This is an amendment to a previous combined solicitation for Generator-ATS Maintenance services at the Department of Veterans Affairs Service & Distribution Center in Hines, Illinois. The solicitation (36S79726Q0006) seeks preventive maintenance, testing, service, and repair of generators, automatic transfer switches (ATS), transformers, breakers, and annual load bank testing. The contracting office is located in Hines, IL (ZIP 60141), with the place of performance at Building 37. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The response deadline is October 19, 2026, at 4:00 PM Central Time. The product service code is J030 (Maintenance and Repair Services), and the NAICS code is 561210. The primary point of contact is Contracting Officer Michelle Williams (michelle.williams4@va.gov, 708-786-7565).

The scope includes maintenance of diesel-powered generators with voltages of 480 and 240 volts, including 600 kW, 500 kW, 1250 kW, and 750 kW units. Monthly preventive maintenance for the critical 600 kW and 500 kW generators backing the Consolidated Mail Order Pharmacy (CMOP) must occur on the second Tuesday of each month from 4:00 AM to 7:00 AM, with other units serviced during normal business hours. The contractor must provide consumables outlined in Attachment B (filters, oil, hoses, and belts) within PM pricing. Annual load bank testing and infrared scans of transformers and ATS equipment are required while energized to identify faults under operating conditions. The VA furnishes fuel for generators during inspections. An unscheduled repair CLIN is funded at $50,000 per contract year for emergency maintenance. Emergency travel and labor costs should be included in the quote. A site visit is scheduled for September 3, 2026, at 9:00 AM, with questions due September 11, 2026, by 4:00 PM CST.

View the file

Other files

File Type Posted
Attachment C.docx DOCX document
36S79726Q0006 0001.docx DOCX document
36S79726Q0006 0001_1.docx DOCX document
Wage Determination.pdf PDF
Generator_Consumables Attachment B.docx DOCX document
36S79726Q0006.docx DOCX document
ATTACHMENT A Generator Equipment.docx DOCX document
36S79726Q0006_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
Generator-ATS Maintenance (VA-27-00002745)

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
60141
SOLICITATION NUMBER*
36S79726Q0006
RESPONSE DATE/TIME/ZONE
10-19-2026 16:00 CENTRAL TIME, CHICAGO, USA
ARCHIVE
45 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SDVOSBC
PRODUCT SERVICE CODE*
J030
NAICS CODE*
561210
CONTRACTING OFFICE ADDRESS
VA NAC / 003B6A

PO Box 76 1st Ave., One Block N of 22nd

Hines IL 60141

POINT OF CONTACT*

Contracting Officer Michelle Williams michelle.williams4@va.gov 708.786.7565

PLACE OF PERFORMANCE

ADDRESS
1st Ave., One Block N of 22nd

Bldg 37

Hines IL

POSTAL CODE
60141

COUNTRY

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

What are the hours of operation for Generator Maintenance? This is in the SOW

Can you provide a Document with each Back-up Generator Model #’s &Serial #’s? This is Attachment A of the package

Please Confirm the Voltage of the Generators? 480 and 240

Regarding Contractor Provided Consumables, many of the items listed are typically repairs quoted and approved before work proceeds on this and some parts(hoses and belts). As an outside vendor there is no way to effectively build this into your maintenance plan to guarantee effective cost for both the vendor and for Edward Hines VA. We request this section is altered to allow for these costs to be sectioned out for repairs and for one annual service to replace filters and oil. See Attachment B.

How many Generators have Diesel Engines? All of them

Are there any Generators with difficulty accessing (Roof, Parking Garage, Basement)? If so, which units are they? NO

Are your Generators within 50 ft of the Entry Door, where our truck will be parked? Yes

Are the Annual Load Tests performed with your Minor B-PMs? No

Can I get the age of each equipment if possible? See Attachment A

Please clarify the Unscheduled Repair CLIN amount. Is the stated “$50,000” intended to mean $50,000 per contract year? This is just a funding item for me to populate an unscheduled maintenance clin for me to address items the break.

Where should emergency travel and labor be priced? All previous contracts has local labor. Never had this issue. Build it in your quote.

Will VA furnish diesel consumed during inspections? VA furnishes Fuel for the generators Period.

Can you provide any previous maintenance reports, emergency calls, major repairs, etc.? After Award.

Consumables Attachment Section 2.1 states “Replace PM Consumables as required” and references “Attachment 1,” while the solicitation package includes “Generator Consumables Attachment B.” Please confirm that Attachment B is the document intended by the reference to Attachment 1, and that the consumables identified in Attachment B are to be furnished and replaced by the contractor as required during preventive maintenance and included within the applicable PM CLIN pricing. Consumables are outlined in Attachment B.

Work Hours / Load Bank Testing Section 4.3 identifies the monthly PM for the two 600 kW generators and one 500 kW generator as occurring on the second Tuesday of each month from 4:00 AM to 7:00 AM, while the 1250 kW and 750 kW generators may be serviced during normal business hours. Please confirm whether the annual load-bank testing, ATS maintenance, sampling, and other annual maintenance activities may also be performed during normal business hours unless otherwise coordinated with the COR.

The 600’s, and 500 are backing up a critical production line that is old and has issues during power transfers. We require them and their associated equipment to be cycled or maintained prior to that department’s workday start, so they can start the production line on time with no delay. This department is the Consolidated Mail Order Pharmacy (CMOP). All the generator maintenance is to be performed on the second Tuesday of each month, we need the CMOP Generators started and done first.

Transformer Annual Inspection and IR Scan The scope includes quarterly energized transformer inspections as well as an annual inspection that includes additional maintenance activities and an IR scan. The pricing schedule only provides a quarterly transformer CLIN with a quantity of four. Please confirm whether the annual transformer inspection and IR scan are to be included within the pricing for the four quarterly inspections, with one quarterly service incorporating the annual work, or if the annual service is to be priced separately.

Please confirm the intended operating condition for the annual IR scan, as it appears under the annual de-energized inspection section.

Annual Transformer and ATS IR Scanning Procedure The annual infrared (IR) scan of transformer lugs and automatic transfer switches (ATSs) is to be completed while the equipment is energized, prior to any deenergizing procedures. This approach allows for the identification of potential faults under operating conditions, ensuring that any issues are detected before maintenance begins.

Once the IR scan is performed, any necessary repairs should be made during the scheduled deenergized maintenance period. This ensures that faults identified during the scan can be addressed safely while the equipment is not under load.

The IR scan should occur once each year and, whenever possible, should be scheduled close to the time of the annual deenergized maintenance. This coordination facilitates efficient fault resolution and minimizes downtime.

In the event of an emergent issue identified during the scan, immediate corrective action will be taken to address the problem as soon as possible, regardless of the scheduled maintenance cycle.