This solicitation is for a minor construction project to expand an existing patient parking garage at the Cleveland VA Medical Center. The project scope includes completing the fourth deck of the garage to add 132 parking spaces, extending vertical transportation and stairs to serve the new floor, and improving lighting and the building facade on the existing structure. The solicitation will be an invitation for bid issued by the VA's Program Contracting Activity Central to service-disabled veteran-owned small businesses only. The NAICS code is 236220 with a size standard of $39.5 million. Bids are due on the date specified in the solicitation to be issued on October 18, 2019. The performance period is approximately 280 calendar days from notice to proceed. The estimated value is between $2 million and $5 million. Questions must be submitted in writing by the specified due date.
36E77619B0020 0003 S-001_-_GENERAL_NOTES.pdf
View the file
Other files
Show 40 more
Latest 50 of 66 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MATERIAL SCHEDULE AND CONCRETE MIX DESIGN TABLE
MEMBER
f'c
MIN
28-DAY
W/C
(MAX) F S P C
EXPOSURE CATEGORY ENTRAINED AIR CONTENT
SHEAR WALLS F1 S0 P0 C1 6 +/-1.5%
F1 S0 P0 C1 6 +/-1.5%
BEAMS, COLUMNS, AND
ELEVATED SLABS
NOTES:
1. PROVIDE CONCRETE MIXES IN ACCORDANCE WITH ACI 301 FOR THE EXPOSURE CATEGORIES IDENTIFIED IN THE ABOVE TABLE.
2. MAXIMUM WATER-CEMENT (W/C) RATIOS INDICATED IN THE TABLE SHALL INCLUDE WATER FROM ADMIXTURES IN W/C
CALCULATIONS.
3. DO NOT AIR-ENTRAIN CONCRETE DESIGNATED TO RECEIVE STEEL TROWEL FINISH.
4. ADMIXTURES OR CONCRETE CONTAINING CHLORIDES SHALL NOT BE USED IN POST-TENSIONED SLABS
4500 PSI 0.45
4500 PSI 0.45
NWC
NWC
REINFORCING BAR DEVELOPMENT LENGTHS (INCHES)
BAR
SIZE
4000 PSI 4500 PSI
#3
#4
#5
#6
#7
#8
TOP BARS OTHER BARS TOP BARS OTHER BARS
CASE 1 CASE 2 CASE 1 CASE 2CASE 1 CASE2CASE 1CASE 2
19 28 14 21 18 27 14 20
25 37 19 28 24 35 18
2731 46 24 36 30 44 23
37 56 28 43 35 53 27 41
54 81 42 62 51 77 40 59
62 4893 71 59 88 46 68
#9 70 54105 81 67 100 51 77
1. TOP BARS AS DEFINED BY ACI 318-11
2. CASE 1: CLEAR SPACING OF BARS DEVELOPED OR SPLICED NOT LESS THAN db, CLEAR COVER NOT LESS THAN db, AND
STIRRUPS OR TIES THROUGHOUT
Ld NOT LESS THAN THE CODE MINIMUM OR CLEAR SPACING OF BARS BEING
DEVELOPED OR SPLICED NOT LESS THAN 2db AND CLEAR COVER NOT LESS THAN db.
CASE 2: BARS DEVELOPED OR SPLICED WITH CLEAR COVER AND/OR SPACING NOT
MEETING THE REQUIREMENTS OF CASE 1
3. SPLICE LENGTHS
A. CLASS A TENSION SPLICE = 1.0 Ld, 12 in MIN
B. CLASS B TENSION SPLICE = 1.3 Ld, 12 in MIN
4. DEVELOPMENT AND SPLICE LENGTHS OF EPOXY COATED BARS SHALL BE 1.5 TIMES
THE LENGTHS REQUIRED FRO NON-EPOXY COATED REINFORCEMENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
PVE ENGINEERING, LLC.
Waterfront Corporate Park III, Suite 101
2000 Georgetowne Drive, Sewickley, PA 15143
Phone: 724-444-1100
Email: info@pve-llc.com
AE Works, LTD.
