36E77619B0020-0003020.pdf

PDF Posted

Attached to
Expand Patient Parking Garage - Cleveland - Minor Construction
Solicitation number
36E77619B0020
Issued by

About this file

This solicitation is for a minor construction project to expand an existing patient parking garage at the Cleveland VA Medical Center. The project scope includes completing the fourth deck of the garage to add 132 parking spaces, extending vertical transportation and stairs to serve the new floor, and improving lighting and the building facade on the existing structure. The solicitation will be an invitation for bid issued by the VA's Program Contracting Activity Central to service-disabled veteran-owned small businesses only. The NAICS code is 236220 with a size standard of $39.5 million. Bids are due on the date specified in the solicitation to be issued on October 18, 2019. The performance period is approximately 280 calendar days from notice to proceed. The estimated value is between $2 million and $5 million. Questions must be submitted in writing by the specified due date.

36E77619B0020 0003 S-001_-_GENERAL_NOTES.pdf

View the file

Other files

File Type Posted
36E77619B0020-0007003.pdf PDF
36E77619B0020-0007004.pdf PDF
36E77619B0020-0007002.pdf PDF
36E77619B0020-0007000.docx DOCX document
36E77619B0020-0007001.pdf PDF
36E77619B0020-0007005.pdf PDF
36E77619B0020-0006004.pdf PDF
36E77619B0020-0006001.pdf PDF
36E77619B0020-0006003.pdf PDF
36E77619B0020-0006000.docx DOCX document
36E77619B0020-0006002.pdf PDF
36E77619B0020-0005000.docx DOCX document
36E77619B0020-0005002.pdf PDF
36E77619B0020-0005001.pdf PDF
36E77619B0020-0004000.docx DOCX document
36E77619B0020-0004001.pdf PDF
36E77619B0020-0004002.pdf PDF
36E77619B0020-0003002.pdf PDF
36E77619B0020-0003016.pdf PDF
36E77619B0020-0003022.pdf PDF
36E77619B0020-0003011.pdf PDF
36E77619B0020-0003004.pdf PDF
36E77619B0020-0003018.pdf PDF
36E77619B0020-0003024.pdf PDF
36E77619B0020-0003003.pdf PDF
36E77619B0020-0003006.pdf PDF
36E77619B0020-0003017.pdf PDF
36E77619B0020-0003023.pdf PDF
36E77619B0020-0003014.pdf PDF
36E77619B0020-0003009.pdf PDF
36E77619B0020-0003021.pdf PDF
36E77619B0020-0003013.pdf PDF
36E77619B0020-0003019.pdf PDF
36E77619B0020-0003025.pdf PDF
36E77619B0020-0003007.pdf PDF
36E77619B0020-0003012.pdf PDF
36E77619B0020-0003026.pdf PDF
36E77619B0020-0003010.pdf PDF
36E77619B0020-0003000.docx DOCX document
36E77619B0020-0003001.pdf PDF
36E77619B0020-0003005.pdf PDF
36E77619B0020-0003008.pdf PDF
36E77619B0020-0003015.pdf PDF
36E77619B0020-0002002.pdf PDF
36E77619B0020-0002001.pdf PDF
36E77619B0020-0002000.docx DOCX document
36E77619B0020-0001001.pdf PDF
36E77619B0020-0001000.docx DOCX document
36E77619B0020-0001000.docx DOCX document
36E77619B0020-0001001.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MATERIAL SCHEDULE AND CONCRETE MIX DESIGN TABLE

MEMBER

f'c

MIN

28-DAY

W/C

(MAX) F S P C

EXPOSURE CATEGORY ENTRAINED AIR CONTENT

SHEAR WALLS F1 S0 P0 C1 6 +/-1.5%

F1 S0 P0 C1 6 +/-1.5%

BEAMS, COLUMNS, AND

ELEVATED SLABS

NOTES:

1. PROVIDE CONCRETE MIXES IN ACCORDANCE WITH ACI 301 FOR THE EXPOSURE CATEGORIES IDENTIFIED IN THE ABOVE TABLE.

2. MAXIMUM WATER-CEMENT (W/C) RATIOS INDICATED IN THE TABLE SHALL INCLUDE WATER FROM ADMIXTURES IN W/C

CALCULATIONS.

