36E77619B0020-0003025.pdf
PDF Posted
- Solicitation number
- 36E77619B0020
About this file
This federal solicitation is seeking proposals for a parking garage expansion project at the Cleveland VA Medical Center. The scope of work involves completing the fourth deck of an existing parking garage to add 132 parking spaces, as well as improving vertical transportation, lighting, and the building facade.
The solicitation will be issued as an Invitation for Bid evaluated according to procedures in the solicitation document. The project will be awarded as a firm-fixed-price contract using design-bid-build procedures. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses. The estimated value is between $2-5 million. The period of performance is approximately 280 days. The solicitation number is 36E77619B0020 and will be issued by the Department of Veterans Affairs on October 18, 2019.
36E77619B0020 0003 S-302_-_POST-TENSIONED_DETAILS.pdf
View the file
Other files
Show 40 more
Latest 50 of 66 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDED STRANDS ARE
GROUPED WITH
CONTINUOUS STRANDS
#4 T&B
CHAIR W/#4
SUPPORT BAR
SEE TENDON LAYOUT FOR DIMENSIONS
SUPPORT BAR
PLASTIC
ENCAPSULATED
ANCHORAGE
PLAN
SECTION
GREASE FILLED
END CAP
T /2
T /2
CHAIR W/#4 SUPPORT BAR
2" MIN
ENCAPSULATED ANCHORAGE
(2) #4 BACK UP BAR, T&B.
EXTEND 6" PAST LAST ANCHOR
SLEEVE W/ SEAL
AND ADAPTER
#3 HAIRPINS, TOTAL EQUAL
TO NUMBER OF TENDONS +1.
HAIRPINS SHALL BE 18" LONG
3/8 T
NOTE: STRESS MINIMUM OF 2 TENDONS ALONG SLAB EDGE PERPENDICULAR
TO THE BANDED TENDONS BEFORE STRESSING THE BANDED TENDONS
ANCHORAGE AND POCKET
FORMER ATTACHED TO
EDGE FORM
PROTECTIVE SLEEVE
PROTECTIVE SLEEVE TUBEHOLE DRILLED IN EDGE FORM
(2) #4 BACK UP BAR, T&B.
EXTEND 6" PAST LAST ANCHOR
#3 HAIRPINS, TOTAL EQUAL
TO NUMBER OF TENDONS +1.
HAIRPINS SHALL BE 18" LONG
FOR STRESSING
12" MIN
GREASE FILLED END CAP
ENCAPSULATED ANCHORAGE
WEDGES
STEEL RING AT STRESSING END
5"
/8
STRAIGHT
1' - 3"
LENGTH OF TRANSITION CURVE
5' - 0" MIN
M
IN SEE PLAN FOR ELEVATIONS
SUPPORT BARS
(2) #4 CONT, TYP
#3 HAIRPINS @ EA
SIDE OF ANCHOR
18" 5"
TENDON
CHAIR W/#4
SUPPORT BAR
6" 6"
SECTION @ END
PLAN
SLAB EDGE
UNIFORM TENDON PROFILE
(REVERSE PARABOLA)
CL CL
TEMPERATURE TENDONS, SHALL BE
PLACED ON TOP OF UNIFORM
TENDONS WITHIN CENTER 1/3 OF SLAB
*TENDON CENTER OF GRAVITY
ABOVE B/SLAB PER PLAN
C
G
INFLECTION
POINTS
C
G
0.1L1
L1 /2 L1 /2 EQ EQ
SLAB CHAIRS
BEAM TENDONS
W/ SUPPORT BAR
SEE PLAN FOR DIMENSION
EVENLY PER PLAN
SPACE TEMPERATURE TENDONS SEE PLAN FOR DIMENSION
1' - 0"
D
M
IN
T Y P4
STEEL PIPE INSERT (SCH 40) IS
REQ'D WHEN SLAB PENETRATIONS
ARE WITHIN THE 45 DEG ZONE OF
ANCHOR
CLR
6" MIN
D
O R
M
IN
PENETRATIONS FARTHER THAN 2x
THE DIA OR WIDTH BUT NOT LESS
THAN 36" MIN FROM ANCHOR, DO
NOT REQUIRE A STEEL PIPE INSERT.NOTES: PENETRATION WITH DIMENSIONS GREATER
THAN 12" REQUIRE TRIMMER BARS, SEE DETAIL 6/S-302
PT TENDON
PROVIDE HAIRPINS FOR
CURVATURE GREATER THAN 1:12
MIN
1' - 0"
STRAIGHT RUN
3' - 0" MIN
MAX
CURVATURE
C
LR
M
IN
MIN
1 1/2" CLR
24" MIN
#5 T&B x 48" TRIMMER
BAR TYP @ EA CORNER
SEE SLAB OPENING
REINF DETAIL ON S-301
1. ALL OPENINGS W/ A DIM OF 12" OF GREATER SHALL BE TRIMMED
2. REINFORCING IS IN ADDITION TO ANY REINFORCING INDICATED ON PLANS
3. WHERE AN ADJACENT OPENING IS CLOSER THAN SMALLER OPENING DIMENSION, EXTEND TRIM
REINFORCING TO 24" MINIMUM PAST ADJACENT OPENINGS
/4
STANDARD CHAIR W/ #
4 SUPPORT BAR
*SEE SUPPORT PLAN FOR SIZE
C G
S
PT STRAND (TIE
SECURELY IN PLACE)
/4