209 Sandusky Street
Pittsburgh, PA 15212
Phone: 412-287-7333 www.ae-works.com
S-001
GENERAL NOTES EXPAND PATIENT PARKING
GARAGE
10701 EAST BOULEVARD, CLEVELAND, OH 44106
161651
05/24/2019 SPL Author
100% BID SET
GENERAL NOTES - DIVISION 1
1. ALL CONSTRUCTION WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE MOST RECENT EDITION OF ALL FEDERAL, STATE AND LOCAL REGULATIONS, INCLUDING BUT NOT LIMITED TO THE OHIO BUILDING CODE, AMERICAN INSTITUTE OF
STEEL CONSTRUCTION (AISC), AMERICAN CONCRETE INSTITUTE (ACI) AND THE BRICK INSTITUTE OF AMERICA (BIA). ANY INFORMATION
CONTAINED IN THESE DRAWINGS THAT DIFFERS FROM STANDARD INDUSTRY PRACTICE SHALL BE BROUGHT TO THE ENGINEER'S
ATTENTION PRIOR TO BEGINNING WORK.
2. ALL DETAILS, SECTIONS, AND NOTES SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL APPLY TO SIMILAR
SITUATIONS, UNO.
3. NO CHANGE IN SIZE, DIMENSION OR POSITION OF STRUCTURAL ELEMENTS SHALL BE MADE WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER OF RECORD.
4. FIELD VERIFY ALL EXISTING CONDITIONS AND INFORMATION CONTAINED ON THESE DRAWINGS AND BRING ANY DISCREPANCIES
TO THE ENGINEER'S ATTENTION IMMEDIATELY BEFORE STARTING CONSTRUCTION AND/OR SUBMITTING SHOP DRAWINGS. ANY
DISCREPANCY BETWEEN THESE PLANS AND THE ACTUAL FIELD CONDITIONS SHALL BE THE CONTRACTOR'S RESPONSIBILITY AND BE
PERFORMED AT NO ADDITIONAL COST.
5. TAKE ALL MEASURES NECESSARY TO PROTECT EXISTING AND NEW UTILITIES AND BUILDINGS AND ASSUME FULL RESPONSIBILITY
FOR ANY DAMAGE DURING CONSTRUCTION. RESTORATION OF DAMAGED AREAS SHALL BE TO THE SATISFACTION OF THE OWNER, AT NO COST TO THE OWNER.
6. ALL MATERIALS USED ON THIS PROJECT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
ALL EQUIPMENT USED ON THIS PROJECT SHALL BE OPERATED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
7.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS AND METHODS TO COMPLETE THE SPECIFIED WORK AND
TO ENSURE THAT ALL WORK IS PERFORMED IN A SAFE MANNER TO THEIR WORKERS AS WELL AS THE PUBLIC. ANY MINOR DETAILS NOT
SHOWN, BUT NECESSARY FOR THE PROPER COMPLETION OF THE SPECIFIED WORK SHALL BE DEEMED INCLUDED IN THE WORK AND BE
PERFORMED AT NO ADDITIONAL COST.
8. THE CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWINGS TO THE ENGINEER FOR THEIR APPROVAL FOR ALL WORK SPECIFIED ABOVE.
ANY WORK PERFORMED PRIOR TO RECEIVING APPROVAL FROM THE ENGINEER IS PERFORMED AT THE CONTRACTOR'S RISK AND IF DEEMED
UNACCEPTABLE WILL BE REPAIRED AT NO ADDITIONAL COST TO THE OWNER.
9. DO NOT REPRODUCE ANY PORTION OF THE STRUCTURAL CONTRACT DRAWINGS FOR RESUBMITTAL AS SHOP DRAWINGS. SHOP
DRAWINGS PRODUCED IN SUCH A MANNER WILL BE REJECTED AND RETURNED.
10. THESE GENERAL DESIGN AND CONSTRUCTION NOTES ARE INTENDED TO BE INTERPRETED IN COMBINATION WITH THE PROJECT
ARCHITECTURAL AND STRUCTURAL SPECIFICATIONS. IN THE EVENT OF ANY INCONSISTENCY, THE MORE STRINGENT REQUIREMENT SHALL
APPLY. IN THE EVENT OF ANY QUESTION OF INTERPRETATION, THE DECISION OF THE ENGINEER SHALL PREVAIL.
11. REFER TO ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR DIMENSIONS AND LOCATIONS OF
OPENINGS, INSERTS, DEPRESSIONS, EQUIPMENT PADS, DRIPS, REVEALS, FINISHES, AND OTHER SUCH PROJECT REQUIREMENTS NOT
SHOWN ON STRUCTURAL DRAWINGS.
