This document provides details for a federal contract opportunity to expand an existing patient parking garage at the Cleveland VA Medical Center. The scope of work includes completing construction of a fourth deck to provide 132 additional parking spaces, extending vertical transportation and stairs, improving lighting and façade, and adding a suicide prevention barrier. The Department of Veterans Affairs will issue the solicitation as a Service-Disabled Veteran-Owned Small Business set-aside and accept bids until the date specified. Specifications and drawings will be provided in attachments to the solicitation posted on FBO.gov. The contract will be a firm-fixed-price design-bid-build agreement with a period of performance of approximately 280 calendar days from notice to proceed. The magnitude of construction is estimated between $2 million and $5 million.
36E77619B0020 0003 282300_-_VIDEO_SURVEILLANCE.pdf
View the file
Other files
Show 40 more
Latest 50 of 66 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Project No. 541-378 Louis Stokes Cleveland VAMC AE Works Project No. 18027 Expand Patient Parking Garage
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 1
SECTION 28 23 00
VIDEO SURVEILLANCE
PART 1 – GENERAL
1.1 DESCRIPTION
A. Provide and install an extension to the existing campus Video
Surveillance System, which is identified as the Video Assessment and
Surveillance System hereinafter referred to as the VASS System as specified in this section.
B. This Section includes video surveillance system consisting of cameras, data transmission wiring, and a control station with its associated equipment.
C. Video surveillance system Video assessment & surveillance system shall be integrated with the existing security system architecture at Louis
Stokes VAMC. PERSONAL PROTECTION SYSTEM] that specifies systems integration.
1.2 RELATED WORK
A. Section 01 00 00 - GENERAL REQUIREMENTS. For General Requirements.
B. Section 07 84 00 - FIRESTOPPING. Requirements for firestopping application and use.
C. Section 10 14 00 - SIGNAGE. Requirements for labeling and signs.
D. Section 14 21 00 - ELECTRIC TRACTION ELEVATORS. Requirements for elevators.
E. Section 14 24 00 - HYDRAULIC ELEVATORS. Requirements for elevators.
F. Section 26 05 11 - REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.
Requirements for connection of high voltage.
G. Section 26 05 21 - LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
(600 VOLTS AND BELOW). Requirements for power cables.
H. Section 26 05 41 - UNDERGROUND ELECTRICAL CONSTRUCTION. Requirements for underground installation of wiring.
I. Section 26 56 00 - EXTERIOR LIGHTING. Requirements for perimeter lighting.
J. Section 28 05 00 – COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for general requirements that are common to more than one section in Division 28.
K. Section 28 05 13 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for conductors and cables.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 2
L. Section 28 05 26 - GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for grounding of equipment.
M. Section 28 05 28.33 - CONDUITS AND BACKBOXES FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for infrastructure.
N. Section 28 08 00 - COMMISIONING OF ELECTRONIC SAFETY AND SECURITY.
Requirements for commissioning, systems readiness checklists, and training.
O. Section 28 13 00 - PHYSICAL ACCESS CONTROL SYSTEM. Requirements for physical access control system integration.
P. Section 28 13 16 - PHYSICAL ACCESS CONTROL SYSTEM AND DATABASE
MANAGEMENT. Requirements for control and operation of all security systems.
Q. Section 28 13 53 - SECURITY ACCESS DETECTION. Requirements for screening of personnel and shipments.
R. Section 28 16 00 - INTRUSION DETECTION SYSTEM (IDS). Requirements for alarm systems.
S. Section 28 26 00 - ELECTRONIC PERSONAL PROTECTION SYSTEM (EPPS).
Requirements for emergency and interior communications.
1.3 DEFINITIONS
A. AGC: Automatic gain control.
B. B/W: Black and white.
C. CCD: Charge-coupled device.
D. CIF: Common Intermediate Format CIF images are 352 pixels wide and
88/240 (PAL/NTSC) pixels tall (352 x 288/240).
E. 4CIF: resolution is 704 pixels wide and 576/480 (PAL/NTSC) pixels tall
(704 x 576/480).
F. H.264 (also known as MPEG4 Part 10): a encoding format that compresses video much more effectively than older (MPEG4) standards.
G. ips: Images per second.
H. MPEG: Moving picture experts group.
I. MPEG4: a video encoding and compression standard that uses inter-frame encoding to significantly reduce the size of the video stream being transmitted.
J. NTSC: National Television System Committee.
K. UPS: Uninterruptible power supply.
L. PTZ: refers to a movable camera that has the ability to pan left and right, tilt up and down, and zoom or magnify a scene.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 3
1.4 QUALITY ASSURANCE
A. The Contractor shall be responsible for providing, installing, and the operation of the VASS System as shown. The Contractor shall also provide certification as required.
B. The security system shall be installed and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the security system is stand-alone or a part of a complete Information Technology (IT) computer network.
C. The Contractor or security sub-contractor shall be a licensed security
Contractor as required within the state or jurisdiction of where the installation work is being conducted.
D. Manufacturers Qualifications: The manufacturer shall regularly and presently produce, as one of the manufacturer's principal products, the equipment and material specified for this project, and shall have manufactured the item for at least three years.
E. Product Qualification:
1. Manufacturer's product shall have been in satisfactory operation, on three installations of similar size and type as this project, for approximately three years.
2. The Government reserves the right to require the Contractor to submit a list of installations where the products have been in operation before approval.