SLAB BOLSTER*SEE SUPPORT PLAN FOR SIZE
C G
S
PT STRAND (TIE
SECURELY IN PLACE)
ANCHORAGE AND POCKET
FORMER ATTACHED TO EDGE
FORM
(2) #4 BACK UP BAR, T&B CONT
PROTECTIVE SLEEVE
CHAIR W/#4 SUPPORT BAR
STRESSING
12" MIN FOR
HOLED DRILLED
IN EDGE FORM
2" MIN
CONDUIT
(D < T/3), TYP, UNO
(3) CONDUIT PER
GROUP, MAX
3" MIN
#4 T&B @ 12" OC REQ'D WHERE
8" MIN SPACING BETWEEN
GROUPED CONDUITS IS NOT
MAINTAINED
D
TYP UNO
D OR 2" MIN
P-T TENDONS
PER PLAN
TYP
1' - 0"
M
ID
D
LE
T H
IR
D
O F
S
LA
B
P
LA
C E
C O
N D
U
IT
I N
T/SLAB EL
SEE PLAN
8" MIN
NOTES:
1. ALUMINUM MATERIALS SHALL NOT BE EMBEDDED IN CONCRETE
2. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS WHICH INDICATE THE PLACEMENT OF CONDUIT IN SLAB
3. DO NOT PLACE CONDUIT WITHIN 48" OF COLUMN FACE OR SLAB EDGE
4. CONDUIT SHALL NOT TOUCH POST TENSIONING TENDONS. PROVIDE CHAIRS TO SUPPORT CONDUIT
5. CONDUIT PLACEMENT NOT MEETING ABOVE CRITERIA MAY REQUIRE ADDITIONAL REINFORCING AND/OR SLAB THICKENING
#5 @ 12" OC x
48" LONG, T&B
3/4"x 2 1/2"x12" KEY @
48" OC, MAX BETWEEN
TENDONS
P-T TENDON
CONTINUOUS,
SEE PLAN
T /2
T /2
SLAB JT SHALL BE 1/2" WIDE x
1" DEEP BLOCKOUT W/
ELASTOMERIC CAULKING
NOTE:
1. ENGINEER SHALL APPROVE THE USE AND LOCATION OF ALL P-T SLAB CONSTRUCTION JOINTS
2. WHERE 1" DP BLOCKOUT OCCURS, MAINTAIN CLEAR COVER PER PLAN
1/2" CHAMFER
(2) #4 CONT, TYP
DISTRIBUTED
TENDON
CHAIR W/#4
SUPPORT BAR
SECTION @ END
PLAN
SUPPORT BARS
BANDED TENDONS
GREASE FILLED
END CAP
T /2
T /2
CHAIR W/#4 SUPPORT BAR
2" MIN
ENCAPSULATED ANCHORAGE
(2) #4 BACK UP BAR, T&B.
EXTEND 6" PAST LAST ANCHOR
PROTECTIVE SLEEVE
ANCHORAGE AND POCKET
FORMER ATTACHED TO EDGE
FORM
(2) #4 BACK UP BAR, T&B CONT
PROTECTIVE SLEEVE
CHAIR W/#4 SUPPORT BAR
STRESSING
12" MIN FOR
HOLED DRILLED
IN EDGE FORM
2" MIN
INTERMEDIATE CAP
W/PROTECTIVE SLEEVE.
ATTACH CAP AND SLEEVE TO
ANCHORAGE AFTER STRESSING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
PVE ENGINEERING, LLC.
Waterfront Corporate Park III, Suite 101
2000 Georgetowne Drive, Sewickley, PA 15143
Phone: 724-444-1100
Email: info@pve-llc.com
AE Works, LTD.
209 Sandusky Street
Pittsburgh, PA 15212
Phone: 412-287-7333 www.ae-works.com
S-302
POST-TENSIONED DETAILS EXPAND PATIENT PARKING
GARAGE
10701 EAST BOULEVARD, CLEVELAND, OH 44106
161651
05/24/2019 Checker Author
100% BID SET
1" = 1'-0"
ADDED POST TENSION STRANDS DETAIL
1 1/2" = 1'-0"
DEAD END ANCHORAGE DETAIL - BANDED TENDONS
1 1/2" = 1'-0"
STRESSING ANCHORAGE DETAIL - BANDED TENDONS
3" = 1'-0"
PLASTIC ENCAPSULATED ANCHOR
1" = 1'-0"
POST TENSIONED SLAB ANCHORAGE @ BANDED TENDONS
1" = 1'-0"
POST TENSIONED SLAB PROFILE
3/4" = 1'-0"
SLAB PENETRATIONS AT POST-TENSIONED ANCHORS
3/4" = 1'-0"
REINFORCING AT OPENING INTERRUPTING PT TENDONS
3" = 1'-0"
STRAND SUPPORT DETAILS
1 1/2" = 1'-0"
STRESSING ANCHORAGE DETAIL - DISTRIBUTED TENDONS 3/4" = 1'-0"
CONDUITS EMBEDDED IN CONCRETE SLAB
3/4" = 1'-0"
TYPICAL CONSTRUCTION JOINT DETAIL
1" = 1'-0"
POST TENSIONED SLAB ANCHORAGE @ DISTRIBUTED TENDONS
1 1/2" = 1'-0"
DEAD END ANCHORAGE DETAIL - DISTRIBUTED TENDONS
1 1/2" = 1'-0"
INTERMEDIATE STRESSING CONSTRUCTION JOINT DETAIL - DISTRIBUTED TENDONS
# Revisions Date
1 Addendum for Solilcitation 11/22/2019
| Sheets |
| S-001 - GENERAL NOTES |
| S-100 - LEVEL4 FRAMING PLAN |
| S-101 - LEVEL 4 POST-TENSIONING PLAN |
| S-300 - CONCRETE DETAILS |
| S-301 - CONCRETE REPAIR DETAILS |
| S-302 - POST-TENSIONED DETAILS |
| S-305 - CONCRETE BEAM SCHEDULE & DETAILS |
File details come from the government source that posted it. Updated .