3. DO NOT AIR-ENTRAIN CONCRETE DESIGNATED TO RECEIVE STEEL TROWEL FINISH.

4. ADMIXTURES OR CONCRETE CONTAINING CHLORIDES SHALL NOT BE USED IN POST-TENSIONED SLABS

4500 PSI 0.45

4500 PSI 0.45

NWC

NWC

REINFORCING BAR DEVELOPMENT LENGTHS (INCHES)

BAR

SIZE

4000 PSI 4500 PSI

#3

#4

#5

#6

#7

#8

TOP BARS OTHER BARS TOP BARS OTHER BARS

CASE 1 CASE 2 CASE 1 CASE 2CASE 1 CASE2CASE 1CASE 2

19 28 14 21 18 27 14 20

25 37 19 28 24 35 18

2731 46 24 36 30 44 23

37 56 28 43 35 53 27 41

54 81 42 62 51 77 40 59

62 4893 71 59 88 46 68

#9 70 54105 81 67 100 51 77

1. TOP BARS AS DEFINED BY ACI 318-11

2. CASE 1: CLEAR SPACING OF BARS DEVELOPED OR SPLICED NOT LESS THAN db, CLEAR COVER NOT LESS THAN db, AND

STIRRUPS OR TIES THROUGHOUT

Ld NOT LESS THAN THE CODE MINIMUM OR CLEAR SPACING OF BARS BEING

DEVELOPED OR SPLICED NOT LESS THAN 2db AND CLEAR COVER NOT LESS THAN db.

CASE 2: BARS DEVELOPED OR SPLICED WITH CLEAR COVER AND/OR SPACING NOT

MEETING THE REQUIREMENTS OF CASE 1

3. SPLICE LENGTHS

A. CLASS A TENSION SPLICE = 1.0 Ld, 12 in MIN

B. CLASS B TENSION SPLICE = 1.3 Ld, 12 in MIN

4. DEVELOPMENT AND SPLICE LENGTHS OF EPOXY COATED BARS SHALL BE 1.5 TIMES

THE LENGTHS REQUIRED FRO NON-EPOXY COATED REINFORCEMENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

PVE ENGINEERING, LLC.

Waterfront Corporate Park III, Suite 101

2000 Georgetowne Drive, Sewickley, PA 15143

Phone: 724-444-1100

Email: info@pve-llc.com

AE Works, LTD.

209 Sandusky Street

Pittsburgh, PA 15212

Phone: 412-287-7333 www.ae-works.com

S-001

GENERAL NOTES EXPAND PATIENT PARKING

GARAGE

10701 EAST BOULEVARD, CLEVELAND, OH 44106

161651

05/24/2019 SPL Author

100% BID SET

GENERAL NOTES - DIVISION 1

1. ALL CONSTRUCTION WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE MOST RECENT EDITION OF ALL FEDERAL, STATE AND LOCAL REGULATIONS, INCLUDING BUT NOT LIMITED TO THE OHIO BUILDING CODE, AMERICAN INSTITUTE OF

STEEL CONSTRUCTION (AISC), AMERICAN CONCRETE INSTITUTE (ACI) AND THE BRICK INSTITUTE OF AMERICA (BIA). ANY INFORMATION

CONTAINED IN THESE DRAWINGS THAT DIFFERS FROM STANDARD INDUSTRY PRACTICE SHALL BE BROUGHT TO THE ENGINEER'S

ATTENTION PRIOR TO BEGINNING WORK.

2. ALL DETAILS, SECTIONS, AND NOTES SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL APPLY TO SIMILAR

SITUATIONS, UNO.

3. NO CHANGE IN SIZE, DIMENSION OR POSITION OF STRUCTURAL ELEMENTS SHALL BE MADE WITHOUT THE APPROVAL OF THE

STRUCTURAL ENGINEER OF RECORD.

4. FIELD VERIFY ALL EXISTING CONDITIONS AND INFORMATION CONTAINED ON THESE DRAWINGS AND BRING ANY DISCREPANCIES

TO THE ENGINEER'S ATTENTION IMMEDIATELY BEFORE STARTING CONSTRUCTION AND/OR SUBMITTING SHOP DRAWINGS. ANY

DISCREPANCY BETWEEN THESE PLANS AND THE ACTUAL FIELD CONDITIONS SHALL BE THE CONTRACTOR'S RESPONSIBILITY AND BE

PERFORMED AT NO ADDITIONAL COST.

5. TAKE ALL MEASURES NECESSARY TO PROTECT EXISTING AND NEW UTILITIES AND BUILDINGS AND ASSUME FULL RESPONSIBILITY

FOR ANY DAMAGE DURING CONSTRUCTION. RESTORATION OF DAMAGED AREAS SHALL BE TO THE SATISFACTION OF THE OWNER, AT NO COST TO THE OWNER.

6. ALL MATERIALS USED ON THIS PROJECT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

ALL EQUIPMENT USED ON THIS PROJECT SHALL BE OPERATED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

7.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS AND METHODS TO COMPLETE THE SPECIFIED WORK AND

TO ENSURE THAT ALL WORK IS PERFORMED IN A SAFE MANNER TO THEIR WORKERS AS WELL AS THE PUBLIC. ANY MINOR DETAILS NOT

SHOWN, BUT NECESSARY FOR THE PROPER COMPLETION OF THE SPECIFIED WORK SHALL BE DEEMED INCLUDED IN THE WORK AND BE

PERFORMED AT NO ADDITIONAL COST.