F. Contractor Qualification:
1. The Contractor or security sub-contractor shall be a licensed security Contractor with a minimum of five (5) years experience installing and servicing systems of similar scope and complexity.
The Contractor shall be an authorized regional representative of the
Video Assessment and Surveillance System’s (VASS) manufacturer. The
Contractor shall provide four (4) current references from clients with systems of similar scope and complexity which became operational in the past three (3) years. At least three (3) of the references shall be utilizing the same system components, in a similar configuration as the proposed system. The references must include a current point of contact, company or agency name, address, telephone number, complete system description, date of completion, and approximate cost of the project. The owner reserves the option
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 4 to visit the reference sites, with the site owner’s permission and representative, to verify the quality of installation and the references’ level of satisfaction with the system. The Contractor shall provide copies of system manufacturer certification for all technicians. The Contractor shall only utilize factory-trained technicians to install, program, and service the VASS. The
Contractor shall only utilize factory-trained technicians to install, terminate and service cameras, control, and recording equipment. The technicians shall have a minimum of five (5) continuous years of technical experience in electronic security systems. The Contractor shall have a local service facility. The facility shall be located within 60 miles of the project site. The local facility shall include sufficient spare parts inventory to support the service requirements associated with this contract. The facility shall also include appropriate diagnostic equipment to perform diagnostic procedures. The COTR reserves the option of surveying the company’s facility to verify the service inventory and presence of a local service organization.
2. The Contractor shall provide proof project superintendent with BICSI
Certified Commercial Installer Level 1, Level 2, or Technician to provide oversight of the project.
3. Cable installer must have on staff a Registered Communication
Distribution Designer (RCDD) certified by Building Industry
Consulting Service International. The staff member shall provide consistent oversight of the project cabling throughout design, layout, installation, termination and testing.
G. Service Qualifications: There shall be a permanent service organization maintained or trained by the manufacturer which will render satisfactory service to this installation within four hours of receipt of notification that service is needed. Submit name and address of service organizations.
1.5 SUBMITTALS
A. Submit below items in conjunction with Master Specification Sections 01
33 23, Shop Drawings, Product Data, and Samples, and Section 02 41 00, Demolition Drawings.
B. Provide certificates of compliance with Section 1.4, Quality Assurance.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 5
C. Provide a pre-installation and as-built design package in both electronic format and on paper, minimum size 1220 x 1220 millimeters
(48 x 48 inches); drawing submittals shall be per the established project schedule.
D. Pre-installation design and as-built packages shall include, but not be limited to:
1. Index Sheet that shall:
a. Define each page of the design package to include facility name, building name, floor, and sheet number.
b. Provide a list of all security abbreviations and symbols.
c. Reference all general notes that are utilized within the design package.
d. Specification and scope of work pages for all security systems that are applicable to the design package that will:
1) Outline all general and job specific work required within the design package.
2) Provide a device identification table outlining device
Identification (ID) and use for all security systems equipment utilized in the design package.
2. Floor plans, site plans, and enlarged plans shall:
a. Include a title block as defined above.
b. Define the drawings scale in both standard and metric measurements.
c. Provide device identification and location.
d. Address all signal and power conduit runs and sizes that are associated with the design of the electronic security system and other security elements (e.g., barriers, etc.).
e. Identify all pull box and conduit locations, sizes, and fill capacities.
f. Address all general and drawing specific notes for a particular drawing sheet.
3. A riser drawing for each applicable security subsystem shall:
a. Indicate the sequence of operation.
b. Relationship of integrated components on one diagram.
c. Include the number, size, identification, and maximum lengths of interconnecting wires.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 6
d. Wire/cable types shall be defined by a wire and cable schedule.
The schedule shall utilize a lettering system that will correspond to the wire/cable it represents (example: A = 18 AWG/1
Pair Twisted, Unshielded). This schedule shall also provide the manufacturer’s name and part number for the wire/cable being installed.
4. A system drawing for each applicable security system shall:
a. Identify how all equipment within the system, from main panel to device, shall be laid out and connected.
b. Provide full detail of all system components wiring from point-to-point.
c. Identify wire types utilized for connection, interconnection with associate security subsystems.
d. Show device locations that correspond to the floor plans.
e. All general and drawing specific notes shall be included with the system drawings.
5. A schedule for all of the applicable security subsystems shall be included. All schedules shall provide the following information:
a. Device ID.
b. Device Location (e.g. site, building, floor, room number, location, and description).
c. Mounting type (e.g. flush, wall, surface, etc.).
d. Power supply or circuit breaker and power panel number.
e. In addition, for the VASS Systems, provide the camera ID, camera type (e.g. fixed or pan/tilt/zoom (P/T/Z), lens type (e.g. for fixed cameras only) and housing model number.
6. Detail and elevation drawings for all devices that define how they were installed and mounted.
E. Pre-installation design packages shall be reviewed by the Contractor along with a VA representative to ensure all work has been clearly defined and completed. All reviews shall be conducted in accordance with the project schedule. There shall be four (4) stages to the review process:
1. 35 percent
2. 65 percent
3. 90 percent
4. 100 percent Commented [HB1]: Ask the VA if they want to reduce this. A draft and a final should be sufficient.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 7
F. Provide manufacturer security system product cut-sheets. Submit for approval at least 30 days prior to commencement of formal testing, a
Security System Operational Test Plan. Include procedures for operational testing of each component and security subsystem, to include performance of an integrated system test.
