sasebo does not possess the certified capability to perform SIS rewinds.
(3) Reference (c), paragraph 4.1, requires that SIS rewinds be performed by a NAVSEA-certified facility. Although SRF-JRMC Yokosuka (X5l) is the nearest former certified facility, it cannot support this rewind since the motor's stator weight exceeds the 800 kg limit of its VPI equipment, as noted in reference 2.2 of reference (a)
(4) References (d) and (e), authorize a one-time rewind of an SIS motor with a non-SIS if it is urgent and the time to rewind with SIS will result in a significant impact to ship's schedule. Procuring a new replacement SIS motor for No. 5 AC Chilled water pump will not meet the ship's schedule.
(5) SRF-JRIvIC Det. Sasebo has verified that there is no existing information plate or maintenance history indicating this motor was previously rewound with a non-SIS system.
Designer's Comments:
(1) Rewind the No. 5 AC Chilled water pump motor using a Class F conventional insulation system.
(2) Fabricate and install a new information plate on the motor enclosure per reference (d), paragraph 300-4.5.7.6.b. (4). The plate shall be made of corrosion-resistant steel and must state: "Future Rewind With Sealed Insulation."
ENCLOSURE (A) 1/2
LHA-7 USS TRIPOLI JON. 38DJA51405 01 AOl
TITLE: No.5 A/C Chilled Water Pump Motor; remove and install
Rev-1(FO)-- No.5 A/C Chilled Water Pump Motor; rewind
(3) Submit satisfactory shop no-load test data to Design Branch Code S241 to support submission of an information-only Liaison Action Request (LAR) required by paragraph 3.b. (2) of reference (e)
(4) Per references (d) and (e), this conventional rewind is authorized only as an emergent repair and subsequent rewind of this motor must be performed using SIS. A conventional rewind will not be authorized for next repair without formal DFS approval.
(5) For future planning, Design Branch Code S241 recommends two primary options for the next repair cycle:
a. Procure a new replacement SIS motor to coincide with the original insulation design, reference (b)
b. Send the existing motor to a NAVSEA-certified facility with the capability to perform an SIS rewind on a motor of this size.
(6) This concludes the design action for ESR LHA7 -0089.
ENCLOSURE 2/2
LHA-7 USS TRIPOLI JON. 380JA51405 01 AOl
TITLE: No.5 A/C Chilled Water Pump Motor; remove and install
Rev-1(FO)- No.5 A/C Chilled Water Pump Motor; rewind
STATOR CORE LOSS TEST
DATE_____________
JOB No.
Customer (Ship/Hull Name)____________________________________________ Description (Motor Name)_____________________________________________________
Motor Name Plate Data HP (KW)______________ RPM____________ Manufacturer Type No.
Model No._____ Style No.______________________________ Form No.______ Serial No.______________________________ VAC____________ AMP__________ Phase_______ Duty Cycle_______________________________ Frame_________ Enclosure________________________________
CORE ll- (-1 /J'LC1fI) © Core Length___________________________________ © Inner Core Diameter__________________________ © Back Iron Depth_____________________________ ® Slot Depth____________________________________ ® Number of Slot____________________________ © Tooth Width____________________________________
5I rh ttJ
ENCLOSURE 1/1
cz