12. SUBMIT DIMENSIONED COORDINATED SHOP DRAWINGS SHOWING THE LOCATIONS OF ALL SLEEVES AND OPENINGS REQUIRED BY
ALL TRADES THROUGH STRUCTURAL ELEMENTS. ANY ADDITIONAL OPENINGS NOT SHOWN ON SHOP DRAWINGS WILL REQUIRE WRITTEN
APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.
13. TAKE ALL MEASURES NECESSARY TO PROTECT EXISTING AND NEW UTILITIES AND BUILDINGS AND ASSUME FULL RESPONSIBILITY
FOR ANY DAMAGE DURING CONSTRUCTION. RESTORATION OF DAMAGED AREAS SHALL BE TO THE SATISFACTION OF THE OWNER, AT NO COST TO THE OWNER.
14. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DETAILED INFORMATION REGARDING FINISHES, WATERPROOFING, LOCATIONS OF NON-LOAD BEARING PARTITIONS, EXTERIOR FACE OF BUILDING, ETC.
15. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY
PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK. ALL NECESSARY SIGNS SHALL BE POSTED WARNING AGAINST
DANGER.
16. THE CONTRACTOR SHALL DO ALL CUTTING, PATCHING, REPAIRING AS REQUIRED TO PERFORM ALL OF THE WORK INDICATED
ON THE DRAWINGS, AND ALL OTHER WORK THAT MAY BE REQUIRED TO COMPLETE THE JOB.
17. ALL WORK TO BE PERFORMED IN AN ORDERLY, CLEAN AND LOGICAL MANNER.
18. ALL WORK SHALL BE PERFORMED BY SKILLED TRADESMEN AND SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN
ACCORDANCE WITH GENERALLY ACCEPTED STANDARDS.
19. THE GENERAL CONTRACTOR SHALL VISIT THE SITE AND HAVE A FAMILIARITY WITH ALL THE BUILDING CONDITIONS AND SYSTEMS.
20. THE GENERAL CONTRACTOR SHALL PROVIDE ALL SHORING, BRACING, BARRICADES, TEMPORARY FENCING, PARTITIONS AND
EXCAVATIONS TO ACCOMPLISH ALL OF THE WORK IN AN APPROVED MANNER. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE
FOR PROTECTING ALL WORK DURING DEMOLITION AND CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, DISTORTION
AND MISALIGNMENT. SPACE SHORING TO NOT OVERSTRESS EXISTING SLABS.
21. THE GENERAL CONTRACTOR SHALL MAINTAIN THE SITE (REMOVE RUBBISH) AND PROTECT THE OWNER’S PROPERTY, PROVIDING SHIELDING AT AREAS ADJOINING THE WORK. SECURE PROPERTY AT THE END OF EACH WORKDAY.
22. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION, REMOVAL, TRANSPORTATION AND DISPOSAL
OF ALL DEBRIS AND CONSTRUCTION MATERIAL RELATED TO THE WORK IN A LEGAL MANNER.
23. DIMENSIONS GOVERN - DRAWINGS ARE NOT TO BE SCALED.
CODES AND STANDARDS
1. THE FOLLOWING CODES AND STANDARDS, INCLUDING ALL SPECIFICATIONS REFERENCED WITHIN, APPLY TO THE DESIGN AND
CONSTRUCTION OF THIS PROJECT:
a. IBC, INTERNATIONAL BUILDING CODE - 2018
b. OHIO BUILDING CODE - 2017
c. ASCE 7-16, "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES"
d. ACI 318-14, "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
e. AISC 360-16, "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS," JULY 7, 2016
f. TMS 402/602-16, BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES, 2016
FOUNDATIONS AND EARTHWORK - DIVISION 2
1. FOUNDATIONS
a. EXISTING FOUNDATIONS VERIFICATION IS BASED ON ALLOWABLE NET BEARING CAPACITY OF 3.0 KSF IN ACCORDANCE WITH
DRAWINGS COMPLETED BY CHURCHES ENGINEERING, DATED JUNE 18, 2009, WHICH REFERENCE A GEOTECHNICAL REPORT
COMPLETED BY DAVID V. LEWIN CORP IN 2009.