G. Submit manufacture’s certification of Underwriters Laboratories, Inc.
(UL) listing as specified. Provide all maintenance and operating manuals per the VA General Requirements, Section 01 00 00, GENERAL
REQUIREMENTS.
H. Submit completed System Readiness Checklists provided by the
Commissioning Agent and completed by the contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 28 08 00 COMMISSIONING OF ELECTRONIC
SAFETY AND SECURITY SYSTEMS.
1.6 APPLICABLE PUBLICATIONS
A. The publications listed below (including amendments, addenda, revisions, supplement, and errata) form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American National Standards Institute (ANSI)/Electronic Industries
Alliance (EIA):
330-09 .................Electrical Performance Standards for CCTV
Cameras
375A-76 ................Electrical Performance Standards for CCTV
Monitors
C. Institute of Electrical and Electronics Engineers (IEEE):
C62.41-02 ..............IEEE Recommended Practice on Surge Voltages in
Low-Voltage AC Power Circuits
802.3af-08 .............Power over Ethernet Standard
D. Federal Communications Commision (FCC):
(47 CFR 15) Part 15 Limitations on the Use of Wireless Equipment/Systems
E. National Electrical Contractors Association (NECA):
303-2005 ...............Installing Closed Circuit Television (CCTV)
Systems
F. National Fire Protection Association (NFPA):
70-08 ..................Article 780-National Electrical Code
G. Federal Information Processing Standard (FIPS):
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 8
140-2-02 ...............Security Requirements for Cryptographic Modules
H. Underwriters Laboratories, Inc. (UL):
983-06 .................Standard for Surveillance Camera Units
3044-01 ................Standard for Surveillance Closed Circuit
Television Equipment
1.7 COORDINATION
A. Coordinate arrangement, mounting, and support of video surveillance equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
3. To allow right of way for piping and conduit installed at required slope.
4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.
B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.
C. Coordinate location of access panels and doors for video surveillance items that are behind finished surfaces or otherwise concealed.
1.8 WARRANTY OF CONSTRUCTION
A. Warrant VASS System work subject to the Article “Warranty of
Construction” of FAR clause 52.246-21.
B. Demonstration and training shall be performed prior to system acceptance.
PART 2 – PRODUCTS
2.1 GENERAL
B. Surge Protection: Protect components from voltage surges originating external to equipment housing and entering through power, communication, signal, control, or sensing leads. Include surge protection for external wiring of each conductor entry connection to components.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 9
C. Power Connections: Comply with requirements in Section 28 05 00 COMMON
WORK REQUIREMENTS FOR ELECTRONIC SAFETY AND SECURITY, Part 2, as recommended by manufacturer for type of line being protected.
D. Tamper Protection: Tamper switches on enclosures, control units, pull boxes, junction boxes, cabinets, and other system components shall initiate a tamper-alarm signal when unit is opened or partially disassembled. Control-station, control-unit alarm display shall identify tamper alarms and indicate locations.
2.2 CAMERAS
A. All Cameras will be EIA 330 and UL 1.Minimum Protection for Power
Connections 120 V and more: Auxiliary panel suppressors shall comply with requirements in Section 28 05 00 COMMON WORK REQUIREMENTS FOR
ELECTRONIC SAFETY AND SECURITY, Part 2.
B. Minimum Protection for Communication, Signal, Control, and Low-Voltage
983 compliant as well as:
1. Will be charge coupled device (CCD cameras and shall conform to
National Television System Committee (NTSC) formatting.
2. Fixed cameras shall be color and the primary choice for monitoring following the activities described below. Pan/Tilt/Zoom (P/T/Z) cameras shall be color and are to be utilized to complement the fixed cameras.
3. Camera power shall be identical to the existing system unless otherwise approved by the Government.
5. Shall be rated for continuous operation under the environmental conditions listed in Part 1, Project Conditions.
6. Will be home run to a monitoring and recording device via a controlling device such as a matrix switcher or network server and monitored on a 24 hour basis at a designated Security Management
System location.
7. Each function and activity shall be addressed within the system by a unique user defined name, with minimum of twenty (20) characters.
The use of codes or mnemonics identifying the VASS action shall not be accepted.
8. Shall come with built-in video motion detection that shall automatically monitor and process information from each camera. The camera motion detection shall detect motion within the camera's
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 10 field of view and provide automatic visual, remote alarms as a result of detected motion.
9. Shall be programmed to digitally flip from color to black and white at dusk and vice versa at low light conditions.
10. Will be fitted with AI/DC lenses to ensure the image quality under different light conditions.
11. P/T/Z cameras shall be utilized in a manner that they complement fixed cameras and shall not be used as a primary means of monitoring activity.
12. Dummy or fake cameras will not be utilized at any time.
13. Appropriate signage shall be designed, provided, and posted that notifies people that an area is under camera surveillance.
2.3 DIGITAL BASED VIDEO MANAGEMENT SYSTEM
A.
2.6 VIDEO CAMERAS
A. The cameras shall be high-resolution color video cameras with wide dynamic range capturing capability.
B. The camera shall meet or exceed the following specifications:
1. The image capturing device shall be a [1/3]/[1/4]-inch image sensor designed for capturing wide dynamic images.
a. The image capturing device shall have a separate analog-to-digital converter for every pixel.
b. The image capturing device shall sample each pixel multiple times per second.
c. The dynamic range shall be 95 dB typical and 120 dB maximum.