8. THE CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWINGS TO THE ENGINEER FOR THEIR APPROVAL FOR ALL WORK SPECIFIED ABOVE.

ANY WORK PERFORMED PRIOR TO RECEIVING APPROVAL FROM THE ENGINEER IS PERFORMED AT THE CONTRACTOR'S RISK AND IF DEEMED

UNACCEPTABLE WILL BE REPAIRED AT NO ADDITIONAL COST TO THE OWNER.

9. DO NOT REPRODUCE ANY PORTION OF THE STRUCTURAL CONTRACT DRAWINGS FOR RESUBMITTAL AS SHOP DRAWINGS. SHOP

DRAWINGS PRODUCED IN SUCH A MANNER WILL BE REJECTED AND RETURNED.

10. THESE GENERAL DESIGN AND CONSTRUCTION NOTES ARE INTENDED TO BE INTERPRETED IN COMBINATION WITH THE PROJECT

ARCHITECTURAL AND STRUCTURAL SPECIFICATIONS. IN THE EVENT OF ANY INCONSISTENCY, THE MORE STRINGENT REQUIREMENT SHALL

APPLY. IN THE EVENT OF ANY QUESTION OF INTERPRETATION, THE DECISION OF THE ENGINEER SHALL PREVAIL.

11. REFER TO ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR DIMENSIONS AND LOCATIONS OF

OPENINGS, INSERTS, DEPRESSIONS, EQUIPMENT PADS, DRIPS, REVEALS, FINISHES, AND OTHER SUCH PROJECT REQUIREMENTS NOT

SHOWN ON STRUCTURAL DRAWINGS.

12. SUBMIT DIMENSIONED COORDINATED SHOP DRAWINGS SHOWING THE LOCATIONS OF ALL SLEEVES AND OPENINGS REQUIRED BY

ALL TRADES THROUGH STRUCTURAL ELEMENTS. ANY ADDITIONAL OPENINGS NOT SHOWN ON SHOP DRAWINGS WILL REQUIRE WRITTEN

APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.

13. TAKE ALL MEASURES NECESSARY TO PROTECT EXISTING AND NEW UTILITIES AND BUILDINGS AND ASSUME FULL RESPONSIBILITY

FOR ANY DAMAGE DURING CONSTRUCTION. RESTORATION OF DAMAGED AREAS SHALL BE TO THE SATISFACTION OF THE OWNER, AT NO COST TO THE OWNER.

14. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DETAILED INFORMATION REGARDING FINISHES, WATERPROOFING, LOCATIONS OF NON-LOAD BEARING PARTITIONS, EXTERIOR FACE OF BUILDING, ETC.

15. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY

PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK. ALL NECESSARY SIGNS SHALL BE POSTED WARNING AGAINST

DANGER.

16. THE CONTRACTOR SHALL DO ALL CUTTING, PATCHING, REPAIRING AS REQUIRED TO PERFORM ALL OF THE WORK INDICATED

ON THE DRAWINGS, AND ALL OTHER WORK THAT MAY BE REQUIRED TO COMPLETE THE JOB.

17. ALL WORK TO BE PERFORMED IN AN ORDERLY, CLEAN AND LOGICAL MANNER.

18. ALL WORK SHALL BE PERFORMED BY SKILLED TRADESMEN AND SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN

ACCORDANCE WITH GENERALLY ACCEPTED STANDARDS.

19. THE GENERAL CONTRACTOR SHALL VISIT THE SITE AND HAVE A FAMILIARITY WITH ALL THE BUILDING CONDITIONS AND SYSTEMS.

20. THE GENERAL CONTRACTOR SHALL PROVIDE ALL SHORING, BRACING, BARRICADES, TEMPORARY FENCING, PARTITIONS AND

EXCAVATIONS TO ACCOMPLISH ALL OF THE WORK IN AN APPROVED MANNER. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE

FOR PROTECTING ALL WORK DURING DEMOLITION AND CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, DISTORTION

AND MISALIGNMENT. SPACE SHORING TO NOT OVERSTRESS EXISTING SLABS.

21. THE GENERAL CONTRACTOR SHALL MAINTAIN THE SITE (REMOVE RUBBISH) AND PROTECT THE OWNER’S PROPERTY, PROVIDING SHIELDING AT AREAS ADJOINING THE WORK. SECURE PROPERTY AT THE END OF EACH WORKDAY.

22. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION, REMOVAL, TRANSPORTATION AND DISPOSAL

OF ALL DEBRIS AND CONSTRUCTION MATERIAL RELATED TO THE WORK IN A LEGAL MANNER.