EXISTING BUILDING INFORMATION
1. ALL EXISTING STRUCTURAL FRAMING, SIZES, REINFORCING, ETC. IS BASED ON DRAWINGS PROVIDED TO PVE, LLC.
a. EAST GARAGE: BARBER & HOFFMAN, INC DATED JUNE 26, 1997
b. WEST GARAGE (ADDITION): CHURCHES CONSULTING ENGINEERS, DATED MAY 13, 2009 & APRIL 30, 2010
CAST-IN-PLACE CONCRETE - DIVISION 3
1. PROVIDE CAST-IN-PLACE CONCRETE FOR EACH CLASS OF CONCRETE SHOWN IN THE CONCRETE MATERIAL SCHEDULE AND AS
REQUIRED BY CONSTRUCTION METHODS & SCHEDULES.
2. REINFORCING SHALL BE AS FOLLOWS:
a. CONVENTIONAL DEFORMED REINFORCING BARS NOT INDICATED TO BE WELDED - ASTM A615, GRADE 60.
b. CONVENTIONAL DEFORMED REINFORCING BARS INDICATED TO BE WELDED - ASTM A706, GRADE 60.
c. WELDED WIRE REINFORCEMENT - ASTM A185, SUPPLIED IN FLAT SHEETS.
3. CONCRETE COVER OVER REINFORCING SHALL BE AS FOLLOWS, UNO:
a. CONCRETE CAST AGAINST & PERMANENTLY EXPOSED TO EARTH OR WEATHER - 3 in.
b. REINFORCING IN SLABS & WALLS NOT EXPOSED TO EARTH OR WEATHER - 3/4 in
c. REINFORCING EXPOSED TO EARTH OR WEATHER
• #5 & SMALLER - 1 1/2 in
• #6 & LARGER - 2 in
• POST TENSIONING TENSONS - 1 1/2 in (SEE PLAN)
d. COVER TO STIRRUPS & TIES IN BEAMS & COLUMNS - 1 1/2 in
4. SPLICE REINFORCING BARS PER ACI 318 WITH CLASS B TENSION LAP SPLICES, UNO. LAP LENGTHS ARE INDICATED IN THE REINFORCING
BAR DEVELOPMENT LENGTH TABLE NOTES.
5. WWR SHALL BE LAP SPLICED PER ACI 318 AND TIED SECURELY.
6. DOWELS SHALL MATCH AND BE CLASS B TENSION LAP SPLICED WITH THE MAIN REINFORCEMENT, UNO.
7. WHERE REINFORCEMENT IS NOT PROVIDED CONTACT THE STRUCTURAL ENGINEER OF RECORD.
8. FIELD BENDING OF REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE IS NOT PERMITTED UNLESS INDICATED ON THE DRAWINGS
OR APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD. REBAR SHALL NOT BE HEATED WITH A TORCH IN THE FIELD.
9. DO NOT WELD REINFORCING UNLESS INDICATED OR APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD.
10. ALL CONSTRUCTION JOINTS SHALL BE WIRE BRUSHED, CLEANED, AND COATED WITH A BONDING AGENT OR MOISTENED WITH A
CEMENT SLURRY SCRUBBED INTO THE JOINT IMMEDIATELY PRIOR TO PLACING NEW CONCRETE.
11. PROVIDE A WATERSTOP IN ALL WALL AND SLAB CONSTRUCTION JOINTS EXPOSED TO EARTH OR WEATHER, COVERED WITH A
WATERPROOF MEMBRANE AND WHERE INDICATED.