3. The camera shall optimize each pixel independently.
4. The camera shall have onscreen display menus for programming of the camera’s settings.
5. The signal system shall be NTSC.
C. The camera shall have composite video output.
D. The camera shall come with a manual varifocal lens.
E. The video output shall be composite: 1.0 volts peak-to-peak at 75-ohm load.
H. Fixed Color Camera
Commented [HB2]: Deleted this entire section based on the assumption that the existing garage system is digital. This will have to go back in if it is analog.
Commented [HB3]: Deleted since they are extending an existing system. None of this applies.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 11
1. The camera shall be a high-resolution color video camera with wide dynamic range capturing capability.
2. Comply with UL 639.
3. Pickup Device: [1/3]/[1/4] CCD interline transfer.
4. Signal-to-Noise Ratio: Not less than 50 dB, with the camera AGC off.
5. With AGC, manually selectable on or off.
6. Manually selectable modes for backlight compensation or normal lighting.
7. Scanning Synchronization: Determined by external synch over the coaxial cable. Camera shall revert to internally generated synchronization on loss of external synch signal.
8. White Balance: Auto-tracing white balance, with manually selectable fixed balance option.
SPEC WRITER NOTE: Copy and edit table in following paragraph to accommodate for all fixed analog color camera models in the project.
9. Fixed Color Cameras Technical Characteristics:
Pickup device 1/3" interline transfer CCD
Total pixels NTSC: 811(H) x 508(V)
Effective pixels NTSC: 768(H) x 494(V)
Resolution 500 TV lines
Sync. System Internal Sync
Scanning system NTSC: 525 Lines/60 Fields
S/N ratio More than 48 dB
Electronic shutter Auto 1/60 (1/50) ~1/100,000 sec.
Min. illumination 0.2 lux F2.0
Video output Composite 1.0 Vp-p/75 ohm
White balance Auto
Automatic gain control ON
Frequency horizontal NTSC: 15.734 KHz
Frequency vertical NTSC: 59.94Hz
Lens type Board lens/[DC]/[AI] varifocal lens
Focal length [3-12mm]<insert values>
Power source DC12V/500mA or AC24/500mA
Power consumption < 3W (Max)
Commented [HB4]: Need this info from VA so we can match the existing system. Or we can change the paragraph to include a site investigation by the vendor.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 12
10. [Fixed color camera shall be enclosed in dome and have board mounted varifocal lens].
11. Camera accessories shall include:
a. Surface mount adapter
b. Wall mount adapter
c. Flush mount adapter
d. <list>
2.8 POWER SUPPLIES
A. Power supplies shall be a low-voltage power supplies matched for voltage and current requirements of cameras and accessories, type as recommended by camera[, infrared illuminator,] and lens manufacturer.
SPEC WRITER NOTE: Revise sub-paragraphs below as required by the project. Specify power supply with sufficient number of outputs for all devices in the project.
Minimum of one output per camera shall be provided.
B. Technical specifications:
1. Input: 115VAC, 50/60Hz, 2.7 amps
2. Outputs:
a. Number of outputs, [16] <insert number of outputs>
b. [Fuse/PTC] <insert type> protected, power limited
c. Output voltage & power:
1) 24VAC @ 12.5 amps (300VA) or 28VAC @ 10 amp (280VA) supply current
3. Illuminated power disconnect circuit breaker with manual reset
4. Surge suppression
5. Camera synchronization
6. [Wall/Rack] <insert mount type> mount.
7. Enclosure: NEMA 250, Type [1] [3] [4X] <Insert enclosure type>.
SPEC WRITER NOTE: Leave paragraph below if VASS designed requires analog cameras to be connected to IP camera based system.
2.9 INFRARED ILLUMINATORS
A. Lighting fixtures that emit light only in the infrared spectrum, suitable for use with cameras indicated, for nighttime surveillance, without emitting visible light.
1. Field-Selectable Beam Patterns: Narrow, medium, and wide.
2. Rated Lamp Life: More than 8000 hours
3. Power Supply: [12-VAC/DC] [120-VAC].
Commented [HB5]: Make list from drawings.
Commented [HB6]: Match existing power
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 13
B. Area Coverage: Illumination to 50 m (150 feet) in a narrow beam pattern.
C. Exterior housings shall be suitable for same environmental conditions
2.12 WIRES AND CABLES
A. Shall meet or exceed the manufactures recommendation for power and signal.
B. Will be carried in an enclosed conduit system, utilizing electromagnetic tubing (EMT) to include the equivalent in flexible metal, rigid galvanized steel (RGS) to include the equivalent of liquid tight, polyvinylchloride (PVC) schedule 40 or 80.
C. All conduits will be sized and installed per the NEC. All security system signal and power cables that traverse or originate in a high security office space will contained in either EMT or RGS conduit.
D. All conduit, pull boxes, and junction boxes shall be clearly marked with colored permanent tape or paint that will allow it to be distinguished from all other conduit and infrastructure.
E. Conduit fills shall not exceed 50 percent unless otherwise documented.
F. A pull string shall be pulled along and provided with signal and power cables to assist in future installations.
G. At all locations where there is a wall penetration or core drilling is conducted to allow for conduit to be installed, fire stopping materials shall be applied to that area
H. High voltage and signal cables shall not share the same conduit and shall be kept separate up to the point of connection. High voltage for the security system shall be defined as any cable or sets of cables carrying 30 VDC/VAC or higher.