23. DIMENSIONS GOVERN - DRAWINGS ARE NOT TO BE SCALED.

CODES AND STANDARDS

1. THE FOLLOWING CODES AND STANDARDS, INCLUDING ALL SPECIFICATIONS REFERENCED WITHIN, APPLY TO THE DESIGN AND

CONSTRUCTION OF THIS PROJECT:

a. IBC, INTERNATIONAL BUILDING CODE - 2018

b. OHIO BUILDING CODE - 2017

c. ASCE 7-16, "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES"

d. ACI 318-14, "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"

e. AISC 360-16, "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS," JULY 7, 2016

f. TMS 402/602-16, BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES, 2016

FOUNDATIONS AND EARTHWORK - DIVISION 2

1. FOUNDATIONS

a. EXISTING FOUNDATIONS VERIFICATION IS BASED ON ALLOWABLE NET BEARING CAPACITY OF 3.0 KSF IN ACCORDANCE WITH

DRAWINGS COMPLETED BY CHURCHES ENGINEERING, DATED JUNE 18, 2009, WHICH REFERENCE A GEOTECHNICAL REPORT

COMPLETED BY DAVID V. LEWIN CORP IN 2009.

EXISTING BUILDING INFORMATION

1. ALL EXISTING STRUCTURAL FRAMING, SIZES, REINFORCING, ETC. IS BASED ON DRAWINGS PROVIDED TO PVE, LLC.

a. EAST GARAGE: BARBER & HOFFMAN, INC DATED JUNE 26, 1997

b. WEST GARAGE (ADDITION): CHURCHES CONSULTING ENGINEERS, DATED MAY 13, 2009 & APRIL 30, 2010

CAST-IN-PLACE CONCRETE - DIVISION 3

1. PROVIDE CAST-IN-PLACE CONCRETE FOR EACH CLASS OF CONCRETE SHOWN IN THE CONCRETE MATERIAL SCHEDULE AND AS

REQUIRED BY CONSTRUCTION METHODS & SCHEDULES.

2. REINFORCING SHALL BE AS FOLLOWS:

a. CONVENTIONAL DEFORMED REINFORCING BARS NOT INDICATED TO BE WELDED - ASTM A615, GRADE 60.

b. CONVENTIONAL DEFORMED REINFORCING BARS INDICATED TO BE WELDED - ASTM A706, GRADE 60.

c. WELDED WIRE REINFORCEMENT - ASTM A185, SUPPLIED IN FLAT SHEETS.

3. CONCRETE COVER OVER REINFORCING SHALL BE AS FOLLOWS, UNO:

a. CONCRETE CAST AGAINST & PERMANENTLY EXPOSED TO EARTH OR WEATHER - 3 in.

b. REINFORCING IN SLABS & WALLS NOT EXPOSED TO EARTH OR WEATHER - 3/4 in

c. REINFORCING EXPOSED TO EARTH OR WEATHER

• #5 & SMALLER - 1 1/2 in

• #6 & LARGER - 2 in

• POST TENSIONING TENSONS - 1 1/2 in (SEE PLAN)

d. COVER TO STIRRUPS & TIES IN BEAMS & COLUMNS - 1 1/2 in

4. SPLICE REINFORCING BARS PER ACI 318 WITH CLASS B TENSION LAP SPLICES, UNO. LAP LENGTHS ARE INDICATED IN THE REINFORCING

BAR DEVELOPMENT LENGTH TABLE NOTES.

5. WWR SHALL BE LAP SPLICED PER ACI 318 AND TIED SECURELY.

6. DOWELS SHALL MATCH AND BE CLASS B TENSION LAP SPLICED WITH THE MAIN REINFORCEMENT, UNO.

7. WHERE REINFORCEMENT IS NOT PROVIDED CONTACT THE STRUCTURAL ENGINEER OF RECORD.

8. FIELD BENDING OF REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE IS NOT PERMITTED UNLESS INDICATED ON THE DRAWINGS

OR APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD. REBAR SHALL NOT BE HEATED WITH A TORCH IN THE FIELD.

9. DO NOT WELD REINFORCING UNLESS INDICATED OR APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD.

10. ALL CONSTRUCTION JOINTS SHALL BE WIRE BRUSHED, CLEANED, AND COATED WITH A BONDING AGENT OR MOISTENED WITH A

CEMENT SLURRY SCRUBBED INTO THE JOINT IMMEDIATELY PRIOR TO PLACING NEW CONCRETE.

11. PROVIDE A WATERSTOP IN ALL WALL AND SLAB CONSTRUCTION JOINTS EXPOSED TO EARTH OR WEATHER, COVERED WITH A

WATERPROOF MEMBRANE AND WHERE INDICATED.