12. CHAMFER ALL EXPOSED CORNERS 3/4 in, UNO.
13. ALL MILD REINFORCEMENT IN BEAMS AND SLABS SHALL BE EPOXY COATED.
ABBREVIATIONS
ABV ABOVE
ACI AMERICAN CONCRETE INSTITUTE
ACIP AUGERED CAST-IN-PLACE PILES
ADD'L ADDITIONAL
AE AIR-ENTRAINED
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATELY
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING & MATERIALS
AWS AMERICAN WELDING SOCIETY
B BOTTOM
B/ BOTTOM OF
BLDG BUILDING
BM BEAM
BOT BOTTOM
CJP COMPLETE JOINT PENETRATION
CLR CLEAR
CLSM CONTROLLED LOW STRENGTH MATERIAL
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
COR CONTRACTING OFFICER'S REPRESENTATIVE
db REINFORCING BAR DIAMETER
DIA DIAMETER
DN DOWN
DTLS DETAILS
DWG DRAWING
DWLS DOWELS
EA EACH
EF EACH FACE
EL ELEVATION
ELECT ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
(E) EXISTING
EXP EXPANSION
FT FOOT/FEET
FTG FOOTING
FP FIRE PROTECTION
GALV GALVANIZE
GL GRIDLINE
H HIGH OR HORIZONTAL
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HS HIGH STRENGTH
HSA HEADED SHEAR ANCHOR
IN INCH(ES)
IP INFLECTION POINT
I.F. INSIDE FACE
JT JOINT
SUBMITTALS
MATERIALS - LITERATURE SAMPLES, MSDS SHEETS, PRODUCT DATA SHEETS, ETC. ON ALL MATERIALS TO BE INSTALLED UNDER THIS CONTRACT
SHALL BE SUBMITTED TO THE ENGINEER FOR THEIR REVIEW AND APPROVAL PRIOR TO USE. IF THE CONTRACTOR INSTALLS ANY MATERIALS PRIOR
TO RECEIVING APPROVAL FROM THE ENGINEER, THEY DO SO AT THEIR OWN RISK. ANY WORK THAT NEEDS TO BE REPLACED FOR THIS REASON
SHALL BE PERFORMED AT NO ADDITIONAL COST TO THE OWNER. THE USE OF ASBESTOS OR MATERIALS CONTAINING ASBESTOS IS PROHIBITED.
IN THE EVENT ANY SPECIFIED MATERIALS CONTAIN ASBESTOS IT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR APPROPRIATE ACTION.
CONTRACTOR MUST ALSO SUBMIT DETAILED SHOP DRAWINGS FOR ALL WORK TO BE INSTALLED ON THIS PROJECT.
SHOP DRAWINGS - PREPARE PROJECT-SPECIFIC INFORMATION, DRAWN ACCURATELY TO SCALE OF ALL WORK SPECIFIED IN THE CONTRACT DOCUMENTS.
ALL SHOP DRAWINGS MUST BE PREPARED USING AUTOCAD OR OTHER SIMILAR SOFTWARE. HAND DRAWN SKETCHES SHALL
NOT BE ACCEPTABLE, UNLESS SPECIFICALLY PERMITTED BY THE ENGINEER. DO NOT BASE SHOP DRAWINGS ON REPRODUCTIONS OF THE
CONTRACT DOCUMENTS OR STANDARD PRINTED DATA. ALL SHOP DRAWINGS MUST INCLUDE THE FOLLOWING:
a. DIMENSIONS.
b. IDENTIFICATION OF PRODUCTS.
c. FABRICATION AND INSTALLATION DRAWINGS.
d. DESIGN CALCULATIONS (IF APPLICABLE) WITH ENGINEER'S SEAL AND SIGNATURE.
e. COMPLIANCE WITH SPECIFIED STANDARDS.
f. NOTATION OF DIMENSIONS ESTABLISHED BY FIELD MEASUREMENT.
g. RELATIONSHIP TO ADJOINING CONSTRUCTION CLEARLY INDICATED.
h. SEAL AND SIGNATURE OF PROFESSIONAL ENGINEER IF A STRUCTURAL INSTALLATION (I.E. – RAILINGS, HEADER BEAMS, ETC.)
THE ENGINEER WILL REVIEW ALL SUBMITTALS AND PROVIDE A WRITTEN RESPONSE AS SOON AS POSSIBLE, BUT NOT TO EXCEED FOURTEEN (14)
DAYS OF RECEIPT OF SAME. IF THERE ARE SUBMITTALS MADE OF A STRUCTURAL INSTALLATION, THEY MUST BE SIGNED AND SEALED BY A
LICENSED PROFESSIONAL ENGINEER IN THE STATE OF OHIO.