I. For all equipment that is carrying digital data between the Physical
Access Control System and Database Management or at a remote monitoring station, shall not be less that 20 AWG and stranded copper wire for each conductor. The cable or each individual conductor within the cable shall have a shield that provides 100% coverage. Cables with a single overall shield shall have a tinned copper shield drain wire.
J. All cables and conductors, except fiber optic cables, that act as a control, communication, or signal lines shall include surge protection.
Surge protection shall be furnished at the equipment end and additional triple electrode gas surge protectors rated for the application on each
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 14 wire line circuit shall be installed within 1 m. (3 ft.) of the building cable entrance. The inputs and outputs shall be tested in both normal and common mode using the following wave forms:
1. A 10 microsecond rise time by 1000 microsecond pulse width waveform with a peak voltage of 1500 watts and peak current of 60 amperes.
2. An 8 microsecond rise time by 20 microsecond pulse width wave form with a peak voltage of 1000 volts and peak current of 500 amperes.
K. The surge suppression device shall not attenuate or reduce the video or sync signal under normal conditions. Fuses and relays shall not be used as a means of surge protection.
L. Coaxial Cables
1. All video signal cables for the VASS System, with exception to the
PoE cameras, shall be a coaxial cable and have a characteristic impedance of 75 ohms plus or minus 3 ohms.
2. For runs up to 750 feet use of an RG-59/U is required. The RG-59/U shall be shielded which provides a minimum of 95 percent coverage, with a stranded copper center conductor of a minimum 23 AWG, polyethylene insulation, and black non-conductive polyvinylchloride
(PVC) jacket.
3. For runs between 750 feet and 1250 feet, RG-6/U is required. RG-6/U shall be shielded which provides a minimum of 95 percent coverage, with a stranded copper center conductor of a minimum 18 AWG, polyethylene insulation, and black non-conductive polyvinylchloride
(PVC) jacket.
4. For runs of 1250 to 2750 feet, RG-11/U is required. RG-11/U shall be shielded which provides a minimum of 95 percent coverage, with a stranded copper center conductor of a minimum 14 AWG, polyethylene insulation, and black non-conductive polyvinylchloride (PVC) jacket.
5. All runs greater than 2750 feet will be substituted with a fiber optic cable. If using fiber optics as a signal carrier then the following equipment will be utilized:
a. Multimode fiber optic cable a minimum size of 62 microns
b. Video transmitter, installed at the camera that utilizes 12 VDC or 24 VAC for power.
c. Video receiver, installed at the switcher.
6. RG-59/U Technical Characteristics
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 15
AWG 22
Stranding 7x29
Conductor Diameter .031 in.
Conductor Material BCC
Insulation Material Gas-injected FHDPE
Insulation Diameter .145 in.
Outer Shield Type Braid/Braid
Outer Jacket Material PVC
Overall Nominal Diameter .242 in.
UL Temperature Rating 75°C
Nom. Characteristic Impedance 75 Ohms
Nom. Inductance 0.094 μH/ft
Nom. Capacitance Conductor to Shield 17.0 pF/ft
Nom. Velocity of Propagation 80 %
Nom. Delay 1.3 ns/ft
Nom. Conductor DC Resistance @ 20°C
12.2 Ohms/1000 ft
Nom. Outer Shield DC Resistance @ 20°C
2.4 Ohms/1000 ft
Max. Operating Voltage UL 300 V RMS
7. RG-6/U Technical Characteristics:
AWG 18
Stranding 7x27
Conductor Diameter .040 in.
Conductor Material BC
Insulation Material Gas-injected FHDPE
Insulation Diameter .180 in.
Outer Shield Material Trade Name Duofoil
Outer Shield Type Tape/Braid
Outer Shield %Coverage 100 %
Outer Jacket Material PVC
Overall Nominal Diameter .274 in.
Nom. Characteristic Impedance
75 Ohms
Nom. Inductance 0.106 μH/ft
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 16
Nom. Capacitance Conductor to Shield 16.2 pF/ft
Nom. Velocity of Propagation
82 %
Nom. Delay 1.24 ns/ft
Nom. Conductor DC Resistance
6.4 Ohms/1000 ft
Nominal Outer Shield DC Resistance @ 20°C
2.8 Ohms/1000 ft
Max. Operating Voltage UL 300 V RMS
8. RG-11/U Technical Characteristics:
AWG 15
Stranding 19x27
Conductor Diameter .064 in.
Conductor Material BC
Insulation Material Gas-injected FHDPE
Insulation Diameter .312 in.
Inner Shield Type Braid
Inner Shield Material BC - Bare Copper
Inner Shield %Coverage 95 %
Inner Jacket Material PE – Polyethylene
Inner Jacket Diameter .391 in.
Outer Shield Type Braid
Outer Shield Material BC - Bare Copper
Outer Shield %Coverage 95 %
Outer Jacket Material Trade Name Belflex
Outer Jacket Material PVC Blend
Overall Nominal Diameter .520 in.