12. CHAMFER ALL EXPOSED CORNERS 3/4 in, UNO.

13. ALL MILD REINFORCEMENT IN BEAMS AND SLABS SHALL BE EPOXY COATED.

ABBREVIATIONS

ABV ABOVE

ACI AMERICAN CONCRETE INSTITUTE

ACIP AUGERED CAST-IN-PLACE PILES

ADD'L ADDITIONAL

AE AIR-ENTRAINED

AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

APPROX APPROXIMATELY

AR ANCHOR ROD

ARCH ARCHITECTURAL

ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING & MATERIALS

AWS AMERICAN WELDING SOCIETY

B BOTTOM

B/ BOTTOM OF

BLDG BUILDING

BM BEAM

BOT BOTTOM

CJP COMPLETE JOINT PENETRATION

CLR CLEAR

CLSM CONTROLLED LOW STRENGTH MATERIAL

CMU CONCRETE MASONRY UNIT

CO CLEAN OUT

COL COLUMN

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

COR CONTRACTING OFFICER'S REPRESENTATIVE

db REINFORCING BAR DIAMETER

DIA DIAMETER

DN DOWN

DTLS DETAILS

DWG DRAWING

DWLS DOWELS

EA EACH

EF EACH FACE

EL ELEVATION

ELECT ELECTRICAL

ELEV ELEVATOR

EMBED EMBEDMENT

EOS EDGE OF SLAB

EQ EQUAL

EQUIP EQUIPMENT

EW EACH WAY

(E) EXISTING

EXP EXPANSION

FT FOOT/FEET

FTG FOOTING

FP FIRE PROTECTION

GALV GALVANIZE

GL GRIDLINE

H HIGH OR HORIZONTAL

HK HOOK

HORIZ HORIZONTAL

HP HIGH POINT

HS HIGH STRENGTH

HSA HEADED SHEAR ANCHOR

IN INCH(ES)

IP INFLECTION POINT

I.F. INSIDE FACE

JT JOINT

SUBMITTALS

MATERIALS - LITERATURE SAMPLES, MSDS SHEETS, PRODUCT DATA SHEETS, ETC. ON ALL MATERIALS TO BE INSTALLED UNDER THIS CONTRACT

SHALL BE SUBMITTED TO THE ENGINEER FOR THEIR REVIEW AND APPROVAL PRIOR TO USE. IF THE CONTRACTOR INSTALLS ANY MATERIALS PRIOR

TO RECEIVING APPROVAL FROM THE ENGINEER, THEY DO SO AT THEIR OWN RISK. ANY WORK THAT NEEDS TO BE REPLACED FOR THIS REASON

SHALL BE PERFORMED AT NO ADDITIONAL COST TO THE OWNER. THE USE OF ASBESTOS OR MATERIALS CONTAINING ASBESTOS IS PROHIBITED.

IN THE EVENT ANY SPECIFIED MATERIALS CONTAIN ASBESTOS IT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR APPROPRIATE ACTION.

CONTRACTOR MUST ALSO SUBMIT DETAILED SHOP DRAWINGS FOR ALL WORK TO BE INSTALLED ON THIS PROJECT.

SHOP DRAWINGS - PREPARE PROJECT-SPECIFIC INFORMATION, DRAWN ACCURATELY TO SCALE OF ALL WORK SPECIFIED IN THE CONTRACT DOCUMENTS.

ALL SHOP DRAWINGS MUST BE PREPARED USING AUTOCAD OR OTHER SIMILAR SOFTWARE. HAND DRAWN SKETCHES SHALL

NOT BE ACCEPTABLE, UNLESS SPECIFICALLY PERMITTED BY THE ENGINEER. DO NOT BASE SHOP DRAWINGS ON REPRODUCTIONS OF THE

CONTRACT DOCUMENTS OR STANDARD PRINTED DATA. ALL SHOP DRAWINGS MUST INCLUDE THE FOLLOWING:

a. DIMENSIONS.

b. IDENTIFICATION OF PRODUCTS.

c. FABRICATION AND INSTALLATION DRAWINGS.

d. DESIGN CALCULATIONS (IF APPLICABLE) WITH ENGINEER'S SEAL AND SIGNATURE.

e. COMPLIANCE WITH SPECIFIED STANDARDS.

f. NOTATION OF DIMENSIONS ESTABLISHED BY FIELD MEASUREMENT.

g. RELATIONSHIP TO ADJOINING CONSTRUCTION CLEARLY INDICATED.

h. SEAL AND SIGNATURE OF PROFESSIONAL ENGINEER IF A STRUCTURAL INSTALLATION (I.E. – RAILINGS, HEADER BEAMS, ETC.)