BUILDING LOADS
1. SUPERIMPOSED DEAD LOAD AND LIVE LOADS
a. GARAGE LIVE LOAD 40 PSF
2. SNOW LOADS
a. GROUND-ROOF SNOW LOAD, Pg 30 PSF
b. FLAT ROOF SNOW LOAD, Pf 25 PSF
b. SNOW EXPOSURE FACTOR, Ce 1.0
c. SNOW IMPORTANCE FACTOR, Ig 1.0
d. THERMAL FACTOR, Ct 1.2
3. WIND
a. WIND SPEED 109 MPH (FACTORED)
b. BUILDING CATEGORY II
c. WIND EXPOSURE B
d. DIRECTIONALITY FACTOR, Kd 0.85
e. TOPOGRAPHIC FACTOR, Kzt 1.0
f. IMPORTANCE FACTOR, Iw 1.0
g. MWFRS DESIGN LOADS
- 0 ft - 20 ft 19 psf
- 20 ft - 33 ft 20 psf
- 33 ft - 46 ft 23 psf
h. BUILDING COMPONENTS AND CLADDING DESIGN LOADS PER IBC 2018, ASCE 7-16 SECTION 30
4. SEISMIC
a. BUILDING OCCUPANCY CATEGORY II
b. IMPORTANCE FACTOR, Ie 1.0
c. SITE CLASS D
d. MAPPED SPECTRAL ACCELERATION
- SHORT PERIOD, Ss .147g
- 1-SECOND PERIOD, S1 .050g
e. SEISMIC DESIGN CATEGORY B
f. LATERAL RESISTING SYSTEM CONCRETE SHEAR WALLS (E-W DIRECTION)
CONCRETE MOMENT FRAME (N-S DIRECTION)
g. RESPONSE MODIFICATION FACTOR, R 3 (N-S) 5 (E-W)
h. SEISMIC RESPONSE COEFFICIENT, Cs 0.053 (N-S) 0.031 (E-W)
i. BASE SHEAR (SEISMIC GOVERNS) 530 K
MASONRY CONSTRUCTION - DIVISION 4
1. REFER TO THE ARCHITECTURAL DRAWINGS FOR LOCATION OF NON-BEARING MASONRY WALLS & PARTITIONS AND ADDITIONAL MASONRY DETAILS.
2. MASONRY WALLS DESIGNATED ON DESIGN DRAWINGS AS “MASONRY PARTITION WALLS” SHALL CONFORM TO THE FOLLOWING REQUIREMENTS:
a. MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF MASONRY, f’m, SHALL BE 2000 PSI.
b. MASONRY MORTAR SHALL BE ASTM C270 TYPE N.
c. GROUT FOR MASONRY CORES SHALL BE PROPORTIONED TO MEET OR EXCEED THE SPECIFIED COMPRESSIVE STRENGTH OF THE MASONRY.
d. UNLESS OTHERWISE NOTED, MASONRY PARTITION WALLS SHALL BE PARTIALLY GROUTED, WITH GROUTED CORES SPACED AT A MAXIMUM
OF 32”, AND GROUTED CORES SHALL BE REINFORCED WITH #6 VERTICAL REINFORCING BARS.
e. UNLESS OTHERWISE NOTED, MASONRY PARTITION WALLS SHALL BE HORIZONTALLY REINFORCED IN ALTERNATE COURSES WITH TRUSS-TYPE
REINFORCING HAVING 8 GAGE WIRE AND CONFORMING WITH ASTM A951.
f. ADJACENT TO ALL WALL OPENINGS, THE TWO VERTICAL CORES NEAREST THE SIDES OF THE OPENING SHALL BE GROUTED AND REINFORCED
WITH #6 VERTICAL REINFORCING BARS, AND THE TWO HORIZONTAL MORTAR JOINTS NEAREST TO THE TOP AND BOTTOM OF THE OPENING
SHALL BE REINFORCED WITH TRUSS-TYPE REINFORCING AS SPECIFIED ABOVE.
g. WHERE TOPS OF MASONRY PARTITION WALLS ADJOIN BOTTOMS OF CONCRETE BEAMS OR ELEVATED SLABS, A 1" ISOLATION JOINT SHALL BE
INSTALLED ATO PERMIT VERTICAL DEFLECTION OF BEAMS AND SLABS WITHOUT IMPOSING LOADS ON PARTITION WALLS.