Operating Temperature Range -35°C To +75°C
Non-UL Temperature Rating 75°C
Nom. Characteristic Impedance 75 Ohms
Nom. Inductance 0.097 μH/ft
Nom. Capacitance Conductor to Shield 17.3 pF/ft
Nom. Velocity of Propagation 78 %
Nom. Delay 1.30 ns/ft
Nom. Conductor DC Resistance 3.1 Ohms/1000 ft
Nom. Inner Shield DC 1.8 Ohms/1000 ft
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 17
Resistance
Nom. Outer Shield DC Resistance
1.4 Ohms/1000 ft
Max. Operating Voltage Non-UL 300 V RMS
9. Signal Cables:
a. Signal wiring for PoE cameras depends on the distance the camera is being installed from either a hub or the server.
b. If the camera is up to 300 ft from a hub or the server, then use a shielded UTP category 5 (CAT-V) cable a with standard RJ-45 connector at each end. The cable with comply with the Power over
Ethernet, IEEE802.3af, Standard.
c. If the camera is over 300 ft from a hub or server then utilize a multimode fiber optic cable with a minimum size of 62 microns.
d. Provide a separate cable for power.
e. CAT-5 Technical Characteristics:
Number of Pairs 4
Total Number of Conductors 8
AWG 24
Stranding Solid
Conductor Material BC - Bare Copper
Insulation Material PO – Polyolefin
Overall Nominal Diameter .230 in.
IEC Specification 11801 Category 5
TIA/EIA Specification 568-B.2 Category 5e
Max. Capacitance Unbalance (pF/100 m) 150 pF/100 m
Nom. Velocity of Propagation 70 %
Max. Delay (ns/100 m) 538 @ 100MHz
Max. Delay Skew (ns/100m) 45 ns/100 m
Max. Conductor DC Resistance 9.38 Ohms/100
Max. DCR Unbalance@ 20°C 3 %
Max. Operating Voltage UL 300 V RMS
10. Fiber Optic Cables Technical Characteristics:
Fiber Type 62.5 Micron
Number of Fibers 4
Core Diameter 6 2.5 +/- 2.5 microns
Core Non-Circularity 5% Maximum
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 18
Clad Diameter 125 +/- 2 microns
Clad Non-Circularity 1% Maximum
Core-clad Offset 1.5 Microns Maximum
Primary Coating Material Acrylate
Primary Coating Diameter 245 +/- 10 microns
Secondary Coating Material Engineering Thermoplastic
Secondary Coating Diameter 900 +/- 50 microns
Strength Member Material Aramid Yarn
Outer Jacket Material PVC
Outer Jacket Color Orange
Overall Diameter .200 in.
Numerical Aperture .275
Maximum Gigabit Ethernet 300 meters
Maximum Gigabit Ethernet 550 meters
11. Power Cables
a. Will be sized accordingly and shall comply with the NEC. High voltage power cables will be a minimum of three conductors, 14
AWG, stranded, and coated with a non-conductive polyvinylchloride
(PVC) jacket. Low voltage cables will be a minimum of 18 AWG, stranded and non-conductive polyvinylchloride (PVC) jacket.
b. Will be utilized for all components of the VASS System that require either a 110 VAC 60 Hz or 220 VAC 50 Hz input. Each feed will be connected to a dedicated circuit breaker at a power panel that is primarily for the security system.
c. All equipment connected to AC power shall be protected from surges. Equipment protection shall withstand surge test waveforms described in IEEE C62.41. Fuses shall not be used as a means of surge protection.
d. Shall be rated for either 110 or 220 VAC, 50 or 60 Hz, and shall comply with VA Master Spec 26 05 21 Low Voltage Electrical Power
Conductors and Cables (600 Volts and Below).
e. Low Voltage Power Cables
1) Shall be a minimum of 18 AWG, Stranded and have a polyvinylchloride outer jacket.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 19
2) Cable size shall determined using a basic voltage over distance calculation and shall comply with the NEC’s requirements for low voltage cables.
PART 3 - EXECUTION
3.1. GENERAL
A. Installation: The Contractor shall install all system components including Owner furnished equipment, and appurtenances in accordance with the manufacturer’s instructions, ANSI C2 and as shown, and shall furnish all necessary connectors, terminators, interconnections, services, and adjustments required for a complete and operable data transmission system.
B. Identification and Labeling: The Contractor shall supply permanent identification labels for each cable at each end that will appear on the as-built drawings. The labeling format shall be identified and a complete record shall be provided to the Owner with the final documentation. Each cable shall be identified by type or signal being carried and termination points. The labels shall be printed on letter size label sheets that are self laminated vinyl that can be printed from a computer data base or spread sheet. The labels shall be E-Z code WES12112 or equivalent.
1. The Contractor shall provide all personnel, equipment, instrumentation, and supplies necessary to perform all testing.
C. Transient Voltage Surge Suppressors (TVSS): The Contractor shall mount
TVSS within 3 m (118 in) of equipment to be protected inside terminal cabinets or suitable NEMA 1 enclosures. Terminate off-premise conductors on input side of device. Connect the output side of the device to the equipment to be protected. Connect ground lug to a low impedance earth ground (less than 10 ohms) via Number 12 AWG insulated, stranded copper conductor.
D. Contractor’s Field Test: The Contractor shall verify the complete operation of the data transmission system during the Contractor’s Field
Testing. Field test shall include a bit error rate test. The
Contractor shall perform the test by sending a minimum of 1,000,000 bits of data on each DTM circuit and measuring the bit error rate. The bit error rate shall not be greater than one (1) bit out of each
100,000 bits sent for each dial-up DTM circuit, and one (1) bit out of
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 20
1,000,000 bits sent for each leased or private DTM circuit. The
Contractor shall submit a report containing results of the field test.
E. Acceptance Test and Endurance Test: The wire line data transmission system shall be tested as a part of the completed IDS and EECS during the Acceptance test and Endurance Test as specified.