THE ENGINEER WILL REVIEW ALL SUBMITTALS AND PROVIDE A WRITTEN RESPONSE AS SOON AS POSSIBLE, BUT NOT TO EXCEED FOURTEEN (14)

DAYS OF RECEIPT OF SAME. IF THERE ARE SUBMITTALS MADE OF A STRUCTURAL INSTALLATION, THEY MUST BE SIGNED AND SEALED BY A

LICENSED PROFESSIONAL ENGINEER IN THE STATE OF OHIO.

BUILDING LOADS

1. SUPERIMPOSED DEAD LOAD AND LIVE LOADS

a. GARAGE LIVE LOAD 40 PSF

2. SNOW LOADS

a. GROUND-ROOF SNOW LOAD, Pg 30 PSF

b. FLAT ROOF SNOW LOAD, Pf 25 PSF

b. SNOW EXPOSURE FACTOR, Ce 1.0

c. SNOW IMPORTANCE FACTOR, Ig 1.0

d. THERMAL FACTOR, Ct 1.2

3. WIND

a. WIND SPEED 109 MPH (FACTORED)

b. BUILDING CATEGORY II

c. WIND EXPOSURE B

d. DIRECTIONALITY FACTOR, Kd 0.85

e. TOPOGRAPHIC FACTOR, Kzt 1.0

f. IMPORTANCE FACTOR, Iw 1.0

g. MWFRS DESIGN LOADS

- 0 ft - 20 ft 19 psf

- 20 ft - 33 ft 20 psf

- 33 ft - 46 ft 23 psf

h. BUILDING COMPONENTS AND CLADDING DESIGN LOADS PER IBC 2018, ASCE 7-16 SECTION 30

4. SEISMIC

a. BUILDING OCCUPANCY CATEGORY II

b. IMPORTANCE FACTOR, Ie 1.0

c. SITE CLASS D

d. MAPPED SPECTRAL ACCELERATION

- SHORT PERIOD, Ss .147g

- 1-SECOND PERIOD, S1 .050g

e. SEISMIC DESIGN CATEGORY B

f. LATERAL RESISTING SYSTEM CONCRETE SHEAR WALLS (E-W DIRECTION)

CONCRETE MOMENT FRAME (N-S DIRECTION)

g. RESPONSE MODIFICATION FACTOR, R 3 (N-S) 5 (E-W)

h. SEISMIC RESPONSE COEFFICIENT, Cs 0.053 (N-S) 0.031 (E-W)

i. BASE SHEAR (SEISMIC GOVERNS) 530 K

MASONRY CONSTRUCTION - DIVISION 4

1. REFER TO THE ARCHITECTURAL DRAWINGS FOR LOCATION OF NON-BEARING MASONRY WALLS & PARTITIONS AND ADDITIONAL MASONRY DETAILS.

2. MASONRY WALLS DESIGNATED ON DESIGN DRAWINGS AS “MASONRY PARTITION WALLS” SHALL CONFORM TO THE FOLLOWING REQUIREMENTS:

a. MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF MASONRY, f’m, SHALL BE 2000 PSI.

b. MASONRY MORTAR SHALL BE ASTM C270 TYPE N.

c. GROUT FOR MASONRY CORES SHALL BE PROPORTIONED TO MEET OR EXCEED THE SPECIFIED COMPRESSIVE STRENGTH OF THE MASONRY.

d. UNLESS OTHERWISE NOTED, MASONRY PARTITION WALLS SHALL BE PARTIALLY GROUTED, WITH GROUTED CORES SPACED AT A MAXIMUM

OF 32”, AND GROUTED CORES SHALL BE REINFORCED WITH #6 VERTICAL REINFORCING BARS.

e. UNLESS OTHERWISE NOTED, MASONRY PARTITION WALLS SHALL BE HORIZONTALLY REINFORCED IN ALTERNATE COURSES WITH TRUSS-TYPE

REINFORCING HAVING 8 GAGE WIRE AND CONFORMING WITH ASTM A951.

f. ADJACENT TO ALL WALL OPENINGS, THE TWO VERTICAL CORES NEAREST THE SIDES OF THE OPENING SHALL BE GROUTED AND REINFORCED

WITH #6 VERTICAL REINFORCING BARS, AND THE TWO HORIZONTAL MORTAR JOINTS NEAREST TO THE TOP AND BOTTOM OF THE OPENING

SHALL BE REINFORCED WITH TRUSS-TYPE REINFORCING AS SPECIFIED ABOVE.

g. WHERE TOPS OF MASONRY PARTITION WALLS ADJOIN BOTTOMS OF CONCRETE BEAMS OR ELEVATED SLABS, A 1" ISOLATION JOINT SHALL BE

INSTALLED ATO PERMIT VERTICAL DEFLECTION OF BEAMS AND SLABS WITHOUT IMPOSING LOADS ON PARTITION WALLS.