K KIPS (1000 POUNDS)
kN KILONEWTON kPa KILOPASCAL l LITER
L LENGTH
LBS POUNDS
Ld REINF BAR DEVELOPMENT LENGTH
LLH LONG LEG HORIZ
LLV LONG LEG VERT
LP LOW POINT
LTWT LIGHT WEIGHT
m METER mm MILLIMETER
MAX MAXIMUM
MANUF MANUFACTURER
MECH MECHANICAL
MEP MECH/ELECT/PLUMBING
MIN MINIMUM
MPa MEGAPASCAL
MTL METAL
N NEWTON
NLWT NORMAL WEIGHT
(N) NEW
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
O.F. OUTER FACE
PJP PARTIAL JOINT PENETRATION
PSF POUNDS PER SQAURE FOOT
PSI POUNDS PER SQAURE INCH
PT POST-TENSION
R RISER
REF REFERENCE
REINF REINFORCING OR REINFORCEMENT
REQ'D REQUIRED
SCHED SCHEDULE
SC SLIP CRITICAL
SDI STEEL DECK INSTITUTE
SDL SUPERIMPOSED DEAD LOAD
SEC SECONDS
SIM SIMILAR
SOG SLAB-ON-GRADE
STD STANDARD
SJI STEEL JOIST INSTITUTE
STL STEEL
STRUCT STRUCTURAL
T TOP OR TREAD
T/ TOP OF
TOF TOP OF FOOTING
TOS TOP OF STEEL
THK THICK
TMS THE MASONRY SOCIETY
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V VERTICAL
VERT VERTICAL
VIF VERIFY IN FIELD
W/C WATER-CEMENTITIOUS MATERIAL RATIO
W WIDTH
WD WOOD
WP WORK POINT
WWR WELDED WIRE REINFORCEMENT
STRUCTURAL STEEL - DIVISION 5
1. STRUCTURAL STEEL FABRICATION, ERECTION AND CONNECTION DESIGN SHALL CONFORM TO AISC "SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS."
2. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING DESIGNATIONS, UNO:
WIDE FLANGE BEAMS ASTM A992
HSS RECTANGULAR ASTM A500 GR B
ANGLES ASTM A36
MISCELLANEOUS STEEL PLATES ASTM A36
ANCHOR RODS ASTM F1554, GRADE 36, UNO
THREADED RODS ASTM A36
3. BOLTS SHALL BE MINIMUM 3/4" DIAMETER AND SHALL CONFORM TO REQUIREMENTS OF ASTM A325, UNO.
4. WELDING ELECTRODES AND FLUXES SHALL CONFORM TO ONE OF THE SPECIFICATIONS OF THE AMERICAN WELDING SOCIETY LISTED IN
STRUCTURAL WELDING CODE - STEEL, AWS D1.1. ELECTRODES SHALL HAVE A MINIMUM TENSILE STRENGTH OF 70 KSI.
5. IF PARTS JOINED BY FILLET WELDS ARE SEPARATED BY MORE THAN 1/16 IN. THE LEG OF THE FILLET WELD SHALL BE INCREASED BY THE
AMOUNT OF THE ROOT OPENING. ROOT OPENING SHALL NOT EXCEED 3/16 IN.
6. UNLESS OTHERWISE INDICATED ON THE DRAWINGS FILLET WELDS SHALL HAVE A MINIMUM SIZE OF 1/4".
7. GROUT UNDER STEEL PLATES SHALL HAVE A MINIMUM 28 DAY DESIGN COMPRESSIVE STRENGTH OF 7000 PSI.
8. BOLTED CONNECTIONS SHALL BE MADE WITH HIGH STRENGTH BOLTS, 3/4" MIN DIAMETER, UNLESS OTHERWISE NOTED, PER ASTM A325X.
HIGH STRENGTH BOLTS SHALL BE TIGHTENED BY THE TURN-OF-NUT METHOD.
9. BOLTED CONNECTIONS SHALL HAVE A MINIMUM OF 2 BOLTS.
10. FABRICATOR AND ERECTOR SHALL BE CURRENTLY CERTIFIED IN THE AISC QUALITY CERTIFICATION PROGRAM, CATEGORY STD.
11. FABRICATOR MAY SUBMIT ALTERNATIVE CONNECTION DETAIL PER AISC FOR THE FACTORED SHEAR REACTION SHOWN IN SCHEDULE.
IF ALTERNATIVE CONNECTION IS SUBMITTED DURING THE SHOP DRAWING PHASE, ENGINEER OF RECORD MUST VERIFY AND APPROVE
CHANGE.
12. CONNECTIONS TO COLUMNS SHALL HAVE A MAXIMUM ECCENTRICITY OF 3" WITH RESPECT TO THE FLANGE OR WEB AS APPLICABLE.
13. PROVIDE ONE SHOP COAT OF RUST-INHIBITING GRAY PRIMER, 2 MILS DRY THICKNESS ON ALL STRUCTURAL STEEL MEMBERS AND
DECKING EXCEPT AT FIELD WELD LOCATIONS.