F. Identification and Labeling: The Contractor shall supply identification tags or labels for each cable. Cable shall be labeled at both end points and at intermediate hand holes, manholes, and junction boxes. The labeling format shall be identified and a complete record shall be provided to the Owner with the final documentation.
Each cable shall be identified with type of signal being carried and termination points.
3.2 INSTALLATION
A. System installation shall be in accordance with NECA 303, manufacturer and related documents and references, for each type of security subsystem designed, engineered and installed.
B. Components shall be configured with appropriate “service points” to pinpoint system trouble in less than 30 minutes.
C. The Contractor shall install all system components including Government furnished equipment, and appurtenances in accordance with the manufacturer's instructions, documentation listed in Sections 1.5 of this document, and shall furnish all necessary connectors, terminators, interconnections, services, and adjustments required for a complete and operable system.
D. The VASS System will be designed, engineered, installed, and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the system is a stand alone or a complete network.
E. For integration purposes, the VASS System shall be integrated where appropriate with the following associated security subsystems:
1. PACS:
a. Provide 24 hour coverage of all entry points to the perimeter and agency buildings, as well as all emergency exits utilizing a fixed color camera.
b. Record cameras on a 24 hours basis.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 21
c. Be programmed go into an alarm state when an emergency exit is opened, and notify the Physical Access Control System and
Database Management of an alarm event.
2. IDS:
a. Provide a recorded alarm event via a color camera that is connected to the IDS system by either direct hardwire or a security system computer network.
b. Record cameras on a 24 hours basis.
c. Be programmed to go into an alarm state when an IDS device is put into an alarm state, and notify the PACS.
d. For additional VASS System requirements as they relate to the
IDS, refer to Section 28 16 00 “INTRUSION DETECTION”.
3. Security Access Detection:
a. Provide full coverage of all vehicle and lobby entrance screening areas utilizing a fixed color camera.
b. Record cameras on a 24 hours basis.
c. The VASS System should have facial recognition software to assist in identifying individuals for current and future purposes.
4. EPPS:
a. Provide a recorded alarm event via a color camera that is connected to the EPPS system by either direct hardwire or a security system computer network.
b. Record cameras on a 24 hours basis.
c. Be programmed to go into an alarm state when an emergency call box or duress alarm/panic device is activated, and notify the
Physical Access Control System and Database Management of an alarm event.
F. Integration with these security subsystems shall be achieved by computer programming or the direct hardwiring of the systems.
G. For programming purposes refer to the manufacturers requirements for correct system operations. Ensure computers being utilized for system integration meet or exceed the minimum system requirements outlined on the systems software packages.
H. A complete VASS System shall be comprised of, but not limited to, the following components:
1. Cameras
2. Lenses
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 22
3. Video Display Equipment
4. Camera Housings and Mounts
5. Controlling Equipment
6. Recording Devices
7. Wiring and Cables
I. The Contractor shall visit the site and verify that site conditions are in agreement/compliance with the design package. The Contractor shall report all changes to the site or conditions that will affect performance of the system to the Contracting Officer in the form of a report. The Contractor shall not take any corrective action without written permission received from the Contracting Officer.
J. Existing Equipment
1. The Contractor shall connect to and utilize existing video equipment, video and control signal transmission lines, and devices as outlined in the design package. Video equipment and signal lines that are usable in their original configuration without modification may be reused with Contracting Officer approval.
2. The Contractor shall perform a field survey, including testing and inspection of all existing video equipment and signal lines intended to be incorporated into the VASS System, and furnish a report to the Contracting Officer as part of the site survey report. For those items considered nonfunctioning, provide (with the report) specification sheets, or written functional requirements to support the findings and the estimated cost to correct the deficiency. As part of the report, the Contractor shall include a schedule for connection to all existing equipment.
3. The Contractor shall make written requests and obtain approval prior to disconnecting any signal lines and equipment, and creating equipment downtime. Such work shall proceed only after receiving
Contracting Officer approval of these requests. If any device fails after the Contractor has commenced work on that device, signal or control line, the Contractor shall diagnose the failure and perform any necessary corrections to the equipment.
4. The Contractor shall be held responsible for repair costs due to
Contractor negligence, abuse, or incorrect installation of equipment.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 23
5. The Contracting Officer shall be provided a full list of all equipment that is to be removed or replaced by the Contractor, to include description and serial/manufacturer numbers where possible.
The Contractor shall dispose of all equipment that has been removed or replaced based upon approval of the Contracting Officer after reviewing the equipment removal list. In all areas where equipment is removed or replaced the Contractor shall repair those areas to match the current existing conditions.
K. Enclosure Penetrations: All enclosure penetrations shall be from the bottom of the enclosure unless the system design requires penetrations from other directions. Penetrations of interior enclosures involving transitions of conduit from interior to exterior, and all penetrations on exterior enclosures shall be sealed with rubber silicone sealant to preclude the entry of water and will comply with VA Master
Specification 07 84 00, Firestopping. The conduit riser shall terminate in a hot-dipped galvanized metal cable terminator. The terminator shall be filled with an approved sealant as recommended by the cable manufacturer and in such a manner that the cable is not damaged.
L. Cold Galvanizing: All field welds and brazing on factory galvanized boxes, enclosures, and conduits shall be coated with a cold galvanized paint containing at least 95 percent zinc by weight.
M. Interconnection of Console Video Equipment: The Contractor shall connect signal paths between video equipment as specified by the OEM.
Cables shall be as short as practicable for each signal path without causing strain at the connectors. Rack mounted equipment on slide mounts shall have cables of sufficient length to allow full extension of the slide rails from the rack.