K KIPS (1000 POUNDS)

kN KILONEWTON kPa KILOPASCAL l LITER

L LENGTH

LBS POUNDS

Ld REINF BAR DEVELOPMENT LENGTH

LLH LONG LEG HORIZ

LLV LONG LEG VERT

LP LOW POINT

LTWT LIGHT WEIGHT

m METER mm MILLIMETER

MAX MAXIMUM

MANUF MANUFACTURER

MECH MECHANICAL

MEP MECH/ELECT/PLUMBING

MIN MINIMUM

MPa MEGAPASCAL

MTL METAL

N NEWTON

NLWT NORMAL WEIGHT

(N) NEW

OC ON CENTER

OPNG OPENING

OPP OPPOSITE

O.F. OUTER FACE

PJP PARTIAL JOINT PENETRATION

PSF POUNDS PER SQAURE FOOT

PSI POUNDS PER SQAURE INCH

PT POST-TENSION

R RISER

REF REFERENCE

REINF REINFORCING OR REINFORCEMENT

REQ'D REQUIRED

SCHED SCHEDULE

SC SLIP CRITICAL

SDI STEEL DECK INSTITUTE

SDL SUPERIMPOSED DEAD LOAD

SEC SECONDS

SIM SIMILAR

SOG SLAB-ON-GRADE

STD STANDARD

SJI STEEL JOIST INSTITUTE

STL STEEL

STRUCT STRUCTURAL

T TOP OR TREAD

T/ TOP OF

TOF TOP OF FOOTING

TOS TOP OF STEEL

THK THICK

TMS THE MASONRY SOCIETY

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

V VERTICAL

VERT VERTICAL

VIF VERIFY IN FIELD

W/C WATER-CEMENTITIOUS MATERIAL RATIO

W WIDTH

WD WOOD

WP WORK POINT

WWR WELDED WIRE REINFORCEMENT

STRUCTURAL STEEL - DIVISION 5

1. STRUCTURAL STEEL FABRICATION, ERECTION AND CONNECTION DESIGN SHALL CONFORM TO AISC "SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS."

2. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING DESIGNATIONS, UNO:

WIDE FLANGE BEAMS ASTM A992

HSS RECTANGULAR ASTM A500 GR B

ANGLES ASTM A36

MISCELLANEOUS STEEL PLATES ASTM A36

ANCHOR RODS ASTM F1554, GRADE 36, UNO

THREADED RODS ASTM A36

3. BOLTS SHALL BE MINIMUM 3/4" DIAMETER AND SHALL CONFORM TO REQUIREMENTS OF ASTM A325, UNO.

4. WELDING ELECTRODES AND FLUXES SHALL CONFORM TO ONE OF THE SPECIFICATIONS OF THE AMERICAN WELDING SOCIETY LISTED IN

STRUCTURAL WELDING CODE - STEEL, AWS D1.1. ELECTRODES SHALL HAVE A MINIMUM TENSILE STRENGTH OF 70 KSI.

5. IF PARTS JOINED BY FILLET WELDS ARE SEPARATED BY MORE THAN 1/16 IN. THE LEG OF THE FILLET WELD SHALL BE INCREASED BY THE

AMOUNT OF THE ROOT OPENING. ROOT OPENING SHALL NOT EXCEED 3/16 IN.

6. UNLESS OTHERWISE INDICATED ON THE DRAWINGS FILLET WELDS SHALL HAVE A MINIMUM SIZE OF 1/4".

7. GROUT UNDER STEEL PLATES SHALL HAVE A MINIMUM 28 DAY DESIGN COMPRESSIVE STRENGTH OF 7000 PSI.

8. BOLTED CONNECTIONS SHALL BE MADE WITH HIGH STRENGTH BOLTS, 3/4" MIN DIAMETER, UNLESS OTHERWISE NOTED, PER ASTM A325X.

HIGH STRENGTH BOLTS SHALL BE TIGHTENED BY THE TURN-OF-NUT METHOD.

9. BOLTED CONNECTIONS SHALL HAVE A MINIMUM OF 2 BOLTS.

10. FABRICATOR AND ERECTOR SHALL BE CURRENTLY CERTIFIED IN THE AISC QUALITY CERTIFICATION PROGRAM, CATEGORY STD.

11. FABRICATOR MAY SUBMIT ALTERNATIVE CONNECTION DETAIL PER AISC FOR THE FACTORED SHEAR REACTION SHOWN IN SCHEDULE.

IF ALTERNATIVE CONNECTION IS SUBMITTED DURING THE SHOP DRAWING PHASE, ENGINEER OF RECORD MUST VERIFY AND APPROVE

CHANGE.