14. ALL STRUCTURAL STEEL SHALL BE FIELD PAINTED BLACK.
15. DO NOT FIELD CUT STRUCTURAL STEEL MEMBERS WITHOUT THE WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.
16. DO NOT SPLICE STEEL MEMBERS EXCEPT WHERE SPECIFICALLY DETAILED ON THE DRAWINGS WITHOUT THE WRITTEN APPROVAL OF
THE STRUCTURAL ENGINEER OF RECORD.
17. THE CONTRACTOR SHALL PROVIDE ADEQUATE TEMPORARY SUPPORTS UNTIL ALL PERMANENT BRACING AND FLOOR SLABS ARE IN PLACE.
18. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED MINOR STEEL PIECES OF PLATES, ANGLES, STRUCTURAL STEEL SHAPES AND CONNECTIONS
NECESSARY TO MAKE THE WORK COMPLETE WHETHER OR NOT SHOWN ON DRAWINGS, WITHOUT ADDITIONAL
COMPENSATION.
19. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND SHALL NOT PROCEED WITH THE WORK UNTIL PLANS AND DETAILS HAVE BEEN
FULLY APPROVED.
20. THE CONTRACTOR SHALL NOT REPRODUCE THE CONSTRUCTION DOCUMENTS FOR USE AS SHOP DRAWINGS.
21. THE CONTRACTOR AND SUBCONTRACTORS MUST SUBMIT IN WRITING ANY REQUEST FOR MODIFICATIONS TO THE PLANS AND
SPECIFICATIONS. SHOP DRAWINGS THAT ARE SUBMITTED TO THE ENGINEER FOR THEIR REVIEW DO NOT CONSTITUTE, "IN WRITING", UNLESS IT IS BROUGHT TO THE ATTENTION OF THE ENGINEER THAT SPECIFIC CHANGES ARE BEING SUGGESTED. CHANGES TO THE PLANS
AND SPECIFICATIONS BY MEANS OF SHOP DRAWINGS SHALL BE THE RESPONSIBILITY OF THE PERSON INITIATING THE CHANGES.
22. ALL STEEL SHALL BE MEET THE ARCHITECTURALLY EXPOSED STRUCTURAL STEEL REQUIREMENTS PER SPECIFICATION 051213
METAL DECK - DIVISION 5
1. METAL ROOF DECK SHALL BE SUPPLIED PRIME-PAINTED, SIZED PER THE CONFIGURATIONS SPECIFIED ON THE DRAWINGS, MANUFACTURED BY VULCRAFT, OR AN APPROVED EQUIVALENT, AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATION AND STEEL DECK INSTITUTE STANDARDS.
2. STEEL DECK SECTIONS SHALL BE LAP CONNECTED AND ATTACHED TO THE SUPPORTING STRUCTURE AS SPECIFIED ON THE DESIGN DRAWINGS
3. PROVIDE, AS REQUIRED, ALL RIDGE AND VALLEY PLATES, COLUMN CLOSURES, CANT STRIPS, SUMP PLATES AT PIPING PENETRATIONS AND
RECESSED SUMP PANS AT ROOF DRAINS. PROVIDE SUPPLEMENTAL FRAMING AT OPENINGS AS REQUIRED FOR SUPPORT OF THE METAL
DECK. ALL OPENINGS SHALL BE COORDINATED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION DRAWINGS
4. NO LOADS EXCEEDING 50 POUNDS SHALL BE PERMITTED TO BE HUNG FROM ANY STEEL DECKING. DUCTWORK, PIPING, ETC. SHALL BE HUNG
DIRECTLY FROM STRUCTURAL STEEL, SUPPLEMENTARY MEMBERS OR ANCHORS EMBEDDED IN THE CONCRETE. SUPPLEMENTARY MEMBERS, IF USED, SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
5. ALL SURFACES OF DECKING THAT WILL BE EXPOSED IN THE FINISHED STRUCTURE SHALL BE FIELD-PAINTED BLACK.
# Revisions Date
1 Addendum for Solilcitation 11/22/2019
| Sheets |
| S-001 - GENERAL NOTES |
| S-100 - LEVEL4 FRAMING PLAN |
| S-101 - LEVEL 4 POST-TENSIONING PLAN |
| S-300 - CONCRETE DETAILS |
| S-301 - CONCRETE REPAIR DETAILS |
| S-302 - POST-TENSIONED DETAILS |
| S-305 - CONCRETE BEAM SCHEDULE & DETAILS |
File details come from the government source that posted it. Updated .