N. Cameras:
1. Install the cameras with the focal length lens as indicated for each zone.
2. Connect power and signal lines to the camera.
3. Aim camera to give field of view as needed to cover the alarm zone.
4. Aim fixed mounted cameras installed outdoors facing the rising or setting sun sufficiently below the horizon to preclude the camera looking directly at the sun.
5. Focus the lens to give a sharp picture (to include checking for day and night focus and image quality) over the entire field of view
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 24
6. Synchronize all cameras so the picture does not roll on the monitor when cameras are selected.
7. PTZ cameras shall have all preset positions and privacy areas defined and programmed.
T. Network Switch:
1. Install the network switch per design and construction documents, and as specified by the OEM.
2. Connect network switch to AC power (UPS).
3. Connect network cameras to network switch.
4. Configure the network switch per manufacturer’s recommendation and project requirements.
U.
5. Provide recording unit programming per VA guidance and the requirements provided by the Owner. Programming shall include:
a. Camera names
b. Screen views
c. Camera recording schedules (continuous and event) driven recording. Events include alarms from other systems (sensors), manual input, and video motion detection.
d. Video detection zones for each camera requiring video motion detection
e. Alarm interface
f. Alarm outputs
g. GUI maps, views, icons and actions
h. PTZ controls (presets, time schedules for privacy zones etc.)
i. Reports
V. Video Recording Equipment:
1. Install the video recording equipment as shown in the design and construction documents, and as specified by the OEM.
2. Connect video signal inputs and outputs as shown and specified.
3. Connect alarm signal inputs and outputs as shown and specified.
4. Connect video recording equipment to AC power.
5. Program the video recording equipment;
a. Recording schedules
b. Camera caption
W. Video Signal Equipment:
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 25
1. Install the video signal equipment as shown in the design and construction documents, and as specified by the OEM.
2. Connect video or signal inputs and outputs as shown and specified.
3. Terminate video inputs as required.
4. Connect alarm signal inputs and outputs as required.
5. Connect control signal inputs and outputs as required
6. Connect electrically powered equipment to AC power.
X. Camera Housings, Mounts, and Poles:
1. Install the camera housings and mounts as specified by the manufacturer and as shown, provide mounting hardware sized appropriately to secure each camera, housing and mount with maximum wind and ice loading encountered at the site.
2. Provide a foundation for each camera pole as specified and shown.
3. Provide a ground rod for each camera pole and connect the camera pole to the ground rod as specified in Division 26 of the VA Master
Specification and the VA Electrical Manual 730.
4. Provide electrical and signal transmission cabling to the mount location via a hardened carrier system from the Physical Access
Control System and Database Management to the device.
5. Connect signal lines and AC power to the housing interfaces.
6. Connect pole wiring harness to camera.
3.3 SYSTEM START-UP
A. The Contractor shall not apply power to the VASS System until the following items have been completed:
1. VASS System equipment items and have been set up in accordance with manufacturer's instructions.
2. A visual inspection of the VASS System has been conducted to ensure that defective equipment items have not been installed and that there are no loose connections.
3. System wiring has been tested and verified as correctly connected as indicated.
4. All system grounding and transient protection systems have been verified as installed and connected as indicated.
5. Power supplies to be connected to the VASS System have been verified as the correct voltage, phasing, and frequency as indicated.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 26
B. The Commissioning Agent will observe startup and contractor testing of selected equipment. Coordinate the startup and contractor testing schedules with the Resident Engineer and Commissioning Agent. Provide a minimum of 7 days prior notice.
C. Satisfaction of the above requirements shall not relieve the Contractor of responsibility for incorrect installation, defective equipment items, or collateral damage as a result of Contractor work efforts.
3.4 SUPLEMENTAL CONTRACTOR QUIALITY CONTROL
A. The Contractor shall provide the services of technical representatives who are familiar with all components and installation procedures of the installed VASS System; and are approved by the Contracting Officer.
B. The Contractor will be present on the job site during the preparatory and initial phases of quality control to provide technical assistance.
C. The Contractor shall also be available on an as needed basis to provide assistance with follow-up phases of quality control.
D. The Contractor shall participate in the testing and validation of the system and shall provide certification that the system installed is fully operational as all construction document requirements have been fulfilled.
3.5 COMMISSIONING
A. Provide commissioning documentation in accordance with the requirements of Section 28 08 00 – COMMISSIONING OF ELECTRONIC SAFETY AND SECURITY
SYSTEMS for all inspection, start up, and contractor testing required above and required by the System Readiness Checklist provided by the
Commissioning Agent.
B. Components provided under this section of the specification will be tested as part of a larger system. Refer to Section 28 08 00 –
“COMMISSIONING OF ELECTRONIC SAFETY AND SECURITY SYSTEMS” and related sections for contractor responsibilities for system commissioning.
3.6 DEMONSTRATION AND TRAINING
A. All testing and training shall be compliant with the VA General
Requirements, Section 01 00 00, “GENERAL REQUIREMENTS”.
B. Provide services of manufacturer’s technical representative for [four]
<insert hours> hours to instruct VA personnel in operation and maintenance of units.
100% Construction Drawings
VIDEO SURVEILLANCE
28 23 00 - 27
C. Submit training plans and instructor qualifications in accordance with the requirements of Section 28 08 00 – “COMMISSIONING OF ELECTRONIC
SAFETY AND SECURITY SYSTEMS”.