12. CONNECTIONS TO COLUMNS SHALL HAVE A MAXIMUM ECCENTRICITY OF 3" WITH RESPECT TO THE FLANGE OR WEB AS APPLICABLE.

13. PROVIDE ONE SHOP COAT OF RUST-INHIBITING GRAY PRIMER, 2 MILS DRY THICKNESS ON ALL STRUCTURAL STEEL MEMBERS AND

DECKING EXCEPT AT FIELD WELD LOCATIONS.

14. ALL STRUCTURAL STEEL SHALL BE FIELD PAINTED BLACK.

15. DO NOT FIELD CUT STRUCTURAL STEEL MEMBERS WITHOUT THE WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.

16. DO NOT SPLICE STEEL MEMBERS EXCEPT WHERE SPECIFICALLY DETAILED ON THE DRAWINGS WITHOUT THE WRITTEN APPROVAL OF

THE STRUCTURAL ENGINEER OF RECORD.

17. THE CONTRACTOR SHALL PROVIDE ADEQUATE TEMPORARY SUPPORTS UNTIL ALL PERMANENT BRACING AND FLOOR SLABS ARE IN PLACE.

18. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED MINOR STEEL PIECES OF PLATES, ANGLES, STRUCTURAL STEEL SHAPES AND CONNECTIONS

NECESSARY TO MAKE THE WORK COMPLETE WHETHER OR NOT SHOWN ON DRAWINGS, WITHOUT ADDITIONAL

COMPENSATION.

19. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND SHALL NOT PROCEED WITH THE WORK UNTIL PLANS AND DETAILS HAVE BEEN

FULLY APPROVED.

20. THE CONTRACTOR SHALL NOT REPRODUCE THE CONSTRUCTION DOCUMENTS FOR USE AS SHOP DRAWINGS.

21. THE CONTRACTOR AND SUBCONTRACTORS MUST SUBMIT IN WRITING ANY REQUEST FOR MODIFICATIONS TO THE PLANS AND

SPECIFICATIONS. SHOP DRAWINGS THAT ARE SUBMITTED TO THE ENGINEER FOR THEIR REVIEW DO NOT CONSTITUTE, "IN WRITING", UNLESS IT IS BROUGHT TO THE ATTENTION OF THE ENGINEER THAT SPECIFIC CHANGES ARE BEING SUGGESTED. CHANGES TO THE PLANS

AND SPECIFICATIONS BY MEANS OF SHOP DRAWINGS SHALL BE THE RESPONSIBILITY OF THE PERSON INITIATING THE CHANGES.

22. ALL STEEL SHALL BE MEET THE ARCHITECTURALLY EXPOSED STRUCTURAL STEEL REQUIREMENTS PER SPECIFICATION 051213

METAL DECK - DIVISION 5

1. METAL ROOF DECK SHALL BE SUPPLIED PRIME-PAINTED, SIZED PER THE CONFIGURATIONS SPECIFIED ON THE DRAWINGS, MANUFACTURED BY VULCRAFT, OR AN APPROVED EQUIVALENT, AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATION AND STEEL DECK INSTITUTE STANDARDS.

2. STEEL DECK SECTIONS SHALL BE LAP CONNECTED AND ATTACHED TO THE SUPPORTING STRUCTURE AS SPECIFIED ON THE DESIGN DRAWINGS

3. PROVIDE, AS REQUIRED, ALL RIDGE AND VALLEY PLATES, COLUMN CLOSURES, CANT STRIPS, SUMP PLATES AT PIPING PENETRATIONS AND

RECESSED SUMP PANS AT ROOF DRAINS. PROVIDE SUPPLEMENTAL FRAMING AT OPENINGS AS REQUIRED FOR SUPPORT OF THE METAL

DECK. ALL OPENINGS SHALL BE COORDINATED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION DRAWINGS

4. NO LOADS EXCEEDING 50 POUNDS SHALL BE PERMITTED TO BE HUNG FROM ANY STEEL DECKING. DUCTWORK, PIPING, ETC. SHALL BE HUNG

DIRECTLY FROM STRUCTURAL STEEL, SUPPLEMENTARY MEMBERS OR ANCHORS EMBEDDED IN THE CONCRETE. SUPPLEMENTARY MEMBERS, IF USED, SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

5. ALL SURFACES OF DECKING THAT WILL BE EXPOSED IN THE FINISHED STRUCTURE SHALL BE FIELD-PAINTED BLACK.

# Revisions Date

1 Addendum for Solilcitation 11/22/2019

Sheets
S-001 - GENERAL NOTES
S-100 - LEVEL4 FRAMING PLAN
S-101 - LEVEL 4 POST-TENSIONING PLAN
S-300 - CONCRETE DETAILS
S-301 - CONCRETE REPAIR DETAILS
S-302 - POST-TENSIONED DETAILS
S-305 - CONCRETE BEAM SCHEDULE & DETAILS